Вы находитесь на странице: 1из 179

TOLCO™ Pipe Hangers & Support Systems

Fittings
Wrot and cast copper pressure fittings • Wrot and cast copper drainage
fittings • Wrot copper PEXlink® fittings • Cast copper alloy flared fittings • Cast
copper alloy flanges • ABS and PVC DWV fittings • Schedule 40 PVC pres-
sure fittings • CPVC CTS fittings • CPVC CTS-to-metal transition fittings
• Schedule 80 PVC and CPVC systems • CPVC metric piping systems.

Valves & Actuation


Pressure-rated bronze, iron and alloy-iron gate, globe and check valves • Pressure-
rated bronze ball valves • Boiler specialty valves • Commercial and industrial butter-
fly valves • Circuit balancing valves • Carbon and stainless steel ball valves • ANSI
flanged steel ball valves • Pneumatic and electric actuators and controls • Grooved
ball and butterfly valves • UL/FM fire protection valves • Low-pressure gate, globe,
check and ball valves • Bronze specialty valves • Frostproof sillcocks • MSS speci-
fication valves • PVC ball valves • CPVC CTS ball valves.

Chemtrol®
Supporting
Ideas
Thermoplastic pipe, valves and fittings in PVC, Corzan® CPVC, polypropylene
and PVDF Kynar® • Chem-Aire® thermoplastic compressed air piping systems
• Pneumatic and electric actuation systems.
the Flow.
that flow. ™

eNIBCO®

Supporting A suite of services designed to make customers more efficient • More cost-effective
• More informed • EDI—Electronic Data Interchange • VMI—Vendor Managed
Inventory • NIBCO.com • NIBCOpartner.com • eNIBCO will continuously develop
the Flow. ™ new products to deliver the competitive advantage.

Every solution TOLCO™


Office / Manufacturing
Begins with 1375 Sampson Avenue
Corona, California 92879

TOLCO . USA
Phone: 909.737.5599
Fax: 909.737.0330
We're committed to Pipe Hangers
Customer Service:
supporting all of your flow
control needs. We can
Phone: 800.786. 5266 Supports
www.tolco.com
Pipe Hangers • Pipe Supports
TOL-Strut Channel • Seismic Bracing

provide creative solutions for Seismic Bracing
your most challenging brac- NIBCO INC.
World Headquarters
ing and support applications.
1516 Middlebury Street
Solutions that make your Elkhart, IN 46515-1167
USA
installations easier, safer
and more cost-effective. Customer Service:
Phone: 800.234.0227
Fax: 800.234.0557
For solutions that will support
your flow-control applications, Technical Service:
call on us. We're TOLCO, a Phone: 888.446.4226
product line committed to
www.nibco.com
quality, service and innovation—
Supporting the Flow.

C-TOLH-0403

w
wwww
w..to
tolclcoo..ccoomm
a brand of
®
Revision 5/24/2001

Engineers Specification Section


Section 15140 - Pipe Hangers and Supports
Part I — General
1.01 SECTION INCLUDES
A. The work covered under this section consists of the furnishing of all necessary labor,
supervision, materials, equipment and services to complete the pipe hangers
and
supports as described in this specification.
1.02 REFERENCES
A. MSS-SP58 — Manufacturers Standardization Society: Pipe Hangers and Supports —
Materials, Design and Manufacture.
B. MSS-SP69 — Manufacturers Standardization Society: Pipe Hangers and Supports —
Selection and Application.
C. NFPA 13 — Standard for the Installation of Sprinkler Systems.
D. ASTM A123 — Specification for Zinc Hot-Galvanized Coatings on Products Fabricated
from Roller, Pressed and Forged Steel Shapes, Plates, Bars and Strip.
E. ASTM A653 G90 — Specification for Steel Sheet, Zinc-Coated by the Hot-Dip Process.
F. ASTM B633 — Specification for Electrodeposited Coatings of Zinc on Iron and Steel
1.03 QUALITY ASSURANCE
A. Steel pipe hangers and supports shall have the manufacturers name, part number and
applicable size stamped in the part itself for identification.
B. Hangers and supports shall be designed and manufactured in conformance with
MSS-SP58.
C. Supports for sprinkler piping shall be in conformance with NFPA 13.
1.04 SUBMITTALS
A. Submit product data on all hanger and support devices. Product data to include, but not
limited to materials, finishes, approvals, load ratings and dimensional information.
Part II — Products
2.01 ACCEPTABLE MANUFACTURERS
A. Manufacturer: Subject to compliance with these specifications, pipe hanger and support
systems shall be as manufactured by TOLCO™.
2.02 PIPE HANGERS AND SUPPORTS
A. Hangers
1. Uninsulated pipes 2" and smaller:
a. Adjustable steel swivel ring (band type) hanger, TOLCO Fig. 2, Fig. 200
b. Adjustable steel swivel J-Hanger, TOLCO Fig. 3
c. Adjustable steel clevis hanger, TOLCO Fig. 1, Fig. 1LD
2. Uninsulated pipes 21/2" and larger:
a. Adjustable steel clevis hanger, TOLCO Fig. 1
b. Pipe roll with sockets, TOLCO Fig. 322
c. Adjustable steel yoke pipe roll, TOLCO Fig. 324

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 51.737.0330
Customer Service • 800.786.5266 1
www.tolco.com
www.tolco.com www.tolco.com
Revision 5/24/2001 Revision 6/1/2002

Catalog Forward Warning Cast Iron Pipe Data


This catalog has been created with an acute aware- Pipe hanger products included in this catalog are
ness of the field problems of the piping contractor. intended for installation and service only as described American Water Works Assn. (AWWA)
We have sought and received input from engineers, herein. Mechanical Joint Pipe Class 150. Approximately same weight for Bell & Spigot. Flanged cast iron pipe add weight of flanges
installers, field inspectors and others closely involved We are aware that these products have been used
with the installation of piping systems. This is where (often without incident) for purposes and in ways other O.D. Wall Wt. Per Wt. of Water
needs are discovered, and where products and serv- than those for which they were designed and manu- Pipe Size C.I. Pipe Thickness Foot per Ft./Lbs.
ices are genuinely tested. factured. Examples of which are: use of products as 3 3.96 .32 12.2 3.73
TOLCO™ is proud to present a complete and versa- erection tools; use of beam clamps on a beam not 4 4.80 .35 16.4 5.72
tile line of pipe hangers and related products. The specified for them; use of concrete inserts as an 6 6.90 .38 25.7 12.80
TOLCO line has been methodically developed to anchor for pulling pipe to proper elevation; suspension 8 9.05 .41 36.7 23.10
10 11.10 .44 48.7 35.50
effectively address support problems in the commer- of one clevis hanger under another resulting in cumu- 12 13.20 .48 62.9 51.00
cial and industrial piping fields. lative load greater than specified capability. In such 14 15.30 .51 78.8 69.30
A thorough knowledge of our customers’ needs and cases of misapplication or improper use, we cannot 16 17.40 .54 95.0 90.30
problems was no less important than the development be held responsible for injuries or property damage. 18 19.50 .58 114.7 114.00
of our manufacturing skills in the emergency of TOLCO pipe hanger products are carefully designed 20 21.60 .62 135.9 141.50
24 25.80 .73 190.4 201.00
TOLCO as a leader in the pipe hanger industry. Our and manufactured to industry standards. Care should 30 32.00 .85 277.3 312.00
people are equipped to respond quickly to your prod- be exercised by installers and end users to install, use 36 38.30 .94 368.9 449.00
uct and service needs on both standard items and and maintain these products properly to avoid any 42 44.50 1.05 479.1 612.00
specialized metal fabrication. possible on-the-job accidents. 48 50.80 1.14 595.2 803.00
Custom Fabrication Designs
We have expanded our manufacturing capacity in Product design and specifications are subject to Standard No Hub “Soil Pipe” Extra Heavy “Soil Pipe”
response to the growing demand for customized change without notice.
metal fabrication and special hangers. When some O.D. I.D. O.D. I.D.
Finishes Pipe Size Pipe Size
detail of construction or piping arrangement makes it 2 2.25 1.89 2 2.38 2.00
necessary to deviate from standard types of hangers, Most hangers are available in: stainless steel, elec-
3 3.25 2.89 3 3.50 3.00
TOLCO is equipped to furnish hangers and supports tro-galvanized or hot-dipped galvanized. Other 4 4.25 3.89 4 4.50 4.00
of any required type. These products combine proven special finishes are available upon request. Items 5 5.25 4.87 5 5.50 5.00
designs and standards with new innovations that ordered hot-dip galvanized may be supplied with elec- 6 6.25 5.85 6 6.50 6.00
enhance their utility. tro-galvanized threaded components unless otherwise 8 8.38 7.94 8 8.62 8.00
specified. If you require a finish not listed in the 10 10.50 9.98 10 10.75 10.00
Approvals and Specifications product data of a specific hanger, please consult
TOLCO, as a member of the American Pipe Fittings our factory.
Association, is cooperating with engineers and archi-
Index
Load Carrying Capacities of Threaded Steel Rod
tects in the preparation of specifications covering
hanger requirements and the interpretation of applica- Figure numbers in this catalog are in numerical order.
Rod Root Area Max. Safe Load Max. Rec. Load Weight per
ble piping safety codes. Terms and Conditions of Sale Diameter In. Thread Sq. In. in Lbs. @650°F* in Lbs. @ 750°F* Ft./Lbs.
All TOLCO products are carefully manufactured to 3/8 .068 610 540 .376
For conditions and terms of sale, please consult our 1/2 .126 1130 1010 .668
meed the highest standards in the industry. All prod- current price guide. 5/8 .202 1810 1610 1.040
ucts, as a minimum conform to Manufacturers
3/4 .302 2710 2420 1.500
Standardization Society MSS-SP-58, and to the allow- 7/8 .419 3770 3360 2.400
able stresses specified in the ANSI B31.1 code for 1 .552 4960 4420 2.670
pressure piping. 11/8 .693 6230 5560 3.380
Many TOLCO Products are also listed, approved or 11/4 .889 8000 7140 4.170
11/2 1.293 11630 10370 6.010
conform to:
13/4 1.744 15700 14000 8.180
Underwriter’s Laboratories UL-203 2 2.300 20700 18460 10.680
Factory Mutual Engineering 21/2 3.023 27200 24260 13.520
National Fire Protection Association NFPA-13, 21/2 3.719 33500 29800 16.960
NFPA-13R, NFPA-13D and NFPA-24 * Maximum recommended load based on minimum safety factor of 5.
Federal Specification WW-H-171EE

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 95.737.0330 Main Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 909.737.5599 • Fax: 909.737.0330
Customer Service • 800.786.5266 Customer Service • 800.786.5266 181
www.tolco.com www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Engineers Specification Section


3. Insulated pipe - Hot or steam piping:
a. 2" and smaller pipes: use adjustable steel clevis with galvanized sheet metal
shield, TOLCO™ Fig. 1 with Fig. 220.
b. 21/2" and larger pipes:
i. Adjustable steel yoke pipe roll with pipe covering protection saddle, TOLCO
Fig. 324 with Fig. 260 thru 265.
ii. Pipe roll with sockets with pipe covering protection saddle, TOLCO Fig. 322
with Fig. 260 thru 265.
4. Insulated pipe - Cold or chilled water piping:
a. 5" and smaller pipes: use adjustable steel clevis with galvanized sheet metal
shield, TOLCO Fig. 1 with Fig. 220.
b. 6" and larger pipes:
i. Adjustable steel yoke pipe roll with pipe covering protection saddle, TOLCO
Fig. 322 with Fig. 260 thru 265.
ii. Pipe roll with sockets with pipe covering protection saddle, TOLCO Fig. 322
with Fig. 260 thru 265.
B. Pipe Clamps
1. When flexibility in the hanger assembly is required due to horizontal movement, use
pipe clamp with weldless eye nuts, TOLCO Fig. 4 or Fig. 4H with Fig. 330. For
insulated lines use bolted pipe clamps, TOLCO Fig. 5 with Fig. 330.
C. Multiple or Trapeze Hangers.
1. Trapeze hangers shall be constructed from 12 gauge roll formed steel channel,
15/8" x 15/8" minimum, TOL-Strut™ A12 strut or stronger as required.
2. Mount pipes to strut channel trapeze with two piece pipe straps sized for outside
diameter of pipe, TOL-Strut Fig. EMTC, RIGID, O.D. or Universal pipe clamps as
required.
3. For pipes subject to axial movement: Strut mounted roller support, TOL-Strut
Fig. ROL 12, 13, 14, 15 or 16 as required. Use pipe protection shield or saddles on
insulated lines, TOLCO Fig. 220 or Fig. 260-265.
D. Wall Supports
1. Pipe 4" and smaller:
a. Carbon steel hook, TOLCO Fig. 41
b. Carbon steel J-hanger, TOLCO Fig. 3
2. Pipes larger than 4":
a. Welded strut bracket and pipe straps, TOLCO Fig. 31, TOL-Strut BR series
as required.
b. Welded steel brackets, TOLCO Fig. 30 as required. With roller chair or
adjustable steel yoke pipe roll, TOLCO Fig. 325 or Fig. 324. Use pipe
protection shield or saddles on insulated lines. With U-bolt, TOLCO
Fig. 110 and square washer, TOLCO Fig. 118.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
2 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Engineers Specification Section


E. Floor Supports
1. Hot piping under 6" and all cold piping:
a. Carbon steel adjustable pipe saddle and nipple attached to steel base stand sized
for pipe elevation. TOLCO™ Fig. 315 and Fig. 316T or Fig. 317, 317A, 318,
318A as required. Pipe saddle shall be screwed or welded to appropriate
base stand.
2. Hot piping 6" and larger:
a. (Adjustable) Roller stand with base plate, TOLCO Fig. 317 or 328.
b. Adjustable roller support and steel support sized for elevation, TOLCO Fig. 316.
F. Vertical Supports
1. Steel riser clamp sized to fit outside diameter pipe, TOLCO Fig. 6.
G. Copper Tubing Supports
1. Hangers shall be sized to fit copper tubing outside diameters.
a. Adjustable steel swivel band hanger, TOLCO Fig. 202
b. Malleable iron ring hanger, TOLCO Fig. 301CT
c. Adjustable steel clevis hanger, TOLCO Fig. 81
H. Plastic Pipe Supports
1. Adjustable band hanger, PVC coated with flared edges, TOLCO Fig. 203. V-Bottom
clevis hanger with a “V” trough support, TOLCO Fig. 1V and Fig. 1VT to provide
continuous support for flexible plastic pipe.
I Supplementary Structural Supports
1. Design and fabricate supports using structural quality steel bolted framing materials
as manufactured by TOLCO. Channels shall be roll formed, 12 gauge steel,
15/8" x 15/8" or greater as required by loading conditions. Submit designs for pipe
tunnels, pipe galleries, etc., to engineer for approval. Use clamps and fittings
designed for use with the strut system.
2.04 UPPER ATTACHMENTS
A. Beam Clamps
1. Beam clamps shall be used where piping is to be suspended from building steel.
Clamp type shall be selected on the basis of load to be supported, and load
configuration.
2. C-Clamps shall have locknuts and cup point set screws, TOLCO Fig. 64. Reversible
top or bottom flange C-clamps shall be used when attaching a hanger rod to the top
of flange of structural shapes, TOLCO Fig. 65 or Fig. 66. Retaining straps shall be
used to maintain the clamps position on the beam where required.
3. Center loaded beam clamps shall be used where specified. Steel clamps shall be
TOLCO Fig. 62. Malleable iron or forged steel beam clamps with cross bolt shall be
TOLCO Fig. 329.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 3
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Engineers Specification Section


B. Concrete Inserts
1. Cast in place spot concrete inserts shall be used where applicable, either steel or
malleable iron body, TOLCO™ Fig. 310 or Fig. 309. Spot inserts shall allow for lateral
adjustment and have means for attachment to forms. Select inserts to suit threaded
hanger rod sizes, TOLCO Fig. 310N or Fig. 309N.
2. Continuous concrete inserts shall be used where applicable. Channels shall be
12 gauge steel, complete with Styrofoam inserts and end caps with nail holes for
attachment to forms. The continuous concrete insert shall have a load rating of
2,000 lbs./ft. in concrete, TOL-Strut™ Fig. B-12 CONCT.
2.05 VIBRATION ISOLATION AND SUPPORTS
A. For refrigeration, air conditioning, hydraulic, pneumatic and other vibrating system
applications, use a clamp that has a vibration dampening insert and a nylon inserted
locknut. For copper and steel tubing use TOL-Strut Cushion Clamp.
B. For larger tubing or piping subjected to vibration, use neoprene or spring hangers
as required.
C. For base mounted equipment use vibration pads, molded neoprene mounts or spring
as required.
D. Vibration isolation products as manufactured by TOLCO, Fig. 506
2.06 ACCESSORIES
A. Hanger rods shall be threaded both ends, or continuous threaded rods of circular cross
section, TOLCO Fig. 100 or Fig. 103. Use adjusting locknuts at upper attachments and
hangers. No wire, chain or perforated straps are allowed.
B. Shields must be 180° galvanized sheet metal, 12" minimum length, 18 gauge minimum
thickness, designed to match outside diameter of the insulated pipe, TOLCO Fig. 220.
C. Pipe protection saddles shall be formed from carbon steel, 1/8" minimum thickness, sized
for insulation thickness. Saddles for pipe sizes greater than 12" shall have a center
support rib, TOLCO Fig. 260 thru 265.
2.07 FINISHES
INDOOR FINISHES
A. Hangers and clamps for support of bare copper piping shall be coated with copper
colored epoxy paint. Additional PVC coating of the epoxy painted hanger shall be used
where necessary.
B. Hangers for other than bare copper pipe shall be zinc plated in accordance with
ASTM B633-SC3.
C. Strut channels shall be pre-galvanized in accordance with ASTM A653-G90
OUTDOOR AND CORROSIVE AREA FINISHES
D. Hangers and strut located outdoors shall be hot dip galvanized after fabrication in accor-
dance with ASTM A123. All hanger hardware shall be hot dip galvanized or stainless
steel. Zinc plated hardware is not acceptable for outdoor or corrosive use.
E. Hangers and strut located in corrosive areas shall be type 304 (316) stainless steel with
stainless steel hardware.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
4 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Engineers Specification Section


Part III — Exclusion
3.01 PIPE HANGERS AND SUPPORTS
A. Pipe shall be adequately supported by pipe hanger and supports specified in
PART II — PRODUCTS. Hangers for insulated pipes shall be sized to accommodate
insulation thickness
B. Horizontal steel piping shall be supported in accordance with MSS SP-69 Tables 3 and 4,
excerpts of which follow below:
NOMINAL PIPE SIZE ROD DIAMETER MAXIMUM SPACING
1/2 - 11/4 3/8 7’0"
11/2 3/8 9”0"
2 3/8 10’0"
21/2 1/2 11’0"
3 1/2 12’0"
31/2 1/2 13’0"
4 5/8 14’0"
5 5/8 16’0"
6 3/4 17’0"
8 3/4 19’0"
10 7/8 22’0"
12 7/8 23’0"
14 1 25’0"
16 1 27’0"

C. Horizontal copper tubing shall be supported in accordance with MSS SP-69


Tables 3 and 4, excerpts of which follow below:
NOMINAL PIPE SIZE ROD DIAMETER MAXIMUM SPACING
1/2 - 3/4 3/8 5’0"
1 3/8 6’0"
11/4 3/8 7’0"
11/2 3/8 8’0"
2 3/8 8’0"
21/2 1/2 9’0"
3 1/2 10’0"
31/2 1/2 11’0"
4 1/2 12’0"
5 1/2 13’0"
6 5/8 14’0"
8 3/4 16’0"
D. Provide means of preventing dissimilar metal contact such as plastic hangers, felt lined
hangers, copper colored epoxy paint or non-adhesive isolation tape. Galvanized felt
isolators sized for copper tubing may also be used, TOLCO™ Fig. 83.
E. Support horizontal cast iron adjacent to each hub, with 5 feet maximum spacing
between hangers.
F. Install hangers to provide a minimum 1/2" space between finished covering and
adjacent work.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 5
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Engineers Specification Section


G. Place a hanger within 12" of each horizontal elbow.
H. Support vertical piping independently of connected horizontal piping. Support vertical
pipes at every (other) floor. Wherever possible, locate riser clamps directly below pipe
couplings or shear lugs.
I. Where several pipes can be installed in parallel and at the same elevation, provide
trapeze hangers as specified in Section 2.02 C. Trapeze hangers shall be spaced
according to the smallest pipe size, or install intermediate supports according to schedule
in Section 3.01 B.
J. Do not support piping from other pipes, ductwork or other equipment which is not
building structure.
3.02 CONCRETE INSERTS
A. Provide inserts for placement in formwork before concrete is poured.
B. Provide inserts for suspending hangers from reinforced concrete slabs and sides of
reinforced concrete beams.
C. Where concrete slabs form finished ceilings, provide inserts to be flush with slab surface.
D. Provide hooked rod to concrete reinforcement section for inserts carrying pipe over 4".

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
6 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 6/11/2004

Fig. 1 - Standard Clevis Hanger


Size Range — Size 1/2" thru 36" pipe.
Material — Carbon Steel
Function — Recommended for the suspension of non-
insulated pipe or insulated pipe with Fig. 220 shield.
Note — When an oversized clevis is used, a pipe spacer
should be placed over the cross bolt to assure that the
lower U-strap will not move in on the bolt. When attaching
seismic bracing to clevis hangers, a Fig. 1 CBS (cross bolt
spacer) must be installed. See TOLCO™ Seismic
Restraint Approval Guidelines.
APPROVALS — Underwriters’ Laboratories Listed in the
USA (UL), Canada (cUL) 3/4" thru 8". FM Approved 3/4" -
11/2", 6" - 8".Conforms to Federal Specification WW-H-
171E, Type 1, and Manufacturers Standardization Society
SP-58, Type 1. Also available to accommodate rod sched-
ule per National Fire Protection Association (NFPA)
Pamphlet 13.
Maximum Temperature — 650°F
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel.

Dimensions • Weights
Pipe Rod Size A Max. Rec. Approx.
Size STD NFPA B C D Load Lbs. Wt./100
1/2 3/8 3/8 21/16 13/16 1 610 36
3/4 3/8 3/8 27/8 17/8 1 610 38
1 3/8 3/8 31/4 21/16 1 610 42
11/4 3/8 3/8 39/16 21/4 1 610 46
11/2 3/8 3/8 37/8 23/8 1 610 49
2 3/8 3/8 47/16 23/4 1 610 55
21/2 1/2 3/8 55/16 31/4 1 1130 124
3 1/2 3/8 515/16 31/2 11/4 1130 140
31/2 1/2 3/8 67/16 33/4 11/4 1130 152
4 5/8 3/8 73/8 41/4 11/2 1430 190
5 5/8 1/2 815/16 51/4 11/2 1430 235
6 3/4 1/2 913/16 51/2 11/2 1940 317
8 3/4 1/2 129/16 71/8 2 2000 428
10 7/8 5/8 161/4 95/8 31/4 3600 918
12 7/8 5/8 191/4 115/8 31/2 3800 1143
14 1 — 2013/16 125/16 313/16 4200 1543
16 1 — 2115/16 127/16 35/8 4600 1925
18 1 — 247/16 1315/16 37/8 4800 2243
20 11/4 — 265/16 147/16 4 4800 4161
*24 11/4 — 313/8 171/2 41/4 4800 4835
*30 11/4 — 387/8 217/8 5 6000 6940
*36 11/2 — 48 273/4 53/4 9500 18103
*Furnished with pipe spacer to support maximum load rating

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 15
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 1CBS - Clevis Bolt Spacer


Size Range — Size 1" thru 20" clevis hanger
Material — Carbon Steel
Function — Used as a spacer at a seismic brace location to
keep clevis hanger from collapsing during seismic event.
Installation Note — Fig. 1CBS fits easily over the cross bolt
and attaches by pinching tabs down.
Finish — Mil Galvanized
Note — Available in HDG finish or Stainless Steel materials.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
16 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 1C.I. - A.W.W.A. Clevis Hanger


Size Range — Size 4" thru 24" pipe.
Material — Carbon Steel
Function — For the suspension of flanged or bell and
spigot A.W.W.A. cast iron or ductile iron pipe. The O.D. of
the A.W.W.A. iron pipe is shown in the data table.
Approvals — Conforms to Federal Specification
WW-H-171E, Type 1 and Manufacturers Standardization
Society SP-69, Type 1.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel.
Order By — Figure number, pipe size and finish

Dimensions • Weights
Pipe Rod Max. Rec. Approx.
Size Size A Pipe O.D. B C D Load Lbs. Wt./100
4 5/8 4.80 8 43/4 15/8 1430 213
6 3/4 6.90 103/16 53/4 13/4 1940 430
8 3/4 9.05 125/8 7 13/4 2000 664
10 7/8 11.10 157/16 85/8 21/4 3600 940
*12 7/8 13.20 167/8 9 21/4 3800 1217
*14 1 15.30 207/8 113/4 21/2 4200 1533
*16 1 17.40 2311/16 131/2 33/8 4600 1925
*18 1 19.50 261/16 147/8 33/8 4800 2223
*20 11/4 21.60 291/16 163/8 33/4 4800 4182
*24 11/4 25.80 333/8 185/8 4 4800 5460
*Furnished with pipe spacer to support maximum load rating

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 17
www.tolco.com

www.tolco.com
a brand of
®
Revision 3/18/2002

Fig. 1A - Clevis Hanger for Insulated Lines


Size Range — Size 3/4" thru 12" pipe.
Material — Carbon Steel
Function — Recommended for the suspension of insulat-
ed pipe where the temperature does not require the use of
slides, guides or rollers for movement.
Approvals — Conforms to Federal Specification
WW-H-171E, Type 1 and Manufacturers Standardization
Society SP-69, Type1.
Maximum Temperature — 650°F
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel.
Order By — Figure number, pipe size and finish

Dimensions • Weights
Pipe Rod Size Max Insulation Max. Rec. Approx.
Size A B C D Thickness E Load Lbs. Wt./100
3/4 3/8 41/4 33/8 1/2 2 610 54
1 3/8 411/16 33/4 5/8 2 610 59
11/4 3/8 51/4 41/8 7/8 2 610 62
11/2 3/8 53/4 49/16 11/16 2 610 67
2 3/8 811/16 7 15/8 4 610 84
21/2 1/2 915/16 8 2 4 1130 185
3 1/2 105/16 81/16 13/4 4 1130 205
4 5/8 115/8 811/16 115/16 4 1430 252
5 5/8 125/8 91/4 13/4 4 1430 309
6 3/4 14 97/8 17/8 4 1940 400
8 7/8 163/4 11 2 4 2000 607
10 7i/8 193/16 121/4 21/8 4 3600 1032
12 7/8 219/16 135/8 27/16 4 3800 1315

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
18 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
®
Revision 5/24/2001
a brand of

Fig. 1F — Felt Lined Standard Clevis Hanger


Fig. 1PVC — PVC Coated Standard Clevis Hanger
Size Range — Size 1/2" thru 8" pipe.
Material — Carbon Steel
Insulation Material — 3/16" felt
Function — The Fig. 1F is designed for the suspension of
copper tube so as to prevent electrolysis between tube and
hanger. The Fig. 1PVC is designed for steel or other pipe
types of same O.D. Both Fig. 1F and Fig. 1PVC act to reduce
noise and vibration in pipe or tube system.
Approvals — Underwriters’ Laboratories Listed in the USA
(UL) and Canada (cUL).
Maximum Temperature — 650°F
Finish — Plain
Note —When Fig. 1F is used for steel or other pipe types,
consult factory for proper size hanger. Available in Electro-
Galvanized and HDG finish or Stainless Steel.
Order By — Figure number, nominal tube size and finish
Fig. 1F

Fig. 1PVC

Dimensions • Weights
Pipe Rod Size A Max. Rec. Approx.
Size STD NFPA B C D Load Lbs. Wt./100
1/2 3/8 3/8 27/8 1 1 610 36
3/4 3/8 3/8 31/16 111/16 1 610 38
1 3/8 3/8 33/8 17/8 1 610 43
11/4 3/8 3/8 33/4 21/16 1 610 47
11/2 3/8 3/8 41/16 23/16 1 610 50
2 3/8 3/8 41/2 29/16 1 610 56
21/2 1/2 3/8 51/2 31/16 1 1130 125
3 1/2 3/8 61/8 35/16 11/4 1130 141
31/2 1/2 3/8 63/4 39/16 11/4 1130 153
4 5/8 3/8 75/8 41/16 11/2 1430 191
5 5/8 1/2 87/8 51/16 11/2 1430 236
6 3/4 1/2 10 55/16 11/2 1940 318
8 3/4 1/2 123/4 615/16 2 2000 429

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 19
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 1LD — Light Duty Clevis Hanger


Fig. 1LDF — Felt Lined Light Duty Clevis Hanger
Fig. 1LD PVC — PVC Coated Light Duty Clevis Hanger
Size Range — Size1/2" thru 4" pipe.
Material — Carbon Steel
Function — Recommended for the suspension of light
pipe or conduit. Fig. 1LDF and Fig. 1LD PVC are designed
to reduce noise and vibration and/or prevent electrolysis.
Approvals — Conforms to Federal Specification
WW-H-171E, Type 12. Electro-Galvanized or HDG finishes
meet Manufacturers Standardization Society SP-69 and
SP-58 Type 1.
Maximum Temperature — 650°F
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel.
Order By — Figure number, pipe size and finish
Fig. 1LD

Fig. 1LDF Fig. 1LD PVC

Dimensions • Weights
Pipe Rod Max. Rec. Approx.
Size Size A B C D Load Lbs. Wt./100
1/2 3/8 213/16 1 1 150 27
3/4 3/8 3 111/16 1 250 29
1 3/8 35/16 17/8 1 250 33
11/4 3/8 311/16 21/16 1 250 35
11/2 3/8 4 23/16 1 250 37
2 3/8 47/16 29/16 1 250 45
21/2 1/2 53/8 31/16 11/4 350 97
3 1/2 6 35/16 11/4 350 106
31/2 1/2 65/8 39/16 11/4 350 111
4 1/2 71/2 41/16 11/2 400 152

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
20 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 1V - "V" Bottom Clevis Hanger


Size Range — Size 1/2" thru 4" pipe.
Material — Carbon Steel
Function — Recommended for the suspension of flexible
plastic pipe. Use with Fig. 1VT "V" support trough for
plastic pipe.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel.
Order By — Figure number, size number and finish

Dimensions • Weights
Pipe Rod Max. Rec. Approx.
Size No. Size Size A B C D Load Lbs. Wt./100
1 1/2 3/8 51/2 43/4 15/8 150 38
1 3/4 3/8 51/2 49/16 15/8 150 38
1 1 3/8 51/2 43/8 15/8 150 38
1 11/4 3/8 51/2 41/8 15/8 150 38
1 11/2 3/8 51/2 4 15/8 150 38
1 2 3/8 51/2 311/16 15/8 150 38
2 21/2 1/2 83/4 65/8 13/4 150 115
2 3 1/2 83/4 63/16 13/4 150 115
2 31/2 1/2 83/4 513/16 13/4 150 115
2 4 1/2 83/4 57/16 13/4 150 115

Fig. 1VT - "V" Support Trough


Size Range — Size 1/2" thru 4" pipe.
Material — Carbon Steel
Function — Designed for use with Fig. 1V as a support for
plastic or other flexible pipe systems.
Finish — Pre-Galvanized
Note — Available in Stainless Steel material.
Order By — Figure number and size number

Dimensions • Weights
For Rod Max. Rec. Approx.
Size No. Pipe Size Length Load Lbs. Wt./100
1 1/2 - 2 10 ft. 150 540
2 21/2 - 4 10 ft. 150 1080

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 21
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 2 — Adjustable Band Hanger


Fig. 2NFPA — Adjustable Band Hanger with Reduced Rod

Size Range — Size 21/2" thru 4" pipe.


Material — Carbon Steel, Pre-Galvanized
Function — Recommended for the suspension of non-insulated
pipe or insulated pipe with Fig. 220 shield.
Fig. 2NFPA accommodates the reduced rod schedule of the
National Fire Protection Association Pamphlet 13.
Approvals — Underwriters’ Laboratories Listed in the USA (UL)
and Canada (cUL). Factory Mutual Engineering approved.
Conforms to Federal Specification
WW-H-171E, Type 10 and Manufacturers Standardization Society
SP-69, Type 10.
Finish — Pre-Galvanized
Note — Available in Stainless Steel materials.
Order By — Figure number, pipe size and material

Dimensions • Weights
Pipe Max. Rec. Approx Wt./100
Size Rod Size A B C Load Lbs. Fig. 2 Fig. 2NFPA
21/2 1/2* 53/4 41/4 15/8 600 41 40
3 1/2* 6 41/8 11/4 600 45 43
31/2 1/2* 73/8 51/4 21/8 600 52 50
4 5/8* 73/8 5 15/8 1000 59 56
5 5/8** 9 61/8 21/4 1250 97 95
6 3/4** 93/8 61/2 17/8 1250 139 105

* 3/8" nut is used when NFPA rod sizing is requested.


** 1/2" nut is used when NFPA rod sizing is requested.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
22 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 2F - Adjustable Band Hanger with Felt Lining

Size Range — 1/2" thru 6" copper tubing


Material — Carbon Steel, Pre-Galvanized
Function — Recommended for the suspension of copper tube so
as to prevent electrolysis. The felt lining also acts to reduce noise in
copper or other pipe types.
Approvals — Underwriters’ Laboratories Listed in the USA (UL) and
Canada (cUL). Conforms to Federal
Specification WW-H-171E, Type 10 and Manufacturers
Standardization Society SP-69, Type 10.
Finish — Pre-Galvanized
Note — When used for steel or other pipe types, consult factory
for proper size. Available in Stainless Steel materials.
Order By — Figure number and copper tube size

Dimensions • Weights
Copper Tube Max. Rec. Approx.
Size Rod Size A B C Load Lbs. Wt./100
1/2 3/8 31/8 25/8 13/8 400 12
3/4 3/8 31/8 21/2 11/8 400 12
1 3/8 33/8 25/8 11/8 400 13
11/4 3/8 33/4 27/8 11/4 400 14
11/2 3/8 37/8 27/8 11/8 400 15
2 3/8 41/4 3 1 400 16
21/2* 1/2 53/4 41/8 13/4 600 41
3* 1/2 6 4 11/2 600 46
31/2* 1/2 73/8 51/4 13/8 600 53
4* 5/8 73/8 5 17/8 1000 60
5** 5/8 9 61/8 21/2 1250 98
6** 3/4 93/8 61/2 21/4 1250 140

* 3/8" nut is used when requested.


** 1/2" nut is used when requested.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 23
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 2WON - Adjustable Band Hanger w/o Swivel Nut


Fig. 2FWON - Felt Lined Band Hanger w/o Swivel Nut

Size Range — (Fig. 2WON) Size 1/2" thru 8" pipe.


(Fig. 2F WON) 1/2" thru 8" copper tube
Material — Pre-Galvanized Steel
Function — Recommended for the suspension of non-
insulated pipe or insulated pipe with Fig. 220 shield.
Approvals — Underwriters’ Laboratories Listed in the USA
(UL) and Canada (cUL). Conforms to Federal
Specification WW-H-171E, Type 7, and Manufacturers
Standardization Society SP-69, Type 7, 3/4" thru 6".
Finish — Pre-Galvanized
Note — Available in Stainless Steel materials.
Order By — Figure number and pipe size

Fig. 2WON

Fig. 2F WON

Dimensions • Weights
Pipe Rod Size Max. Rec. Approx.
Size A B C D Load Lbs. Wt./100
1/2 3/8 25/8 21/8 11/4 400 14
3/4 3/8 25/8 2 1 400 14
1 3/8 27/8 21/8 1 400 16
11/4 3/8 33/8 21/2 11/4 400 17
11/2 3/8 31/2 21/2 1 400 18
2 3/8 33/4 21/2 7/8 400 20
21/2 1/2* 5 31/2 11/2 600 27
3 1/2* 51/2 35/8 11/4 600 40
31/2 1/2* 63/4 45/8 2 600 48
4 5/8* 63/4 43/8 11/2 1000 53
5 5/8** 81/2 55/8 21/8 1250 91
6 3/4** 91/4 57/8 15/8 1250 99
8 3/4** 121/4 77/8 25/8 1250 120

* 3/8" nut is used when NFPA rod sizing is requested.


