SCHEDULE OF LOADS & DESIGN COMPUTATION

PANEL BOARD (PB 1) MAIN PANELBOARD


MAIN CB: 100 AT/AF CB, SINGLE PHASE, 60 HZ, CB
BRANCHES
BRANCHES: 3 - 20 AT/AF CB, SINGLE PHASE, 60 HZ, CB
voltage POWER CURRENT 5 - 30 AT/AF CB, SINGLE PHASE, 60 HZ, CB
CIRCUIT NO. DESCRIPTION NO. OF NO. OF WIRE SIZE CONDUIT SIZES
VOLTS VA AMPERE 8 - SPARE
OUTLETS SWITCHES TRIP POLE FRAME TYPE UPVC DIA

C1 LIGHTING OUTLET 11 3 230 1100 4.78 20 2 20 MCCB 3.5 MM2 THHN 20 MM


C2 LIGHTING OUTLET 12 6 230 1200 5.22 20 2 20 MCCB 3.5 MM2 THHN 20 MM WIRE SIZE:
2 - # 30 MM SQ THHN WIRE
M
C3 LIGHTING OUTLET 8 1 230 800 3.48 20 2 20 MCCB 3.5 MM2 THHN 20 MM
C4 CONVENIENCE OUTLET 8 230 1600 6.96 30 2 30 MCCB 3.5 MM2 THHN 20 MM
C5 ACU 1 230 200 0.87 30 2 30 MCCB 3.5 MM2 THHN 20 MM 100AT
C6 REFRIGERATOR OUTLET 1 230 200 0.87 30 2 30 MCCB 3.5 MM2 THHN 20 MM L.O. C1 20 20 C2 L.O.

C7 RANGE OUTLET 1 230 200 0.87 30 2 30 MCCB 3.5 MM2 THHN 20 MM L.O. C3 20 30 C4 C.O.

C8 ACU 1 230 200 0.87 30 2 30 MCCB 3.5 MM2 THHN 20 MM 30 30


ACU C5 C6 REF.

C9 SPARE 1
RANGE C7 30 30 C8 ACU
C10 SPARE 1
SPARE SPARE
1 30 30
C11 SPARE
PANEL SPARE
30 30 SPARE
C12 1
SPARE BOARD-1
C13 SPARE 1 SPARE 30 30 SPARE

C14 1
SCALE
SPARE NDTS SPARE C15 30 30 C14 SPARE

C15 SPARE 1 GROUND

C16 SPARE 1

TOTAL 5,500 23.92

RESIDENTIAL TYPE OF OCCUPANCY = 24 VA VPER SQ.M GENERAL SPECIFICATION


OR 100 VA PER LIGHTING OUTLET 1. ALL ELECTRICAL WORKS HEREIN SHALL COMPLY WITH THE LATEST EDITION OF THE
200 VA PER CONVENIENCE OUTLET PHILIPPINES ELECTRICAL CODE WITH THE RULES AND REGULATIONS OF THE
UTILITY POWER COMPLY CONCERNED.
2. SERVICE POWER SUPPLY SHALL BE 230 VOLTS SINGLE PHASE TWO-WIRE SYSTEM,
TOTAL LOAD ( INCLUDING FUTURE ) = 5,500 VA
60Hz.
It = 5,500/230 = 23.92 AMPERES
3. WIRING METHOD SHALL BE DONE IN RSC & uPVC CONDUIT.
4. SMALLEST BRANCHES CIRCUIT WIRE SHALL BE 2.0mm² THW & 3.5mm² THW
FOR MAIN CIRCUIT BREAKER PROTECTION COPPER WIRE FOR LIGHTING & POWER SYSTEM RESPECTIVELY & RACEWAY 15mmØ
I t = 1.25 X 23.92 = 29.90 AMPERES TRADE SIZE CONDUIT WIRE SHALL BE INSULATED FOR 600 VOLTS.
USE: 100 AT/AF SINGLE PHASE, 60 HZ CIRCUIT BREAKER 5. ALL LIGHT CONTROL SWITCHES SHALL BE RATED 15 AMP 220 VOLTS AC ONLY.
6. THE CONTRACTOR SHALL BE VERIFY & ORIENT THE ACTUAL LOCATION OF THE
BRANCHES: SERVICE ENTRANCE FOR THE CONNECTION TO THE POWER SUPPLY.
3 - 20 AT/AF, SINGLE PHASE, 60 HZ, CB 7. ALL MATERIALS & EQUIPMENTS TO BE USED SHALL BE OF A TYPE APPROVED FOR
5 - 30 AT/AF, SINGLE PHASE, 60 HZ, CB THE PURPOSE & LOCATION.
8 - SPARE 8. WHERE EVER NECESSARY PROVIDE JUNCTION BOX OR PULL BOX IN IN
FOR MAIN SERVICE ENTRANCE WIRE CONSPICIOUS LOCATION.
I t = 5,500/230 = 23.92 9. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A
AMPERES DULY REGISTERED ELECTRICAL ENGINEER.
USE 2 - # 30 MM SQ THHN WIRE