** 1/2" nut is used when NFPA rod sizing is requested.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
24 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 3 - J-Hanger for Pipe or Conduit


Fig. 3F - Felt Lined J-Hanger for Copper Tubing
Fig. 3PVC - PVC Coated J-Hanger for Pipe or Conduit
Size Range — 1/2" thru 12" pipe
Material — Carbon Steel
Function — Recommended for the suspension of non-insulated pipe,
or insulated pipe with Fig. 220 shield. Side hole allows for wall
mounting. Fig. 3F and Fig. 3PVC are designed to reduce noise and
vibration and/or prevent electrolysis between pipe and hanger.
Approvals — Conforms to Manufacturers Standardization Society
SP-69, Type 5.
Finish — Electro-Galvanized
Note — Available in HDG finish or Stainless Steel materials.
Order By — Figure number, pipe size and finish

Fig. 3

Fig. 3F Fig. 3PVC

Dimensions • Weights
Copper Tube Rod Size Max. Rec. Approx.
Size A B C D E F Load Lbs. Wt./100
1/2 3/8 25/8 13/4 7/16 11/2 115/16 400 18
3/4 3/8 27/8 17/8 7/16 111/16 21/8 400 21
1 3/8 215/16 115/16 7/16 113/16 25/16 400 22
11/4 3/8 31/4 2 7/16 21/16 25/8 400 25
11/2 3/8 39/16 23/16 7/16 27/16 27/8 400 27
2 3/8 311/16 21/8 7/16 29/16 31/16 400 29
21/2 1/2 47/16 27/16 9/16 33/16 35/8 500 64
3 1/2 413/16 29/16 9/16 31/2 41/16 500 72
31/2 1/2 51/8 25/8 9/16 33/4 43/8 500 84
4 5/8 61/8 33/16 9/16 45/8 53/16 550 138
5 5/8 63/4 31/4 9/16 51/16 53/4 550 162
6 3/4 73/4 39/16 9/16 513/16 65/8 600 249
8 7/8 93/16 315/16 9/16 615/16 8 760 291
10 7/8 103/4 37/8 9/16 75/8 91/8 760 315

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 25
www.tolco.com

www.tolco.com
a brand of
®
Revision 8/30/2002

Fig. 4 - Standard Pipe Clamp


Fig. 4F - Standard Pipe Clamp Felt Lined
Fig. 4PVC - Standard Pipe Clamp PVC Coated
Size Range — (Fig. 4) Size 1/2" thru 30" pipe.
Size Range — (Fig. 4F) Size 1/2" thru 21/2" copper tubing
Material — Carbon Steel
Function — Recommended for the suspension of non-insulated pipe or insulated pipe with
Fig. 220 shields. (Use Fig. 330 Weldless Eye Nut, Fig. 102 Eye Rod or Fig. 101 Welded Eye
Rod.) Also recommended for attachment of sway bracing up to 31/2" pipe size, for larger
pipe sizes use Fig. 4A. Fig. 4F and Fig. 4PVC are designed to reduce noise and vibration
and/or prevent electrolysis.
Approvals — Underwriters’ Laboratories Listed in the USA (UL), Canada (cUL) 3/4" - 8",
and approved by Factory Mutual Engineering, 3/4" - 8". Federal Specification WW-H-171E,
Type 4, 11/2" thru 24" and Manufacturers Standardization Society SP-69, Type 4. Included
in our Seismic Restraints Catalog approved by the State of California Office of Statewide
Health Planning and Development (OSHPD). For additional load, spac- Fig. 4
ing and placement information relating to OSHPD projects, please refer
to the TOLCO Seismic Restraint Systems Guidelines.
Note — When the Fig. 4 is used as a sway brace, to ensure perform-
ance, the UL Listing requires that it must be used with other
TOLCO™ brace products.
Maximum Temperature — 750°F
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or Stainless
Steel materials.
Order By — Figure number, pipe size and finish. Fig. 4F
Order Note — When ordering Fig. 4F allow for 3/16" felt on each half of clamp. Fig. 4PVC

Dimensions • Weights
Max. Design Load Lbs.
Pipe For Service Temp. Approx.
Size A B C D Bolt Size 650° 750°F Wt./100
1/2 37/16 1/4 11/8 11/8 5/16 500 445 29
3/4 39/16 1/4 11/4 11/4 5/16 500 445 31
1 39/16 1/4 11/4 15/16 5/16 500 445 35
11/4 43/16 1/2 13/8 111/16 5/16 500 445 40
11/2 49/16 5/16 15/8 17/8 5/16 800 715 42
2* 59/16 1/2 2 21/4 3/8 1040 930 93
21/2* 67/16 9/16 21/2 23/4 1/2 1040 930 126
3* 7 5/8 23/4 31/16 1/2 1040 930 141
31/2* 711/16 3/8 31/8 33/8 1/2 1040 930 154
4 81/2 5/8 35/16 311/16 5/8 1040 930 229
5 93/4 3/4 37/8 43/8 5/8 1040 930 261
6 115/8 3/4 47/8 51/8 3/4 1615 1440 537
8 135/16 1 55/8 6 3/4 1615 1440 625
10 161/2 1 71/4 71/4 7/8 2490 2220 1378
12 181/2 1 81/4 81/4 7/8 2490 2220 1574
14 20 11/8 9 9 7/8 2490 2220 2103
16 23 11/8 101/4 101/4 7/8 2490 2220 2314
18 257/8 11/4 111/2 111/2 1 3060 2730 3276
20 28 13/8 121/2 121/2 11/8 3060 2730 3863
24 33 /2
1
1 /8
5
15 /4
1
15 /4
1
11/4 3060 2730 5222
30 417/8 2 19 19 13/4 3500 3360 10511
*Meets UL 203A requirements for attachment of sway bracing. Horizontal design load for 1/2"-2" - 380#, 21/2" - 395#, 3" - 435#, 31/2" - 540#

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
26 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 4A - Pipe Clamp for Sway Bracing


Size Range — 4" thru 8" pipe. For sizes smaller than 4" use TOLCO™ Fig. 4.
Component of State of
Material — Carbon Steel California OSHPD Approved
Function — For bracing pipe against sway and seismic disturbance. Seismic Restraints System

Approvals — Underwriters’ Laboratories Listed in the USA (UL) and Canada


(cUL) 4" thru 8". Included in our Seismic Restraints Catalog approved by the
State of California Office of Statewide Health Planning and Development
(OSHPD). For additional load, spacing and placement information relating to
OSHPD projects, please refer to the TOLCO Seismic Restraint Systems
Guidelines.
Installation Instructions — Install Fig. 4A Pipe Clamp on pipe to be braced.
Attach Sway-Brace Fitting to 1/2" Clamp bolt (Sway-Brace Fitting to be on out-
side ears of clamp). Tighten securely. (min. torque requirement — 50 ft. lbs.)
Sway Brace Assemblies are intended to be installed in accordance with NFPA
13 and the Manufacturers Installation Instructions.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or Stainless Steel
materials.
Order By — Figure number, pipe size and finish

Fig. 4A - Longitudinal Brace Fig. 4A - Brace

Dimensions • Weights
Pipe Max. Horizontal Approx.
Sizes A B C D Bolt Size Design Load Wt./100
4 81/2 9/16 33/8 311/16 1/2 2015 221
5 93/4 9/16 37/8 43/8 1/2 2015 253
6 111/2 5/8 5 51/8 1/2 2015 513
8 131/4 3/4 611/16 61/8 1/2 2015 601

OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266 27
www.tolco.com

www.tolco.com
a brand of
®
Revision 8/30/2002

Component of State of
Fig. 4B - Pipe Clamp for Sway Bracing California OSHPD Approved
Seismic Restraints System
Size Range — 3/4" thru 8" pipe.
Material — Carbon Steel
Function — For bracing pipe against sway and seismic distur-
bance.
Approvals — Included in our Seismic Restraints Catalog approved
by the State of California Office of Statewide Health Planning and
Development (OSHPD).
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or Stainless
Steel materials.
Order By — Figure number, pipe size and finish.

Shown with two TOLCO™


Fig. 980’s and Schedule 40
brace pipe.

Shown with two TOLCO


Fig. 980’s and TOL-Strut™
Channel brace.
Fig. 4B - Hanger/Longitudinal Brace Fig. 4B - Hanger/Transverse Brace
Dimensions • Weights
Pipe Rod Size Max. Design Approx.
Sizes A B C D Bolt Size Load Lbs. Wt./100
3/4 3/8 1 27/8 25/8 5/16 330 56
1 3/8 1 31/4 215/16 5/16 330 60
11/4 3/8 1 39/16 31/4 5/16 330 74
11/2 3/8 1 313/16 37/16 5/16 330 79
2 3/8 11/2 51/8 45/8 5/16 440 156
21/2 1/2 13/4 55/8 53/8 3/8 440 176
3 1/2 17/8 63/4 61/8 3/8 660 198
31/2 1/2 2 71/4 63/4 3/8 660 219
4 5/8 2 85/8 71/4 1/2 800 288
5 5/8 2 97/8 85/16 5/8 980 390
6 3/4 21/8 1015/16 91/2 5/8 980 448
8 7/8 21/8 137/16 111/2 3/4 1200 691

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
28 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 4CI - A.W.W.A. Pipe Clamp


Size Range — 4" thru 24" pipe
Material — Carbon Steel
Function — Recommended for the suspension of flanged or bell and spigot A.W.W.A. cast
iron or ductile iron pipe. The O.D. of the A.W.W.A. iron pipe is shown in the data table.
Used with Fig. 330 Weldless Eye Nut, Fig. 102 Eye Rod or Fig. 101 Welded Eye Rod.
Approvals — Conforms to Federal Specification WW-H-171E, Type 4, and Manufacturers
Standardization Society SP-69, Type 4.
Maximum Temperature — 650°F
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or Stainless Steel materials.
Order By — Figure number, pipe size and finish
Dimensions • Weights
Pipe Bolt Max. Rec. Approx.
Sizes Pipe O.D. A B Size Load Lbs. Wt./100
4 4.80 11/8 41/16 5/8 1400 860
6 6.90 11/8 51/16 5/8 1400 1060
8 9.05 11/8 63/16 5/8 1400 1230
10 11.10 11/8 71/4 5/8 1400 1430
12 13.20 11/8 85/16 5/8 1400 1630
14 15.30 13/4 97/8 3/4 2000 2300
16 17.40 13/4 115/16 7/8 2500 3725
18 19.50 17/8 129/16 1 3000 4200
20 21.60 2 135/8 1 3100 4575
24 25.80 2 165/16 11/4 4500 6400

Fig. 4H - Heavy Duty Pipe Clamp


Size Range — 3" thru 42" pipe
Material — Carbon Steel
Function — Recommended for the suspension of heavy-duty pipe lines. (Use with
Fig. 330 Weldless Eye Nut, Fig. 102 Eye Rod or Fig. 101 Welded Eye Rod).
Approvals — Conforms to Federal Specification WW-H-171E, Type 4, and
Manufacturers Standardization Society SP-69, Type 4.
Maximum Temperature — 650°F
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or Stainless Steel materials.

Dimensions • Weights
Pipe Max. Rec.Load Lbs. — Temps. Approx.
Sizes A B C Bolt Size 650F 750°F Wt./100
3 1 3 41/8 3/4 3370 3005 498
4 1 311/16 415/16 7/8 3515 3135 634
5 1 45/16 59/16 7/8 3515 3135 714
6 11/8 53/16 611/16 1 4865 4340 1351
8 11/8 61/4 73/4 1 4865 4340 1573
10 11/4 77/8 91/2 11/4 6010 5360 2537
12 15/8 91/2 115/8 11/2 8675 7740 4300
14 15/8 101/8 121/4 11/2 9120 8135 5228
16 15/8 113/16 135/16 11/2 9120 8135 5657
18 15/8 123/16 145/16 11/2 9150 8160 6914
20 15/8 135/16 157/16 11/2 9150 8160 7468
24 13/4 153/8 173/4 11/2 9200 `8205 12629
* Consult factory for sizes larger than 24"
Based on the allowable stresses shown in the ANSI code for pressure piping.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 29
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 4L
Longitudinal “In-Line” Sway Brace Attachment
Size Range — 2 ½" through 8" IPS.
Material — Carbon Steel
Function — For bracing pipe against sway and seismic disturbance.
Approvals — Underwriter's Laboratories Listed in the USA (UL) and
Canada (cUL) 2 ½" through 8".
Installation Instructions — Install Fig. 4L on the pipe to be braced.
Tighten bolts on ears of clamp securely. Insert brace pipe in swivel
jaw and tighten set screw until head breaks off. Sway brace assemblies
are intended to be installed in accordance with NFPA 13 and the
manufacturer's installation instructions.
Finish — Plain
Note — Available in electro-galvanized and HDG finish.
Order By — Figure number, pipe size and finish.
Important Note — The Fig. 4L is precision manufactured to perform its func-
tion as a critical component of a complete bracing assembly. To ensure per-
formance, the UL Listing requires that the Fig. 4L must be used only
with other TOLCO bracing products.

Dimensions • Weights
Bolt Max. Rec. Approx.
Sizes A C D Size Load Lbs. Wt./100
21/2 67/16 21/2 23/4 1/2 2015 253
3 7 23/4 31/16 1/2 2015 268
4 81/2 33/8 311/16 1/2 2015 348
5 93/4 37/8 43/8 1/2 2015 380
6 111/2 5 51/8 1/2 2015 640
8 131/4 611/16 61/8 1/2 2015 728

Longitudinal Brace

4-Way Riser Brace Transverse Brace


(Plan view)

OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
30 CUSTOMER SERVICE • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 9/22/2001

Component of State of
Fig. 5 - Standard Double Bolt Pipe Clamp California OSHPD Approved
Seismic Restraints System

Size Range — 1/2" thru 36" pipe.


Material — Carbon Steel
Function — Recommended for the suspension of pipe requiring up to 4" of insulation
and where flexibility of the clamp may be necessary. Use
Fig. 330 Weldless Eye Nut, Fig. 102 Eye Rod or Fig. 101 Welded Eye Rod. Also rec-
ommended for the attachment of sway bracing up to 8 inches. Refer to TOLCO™
State of California Approved Seismic Restraint Product Manual.
Approvals — Conforms to Federal Specification WW-H-171E, Type 3 and
Manufacturers Standardization Society SP-69, Type 3. Included in our Seismic
Restraints Catalog approved by the State of California Office of Statewide Health
Planning and Development (OSHPD).
Maximum Temperature — 750°F
Finish — Plain
Note — Available in Electro-Galvanized and HDG
finish or Stainless Steel materials.
Order By — Figure number, pipe size and finish.

Dimensions • Weights
Max. Design Load Lbs.
Pipe For Service Temp. Approx.
Size A B C D E Bolt Size 650° 750°F Wt./100
1/2 3/8 2 /16
13
2 /16
13
1 /2
1
7/8 3/8 950 — 73
3/4 5/8 3 23/8 111/16 11/16 3/8 950 — 73
1 5/8 31/4 25/8 115/16 15/16 3/8 950 — 77
11/4 5/8 31/2 27/8 23/16 19/16 3/8 950 — 79
11/2 1 53/8 41/2 25/8 13/4 5/8 1545 1380 236
2 1 513/16 415/16 215/16 21/16 5/8 1545 1380 251
21/2 1 61/8 51/4 31/4 23/8 5/8 1545 1380 274
3 1 63/4 57/8 35/8 211/16 5/8 1545 1380 289
31/2 1 73/16 65/16 37/8 3 5/8 1545 1380 315
4 1 73/4 65/8 411/16 39/16 3/4 2500 2230 745
5 1 89/16 77/16 55/16 43/16 3/4 2500 2230 828
6 11/2 97/8 81/2 61/8 43/4 7/8 2865 2555 1261
8 11/2 11 95/8 75/16 515/16 7/8 2865 2555 1535
10 11/2 12 101/2 87/8 75/16 1 3240 2890 2173
12 11/2 131/8 115/8 915/16 87/16 1 3240 2890 2404
14 2 145/16 129/16 115/16 99/16 11/4 4300 3835 4002
16 2 159/16 1313/16 125/16 109/16 11/4 4300 3835 4362
18 2 167/8 151/8 133/8 115/8 11/4 4300 3835 4935
20 2 181/4 163/8 151/8 131/4 13/8 5490 4900 6570
24 2 207/16 187/16 175/16 155/16 13/8 4500 4015 7524
30 21/2 26 23 22 19 13/8 7500 — 19502
36 21/2 323/8 287/8 255/8 221/8 13/4 10500 — 23488
Based on allowable stresses shown in the ANSI code for pressure piping.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 31
www.tolco.com

www.tolco.com
a brand of
®
Revision 9/22/2001

Fig. 5H - Heavy Duty Double Bolt Pipe Clamp


Size Range — 1/2" thru 36" pipe.
Material — Carbon Steel
Function — Recommended for the suspension of heavy duty high
temperature pipe runs requiring up to 4" of insulation and where
flexibility of the clamp may be necessary. Use with Fig. 330
Weldless Eye Nut, Fig. 102 Eye Rod or Fig. 101 Welded Eye Rod.
Approvals — Conforms to Federal Specification WW-H-171E, Type
3 and Manufacturers Standardization Society SP-69, Type 3.
Maximum Temperature — 750°F
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or Stainless
Steel materials.
Order By — Figure number, pipe size and finish.

Dimensions • Weights
Max. Design Load Lbs.
Pipe For Service Temp. Approx.
Size A B C D E Bolt Size 650° 750°F Wt./100
6 1 /4
3
10 /16
3
8 /16
15
6 4 /4
3
1 3500 3125 1200
8 2 113/8 101/8 71/4 6 11/8 4800 4285 1850
10 21/4 131/8 113/8 9 71/4 11/4 5500 4910 3030
12 21/2 145/16 129/16 103/8 85/8 13/8 7000 6250 4200
14 21/2 151/2 131/2 115/8 95/8 11/2 9500 8485 6000
16 3 171/8 147/8 131/8 107/8 13/4 10000 8930 8000
18 31/2 181/4 161/4 141/2 121/2 2 13800 12325 11500
20 31/2 193/4 171/4 16 131/2 2 15300 13665 14000
24 31/2 223/8 195/16 181/2 151/2 2 16300 14555 19000
30 41/4 323/4 281/4 243/8 197/8 21/4 20500 — 40600
36 41/2 401/4 343/4 3051/8 225/8 23/4 28000 — 67800
Based on allowable stresses shown in the ANSI code for pressure piping.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951737.5599 • Fax: 951.737.0330
32 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 6 - Riser Clamp


Fig. 6F - Felt Lined Riser Clamp
Fig. 6PVC - PVC Coated Riser Clamp
Size Range — (Fig. 6) 1/2" thru 20" pipe
(Fig. 6F) 1/2" thru 21/2" copper tubing
(Fig. 6PVC) 1/2" thru 6" pipe
Material — Carbon Steel
Insulation Material — (Fig. 6F) 3/16" felt.
Function — Used for supporting vertical piping.
Approvals — Underwriters’ Laboratories Listed in the USA (UL), Canada
(cUL) 1/2" - 8". Factory Mutual Engineering Approved, 3/4" thru 8".
Conforms to Federal Specification WW-H-171E, Type 8, 3/4" thru 20" and
Manufacturers Standardization Society SP-69, Type 8.
Maximum Temperature — 650°F
Finish — Plain Fig. 6
Note — Available in Electro-Galvanized and HDG finish or Stainless Steel
materials.
Order By — (Fig. 6 and Fig. 6PVC) pipe size and finish. (Fig. 6F) copper
tube size and finish. (Fig. 6F is available for Iron Pipe Size, consult factory.

Fig. 6PVC Fig. 6F


Dimensions • Weights
Pipe Max. Rec. Approx.
Size A B C Bolt Size Load Lbs. Wt./100
1/2 91/4 1/2 11/8 3/8 255 144
3/4 91/4 1/2 11/8 3/8 255 144
1 99/16 1/2 11/4 3/8 255 147
11/4 911/16 1/2 13/8 3/8 255 150
11/2 103/8 1/2 11/2 3/8 255 153
2 103/4 1/2 2 3/8 255 165
21/2 11 5/8 21/4 3/8 390 228
3 12 5/8 3 3/8 530 246
31/2 13 5/8 31/4 1/2 670 264
4 131/2 3/4 33/8 1/2 810 347
5 141/2 3/4 43/8 1/2 1160 385
6 151/8 7/8 47/8 1/2 1570 564
8 181/2 1 53/4 5/8 2500 1017
10 201/4 1 71/4 5/8 2500 1138
12 223/4 1 81/4 5/8 2700 1759
14 24 11/8 9 5/8 2700 1922
16 26 11/8 101/4 3/4 2900 3245
18 28 11/4 111/2 3/4 2900 3372
20 30 13/8 121/2 3/4 2900 3499

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 33
www.tolco.com

www.tolco.com
®
Revision 5/24/2001
a brand of

Fig. 7 - Offset Pipe Clamp


Size Range — 1/2" thru 12" pipe
Material — Carbon Steel
Function — Recommended for support of pipe lines running at a definite
distance from the wall or floor of a building or structure.
Maximum Temperature — 650°F
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or Stainless Steel
materials. Special “B” dimensions available on request, consult factory.
Order By — Figure number, pipe size and finish
Dimensions • Weights
Pipe Hole Size Max. Rec. Approx.
Size A B C Bolt Size Load Lbs. Wt./100
1/2 513/16 27/16 7/16 3/8 190 107
3/4 515/16 21/2 7/16 3/8 190 109
1 61/4 25/8 7/16 3/8 190 116
11/4 611/16 23/4 7/16 3/8 190 126
11/2 615/16 3 7/16 3/8 190 134
2 85/16 33/16 7/16 3/8 420 191
21/2 87/8 37/16 7/16 3/8 420 209
3 91/2 33/4 7/16 3/8 420 232
31/2 101/16 4 7/16 3/8 420 250
4 109/16 41/4 9/16 1/2 610 327
5 1111/16 43/4 9/16 1/2 610 370
6 143/8 55/16 9/16 1/2 870 650
8 167/16 65/16 9/16 1/2 870 787
10 211/2 73/8 13/16 3/4 925 1238
12 247/8 83/8 13/16 3/4 1225 2100

Fig. 8 - Extended Pipe Clamp


Size Range — 3/4" thru 8" pipe
Material — Carbon Steel
Function — For suspending or
Dimensions • Weights
supporting piping runs where the Pipe Bolt Approx.
Size A B Size Wt./100
pipe cannot be determined until
installation. Field modify to suit 3/4 47/16 12 3/8 225
1 411/16 12 3/8 230
conditions
11/4 5 12 3/8 235
Maximum Temperature — 650°F 11/2 51/4 12 3/8 240
Finish — Plain 2 6 12 1/2 345
Note — Available in Electro- 21/2 71/4 12 1/2 360
3 77/8 12 1/2 375
Galvanized and HDG finish or
31/2 83/8 12 12 390
Stainless Steel materials. Special
4 91/4 12 1/2 500
“B” dimensions available on 5 101/2 12 1/2 545
request, consult factory. 6 121/2 12 5/8 870
Order By — Figure number, pipe 8 145/8 12 5/8 980
size and finish

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
34 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
®
Revision 10/3/2001
a brand of

Fig. 9 - Underground Socket Clamp


Size Range — 4" thru 24" pipe
Material — Carbon Steel
Function — Clamp is used for underground A.W.W.A. cast iron and
ductile iron water pipe to prevent joints from separating. The O.D. of the
A.W.W.A. pipe is shown in the data table.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or Stainless
Steel materials.
Order By — Figure number, pipe size and outside diameter of pipe.
Order Fix. 9X lugs, tie rods and hex nuts separately.

Dimensions • Weights
Pipe Pipe Fig. 9X Approx.
Size O.D. A B* Bolt Size Washer Size Wt./100
4 4.80 109/16 121/2 5/8 3/4 866
6 6.90 13 151/8 5/8 3/4 1058
8 9.05 16 177/8 5/8 3/4 1246
10 11.10 173/4 191/8 5/8 3/4 1434
12 13.20 193/4 23 5/8 3/4 1614
14 15.30 253/4 277/8 7/8 11/4 4557
16 17.40 293/16 317/8 1 11/4 6730
18 19.50 31 3311/16 11/4 11/4 7643
20 21.60 301/8 357/8 11/4 11/2 9174
24 25.80 365/8 405/8 11/2 11/2 11991

Fig. 9X - Socket Clamp Washer


Size Range — 3/4" thru 11/2" rod
Material — Cast Iron
Function — Used with Fig. 9 to secure tie rods. The projecting lug bears
against the clamp bolt to prevent washer and tie rod from slipping off clamp.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or Stainless Steel
materials.
Order By — Figure number, rod size and finish

Dimensions • Weights
Tie Rod Approx.
Size A B Wt./100
3/4 213/16 7/8 95
1 313/16 15/16 253
11/4 313/16 13/8 248
11/2 31/2 15/8 240

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 35
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 14 - Double Bolt Underground Socket Clamp


Size Range — 4" thru 24" pipe
Material — Carbon Steel
Function — Clamp is used for underground A.W.W.A. cast iron and
ductile iron water pipe to prevent joints from separating. The O.D. of the
A.W.W.A. pipe is shown in the data table.
Approvals — Conforms to National Fire Protection Association (NFPA)
Pamphlet 24, 4" thru 12" pipe sizes.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or Stainless
Steel materials.
Order By — Figure number, pipe size and outside diameter of pipe.
Order Fig. 14X plate washers, tie rods and hex nuts separately.
Dimensions • Weights
Pipe Pipe Fig. 9X Approx.
Size O.D. A B* Bolt Size Washer Size Wt./100
4 4.80 141/16 95/16 5/8 3/4 1275
6 6.90 167/16 1111/16 5/8 3/4 1455
8 9.05 195/8 147/8 5/8 3/4 2350
10 11.10 2113/16 171/16 3/4 3/4 2925
12 13.20 241/2 191/4 7/8 1 4030
14 15.30 2615/16 2111/16 7/8 1 5385
16 17.40 303/4 243/4 1 11/8 7645
18 19.50 345/16 275/16 11/4 11/4 9425
20 21.60 365/8 295/8 11/4 11/2 10975
24 25.80 421/8 343/8 11/2 11/2 14865

Fig. 14X - Plate Washer


Size Range — 3/4" thru 11/2" pipe
Material — Carbon Steel
Function — Used with Fig. 14 to secure tie rods.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or Stainless Steel
materials.

Dimensions • Weights
Tie Rod Approx.
Size A B Wt./100
3/4 3 7/8 120
1 31/2 11/8 157
11/8 31/2 11/4 194
11/4 31/2 13/8 230
11/2 31/2 15/8 240

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
36 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 20 - Standard Pipe Strap


Fig. 20S - Flush Mount Pipe Strap
Data Table for Fig. 20S
Size Range — 1/2" thru 8" pipe
Dimensions • Weights
Material — Carbon Steel
Pipe Hole Max. Rec. Approx.
Function — Recommended for supporting pipe Sizes A B C D Size Load Lbs. Wt./100
with fittings vertically or horizontally to walls or 1/2 41/8 5/16 27/8 3/4 7/16 410 21
ceiling. Fig. 20S will support pipe flush with 3/4 45/16 7/16 3 15/16 7/16 410 24
mounting surface. 1 49/16 9/16 33/8 11/8 7/16 410 26
Approvals — Conforms to Federal Specification 11/4 415/16 11/16 33/4 11/2 7/16 410 30
WW-H-171E, Type 26 and Manufacturers 11/2 53/16 13/16 41/4 15/8 7/16 410 33
Standardization Society SP-69, Type 26. 2 53/4 11/16 43/4 21/4 7/16 410 38
21/2 61/4 19/16 51/4 23/4 7/16 610 102
Finish — Plain 3 67/8 15/8 57/8 33/8 7/16 610 118
Note — Available in Electro-Galvanized and HDG 31/2 73/8 17/8 63/8 37/8 7/16 610 130
finish or Stainless Steel materials. 4 83/8 21/8 7 43/8 9/16 725 159
Order By — Figure number, pipe size, material 5 97/16 25/8 77/8 53/8 9/16 725 191
6 101/2 33/16 87/8 67/16 9/16 725 234
and finish 8 14 41/4 111/2 83/8 11/16 900 446

Data Table for Fig. 20


Dimensions • Weights
Pipe Hole Max. Rec. Approx.
Sizes A B C D Size Load Lbs. Wt./100
1/2 37/8 3/4 31/16 15/32 7/16 410 16
3/4 4 13/16 31/8 15/16 7/16 410 21
1 49/16 7/8 33/8 11/2 7/16 410 26
11/4 415/16 1 33/4 17/8 7/16 410 30
11/2 53/16 13/16 41/4 21/8 7/16 410 33
2 53/4 17/16 43/4 25/8 7/16 410 38
21/2 61/4 111/16 51/4 31/8 7/16 610 102
3 67/8 2 57/8 33/4 7/16 610 118
31/2 73/8 21/4 63/8 41/4 7/16 610 130
4 83/8 21/2 7 43/4 9/16 725 159
5 97/16 31/16 77/8 513/16 9/16 725 191
6 101/2 35/8 87/8 67/8 9/16 725 234
8 14 45/8 111/2 9 11/16 900 446

FIG. 21 - “Tin Strap”


Size Range — 1/2" thru 2" pipe
Material — Carbon Steel
Function — Light duty strap that attaches pipe or copper
tubing to horizontal or vertical structure.
Finish — Pre-Galvanized
Note — Available with felt lining, order TOLCO™ Fig. 21F.
Order By — Figure number and pipe size

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 37
www.tolco.com

www.tolco.com
a brand of
®
Revision 3/31/2003

Fig. 22 - Hanger for CPVC Plastic Pipe


Single Fastener Strap Type
Size Range — 3/4" thru 2" CPVC pipe
Material — Carbon Steel, Pre-Galvanized
Function — Intended to perform as a hanger to support only CPVC piping
used in automatic fire sprinkler systems. The product acts as a hanger when
tab is upward and the fastener screw is in the horizontal position. Figure 22
can be installed on the top of a beam, but in this situation acts as a guide to
the piping which is supported by the beam itself. It is not intended to support
CPVC pipe from under a flat horizontal surface, such as a ceiling. For this
type of installation, use the TOLCO™ Fig. 23, Double Fastener Strap for
CPVC Piping. Fig. 22, when inverted, with the hanger tab downward, can
function as a restrainer to prevent the upward movement of the sprinkler head
during activation.
Approvals — Underwriters’ Laboratories Listed in the USA (UL) and Canada
(cUL) to support fire sprinkler piping. Meets and exceeds the requirements of
NFPA 13, 13R and 13D.
Features — Fig. 22 incorporates features which protect the pipe and ease installation. The flared edge design* pro-
tects CPVC pipe from any rough surface. It is easily attached to the building structure using the special UL Listed hex
head self threading screw furnished with the product, this is the minimum size fastener acceptable. It is recommended
that rechargeable electric drills fitted with a hex socket attachment to be used as installation tools. No impact tools
(such as a hammer) or impact fasteners (such as drive screws or nails) are allowed. Damage has been know to result
from installations using impact type tools. No pre-drilling of a pilot hole in wood is required.
Finish — Pre-Galvanized
Note — Fastener into light gauge metal may be ordered separately. Minimum acceptable: #10 x 1" Hardened Self
Threading Screw with 5/16" hex washer head.
Order By — Figure number and CPVC pipe size.

* Patent Pending

Dimensions • Weights
CPVC Max. Hanger Fastener Hex Approx.
Pipe Size A B C Spacing (Ft.) Head Size Wt./100
3/4 27/16 15/16 13/16 51/2 5/16 9
1 211/16 17/16 13/16 6 5/16 9
11/4 31/16 15/8 13/16 61/2 5/16 11
11/2 35/16 13/4 13/16 7 5/16 12
2 33/4 21/8 13/16 8 5/16 15

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
38 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 22C - Combination


Hanger & Restrainer Application
Size Range — 3/4" thru 2" CPVC pipe
Material — Carbon Steel, Pre-Galvanized
Function — Designed to support a CPVC pipe away
from the corner of a beam. This position allows for easy
installation of drops or risers without adding additional
wood blocks.
Approvals — Underwriters’ Laboratories Listed in the USA
(UL) and Canada (cUL) for use as a combination hanger and
restrainer.
Finish — Pre-Galvanized
Note — Approved UL Listed fastener into wood is furnished
with the product. A fastener into light gauge metal may be
ordered separately. Minimum acceptable #10 x 1" hardened
self threading screw with 5/16" hex washer head.
Order By — Fig. 22C application is composed of two
standard Fig. 22 models — order two singles for each hanger
and restrainer application required.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 39
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 23 - Hanger for CPVC Plastic Pipe


Double Fastener Strap Type
Size Range — 3/4" thru 2" CPVC pipe
Material — Carbon Steel, Pre-Galvanized
Function — Intended to perform as a hanger/restrainer to support
only CPVC piping used in automatic fire sprinkler systems. Can be
installed on the top or on the bottom of a beam. The Fig. 23 can also
be installed on the side of a beam. The Fig. 23 can also function as
a restrainer to prevent the upward movement of the sprinkler head
during activation.
Approvals — Underwriters’ Laboratories Listed in the USA (UL) and
Canada (cUL) to support fire sprinkler piping. Meets and exceeds
the requirements of NFPA 13, 13R and 13D.
Features — Fig. 23 incorporates features which protect the pipe and
ease installation. The flared edge design* protects the CPVC pipe
from any rough surface. It also incorporates snap restrainers allow-
ing easier and faster installation. Easily attaches to the building
structure using the two UL Listed hex head self threading screws**
furnished with the product. It is recommended that rechargeable
electric drills fitted with a hex socket attachment be used as installa-
tion tools. No impact tools (such as a hammer) or impact fasteners
(such as drive screws or nails) are allowed. Damage has been
known to result from installations using impact type tools.
No pre-drilling of a pilot hole in wood is required.
Finish — Pre-Galvanized
Order By — Figure number and pipe size
* Patent Pending
** Hardened hex head self threading screw is furnished with the
product and is the minimum fastener size acceptable.

Dimensions • Weights
CPVC Max. Hanger Fastener Hex Approx.
Pipe Size A B C Spacing (Ft.) Head Size Wt./100
3/4 31/8 19/16 13/16 51/2 5/16 9
1 33/8 111/16 13/16 6 5/16 9
11/4 43/16 23/32 13/16 61/2 5/16 11
11/2 47/16 27/32 13/16 7 5/16 12
2 47/8 27/16 13/16 8 5/16 15

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
40 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 24 - Hanger for CPVC Plastic Pipe


Double Fastener Strap Type - Side Mount
Size Range — 3/4" thru 2" CPVC pipe
Material — Carbon Steel, Pre-Galvanized
Function — Intended to perform as a hanger/restrainer to support only
CPVC piping used in automatic fire sprinkler systems. Can be installed
on the top or on the bottom of a beam. The Fig. 24 can also function
as a restrainer to prevent the upward movement of the sprinkler head
during activation.
Approvals — Underwriters’ Laboratories Listed in the USA (UL) and
Canada (cUL) to support fire sprinkler piping. Meets and exceeds the
requirements of NFPA 13, 13R and 13D.
Features — Fig. 24 incorporates features which protect the pipe and
ease installation. The flared edge design* protects the CPVC pipe from
any rough surface. Easily attaches to the building structure using the two
UL Listed hex head self threading screws** furnished with the product. It
is recommended that rechargeable electric drills fitted with a hex socket
attachment be used as installation tools. No impact tools (such as a hammer)
or impact fasteners (such as drive screws or nails) are allowed. Damage has
been known to result from installations using impact type tools. No pre-drilling
of a pilot hole in wood is required.
Finish — Pre-Galvanized
Order By — Figure number and pipe size
* Patent Pending
** Hardened hex head self threading screw is furnished with the
product and is the minimum fastener size acceptable.

Dimensions • Weights
CPVC Max. Hanger Fastener Hex Approx.
Pipe Size A B C Spacing (Ft.) Head Size Wt./100
3/4 25/16 15/32 13/16 51/2 5/16 9
1 25/8 15/16 13/16 6 5/16 9
11/4 3 11/2 13/16 61/2 5/16 11
11/2 31/4 15/8 13/16 7 5/16 12
2 311/16 127/32 13/16 8 5/16 15

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 41
www.tolco.com

www.tolco.com
a brand of
®
Revision 3/24/2003

Fig. 25 - Surge Restrainer


Size Range — One size fits 3/4" thru 2" pipe.
Material — Steel
Function — Designed to be used in conjunction with TOLCO™ Band
Hangers to restrict the upward movement of piping as it occurs during
sprinkler head activation or earthquake type activity. The surge restrainer
is easily and efficiently installed by snapping into a locking position on
the bank hanger. This product is intended to satisfy the requirements as
indicated in the National Fire Protection Association (NFPA 13, 1999
Edition), 6-2.3.3, 6-2.3.4 and A-6i-2.3.3 Can be used to restrain either
steel pipe or CPVC plastic Pipe.
Approvals — Underwriters’ Laboratories Listed only when used with
TOLCO band hangers Fig. 2, 2NFPA and 200, in the USA (UL) and
Canada (cUL).
Finish — Pre-Galvanized
Order By — Figure number and TOLCO band hanger, size from 3/4"
thru 2".
Patent #5,344,108

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951737.5599 • Fax: 951.737.0330
42 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 27 & 27A


“Stand-Off” Hanger/Restrainer for CPVC Plastic Pipe
Size Range — 3/4" and 1" CPVC Plastic Pipe*.
Material — Carbon Steel, Pre-Galvanized
Function — Designed to be used as a hanger/restrainer** for CPVC piping
where the “stand-off” design will ease installation by eliminating the need for
wood blocking.
Features:
• Flared edge design protects CPVC from any rough or abrasive surfaces.
• Snap-in retainers hold pipe firmly in place during installation.
• The “Stand-Off” design eliminates the need for wood block extension. Fig. 27
• Can be installed on horizontal or vertical piping regardless of mounting
surface orientation.
• Attaches easily to wood structure with two hex head self-threading
screws furnished with product.
• Installs easily using rechargeable electrical driver with 5/16" sockets,
eliminating impact tool damage to pipe.
Approvals — Underwriters’ Laboratories Listed in the USA (UL) and Canada
(cUL) to support automatic fire sprinkler systems. Meets and exceeds the Fig. 27A
requirements of NFPA 13, 13R and 13D.
Important Note** — When installed in slot opening on Fig. 27, Fig. 27A
provides additional stability and satisfies the UL vertical restraint requirement
where needed.
Order By — Fig. 27: By figure number and CPVC pipe size
Fig. 27A: By figure number and CPVC pipe size
US and International Patent application in process.
*For other sizes, consult factory.
Fig. 27 and Fig. 27/27A have also been tested by UL mounted on 3/8"
composite wood web material (such as TJI Series/Trus Joist MacMillan) Fig. 27/Fig. 27A
without the use of back-up wood blocking. When using Fig. 27 and 27A in
combination on 3/8" web to satisfy the UL requirement for vertical restraint,
install two reinforcing speed nuts (Fig. 27B). Fig. 27B is UL Listed only when
used with TOLCO™ products.

Typical Applications

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 43
www.tolco.com

www.tolco.com
a brand of
®
Revision 1/11/05

Fig. 28
"Stand-Off" Hanger & Restrainer for CPVC Plastic Pipe
Size Range — ¾" through 2"
Material — Carbon Steel, Pre-Galvanized
Function — Designed to be used as a hanger and restrainer for CPVC piping
where the "stand-off" design will ease installation by eliminating the need for wood
blocking.
Features:
• Flared edge design protects CPVC pipe from any rough or abrasive surfaces.
• Unique twist and lock design holds pipe firmly in place and allows retrofit type
of installation.
• The "Stand-Off" design eliminates the need for wood block
extension.
• Can be installed on horizontal or vertical piping regardless of mounting sur-
face orientation.
• Attached easily to wood structure with two hex head self-threading screws
furnished with product.
• Installs easily using rechargeable electrical driver with 5/16" extension socket
eliminating impact tool damage to pipe.
• U.L. Listed as a hanger and a restrainer for fire sprinkler piping.
Approvals — Underwriters' Laboratory Listed in the USA (UL) and Canada (cUL) to
support automatic fire sprinkler systems. Meets and exceeds the requirements of
NFPA 13, 13R and 13D. Fig. 28 satisfies the UL vertical restraint requirement where
needed. UL Listed as a hanger and vertical restraint when installed on 3/8" composite
wood material. Use two Fig. 27B Speed Nuts when used as a hanger and restraint.
Use one Fig. 27B Speed Nut on the upper installed screw when used as a hanger only.
Order by — Figure number and pipe size.
US AND INTERNATIONAL PATENT APPLICATION IN PROCESS.

Dimensions • Weights
Approx.
A B C Wt.
3/4 31/8 2 .180
1 33/8 21/8 .210
11/4 35/8 23/8 .225
11/2 41/8 21/2 .310
2 41/2 23/4 .340

OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
50 CUSTOMER SERVICE • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 30 - Light Welded Bracket


Material — Carbon Steel
Function —Recommended for suspending pipe
outward from mounting surface.
Approvals — Conforms to Federal Specification WW-H-171E,
Type 32 and Manufacturers Standardization Society SP-69,
Type 31.
Finish — Plain
Note — Available in Electro-Galvanized and HDG
finish or Stainless Steel materials.
Order By — Figure number, indicate “A” dimensions,
“H” diameter and finish

Dimensions • Weights
Approx.
A B C Wt./100
9 8 6.5 750
13 12 10.5 750
19 18 16.5 750

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 45
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 30L - Welded Bracket - Light Duty


Fig. 30M - Welded Bracket - Medium Duty
Fig. 30H - Welded Bracket - Heavy Duty
Max. Recommended Load — (Fig. 30L) 750 lbs.,
(Fig. 30M) 1500 lbs., (Fig. 30H) 3000 lbs.
Material — Carbon Steel
Function — Recommended for supporting pipe on top or
hanging through support bracket outward from mounting sur-
face..
Approvals — Conforms with the following Federal
Specification WW-H-171E and Manufacturers
Standardization Society Types:
30L — WW-H-171E, Type 32 and MSS SP-69 Type 31
30M — WW-H-171E, Type 33 and MSS SP-69 Type 32
30H — WW--171E, Type 34 and MSS SP-69 Type 33
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.

Fig. 30L
Dimensions • Weights
Hole Max. Rec. Approx.
Sizes A B C Size Load Lbs. Wt./100
1 13 9 111/2 9/16 750 571
2 17 13 151/2 9/16 750 769
3 23 19 211/2 9/16 750 1057

Fig. 30M
Dimensions • Weights
Hole Max. Rec. Approx.
Sizes A B C Size Load Lbs. Wt./100
0 18 12 151/2 13/16 1500 1577
1 24 18 211/2 13/16 1500 2578
2 30 24 271/2 13/16 1500 4446

Fig. 30H
Dimensions • Weights
Hole Max. Rec. Approx.
Sizes A B C D Size Load Lbs. Wt./100
1 18 12 151/4 * 11/8 3000 2195
2 24 18 211/4 21/2 11/8 3000 4398
3 30 24 271/4 21/2 11/8 3000 6294
4 36 30 33 21/2 11/8 3000 7196
5 42 36 39 31/2 11/8 3000 13197
6 50 42 46 31/2 11/8 3000 15795
* One hole

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
46 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 31-M - Welded Knee Bracket


Size Range — 1/2" thru 8" pipe
Material — Carbon Steel
Function —Recommended for suspending pipe outward from
mounting surface.
Finish — Plain
Note — Maximum “L” dimension 1" - 4". Available in Electro-
Galvanized and HDG finish or Stainless Steel materials.
Order By — Figure number, pipe size, indicate “L” dimension
and finish

Dimensions • Weights
Pipe H Approx.
Size Hole Size Wt./100
1/2 - 21/2 9/16 1000
3 9/16 1000
31/2 9/16 1000
4 11/16 1000
5 11/16 1000
6 11/16 1000
8 11/16 1000

Fig. 31-O - “O” Bracket


Size Range — 1/2" thru 8" pipe
Material — Carbon Steel
Function —Recommended for suspending pipe outward from
mounting surface.
Finish — Plain
Note — Maximum “L” dimension 1" - 4". Available in Electro-
Galvanized and HDG finish or Stainless Steel materials.
Order By — Figure number, pipe size, indicate “L” dimension
and finish

Dimensions • Weights
Pipe H Approx.
Size Hole Size Wt./100
1/2 - 21/2 9/16 450
3 9/16 450
31/2 9/16 450
4 11/16 450
5 11/16 450
6 11/16 450
8 11/16 450

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 909.737.5599 • Fax: 909.737.0330
Customer Service • 800.786.5266 47
www.tolco.com

www.tolco.com
a brand of
®
Revision 9/22/2001

Fig. 32 - Anchor Chair


Size Range — 1/2" thru 24" pipe
Material — Carbon Steel
Function — Recommended for anchoring pipe to structure.
Finish — Plain
Note — 1/2" thru 4", use U-bolt to fasten chair to support; 5"
thru 24" U-bolt attaches directly to support structure. Holes
are provided in chair for fastening to support if required.
Available in Electro-Galvanized and HDG finish or Stainless
Steel materials.
Order By — Figure number and pipe size

Dimensions • Weights
Pipe U-Bolt Approx.
Size Dia. A B C Wt./100
1/2 3/8 15/16 4 13/16 80
3/4 3/8 11/16 23/8 13/8 88
1 3/8 13/16 25/8 13/8 96
11/4 3/8 13/8 27/8 21/16 107
11/2 3/8 19/16 31/4 23/8 118
2 3/8 13/4 33/8 213/16 132
21/2 1/2 2 415/16 37/16 175
3 1/2 23/8 59/16 41/16 215
31/2 1/2 23/8 61/16 49/16 240
4 1/2 27/8 69/16 51/16 265

Dimensions • Weights
Pipe U-Bolt Approx.
Size Dia. A B C D Wt./100
5 1/2 37/16 4 61/8 21/4 290
6 3/8 4 5 73/8 3 315
8 5/8 51/4 7 93/8 41/2 885
10 3/4 67/16 8 115/8 51/2 1050
12 7/8 71/2 9 133/4 6 1210
14 7/8 83/16 10 15 7 1480
16 7/8 91/4 10 17 7 1735
18 1 103/8 11 191/8 7 2011
20 1 113/8 12 211/8 7 2332
24 1 135/8 12 251/8 8 2550

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951737.5599 • Fax: 951.737.0330
48 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 33 - Concrete Single Lug Plate


Size Range — 1/2" thru 2" rod
Material — Carbon Steel
Function — Structural attachment to concrete ceiling. Use
with Fig. 332 Bridge Clevis to attach to center lug.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, rod size and finish

Dimensions • Weights
Rod Max. Rec. Approx.
Size A B C D H T Load Lbs.* Wt./100
1/2 10 8 9/16 17/8 5/8 1/4 1130 1115
5/8 10 8 9/16 2 3/4 1/4 1810 1465
3/4 10 8 11/16 2 7/8 3/8 2710 1478
7/8 10 8 11/16 23/4 1 3/8 3770 2195
1 12 8 13/16 23/4 11/8 1/2 4960 3185
11/4 12 8 15/16 4 13/8 5/8 8000 4385
11/2 12 8 11/8 4 15/8 3/4 11630 4568
13/4 12 8 13/8 41/4 17/8 3/4 15700 5578
2 12 8 13/8 41/4 21/4 3/4 20630 5820
* Based on allowable stresses shown in the ANSI code for pressure piping.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 49
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 34 - Concrete Clevis Plate with Pin


Size Range — 3/8" thru 2" rod
Material — Carbon Steel
Function — Structural attachment to concrete ceiling where
flexibility is desired. (Use with Fig. 330 Weldless Eye Nut,
Fig. 102 Eye Rod or Fig. 101 Welded Eye Rod.)
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, rod size and finish

Dimensions • Weights
Rod Pin Dia. Max. Rec. Approx.
Size A B C D E F Load Lbs.* Wt./100
3/8 10 8 9/16 23/8 13/4 1/2 610 1175
1/2 10 8 9/16 23/8 13/4 5/8 1130 1185
5/8 10 8 9/16 21/2 13/4 3/4 1810 1565
3/4 10 8 11/16 21/2 21/4 7/8 2710 1685
7/8 10 8 11/16 31/2 23/4 1 3770 1805
1 12 8 13/16 33/4 3 11/8 4960 3685
11/4 12 8 15/16 33/4 33/4 13/8 8000 4085
11/2 12 8 11/8 5 41/2 15/8 11630 5975
13/4 14 10 13/8 51/4 51/4 17/8 15700 9355
2 14 10 13/8 51/4 51/4 21/4 20700 10000
* Based on allowable stresses shown in the ANSI code for pressure piping.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
50 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 35 - Concrete Rod Attachment Plate


Size Range — 3/8" thru 2" rod
Material — Carbon Steel
Function — Structural attachment to concrete ceiling where
vertical attachment is desired. Attach hanger rod directly to
support bracket.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, rod size and finish

Dimensions • Weights
Rod Max. Rec. Approx.
Size A B C D Load Lbs.* Wt./100
3/8 10 8 9/16 31/4 610 1155
1/2 10 8 9/16 31/4 1130 1160
5/8 10 8 9/16 31/2 1810 1505
3/4 10 8 11/16 35/8 2710 1605
7/8 10 8 11/16 43/4 3770 1665
1 12 8 13/16 51/4 4960 3485
11/4 12 8 15/16 53/4 8000 3865
11/2 12 8 11/8 71/2 11630 5635
13/4 14 10 13/8 9 15700 8805
2 14 10 13/8 91/2 20700 9215
* Based on allowable stresses shown in the ANSI code for pressure piping.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 51
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 40 - Return Line Offset J-Hook


Size Range — 1/2" thru 8" pipe
Material — Carbon Steel
Function —Recommended for supporting light pipe runs with
a 1" offset from mounting surface.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, pipe size and finish

Dimensions • Weights

Pipe Size Max. Rec. Load Lbs. Approx. Wt./100


1/2 200 54
3/4 200 55
1 200 78
11/4 200 85
11/2 200 90
2 200 98
21/2 350 126
3 350 136
31/2 350 147
4 450 235
5 450 350
6 450 383
8 450 605

Fig. 41 - Return Line Straight J-Hook


Size Range — 1/2" thru 8" pipe
Material — Carbon Steel
Function —Recommended for supporting light pipe runs.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, pipe size and finish

Dimensions • Weights

Pipe Size Max. Rec. Load Lbs. Approx. Wt./100


1/2 200 54
3/4 200 55
1 200 76
11/4 200 82
11/2 200 87
2 200 96
21/2 350 124
3 350 134
31/2 350 145
4 450 153
5 450 348
6 450 381
8 450 600

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
52 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 42 - Angle Bracket


Material — Carbon Steel
Function — Recommended for supporting pipe at various
distances from wall or column.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, size and finish

Dimensions • Weights
Pipe Hole Max. Rec. Approx.
Size A B Size Load Lbs. Wt./100
1 3 2 7/16 180 46
2 4 3 7/16 180 65
3 3 2 9/16 390 85
4 4 3 9/16 390 115

Fig. 50 - Side Beam Bracket


Size Range — 3/8" thru 7/8" rod
Material — Carbon Steel
Function — Recommended for attaching hanger rod to side
of beams or walls.
Approvals — 3/8", Underwriters’ Laboratories Listed in the
USA (UL) and Canada (cUL), and Factory Mutual
Engineering approved.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, rod size and finish

Dimensions • Weights
Pipe Hole Max. Rec. Approx.
Size A B C Size Load Lbs. Wt./100
3/8 2 3/4 2 7/16 700 35
1/2 2 3/4 2 9/16 700 35
5/8 2 3/4 2 11/16 700 32
3/4 21/2 3/4 21/2 13/16 1250 110
7/8 21/2 3/4 21/2 15/16 1250 100

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 53
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 51 - Side Beam Bracket for


NFPA Rod and Fastener Sizing
Size Range — 3/8" and 1/2" rod, 1/2" thru 8" pipe
Material — Carbon Steel
Function — Recommended for attaching hanger rod to side of
beams or walls. Designed to accommodate current rod schedule
and fastener requirements per National Fire Protection
Association (NFPA) Pamphlet 13.
Approvals — Underwriters’ Laboratories Listed in the USA (UL)
and Canada (cUL), and Factory Mutual Engineering approved.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, rod size and finish

Dimensions • Weights
Pipe Rod Hole Size Max. Rec. Approx.
Size Size A B C H-1 H-2 Load Lbs.* Wt./100
1/2 - 2 3/8 2 3/4 2 7/16 7/16 700 35
21/2 - 4 3/8 2 3/4 2 9/16 7/16 700 34
5-6 1/2 21/2 3/4 21/2 9/16 9/16 1250 71
8 1/2 21/2 3/4 21/2 11/16 9/16 1250 70

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
54 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 52 - Six Hole Side Beam Bracket


Size Range — 3/8" and 1/2" rod, 1/2" thru 31/2" pipe
Material — Carbon Steel
Function — Recommended for attaching hanger rod to steel or
wood beams.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, rod size and finish

Dimensions • Weights
Pipe Hole Size Max. Rec. Approx.
Size A B C H-1 H-2 H-3 Load Lbs.* Wt./100
3/8 x 1/2 2 13/16 2 9/16 7/16 5/16 700 35
1/2 x 1/2 2 3/4 2 9/16 9/16 5/16 700 34

Fig. 56 - Tapped Side Beam Connector


Size Range — 1/2" thru 4" pipe (3/8" rod).
Material — Carbon Steel
Function — Recommended for attaching hanger rod to steel or
wood beams. Tapped hole allows easy adjustment of hanger rod.
Approvals — Underwriters’ Laboratories Listed in the USA (UL)
and Canada (cUL), and Factory Mutual Engineering approved for
1/2" thru 4" pipe.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, rod size and finish
Note — Per NFPA 13: 1/2" thru 2" pipe use 3/8" fastener; 21/2" thru
4" pipe, use 1/2" fastener.

Dimensions • Weights

Pipe Rod Size Hole Size Approx.


Size A B C D G H Wt./100
1/2 - 4 3/8 25/8 1 11/4 7/16 9/16 20

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 55
www.tolco.com

www.tolco.com
a brand of
®
Revision 8/06/2003

Fig. 58 - Threaded Side Beam Bracket


Size Range — 3/8" rod, pipe sizes 1/2" thru 4"
Material — Carbon Steel
Function — Practical and economical bracket used to support
piping from wood, concrete or steel beams.
Features — Unique design allows rod to be easily threaded into
bracket. Offset design permits unlimited rod adjustment. Center
mounting hole will accept 3/8" and 1/2" fastener bolts. Per NFPA
13: 1/2" thru 2" pipe requires 3/8" fastener, 21/2" thru 4" pipe
requires 1/2" fastener.*
Approvals — Underwriters’ Laboratories Listed in the USA (UL)
and Canada (cUL), and Factory Mutual Engineering approved thru
4" pipe.
*Note — Additionally UL has listed the Fig. 58 with fasteners as
shown in table below.
Finish — Plain
Note — Available in Electro-Galvanized finish.
Order By — Figure number and finish

Dimensions • Weights

Pipe Size Qty. Fastener Type Material


2 2 #16 x 2 Drive Screws Wood
2 1 3/8 Lag Bolt Wood
21/2 - 4 1 1/2 Lag Bolt Wood
31/2 2 1/4 x 11/2 Lag Bolt Wood
4 2 1/4 x 2 Lag Bolts* Wood
4 2 1/4 x 1 tek screws 14 gauge
4 2 1/4 x 1 tek screws 16 gauge
* No pre-drilling required

Dimensions • Weights
Pipe Rod Max. Rec. Approx.
Size Size A B C Load Lbs. Wt./100
1/2 thru 4 3/8 23/4 11/2 11/8 300 14

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
56 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 60 - Top Beam Clamp


Size Range — 3/4" thru 6" pipe
Material — Carbon Steel
Function — Recommended for use on top flange of
standard I-beams, wide flange beams and roof trusses
where the flange thickness does not exceed .81".
Installation — Slide steel clip against beam flange and
attach hook rod and I-rod (Fig. 102). Tighten hook rod
and I-rod (Fig. 102). Hammer clip firmly against the
underside of the beam to complete the installation.
Features — The clamp holds firmly to the beam provid-
ing an efficient and economical means of supporting
small piping from the top flange of steel beams and roof
trusses.
Maximum Temperature — 650°F
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish
or Stainless Steel materials.
Order By — Figure number, flange width and flange
thickness

Dimensions • Weights
Hood Rod I-Rod (Fig. 102) Max. Rec.
Pipe Size Diameter A Load Lbs.
3/4 - 2 3/8 3/8 610
21/2 - 31/2 1/2 1/2 940
4-5 1/2 5/8 940
6 1/2 3/4 940

Fig. 61 - Top Beam Hook


Material — Carbon Steel
Function — Designed to hook onto top flange of beam
or angle truss. The support rod completes assembly and
secures it to flange.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish
or Stainless Steel materials.

Dimensions • Weights
Max. Rec.
Type A B C Load Lbs.
1 3/8 5/16 1 300
2 1/2 3/8 1 500
3 5/8 7/16 1 700
4 3/4 1/2 11/2 1000
5 7/8 9/16 11/2 2000

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 57
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 61T - Bar Joist Hanger


Size Range — 3/8" thru 1/2" rod sizes
Material — Carbon Steel
Function — Designed to hook on top chord of metal bar joist.
Hanger rod is threaded into product and secured with a washer
and nut.
Approvals — Underwriters’ Laboratories Listed in the USA
(UL) and Canada (cUL) for up to 4" pipe with 3/8" rod, up to 6"
pipe with 1/2" rod.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, rod size, and thickness of
bar joist.

Dimensions • Weights
Pipe Rod Max. Rec.
Size Size Load Lbs.
Up to 4 3/8 300
6 1/2 600

OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
64 CUSTOMER SERVICE • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 62 - Center Load Beam Clamp


Material — Carbon Steel
Function — Recommended for the suspending of hanger rod from
the center of an I-beam, equally distributing the load on both sides of
the beam. Use with Fig. 102 Eye Rod, Fig. 101 Welded Eye Rod or
Fig. 330 Weldless Eye Rod.
Approvals — Conforms to Federal Specification WW-H-171E, Type
21, and Manufacturers Standardization Society SP-58, Type 21.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or Stainless
Steel materials.
Order By — Figure number, type, width of flange and finish.

Dimensions • Weights
Max. Rec.
Type A B* Bolt Size Load Lbs.
1 1/2 13/8 3/8 1000
2 1/2 13/8 1/2 1250
3 5/8 19/16 1/2 1500
4 3/4 21/4 5/8 3000
5 3/4 21/4 5/8 3250
6 3/4 25/16 3/4 3500
* Not applicable for type 1 — 2" and type 3 — 2" flange widths.

Dimensions • Weights
Flange Max. Flange Approx. Wt./100
Width Thickness Type 1 Type 2 Type 3 Type 4 Type 5 Type 6
2 7/16 66 85 — — — —
3 1/2* 75 95 151 355* — —
4 1/2 91 114 163 382 470 634
5 5/8 100 125 187 435 536 667
6 3/4 115 143 216 452 558 728
7 7/8 129 16 242 484 606 767
8 7/8 144 177 267 510 659 861
9 1 159 196 295 583 721 913
10 1 172 210 319 625 773 982
11 1 185 227 343 667 826 1048
12 1 198 243 367 709 879 1115
* Maximum flange thickness type 1, 2 and 3 = 7/16"

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 59
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 64 - Steel “C” Clamp with Locknut


Size Range — 3/8" thru 7/8" rod
Material — Carbon Steel
Function — For attachment to I-beams, channels, and wide
flange beams where the thickness does not exceed 3/4".
Hardened set screw secures “C” Clamp to beam.
Approvals — Conforms to Federal Specification WW-H-171E,
Type 23 and Manufacturers Standardization Society SP-69,
Type 23.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, rod size and finish

Dimensions • Weights
Max. Pipe Rod Size Max. Rec. Approx.
Size A B C D Load Lbs. Wt./100
2 3/8 23/8 23/8 1 400 40
31/2 1/2 23/8 23/8 1 400 50
5 5/8 23/8 23/8 1 550 70
6 3/4 25/16 23/8 1 630 83
*8 7/8 35/16 3 13/8 1200 158
* Throat opening is 1".

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
60 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 65 and Fig. 66


Reversible C-Type Beam Clamps 3/4" and 11/4" Throat Openings

Size Range — (Fig. 65 and Fig. 66) 3/8", 1/2" and 5/8" rod
Material — Carbon Steel with hardened cup point set screw
and jam nut
Function — Recommended for hanging from steel beam where
flange thickness does not exceed 3/4" (Fig. 65) or 11/4" (Fig. 66).
Features — All steel construction eliminates structural deficien-
cies associated with casting type beam clamps. May be used on
top or bottom flange of the beam. (Beveled lip allows hanging
from top flange where clearance is limited.) May be installed with
set screw in up or down position. Offset design permits unlimited
rod adjustment by allowing the rod to be threaded completely
through the clamp. Open design permits inspection of thread
engagement.
Approvals — Underwriters’ Laboratories Listed in the USA (UL)
and Canada (cUL). Factory Mutual Engineering approved.
Conforms to Federal Specification WW-H-171E, Type 23 and
Manufacturers Standardization Society SP-69, Type 19. Exceeds
requirements of the National Fire Protection Association (NFPA),
Pamphlet 13, 3/8" rod will support 1/2" thru 4" pipe, 1/2" rod will
support 1/2" thru 8" pipe.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish.
Order By — Figure number, rod size and finish
Fig. 65 Patent #4,570,885

Fig. 65
Dimensions • Weights
Rod Size Max. Rec. Approx.
A B C D E F Load Lbs.* Wt./100
3/8 13/16 3/4 1 7/16 1 610 28
1/2 11/2 3/4 1 9/16 11/4 1130 55
5/8 11/2 3/4 1 9/16 11/4 1130 55
* Max. loads for clamp with set screw in up or down position.

Fig. 66
Dimensions • Weights
Rod Size Max. Rec. Approx.
A B C D E F Load Lbs.* Wt./100
3/8 13/16 11/4 1 7/16 1 610 28
1/2 11/2 11/4 1 9/16 11/4 1130 55
5/8 11/2 11/4 1 9/16 11/4 1130 55
* Max. loads for clamp with set screw in up or down position.

OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266 61
www.tolco.com

www.tolco.com
a brand of
®
Revision 9/22/2001

Fig. 68 - Wide Throat Top Beam “C” Clamp w/Locknut


Size Range — 3/8" thru 3/4" rod
Function — For attachment to structural shapes requiring
wider throat especially under roof with bar joist construction. B
This clamp may be used in the set screw down position only.
Approvals — Factory Mutual Engineering approved for rod
sizes 3/8" and 1/2". Conforms to Federal Specification
WW-H-171E, Type 23 and Manufacturers Standardization
Society SP-69, Type 19.
Finish — Plain
Note — Available in Electro-Galvanized finish.
E
Order By — Figure number, rod size and finish
Note — Do not over tighten set screw.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
62 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 6/01/2003

Fig. 67SS
Stainless Steel Reversible C-Type Beam Clamps
3/4" and 11/4" Throat Openings
Size Range — 3/8" and 1/2" rod sizes
Material — All Stainless Steel (T-316 or T-304)
Function — Recommended for hanging from steel beams where
flange thickness does not exceed 3/4".
Features — All steel construction eliminates structural deficiencies
associated with casting type beam clamps. May be used on top or
bottom flange of the beam. May be installed with the set screw in
up or down position. Offset design permits unlimited rod adjust-
ment by allowing the rod to be threaded completely through the
clamp.
Approvals — Underwriters’ Laboratories LIsted in the USA (UL)
and Canada (cUL). Factory Mutual Engineering approved.
Conforms to Manufacturers’ Standardization Society SP-69, Type
19. Meets or exceeds requirements of the National Fire Protection
Association (NFPA), pamphlet 13, 3/8" rod will support 1/2" through
4" pipe, 1/2" rod will support 1/2" through 8" pipe.
Order By — Figure number and rod size

Fig. 67SS

Dimensions • Weights
Pipe Stock Test Approx.
Size A B C D E F G Size Load Wt./100
1/2 - 4 3/8 17/8 11/2 3/4 3/4 7/8 11/8 5/16 x 1 1500 lbs. 47
5, 6, 8 1/2 17/8 13/4 13/16 3/4 7/8 11/8 3/8 x 11/2 4050 lbs. 84

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 63
www.tolco.com

www.tolco.com
a brand of
®
Revision 6/01/2003

Fig. 68SS
Stainless Steel Reversible C-Type Beam Clamps
3/4" and 11/4" Throat Openings
Size Range — 3/8" and 1/2" rod sizes
Material — All Stainless Steel (T-316 or T-304)
Function — Recommended for hanging from steel beams where
flange thickness does not exceed 11/4" (Fig. 68SS).
Features — All steel construction eliminates structural deficiencies
associated with casting type beam clamps. May be used on top or
bottom flange of the beam. May be installed with the set screw in
up or down position. Offset design permits unlimited rod adjust-
ment by allowing the rod to be threaded completely through the
clamp.
Approvals — Underwriters’ Laboratories LIsted in the USA (UL)
and Canada (cUL). Factory Mutual Engineering approved.
Conforms to Manufacturers’ Standardization Society SP-69, Type
19. Meets or exceeds requirements of the National Fire Protection
Association (NFPA), pamphlet 13, 3/8" rod will support 1/2" through
4" pipe, 1/2" rod will support 1/2" through 8" pipe.
Order By — Figure number and rod size

Fig. 68SS

Dimensions • Weights
Pipe Stock Test Approx.
Size A B C D E F Size Load Wt./100
1/2 - 4 3/8 21/16 2 3/4 11/4 11/8 3/8 x 11/2 1500 lbs. 84
5, 6, 8 1/2 21/4 21/4 13/16 11/4 11/4 1/2 x 2 4050 lbs. 170

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
64 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 8/13/2001

Fig. 69 - Beam Clamp Retaining Strap


Size Range — 3/8" thru 7/8" rod by 4" thru 16" length.*
Function — To offer more secure fastening of various types
of beam clamps to beam where danger of movement might be
expected. NFPA 13 requires the use of retaining straps with
all beam clamps installed in earthquake areas. Satisfies
requirements of NFPA 13 (1999) 6-4.7.1.
Important Note — Good installation practice of a retaining
strap requires that the strap be held tightly and securely to all
component parts of the assembly. Therefore a locking mecha-
nism of some kind such as a hex nut or the beveled locking
slot on the TOLCO™ Fig. 69R will provide a more secure B
reliable installation.
Approvals — Underwriters’ Laboratories listed in the
USA (UL) and Canada (cUL). Approved for use with any
listed beam clamp. Included in our Seismic Restraints
Catalog approved by the State of California Office of
Statewide Health Planning and Development (OSHPD). For
additional load, spacing and placement information relating to
OSHPD projects, please refer to the TOLCO Seismic
Restraint Systems Guidelines.
Finish — Pre-Galvanized
Order By — Figure number, type, length “B” and rod size
being used with beam clamp
Note — Minimum return on Strap: 1".

Dimensions • Weights
Type Rod Size A Hole Size B
1 3/8 7/16 Specify
1/2 9/16 Specify
2 5/8 11/16 Specify
3/4 13/16 Specify
3 3/8 - 7/8 Specify Specify
* Longer lengths are available, consult factory.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 65
www.tolco.com

www.tolco.com
a brand of
®
Revision 8/31/2001

Fig. 69R - Retrofit Capable Beam Clamp


Retaining Strap
Size Range — 3/8" and 1/2" rod; 4" thru 16" length.**
Material — Pre-Galvanized Steel
Function — To offer more secure fastening of various types
of beam clamps to beam where danger of movement might be
expected. NFPA 13 requires the use of retaining straps with
all beam clamps installed in earthquake areas. Satisfies
requirements of NFPA 13 (1999) 6-4.7.1.
Features — Beveled locking slot* is precisely formed to align
with the threaded section of a hanger rod or set screw and
engage the unit securely. May be used as shown in section
“A-A” or inverted. Allows easy installation for new construction
or retrofit applications.
Important Note — Good installation practice of a retaining
strap requires that the strap be held tightly and securely to all
component parts of the assembly. Therefore a locking mecha-
nism of some kind, such as the beveled locking slot of the Fig.
69R or a hex nut tightened against other types of retaining
straps will provide a more secure and reliable installation.
Approvals — Underwriters’ Laboratories listed in the
USA (UL) and Canada (cUL). Approved for use with any
listed beam clamp. Included in our Seismic Restraints
Catalog approved by the State of California Office of
Statewide Health Planning and Development (OSHPD). For
additional load, spacing and placement information relating to
OSHPD projects, please refer to the TOLCO Seismic
Restraint Systems Guidelines.
Finish — Pre-Galvanized
Order By — Figure number, rod or set screw size and length
Note — Minimum return on Strap: 1".
* Patent #5,947,424 Dimensions • Weights
Rod Size A Length
3/8" Specify
1/2" Specify

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
66 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 70 - Steel Rod Coupling


Fig. 70R - Steel Reducing Rod Coupling
Fig. 70S - Short Pattern Steel Rod Coupling
Fig. 71 - Steel Window Rod Coupling
Size Range — 1/4" thru 11/2" rod
Material — Carbon Steel
Function — Used for coupling two threaded rods together of
equal or reduced rod sizes, with or without inspection hole.
Finish — Electro-Galvanized
Note — Available in HDG finish or Stainless Steel materials.

Fig. 70
Dimensions • Weights FIG. 70
Rod Max Rec. Approx.
Size Length Load Lbs. Wt./100
1/4 7/8 240 2
5/16 13/4 300 13
3/8 13/4 610 11
1/2 13/4 1130 11
5/8 21/8 1810 16
3/4 21/4 2710 27
7/8 21/2 3770 57
1 23/4 4960 70
11/8" - 11/2" — Consult factory for specifications
FIG. 70R
Fig. 70R
Dimensions • Weights
Rod Max Rec. Approx.
Size Length Load Lbs. Wt./100
3/8 x 1/4 7/8 240 4
1/2 x 3/8 13/4 610 7
5/8 x 1/2 21/8 1130 14
3/4 x 5/8 21/4 1810 21
7/8 x 3/4 21/2 2710 40
FIG. 70S
Fig. 70S/Fig. 71
Dimensions • Weights
Rod Max Rec. Approx.
Size Length Load Lbs. Wt./100
3/8 11/8 610 4
1/2 11/4 1130 6

FIG. 71

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 67
www.tolco.com

www.tolco.com
a brand of
®
Revision 3/31/2003

Fig. 78 - All Steel Ceiling Plate


Size Range — 3/8" rod
Material — Carbon Steel
Features — Attachment to wood beams, ceilings, metal decks or
walls. Can also be welded to steel beams.
Approvals — Underwriters’ Laboratories Listed in the USA (UL) C A
and Canada (cUL). Factory Mutual Engineering approved.
Additionally, (UL) has listed the Fig. 78 with fasteners as shown in B
the table below.
Finish — Plain and Electro-Galvanized
Note — Available in Electro-Galvanized and HDG finish. E
Order By — Figure number, rod size and finish
D(2)
Patent #5,702,077

UL Listed Fastener Table

Pipe Size Qty Fastener Type Material

1/2 - 2 2 #14 x 11/4 A-point hex-washer-head sheet metal screw Wood


21/2 - 4 2 1/4 x 11/2 wood screws* Wood
1/2 - 2 2 1/4 x 1 tek screws Metal (18 gauge)
1/2 - 2 2 #14 x 11/4 A-point hex-washer-head sheet metal screw Wood
1/2 - 2 2 #14 x 2 A-point-hex-washer-head sheet metal screw Wood thru 5/8" gyp board
* No pre-drilling

Dimensions • Weights

Max. Rec. Approx.


Pipe Size A B C D E Load Lbs.* Wt./100
1/2 - 2 3 21/8 11/8 5/16 3/8 150 15
5-6 Consult factory for data
* Minimum safety factor of 5

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
68 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 81 - Copper Tubing Clevis Hanger


Fig. 81PVC - PVC Coated Copper Tubing Clevis Hanger
Size Range — Size1/2" thru 6" copper tubing
A
Material — Carbon Steel
Function — Recommended for the suspension of non-
insulated stationary copper tubing line.
Approvals — Conforms to Federal Specification
WW-H-171E, Type 12 and Manufacturers Standardization
B
Society SP-69 Type 1.
Finish — Copper plated D
Note — Available with plastic coating, specify by ordering
Fig. 81PVC
Order By — Figure number and nominal tubing size C

Fig. 81

Fig. 81PVC

Dimensions • Weights
Copper Tube Max. Rec. Approx.
Size A B C D Load Lbs. Wt./100
1/2 3/8 25/8 111/16 5/8 150 27
3/4 3/8 25/8 111/16 5/8 250 29
1 3/8 27/8 113/16 3/4 250 32
11/4 3/8 3 17/8 13/16 250 34
11/2 3/8 35/8 25/16 11/16 250 36
2 3/8 41/2 3 15/8 250 44
21/2 1/2 6 31/4 21/8 350 96
3 1/2 61/8 37/8 2 350 105
31/2 1/2 65/8 41/4 113/16 350 110
4 1/2 71/16 43/8 19/16 400 151
5 1/2 81/2 55/16 17/8 550 220
6 5/8 93/4 59/16 111/16 550 265

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 69
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 82 - Copper Tubing Riser Clamp


Fig. 82PVC - PVC Coated Copper Tubing Riser Clamp

Size Range — Size1/2" thru 6" copper tubing


Material — Carbon Steel
Function — Used for supporting vertical copper tubing.
Approvals — Conforms to Federal Specification A
WW-H-171E, Type 8 and Manufacturers Standardization Society SP-
69 Type 8.
Finish — Copper plated
Note — Available with plastic coating, specify by ordering Fig. 82PVC
Order By — Figure number and nominal tubing size

Fig. 82

Fig. 82PVC

Dimensions • Weights
Copper Tube Max. Rec. Approx.
Size A Bolt Size Load Lbs. Wt./100
1/2 61/2 3/8 75 68
3/4 91/4 3/8 75 69
1 93/8 3/8 120 95
11/4 95/8 3/8 150 101
11/2 10 3/8 150 152
2 10 3/8 150 164
21/2 11 3/8 300 172
3 111/2 3/8 300 184
31/2 12 3/8 300 196
4 13 3/8 300 247
5 14 1/2 400 258
6 15 1/2 500 405

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
70 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 83 - Isolator for Copper Tubing


Fig. 84 - I.P.S. Isolator
Size Range — Fig. 83 - 3/8" thru 7" copper tubing;
Fig. 84 - 3/8" thru 8" pipe
Material — Pre-Galvanized steel and felt
Function — A non-conductive felt lining serves to prevent electrolysis, dampen
sound vibration and prevent transmission of sound to the
building structure.
Finish — Pre-Galvanized
Standard Steel Pipe Hangers for use with Isolators: Fig. 1 Clevis Hanger,
Fig. 2 Band Hanger, Fig. 3 J-Hanger and TOL-Strut™ Rigid or O.D. Pipe
Clamps
Order By — Figure number and nominal tube size

Fig. 83
Dimensions • Weights

Copper Tube Hanger TOL-Strut™ Approx.


Size A B C Size Clamp Size Wt./100
3/8 1 11/4 21/4 3/4 11/8 O.D. 4
1/2 11/8 11/4 21/4 3/4 11/8 O.D. 4
3/4 13/8 11/4 21/4 1 1 RIGD 4
1 15/8 11/4 21/4 11/4 11/2 O.D. 6
11/4 17/8 11/4 21/4 11/2 13/4 O.D. 1
11/2 21/8 11/4 21/4 2 21/8 O.D. 10
2 25/8 11/4 21/4 21/2 25/8 O.D. 12
21/2 31/8 11/4 21/4 3 31/8 O.D. 13
3 35/8 11/4 21/4 3 3 RIGD 15
31/2 41/8 11/4 21/4 31/2 31/2 RIGD 28
4 51/8 11/4 21/4 5 5 O.D. 44

Fig. 84
Dimensions • Weights

Pipe Hanger TOL-Strut™ Approx.


Size A B C Size Clamp Size Wt./100
3/8 11/8 11/4 21/4 1 1 RIGD 4
1/2 13/8 11/4 21/4 1 1 RIGD 4
3/4 11/2 11/4 21/4 11/4 11/4 O.D. 6
1 113/16 11/4 21/4 11/2 11/2 O.D. 10
11/4 21/8 11/4 21/4 2 2 O.D. 10
11/2 23/8 11/4 21/4 2 2 RIGD 12
2 27/8 11/4 21/4 21/2 21/2 RIGD 14
21/2 33/8 11/4 3 3 3 O.D. 20
3 4 11/4 3 31/2 31/2 RIGD 25
31/2 41/2 11/4 3 4 4 RIGD 36
4 51/2 11/4 31/2 5 5 RIGD 65
5 61/2 11/4 4 6 6 RIGD 67
6 75/8 21/8 51/2 8 75/8 O.D. 196
8 95/8 21/8 51/2 10 95/8 O.D. 210

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 71
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 98 - Rod Stiffener


Size Range — Secures 3/8" thru 7/8" hanger rod
Material — Carbon Steel
Function — Secures channel to hanger rod for vertical seismic bracing.
Finish — Electro Galvanized
Note — Available in HDG finish or Stainless Steel materials.
Order By — Figure number

Fig. 99 - All Thread Rod Cut to Length


Size Range — Secures 3/8" thru 7/8" rod in Dimensions • Weights
1" increments Rod Max. Rec. Load Lbs.
Material — Carbon Steel Size For Service Temps
650°F 750°F
Maximum Temperature — 750°F
3/8 610 540
Finish — Plain 1/2 1130 1010
Note — Available in Electro-Galvanized and 5/8 1810 1610
HDG finish or Stainless Steel materials. 3/4 2710 2420
7/8 3770 3360
Order By — Figure number, rod diameter, rod
length and finish

Fig. 100 - All Thread Rod Full Lengths


Size Range — Secures 3/8" thru 7/8" rod in
10’ lengths
Material — Carbon Steel
Maximum Temperature — 750°F
Finish — Plain
Note — Available in Electro-Galvanized and
HDG finish or Stainless Steel materials.
Order By — Figure number, rod diameter
and finish

Dimensions • Weights
Max Rec. Load Lbs.
Rod For Service Temps Approx.
Size 650°F 750°F Wt./100
1/4 240 215 12
3/8 610 540 29
1/2 1130 1010 53
5/8 1810 1610 84
3/4 2710 2420 123
7/8 3770 3360 169
1 4960 4420 222
11/4 8000 7140 360
11/2 11630 10370 510

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
72 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 101 - Welded Eye Rod


Size Range — 3/8" thru 21/2" rod
Material — Carbon Steel
Function — Designed for use as support hanger rod that may be attached directly to
structure or to other pipe support product. The welded eye allows for heavier loads.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or Stainless Steel materials.
Order By — Figure number, rod size, length and finish
Important Note — “A” dimension should be 1/16" larger than fastener. Please notify
factory if larger “A” dimension is needed.
A
Dimensions • Weights
Rod Max. Rec. Load Lbs. for Service Temps.
Size A B 650°F 750°F
3/8 7/16 21/2 610 540
1/2 9/16 21/2 1130 1010 B
5/8 13/16 21/2 1810 1610
3/4 1 3 2710 2420
7/8 11/8 31/2 3770 3360
1 11/4 4 4960 4420
11/4 11/2 5 8000 7140
11/2 2 6 11630 10370
13/4 21/4 7 15700 14000 LENGTH
2 21/2 8 20700 18460
21/4 23/4 9 27200 24260
21/2 3 10 33500 29800

Fig. 102 - Eye Rod


Size Range — 3/8" thru 21/2" rod
Material — Carbon Steel
Function — Designed for use as support hanger rod that may be attached directly to
structure or to other pipe support product.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or Stainless Steel materials.
Order By — Figure number, rod size, length and finish
Important Note — “A” dimension should be 1/16" larger than fastener. Please notify
factory if larger “A” dimension is needed.
A
Dimensions • Weights
Rod Max. Rec. Load Lbs. for Service Temps.
Size A B 650°F
3/8 7/16 21/2 210
1/2 9/16 21/2 395 B
5/8 13/16 21/2 630
3/4 1 3 945
7/8 11/8 31/2 1315
1 11/4 4 1735
11/4 11/2 5 2800
LENGTH
11/2 2 6 4070
13/4 21/4 7 5490
2 21/2 8 7240
21/4 23/4 9 9520
21/2 3 10 11725

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 73
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 101L - Linked Welded Eye Rod


Size Range — 3/8" thru 21/2" rod
Material — Carbon Steel
Function — Designed for use in a hanger assembly where
universal movement is necessary. The welded eye rods allow
for heavier loads.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, rod size, dimension A, B, and C.

Dimensions • Weights
Max. Rec. Load Lbs.
Rod for Service Temps.
Size D 650°F
3/8 21/2 610
1/2 21/2 1130
5/8 21/2 1810
3/4 3 2710
7/8 31/2 3770
1 4 4960
11/4 5 8000
11/2 6 11630

Fig. 102L - Linked Eye Rod Not Welded


Size Range — 3/8" thru 21/2" rod
Material — Carbon Steel
Function — Designed for use in a hanger assembly where
universal movement is necessary.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.

Dimensions • Weights
Max. Rec. Load Lbs.
Rod for Service Temps.
Size D 650°F
3/8 21/2 240
1/2 21/2 440
5/8 21/2 705
3/4 3 1050
7/8 31/2 1470
1 4 1940
11/4 5 3120
11/2 6 4650

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
74 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 103 - Hanger Rod Threaded Both Ends


Size Range — 3/8" thru 21/2" rod
Material — Carbon Steel
Function — Recommended for use as a hanger support in
hanger assemblies. Rod is threaded on both ends with right
hand threads of the length shown. Also available with left
and right hand threads. Specify Fig. 103L when ordering.
Maximum Temperature — 750°F
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, rod size, length and finish
Dimensions • Weights
Standard Max. Rec. Load Lbs.
Rod Size Length for Service Temps.
A Thread 650°F 750°F
3/8 21/2 610 540
1/2 21/2 1130 1010
5/8 21/2 1810 1610
3/4 3 2710 2420
7/8 31/2 3770 3360
1 4 4960 4420
11/4 5 8000 7140
11/2 6 11630 10370

Fig. 104 - “J” Bolt


Size Range — 3/8" thru 3/4" rod
Material — Carbon Steel
Function — Designed to be hooked or hung from beam
flange or purlin.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, rod size, length and finish

Dimensions • Weights
Rod Size Radius Max. Rec.
A B C Load Lbs.
3/8 1/2 21/2 240
1/2 5/8 21/2 440
5/8 3/4 21/2 705
3/4 7/8 21/2 1050

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 75
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 105 - Coach Screw Hanger Rod


Size Range — 3/8" thru 1/2" rod
Material — Carbon Steel
Function — Typically used to suspend pipe from wood joists.
Machine threaded on one end and lag threaded on the other
end. It is recommended that pilot holes be pre-drilled to pre-
vent beam from splitting and to aid in starting lag threads.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, rod size, length and finish
Dimensions • Weights
Machine
Rod Size Rod Thread Lag
A Length Length Length
3/8 3 1/2 21/2
3/8 or 1/2 4 11/2 21/2
3/8 5 21/2 21/2
3/8 or 1/2 6 21/2 21/2
3/8 7 21/2 21/2
3/8 or 1/2 8 21/2 21/2
3/8 9 21/2 21/2
3/8 10 21/2 21/2
3/8 11 21/2 21/2
3/8 12 21/2 21/2

Fig. 106 - Tie Bolt


Material — Carbon Steel
Function — Recommended for securing the
connection of steel pipe to ductile pipe by
attaching tie bolts to pipe flanges then
connect tie rods. May be used in vertical or
horizontal applications.
Approvals — Conforms to NFPA Pamphlet
24, Installation of Private Fire Service
Maintenance 4" - 12" pipe size.
Finish — Plain
Note — Available in Electro-Galvanized and
HDG finish or Stainless Steel materials.
Order By — Figure number, size and finish.
Custom lengths for thicker flange available.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
76 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 107 - Anchor Bolt


Size Range — 3/8" thru 1/2" rod
Material — Carbon Steel
Function — Embedded in concrete for fastening of pipe
support, structural steel or other apparatus to surface .
Maximum Temperature — 750°F
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, rod size, length and finish

Dimensions • Weights
Rod
Size A B
3/8 2 21/2
1/2 2 21/2
5/8 21/2 21/2
3/4 23/4 21/2
7/8 3 21/2
1 31/2 3
11/8 4 31/2
11/4 41/2 4
11/2 51/4 4

Fig. 108 - L-Rod Thread Both Ends


Size Range — 3/8" thru 7/8" rod
Material — Carbon Steel
Function — Recommended for bolting through structure
with short end, using long end as Hanger Rod.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, rod size, length, width of bend
and finish

Dimensions • Weights
Rod Thread Length
Size Length Short End Long End
3/8 - 7/8 4" - 8" 11/2 11/2
3/8 - 7/8 8" and up 11/2 21/2

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 77
www.tolco.com

www.tolco.com
a brand of
®
Revision 10/24/2001

Fig. 107F - Concrete Insert


Size Range — 5/8" thru 11/2" rod
Material — Carbon Steel
Function — Designed to be embedded in concrete to provide
a point of support for 5/8" thru 11/2" rod or bolt sizes .
Finish — Plain anchor bolt with Electro-Galvanized coupling.
Note — For rod sizes 3/8" and 1/2", refer to Fig. 109F.
Available in Electro-Galvanized and HDG finish.
Order By — Figure number and rod size

Dimensions • Weights
Rod B Max. Rec. Load Lbs.
A Min. Embed. (In 3000 lb. Hard Rock Concrete)
Size
5/8 3 31/2 1810
3/4 3 31/2 2710
7/8 3 4 3770
1 3 4 4960
Consult factory for specifications on rod sizes 11/8", 11/4" and 11/2".

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
78 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 109 - Concrete Deck Insert


Component of State of
California OSHPD Approved
Seismic Restraints System

Size Range — 3/8" thru 7/8" rod


Material — Carbon Steel
Function — For use in metal deck formed concrete to attach hanger
rods. Allows for pre-positioning of hanger rods in poured concrete decks.
Fig. 109 is approved for seismic brace attachments.
Approvals — Included in our Seismic Restraints Catalog approved by the
State of California Office of Statewide Health Planning and Development
(OSHPD). For additional load, spacing and placement information relating
to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems
Guidelines.
Finish — Plate: Plain Steel. Rod: Electro-Galvanized
Note — Available in HDG finish or Stainless Steel materials.
Order By — Figure number, rod size and finish. Custom rod lengths are
available. Consult factory.

Design Load Chart for 3000 PSI Hard Rock Concrete Design Load Chart for Light Weight Concrete
Dimensions • Weights Dimensions • Weights
Design Load Design Load Design Load Design Load Design Load Design Load
Vertical Shear 45° Vertical Shear 45°
Rod De De Rod De De
Size A B C (in.)
A B C (in.)
A B C Size A B C (in.)
A B C (in.)
A B C
3/8 1207 457 457 1 675 675 675 2 612 364 385 3/8 905 343 343 7/8 590 590 590 2 547 307 321
1/2 2043 496 496 1.4 912 912 912 2 892 454 454 1/2 1632 372 372 7/8 590 590 590 2 828 323 374
5/8 1690 532 532 1.7 1148 1148 1148 2 967 514 514 5/8 1268 399 399 7/8 590 590 590 2 852 337 419
3/4 2321 567 567 2 1368 1368 1368 2.5 1217 597 567 3/4 1741 426 426 7/8 590 590 590 21/2 1084 350 459
7/8 2321 878 878 4 1596 1596 1596 3 1338 801 801 7/8 1741 656 656 7/8 590 590 590 3 1178 439 654

Note — To hold maximum design load the plate must be installed on top of deck ribs with anchor rod extending
through bottom flute as shown in detail “A”. Inserts can be positioned anywhere on the lower surfaces of metal deck
as shown in details “B” and “C”. Mounting holes are standard. If the plate is not mechanically secured to the deck
ribs, a jamb nut is required to prevent the anchor bolt from laying over when concrete is poured. Design load
vertical values are for vertical support applications only. Use Design Load 45° and Design Load Shear values for
attachment of seismic bracing. Seismic brace attachments must be securely tight to the underside of concrete deck.
Structural Engineer shall verify adequacy of concrete or metal deck for the tabulated allowable loads. Minimum edge
distance: 6 bolt diameters. Minimum distance between inserts: 12 bolt diameters.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 79
www.tolco.com

www.tolco.com
a brand of
®
Revision 8/13/2001

Fig. 109F - Concrete Insert


Component of State of
California OSHPD Approved
Seismic Restraints System

Size Range — 3/8" thru 7/8" rod


Material — Carbon Steel
Function — Designed to be embedded in concrete to provide a point of
support.
Approvals — Underwriters’ Laboratories listed in the USA (UL) and
Canada (cUL) for 3/8" and 1/2". Included in our Seismic Restraints
Catalog approved by the State of California Office of Statewide Health
Planning and Development (OSHPD). For additional load, spacing and
placement information relating to OSHPD projects, please refer to the
TOLCO Seismic Restraint Systems Guidelines.
Finish — Plain anchor bolt with Electro-Galvanized hardware and plate.
Note — For rod sizes 5/8" - 11/2" refer to Fig. 107F. Available in Stainless
Steel or HDG finish on request.
Order By — Figure number, rod size and finish.
Note — The Hex or Jam Nut has NO value in determining the loads. Their
function is to assist in locking the Coupling snug to the bottom of the deck
form preventing the concrete from leaking into the coupling threads. Any
other suitable locking device may be substituted if desired.

Dimensions • Weights

Rod Design Load Vertical Design Load Shear Design Load 45° “E” Embedment De
Size Hard Rock Lt. Wt. Hard Rock Lt. Wt. Hard Rock Lt. Wt. Depth min. (in.)
3/8 1255 735 978 733 777 525 31/2 2
1/2 2321 1392 978 733 980 679 31/2 2
5/8 780 468 1278 958 688 445 4 2
3/4 1346 806 1278 958 927 619 4 21/2
7/8 2321 1392 1278 958 1166 803 4 6

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
80 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 110 - Standard U-Bolt with 4 Hex Nuts


Size Range — Size1/2" thru 36" pipe
Material — Carbon Steel
Function — Recommended for support, anchor or guide of pipe.
Approvals — Conforms to Federal Specification WW-H-171E,
Type 24 and Manufacturers Standardization Society SP-69 Type
24.
Maximum Temperature — 750°F
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, rod size and pipe size. U-bolt can be
furnished with longer tangents “D” or with longer threads “E”.
Consult factory.
Note — When furnished with hot-dip galvanized, oversize hex nuts
must be used.

Dimensions • Weights
Max. Rec. Load Lbs.
Rod Pipe for Service Temps. Approx.
Size A Size B C D E F 650°F 750°F Wt./100
1/4 1/2 15/16 13/16 23/4 21/8 25/16 485 435 11
1/4 3/4 11/8 13/8 23/4 21/8 27/32 485 435 12
1/4 1 13/8 15/8 23/4 21/8 23/32 485 738 12
3/8 11/4 111/16 21/16 27/8 21/8 21/32 1220 1090 28
3/8 11/2 2 23/8 3 21/2 21/16 1200 1090 30
3/8 2 27/16 213/16 31/4 21/2 21/16 1220 1090 33
1/2 21/2 215/16 37/16 33/4 3 25/16 2260 2020 85
1/2 3 39/16 41/16 4 3 21/4 2260 2020 93
1/2 31/2 41/16 49/16 41/4 3 21/4 2260 2020 101
1/2 4 49/16 51/16 41/2 3 21/4 2260 2020 110
1/2 5 55/8 61/8 5 3 27/32 2260 2020 124
5/8 6 63/4 73/8 61/8 33/4 213/16 3620 3230 200
5/8 8 83/4 93/8 71/8 33/4 213/16 3620 3230 230
3/4 10 107/8 115/8 83/8 4 3 5420 4830 486
7/8 12 127/8 133/4 95/8 41/4 31/4 7540 6730 790
7/8 14 141/8 15 101/4 41/4 31/4 7540 6730 850
7/8 16 161/8 17 111/4 41/4 31/4 7540 6730 935
1 18 181/8 191/8 125/8 43/4 35/8 9920 8850 1360
1 20 201/8 211/8 135/8 43/4 35/8 9920 8850 1476
1 24 241/8 251/8 155/8 43/4 35/8 9920 8850 1698
1 30 301/8 311/8 185/8 43/4 35/8 9920 8850 2027
1 36 361/8 371/8 215/8 43/4 35/8 9920 8850

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 81
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 111 - Light Weight U-Bolt with 2 Hex Nuts


Size Range — Size 1/2" thru 10" pipe
Material — Carbon Steel
Function — Recommended for supporting or anchoring light
pipe loads.
Maximum Temperature — 650°F
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, pipe size and finish
Note — When furnished in hot-dip galvanized finish, oversize
tapped hex nuts must be used.

Dimensions • Weights
Rod Pipe Max. Design Approx.
Size A Size B C D E Load Lbs. Wt./100
1/4 1/2 15/16 13/16 115/16 13/4 485 8
1/4 3/4 11/8 13/8 21/16 13/4 485 8
1/4 1 13/8 15/8 23/16 13/4 485 9
1/4 11/4 111/16 115/16 23/8 13/4 485 9
1/4 11/2 2 21/4 27/16 13/4 485 10
1/4 2 27/16 211/16 211/16 13/4 485 11
3/8 21/2 215/16 35/16 31/16 2 1220 31
3/8 3 39/16 315/16 33/8 2 1220 33
3/8 31/2 41/16 47/16 35/8 2 1220 40
3/8 4 49/16 415/16 37/8 2 1220 40
3/8 5 55/8 6 49/16 21/4 1220 47
1/2 6 63/4 71/4 51/16 21/4 2260 125
1/2 8 83/4 91/4 61/16 21/4 2260 156
5/8 10 107/8 111/2 71/4 21/2 3620 318

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
82 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 113 - Standard Hex Nut Fig. 114 - Heavy Hex Nut
Size Range — Size1/4" thru 1 /2" 1
Size Range — Size1/4" thru 11/2"
Material — Carbon Steel Material — Carbon Steel
Finish — Plain Finish — Plain
Note — Available in Electro-Galvanized and HDG Note — Available in Electro-Galvanized and HDG finish
finish or Stainless Steel materials. or Stainless Steel materials.
Order By — Figure number size and finish

Dimensions • Weights Dimensions • Weights


Width Width Width Width
Rod Rod Across Across Approx.
Across Across Approx.
Size Thickness Size Flats Points Thickness Wt./100
Flats Points Wt./100
1/4 7/16 1/2 7/32 .7 1/4 1/2 37/64 15/64 1.2
5/16 1/2 37/64 17/64 1.1 5/16 9/16 21/32 19/64 1.7
3/8 9/16 21/32 21/64 1.6 3/8 11/16 51/64 23/64 3.1
1/2 3/4 55/64 7/16 3.7 1/2 7/8 11/6 31/64 6.5
5/8 15/16 13/32 35/64 7.3 5/8 11/16 115/64 39/64 12.0
3/4 11/8 15/16 41/64 12.0 3/4 11/4 129/64 47/64 19.0
7/8 15/16 133/64 3/4 19.0 7/8 17/16 121/32 55/64 30.0
1 11/2 13/4 55/64 28.0 1 15/8 17/8 63/64 43.0
11/4 17/8 211/64 11/16 54.0 11/4 2 25/16 17/32 79.0
11/2 21/4 219/32 19/32 94.0 11/2 23/8 23/4 115/32 131.0

Fig. 115 - Flat Washer Fig. 117 - Lock Washer


Size Range — Size1/4" thru 11/2" Size Range — Size1/4" thru 3/4" bolt
Material — Carbon Steel Material — Carbon Steel
Finish — Plain Finish — Plain
Note — Available in Electro-Galvanized and HDG Note — Available in Electro-Galvanized and HDG
finish or Stainless Steel materials. finish or Stainless Steel materials.
Order By — Figure number size and finish Order By — Figure number size and finish

Dimensions • Weights Dimensions • Weights


Rod Size Outside Diameter Approx. Wt./100 Rod Size Outside Diameter Approx. Wt./100
1/4 3/4 .7 3/8 11/16 .6
5/16 1 1.5 1/2 7/8 1.3
3/8 13/8 3.9 5/8 11/16 2.4
1/2 13/4 7.7 3/4 11/4 4.0
5/8 15/16 7.3
3/4 2 11.0
7/8 21/4 19.0
1 23/4 22.0
11/4 3 26.0
11/2 31/2 39.0

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 83
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 116 - Bevel Washer


Size Range — Size1/4" thru 7/8" bolt Dimensions • Weights
Material — Malleable Iron
Rod Approx.
Function — Designed to match taper of Size A B C Wt./100
flange of I-beam or channel to permit right
3/8 11/4 11/32 5/32 9
angle fastening of bolt.
1/2 11/4 11/32 5/32 9
Finish — Plain 5/8 11/2 13/32 5/32 14
Note — Available in Electro-Galvanized 3/4 11/2 15/32 7/32 16
and HDG finish or Stainless Steel 7/8 2 9/16 7/32 33
materials.
Order By — Figure number size and finish

Fig. 118 - Square Washer


Size Range — Size1/4" thru 1" bolt Dimensions • Weights
Material — Malleable Iron
Rod Hole Approx.
Function — Heavy duty washer for use on Size Size A B Wt./100
top of channels or angles to support hang-
3/8 7/16 2 1/4 27
er rod.
1/2 9/16 2 1/4 27
Finish — Plain 5/8 11/16 21/2 1/4 47
Note — Available in Electro-Galvanized 3/4 13/16 3 3/8 85
and HDG finish or Stainless Steel 1 11/8 4 3/8 160
materials.
Order By — Figure number size and finish

Fig. 119 - Fender or Oversize Washer


Size Range — Size1/4" thru 1/2" bolt Dimensions • Weights
Material — Carbon Steel
Rod Inside Outside Approx.
Function — To provide a greater bearing Size Diameter Diameter Wt./100
surface than standard washer.
1/4 5/16 11/8 3.3
Finish — Plain 3/8 1/2 11/8 3.0
Note — Available in Electro-Galvanized and 1/2 9/16 2 2.8
HDG finish or Stainless Steel materials.
Order By — Figure number and size

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
84 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 120 - “U” Hanger


Size Range — Size 3/4" thru 8" pipe
Material — Carbon Steel
Function — Used to support piping from wood beams where no
contraction is expected. Used extensively in automatic fire sprin-
kler systems.
Approvals — Meets or exceeds the requirements of National Fire
Protection Association (NFPA), Pamphlet 13.
Maximum Temperature — 750°F
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, pipe size, length and finish

Dimensions • Weights
Pipe Fastener Max Rec.
Size A Size Load Lbs.***
3/4 5/16 16 x 2* 250
1 5/16 16 x 2* 250
11/4 5/16 16 x 2* 250
11/2 5/16 16 x 2* 250
2 5/16 16 x 2* 250
21/2 3/8 3/8 x 21/2** 320
3 3/8 3/8 x 21/2** 320
31/2 3/8 3/8 x 21/2** 560
4 3/8 1/2 x 3** 560
5 1/2 1/2 x 3** 560
6 1/2 1/2 x 3** 760
8 1/2 5/8 X 3**
* Drive screw
** Lag bolt
*** With minimum safety factor of 5
Fastener schedule per NFPA

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 85
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 120MJ - Mutt & Jeff “U” Hanger


Size Range — Size 3/4" thru 8" pipe
Material — Carbon Steel
Function — Used to support piping from wood beams where no
contraction is expected. Used extensively in automatic fire sprinkler
systems. The Mutt & Jeff is used when the wood beam is on a
diagonal.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or Stainless
Steel materials.
Order By — Figure number, pipe size, side length and finish

Fig. 120W - Wrap Around “U” Hanger


Size Range — Size 3/4" thru 2" pipe
Material — Carbon Steel
Function — Required for automatic fire protection agencies
to be used on the end of branch lines to prevent pipe from whipping
vertical and striking ceiling or beam
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or Stainless
Steel materials.
Order By — Figure number, pipe size, length and finish

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
86 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 120RWA (Models A&B)


Retrofit Wrap Around U-Hanger Clamp
Component of State of
California OSHPD Approved
Seismic Restraints System

Size Range — Model A 1" thru 2" pipe


Model B 1" thru 8" pipe
Material — Carbon Steel
Function — Clamp Models “A” and “B” are designed to restrain
movement of the pipe within standard U-hangers as is required
by NFPA 13. Where retrofit capability is crucial, the Fig.
120RWA is a labor efficient alternative to the standard
TOLCO™ Fig. 120W Wrap Around U-Hanger.
Features — Model “A” is installed fast and easily by hand. No
tools are necessary. Model “B” installs easily by tightening two
hex nuts. Both Models feature a unique bracing slot that locks
onto a standard U-hanger to become a solid unit that will stabi-
lize the pipe during seismic activity or sprinkler head activation.
Models “A” and “B” are designed to be used in retrofit or new
construction applications. Both Models will clamp to existing
U-Hangers without restriction to leg angle
Approvals — Underwriters’ Laboratories listed in the USA (UL) Model A
and Canada (cUL). Included in our Seismic Restraints Catalog
approved by the State of California Office of Statewide Health
Planning and Development (OSHPD). For additional load,
spacing and placement information relating to OSHPD projects,
please refer to the TOLCO Seismic Restraint Systems
Guidelines. NFPA 13 (1999) A-6-2.3.3.
Finish — Model “A”, Galvanized. Model “B”, Plain and
Galvanized. Consult factory for Stainless Steel material.
Order By — Figure number, model, type numbers and pipe
size
Ordering Note — Order Model “A” by pipe size (1" thru 2").
Order Model “B” by the following type and pipe size:
Type 1 — (1" and 11/4" pipe size)
Type 2 — (11/2" and 2" pipe size)
Type 3 — (21/2" and 3" pipe size)
Type 4 — (4" pipe size)
Type 6 — (5" and 6" pipe size)
Type 8 — (8" pipe size)
Important Note — The bracing slot feature is sized to fit the U-
Hanger rod schedule as required by NFPA 13 as follows:
Model B
5/16" rod for up to 2" pipe
3/8" rod for 21/2" - 6" pipe
1/2" rod for 8" pipe
For other rod size requirements consult factory.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 87
www.tolco.com

www.tolco.com
a brand of
®
Revision 3/31/2003

Fig. 122 - Wood Screw Flat Head Fig. 123 - Toggle Bolt

Material — Carbon Steel Material — Carbon Steel


Finish — Electro-Galvanized Finish — Electro-Galvanized
Order By — Figure number and size Order By — Figure number and size

Fig. 124 - Spring Toggle Head Only Fig. 125 - Drive Screw

Material — Carbon Steel


Function — Used with threaded rod in hollow walls Material — Carbon Steel
Finish — Electro-Galvanized Function — Equivalent to a nail, but has greater
holding power
Order By — Figure number and size
Finish — Plain and Electro-Galvanized
Dimensions • Weights Order By — Figure number, size and finish
Approx.
Size Drill Hole Size Wt./100
Dimensions • Weights
1/4 5/8 3
3/8 7/8 7 Approx.
5/8 11/4 10 Size Length Wt./100
16 2 2.2

Fig. 126 - Lag Bolt Gimlet Point


Material — Carbon Steel
Function — Designed to fasten metal to wood. Lag screws are made with hex heads in lengths of
6" or shorter and square heads in lengths longer than 6". Both types have coarse lag threads and
gimlet points and are available in diameters of 1/4" to 5/8" inclusive. Square-head lag screws are
also available in 3/4", 7/8" and 1" diameters.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish.
Order By — Figure number, bolt size, length and finish
Dimensions • Weights Dimensions • Weights
Approx. Wt./100 Hex Lag Bolt Head Dimensions
Lag Bolt 1" 11/8" 2" 21/8" 3" 4" Lag Bolt Width Across Width Across Head
Screw Size Length Length Length Length Length Length Screw Size Flats Points Thickness
1/4 1.5 2.1 2.7 3.2 3.8 4.9 1/4 7/16 1/2 11/64
3/8 4.0 5.3 6.6 7.8 9.1 11.6 3/8 9/16 21/32 1/4
1/2 11.0 13.3 15.5 17.8 22.3 1/2 3/4 7/8 11/32
5/8 23.2 26.8 30.4 37.6 5/8 15/16 13/32 27/64

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
88 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 1/13/2004

Fig. 130 - Beam Clamp with Bolt and Nut


Size Range — Fig. 130-1 = TJI 35
Fig. 130-2 = —
Fig. 130-3 = TJI 25
Fig. 130-4 = TJI 55 & 65
Fig. 130-5 = TJI 75
Fig. 130-6 = TJI 96
Material — Carbon Steel
Function — Effective and economical method of hanging from
“Trus Joist” type beams. Use with Fig. 102 Eye Rod.
Approvals — Sizes 1, 2, 3 and 4 Underwriters’ Laboratories
listed in the USA (UL) and Canada (cUL) listed through 4" pipe.
All Fig. 130 Beam Clamps meet requirements of Factory Mutual
Engineering and NFPA 13, through 4" pipe.
Finish — Electro-Galvanized
Note — Available in HDG finish or Stainless Steel materials.
Order By — Figure number with dash designation and finish or
by H&W of beam and finish.

Dimensions • Weights
Size Beam Dimensions Approx.
130- A H W Wt./100
1 31/4 11/2 25/16 65
2 31/2 13/4 21/2 70
3 31/4 11/2 13/4 58
4 31/2 11/2 31/2 83
5† 35/8 13/4 31/2 86
6† 41/2 21/2 37/8 101
* Max. Rec. Load 500 lbs.
**Safety Factor of 5
† Larger bolts and I-rods are required for 5" and 6" pipe sizes

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 89
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 200 - “Trimline” Adjustable Band Hanger


Size Range — 1/2" thru 8" pipe
Material — Carbon Steel, Mil. Galvanized to G90
specifications
Function — For fire sprinkler and other general piping
purposes. Knurled swivel nut design permits hanger
adjustment after installation.
Features —
• (1/2" thru 2") Flared edges ease installation for
all pipe types and protect CPVC plastic pipe from
abrasion. Captured design keeps adjusting nut
from separating with hanger. Hanger is easily
installed around pipe.
• (21/2" thru 8" Spring tension on nut holds it
securely in hanger before installation. Adjusting
nut is easily removed.
Approvals — Underwriters’ Laboratories listed (1/2"
thru 8") in the USA (UL) and Canada (cUL) for steel
and CPVC plastic pipe and Factory Mutual Engineering
Approved (3/4" thru 8"). Conforms to Federal
Specifications WW-H-171E, Type 10 and Manufacturers
Standardization Society SP-69, Type 10.
Maximum Temperature — 650°F
Finish — Mil. Galvanized. For Stainless Steel materi-
als, order TOLCO™ Fig. 200WON.
Order By — Figure number and pipe size

Dimensions • Weights
Pipe Rod Size Max. Rec. Approx.
Size Inch Metric A B Load Lbs. Length
1/2 3/8 8mm or 10mm 31/8 25/8 400 11
3/4 3/8 8mm or 10mm 31/8 21/2 400 11
1 3/8 8mm or 10mm 33/8 25/8 400 12
11/4 3/8 8mm or 10mm 33/4 27/8 400 13
11/2 3/8 8mm or 10mm 37/8 27/8 400 14
2 3/8 8mm or 10mm 41/2 3 400 15
21/2 3/8 10mm 55/8 41/8 600 27
3 3/8 10mm 57/8 4 600 29
31/2 3/8 10mm 73/8 51/4 600 34
4 3/8 10mm 73/8 5 1000 35
5 1/2 12mm 91/8 61/4 1250 66
6 1/2 12mm 101/8 63/4 1250 73
8 1/2 12mm 131/8 83/4 1250 136

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
90 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 200H - Heavy Duty Band Hanger (for Trapeze)


Size Range — 1/2" thru 4" trapeze pipe size.
Used to support up to 8" pipe.
Material — Carbon Steel — Pre-Galvanized to
G40 Spec
Function —Designed primarily to support sub-
stantially heavier loads than is normally intend-
ed for the nominal hanger size. Used exten-
sively to support trapeze installations and the
increased loads from both above and below
the trapeze assembly.
Features — Furnished with 3/8" or 1/2" adjust-
ing threaded ring nut.
Approvals — Underwriters’ Laboratories listed
in the USA (UL) and Canada (cUL). Conforms
to Federal Specification WW-H-171E, Type 10
and Manufacturers Standardization Society
SP-69, Type 10.
Maximum Temperature — 650°F
Finish — Pre-Galvanized
Order By — Figure number, pipe size and rod
size.
Important Design Note — Because of the
increased loads applied to the trapeze assem-
bly, both the upper trapeze supports as well as
the lower hanging unit must be able to hold the
maximum loads intended.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 91
www.tolco.com

www.tolco.com
a brand of
®
Revision 11/30/2001

Fig. 200WON - “Trimline” Adjustable Band Hanger w/o Swivel Nut


Size Range — 1/2" thru 8" pipe
Material — Carbon Steel
Function — Recommended for the suspension of fire
sprinkler and non-insulated pipe or insulated pipe with
Fig. 220 shield. Generally installed with two hex nuts.
Features — Flared edges on sizes 1/2" thru 2". Eases
installation and protects CPVC pipe from any abrasion.
Approvals — Underwriters’ Laboratories listed
(1/2" thru 8") in the USA (UL) and Canada (cUL) for
steel and CPVC plastic pipe and Factory Mutual
Engineering approved. Conforms to Federal
Specifications WW-171E, Type 7 and Manufacturers
Standardization Society SP-69, Type 7
Maximum Temperature — 650°F
Finish — Mil. Galvanized to G-90
Note — Available in Stainless Steel materials
Order By — Figure number and pipe size

Dimensions • Weights
Pipe Rod Size Max. Rec. Approx.
Size A B C Load Lbs. Length
1/2 3/8 21/2 2 400 8
3/4 3/8 21/2 2 400 8
1 3/8 27/8 21/8 400 9
11/4 3/8 33/8 21/2 400 10
11/2 3/8 31/2 21/2 400 11
2 3/8 33/4 21/2 400 12
21/2 3/8 51/8 35/8 600 24
3 3/8 53/8 31/2 600 27
31/2 3/8 63/4 45/8 600 32
4 3/8 63/4 41/2 1000 33
5 1/2 83/8 51/2 1250 60
6 1/2 93/8 6 1250 68
8 1/2 123/8 8 1250 130

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
92 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 202 - Adjustable Copper Tubing Ring Hanger


Size Range — 1/2" thru 6" copper tubing
Material — Carbon Steel
Function — Recommended for the suspension of non-
insulated stationary copper tubing.
Approvals — Conforms to Federal Specification
WW-H-171E, Type 10, 1/2" thru 4", and Manufacturers
Standardization Society SP-69, Type 10
Finish — Copper-plated
Order By — Figure number and nominal tubing size

Dimensions • Weights
Pipe Rod Size Max. Rec. Approx.
Size Rod Size A B C Load Lbs. Wt./100
1/2 3/8 31/8 23/4 11/2 400 11
3/4 3/8 31/8 25/8 11/4 400 11
1 3/8 31/8 21/2 1 400 12
11/4 3/8 31/4 21/2 1 400 13
11/2 3/8 37/8 3 11/4 400 14
2 3/8 41/2 33/8 11/2 400 15
21/2 3/8* 51/2 43/8 2 600 40
3 1/2 63/8 43/4 2 600 45
31/2 1/2 63/8 41/2 11/2 600 52
4 1/2* 73/8 51/4 2 1250 59
5 5/8 83/8 53/4 2 1250 97
6 5/8 91/2 63/8 11/8 1250 139
* 21/2" CT filled with water weighs less than 2" IP filled with water, 4" CT less than
31/2" IP with water. 21/2" CT available with 1/2" thread and 4" CT available with
5/8" thread for Government Specs.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 93
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 203 - Adjustable PVC Coated Ring Hanger


Size Range — 1/2" thru 8" pipe
Material — Carbon Steel
Function — PVC coated for protection of glass, plastic
or stainless steel pipe.
Approvals — Conforms to Federal Specification
WW-H-171E, Type 10, 1/2" thru 8", and Manufacturers
Standardization Society SP-69, Type 10
Maximum Temperature — 275°F
Finish — Pre-Galvanized then PVC coated
Order By — Figure number and pipe size

Dimensions • Weights
Pipe Max. Rec. Approx.
Size Rod Size A B C Load Lbs. Wt./100
1/2 3/8 31/8 25/8 13/8 400 11
3/4 3/8 31/8 21/2 11/8 400 11
1 3/8 33/8 25/8 11/8 400 12
11/4 3/8 31/4 21/2 1 400 13
11/2 3/8 37/8 27/8 1 400 14
2 3/8 41/4 3 1 400 15
21/2 3/8 53/4 41/4 15/8 600 40
3 1/2 6 41/8 11/4 600 45
31/2 1/2 73/8 51/4 21/8 600 52
4 1/2 73/8 5 15/8 1250 59
5 5/8 9 61/8 21/4 1250 97
6 3/4 93/8 61/2 17/8 1250 139
8 7/8 131/8 83/4 31/4 1250 145

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
94 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 207 - Multi-Use Plate


Material — Carbon Steel
Function — Multi-use
Finish — Pre-Galvanized Dimensions • Weights
Order By — Figure number, square
Approx.
dimension, gauge material and hole size
Size Wt./100
Note — Other sizes and split plate types
12 x 12 x 20ga 150
available. Consult factory.
18 x 18 x 20ga 350

Fig. 209 - Wedge Anchor Dimensions • Weights


Rod Outside Approx.
Size Range — Size1/4" thru 1" machine thread Size Diameter Wt./100
Material — Carbon Steel or Stainless Steel 1/4 3/4 7
Finish — Electro-Galvanized 3/8 1 1.5
Order By — Figure number, diameter length and finish 1/2 13/8 3.9
5/8 13/4 7.7
3/4 2 11
7/8 21/4 15
1 21/2 19
11/8 23/4 22
11/4 3 26
11/2 31/2 39

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 95
www.tolco.com

www.tolco.com
®
Revision 5/24/2001
a brand of

Fig. 219 - Rib Shield

Size Range — 23/8" thru 14" O.D. of insulation


Material — Carbon Steel
Function — Designed to prevent damage to insulation
by hanger. Ribs keep shield centered on hanger.
Finish — Pre-Galvanized
Order By — Figure number and shield size

Dimensions • Weights
Shield Max. O.D. of Rib Hanger Approx.
Size Insulation Space Size Wt./100
1 23/8 2 2 44
2 25/8 2 21/2 48
3 27/8 2 21/2 52
4 31/2 2 3 63
5 4 2 31/2 71
6 41/2 2 4 81
7 5 2 5 90
8 55/8 2 6 101
9 6 2 6 106
10 65/8 2 6 120
11 75/8 2 8 204
12 85/8 2 8 229
13 95/8 2 10 220
14 103/4 2 10 286

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
96 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 220 - Insulation Protection Shield

Size Range — 23/8" thru 28" inside diameter


Material — Carbon Steel
Function — Recommended for outside of foam or fiber
glass insulation to preclude crushing of insulation with-
out breaking the vapor barrier. Actual foam or fiber-
glass insulation thickness vary, verify that the I.D. of the
selected shield is suitable for the required application.
Approvals — Conforms to Federal Specifications
WW-H-171E, Type 41 and Manufacturers
Standardization Society SP-69, Type 40
Finish — Mil. Galvanized
Order By — Figure number, shield size, gauge and
length. Data applicable to shield for thicker insulation
or larger pipe sizes is available upon request.

Dimensions • Weights
Shield Size
Inside Dia. (in.) Stock Shield Length Approx
A Size L Wt./100
2.38 18ga 12 69
2.88 18ga 12 84
3.50 18ga 12 99
4.00 18ga 12 114
4.50 18ga 12 129
5.00 18ga 12 142
5.56 18ga 12 160
6.64 16ga 12 190
7.65 16ga 12 268
8.64 16ga 12 305
7.65 16ga 18 403
8.64 16ga 18 457
9.64 16ga 18 510
10.76 16ga 18 563
11.76 14ga 24 1018
12.76 14ga 24 1108
14.00 14ga 24 1190
15.00 14ga 24 1276
16.00 14ga 24 1359
17.00 14ga 24 1450
18.00 12ga 24 2124
19.00 12ga 24 2241
20.00 12ga 24 2358
21.00 12ga 24 2475
22.00 12ga 24 2592
23.00 12ga 24 2709
24.00 12ga 24 2862
26.00 12ga 24 3060
27.00 12ga 24 3177
28.00 12ga 24 3303

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 97
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 244H, 244HR, 244C, 244CR


Pre-Insulated Hanger Inserts
Crush-Resistant Insulation for Pipe and Tubing at the Support Point
Size Range — 1/2" thru 8" pipe size
Material — Asbestos-free Hydrous Calcium Silicate, treated for water
resistance, encased in a 360° A-527 Galvanized Sheet Metal Jacket.
Minimum 100 PSI compressive strength.
Function — (Fig. 244H) use on all hot lines to 1200°F and DWC where
no vapor barrier is required
(Fig. 244HR) same as Fig. 244H except a double thick
-ness of sheet metal on lower half when used with rollers
or when hanger span exceeds ten feet.
(Fig. 244C) use for chilled water and refrigeration lines, or
wherever a vapor barrier is required.
(Fig. 244CR) same as Fig. 244C except a double thick
-ness of sheet metal on lower half when used with rollers
or when hanger span exceeds ten feet. (On Fig. 244C and
244CR insulshields the insulation extends 1" beyond the
sheet metal saddle.)
Order By — When ordering for steel nominal pipe size specify
244H — 2" x 1" — indicating 2" IPS with 1" insulation for hot pipe,
244HR — 2" x 1" for roller support or where hanger span exceeds
ten feet. When ordering for copper pipe of O.D. tubing specify
244C 21/8" x 2" — indicating 2" copper with 1" insulation for cold pipe.
244CR 21/8" x 1" for roller support or where hanger span exceeds
ten feet.

Insulation Length Specification


I.P.S.
Nominal 1" 11/2" 2" 21/2" 3" 4"
1/2" to 1 /2"
1
4 4 4 4 6 6
2" 6 6 6 6 6 6
21/2" to 6" 6 6 6 6 9 9
8" to 10" 9 9 9 9 9 9
12" to 18" 12 12 12 12 12 12

Sheet Metal Gauge


I.P.S.
Nominal 1" 11/2" 2" 21/2" 3" 4"
1/2" to 1 /2"
1
24 24 24 20 20 20
2" 20 20 20 20 20 20
21/2" to 5" 20 20 20 20 20 20
6" 20 20 20 18 18 18
8" to 18" 16 16 16 16 16 16

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
98 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 244H, 244HR, 244C, 244CR


Pre-Insulated Hanger Inserts

Insulation Thickness
1" 11/2" 2" 21/2"
Pipe
Size S D L S D L S D L S D L
1/2" 167 334 10 305 610 10 352 352 10 352 352 10
3/4" 192 385 13 339 440 13 440 440 13 440 440 13
1" 227 445 20 385 551 20 551 551 20 551 551 20
11/4" 227 554 29 449 695 29 662 695 29 695 695 29
11/2" 315 629 36 496 796 36 770 796 36 796 796 36
2" 379 757 50 571 1143 51 804 1492 51 1076 1492 51
21/2" 479 940 78 683 1365 78 935 1806 78 1227 1806 78
3" 598 1197 107 836 1671 107 1113 2199 107 1429 2199 107
4" 836 1671 163 1113 2225 163 1429 2827 163 1785 2827 163
5" 1131 2263 232 1408 2816 232 1809 3495 232 2296 3485 232
6" 1471 2943 314 1832 3665 314 2233 4163 314 3483 4163 314
8" — — — 2858 5715 501 3370 6741 501 3925 7851 501
10" — — — 3998 7995 745 4600 9201 745 5245 10132 745
12" — — — 3934 7868 1021 4449 8899 1021 4997 9993 1021
14" — — — 4583 9166 1215 5138 10276 1215 5725 11450 1215
16" — — — 5725 11450 1595 6344 12687 1595 6994 13987 1595
18" — — — 6994 13987 2022 7676 15351 2022 8389 16779 2022

3" 31/2" 4"


Pipe
Size S D L S D L S D L
1/2" 352 528 10 528 528 10 528 528 10
3/4" 660 660 13 660 660 13 660 660 13
1" 826 826 20 826 826 20 826 826 20
11/4" 1043 1043 29 1043 1043 29 1043 1043 29
11/2" 1194 1194 36 1194 1194 36 1194 1194 36
2" 1387 1482 51 1492 1492 51 1492 1492 51
21/2" 1039 2710 78 1286 2572 78 1560 2710 78
3" 1190 2380 107 1454 2908 107 1744 2399 107
4" 1454 2908 163 1744 3488 163 2060 4121 163
5" 1763 3526 232 2081 4162 232 2426 4851 232
6" 2739 5477 314 3109 6244 314 3675 6244 314
8" 4523 8129 501 5162 8129 501 5844 8129 501
10" 5933 10132 745 6662 10132 745 7434 10132 745
12" 5575 11151 1021 6186 12321 1021 6828 13656 1021
14" 6344 12687 1215 6994 13987 1215 7676 15351 1215
16" 7676 15351 1595 5725 11450 1595 6433 12687 1595
18" 9135 18269 2022 9912 19823 2022 10721 21441 2022

Legend:
S — Maximum load allowable on single saddle ie, 244H or 244C
D — Maximum load allowable on double saddle ie, 244HR or 244CR
L — Actual load on 10 ft. spacing
Notes:
1. These values are good for flat surfaces, roller hangers and clevis hangers.
2. The values listed in this table take into consideration maximum crushing load on calcium silicate insert.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 99
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 260-1 - Pipe Covering Protection Saddle — 1" Insulation


Size Range — 3/4" thru 8" pipe
Material — Carbon Steel
Function — Designed to provide bearing surface,
for support, outside of the insulation, thus preventing
damage. Notches are provided to minimize saddle
contact with pipe and prevent heat loss.
Approvals — Conforms to Federal Specifications
WW-171E, Type 40A and 40B and Manufacturers
Standardization Society SP-69, Type 39.
Note — All saddles are 12" long and cover 60° of
circumference of the pipe
Finish — Plain
Note — Available in Electro-Galvanized and
HDG finish.
Order By — Figure number, pipe size and finish

Dimensions • Weights
Actual
Pipe Insulation Use with Roller Max. Rec. Approx.
Size A B C Thickness 324 326 327/328 Load Lbs.* Wt./100
3/4 113/16 25/16 27/16 15/16 21/2 2 2 - 31/2 1200 141
1 115/16 27/16 25/8 11/8 3 21/2 2 - 31/2 1200 141
11/4 21/16 29/16 23/4 15/16 3 21/2 2 - 31/2 1200 141
11/2 23/16 23/4 215/16 11/16 4 3 2 - 31/2 1200 167
2 27/16 3 31/8 11/16 4 31/2 2 - 31/2 1200 167
21/2 211/16 31/4 37/16 11/16 5 31/2 2 - 31/2 1200 178
3 3 33/4 33/4 11/16 5 4 2 - 31/2 1200 178
31/2 31/2 41/4 41/4 15/16 6 5 4 - 6 1800 247
4 33/4 41/2 49/16 11/16 6 5 4 - 6 1800 247
5 45/16 5 51/8 11/16 8 6 4 - 6 1800 247
6 49/16 55/16 53/8 1 8 8 4 - 6 1800 371
8 55/8 61/2 61/2 11/16 10 10 8 - 10 1800 442
* Maximum recommended loads are based on a safety factor of 5 and are applicable only when saddle is used on a flat bearing surface. When
saddle is used with a pipe roll, the maximum load given for the pipe roll applies to the saddle.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
100 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 261-11/2 - Pipe Covering Protection Saddle — 11/2" Insulation


Size Range — 3/4" thru 36" pipe
Material — Carbon Steel
Function — Designed to provide bearing
surface, for support, outside of the insu-
lation, thus preventing damage. Notches
are provided to minimize saddle contact
with pipe and prevent heat loss.
Approvals — Conforms to Federal
Specifications WW-171E, Type 40A and
40B and Manufacturers Standardization
Society SP-69, Type 39.
Note — All saddles are 12" long and
cover 60° of circumference of the pipe.
Center bar is furnished with 12" pipe size
and larger
Finish — Plain
Note — Available in Electro-Galvanized
and HDG finish.
Order By — Figure number, pipe
size and finish

Dimensions • Weights
Actual
Pipe Insulation Use with Roller Max. Rec. Approx.
Size A B C Thickness 324 326 327/328 Load Lbs.* Wt./100
3/4 25/16 27/8 3 19/16 31/2 3 2 -
31/2 1200 212
1 27/16 3 31/8 19/16 4 3 2 -
31/2 1200 212
11/4 211/16 31/4 33/8 15/8 5 31/2 2 -
31/2 1200 244
11/2 23/4 35/16 37/16 15/8 5 31/2 2 -
31/2 1200 244
2 3 311/16 33/4 15/8 5 4 2 -
31/2 1200 244
21/2 37/16 41/4 43/16 17/8 6 5 2 -
31/2 1200 284
3 33/4 41/2 49/16 19/16 6 5 2 -
31/2 1200 284
31/2 315/16 415/16 43/4 113/16 8 6 4 -
6 1800 321
4 43/16 5 5 19/16 8 6 4 -
6 1800 321
5 43/4 59/16 59/16 19/16 10 8 4 -
6 1800 321
6 51/16 57/8 515/16 11/2 12 8 8 -
10 1800 442
8 63/16 71/4 71/8 19/16 14 10 8 -
10 1800 590
10 71/4 81/2 85/16 15/8 16 12 8 -
10 1800 590
12 83/16 911/16 95/16 15/8 18 14 12 -
14 5000 779
14 813/16 105/16 101/16 11/2 20 16 12 -
14 5000 779
16 93/4 113/8 111/16 11/2 24 18 16 -
20 5000 853
18 103/4 129/16 121/16 11/2 24 20 16 -
20 5000 912
20 113/4 135/8 121/8 11/2 — 24 24 7200 1044
24 133/4 16 155/16 11/2 — 30 30 7200 1183
30 163/4 191/4 181/2 11/2 — — 36 - 42 7200 1331
36 203/16 — 211/16 11/2 — — 36 - 42 7200 1695
* Maximum recommended loads are based on a safety factor of 5 and are applicable only when saddle is used on a flat bearing surface. When
saddle is used with a pipe roll, the maximum load given for the pipe roll applies to the saddle.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 101
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 262-2 - Pipe Covering Protection Saddle — 2" Insulation


Size Range — 3/4" thru 36" pipe
Material — Carbon Steel
Function — Designed to provide bearing
surface, for support, outside of the insu-
lation, thus preventing damage. Notches
are provided to minimize saddle contact
with pipe and prevent heat loss.
Approvals — Conforms to Federal
Specifications WW-171E, Type 40A and
40B and Manufacturers Standardization
Society SP-69, Type 39.
Note — All saddles are 12" long and
cover 60° of circumference of the pipe.
Center bar is furnished with 12" pipe size
and larger
Finish — Plain
Note — Available in Electro-Galvanized
and HDG finish.
Order By — Figure number, pipe
size and finish

Dimensions • Weights
Actual
Pipe Insulation Use with Roller Max. Rec. Approx.
Size A B C Thickness 324 326 327/328 Load Lbs.* Wt./100
3/4 213/16 31/2 39/16 21/16 5 4 2 - 31/2 1200 279
1 215/16 311/16 311/16 21/16 5 4 2 - 31/2 1200 279
11/4 31/8 37/8 37/8 21/16 5 4 2 - 31/2 1200 279
11/2 37/16 41/8 43/16 25/16 5 5 4-6 1800 319
2 35/8 45/16 47/16 25/16 6 5 4-6 1800 319
21/2 315/16 411/16 43/4 25/16 6 6 4-6 1800 340
3 41/4 5 51/16 21/16 8 6 4-6 1800 340
31/2 47/16 53/16 51/4 25/16 8 8 4-6 1800 359
4 411/16 51/2 51/2 21/16 8 8 4-6 1800 359
5 53/16 6 61/8 21/16 10 8 8 - 10 1800 359
6 59/16 61/2 61/2 21/16 10 10 8 - 10 1800 574
8 69/16 75/8 79/16 21/16 12 10 8 - 10 1800 637
10 711/16 91/8 87/8 21/8 16 14 12 - 14 1800 761
12 813/16 101/4 103/16 21/8 18 16 16 - 20 5000 970
14 97/16 1015/16 1013/16 2 18 16 16 - 20 5000 970
16 105/16 12 113/4 2 20 18 16 - 20 5000 1046
18 115/16 13 123/4 2 24 20 16 - 20 7200 1046
20 125/16 143/16 133/4 2 24 24 24 7200 1157
24 145/16 169/16 157/8 2 — 30 30 7200 1333
30 175/16 20 191/8 2 — — 36 - 42 7200 1492
36 207/16 — 223/8 2 — — 36 - 42 7200 1723
* Maximum recommended loads are based on a safety factor of 5 and are applicable only when saddle is used on a flat bearing surface. When
saddle is used with a pipe roll, the maximum load given for the pipe roll applies to the saddle.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
102 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
®

a brand of Revision 5/24/2001

Fig. 263-21/2 - Pipe Covering Protection Saddle — 21/2" Insulation


Size Range — 11/4" thru 36" pipe
Material — Carbon Steel
Function — Designed to provide bearing
surface, for support, outside of the insu-
lation, thus preventing damage. Notches
are provided to minimize saddle contact
with pipe and prevent heat loss.
Approvals — Conforms to Federal
Specifications WW-171E, Type 40A and
40B and Manufacturers Standardization
Society SP-69, Type 39.
Note — All saddles are 12" long and
cover 60° of circumference of the pipe.
Center bar is furnished with 12" pipe size
and larger
Finish — Plain
Note — Available in Electro-Galvanized
and HDG finish.
Order By — Figure number, pipe
size and finish

Dimensions • Weights
Actual
Pipe Insulation Use with Roller Max. Rec. Approx.
Size A B C Thickness 324 326 327/328 Load Lbs.* Wt./100
11/4 33/4 41/2 49/16 213/16 6 5 4 -
6 1200 369
11/2 37/8 45/8 43/4 213/16 8 6 4 -
6 1800 369
2 41/8 415/16 415/16 213/16 8 6 4 -
6 1800 369
21/2 47/16 53/16 51/4 23/4 8 8 4 -
6 1800 406
3 43/4 59/16 55/8 23/4 8 8 4 -
6 1800 406
31/2 415/16 57/8 513/16 213/16 10 8 8 -
10 1800 446
4 53/16 61/8 61/16 213/16 10 8 8 -
10 1800 446
5 53/4 63/4 63/8 213/16 10 10 8 -
10 1800 446
6 61/16 71/8 7 29/16 12 10 8 -
10 1800 653
8 71/4 83/8 83/8 211/16 14 12 12 -
14 1800 721
10 83/16 911/16 97/16 25/8 16 14 12 -
14 1800 821
12 91/4 103/4 105/8 25/8 18 16 16 -
20 5000 1048
14 97/8 111/2 111/4 25/8 20 18 16 -
20 5000 1048
16 103/4 129/16 1213/16 21/2 24 20 16 -
20 7200 1112
18 113/4 135/8 131/8 21/2 24 20 24 7200 1235
20 123/4 145/8 141/8 21/2 — 24 24 7200 1235
24 143/4 17 163/8 21/2 — 30 30 7200 1430
30 173/4 203/8 1911/16 21/2 — — 36 - 42 7200 1314
36 2013/16 — 227/8 21/2 — — 36 - 42 7200 1857
* Maximum recommended loads are based on a safety factor of 5 and are applicable only when saddle is used on a flat bearing surface. When
saddle is used with a pipe roll, the maximum load given for the pipe roll applies to the saddle.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 103
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 264-3 - Pipe Covering Protection Saddle — 3" Insulation


Size Range — 11/2" thru 36" pipe
Material — Carbon Steel
Function — Designed to provide bearing
surface, for support, outside of the insu-
lation, thus preventing damage. Notches
are provided to minimize saddle contact
with pipe and prevent heat loss.
Approvals — Conforms to Federal
Specifications WW-171E, Type 40A and
40B and Manufacturers Standardization
Society SP-69, Type 39.
Note — All saddles are 12" long and
cover 60° of circumference of the pipe.
Center bar is furnished with 12" pipe size
and larger
Finish — Plain
Note — Available in Electro-Galvanized
and HDG finish.
Order By — Figure number, pipe
size and finish

Dimensions • Weights
Actual
Pipe Insulation Use with Roller Max. Rec. Approx.
Size A B C Thickness 324 326 327/328 Load Lbs.* Wt./100
11/2 41/2 53/8 55/16 35/16 8 8 4 -
6 1500 449
2 43/4 53/8 59/16 35/16 8 6 4 -
6 1800 449
21/2 5 57/8 513/16 23/4 10 8 4 -
6 1800 470
3 51/16 61/4 61/4 31/16 10 8 8 -
10 1800 470
31/2 51/2 67/16 63/8 33/8 10 10 8 -
10 1800 491
4 53/4 611/16 611/16 31/8 10 10 8 -
10 1800 491
5 65/16 71/4 71/4 31/8 12 10 8 -
10 1800 491
6 65/8 73/4 79/16 31/16 12 12 12 -
14 1800 773
8 75/8 87/8 87/8 31/8 16 14 12 -
14 1800 773
10 811/16 101/8 101/16 31/8 18 16 16 -
20 1800 884
12 911/16 115/16 111/16 31/8 20 18 16 -
20 5000 1141
14 105/16 12 113/4 3 20 18 16 -
20 5000 1140
16 115/16 1313/16 1211/16 3 24 24 24 7200 1317
18 125/16 143/16 1311/16 3 24 24 24 7200 1317
20 135/16 155/16 157/8 3 — 24 30 7200 1450
24 155/16 179/16 1615/16 3 — 30 30 7200 1564
30 185/16 — 205/16 3 — — 36 - 42 7200 1765
36 215/16 — 235/16 3 — — 36 - 42 7200 1954
* Maximum recommended loads are based on a safety factor of 5 and are applicable only when saddle is used on a flat bearing surface. When
saddle is used with a pipe roll, the maximum load given for the pipe roll applies to the saddle.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
104 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 265-4 - Pipe Covering Protection Saddle — 4" Insulation


Size Range — 4" thru 36" pipe
Material — Carbon Steel
Function — Designed to provide bearing
surface, for support, outside of the insu-
lation, thus preventing damage. Notches
are provided to minimize saddle contact
with pipe and prevent heat loss.
Approvals — Conforms to Federal
Specifications WW-171E, Type 40A and
40B and Manufacturers Standardization
Society SP-69, Type 39.
Note — All saddles are 12" long and
cover 60° of circumference of the pipe.
Center bar is furnished with 12" pipe size
and larger
Finish — Plain
Note — Available in Electro-Galvanized
and HDG finish.
Order By — Figure number, pipe
size and finish

Dimensions • Weights
Actual
Pipe Insulation Use with Roller Max. Rec. Approx.
Size A B C Thickness 324 326 327/328 Load Lbs.* Wt./100
4 65/8 73/4 79/16 43/16 12 10 8 -
10 1800 611
5 73/16 81/8 83/16 43/16 14 12 8 -
10 1800 611
6 711/16 91/8 87/8 43/16 16 14 12 -
14 1800 1020
8 811/16 101/8 10 43/16 18 16 12 -
14 1800 1020
10 911/16 105/16 111/16 41/8 20 18 16 -
20 1800 1084
12 103/4 129/16 121/4 41/8 — 20 16 -
20 5000 1400
14 113/8 131/4 127/8 4 — 20 16 -
20 5000 1400
16 125/16 1413/16 133/4 4 — 24 24 7200 1528
18 135/16 153/16 143/4 4 — 24 24 7200 1528
20 145/16 169/16 1513/16 4 — 30 30 7200 1707
24 165/16 187/8 1713/16 4 — 30 30 7200 1835
30 195/16 — 215/16 3 — — 36 - 42 7200 2042
36 225/16 — 245/8 4 — — 36 - 42 7200 2237
* Maximum recommended loads are based on a safety factor of 5 and are applicable only when saddle is used on a flat bearing surface. When
saddle is used with a pipe roll, the maximum load given for the pipe roll applies to the saddle.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 105
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 301CT - Copper Tubing Split Ring Extension Hanger


Size Range — 1/2" thru 2" copper tubing
Material — Malleable Iron
Function — A rigid support to suspend tubing horizontally
or vertically
Approvals — Conforms to Federal Specification
WW-H-171E, Type 25 and Manufacturers Standardization
Society SP-69, Type 12.
Finish — Copper Plated
Order By — Figure number and nominal tube size

Dimensions • Weights
Copper Rod Size Max. Rec. Approx.
Tube Size A B Load Lbs. Wt./100
1/2 3/8 3/4 180 10
3/4 3/8 7/8 180 12
1 3/8 7/8 180 14
11/4 3/8 11/8 180 16
11/2 3/8 11/4 180 21
2 3/8 11/2 180 25

Fig. 302 - Split Ring Extension Hanger


Size Range — 3/8" thru 3" pipe
Material — Malleable Iron
Function — A rigid support to suspend pipe horizontally or
vertically
Approvals — Conforms to Federal Specification
WW-H-171E, Type 25 and Manufacturers Standardization
Society SP-69, Type 12.
Finish — Plain
Note — Available in Electro-Galvanized finish

Dimensions • Weights
Pipe Rod Size Max. Rec. Approx.
Size A B Load Lbs. Wt./100
3/8 3/8 7/8 180 10
1/2 3/8 7/8 180 12
3/4 3/8 7/8 180 14
1 3/8 11/8 180 17
11/4 3/8 15/16 180 21
11/2 3/8 13/8 180 24
2 3/8 111/16 180 29
21/2 1/2 23/16 300 58
3 1/2 21/2 300 75

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
106 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 303 - Split Ring Hanger


Size Range — 3/8" thru 8" pipe
Material — Malleable Iron
Function — Recommended for suspending non-insulated
pipe (For use with Fig. 307 Eye Socket or 306 Swivel
Turnbuckle)
Approvals — Conforms to Federal Specification
WW-H-171E, Type 11, 1/2" thru 8" and Manufacturers
Standardization Society SP-69, Type 11.
Maximum Temperature — 450°F
Finish — Plain
Note — Available in Electro-Galvanized finish.

Dimensions • Weights
Pipe Bolt Max. Rec. Approx.
Size A Size Load Lbs. Wt./100
3/8 3/4 1/4 200 6
1/2 7/8 1/4 200 8
3/4 1 1/4 300 9
1 11/4 1/4 300 10
11/4 11/2 1/4 300 16
11/2 13/4 1/4 300 24
2 2 1/4 300 33
21/2 23/8 1/4 450 45
3 213/16 5/16 450 65
31/2 31/8 5/16 450 74
4 35/8 3/8 520 86
5 43/16 3/8 520 135
6 5 3/8 800 178
8 63/16 1/2 1600 314

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 107
www.tolco.com

www.tolco.com
a brand of
®
Revision 9/22/2001

Fig. 304 - Weld Beam Attachment


Fig. 305 - Weld Beam Attachment with Pin
Size Range — 3/8" thru 31/2" rod
Material — Carbon Steel
Function — Designed for attaching hanger rod to bottom
of steel structures. Can be used in an upright (Fig. 304)
or inverted position (Fig. 305). When using Fig. 305,
attach hanger rod to bolt or pin with a Fig. 330 Weldless
Eye Nut or Fig. 101 and Fig. 102 series Eyerods.
Approvals — Conforms to Federal Specification
WW-H-171E, Type 22 and Manufacturers Standardization
Society SP-69, Type 22.
Finish — Plain
Note — Available in Electro-Galvanized and GDG finish
or Stainless Steel materials.
Order By — Figure number, rod size and finish.

Dimensions • Weights
304 305
Rod Max. Rec. Load Lbs. Approx. Approx.
Size A B C D E F Bolt Size 650°F 750°F Wt./100 Wt./100
3/8 7/8 2 2 11/4 9/16 7/16 1/2 x 21/2 610 510 86 107
1/2 7/8 2 2 11/4 11/16 9/16 5/8 x 21/2 1130 940 83 118
5/8 1 2 2 11/4 13/16 11/15 3/4 x 23/4 1810 1510 84 140
3/4 11/8 2 21/2 11/2 15/16 13/16 7/8 x 3 2710 2260 174 261
7/8 11/4 3 21/2 2 11/8 15/16 1 x 4 3770 3150 232 374
1 11/2 3 3 2 11/4 11/8 11/8 x 41/2 4960 4150 394 595
11/4 2 3 4 21/2 15/8 13/8 11/2 x 53/4 8000 6660 738 1026
11/2 21/2 4 5 3 17/8 15/8 13/4 x 61/2 11630 9700 1449 1892
13/4 23/4 5 5 33/4 21/8 17/8 2 x 73/4 15700 14000 1747 2437
2 31/4 5 6 33/4 23/8 21/8 21/4 x 73/4 20700 18460 2201 3074
21/4 31/2 6 6 41/2 25/8 2 21/2 x 73/4 27200 24260 2523 3601
21/2 33/4 6 6 41/2 27/8 23/8 23/4 x 8 33500 29880 2552 3898
*23/4 4 53/4 6 33/4 31/8 — 3 x 75/8 41580 37066 2675 4202
*3 4 61/4 7 33/4 33/8 — 31/4 x 75/8 50580 45085 3250 5043
*31/4 41/2 7 7 41/4 35/8 — 31/2 x 81/2 60480 53906 4500 6817
*31/2 41/2 71/2 8 41/4 37/8 — 33/4 x 81/2 71280 63493 5320 7980
Note: Sizes 3/8" thru 1" furnished with machine bolt; sizes 11/4" thru 31/2" furnished with pin and cotter.
* Welded Plate

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
108 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 306 - Turnbuckle with Swivel Short Pattern


Size Range — 1/2" thru 3/4" rod
Material — Malleable Iron
Function — To provide an adjustable threaded connection
for hanger rods when used with Fig. 303 Split Ring Hanger.
Approvals — Conforms to Federal Specification
WW-H-171E, Type 15 and Manufacturers Standardization
Society SP-69, Type 15.
Finish — Plain
Note — Available in Electro-Galvanized finish
Order By — Figure number, rod size and finish

Dimensions • Weights
Rod Size Max. Rec. Approx.
Pipe Size A B C D Load Lbs. Wt./100
1/2 - 2 3/8 2 33/4 7/16 610 28
21/2 - 31/2 1/2 2 33/4 7/16 725 31
4-5 5/8 21/2 5 9/16 710 72
6 3/4 21/2 5 9/16 860 70

Fig. 307 - Eye Socket


Size Range — 3/8" thru 7/8" rod
Material — Malleable Iron
Function — To provide a non-adjustable threaded connec-
tion for hanger rods when used with Fig. 303 Split Ring
Hangers.
Approvals — Conforms to Federal Specification
WW-H-171E, Type 16 and Manufacturers Standardization
Society SP-69, Type 16.
Finish — Plain
Note — Available in Electro-Galvanized finish

Dimensions • Weights
Rod Size Max. Rec. Approx.
Pipe Size A B C Load Lbs. Wt./100
1/2 - 2 3/8 1/4 15/16 570 7
21/2 - 31/2 1/2 1/4 11/2 1130 13
4-5 5/8 3/8 13/4 1400 19
6 3/4 1/2 21/8 1900 31
8 7/8 1/2 23/8 2200 44

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 109
www.tolco.com

www.tolco.com
a brand of
®
Revision 1/13/2004

Fig. 309 - Concrete Insert


Material — Malleable Iron
Function — For use in concrete to attach 3/8" thru 7/8"
hanger rod.
Note — Other Manufacturers Insert Nuts are not necessarily
compatible with TOLCO™ Fig. 309 (Concrete Insert). Therefore it
is recommended that TOLCO Fig. 309N (Concrete Insert Nuts)
be ordered concurrently with Fig. 309.
Approvals — Conforms to Federal Specification
WW-H-171E, Type 18 and Manufacturers Standardization Society
SP-69, Type 18.
Finish — Plain
Note — Available in Electro-Galvanized finish

Dimensions • Weights
Max. Rec. Approx.
Rod Size* Load Lbs.* Wt./100
Insert Only 3/8 - 7/8 1140 130
* See Fig. 309N
† Based on minimum safety factor of 5. Rating is subject to the condition that the
concrete used is of sufficient strength to hold the insert.

Fig. 309N - Concrete Insert Nut


Size Range — 3/8" thru 7/8" mach thread
Material — Ductile Iron
Function — For use in Fig. 309 (Concrete Insert).
Note — Other Manufacturers Concrete Inserts are not nec-
essarily compatible with TOLCO Fig. 309N (Concrete Insert
Nuts). Therefore it is recommended that TOLCO Fig. 309
be ordered concurrently with Fig. 309N.
Finish — Plain
Note — Available in Electro-Galvanized finish

Dimensions • Weights
Max. Rec. Approx.
Rod Size* Load Lbs.* Wt./100
3/8 610 20
1/2 1130 21
5/8 1140 20
3/4 1140 22
7/8 1140 21
† Based on minimum safety factor of 5. Rating is subject to the condition that the
concrete used is sufficient strength to hold the insert.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
110 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 310 - Steel Spot Concrete Insert


Material — Carbon Steel
Function — Fig. 310 is for use as a structural attachment in
concrete ceilings. Knockout plug designed to protect against con-
crete seepage. Place insert face down on concrete form and nail
in place. Reinforcing rods may be positioned under flange lips.
Specified load ratings and approvals are not dependent on the
use of any reinforcing rods in contact with the insert. Pour con-
crete, strip forms, place screwdriver tip in slot of knockout plug
and twist sharply. Insert square nut (Fig. 310N) and run rod
through nut until tight against top of insert, turn rod one-half turn
to lock and protect against vibration.
Note — Other Manufacturers Insert Nuts are not necessarily
compatible with TOLCO™ Fig. 310 (Spot Inserts). Therefore it is
recommended that TOLCO Fig. 310N (Spot Insert Nuts) be
ordered concurrently with Fig. 310 (Spot Inserts).
Approvals — Conforms to Federal Specification
WW-H-171E, Type 19 and Manufacturers Standardization Society
SP-69, Type 18. Dimensions • Weights
Finish — Plain Max. Rec. Approx.
Note — Available in Electro-Galvanized finish Load Lbs.* Wt./100
Order By — Figure number and finish. Order Fig. 310N (Spot 600 53
Insert Nuts) separately. * Based on a straight pull of 600 lbs.

Fig. 310N - Steel Spot Insert Nut


Size Range — 1/4" thru 7/8" mach thread
Material — Carbon Steel
Function — Fig. 310N is for use with Fig. 310 Spot Concrete
Insert for means of rod attachment.
Note — Other Manufacturers’ spot inserts are not necessarily
compatible with TOLCO Fig. 310N (Spot Insert Nuts). Therefore
it is recommended that TOLCO Fig. 310 (Spot Insert) be
ordered concurrently with Fig. 310N (Spot Insert Nuts).
Finish — Plain
Note — Available in Electro-Galvanized finish

Dimensions • Weights
Max. Rec. Approx.
Rod Size Load Lbs.* Wt./100
1/4 240 8
3/8 600 13
1/2 600 12
5/8 600 11
3/4 600 10
7/8 600 9
* Based on straight pull of 600 lbs. when used with Fig. 310.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 111
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 311 - Pipe Saddle with Strap


Size Range — Size 4" thru 36" pipe
Material — Carbon Steel
Function — Designed to support horizontal pipe from floor
stanchion. Top clamp holds pipe securely to saddle. To complete
floor stanchion use with Fig. 316 Stand Pipe. For complete floor
stanchion with vertical adjustment use Fig. 319 Threaded Pipe
Adjuster and Fig. 316T Threaded Stand Pipe.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, pipe size and finish

GUSSETS ON SIZES 8"


AND LARGER

Dimensions • Weights
Pipe Bolt
Size A B C D E F Size
4 7 313/16 2 23/8 21/2 3/4 1/2
5 85/8 43/16 2 23/8 21/2 3/4 1/2
6 11 47/8 2 23/8 21/2 7/8 5/8
8 127/8 615/16 2 23/8 21/2 1 5/8
10 161/4 715/16 2 23/8 21/2 1 3/4
12 181/4 91/8 3 23/8 21/2 1 3/4
14 193/4 101/2 3 27/8 3 11/8 3/4
16 223/4 111/2 3 27/8 3 11/8 3/4
18 257/8 131/2 4 33/4 4 11/4 3/4
20 273/4 141/2 4 33/4 4 13/8 3/4
22 293/4 151/2 4 33/4 4 13/8 3/4
24 33 171/2 4 33/4 4 15/8 7/8
26 35 181/2 4 33/4 4 2 7/8
30 413/8 205/8 4 33/4 4 2 7/8
32 433/8 215/8 4 33/4 4 2 7/8
36 473/8 235/8 4 33/4 4 2 7/8

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
112 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 312 - Adjustable Pipe Support


Size Range — Size 2" thru 12" pipe
Material — Carbon Steel
Function — Designed to support horizontal pipe from
floor stanchion where vertical adjustment is required.
Maximum Temperature — 650°F
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish
or Stainless Steel materials.
Order By — Figure number, pipe size and finish

Dimensions • Weights
Max. O.D. A Use with Fig. 316 Approx.
Pipe Size Pipe Min. Max. B Stand Pipe Size Wt./100
2 23/8 23/4 6 7/8 1 210
21/2 27/8 31/4 61/2 7/8 1 219
3 4 31/2 63/4 7/8 1 240
31/2 4 31/2 63/4 7/8 1 240
4 47/8 41/4 71/2 1 1 340
5 55/8 41/2 73/4 1 1 360
6 7 55/8 83/8 11/4 11/4 580
8 91/8 63/4 91/2 11/4 11/4 640
10 111/8 8 10 11/4 11/4 1060
12 131/2 91/4 111/4 11/4 11/4 1060

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 113
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 313 - Adjustable Pipe Support with U-Bolt


Size Range — Size 2" thru 12" pipe
Material — Carbon Steel
Function — Designed to support horizontal pipe from
floor stanchion where vertical adjustment is required.
U-bolt and hex nuts are provided to hold pipe securely
to saddle.
Maximum Temperature — 650°F
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish
or Stainless Steel materials.
Order By — Figure number, pipe size and finish

Dimensions • Weights
Max. O.D. A Use with Fig. 316 Approx.
Pipe Size Pipe Min. Max. B C Stand Pipe Size Wt./100
2 23/8 23/4 6 7/8 3/8 1 210
21/2 27/8 31/4 61/2 7/8 3/8 1 219
3 4 31/2 63/4 7/8 1/2 1 240
31/2 4 31/2 63/4 7/8 1/2 1 240
4 47/8 41/4 71/2 1 1/2 1 340
5 55/8 41/2 73/4 1 1/2 1 360
6 7 55/8 83/8 11/4 5/8 11/4 580
8 91/8 63/4 91/2 11/4 5/8 11/4 640
10 111/8 8 10 11/4 3/4 11/4 1060
12 131/2 91/4 111/4 11/4 7/8 11/4 1060

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
114 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 314 - Flange Support


Size Range — Size 4" thru 36" pipe
Material — Carbon Steel
Function — Designed to support 125 lb. cast iron and 150 lb. forged
steel flanged connections. (Consult factory for other flanged bolt
patterns). To complete floor stanchion, use Fig. 316 Stand Pipe. For
complete floor stanchion with vertical adjustment, use Fig. 319
Threaded Pipe Adjuster and Fig. 316T Threaded Pipe Stand.
Approvals — Conforms to Federal Specification WW-H-171E, Type 38,
4" thru 36" and Manufacturers Standardization Society SP-69, Type 37.
Maximum Temperature — 750°F
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or Stainless
Steel materials.
Order By — Figure number, pipe size and finish

Dimensions • Weights
Pipe
Size A B C D E H
4 6 /8
7
2 6 /8
3
2 /8
3
2 /2
1
3/4
5 73/8 2 71/16 23/8 21/2 7/8
6 77/8 2 73/4 23/8 21/2 7/8
8 101/8 2 99/16 23/8 21/2 7/8
10 113/8 2 8 23/8 21/2 1
12 127/8 3 91/2 23/8 21/2 1
14 15 3 183/16 27/8 3 11/8
16 161/4 3 165/8 27/8 3 11/8
18 18 4 1711/16 33/4 4 11/4
20 191/4 4 153/4 33/4 4 11/4
22 201/4 4 165/16 33/4 4 13/8
24 221/2 4 183/8 33/4 4 13/8
26 235/8 4 171/8 33/4 4 13/8
30 257/8 4 163/8 33/4 4 13/8
32 273/8 4 175/8 33/4 4 15/8
36 291/2 4 171/2 33/4 4 15/8

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 115
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 315 - Adjustable Pipe Support


Size Range — Size 4" thru 10" pipe
Material — Carbon Steel
Function — Designed to support horizontal pipe from
floor stanchion where vertical adjustment is required.
Finish — Plain
Note — Available in Electro-Galvanized and HDG
finish or Stainless Steel materials.
Order By — Figure number, pipe size and finish

Dimensions • Weights
Pipe IPS Use with Fig. 316 Approx.
Size A B C D Stand Pipe Size Wt./100
4 105/8 8 6 11/2 2 210
6 1111/16 8 6 11/2 2 219
8 1211/16 8 6 2 21/2 240
10 133/4 8 6 2 21/2 240

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
116 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
®
Revision 5/24/2001
a brand of

Fig. 316 - Stand Pipe


Fig. 316T - Threaded Stand Pipe

Size Range — 1" thru 8" pipe


Material — Carbon Steel
Function — Fig. 316 provides the support base for a floor stan-
chion support. Use with Fig. 311, Fig. 312, Fig. 313,
Fig. 314, Fig. 315, Fig. 317 or Fig. 318. Fig. 316T provides a
threaded support base for a floor stanchion support where verti-
cal adjustment is required. Use with Fig. 317A or
Fig. 318A or Fig. 319 and use with Fig. 311 thru Fig. 318.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, pipe size, “L” dimension and finish

Dimensions • Weights
Stand Pipe Approx.
Size A H Plate Size Wt./100*
1 1 1/2 6 sq. 423
11/4 1 1/2 6 sq. 482
11/2 1 1/2 6 sq. 525
2 1 1/2 6 sq. 748
21/2 11/8 5/8 71/2 sq. 1377
3 11/8 5/8 9 sq. 1555
4 11/4 3/4 11 sq. 2514
6 11/2 7/8 131/2 sq. 4469
8 11/2 1 16 sq. 10120
* Weight is based on “L” dimension of 1'0"

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 117
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 317 - Pipe Saddle


Size Range — 11/2" thru 36" pipe
Material — Carbon Steel
Function — Designed to support horizontal
pipe from floor stanchion. To complete floor
stanchion, use with Fig. 316 Stand Pipe.
For complete floor stanchion with vertical
adjustment, use Fig. 319 Threaded Pipe
Adjuster and Fig. 316T Threaded Stand
Pipe.
Approvals — Conforms to Federal
Specification WW-H-171E, Type 37,
4" thru 36", and Manufacturers
Standardization Society SP-69, Type 36
Maximum Temperature — 750°F
Finish — Plain
Note — Available in Electro-Galvanized
and HDG finish or Stainless Steel
materials.
Order By — Figure number, pipe size and
finish

Dimensions • Weights
Max. O.D. Approx.
Pipe Size Pipe A B C D Wt./100
11/2 2 21/4 1* 2 1 127
2 23/8 27/16 1* 2 1 131
21/2 27/8 211/16 11/2* 2 11/2 149
3 31/2 3 11/2* 2 11/2 162
31/2 4 31/4 11/2* 2 11/2 178
4 47/8 313/16 23/8 3 21/2 455
5 55/8 43/16 23/8 3 21/2 489
6 7 47/8 23/8 3 21/2 550
8 91/8 615/16 23/8 4 21/2 790
10 111/8 715/16 23/8 4 21/2 872
12 131/2 91/8 23/8 4 21/2 1007
14 14 101/2 27/8 4 3 1541
16 16 111/2 27/8 4 3 1680
18 18 131/2 33/4 4 4 2220
20 20 141/2 33/4 4 4 2415
22 22 151/2 33/4 4 4 2600
24 24 171/2 33/4 4 4 2970
26 26 181/2 33/4 4 4 3172
30 30 205/8 33/4 4 4 4047
32 32 215/8 33/4 4 4 4230
36 36 235/8 33/4 4 4 4608
* For pipe sizes 11/2" thru 31/2", a rod shank is used.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
118 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 317A - Pipe Saddle and Threaded Pipe Adjuster


Size Range — 21/2" thru 36" pipe
Material — Carbon Steel with cast iron
reducer
Function — Designed to support horizontal
pipe from floor stanchion where vertical
adjustment is required. To complete floor
stanchion, use with Fig. 316T Threaded
Pipe Stand.
Approvals — Conforms to Federal
Specification WW-H-171E, Type 39,
4" thru 36", and Manufacturers
Standardization Society SP-69, Type 38
Finish — Plain
Note — Available in Electro-Galvanized
and HDG finish or Stainless Steel
materials.
Order By — Figure number, pipe size ,
adjuster size and finish
Note — Order with TOLCO™ Fig. 316T for
complete stanchion support

Dimensions • Weights
Pipe A B C C Approx.
Size Stand Pipe Size Adj. Pipe Size Min. Max. Wt./100
21/2 2 11/2 7 111/2 453
3 2 11/2 75/16 1113/16 466
31/2 2 11/2 79/16 121/16 482
4 3 21/2 101/4 143/4 1248
5 3 21/2 111/16 159/16 1282
6 3 21/2 119/16 161/16 1343
8 3 21/2 139/16 181/16 1583
10 3 21/2 145/8 191/8 1665
12 3 21/2 155/8 201/8 1800
14 4 3 187/8 233/8 2761
16 4 3 197/8 243/8 2900
18 6 4 221/4 263/4 4468
20 6 4 231/4 273/4 4663
22 6 4 241/4 283/4 4848
24 6 4 261/2 31 5218
26 6 4 271/2 32 5420
30 6 4 295/8 341/8 6295
32 6 4 305/8 351/8 6478
36 6 4 325/8 371/8 6856

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 119
www.tolco.com

www.tolco.com
a brand of
®
Revision 9/22/2001

Fig. 318 - Pipe Saddle with U-Bolt


Size Range — 4" thru 36" pipe
Material — Carbon Steel
Function — Designed to support
horizontal pipe from floor stanchion.
U-bolts and hex nuts are provided to hold
pipe securely to saddle. To complete floor
stanchion, use with Fig. 316 Stand Pipe.
For complete floor stanchion with vertical
adjustment, use Fig. 319 Threaded Pipe
Adjuster and Fig. 316T Threaded Pipe
Stand.
Approvals — Conforms to Federal
Specification
WW-H-171E, Type 38, 4" thru 36", and
Manufacturers Standardization Society
SP-69, Type 37
Maximum Temperature — 750°F
Finish — Plain
Note — Available in Electro-Galvanized
and HDG finish or Stainless Steel
materials.
Order By — Figure number and pipe size

Dimensions • Weights
Max. O.D. Approx.
Pipe Size Pipe A B C D Wt./100
4 47/8 313/16 23/8 1/2 21/2 620
5 55/8 43/16 23/8 1/2 21/2 660
6 7 47/8 23/8 5/8 21/2 835
8 91/8 615/16 23/8 5/8 21/2 1120
10 111/8 715/16 23/8 3/4 21/2 1400
12 131/2 91/8 23/8 7/8 3 1800
14 14 101/2 27/8 7/8 3 2930
16 16 111/2 27/8 7/8 3 3225
18 18 131/2 33/4 1 4 3960
20 20 141/2 33/4 1 4 4309
22 22 151/2 33/4 1 4 4660
24 24 171/2 33/4 1 4 5188
26 26 181/2 33/4 1 4 5520
30 30 205/8 33/4 1 4 6948
32 32 215/8 33/4 1 4 7327
36 36 235/8 33/4 1 4 8046

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
120 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 318A - Pipe Saddle with U-Bolt and Threaded Pipe Adjuster
Size Range — 4" thru 36" pipe
Material — Carbon Steel with cast iron
reducer
Function — Designed to support horizon-
tal pipe from floor stanchion where verti-
cal adjustment is required. U-bolt and
hex nuts are provided to hold pipe
securely to saddle. To complete floor
stanchion, use with Fig. 316T Threaded
Pipe Stand.
Approvals — Conforms to Federal
Specification
WW-H-171E, Type 38, 4" thru 36", and
Manufacturers Standardization Society
SP-69, Type 37
Finish — Plain
Note — Available in Electro-Galvanized
and HDG finish or Stainless Steel
materials.
Order By — Figure number, pipe size,
adjuster size and finish
Note — Order with TOLCO™ Fig. 316T
for complete stanchion support.

Dimensions • Weights
Pipe A B C C Approx.
Size Stand Pipe Size Adj. Pipe Size Min. Max. Wt./100
4 3 21/2 101/4 143/4 1413
5 3 21/2 111/16 159/16 1453
6 3 21/2 119/16 161/16 1628
8 3 21/2 139/16 181/16 1913
10 3 21/2 145/8 191/8 2193
12 3 21/2 155/8 201/8 2593
14 4 3 187/8 233/8 4150
16 4 3 197/8 243/8 4445
18 6 4 221/4 263/4 4468
20 6 4 231/4 273/4 6557
22 6 4 241/4 283/4 6908
24 6 4 261/2 31 7436
26 6 4 271/2 32 7768
30 6 4 295/8 341/8 9196
32 6 4 305/8 351/8 9575
36 6 4 325/8 371/8 10294

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 121
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 319 - Threaded Pipe with Adjuster


Size Range — For use with 21/2" thru 36" pipe
Material — Carbon Steel
Function — Straight threaded shank that
permits adjustment after installation
Approvals — Conforms to Federal
Specification
WW-H-171E, Type 39 21/2" thru 36" and
Manufacturers Standardization Society
SP-69, Type 38, when used with Fig. 317 and
Fig. 318 Pipe Saddle.
Maximum Temperature — 650°F
Finish — Plain
Note — Available in Electro-Galvanized
Order By — Figure number, adjuster size and
finish

Dimensions • Weights
Adjuster Pipe Max. O.D. A B C C Approx.
Size Size of Pipe Pipe Size Pipe Size Min. Max. Wt./100
11/2 x 2 21/2 27/8 2 11/2 7 111/2 304
11/2 x 2 3 31/2 2 11/2 75/16 1113/16 304
11/2 x 2 31/2 4 2 11/2 79/16 121/16 304
21/2 x 3 4 47/8 3 21/2 101/4 143/4 793
21/2 x 3 5 55/8 3 21/2 111/16 159/16 793
21/2 x 3 6 7 3 21/2 119/16 161/16 793
21/2 x 3 8 91/8 3 21/2 139/16 181/16 793
21/2 x 3 10 111/8 3 21/2 145/8 191/8 793
21/2 x 3 12 131/2 3 21/2 155/8 201/8 793
3 x 4 14 14 4 3 187/8 233/8 1220
3 x 4 16 16 4 3 197/8 243/8 1220
4 x 6 18 18 6 4 221/4 263/4 2248
4 x 6 20 20 6 4 231/4 273/4 2248
4 x 6 22 22 6 4 241/4 283/4 2248
4 x 6 24 24 6 4 261/2 31 2248
4 x 6 26 26 6 4 271/2 32 2248
4 x 6 30 30 6 4 295/8 241/8 2248
4 x 6 32 32 6 4 305/8 351/8 2248
4 x 6 36 36 6 4 325/8 371/8 2248

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
122 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 322 - Pipe Roll with Sockets


Size Range — 2" thru 36" pipe
Material — Cast iron and carbon steel axle
Function — For supporting pipe where expansion may
occur due to thermal movement. Double rod design
provides support for greater loads.
Approvals — Conforms to Federal Specification
WW-H-171E, Type 42, 2" thru 24", and Manufacturers
Standardization Society SP-69, Type 41
Note — When pipe line is insulated, total outside diameter
of pipe and covering should be used to determine size of
hanger; also see Figs. 260-1 to 265-4.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish.
Order By — Figure number, pipe size and finish

Dimensions • Weights
Rod Size Max. Rec. Approx.
Pipe Size A B* C D Load Lbs. Wt./100
1 3/8 3 15/8 41/8 600 45
11/4 3/8 33/8 113/16 41/2 600 48
11/2 3/8 35/8 115/16 43/4 600 51
2 3/8 41/16 23/16 57/16 600 58
21/2 1/2 47/8 25/8 61/4 660 123
3 1/2 51/2 215/16 67/8 700 133
31/2 1/2 6 35/16 73/8 750 146
4 5/8 67/8 33/4 87/16 750 230
5 5/8 8 45/16 99/16 750 285
6 3/4 95/8 415/16 119/16 1070 460
8 7/8 1113/16 65/16 14 1350 720
10 7/8 14 79/16 163/16 1730 1100
12 7/8 16 811/16 183/16 2400 1630
14 1 18 913/16 2011/16 3130 2150
16 11/4 201/4 111/16 23 3970 2850
18 11/4 221/2 121/8 251/4 4200 3650
20 11/4 25 131/2 261/4 4550 4650
24 11/2 285/8 1511/16 317/8 6160 6200
30 11/2 331/2 193/8 395/8 7290 12500
* Due to the inconsistent dimensions associated with cast parts, please contact the factory if the
“B” dimension is critical for installation.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 123
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 323 - Adjustable Support Roller


Size Range — 2" thru 10" pipe
Material — Cast iron and carbon steel axle
Function — For supporting pipe where expansion may
occur due to thermal movement. Used when ceiling support
is impractical.
Note — When pipe line is insulated, total outside diameter
of pipe and covering should be used to determine size of
hanger; also see Figs. 260-1 to 265-4.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish.

Dimensions • Weights
Rod Size Max. Rec. Approx.
Pipe Size A B C D Max. Adj. Load Lbs. Wt./100
2 41/4 19/16 33/4 3/8 13/4 450 65
21/2 41/2 17/8 41/8 1/2 21/4 500 130
3 53/8 23/16 41/8 1/2 21/4 520 147
31/2 53/4 21/2 41/8 1/2 21/4 560 159
4 65/8 215/16 53/8 1/2 3 560 240
5 73/4 37/16 53/8 5/8 3 560 305
6 85/8 41/16 61/8 3/4 31/2 800 465
8 111/4 51/8 71/8 7/8 4 1010 712
10 131/2 63/8 71/8 7/8 4 1290 955

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
124 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 324 - Pipe Roll Hanger


Size Range — 21/2" thru 24" pipe
Material — Cast iron and carbon steel
Function — For supporting pipe where movement may
occur due to thermal expansion.
Approvals — Conforms to Federal Specification
WW-H-171E, Type 44, 1" thru 20", and Manufacturers
Standardization Society SP-69, Type 43
Note — When pipe line is insulated, total outside diameter
of pipe and covering should be used to determine size of
hanger; also see Figs. 260-1 to 265-4.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.

Dimensions • Weights
Rod Size Max. Rec. Approx.
Pipe Size A B* C D Load Lbs. Wt./100
21/2 1/2 515/16 35/16 17/8 225 171
3 1/2 65/8 315/16 23/16 310 224
31/2 1/2 71/4 43/8 29/16 390 250
4 5/8 77/8 51/16 27/8 475 372
5 5/8 91/8 61/8 37/16 685 649
6 3/4 103/16 71/16 41/16 780 869
8 7/8 121/2 93/16 51/16 780 1368
10 7/8 155/16 113/8 65/16 965 1909
12 7/8 179/16 131/2 77/16 1200 3001
14 1 201/4 145/8 87/16 1200 3578
16 1 223/8 165/8 95/16 1200 4150
18 1 241/2 185/8 103/8 1400 5382
20 11/4 263/4 205/8 2611/16 1600 7317
24 11/2 319/16 245/8 1313/16 1600 12600

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 125
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 325 - Pipe Roller Chair


Size Range — 2" thru 24" pipe
Material — Cast iron and carbon steel
Function — For supporting pipe where movement may
occur due to thermal expansion. Used when ceiling suspen-
sion is impractical
Note — When pipe line is insulated, total outside diameter
of pipe and covering should be used to determine size of
hanger; also see Figs. 260-1 to 265-4.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order by — Figure number, pipe size and finish

Dimensions • Weights
Max. Rec. Approx.
Pipe Size A B C D Bolt Size Load Lbs. Wt./100
2 11/4 11/2 19/16 4 3/8 x 11/2 600 104
21/2 11/4 17/8 17/8 41/2 3/8 x 11/2 660 163
3 2 2 23/16 51/2 3/8 x 11/2 700 175
31/2 2 25/16 21/2 6 3/8 x 11/2 750 245
4 2 25/16 25/16 61/2 1/2 x 13/4 750 347
5 3 29/16 37/16 71/2 1/2 x 13/4 750 488
6 31/8 23/4 41/16 9 1/2 x 13/4 1070 613
8 33/8 31/8 51/8 125/8 5/8 x 13/4 1350 1039
10 51/4 313/16 63/8 143/4 5/8 x 2 1730 1654
12 51/2 41/8 79/16 167/8 5/8 x 2 2400 2190
14 61/2 411/16 87/16 183/4 3/4 x 2 3130 2770
16 81/4 53/8 97/16 21 3/4 x 21/2 3970 3460
18 91/4 6 109/16 231/8 3/4 x 21/2 4200 4120
20 101/4 61/2 113/4 245/8 3/4 x 21/2 4550 5510
24 121/4 77/8 137/8 293/8 7/8 x 31/2 6160 9000

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
126 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 326 - Adjustable Support Roller


Size Range — 1" thru 30" pipe
Material — Cast iron and carbon steel
Function — For supporting pipe where movement may
occur due to thermal expansion. Used where adjustment up
to 6" is required.
Note — When pipe line is insulated, total outside diameter
of pipe and covering should be used to determine size of
hanger; also see Figs. 260-1 to 265-4.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish.
Furnished With — Fig. 322 Roller, two support rods and
eight Fig. 113 Hex Nuts — not assembled.

Dimensions • Weights
Rod Size Max. Rec. Approx.
Pipe Size A B* C D Load Lbs. Wt./100
1 3/8 31/8 25/16 9 600 100
11/4 3/8 37/16 21/2 9 600 101
11/2 3/8 35/8 25/8 9 600 104
2 3/8 41/16 213/16 9 600 112
21/2 1/2 47/8 31/2 10 600 236
3 1/2 51/2 313/16 10 700 246
31/2 1/2 6 43/16 10 750 259
4 1/2 67/8 47/8 11 750 451
5 5/8 8 57/16 11 750 486
6 3/4 95/8 65/16 12 1070 795
8 7/8 1113/16 715/16 13 1350 1182
10 7/8 14 93/16 13 1730 1562
12 1 16 107/16 13 2400 2312
14 1 18 1113/16 15 3130 3091
16 11/4 201/4 135/16 151/2 3970 4102
18 11/4 221/2 143/8 151/2 4200 4902
20 11/4 25 157/8 161/2 4550 7480
24 11/2 255/8 185/16 161/2 6160 8572
30 11/2 341/2 231/8 21 7290 16396
* Due to the inconsistent dimensions associated with cast parts, please contact the factory if the
“B” dimension is critical for installation.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 127
www.tolco.com

www.tolco.com
a brand of
®
Revision 3/18/2002

Fig. 327 - Pipe Roller and Stand


Size Range — 2" thru 30" pipe
Material — Cast iron roller and Carbon Steel base
Function — Designed to support pipe where movement
may occur due to thermal expansion.
Approvals — Complies with Federal Specification
WW-H-171E, Type 45 and Manufacturers Standardization
Society SP-69, Type 44.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order by — Figure number, pipe size and finish

Dimensions • Weights
Max. Rec. Approx.
Pipe Size C D E Load Lbs. Wt./100
2 53/4 81/2 11/2 390 570
21/2 53/4 81/2 13/4 390 570
3 53/4 81/2 21/8 390 570
4 53/4 101/8 23/4 950 760
5 53/4 101/8 33/8 950 760
6 53/4 101/8 37/8 950 760
8 67/8 87/8 51/8 2100 760
10 67/8 87/8 61/4 2100 1330
12 77/8 11 73/8 3075 1330
14 77/8 11 8 3075 2375
16 83/4 121/2 87/8 4980 2375
18 83/4 121/2 10 4980 3420
20 83/4 121/2 11 4980 3420
24 87/8 133/4 13 6100 4275
30 103/4 171/4 161/4 7500 8550

Dimensions • Weights

Pipe Size F G H J K M
2 - 3 6 /2
1
1 2 7/16 3 /2
1
41/8
4 - 6 8 1 23/8 9/16 43/4 41/4
8 - 10 4 1 33/4 5/8 7 5
12 - 14 53/4 1 33/4 9/16 91/4 6
16 - 20 63/4 1 45/8 3/4 101/4 61/2
22 - 24 71/2 1 43/4 13/16 111/2 63/4
26 - 30 10 1 55/8 1 143/8 8

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
128 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 328 - Adjustable Pipe Roller Stand


Size Range — 2" thru 30" pipe
Material — Cast iron roller and Carbon Steel frame and
base
Function — Designed to support pipe where movement
may occur due to thermal expansion. Set screws allow for
vertical adjustment
Approvals — Complies with Federal Specification
WW-H-171E, Type 47 and Manufacturers Standardization
Society SP-69, Type 46.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order by — Figure number, pipe size and finish

Dimensions • Weights
Max. Rec. Approx.
Pipe Size C D D Load Lbs. Wt./100
2 67/8 51/2 11/2 390 964
21/2 67/8 51/2 13/4 390 964
3 67/8 51/2 21/8 390 964
4 81/8 53/4 23/4 950 1102
5 81/8 53/4 33/8 950 1102
6 81/8 53/4 37/8 950 1102
8 105/8 63/4 51/8 2100 2261
10 105/8 63/4 61/4 2100 2261
12 13 8 73/8 3075 4066
14 13 8 8 3075 4066
16 145/8 85/8 87/8 4980 5330
18 145/8 85/8 10 4980 5330
20 145/8 85/8 11 4980 5330
24 153/4 85/8 13 6100 7230
30 191/4 101/2 161/4 7500 14225

Dimensions • Weights
L
Pipe Size E G K Min. Max.
2 - 3 5/8 31/2 41/8 3 37/8
4 - 6 5/8 43/4 43/8 33/8 41/2
8 - 10 3/4 7 5 47/8 65/8
12 - 14 7/8 91/4 6 57/8 75/8
16 - 20 1 101/4 61/2 57/8 73/4
22 - 24 1 111/2 63/4 61/8 8
26 - 30 11/4 143/8 8 71/4 101/2

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 129
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 329 - Adjustable Beam Clamp


Maximum Recommended Load — 1290 lbs.
Material — Malleable Iron
Function — For attachment to beam flanges under normal
service conditions where the flange thickness does not exceed
.60" and where beam widths are from 23/8" min. to 7" max.
Approvals — Complies with Federal Specification
WW-H-171E, Type 30 and Manufacturers Standardization
Society SP-69, Type 30, when used with Fig. 333 Extension
Piece.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish

Dimensions • Weights
A Bolt Max. Rec. Approx.
Min Max. Size Load Lbs. Wt./100
17/8 31/2 7/16 1290 221

Fig. 330 - Weldless Steel Eye Nut


Size Range — 3/8 thru 21/2" machine thread.
Material — Forged Steel
Quality Assurance — Conforms to the requirements of NCA 3800.
Threads — Tapped UNC Class 2B. Right hand threads are standard. Left hand
threads supplied upon request.
Function — Used on piping installations where high strength and swivel action is
required. Left hand tap also available.
Approvals — Complies with Federal Specification WW-H-171E, Type 17 and
Manufacturers Standardization Society SP-69, Type 17.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish

Dimensions • Weights
Rod Size Max. Rec. Load Lbs. Approx.
A B C D E F G 650°F 750°F Wt./100
3/8 11/2 13/16 1/2 2 13/8 11/16 610 540 63
1/2 11/2 13/16 1/2 2 13/8 11/16 1130 1010 60
5/8 11/2 13/16 1/2 2 13/8 11/16 1810 1610 59
3/4 11/2 13/16 1/2 2 13/8 11/16 2710 2420 56
7/8 2 111/16 3/4 25/8 115/16 1 3770 3360 170
1 2 111/16 3/4 25/8 115/16 1 4960 4420 174
11/8 21/2 113/16 1 33/8 23/8 11/4 6230 5560 373
11/4 21/2 113/16 1 33/8 23/8 11/4 8000 7140 364
11/2 21/2 113/16 1 33/8 23/8 11/4 11630 10370 345
13/4 4 4 11/2 61/4 4 21/4 15700 14000 1657
2 4 4 11/2 61/4 4 21/4 20700 18460 1614
21/4 4 4 11/2 61/4 4 21/4 27200 24260 1562
21/2 4 4 11/2 61/4 4 21/4 33500 29880 1506

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
130 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 331 - Turnbuckle


Size Range — 3/8" thru 2" machine thread
Material — Forged Steel
Function — Standard turnbuckle tapped right and left hand
which provides 6" take up (3" rod take out).
Approvals — Conforms to Federal Specification
WW-H-171E, Type 13, 3/8" thru 11/2" rod, and Manufacturers
Standardization Society SP-69, Type 13.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish.
Order By — Figure number, rod size and finish

Dimensions • Weights
Rod Size Max. Rec. Approx.
A B C D E Load Lbs. Wt./100
3/8 6 9/16 7/8 71/8 610 42
1/2 6 3/4 11/8 71/2 1130 65
5/8 6 15/16 13/8 77/8 1810 98
3/4 6 11/8 111/16 81/4 2270 145
7/8 6 15/16 115/16 85/8 3770 185
1 6 11/2 21/4 9 4960 260
11/8 6 19/16 25/8 91/8 6230 406
11/4 6 19/16 25/8 91/8 8000 400
11/2 6 17/8 3 93/4 11630 615
13/4 6 23/16 35/8 103/8 15690 980
2 6 21/2 43/16 11 20690 1400

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 131
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 332 - Bridge Clevis


Size Range — 3/8" thru 4" rod
Material — Forged Steel
Function — For use on high temperature piping
installations providing hanger rod adjustability.
Features — Complies fully with code for pressure
piping. Supports loads equal to the full limitation of
the hanger rod.
Available with pin and cotter pins, if required.
Approvals — Conforms to Federal Specification
WW-H-171E, Type 14, and Manufacturers
Standardization Society SP-69, Type 14.
Finish — Plain
Note — Available in Electro-Galvanized and HDG
finish.
Order By — Figure number, rod size and finish. If pin
and cotter pins are required, specify “with pin.” If other
than standard combination of clevis size and rod tap-
ping is required, specify clevis number, special rod
tapping size and grip.

Dimensions • Weights
Rod Max. Rec. Load Lbs.**
Size Tap Pin Size For Service Temps. Approx. Wt. Each
No. Size A D N P T W Grip 650°F 750°F W/O Pin W/Pin
2 3/8 3 /16
11
1 /16
7
5/8 1/2 5/16 1 /16
1
1/2 610 540 .90 1.00
2 1/2 311/16 17/16 5/8 5/8 5/16 11/16 1/2 1130 1010 .70 .90
2 5/8 311/16 17/16 5/8 3/4 5/16 11/16 5/8 1810 1610 .70 .90
21/2 3/4 5 2 7/8 7/8 3/8 11/4 3/4 2710 2420 2.50 3.00
21/2 7/8 5 2 7/8 1 3/8 11/4 7/8 3770 3360 2.50 3.40
3 1 5 3 15/16 11/8 1/2 11/2 1 4960 4420 4.00 5.10
3 11/4 5 3 15/16 13/8 1/2 11/2 11/4 8000 7140 3.80 5.50
31/2 11/2 6 31/2 15/8 15/8 1/2 13/4 11/2 11630 10370 6.00 8.50
4 13/4 6 4 13/4 17/8 1/2 2 11/2 15700 14000 8.00 12.90
5 2 7 5 21/4 21/4 5/8 21/2 21/2 20700 18460 16.00 23.30
6 21/4 8 6 23/4 21/2 3/4 3 21/2 27200 24260 26.00 35.10
6 21/2 8 6 23/4 23/4 3/4 3 21/2 33500 29880 25.50 36.00
7 23/4 9 7 3 3 7/8 31/2 21/2 41580 37066 36.00 50.00
7 3 9 7 3 31/4 7/8 31/2 21/2 50580 45085 35.00 51.50
8 31/4* 10 8 4 31/2 11/2 4 4 60480 53906 90.00 116.00
8 31/2* 10 8 4 33/4 11/2 4 4 71280 63493 88.00 118.00
8 83/4* 10 8 4 4 11/2 4 4 82890 73855 86.00 120.00
8 4* 10 8 4 41/4 11/2 4 4 95400 85001 84.00 122.00
* Furnished with 8 UN series threads.
** Based on the allowable stresses shown in the ANSI Code for Pressure Piping.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
132 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 3/18/2002

Fig. 333 - Extension Piece


Size Range — 3/8 thru 7/8" rod
Material — Malleable Iron
Function — For use in attaching hanger rod to other
attachments. (Use with fig. 329.)
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish.
Order By — Figure number, rod size and finish

Dimensions • Weights
Pipe Rod Size Max. Rec. Approx.
Size A B C D E F Load Lbs. Wt./100
3/4 - 2 3/8 21/16 9/16 1/2 1/2 1/2 610 20
21/2 - 31/2 1/2 25/16 11/16 5/8 1/2 5/8 1130 40
4- 5 5/8 27/16 3/4 5/8 1/2 5/8 1550 44
6 3/4 27/8 7/8 5/8 1/2 5/8 2100 65
8- 12 7/8 3 7/8 3/4 9/16 3/4 2350 78
* With minimum Safety Factor of 5 at maximum temperature of 450°F.

Fig. 335 - Adjustable Side Beam Clamp


Size Range — 2" thru 12" flange size
Material — Carbon Steel
Function — Recommended for attachment to I-beams and wide flange
beams where it is desirable for the rod and pipe to be suspended from
the edge of flange.
Approvals — Conforms to Federal Specification WW-H-171E, Type 53
and Manufacturers Standardization Society SP-69, Type 25.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or Stainless
Steel Materials
Order By — Figure number, rod size, width and thickness of flange and
finish.

Dimensions • Weights
Rod Size Flange Max. Rec. Approx.
A B Width Load Lbs.* Wt./100
3/8 21/16 3" - 9" 300 20
1/2 25/16 3" - 9" 500 40
5/8 27/16 3" - 9" 700 44
3/4 27/8 3" - 9" 800 65
7/8 3 3" - 9" 1200 78
* With minimum Safety Factor of 5 at maximum temperature of 450°F.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 133
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 336 - Adjustable Beam Clamp


Size Range — 3/8 thru 5/8" rod
Material — Carbon Steel
Function — Fits structural I-Beams and wide flange
beams, flange widths 31/2" to 8", thickness up to 1/2".
Approvals — Conforms to Federal Specification
WW-H-171E, Type 54, and Manufacturers Standardization
Society SP-69, Type 27.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish
or Stainless Steel materials.

Dimensions • Weights
Rod Size Max. Rec. Approx.
A B C Load Lbs. Wt./100
3/8 23/4 11/16 300 109
1/2 23/4 1 700 167
5/8 23/4 15/16 1000 223

Fig. 337 - Adjustable Beam Attachment


Size Range — 3/8" thru 7/8" rod
Material — Carbon Steel
Function — Designed for attaching hanger rod to bottom
flange or beam or ceilings allowing for vertical adjustment
where required.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish
or Stainless Steel Materials
Order By — Figure number, rod size and finish.

Dimensions • Weights
Rod Size Max. Rec. Approx.
A B C D E F Load Lbs. Wt./100
3/8 23/4 37/8 47/8 7/16 21/8 610 53
1/2 31/8 43/4 6 9/16 25/16 1130 129
5/8 31/8 43/4 6 9/16 23/16 1810 128
3/4 311/16 61/4 73/4 11/16 29/16 2710 196
7/8 33/4 63/8 81/4 13/16 21/2 3770 282

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
134 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 343 - Welding Lug


Size Range — Short lug is available for use with 1/2"
thru 33/4" rod; long lug may be used with 1/2" thru 2"
rod.
Material — Carbon Steel
Function — Used for attachment to structural steel.
The lugs are designed to be used in conjunction with
Fig. 332 Bridge Clevis.
Approvals — Manufacturers Standardization Society
SP-69, Type 57.
Finish — Plain
Order By — Figure number and rod size, short or
long.

Dimensions • Weights
Rod H Max. Rec. Approx. Wt./100
Size PIN D F Short Long R T W Load Lbs. Short Long
1/2 5/8 1 11/16 11/2 3 1 1/4 2 1130 33 54
5/8 3/4 1 13/16 11/2 3 1 1/4 2 1810 32 53
3/4 7/8 11/4 15/16 11/2 3 11/4 3/8 21/2 2710 64 104
7/8 1 11/4 11/8 2 3 11/4 3/8 21/2 3770 74 101
1 11/8 11/2 11/4 2 3 11/2 1/2 3 4960 121 164
11/8 11/4 11/2 13/8 3 4 11/2 1/2 3 6230 160 203
11/4 11/2 2 15/8 3 4 2 5/8 4 8000 288 359
11/2 13/4 21/2 17/8 3 41/2 21/2 3/4 5 11630 469 629
13/4 2 21/2 21/8 3 41/2 21/2 3/4 5 15700 453 613
2 21/4 3 23/8 4 41/2 3 3/4 6 20630 718 782
21/4 21/2 3 25/8 41/2 — 3 3/4 6 23000 761 —
21/2 23/4 4 27/8 41/2 — 4 1 8 30550 1552 —
23/4 3 4 31/8 41/2 — 4 1 8 41600 1518 —
3 31/4 4 33/8 5 — 4 1 8 50500 1596 —
31/4 31/2 41/2 35/8 5 — 41/2 1 9 60500 1888 —
31/2 33/4 41/2 37/8 6 — 41/2 11/2 9 71300 3153 —
33/4 4 41/2 41/8 6 — 41/2 13/4 9 82900 3601 —

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 135
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 405 - Anchor Hold Down Clamp


Size Range — 2" thru 30" pipe
Material — Carbon Steel
Function — Designed for use where pipe is
anchored to concrete piers or other supports.
Fig. 406 Base Plate is recommended for use on
rough or uneven surfaces.
Maximum Temperature — 650°F
Finish — Plain
Note — Available in Electro-Galvanized and
HDG finish or Stainless Steel materials
Order By — Figure number, pipe size and finish.
Order Fig. 406 separately.

Dimensions • Weights
Pipe Hole Size Approx.
Size A B C D E F Wt./100
2 15/16 53/8 75/8 11/2 7/8 13/16 306
21/2 13/16 57/8 81/8 11/2 7/8 17/16 348
3 11/2 61/2 83/4 11/2 7/8 13/4 409
31/2 13/4 7 91/4 11/2 7/8 2 449
4 2 71/2 93/4 11/2 7/8 21/4 491
5 29/16 89/16 1013/16 11/2 7/8 213/16 581
6 31/16 105/8 135/8 3 1 35/16 1818
8 44/16 125/8 155/8 3 1 45/16 2400
10 51/8 151/4 183/4 21/2 11/8 53/8 3786
12 61/8 171/4 203/4 21/2 11/8 63/8 4546
14 63/4 181/2 22 3 11/8 7 6800
16 73/4 201/2 24 3 11/8 8 7600
18 83/4 221/2 26 31/2 11/8 9 10800
20 93/4 241/2 28 31/2 11/8 10 12000
24 113/4 281/2 32 31/2 11/8 12 13900
30 143/4 341/2 38 31/2 11/8 15 16200

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
136 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 406 - Anchor Base Plate


Size Range — 2" thru 30" pipe
Material — Carbon Steel
Function — To provide a smooth and even bearing
surface on which to place pipe. Can also be used
to locate and set anchor bolts.
Finish — Plain
Note — Available in Electro-Galvanized and HDG
finish or Stainless Steel materials
Order By — Figure number, pipe size and finish.

Dimensions • Weights
Pipe Hole Size Approx.
Size A B C D E F Wt./100
2 11/8 53/8 75/8 11/2 — 7/8 230
21/2 11/8 57/8 81/8 11/2 — 7/8 246
3 11/8 61/2 83/4 11/2 — 7/8 266
31/2 11/8 7 91/4 11/2 — 7/8 281
4 11/8 71/2 93/4 11/2 — 7/8 297
5 11/8 89/16 1013/16 11/2 — 7/8 331
6 11/2 105/8 135/8 3 — 1 1131
8 11/2 125/8 155/8 3 — 1 1300
10 13/4 151/4 183/4 11/2 5 11/8 2059
12 13/4 171/4 203/4 11/2 5 11/8 2285
14 13/4 181/2 22 2 6 11/8 3046
16 13/4 201/2 24 2 6 11/8 3328
18 13/4 221/2 26 21/2 7 11/8 4343
20 13/4 241/2 28 21/2 7 11/8 4682
24 13/4 281/2 32 21/2 7 11/8 5358
30 13/4 341/2 38 21/2 7 11/8 6374

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 137
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 420 - Pipe Alignment Guide — Long Traverse


Fig. 421 - Pipe Alignment Guide — Intermediate Traverse
Size Range — (Fig. 420 and Fig. 421) 3/4" thru 24" pipe
Material — Carbon Steel
Function — To maintain alignment of piping through its axial expansion and contraction cycles. Normally, two or more
pipe alignment guides are used on a single piping run to avoid a pivoting effect within the piping system. It is recom-
mended that the first guide should be located a maximum of four pipe diameters from an expansion joint. Additional
guides should be employed in accordance with the guide spacing data shown below. Additional supports are usually
required between the intermediate guides to comply with the standard support practice.
Installation — The base is set to elevation and welded or bolted to a supporting structure. With the upper half
removed, the pipe or tube with spider attached is set into the base and completely insulated. The upper half is then
bolted into place to complete the guide.
Note — Spider attachments to pipe or tube must be properly located during installation to insure that a minimum of
one-half of the spider width remains within the length of the casing for all conditions of operation. See table for maxi-
mum recommended travels. If larger travels are required, special guides can be furnished to special order. Guide
casings can be rotated in manufacturing to decrease pipe centerlines. SPECIFY WHEN ORDERING.
Maximum Temperature — 650°F
Finish — Casing and Spider — One shop coat paint. Bolts and Nuts — Electro Galvanized. Also available in HDG
finish. Specify.
Order By — Figure number, standard pipe size and insulation thickness. If other than standard pipe is used, specify
type and O.D.

Recommended Expansion Joint Guide Spacing


Maximum Distance (Feet) Between Intermediate Guides for Pressure (PSIG)
Pipe
Size 50 100 150 200 250 300 350 400 500 600
2 38 27 22 20 18 17 15 14 13 12
21/2 52 37 32 27 25 23 22 19 17 16
3 66 47 40 35 31 28 27 25 23 20
31/2 85 62 51 45 40 36 35 32 29 27
4 103 75 62 54 50 45 42 40 35 32
5 118 85 70 60 55 50 46 43 40 35
6 120 87 72 62 57 52 48 45 41 37
8 130 95 78 68 61 57 52 49 45 41
10 145 105 87 75 68 62 58 55 50 45
12 155 110 92 80 73 68 62 58 53 49
14 180 128 105 90 83 75 70 65 60 54

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
138 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 420 - Pipe Alignment Guide — Long Traverse

Dimensions • Weights
Pipe Hole Size Max. Insul. Approx.
Size A B C D # Thickness Wt./100
3/4 85/16 413/16 4 53/4 5/8 111/16 2430
1 85/16 413/16 4 53/4 5/8 19/16 2890
11/4 85/16 413/16 5 53/4 5/8 13/8 3261
11/2 91/4 53/4 5 6 5/8 113/16 3257
2 111/4 79/16 6 65/8 7/8 23/8 4017
21/2 111/4 79/16 6 65/8 7/8 21/8 4050
3 111/4 79/16 6 65/8 7/8 13/4 4200
31/2 131/4 91/8 71/2 81/8 7/8 25/16 4483
4 131/4 91/8 71/2 81/8 7/8 21/16 4491
5 153/4 111/2 81/2 93/8 7/8 211/16 5771
6 153/4 111/2 81/2 93/8 7/8 23/16 7045
8 195/16 15 10 127/16 7/8 215/16 7495
10 213/4 173/8 11 1311/16 11/8 215/16 9045
12 237/8 193/8 12 141/4 11/8 215/16 9901
14 27 205/8 13 153/4 11/8 215/16 10614
16 29 225/8 14 171/16 11/8 215/16 12298
18 311/4 251/4 15 185/8 11/8 31/4 13393
20 335/8 271/4 16 193/8 11/8 31/4 14062
24 365/8 311/4 17 2311/16 11/8 31/4 15406

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 139
www.tolco.com

www.tolco.com
a brand of
®
Revision 11/14/2001

Fig. 421 - Pipe Alignment Guide — Intermediate Traverse

Dimensions • Weights
Pipe Hole Size Max. Insul. Approx.
Size A B C D E F G Thickness Wt./100
3/4 85/16 413/16 4 53/4 5/8 2 4 111/16 1083
1 85/16 413/16 4 53/4 5/8 2 4 19/16 1090
11/4 85/16 413/16 5 53/4 5/8 2 4 13/8 1213
11/2 91/4 53/4 5 6 5/8 2 4 113/16 1245
2 111/4 79/16 6 65/8 7/8 2 4 23/8 1507
21/2 111/4 79/16 6 65/8 7/8 2 4 21/8 1509
3 111/4 79/16 6 65/8 7/8 2 4 13/4 1510
31/2 131/4 91/8 71/2 81/8 7/8 4 6 25/16 2443
4 131/4 91/8 71/2 81/8 7/8 4 6 21/16 2494
5 153/4 111/2 81/2 93/8 7/8 5 8 211/16 4122
6 153/4 111/2 81/2 93/8 7/8 5 8 23/16 5055
8 195/16 15 10 127/16 7/8 5 8 215/16 5414
10 213/4 173/8 11 1311/16 11/8 5 8 215/16 6673
12 237/8 193/8 12 141/4 11/8 5 8 215/16 7290
14 27 205/8 13 153/4 11/8 5 8 215/16 7818
16 29 225/8 14 171/16 11/8 5 8 215/16 9130
18 311/4 251/4 15 185/8 11/8 5 8 31/4 9924
20 335/8 271/4 16 193/8 11/8 5 8 31/4 10434
24 365/8 311/4 17 2311/16 11/8 5 8 31/4 11464

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
140 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
®
Revision 5/24/2001
a brand of

Fig. 422 - Light Weight Pipe Alignment Guide


Function — For maintaining alignment of piping through its axial
expansion and contraction cycles.
Material and Finish — Carbon Steel, black and galvanized.
Order By — Figure number, pipe size and insulation thickness.

Dimensions • Weights
Pipe Hole Size Max. Insul. Approx.
Size A B C D E F G H Thickness Wt./100
3/4 65/8 43/8 55/16 31/8 5 11/2 3 5/8 15/8 400
1 81/2 61/4 55/8 31/2 61/4 11/2 3 5/8 15/8 400
11/4 81/2 61/4 55/8 31/2 61/4 11/2 3 5/8 15/8 630
11/2 81/2 61/4 55/8 31/2 61/4 11/2 3 5/8 15/8 630
2 81/2 61/4 55/8 31/2 61/4 11/2 3 5/8 15/8 630
21/2 91/2 71/4 75/8 4 63/4 11/2 3 5/8 21/8 760
3 113/4 91/2 93/4 5 73/8 11/2 3 5/8 21/8 1260
31/2 113/4 91/2 93/4 5 73/8 11/2 3 5/8 21/8 1260
4 113/4 91/2 93/4 5 73/8 11/2 3 5/8 21/8 1260
5 135/8 105/8 119/16 61/4 73/8 2 4 5/8 21/8 1260
6 155/8 125/8 139/16 71/4 8 2 4 5/8 25/8 1920
8 181/4 151/4 161/8 81/2 93/4 2 4 3/4 25/8 2860

Size J Max. Movement


1" - 4" 4 4
5" - 8" 6 6

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 141
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 422C - Copper Tubing Light Weight Pipe Alignment Guide


Size Range — 3/4" thru 6" pipe
Material — Carbon Steel
Function — For maintaining alignment of piping through its axial
expansion and contraction cycles.
Material and Finish — All surfaces are coated with a protective black
enamel paint.
Order By — Figure number, tube size and insulation thickness.

Dimensions • Weights
Pipe Actual Tube Hole Size Max. Insul. Approx.
Size O.D. A B C D E Thickness Wt./100
3/4 7/8 65/8 43/8 31/8 5 5/8 15/8 400
1 11/8 65/8 43/8 31/8 5 5/8 15/8 400
11/4 13/8 81/2 61/4 31/2 61/4 5/8 15/8 630
11/2 15/8 81/2 61/4 31/2 61/4 5/8 15/8 630
2 21/8 81/2 61/4 31/2 61/4 5/8 15/8 630
21/2 25/8 91/2 71/4 4 63/4 5/8 21/8 760
3 31/8 113/4 91/2 5 73/8 5/8 21/8 1260
31/2 35/8 113/4 91/2 5 73/8 5/8 21/8 1260
4 41/8 113/4 91/2 5 73/8 5/8 21/8 1260
5 51/8 113/4 91/2 5 73/8 5/8 21/8 1260
6 61/8 135/8 105/8 61/4 73/8 5/8 21/8 1920

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
142 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 425 - PTFE Bearing Pads and Strips


Size Range — “Overall Thickness” includes PTFE
and Backing Plate — PTFE is always 3/23" thick.
Material — PTFE and metal backing
Note — Available in Electro-Galvanized and HDG
finish. Stainless Steel or Aluminum materials

Dimensions • Weights
“Overall Thickness”
Description (Inches)
1010 7/32
1025 11/32
1050 19/32
1075 27/32
10100 13/32

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 143
www.tolco.com

www.tolco.com
a brand of
®
Revision 6/12/2003

Fig. 426 - T-Pipe Slide PTFE


Fig. 426G - T-Pipe Slide PTFE with Gussets
Fig. 426C - T-Pipe Slide PTFE with Clamps
Size Range — 1" thru 36" pipe
Material — Carbon Steel and PTFE
Function — An economical sliding support
for all pipe sizes subject to movement in two
planes. Designed for minimum heat loss
transmission through the shoe. Can be
welded or clamped to the pipe. Use only
with PTFE slide plate.
Finish — Plain
Note — Available in Electro-Galvanized and
HDG finish or Stainless Steel materials.
Order By — Figure number, type and size

Dimensions • Weights
Type 1 (2" Insulation) Max. 4" Travel
Pipe Max. Approx.
Size A B C D E L T Load* Wt./Each
1 - 4 21/2 23/4 11/2 — 3 6 1/4 6000 2
5 - 8 3 31/4 2 — 3 6 5/16 8000 3 H Dimensions
10 - 14 4 31/4 3 — 3 6 1/4 12000 3 Pipe Type Type Type
16 - 20 6 31/4 — 2 3 6 1/4 16000 5 Size 1 2 3
24 - 30 6 31/4 — 2 3 6 1/4 16000 5 1 33/8 47/8 57/8
11/4 39/16 51/16 61/16
Type 2 (3" Insulation) Max. 6" Travel 11/2 311/16 53/16 63/16
Pipe Max. Approx. 2 315/16 57/16 67/16
Size A B C D E L T Load* Wt./Each 21/2 43/16 511/16 611/16
1-4 211/16 41/4 11/2 — 4 9 3/16 6000 4 3 41/2 6 7
5-8 4 41/4 21/2 — 4 9 1/4 10000 5 31/2 43/4 61/4 71/4
10 - 14 4 41/4 3 — 4 9 1/4 12000 6 4 5 61/2 71/2
16 - 20 61/2 41/4 — 2 4 9 1/4 16000 10 5 6 7 8
24 - 30 61/2 41/4 — 2 4 9 1/4 16000 10 6 69/16 79/16 89/16
36 8 41/4 — 2 4 9 5/16 16000 13 8 79/16 89/16 99/16
10 85/8 95/8 105/8
Type 3 (4" Insulation) Max. 9" Travel 12 95/8 105/8 115/8
Pipe Max. Approx. 14 101/4 111/4 121/4
Size A B C D E L T Load* Wt./Each 16 111/4 121/4 141/4
1-4 211/16 51/4 11/2 — 6 12 3/16 6000 5 18 121/4 131/4 151/4
5-8 4 51/4 21/2 — 6 12 1/4 10000 8 20 131/4 141/4 161/4
10 - 14 4 51/4 3 — 6 12 1/4 12000 8 24 151/4 161/4 181/4
16 - 20 61/2 61/4 — 2 6 12 1/4 16000 15 30 181/4 191/4 211/4
24 - 30 61/2 61/4 — 2 6 12 1/4 16000 15 36 — 221/4 241/4
36 8 61/4 — 2 6 12 5/16 16000 21
* Based on using 2" wide PTFE slide plate at 70°F temperature

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
144 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 426A - T-Pipe Anchor


Fig. 426AG - T-Pipe Anchor with Gussets
Fig. 426AC - T-Pipe Anchor with Clamps
Size Range — 1" thru 24" pipe
Material — Carbon Steel
Function — Designed to anchor pipe and restrict pipe
movement in every direction. The pipe is normally welded
directly to the anchor and the anchor chair is either bolted
or welded to the supporting steel structure.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number and size

Fig. 426AG - Pipe Anchor with Gussets


Fig. 426A Pipe Anchor
Fig. 426AC - Pipe Anchor with Clamps (4" thru 24")
PIpe Approx. Approx.
Size A B C H Wt./100 Size H Wt./100
2 4 4 1111/16 53/16 8 1 411/16 600
21/2 4 4 215/16 57/16 8 11/4 413/16 600
3 4 4 33/16 53/4 8 11/2 415/16 600
31/2 4 4 311/32 6 8 2 53/16 600
4 4 4 31/2 61/4 8 21/2 57/16 600
5 4 4 325/32 613/16 8 3 53/4 600
6 4 4 41/16 75/16 8 31/2 6 600
8 4 4 51/8 85/16 10 4 61/4 600
10 4 4 63/16 93/8 10 5 513/16 600
12 4 4 73/16 103/8 10
14 4 4 713/16 11 10
16 4 4 813/16 12 11
18 7 4 10 13 18
20 7 4 11 14 19
24 7 4 13 16 20

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 145
www.tolco.com

www.tolco.com
a brand of
®
Revision 10/24/2001

Fig. 427 - U-Pipe Slide PTFE


Size Range — 6" thru 36" pipe
Material — Carbon Steel and PTFE
Function — To provide a support with a low center of gravity for
greater stability on all sizes of pipe with bi-directional movements.
Recommended for use where concentrated and eccentric loads
tend to rotate the pipe. Can be welded or clamped to the pipe.
Use only with Fig. 429 Type 1 PTFE slide plate.
Nominal Insulation Thickness — Pipe sizes 6" and 8", 21/2"; pipe
sizes 10" thru 20", 3" pipe sizes 24" thru 36", 31/2"
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number and pipe size

Dimensions • Weights
Pipe Max. Max. Approx.
Size A B C D H L Travel Load # Wt./Each
6 4 31/4 21/2 — 6 6 4 7000 3
8 4 31/4 21/2 — 73/16 6 4 7000 3
10 6 33/4 — 11/2 81/4 9 7 12000 13
12 6 33/4 — 11/2 93/8 9 7 12000 13
14 7 33/4 — 11/2 93/4 9 7 12000 14
16 7 33/4 — 11/2 107/8 9 7 12000 14
18 9 33/4 — 2 119/16 9 7 16000 17
20 9 33/4 — 2 1211/16 9 7 16000 17
24 12 4 — 3 145/8 12 10 24000 34
30 13 41/4 — 3 173/4 12 10 24000 31
36** 18 41/4 — 4 197/8 12 10 24000 48
* Based on using 2" wide PTFE slide plate at 70°F temperature.
** Denotes use of stiffeners.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
146 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 428 - H-Pipe Slide PTFE


Size Range — 6" thru 36" pipe
Material — Carbon Steel and PTFE
Function — A heavy duty pipe slide support for larger pipes with
heavy loads at maximum spans and where movement is lateral as
well as axial. Also recommended for use as a tank support. Must
be used with slide plate.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, pipe size and finish

Dimensions • Weights
Pipe Max. Max. Wt. Per Approx.
Size A B C D H L Travel Load # C Pcs. Wt./100
6 6 41/2 3 — 75/16 9 7 12000 1315 1500
8 6 41/2 3 — 87/16 9 7 12000 1315 1500
10 8 41/2 4 — 91/8 9 7 16000 1291 1300
12 8 41/2 4 — 101/4 9 7 16000 1291 1300
14 10 41/2 — 2 107/16 9 7 16000 1531 1500
16 10 11/2 — 2 119/16 9 7 16000 1531 1500
18 12 45/8 — 2 121/4 9 7 16000 2154 2200
20 12 45/8 — 2 137/16 9 7 16000 2154 2200
24 14 43/4 — 3 155/16 12 10 24000 4080 4100
30 16 53/4 — 3 191/4 12 10 24000 5000 5200
36 18 61/4 — 3 225/8 12 10 24000 5950 5900
* Based on using 2" wide PTFE slide plate at 70°F temperature.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 147
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 429 - Slide Plate PTFE


Material — Carbon Steel and PTFE
Function — Base support for pipe slides. Wider
and longer pads can be furnished for heavier
load and greater movements. Slide plates must
be attached to supporting beam or structure by
bolting or tack welding. They are not structural
members in themselves. Use only with PTFE
pipe slides.
Finish — Plain
Note — Available in Electro-Galvanized and HDG
finish or Stainless Steel materials.
Order By — Figure number, type and size.
Indicate if bolt holes are required.

Dimensions • Weights
Approx.
Size A B C D E F G H T Wt./Each
1 61/2 5 — 3 2 4 2 3/8 1/8 1
2 101/2 9 — 3 2 8 2 3/8 1/8 2
3 141/2 13 — 3 2 12 2 3/8 1/8 2
4 181/2 17 91/4 4 3 16 2 7/16 3/16 5
5 221/2 21 111/4 4 3 20 2 7/16 3/16 6
6 261/2 25 131/4 4 3 24 2 7/16 3/16 7
7 7 51/2 — 6 41/2 4 3 3/8 1/8 2
8 11 91/2 — 6 41/2 8 3 3/8 1/8 3
9 15 131/2 — 6 41/2 12 3 7/16 3/16 6
10 21 191/2 101/2 6 41/2 18 3 7/16 3/16 9
11 27 251/2 131/2 6 41/2 24 3 7/16 3/16 11
12 40 38 20 6 41/2 36 3 7/16 3/16 17

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
148 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 430 - PTFE Guided Slide Plate


Material — Carbon Steel and PTFE
Function — Supports pipe slide where only axial
movement is allowed. Acts as horizontal restraint
in one direction. Slide plate must be attached to
supporting beam or structure by bolting or tack
welding. They are not structural members in
themselves. Use only with PTFE slides.
Finish — Plain
Note — Available in Electro-Galvanized and HDG
finish or Stainless Steel materials.
Order By — Figure number, type and size.
Indicate if bolt holes are required.

Dimensions • Weights
Slide Approx.
Size Width A B C D E F H J K Wt./Each
A 23/4 5 41/4 27/8 3 21/4 2 13/16 5/16 7/16 1
B 3 5 41/4 31/8 3 21/4 2 13/16 5/16 7/16 1
C 4 7 6 41/8 4 3 3 13/4 7/16 1/2 3
D 6 10 81/2 61/4 6 41/2 6 17/8 9/16 5/8 9
E 61/2 10 81/2 63/4 6 41/2 61/2 17/8 9/16 5/8 9
F 7 12 101/2 71/4 6 41/2 7 17/8 9/16 5/8 10
G 8 12 101/2 81/4 6 41/2 8 17/8 9/16 5/8 10
H 9 14 121/2 91/4 6 41/2 9 17/8 9/16 5/8 11
J 10 14 121/2 101/4 6 41/2 10 17/8 9/16 5/8 12
K 12 15 14 121/4 6 41/2 10 17/8 9/16 5/8 12
L 13 16 15 131/4 6 41/2 10 21/8 9/16 5/8 13
M 14 17 16 141/4 6 41/2 10 21/8 11/16 5/8 14
N 16 21 19 161/4 8 6 12 21/4 11/16 3/4 28
P 18 23 21 181/4 8 6 14 21/4 11/16 3/4 31

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 149
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 431 - PTFE Hold Down Slide Plate


Material — Carbon Steel and PTFE
Function — Supports pipe slide where horizontal
movement in one plane is desired and pipe may
have a tendency to buckle or rotate. Slide plates
must be attached to supporting beam or structure
by bolting or tack welding. They are not structural
members in themselves. Use only with PTFE slides.
Finish — Plain
Note — Available in Electro-Galvanized and HDG fin-
ish or Stainless Steel materials.
Order By — Figure number, type and size. Indicate
if bolt holes are required.

Dimensions • Weights
Slide Approx.
Size Width A B C D E F H J K Wt./Each
A 21/2 5 41/4 27/8 3 21/4 2 17/16 5/16 7/16 2
B 3 5 41/4 31/8 3 21/4 2 17/16 5/16 7/16 3
C 4 7 6 41/8 4 3 3 11/2 7/16 1/2 3
D 6 10 81/2 61/4 6 41/2 6 15/8 9/16 5/8 6
E 61/2 10 81/2 63/4 6 41/2 61/2 17/8 9/16 5/8 12
F 8 12 101/2 81/4 6 41/2 7 17/8 9/16 5/8 13
G 10 14 121/2 101/4 6 41/2 10 17/8 9/16 5/8 14
H 12 15 14 121/4 6 41/2 10 17/8 9/16 5/8 16
J 14 17 16 141/4 6 41/2 10 21/8 9/16 5/8 18
K 16 21 19 161/4 8 41/2 12 21/4 11/16 3/4 21
L 18 23 21 181/4 8 41/2 14 21/4 11/16 3/4 36

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
150 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
®
Revision 5/24/2001
a brand of

Fig. 432 - Slide Plate for TOL-Strut™ Channel PTFE


Material — Carbon Steel and PTFE
Function — To support pipe slides used with
TOL-Strut channel. To allow pipe to move freely
in the horizontal plane.
Finish — Plain
Note — Available in Electro-Galvanized and HDG fin-
ish or Stainless Steel materials.
Order By — Figure number and size

Dimensions • Weights
Approx
Size A B Wt./100
1 4 3 41
2 8 7 67
3 12 10 93
4 16 14 119
5 20 18 145
6 24 22 171

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 151
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 433 - Copper Tube Clamp


Size Range — 2" thru 12" copper tube
Material — Carbon Steel
Function — To be used with and where pipe slides
cannot be welded directly to the copper tube.
Recommended for galvanized, stainless and coated
pipe. When used with plastic or aluminum pipe, a
thin protective liner should be inserted between the
pipe and the clamp.
Finish — Plain
Note — Available in Electro-Galvanized finish
Order By — Figure number, copper tube size, pipe
size and figure number. Indicate welded or loose for
field weld and finish.

Dimensions • Weights
Pipe Approx.
Size L M N P Q Wt./100
2 6 41/2 35/8 1/4 41/2 200
21/2 6 5 41/8 1/4 41/2 300
3 6 51/2 45/8 1/4 41/2 300
31/2 6 6 51/8 1/4 41/2 300
4 6 61/2 55/8 1/4 41/2 400
5 6 71/2 65/8 1/4 41/2 400
6 9 9 77/8 1/2 6 1100
8 9 11 97/8 1/2 6 1400
10 9 13 117/8 1/2 6 1700
12 9 15 137/8 1/2 6 2000

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
152 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 434 - IPS Clamp


Size Range — 2" thru 24" copper tube
Material — Carbon Steel
Function — To be used with and where pipe slides
cannot be welded directly to the pipe. Recommended
for galvanized, stainless and coated pipe. When used
with plastic or aluminum pipe, a thin protective liner
should be inserted between the pipe and the clamp.
Finish — Plain
Note — Available in Electro-Galvanized finish
Order By — Figure number, pipe size, pipe slide size
and figure number. Indicate welded or loose for field
weld and finish.

Dimensions • Weights
Pipe Approx.
Size L M N P Q Wt./100
2 6 43/4 37/8 1/4 41/2 200
21/2 6 5 43/8 1/4 41/2 300
3 6 57/8 5 1/4 41/2 300
31/2 6 63/8 51/2 1/4 41/2 400
4 6 615/16 61/16 1/4 41/2 400
5 6 8 71/8 1/4 41/2 500
6 9 91/2 83/8 1/2 6 1200
8 9 111/2 103/8 1/2 6 1500
10 9 135/8 121/2 1/2 6 1800
12 9 1511/16 149/16 1/2 6 2100
14 12 177/16 1513/16 5/8 8 4100
16 12 197/16 1713/16 5/8 8 4600
18 12 217/16 1913/16 5/8 8 5200
20 12 237/16 2113/16 5/8 8 5700
24 12 271/2 257/8 5/8 8 6700

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92870 • Ph: 909.737.5599 • Fax: 909.737.0330
www.tolco.com
153

www.tolco.com
a brand of
®
Revision 7/3/2001

Fig. 500 - Spring Cushion Fig. 505 — ISO-Flex Enclosed


Note — Made to order; Consult factory for Spring Hanger*
specifications.
Material — Carbon Steel
Function — Light duty spring hanger for use on steam
mains, drain lines, etc.
Approvals — Conforms to Federal Specification
WW-H-171E, Type 49.
Note — Made to order; Consult factory for specifications.

Fig. 506 - Vibration Isolation Fig. 568 - Spring Hanger*


Springs Approvals — Conforms to Federal Specification
WW-H-171E, Type 51, 56 and 57, and Manufacturers
Note — Made to order; Consult factory for Standardization Society SP-69, Type 51, 52 and 53
specifications. Note — Made to order; Consult factory for
specifications.

*Currently unavailable in: Texas, Oklahoma, New Mexico, Arkansas and Louisiana.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
154 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 580 & Fig. 581 Fig. 582 — Short Spring Hanger*
Constant Supports Approvals — Conforms to Federal Specification
Approvals — Constant support hangers conform WW-H-171E, Type 51, 56 and 57 and Manufacturers
to Federal Specification WW-H-171E, Types 52, 58 Standardization Society SP-69, Types 51, 52 and 53..
and 59, and Manufacturers Standardization Society Note — Made to order; Consult factory for specifications.
ANSI/MSS SP-58, Type 54,55 and 56 and
*Currently unavailable in: Texas, Oklahoma, New Mexico, Arkansas and
ANSI B31 1-1980.
Louisiana.
Note — Made to order; Consult factory for
specifications.

Fig. 598 - Double Spring Hanger* Fig. 650 - Sway Brace


Approvals — Conforms to Federal Specification Approvals — Conforms to Federal Specification
WW-H-171E, Type 51, 56 and 57, and Manufacturers WW-H-171E, Type 55, and Manufacturers
Standardization Society SP-69, Type 51, 52 and 53 Standardization Society SP-69, Type 50.
Note — Made to order; Consult factory for Note — Made to order; Consult factory for
specifications. specifications.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 155
www.tolco.com

www.tolco.com
a brand of
®
Revision 8/30/2002

Fig. 800 - Adjustable Sway Brace Attachment to Steel


Size Range — 4" thru 18" beam width Component of State of
California OSHPD Approved
Material — Carbon Steel Seismic Restraints System
Function — Seismic brace attachment to steel.
Features — This product’s design incorporates a concentric attach-
ment point which is critical to the performance of structural seismic
connections. NFPA 13 indicates the importance of concentric loading
of connections and fasteners. Permits secure connection to steel
where drilling and/or welding of brace connection could present struc-
tural issues. Comes completely assembled ready for installation. The
Fig. 800 must be used with one of the TOLCO™ Fig. 900 series brace
fittings (ordered separately).
Installation Instructions — Tighten set bolts against flange until bolt
head breaks off. Tighten hex head bolts into clamp body until lock
washers are fully flat.
Application Note — Allows bracing in either lateral or longitudinal
direction.
Approvals — Underwriters Laboratories Listed in the USA (UL) and
Canada (cUL). Included in our Seismic Restraints Catalog approved
by the State of California Office of Statewide Health Planning and
Development (OSHPD). For additional load, spacing and placement
information relating to OSHPD projects, please refer to the TOLCO
Seismic Restraint Systems Guidelines.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish.
Order By — Figure number, type number and size number.
Important Structural Note:
TOLCO Steel Fig. 65/66 components were used during structural test-
ing and are required to achieve the listed results. Malleable iron com-
ponents must never be substituted because of their serious potential for
fracture and failure.

Dimensions • Weights
*Max. Design Loads/Lbs.
Flange Thickness Along Across
Type Max. (In.) Beam Beam
1 3/4 1265 2015
2 11/4 1265 2015

Dimensions • Weights
*Max. Design Loads/Lbs.
Fits Beam Along Across
Size Range (In.) Beam Beam
1 4 - 6 1265 2015
2 6 - 8 1265 2015
3 8 - 10 1265 2015
4 10 - 12 1265 2015
5 12 - 14 1265 2015
6 14 - 16 1265 2015
7 16 - 18 1265 2015

OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
156 CUSTOMER SERVICE • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 825 - Bar Joist Sway Brace Attachment


Size Range — One size accommodates all TOLCO Fig. 900 Series sway Component of State of
California OSHPD Approved
brace attachments. Maximum Horizontal Design Load 2015 lbs. Seismic Restraints System
Material — Carbon Steel
Function — *To attach sway and hanger assemblies bracing to steel bar
joist structural members..
Features — This product’s design incorporates a concentric attachment
point which is critical to the performance of structural seismic connections.
NFPA 13 indicates the importance of concentric loading of connections and
fasteners. Permits secure non-friction connection without drilling or welding.
Unique design reinforces point of connection to joist. Break off head bolt
design assures verification of proper installation.
Approvals — Underwriters Laboratories Listed in the USA (UL) and
Canada (cUL). Included in our Seismic Restraints Catalog approved by the
State of California Office of Statewide Health Planning and Development
(OSHPD). For additional load, spacing and placement information relating
to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems
Guidelines.
Important Structural Note:
The TOLCO Fig. 825 has significant UL established design loads, however,
structural issues related to the steel joist member require restricted location
installation for all bracing. Steel Joist Manufacturers require that all earth- Maximum Design Load 2015 Lbs.
quake bracing connections be within 6" of the cord panel point. Installation Weight/100 237.5 Lbs.
of the Fig. 825 must be limited to the outer third sections of the joist span.
For installations within the center third section of the joist span, use UL UL Listed as Hanger Attachment
Listed TOLCO Fig. 825A. 6" Pipe Max.
Finish — Plain, Electro-Galvanized and HDG
Order By — Figure number and finish
*Important Note — The Fig. 825 is precision manufactured to perform its
function as a critical component of a complete bracing assembly.
To ensure performance, the UL Listing requires that the Fig. 825 must
be used only with other TOLCO bracing products.
US Patent #6,098,942, Canada Patent #2,286,659

OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266 163
www.tolco.com

www.tolco.com
a brand of
®
Revision 3/28/2003

Fig. 825A - Bar Joist Sway Brace Attachment


Size Range — One size accommodates all TOLCO Fig. 900 Series sway
brace attachments. Maximum Horizontal Design Load 1265 lbs.
Material — Carbon Steel
Function — *To attach sway bracing to steel bar joist structural members.
Features — This product’s design incorporates a concentric attachment
point which is critical to the performance of structural seismic connections.
NFPA 13 indicates the importance of concentric loading of connections and
fasteners. Permits secure non-friction connection without drilling or welding.
Unique design reinforces point of connection to joist. Break off head bolt
design assures verification of proper installation.
Approvals — Underwriters Laboratories Listed in the USA (UL) and
Canada (cUL). For additional load, spacing and placement information
relating to OSHPD projects, please refer to the TOLCO Seismic Restraint
Systems Guidelines.
Important Structural Note:
The TOLCO Fig. 825A has significant UL established design loads, however,
structural issues related to the steel joist member require restricted location
installation for all bracing. Steel Joist Manufacturers require that all earth-
quake bracing connections be within 6" of the cord panel point. Installation Maximum Design Load 1265 Lbs.
of the Fig. 825A is not restricted to the two outer third sections of the joist.
For greater design loads, refer to TOLCO Fig. 825.
Finish — Plain
Order By — Figure number and finish
*Important Note — The Fig. 825A is precision manufactured to perform its
function as a critical component of a complete bracing assembly.
To ensure performance, the UL Listing requires that the Fig. 825A must
be used only with other TOLCO bracing products.
Patent #6,098,942

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
158 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 906 - Sway Brace Multi-Fastener Adapter


Size Range — Use with 1" and 11/4" TOLCO UL listed 900 Series
Earthquake Brace Attachments.
Material — Carbon Steel
Application — Allows sway brace fittings to develop greater load
carrying ability by providing multiple fastener attachments. The
National Fire Protection (NFPA) provides information on fastener
loads to various structures. Refer to NFPA Pamphlet 13 (1996)
Edition, Table 4-14.4.3.5.6.
Approvals — Underwriters Laboratories Listed in the USA (UL)
and Canada (cUL) only when used with TOLCO 900 Series
Earthquake Brace Attachments. Included in our Seismic
Restraints Catalog approved by the State of California Office of
Statewide Health Planning and Development (OSHPD). For
additional load, spacing and placement information relating to
OSHPD projects, please refer to the TOLCO Seismic Restraint
Systems Guidelines.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number and specify dimensions H1 and H2.

Dimensions • Weights
Approx.
A B C D H1 H2 Wt./100
12 9 2 1/4 Specify Specify Varies

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 159
www.tolco.com

www.tolco.com
a brand of
®
Revision 8/01/2003

Fig. 907 - 4-Way Longitudinal Sway Brace Attachment


Size Range — 1" x 1", 1" x 11/4" and 11/4" x 11/4" bracing pipe. Component of State of
California OSHPD Approved
Material — Carbon Steel, hardened cone point engaging screw Seismic Restraints System
Function — For bracing pipe against sway and seismic disturbances,
Functions as as longitudinal brace connection when attached to a lateral brace
pipe. Bracing connection must be positioned as close as physically possible
to the braced pipe (No more than 3" away). Must be used only with TOLCO
bracing components. When used in conjunction with TOLCO Fig. 1000, this
combination bracing restricts piping movement in tension and compression
both laterally and longitudinally.
Features — Universal swivel design allows the Fig. 907 to achieve any angle of
attachment required. Pipe end requires no threads — simply slide bracing
pipes through fittings and tighten each set screw until lock washer is fully
compressed.
Application Note — Length of bracing pipe per NFPA 13, Table 6-4.5.8
(L/R=200); 1" schedule 40 pipe maximum 7’0": 11/4" schedule 40 pipe
maximum 9’0". Alternative pipe materials are currently under review. Please
consult factory.
Approvals — Underwriters Laboratories Listed in the USA (UL) and Canada
(cUL). Included in our Seismic Restraints Catalog approved by the State of
California Office of Statewide Health Planning and Development (OSHPD). For
additional load, spacing and placement information relating to OSHPD projects,
please refer to the TOLCO Seismic Restraint Systems Guidelines.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish.
Order By — Figure number, bracing pipe sizes and finish.
Important Note — The Fig. 907 is precision manufactured to perform its
function as a critical component of a complete bracing assembly. To ensure
performance, the UL Listing requires that the Fig. 907 must be used only
with other TOLCO bracing products. The Fig. 907 is not intended for use
with the Fig. 1001 Sway Brace Attachment.
NATIONAL AND INTERNATIONAL PATENT APPLICATION IN PROCESS.

Dimensions • Weights
Max. Design Approx.
Pipe Size A B Load Lbs.* Wt./100
1x1 43/4 43/4 655* 103
1 x 11/4 51/16 413/16 655* 107
1 /4 x 11/4
1
53/8 51/4 655* 109
* Load will accommodate up to 4" pipe at maximum spacing.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
160 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 2/02/2005

Fig. 909 - No-Thread Swivel Sway Brace Attachment


Size Range — 1" bracing pipe. For brace pipe sizes larger than 1", Component of State of
California OSHPD Approved
use TOLCO Fig. 980. Seismic Restraints System
Material — Carbon Steel, hardened cone point engaging screw
Function — The structural component of a sway and seismic bracing
system.
Features — This product’s design incorporates a concentric attach-
ment opening which is critical to the performance of structural seismic
connections. NFPA 13 (1999 Edition) Table 6-4.5.9 indicates clearly
that fastener table load values are based only on concentric loading.
No threading of the bracing pipe is required. Open design allows for
easy inspection of pipe engagement. All steel construction eliminates
deficiencies associated with malleable type attachments. Fastener
can be mounted to all surface angles.
Application Note — The Fig. 909 is used in conjunction with the
TOLCO Fig. 1000, Fig. 1001, or Fig. 4 (A) pipe clamp, and joined
together with bracing pipe. Install per NFPA 13 and/or TOLCO State
of California OSHPD Approved Seismic Restraint Manual. The
required type, number and size of fasteners used for the structure
attachment fitting shall be in accordance with NFPA13 and/or
OSHPD.
Installation — Extend bracing pipe through opening. Tighten cone
point engaging screw until head bottoms out or minimum torque
23 ft./lbs.
Approvals — Underwriters Laboratories Listed in the USA (UL) and
Canada (cUL). Included in our Seismic Restraints Catalog approved
by the State of California Office of Statewide Health Planning and
Development (OSHPD). For additional load, spacing and placement
information relating to OSHPD projects, please refer to the TOLCO
Seismic Restraint Systems Guidelines.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish.
Order By — Figure number, pipe size and finish.
Important Note — The Fig. 909 is precision manufactured to perform
its function as a critical component of a complete bracing assembly.
Sway brace assemblies are intended to be installed in accordance
with NFPA13 and the manufacturer’s installation instructions. To
ensure performance, the UL Listing requires that the Fig. 909
must be used only with other TOLCO bracing products.
NATIONAL AND INTERNATIONAL PATENT APPLICATION IN
PROCESS.

Dimensions • Weights
Max. Design. Max. Design Load Approx.
Pipe Size A B H* Load Lbs. Lbs. w/Washer Wt./100
1 6 15/8 17/32 2015 2765 91
* Available with hole sizes to accommodate up to 3/4" fastener. Consult Factory.

OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266 167
www.tolco.com

www.tolco.com
a brand of
®
Revision 3/28/2003

Fig. 910 - Swivel Sway Brace Fitting


Size Range — 1" and 11/4" bracing pipe. For brace pipe sizes larger than Component of State of
California OSHPD Approved
11/4", use TOLCO Fig. 980. Seismic Restraints System
Material — Carbon Steel
Function — For bracing pipe against sway and seismic disturbances. The
building attachment component of a sway brace system; the
Fig. 910 is used in conjunction with the Fig. 1001, Fig. 1000 or with a Fig. 4A
Pipe Clamp and joined together with a brace pipe per NFPA 13.
Features — This product’s design incorporates a concentric attachment
opening which is critical to the performance of structural seismic connections.
NFPA 13 (1999 Edition) Table 6-4.5.9 indicates clearly that fastener table load
values are based only on concentric loading. Universal swivel design allows
Fig. 910 to be attached at any surface angle. All steel construction. NFPA
13 (1999 Edition) Table 6-4.5.8: 1" Schedule 40 bracing pipe maximum 7’0".
11/4" Schedule 40
bracing pipe maximum 9’0".
Approvals — Underwriters Laboratories Listed in the USA (UL) and Canada
(cUL). Included in our Seismic Restraints Catalog approved by the State of
California Office of Statewide Health Planning and Development (OSHPD).
For additional load, spacing and placement information relating to OSHPD
projects, please refer to the TOLCO Seismic Restraint Systems Guidelines.
Note — The Fig. 910 Swivel Attachment and the Fig. 1001, Fig. 1000
, or Fig. 4A Pipe Clamp make up a sway brace
system of (UL) Listed attachments and bracing materials which
satisfies the requirements of Underwriters’ Laboratories and the National Fire
Protection Association (NFPA).
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Figure number, pipe size and finish.
Note — Specific weight load conditions may require
more than one fastener to the building surface. Sway
brace attachments may be ordered with multiple
and/or larger fastener mounting holes. Consult the
factory. The Fig. 910 is precision manufactured to per-
form its function as a critical component of a complete
bracing assembly.
To ensure performance, the UL Listing requires that
the Fig. 910 must be used only with other TOLCO
bracing products.

Dimensions • Weights
D Hole Max. Design Approx.
Pipe Size A B C Size E F Load Lbs. Wt./100
1 2 11/2 3 9/16 25/16 2 2015 88
11/4 13/16 15/16 3 9/16 25/16 25/16 2015 99

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
162 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 975 - Straight Sway Brace Fitting


Size Range — 1" bracing pipe. For brace pipe sizes larger than 1",
use TOLCO Fig. 980.
Material — Carbon Steel
Function — For bracing pipe against sway and seismic disturbances.
The building attachment component of a sway brace system; the
Fig. 975 is used in conjunction with the Fig. 1000, Fig. 1001 or with a
Fig. 4A Pipe Clamp and joined together with a brace pipe per NFPA
13.
Features — Open design allows for easy checking of thread engage-
ment. All steel construction eliminates deficiencies associated with
malleable type attachments.
Application Note — Length of bracing pipe per National Fire
Protection Association Pamphlet NFPA 13, Table 4-5.4.3.5.1(B):
1" Schedule 40 bracing pipe maximum 7’0".
Approvals — Underwriters Laboratories Listed in the USA (UL) and
Canada (cUL).
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or Stainless
Steel materials.
Order By — Figure number and finish.
Note — Specific weight load conditions may require more than one
fastener to the building surface. Sway brace attachments may be
ordered with multiple and/or larger fastener mounting holes. Consult
the factory. Use Fig. 975 in straight position only. Bending of this fit-
ting alters the material strength. Use Fig. 909 or Fig. 910 when angle
fitting is required.
Important Note — The Fig. 975 is precision manufactured to perform
its function as a critical component of a complete bracing assembly.
To ensure performance, the UL Listing requires that the Fig. 975
must be used only with other TOLCO bracing products.

Dimensions • Weights
Hole Max. Design Approx.
Pipe Size A B C Size Load Lbs. Wt./100
1 4 31/2 11/2 9/16 2015 88

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 163
www.tolco.com

www.tolco.com
a brand of
®
Revision 3/28/2003

Fig. 980 - Universal Swivel Sway Brace Attachment


Size Range — One size fits bracing pipe 1" thru 2", TOLCO 12 gauge channel, and all structural Component of State of
California OSHPD Approved
steel up to 1/4" thick. Seismic Restraints System
Material — Carbon Steel
Function — Multi-functional attachment to structure or braced pipe fitting.
Features — This product’s design incorporates a concentric attach-
ment opening which is critical to the performance of structural seismic
connections. NFPA 13 (1999 Edition) Table 6-4.5.9 H
indicates clearly that fastener table load values are based only
on concentric loading. Fits multiple sizes of bracing pipe,
strut or structural steel. Mounts to any surface angle. Break
off bolt head assures verification of proper installation.
Application Note — Install per NFPA 13 and/or TOLCO State
of California (OSHPD) Approved Seismic Restraint Manual.
A
Installation — Place bracing component into jaw fully and tighten bolt until
head breaks off. B
Approvals — Underwriters Laboratories Listed in the USA (UL) and Canada (cUL).
Included in our Seismic Restraints Catalog approved by the State of California Office of
Statewide Health Planning and Development (OSHPD). For additional load, spacing and placement information relat-
ing to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines.
Note — The Fig. 980 Swivel Attachment and the Fig. 1001, Fig. 1000 , Fig. 2001 or Fig. 4A Pipe Clamp make up a
sway brace system of UL Listed attachments and bracing materials which satisfies the requirements of Underwriters’
Laboratories and the National Fire Protection Association (NFPA)
Finish — Plain
Note — Available in Electro-Galvanized finish.
Order By — Figure number and finish.
Important Note — The Fig. 98= is precision manufactured to perform its function as a critical component of a com-
plete bracing assembly. To ensure performance, the UL Listing requires that the Fig. 980 must be used only
with other TOLCO bracing products.
NATIONAL AND INTERNATIONAL PATENT APPLICATION IN PROCESS.

Dimensions • Weights
Max. Design Approx.
A B H* Load Lbs. Wt./100
51/4 17/8 17/32 2765 132
* Available with hole sizes to accommodate up to 3/4" fastener. Consult factory.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
164 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 981 - Fast Attach — Universal Swivel Sway Brace Attachment


Size Range — One size fits bracing pipe 1" thru 2", TOLCO 12 gauge channel,
and all structural steel up to 1/4" thick.
Material — Carbon Steel
Function — Multi-functional attachment to hanger rod, trapeze rod,
structure or braced pipe fitting.
Features — Fits multiple sizes of bracing pipe, strut or structural steel. Swivel
allows adjustment to various surface angles. Break-away bolt head assures
verification of proper installation torque. Unique “fast attach” yoke design allows
Fig. 981 to be installed using hanger rods 3/8" through 3/4" in size. “Stackable”
design allows installation of both lateral and longitudinal braces, as well as
opposing braces, to be easily installed on a single hanger rod, with no
disassembly. The retrofit yoke has a visual verification of proper installation
torque. Tighten existing hex nut down until the slight gap in the yoke assembly
closes completely.
Approvals — Included in our Seismic Restraint Systems Guidelines, approved by
the California Office of Statewide Health Planning and Development (OSHPD).
Finish — Electro-Galvanized
Note — Available in Electro-Galvanized finish.
Order By — Figure number, rod size 3/8" thru 3/4" and finish.
US AND INTERNATIONAL PATENT APPLICATION IN PROCESS.

Dimensions • Weights
Max. Design Approx.
A B C D Load Lbs. Wt./100
51/8 41/8 11/4 21/4 2015 88

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
165 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 8/30/2002

Fig. 990 - Cable Sway Brace Attachment


Size Range — 1/8", 3/16" and 1/4" pre-stretched cable.
3/8" thru 11/4" hanger rod bolt or fastener.
Material — Carbon Steel
Function — Cable attachment for sway bracing.
Attaches sway brace to structure or to hanger. To be
used with 7 x 19 strand core pre-stretched galvanized
aircraft cable.
Features — Cable easily slides into oversized front arch
opening. Breakaway hex nuts assure verification of
proper installation. Will mount to any surface angle.
Finish — Electro-Galvanized
Order By — Figure number, cable size and mounting
hole size.
Note — Order 990H for hanger rod, bolt or fastener hole
size 1" thru 11/4".

Dimensions • Weights
Cable Maximum Design
Diameter A B Load Lbs.
1/8" 45/16" 2" 975*
3/16" 5" 21/4" 2050*
1/4" 5" 25/8" 3150*
* Maximum load rating controlled by cable breaking strength.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
166 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Fig. 991 - Fast Attach — Cable Sway Brace Attachment


Size Range — 1/8", 3/16" and 1/4" pre-stretched cable. Fits rod
size 3/8" thru 3/4".
Material — Carbon Steel
Function — Cable attachment for sway bracing. Attaches sway
brace to support rod. To be used with 7 x 19 strand core pre-
stretched galvanized aircraft cable.
Features — Allows fast attachment to support rod already in place
without costly disassembly. Cable easily slides into oversized front
arch opening. Breakaway hex nuts assure verification of proper
installation.
Finish — Electro-Galvanized

D
Order By — Figure number, cable size and hanger

ON
UE
A TI
N
RM
I
FO
T
Dimensions • Weights
IN
N
Cable Maximum Design
Diameter A B Load Lbs.
T

1/8" 53/4" 21/8" 975*


O
UC

3/16" 63/4" 21/2" 2050*


1/4" 63/4" 21/2" 3150*
* Maximum load rating controlled by cable breaking strength.
OD
S C
PR
I
W
D
NE
E
SE

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 168
www.tolco.com

www.tolco.com
a brand of
®

Revision 10/17/2003

Fig. 991 - Fast Attach — Cable Sway Brace Attachment


Size Range — 1/8", 3/16" and 1/4" pre-stretched cable. Fits rod size
3/8" thru 3/4".
Material — Carbon Steel
Function — Cable attachment for sway bracing. Attaches sway brace to
hanger rod. To be used with 7 x 19 strand core pre-stretched galvanized
aircraft cable.
Features — Fits multiple sizes of cable. Cable easily slides into
oversized front arch opening. Swivel allows adjustment to various
surface angles. Break-away hex nuts assure verification of proper
installation torque. Unique “Fast-Attach” yoke design allows Fig. 991 to
be installed using hanger rods 3/8" through 3/4" in size. “Stackable”
design allows installation of both lateral and longitudinal braces, as well
as opposing braces, to be easily installed on a single hanger rod, with no
disassembly. The retrofit yoke has a visual verification of proper installa-
tion torque. Tighten existing hex nut down until the slight gap in the yoke
assembly closes completely.
Approvals — Included in our Seismic Restraint Systems Guidelines,
approved by the California Office of Statewide Health Planning and
Development (OSHPD).
Finish — Electro-Galvanized
Order By — Figure number, rod size 3/8" through 3/4"
US AND INTERNATIONAL PATENT APPLICATION IN PROCESS.

Dimensions • Weights
Cable Maximum Design
Diameter A B Load Lbs.
1/8" 53/4" 21/8" 975*
3/16" 63/4" 21/2" 2050*
1/4" 63/4" 21/2" 3150*
* Maximum load rating controlled by cable breaking strength.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
167 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 8/30/2002

Fig. 1000 - “Fast Clamp” Sway Brace Attachment


Size Range — Pipe size to be braced: 1" thru 6" Schedule 10 Component of State of
California OSHPD Approved
thru 40.* Pipe size used for bracing: 1" and 11/4" Schedule 40 Seismic Restraints System
IPS.
* Additionally (UL) approved for use to brace Schedule 7
sprinkler pipe up to 4" (maximum horizontal design load
655 lbs.) Torque requirement 6 — 8 ft. lbs.
Material — Carbon Steel
Function — For bracing pipe against sway and seismic
disturbance. The pipe attachment component of a sway brace
system: Fig. 1000 is used in conjunction with a TOLCO™ Fig.
900 Series Fitting and joined together with bracing pipe per
NFPA 13* or TOLCO OSHPD Approved Seismic Manual,
forming a complete sway brace assembly.
Features — Can be used to brace Schedules 7 thru 40 IPS.
Field adjustable, making critical pre-engineering of bracing pipe
unnecessary. Unique design requires no threading of bracing
pipe. Can be used as 4-way riser brace. Can be used as
longitudinal brace with Fig. 907. All steel construction eliminates
structural deficiencies associated with casting type sway brace
fittings. Comes assembled and individually packaged with
illustrated installation instructions — sizes are clearly marked.
Steel leaf spring insert provided to assure installer and inspector
necessary minimum torque has been achieved.
Application Note — Position Fast Clamp and tighten two hex Maximum Design Load
nuts until leaf spring flattens. A minimum of 1" pipe extension 1" thru 4" pipe size — 2015 lbs.
beyond the Fig. 1000 is recommended. 6" size — 1265 lbs.
Approvals — Underwriters Laboratories Listed in the USA (UL)
and Canada (cUL). Included in our Seismic Restraints Catalog
approved by the State of California Office of Statewide Health
Planning and Development (OSHPD). For additional load, spac-
ing and placement information relating to OSHPD projects,
please refer to the TOLCO Seismic Restraint Systems
Guidelines.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By — Order first by pipe size to be braced, followed by
pipe size used for bracing, figure number and finish.
Important Note — The Fig. 1000 is precision manufactured to
perform its function as a critical component of a complete
bracing assembly. To ensure performance, the UL Listing
requires that the Fig. 1000 must be used only with other
TOLCO bracing products.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
168 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 8/01/2003

Fig. 1001 - Sway Brace Attachment


Size Range — Pipe size to be braced: 21/2" thru 8" IPS.* Pipe size used Component of State of
California OSHPD Approved
for bracing: 1" and 1 /4" Schedule 40 IPS.
1
Seismic Restraints System
Material — Carbon Steel
Function — For bracing pipe against sway and seismic disturbance.
The pipe attachment component of a sway brace system: The Fig. 1001
is used in conjunction with a TOLCO™ 900 Series fitting and joined
together with bracing pipe per NFPA 13, forming a complete sway brace
assembly.
Features — *Can be used to brace schedules 7 through 40 IPS. Field
adjustable, making critical pre-engineering of bracing pipe length unnec-
essary. Unique design requires no threading of bracing pipe. Can be
used as a component of a four-way riser brace. Comes assembled and
ready for installation. Fig. 1001 has built-in visual verification of correct
installation. See installation note below.
Installation Note — Position Fig. 1001 over the pipe to be braced Maximum Design Load
and tighten two hex head cone point set bolts until heads bottom Sch 7 - 1600 lbs.
out. A minimum of 1" pipe extension is recommended. Sch 10 & 40 w/1" Brace Pipe - 2015 lbs.
Approvals — Underwriters Laboratories Listed in the USA (UL) and Sch 10 & 40 w/11/4" Brace Pipe - 2765 lbs.
Canada (cUL). Included in our Seismic Restraints Catalog
approved by the State of California Office of Statewide Health Planning
and Development (OSHPD). For additional load, spacing and placement
information relating to OSHPD projects, please refer to the TOLCO
Seismic Restraint Systems Guidelines.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish.
Order By — Indicate pipe size to be braced followed by pipe size used
for bracing, figure number and finish.
Important Note — The Fig. 1001 is precision manufactured to perform
its function as a critical component of a complete bracing assembly. To
ensure performance, the UL Listing requires that the Fig. 1001 must
be used only with other TOLCO
bracing products. The Fig 1001 is not intended for use with the Fig.
907 4-Way Longitudinal Brace Attachment.
NATIONAL AND INTERNATIONAL PATENT APPLICATION IN
PROCESS

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 169
www.tolco.com

www.tolco.com
a brand of
®
Revision 8/30/2002

Fig. 2002 - Sway Brace Attachment


Size Range — Pipe size to be braced: 21/2" thru 8" all steel
schedules, copper, plastic, FRP, cast iron and ductile iron.
Consult factory when bracing other than steel. The Fig. 2002
accepts brace pipes sizes 11/2" and 2" steel schedule 100
through schedule 40.
Material — Carbon Steel
Function — For bracing pipe against sway and seismic distur-
bance. The pipe attachment component of a sway brace sys-
tem: The Fig. 2002 is used in conjunction with a TOLCO™
900 Series sway brace attachments and joined together with
bracing pipe. Install per NFPA 13 and/or TOLCO State of
California OSHPD Approved Seismic Restrain Manual.
Features — Unique design will not damage thin wall, plastic,
copper or ductile iron pipe. Easy verification of proper installa-
tion by tightening bolts until ears touch.
Installation — Place Fig. 2002 over pipe to be braced. Slide
bracing pipe through attachment and tighten hex nuts until
ears touch.
Approvals — Underwriters Laboratories Listed in the USA
(UL) and Canada (cUL). For additional load, spacing and
placement information relating to OSHPD projects, please
refer to the TOLCO Seismic Restraint Systems Guidelines.
Maximum Design Load 2015 Lbs.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish.
Order By — Figure number, pipe size to be braced, pipe size
used for bracing (11/2" or 2") and finish.
Important Note — The Fig. 2002 is precision manufactured to
perform its function as a critical component of a complete
bracing assembly. To ensure performance, the UL Listing
requires that the Fig. 2002 must be used only with other
TOLCO bracing products.

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
170 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Reference

Material

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 171
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

TOLCO Cross Reference Chart


SUPER SUPER
TOLCO GRINNELL B-LINE MCO PHD STRUT TOLCO GRINNELL B-LINE MCO PHD STRUT
1 260 B3100 400 450 C710 50 202 B3060 325 — 540
1A 300 B3108 415 430 CX710 51 206 — — — AB201
1CBS — — — — — 52 — B3070 326 925 542
1 C.I. 590 B3102 405 420 CI710 58 — — — — —
1F — B3100F 400FL 450F C710F 60 227 — — — —
1LD 65 B3104 410 440 CL710 61 — B3042 359 — —
1LDF — B3104F 410FL 440F — 61T — — — — —
1PVC — B3100C 420 453 C710P 62 133-134 B3050 361 610, C755T
620 -C757T
1LDPVC — B3104C — — — 64 95 B351L 200 250 C775L
1V — B3106 — 450V — 65 92 — 300 350 C777
2 — B3170 100 151 C727 66 93 B3033 310 — C778
2F — B3170NFF 100FL 151F C727F 68 93 B3033 — 360 M778
2FWON — B3172F — 180F C725 69 89, 87 B3367 255C 359 U568
2WON — B3172 105 180 C727 69R — — — — —
3 67 B3690 418 970 C711 70 135 B655 25 100 H119
3F — B3690F 418FL 970F C711F 70R 136R B656 25R 105 H119R
4 212 B3140 450 520 C725 70S — — 25S 104 —
4A 212FP — — — — 71 135 B3220 — — —
4B — — — — — 78 128R B3199 — 940 M742R
4 C.I. — — — — — 81 CT65 B3104CT 402 442 CTL710
4F — — — — — 81PVC — B3104CTC — — —
4H 216 B3142 451 522 — 82 CT121 B3373CT 511 552 CT720
4PVC — — — — — 82PVC — B3373CTC — 554 —
5 295 B3144 452 525 C726 83 — B3195CT — 982 C716
6 261 B3373 510 550 C720 84 — B3195CT — 980 —
6F — — — — — 99 — — 51 10 —
6PVC — B3373C 520 553 C720P 100 146 — 50 20 H104
7 103 B3148 700 535 C720L 101 278 B3211 40W 55 E157
8 100 B3149 705 545 CX725 101L 278X B3211X — — —
9 600 B3132 517 580 C724 102 248 B3210 40 50 E156
9X 599 B3132W 516 585 W724 102L 248X B3210X — — —
14 595 B3134 — 590 — 103 140 B3205 — 15 —
14X 594 B3134W — 595 — 104 — B3212 — 60 —
20 262 B3180 470 825 164 105 142 B3213 — 40 E151
20S — B3256 — 830 — 106 — — 46 — —
21 — — 8EG — — 107 — — — 70 —
21F — — — — — 107F — — — — —
22 — — 107 — — 108 — — — — —
23 — — 108 — — 109 — B3019 370A 885 C745
24 — — 109 — — 109F — B2501 — — —
25 — — — — — 110 137 B3188 150 90 H115
27 — — — — — 111 120 B3501 — 95, 110 HL115
27A — — — — — 113 — — 10 110 E145
30 194 B3068 348 — C736 114 — — 10H 110H —
30L — — 351 850 — 115 — — 11 130 E147
30M 195 B3066 352 855 C739M 116 — B3234 — 135 —
30H 199 B3067 353 860 C739H 117 — — 13 134 E148
31-M — — — — — 118 60 B3248 340 960 C781
31-O — — — — — 119 — — 12 136 EF147
32 — B3147 712 840 RCS 120 — — — 80 —
33 47 B3084 373 — — 120MJ — — — — —
34 49 B3086 374 904 — 120RWAA — — — — —
35 52 B3085 374A 903 — 120RWAB — — — — —
40 — B3190 457 820 C704A 120W — — — — —
41 — B3191 458 810 C704 122 — — — — —
42 — — 319 910 — 123 — — — — —

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
172 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

TOLCO™ Cross Reference Chart


SUPER SUPER
TOLCO GRINNELL B-LINE MCO PHD STRUT TOLCO GRINNELL B-LINE MCO PHD STRUT
124 — — — — — 328 274 B3118SL 619 487 C730D
125 — DS16 43 48 E151D 329 218, 229 B3054 360 630 M732
126 — B3228 42 45 E150S 330 290 B3200 35 35 E120A
130 — — 356 — — 331 230 B3202 30 960 F112
200 69 B3170NF 130 — — 332 299 B3201 31 38 F111
200W ON — — 105 — — 333 157 B3203 26 25 M129
202 CT69 B3170CT 101 — CT727 335 217 B3045 369 — C769
203 — B3170CTC 102 153 CT727P 336 14 B3040 363 635 —
207 — — — — — 337 — B3082 321 — C747
209 — — — 47W — 343 55 B3080 371 936 —
210 — — — 47D — 405 — B3256 — — —
219 168 — — 160 — 406 — B3257 — — —
220 167 B3151 125 170 C790 420 — — 650 — —
244H — — 126 165 — 421 256 B3281 651 670-678 PG794
244HR — — — — — 421C — — — — —
244C — — 127 165 — 422 255 — — — —
244CR — — — — — 425 — — — — —
260-1 160 B3160 630 651 C789 426 280 B3891 640 690 —
216-11/2 161 B3161 631 653 C789A 427 436 — — — —

262-2 162 B3162 632 654 C789B 428 437 — — — —


263-21/2 163 B3163 633 655 C789C 429 438-1 B3891 640-1 690-1 —
264-3 164 B3164 634 656 C789D 430 438-2 B3892 640-2 690-2 —
265-4 165 B3165 635 658 C789E 431 438-3 B3893 640-3 690-3 —
301CT CT138R B3198HCT 456 512H MT718 432 — — — — —
302 138R B3198H 455 508 M718 500 178 B3264 625 — —
303 108 B3173 — 500 — 505 247 — — — —
304 66 B3083WO 320L 900-1 C780W/O 506 — — — — —
305 66 B3083WO 320W 900 C780W/HW 568 B268 — — — —
306 114 B3224 — 44 — 580 80-V — — — —
307 110R B3222 47 32 E120 581 81H — — — —
309 282 B3014 282 950 — 582 82A-G — — — —
309N — B3014N 282N 950N — 598 98A-G — — — —
310 282 B2500 355 — 452 650 296 — — — —
310N 285N N2500 355N — AB102 800 — — — — —
312 192 B3096 — 875 — 825 — — — — —
313 191 B3092 724 880 — 825A — — — — —
315 — B3093 722 882 C786 906 — — — — —
316 — B3088 — — — 907 — — — — —
316T — B3088T — 871 — 909 — — — — —
317 — B3095 720 880 — 910 112 — 335AB — —
317/319 264 B3093 — 875 C786 975 — — 335A 890 —
318/319 — B3092 — 876 — 980 — — — — —
318 259 B3090 721 882 C785 981 — — — — —
322 171 B3114R 605 490 — 1000 — — — — —
323 — B3121 621 — C729-21/2 2001 — — — — —
324 181 B3110 610 470 C729-2
325 175 B3120 615 460 CR729A
326 177 B3122 620 480 RC729
327 271 B3117SL 617 486 C730C

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 173
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Cross Reference Chart - Grinnell to TOLCO

GRINNELL TOLCO GRINNELL TOLCO GRINNELL TOLCO GRINNELL TOLCO


14 336 178 500 — 1CBS — 120W
47 33 181 324 — 1F — 122
49 34 191 313 — 1LDF — 123
52 35 192 312 — 2 — 124
55 343 194 30 — 2F — 125
60 118 195 30M — 2FWON — 126
65 1LD 199 30H — 2WON — 130
CT65 81 202 50 — 3F — 200WON
66 305 206 51 — 4B — 203
67 3 212 4 — 4C.I. — 207
69 200 212FP 4A — 4F — 209
CT69 202 216 4H — 6F — 210
80-V 580 217 335 — 20S — 244H
81H 581 227 60 — 21 — 244HR
82A-G 582 230 331 — 21F — 244C
89, 87 69 247 505 — 22 — 244CR
92 65 248 102 — 23 — 315
93 66 248X 102L — 24 — 316
95 64 255 422 — 25 — 317
98A-G 598 256 421 — 30L — 316T
100 8 257 426 — 31M — 318/319
103 7 259 318 — 31O — 323
108 303 260 1 — 32 — 337
110R 307 261 6 — 40 — 405
112 910 262 20 — 41 — 406
114 306 264 317/319 — 42 — 420
120 111 B268 568 — 52 — 421
CT121 82 271 327 — 58 — 425
CT138R 301CT 274 328 — 61 — 432
128R 78 278 101 — 69R — 506
133-134 62 278X 101L — 70S — 800
135 70, 71 280 426 — 83 — 825
136R 70R 282 309, 309N — 84 — 825A
137 110 285N 310N — 99 — 906
138R 302 290 330 — 104 — 907
140 103 295 5 — 106 — 909
142 105 296 650 — 107 — 975
146 100 299 332 — 107F — 980
157 333 300 1A — 108 — 981
160 260-1 436 427 — 109 — 1000
161 261-11/2 437 428 — 109F — 2001
162 262-2 438-1 429 — 113
163 263-21/2 438-2 430 — 114
164 264-3 438-3 431 — 115
165 265-4 590 1C.I. — 116
167 220 594 14X — 117
168 219 595 14 — 119
171 322 599 9X — 120
175 325 600 9 — 120MJ
177 326 218, 229 329 — 120RWA

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
174 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Cross Reference Chart - B-Line to TOLCO

B-LINE TOLCO B-LINE TOLCO B-LINE TOLCO B-LINE TOLCO


DS16 125 B3121 323 B3256 405 — 120
B351L 64 B3122 326 B3257 406 — 120MJ
B655 70 B3132 9 B3264 500 — 120RWA
B656 70R B3132W 9X B3281 421 — 120W
B2500 310 B3134 14 B3367 69 — 122
N2500 310N B3134W 14X B3373 6 — 123
B2501 109F B3140 4 B3373C 6PVC — 124
B3014 309 B3142 4H B3373CT 82 — 130
B3014N 309N B3144 5 B3373CTC 82PVC — 200
B3019 109 B3147 32 B3501 111 — 200WON
B3033 68 B3148 7 B3690 3 — 207
B3040 336 B3149 8 B3690F 3F — 209
B3042 61 B3151 220 B3891 426 — 210
B3045 335 B3160 260-1 B3892 430 — 219
B3050 62 B3161 216-11/2 B3893 431 — 244H
B3054 329 B3162 262-2 — 1CBS — 244HR
B3060 50 B3163 263-21/2 — 4A — 244C
B3066 30M B3164 264-3 — 4B — 244CR
B3067 30H B3165 265-4 — 4C.I. — 420
B3068 30 B3170 2 — 4F — 421C
B3070 52 B3170CT 202 — 6F — 422
B3080 343 B3170CTC 203 — 20S — 425
B3082 337 B3170NFF 2F — 21 — 427
B3083WO 304 B3172 2WON — 21F — 428
B3083 305 B3172F 2FWON — 22 — 432
B3084 33 B3173 303 — 23 — 505
B3085 35 B3180 20 — 24 — 506
B3086 34 B3188 110 — 25 — 568
B3088 316 B3190 40 — 30L — 580
B3088T 316T B3191 41 — 31M — 581
B3090 318 B3195CT 83 — 31O — 582
B3092 318/319 B3198H 302 — 42 — 598
B3093 317/319 B3198HCT 301CT — 51 — 650
B3095 317 B3199 78 — 58 — 800
B3096 312 B3200 330 — 60 — 825
B3100 1 B3201 332 — 65 — 825A
B3100C 1PVC B3202 331 — 66 — 906
B3100F 1F B3203 333 — 69R — 907
B3102 1C.I. B3205 103 — 70S — 909
B3104 1LD B3210 102 — 84 — 910
B3104C 1LDPVC B3210X 102L — 99 — 975
B3104CT 81 B3211 101 — 100 — 980
B3104CTC 81PVC B3211X 101L — 106 — 981
B3104F 1LDF B3212 104 — 107 — 1000
B3106 1V B3213 105 — 107F — 2001
B3108 1A B3220 71 — 108
B3110 324 B3224 306 — 113
B3114 322 B3228 126 — 114
B3117SL 327 B3234 116 — 115
B3118SL 328 B3248 118 — 117

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 175
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Cross Reference Chart - MCO to Tolco

MCO TOLCO MCO TOLCO MCO TOLCO MCO TOLCO


8EG 21 355N 310N 640-3 431 — 111
10 113 356 130 650 420 — 116
10H 114 359 61 651 421 — 120
11 115 360 329 700 7 — 120MJ
12 119 361 62 705 8 — 120RWAA
13 117 363 336 712 32 — 120RWAB
25 70 367 335 720 317 — 120W
25R 70R 370A 109 721 318 — 122
25S 70S 371 343 722 315 — 123
26 333 373 33 724 313 — 124
30 331 374 34 — 1CBS 101 202
31 332 374A 35 420 1PVC — 207
35 330 400 1 — 1LDPVC — 209
40 102 400FL 1F — 1V — 210
40W 101 402 81 — 2FWON — 219
42 126 405 1 C.I. — 4A — 244HR
43 125 410 1LD — 4B — 244CR
46 106 410FL 1LDF — 4 C.I. — 303
47 307 415 1A — 4F — 306
50 100 418 3 — 6F — 312
51 99 418FL 3F 520 6PVC — 316
100 2 450 4 — 14 — 316T
100FL 2F 451 4H — 14X — 317/319
102 203 452 5 — 20S — 318/319
105 200WON 455 302 — 21F — 405
125 220 456 301CT 107 22 — 406
126 244H 457 40 108 23 — 421C
127 244C 458 41 109 24 — 422
130 200 470 20 — 25 — 425
150 110 510 6 — 31M — 427
200 64 511 82 — 31O — 428
255C 69 516 9X — 51 — 432
282 309 517 9 — 58 — 505
282N 309N 605 322 — 60 — 506
300 65 610 324 — 68 — 568
310 66 615 325 — 69R — 580
319 42 617 327 — 71 — 581
320L 304 619 328 — 78 — 582
320W 305 620 326 — 81PVC — 598
321 337 621 323 — 82PVC — 650
325 50 625 500 — 83 — 800
326 52 630 260-1 — 84 — 825A
335A 975 631 261-11/2 — 101L — 906
335AB 910 632 262-2 — 102L — 907
340 118 633 263-21/2 — 103 — 909
348 30 634 264-3 — 104 — 980
351 30L 635 265-4 — 107 — 1000
352 30M 640 426 — 107F — 2001
353 30H 640-1 429 — 108
355 310 640-2 430 — 109F

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
176 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Cross Reference Chart - PHD to TOLCO

PHD TOLCO PHD TOLCO PHD TOLCO PHD TOLCO


10 99 480 326 925 52 — 130
15 103 486 327 930 118 — 200
20 100 487 328 936 343 — 200WON
25 333 490 322 940 78 — 202
32 307 500 303 950 309 — 207
35 330 508 302 950N 309N — 244HR
38 332 512H 301CT 960 331 — 244CR
40 105 520 4 970 3 — 310
44 306 522 4H 970F 3F — 310N
45 126 525 5 980 84 — 316
47D 210 535 7 982 83 — 323
47W 209 545 8 — 1CBS — 335
48 125 550 6 — 1LDPVC — 337
50 102 552 82 — 4A — 405
55 101 553 6PVC — 4B — 406
60 104 554 82PVC — 4PVC — 420
70 107 580 9 — 4 C.I. — 421C
80 120 585 9X — 4F — 422
90 110 590 14 — 6F — 425
95, 110 111 595 14X — 21 — 427
100 70 610, 620 62 — 21F — 428
104 70S 630 329 — 22 690-1 429
105 70R 635 336 — 23 690-2 430
110 113 651 260-1 — 24 690-3 431
110H 114 653 261-11/2 — 25 — 432
130 115 654 262-2 — 30 — 500
134 117 655 263-21/2 — 31M — 505
135 116 656 264-3 — 31O — 506
136 119 658 265-4 — 33 — 568
151 2 670-678 421 — 50 — 580
151F 2F 690 426 — 51 — 581
153 203 810 41 — 58 — 582
160 219 820 40 — 60 — 598
165 244H/244C 825 20 — 61 — 650
170 220 830 20S — 61T — 800
180 2WON 840 32 — 66 — 825
180F 2FWON 850 30L — 69R — 825A
250 64 855 30M — 71 — 906
350 65 860 30H — 81PVC — 907
359 69 871 316T — 101L — 909
360 68 875 317/319 — 102L — 910
420 1 C.I. 876 318/319 — 106 — 980
430 1A 880 317 — 107F — 1000
440 1LD 882 318 — 108 — 2001
440F 1LDF 885 109 — 109F
450 1 890 975 — 120MJ
450F 1F 900 305 — 120RWAA
450V 1V 900-1 304 — 120RWAB
453 1PVC 903 35 — 120W
460 325 904 34 — 122
470 324 910 42 — 124

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 177
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Cross Reference Chart - Super Strut to TOLCO


SUPER SUPER SUPER SUPER
STRUT TOLCO STRUT TOLCO STRUT TOLCO STRUT TOLCO
AB102 310N C727 2WON — 22 — 306
F111 332 C727F 2F — 23 — 309
F112 331 CT727 202 — 24 — 309N
H104 100 CT727P 203 — 25 — 312
H115 110 C729-2 324 — 30L — 313
H119 70 C729-21/2 323 — 31M — 316
H119R 70R CR729A 325 — 31O — 316T
HL115 111 RC729 326 — 33 — 317
E120 307 C730C 327 — 34 — 318/319
E120A 330 C730D 328 — 35 — 322
M129 333 M732 329 — 42 — 336
E145 113 C736 30 — 58 — 343
E147 115 C739H 30H — 60 — 405
EF147 119 C739M 30M — 61 — 406
E148 117 M742R 78 — 61T — 420
E150S 126 C747 337 — 69R — 421C
E151 105 C755T-C757T 62 — 70S — 422
E151D 125 C777 65 — 71 — 425
E156 102 C769 335 — 81PVC — 426
E157 101 C775L 64 — 82PVC — 427
164 20 C778 66 — 84 — 428
AB201 51 M778 68 — 99 — 429
C475 109 C780W/HW 305 — 101L — 430
452 310 C780W/O 304 — 102L — 431
540 50 C781 118 — 103 — 432
542 52 C785 318 — 104 — 500
U568 69 C786 317/319 — 106 — 505
C704 41 C789 260-1 — 107 — 506
C704A 40 C789A 261-11/2 — 107F — 568
C710 1 C789B 262-2 — 108 — 580
C710F 1F C789C 263-21/2 — 109F — 581
C710P 1PVC C789D 264-3 — 114 — 582
CI710 1 C.I. C789E 265-4 — 116 — 598
CL710 1LD C790 220 — 120 — 650
CTL710 81 PG794 421 — 120MJ — 800
CX710 1A RCS 32 — 120RWA — 825
C711 3 — 1CBS — 120W — 825A
C711F 3F — 1LDF — 122 — 906
C716 83 — 1LDPVC — 123 — 907
M718 302 — 1V — 124 — 909
MT718 301CT — 4A — 130 — 910
C720 6 — 4B — 200 — 975
C720L 7 — 4 C.I. — 200WON — 980
C720P 6PVC — 4F — 207 — 1000
CT720 82 — 4H — 209 — 2001
C724 9 — 4PVC — 210
W724 9X — 6F — 219
C725 2FWON — 14 — 244HR
C725 4 — 20S — 244C
C726 5 — 21 — 244CR
C727 2 — 21F — 303

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
178 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

TOLCO to MSS and Federal Specification Cross Reference


Federal Spec. Federal Spec.
TOLCO MSS-SP-69 Ww-H-171E TOLCO MSS-SP-69 Ww-H-171E
1 Type 1 Type 1 262-2 Type 39 Type 40A & 40B
1A Type 1 Type 1 263-21/2 Type 39 Type 40A & 40B
1LD — Type 12 264-3 Type 39 Type 40A & 40B
2 Type 10 Type 10 265-4 Type 39 Type 40A & 40B
2NFPA Type 10 Type 10 301CT Type 12 Type 25
2WON Type 7 Type 7 302 Type 12 Type 25
3 Type 5 — 303 Type 11 Type 11
4 Type 4 Type 4 304 Type 22 Type 22
4 CI Type 4 Type 4 305 Type 22 Type 22
4H Type 4 Type 4 306 Type 15 Type 15
5 Type 3 Type 3 307 Type 16 Type 16
6 Type 8 Type 8 309 Type 18 Type 18
20 Type 26 Type 26 310 Type 18 Type 19
20S Type 26 Type 26 317 Type 36 Type 37
30L Type 31 Type 32 318 Type 37 Type 38
30M Type 32 Type 33 317A Type 38 Type 39
30H Type 33 Type34 322 Type 41 Type 42
62 Type 21 Type 21 324 Type 43 Type 44
64 Type 23 Type 23 327 Type 44 Type 45
65 Type 19 Type 23 328 Type 46 Type 47
66 Type 19 Type 23 329 Type 30 Type 30
68 Type 19 Type 23 330 Type 17 Type 17
81 — Type 12 331 Type 13 Type 13
82 Type 8 Type 8 332 Type 14 Type 14
110 Type 24 Type 24 335 Type 25 Type 53
200 Type 10 Type 10 336 Type 27 Type 54
200WON Type 7 Type 7 343 Type 57 —
202 Type 10 Type 10 499 Type 58 —
203 Type 10 Type 10 500 Type 49 Type 50
220 Type 40 Type 41 568 Type 51 Type 51
260-1 Type 39 Type 40A & 40B 580 Type 54 & 55 Type 52
261-11/2 Type 39 Type 40A & 40B 582 Type 51 Type 51
598 Type 51 Type 51
650 Type 50 —

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 179
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Beam Dimensions
American Standard American Standard
American Standard Wide Flange — W Shapes
Channels — C Shapes I Beams — S Shapes

Designation Flange Ave. Designation Flange Ave. Designation Flange Ave. Designation Flange Ave.
Depth & Wt. Width Thickness Depth & Wt. Width Thickness Depth & Wt. Width Thickness Depth & Wt. Width Thickness
"x" Lbs. "Y" "Z" "x" Lbs. "Y" "Z" "x" Lbs. "Y" "Z" "x" Lbs. "Y" "Z"
C3 x 4.1 13/8 S3 x 5.7 23/8 .250 W4 x 13 4 .375 W14 x 99 145/8 .780
C3 x 5.0 11/2 .250 S3 x 7.5 21/2 W5 x 19 5 .430 W14 x 109 145/8 .860
C3 x 6.0 15/8 S4 x 7.7 25/8 W6 x 25 51/8 .455 W14 x 120 145/8 .940
.313 W14 x 132 143/4 1.030
C4 x 5.4 15/8 S4 x 9.5 23/4 W8 x 18 51/4 .330
.313
C4 x 7.25 13/4 S5 x 10.0 3 W8 x 21 51/4 .400 W16 x 36 7 .630
.313 W16 x 40 7 .505
C5 x 6.7 13/4 .313 S5 x 14.75 31/4 W8 x 24 61/2 .400
C5 x 9.0 17/8 S6 x 12.5 33/8 W8 x 28 61/2 .465 W16 x 45 7 .565
.375 W16 x 50 71/8 .630
C6 x 8.2 17/8 S6 x 17.25 35/8 W8 x 31 8 .435
C6 x 10.5 2 .375 W8 x 35 8 .495 W16 x 57 71/8 .715
S7 x 15.3 35/8 .375 W16 x 67 101/4 .665
C6 x 13.0 21/8 S7 x 20.0 37/8 W8 x 40 81/8 .560
W8 x 48 81/8 .685 W16 x 77 101/4 .760
C7 x 9.8 21/8 S8 x 18.4 4 W16 x 89 103/8 .875
C7 x 12.25 21/4 .375 .438 W8 x 58 81/4 .810
S8 x 23.0 41/8 W16 x 100 103/8 .985
C7 x 14.75 21/4 W8 x 67 81/4 .935
S10 x 25.4 45/8 .500 W18 x 50 71/2 .570
C8 x 11.5 21/4 S10 x 35.0 5 W10 x 22 53/4 .360
W10 x 26 53/4 .440 W18 x 55 71/2 .630
C8 x 13.75 23/8 .375 S12 x 31.8 5 W18 x 60 71/2 .695
C8 x 18.75 21/2 W10 x 33 8 .435
S12 x 35.0 51/8 .563 W10 x 39 8 .530 W18 x 65 75/8 .750
C9 x 13.4 21/2 S12 x 40.8 51/4 W18 x 71 75/8 .810
C9 x 15.0 21/2 .438 .688 W10 x 45 8 .620
S12 x 50.0 51/2 W10 x 49 10 .560 W18 x 76 11 .680
C9 x 20.0 25/8 W18 x 86 111/8 .770
S15 x 42.9 51/2 .625
W10 x 54 10 .615
C10 x 15.3 25/8 S15 x 50.0 55/8 W10 x 60 101/8 .680 W18 x 97 111/8 .870
C10 x 20.0 23/4 W10 x 68 101/8 .770 W18 x 106 111/4 .940
.438 S18 x 54.7 6
C10 x 25.0 27/8 .688 W10 x 77 101/4 .870 W21 x 62 81/4 .615
C10 x 30.0 3 S18 x 70.0 61/4
W10 x 88 101/4 .990 W21 x 68 81/4 .685
C12 x 20.7 3 S20 x 66.0 61/4 .813 W21 x 73 81/4 .740
S20 x 75.0 63/8 W12 x 26 61/2 .380
C12 x 25.0 3 .500 W12 x 30 61/2 .440 W21 x 83 83/8 .835
C12 x 30.0 31/8 S20.3 x 86.0 7 .938 W21 x 93 83/8 .930
S20.3 x 96.0 71/4 W12 x 35 61/2 .520
C15 x 33.9 33/8 W12 x 40 8 .515 W21 x 101 121/4 .800
C15 x 40.0 31/2 .625 S24 x 80.0 7 W12 x 45 8 .575 W21 x 111 123/8 .875
C15 x 50.0 33/4 S24 x 90.0 71/8 .875 W12 x 50 81/8 .640 W21 x 122 123/8 .960
C18 x 42.7 4 S24 x 100.0 71/4 W12 x 53 10 .575 W24 x 76 9 .680
C18 x 45.8 4 W12 x 58 10 .640 W24 x 84 9 .770
.625 W24 x 94 91/8 .875
C18 x 51.9 41/8 W12 x 65 12 .605
C18 x 58.0 41/4 W12 x 72 12 .670 W24 x 104 123/4 .750
W12 x79 121/8 .735 W24 x 117 123/4 .850
W12 x 87 121/8 .810 W24 x 131 127/8 .960
W12 x 96 121/8 .900 W27 x 94 10 .745
W12 x 106 121/4 .990 W27 x 102 10 .830
W14 x 30 63/4 .385 W27 x 114 101/8 .930
W14 x 34 63/4 .455 W27 x 146 14 .975
W14 x 38 63/4 .515 W30 x 108 101/2 .760
W14 x 43 8 .530 W30 x 116 101/2 .850
W14 x 48 8 .595 W30 134 101/2 .930
W14 x 53 8 .660 W30 x 132 101/2 1.000
W14 x 61 10 .645 W33 x 118 111/2 .740
W14 x 68 10 .720 W33 x 130 111/2 .855
W14 x 74 101/8 .785 W33 x 141 111/2 .960
W14 x 82 101/8 .855 W36 x 135 12 .790
W14 x 90 141/2 .710 W36 x 150 12 .940
W36 x 160 12 1.020

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
180 Customer Service • 800.786.5266
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Decimals of a Foot

Inch 0" 1" 2" 3" 4" 5" 6" 7" 8" 9" 10" 11"
0 0 .0833 .1667 .2500 .3330 .4167 .5000 .5833 .6667 .7500 .8333 .9167
1/16 .0052 .0085 .1719 .2552 .3385 .4219 .5052 .5885 .6719 .7552 .8385 .9219
1/8 .0104 .0938 .1771 .2604 .3438 .4271 .5104 .5938 .6771 .7604 .8438 .9271
3/16 .0156 .0990 .1823 .2656 .3490 .4323 .5156 .5990 .6823 .7656 .8490 .9323
1/4 .0208 .1042 .1875 .2708 .3542 .4375 .5208 .6042 .6875 .7708 .8542 .9375
5/16 .0260 .1094 .1927 .2760 .3594 .4427 .5260 .6094 .6927 .7760 .8594 .9427
3/8 .0313 .1146 .1979 .2812 .3646 .4479 .5313 .6146 .6979 .7813 .8646 .9479
7/16 .0365 .1198 .2031 .2891 .3724 .4557 .5391 .6224 .7057 .7891 .8724 .9557
1/2 .0417 .1250 .2083 .2917 .3750 .4583 .5417 .6250 .7083 .7917 .8750 .9583
9/16 .0469 .1302 .2135 .2969 .3802 .4635 .5469 .6302 .7135 .7969 .8802 .9635
5/8 .0521 .1354 .2188 .3021 .3854 .4688 .5521 .6354 .7188 .8021 .8854 .9688
11/16 .0573 .1406 .2240 .3073 .3906 .4740 .5573 .6406 .7240 .8073 .8906 .9740
3/4 .0625 .1458 .2292 .3125 .3958 .4792 .5625 .6458 .7292 .8125 .8958 .9792
13/16 .0677 .1510 .2344 .3177 .4010 .4844 .5677 .6510 .7344 .8177 .9010 .9844
7/8 .0729 .1563 .2396 .3229 .4063 .4896 .5729 .6563 .7396 .8229 .9063 .9896
15/16 .0781 .1615 .2448 .3281 .4118 .4948 .5781 .6615 .7448 .8221 .9115 .9948

Decimals of an Inch

Fraction Decimal Fraction Decimal


1/32 .0312 17/32 .5312
1/16 .0625 9/16 .5625
3/32 .0937 19/32 .5937
1/8 .1250 5/8 .6250
5/32 .1562 21/32 .6562
3/16 .1875 11/16 .6875
7/32 .2187 23/32 .7187
1/4 .2500 3/4 .7500
9/32 .2812 25/32 .7812
5/16 .3125 13/16 .8125
11/32 .3437 27/32 .8437
3/8 .3750 7/8 .8750
13/32 .4062 29/32 .9062
7/16 .4375 15/16 .9375
15/32 .4687 31/32 .9687
1/2 .500

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 181
www.tolco.com

www.tolco.com
a brand of
®
Revision 5/24/2001

Steel Pipe Data

Schedule 40 & 80

Pipe Sched. Wall Wt. Per Water Weight Pipe Sched. Wall Wt. Per Water Weight
Size No. O.D. Thickness Foot per Ft./Lbs Size No. O.D. Thickness Foot per Ft. Lbs.

3/8 40 .675 .091 .567 .083 5 40 5.563 .258 14.620 8.660


80 .126 .738 .061 80 .375 20.780 7.870
1/2 40 .840 .109 .850 .132 6 40 6.625 .280 18.970 12.510
80 .147 1.087 .101 80 .432 28.570 11.290
3/4 40 1.050 .113 1.130 .230 8 40 8.625 .322 28.550 21.600
80 .154 1.473 .186 80 .500 43.390 19.800
1 40 1.315 .133 1.678 .374 10 40 10.750 .365 40.480 34.100
80 .179 2.171 .311 80 .593 64.400 31.100
11/4 40 1.660 .104 2.272 .647 12 40 12.750 .406 53.600 48.500
80 .191 2.996 .555 80 .687 88.60 44.000
11/2 40 1.900 .145 2.717 .882 14 40 14.000 .437 63.00 58.500
80 .200 3.631 .765 80 .750 107.000 51.200
2 40 2.375 .154 3.652 1.452 16 40 16.000 .500 83.000 76.500
80 .218 5.022 1.279 80 .843 137.000 69.700
21/2 40 2.875 .203 5.790 2.072 18 40 18.000 .563 105.000 97.200
80 .276 7.660 1.834 80 .937 171.000 88.500
3 40 3.500 .216 7.570 3.200 20 40 20.000 .593 123.000 120.400
80 .300 10.250 2.860 80 1.031 209.000 109.400
31/2 40 4.000 .226 9.110 4.280 24 40 24.000 .687 171.000 174.200
80 .318 12.510 3.850 80 1.218 297.000 158.200
4 40 4.500 .237 10.790 5.510 30 20 30.000 .500 158.000 286.000
80 .337 14.980 4.980 36 API 36.000 .500 190.000 417.000

Copper Tube Data


Type L Type K

Nom. Nom.
Tube O.D. Wall Wt. Per Water Weight Tube O.D. Wall Wt. Per Water Weight
Size Tubing O.D. Thickness Foot per Ft./Lbs Size Tubing O.D. Thickness Foot per Ft. Lbs.
1/4 3/8 .375 .030 .126 .034 1/4 3/8 .375 .035 .145 .032
3/8 1/3 .500 .035 .198 .062 3/8 1/2 .500 .049 .269 .055
1/2 5/8 .625 .040 .285 .100 1/2 5/8 .625 .049 .344 .094
5/8 3/4 .750 .042 .362 .151 5/8 3/4 .750 .049 .418 .144
3/4 7/8 .875 .045 .455 .209 3/4 7/8 .875 .065 .641 .188
1 11/8 1.125 .050 .655 .357 1 11/8 1.125 .065 .839 .337
11/4 13/8 1.375 .055 .884 .546 11/4 13/8 1.375 .065 1.040 .527
11/2 15/8 1.625 .060 1.140 .767 11/2 15/8 1.625 .072 1.360 .743
2 21/8 2.125 .070 1.75 1.341 2 21/8 2.125 .083 2.050 1.310
21/2 25/8 2.625 .080 2.480 2.064 21/2 25/8 2.625 .095 2.920 2.000
3 31/8 3.125 .090 3.330 2.949 3 31/8 3.125 .109 4.000 2.960
31/2 35/8 3.625 .100 4.290 3.989 31/2 35/8 3.625 .120 5.120 3.900
4 41/8 4.125 .110 5.380 5.188 4 41/8 4.125 .134 6.510 5.060
5 51/8 5.125 .125 7.610 8.081 5 51/8 5.125 .160 9.670 8.000
6 61/8 6.125 .140 10.200 11.616 6 61/8 6.125 .192 13.870 11.200

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
182 Customer Service • 800.786.5266
www.tolco.com
www.tolco.com www.tolco.com
Revision 5/24/2001 Revision 6/1/2002

Catalog Forward Warning Cast Iron Pipe Data


This catalog has been created with an acute aware- Pipe hanger products included in this catalog are
ness of the field problems of the piping contractor. intended for installation and service only as described American Water Works Assn. (AWWA)
We have sought and received input from engineers, herein. Mechanical Joint Pipe Class 150. Approximately same weight for Bell & Spigot. Flanged cast iron pipe add weight of flanges
installers, field inspectors and others closely involved We are aware that these products have been used
with the installation of piping systems. This is where (often without incident) for purposes and in ways other O.D. Wall Wt. Per Wt. of Water
needs are discovered, and where products and serv- than those for which they were designed and manu- Pipe Size C.I. Pipe Thickness Foot per Ft./Lbs.
ices are genuinely tested. factured. Examples of which are: use of products as 3 3.96 .32 12.2 3.73
TOLCO™ is proud to present a complete and versa- erection tools; use of beam clamps on a beam not 4 4.80 .35 16.4 5.72
tile line of pipe hangers and related products. The specified for them; use of concrete inserts as an 6 6.90 .38 25.7 12.80
TOLCO line has been methodically developed to anchor for pulling pipe to proper elevation; suspension 8 9.05 .41 36.7 23.10
10 11.10 .44 48.7 35.50
effectively address support problems in the commer- of one clevis hanger under another resulting in cumu- 12 13.20 .48 62.9 51.00
cial and industrial piping fields. lative load greater than specified capability. In such 14 15.30 .51 78.8 69.30
A thorough knowledge of our customers’ needs and cases of misapplication or improper use, we cannot 16 17.40 .54 95.0 90.30
problems was no less important than the development be held responsible for injuries or property damage. 18 19.50 .58 114.7 114.00
of our manufacturing skills in the emergency of TOLCO pipe hanger products are carefully designed 20 21.60 .62 135.9 141.50
24 25.80 .73 190.4 201.00
TOLCO as a leader in the pipe hanger industry. Our and manufactured to industry standards. Care should 30 32.00 .85 277.3 312.00
people are equipped to respond quickly to your prod- be exercised by installers and end users to install, use 36 38.30 .94 368.9 449.00
uct and service needs on both standard items and and maintain these products properly to avoid any 42 44.50 1.05 479.1 612.00
specialized metal fabrication. possible on-the-job accidents. 48 50.80 1.14 595.2 803.00
Custom Fabrication Designs
We have expanded our manufacturing capacity in Product design and specifications are subject to Standard No Hub “Soil Pipe” Extra Heavy “Soil Pipe”
response to the growing demand for customized change without notice.
metal fabrication and special hangers. When some O.D. I.D. O.D. I.D.
Finishes Pipe Size Pipe Size
detail of construction or piping arrangement makes it 2 2.25 1.89 2 2.38 2.00
necessary to deviate from standard types of hangers, Most hangers are available in: stainless steel, elec-
3 3.25 2.89 3 3.50 3.00
TOLCO is equipped to furnish hangers and supports tro-galvanized or hot-dipped galvanized. Other 4 4.25 3.89 4 4.50 4.00
of any required type. These products combine proven special finishes are available upon request. Items 5 5.25 4.87 5 5.50 5.00
designs and standards with new innovations that ordered hot-dip galvanized may be supplied with elec- 6 6.25 5.85 6 6.50 6.00
enhance their utility. tro-galvanized threaded components unless otherwise 8 8.38 7.94 8 8.62 8.00
specified. If you require a finish not listed in the 10 10.50 9.98 10 10.75 10.00
Approvals and Specifications product data of a specific hanger, please consult
TOLCO, as a member of the American Pipe Fittings our factory.
Association, is cooperating with engineers and archi-
Index
Load Carrying Capacities of Threaded Steel Rod
tects in the preparation of specifications covering
hanger requirements and the interpretation of applica- Figure numbers in this catalog are in numerical order.
Rod Root Area Max. Safe Load Max. Rec. Load Weight per
ble piping safety codes. Terms and Conditions of Sale Diameter In. Thread Sq. In. in Lbs. @650°F* in Lbs. @ 750°F* Ft./Lbs.
All TOLCO products are carefully manufactured to 3/8 .068 610 540 .376
For conditions and terms of sale, please consult our 1/2 .126 1130 1010 .668
meed the highest standards in the industry. All prod- current price guide. 5/8 .202 1810 1610 1.040
ucts, as a minimum conform to Manufacturers
3/4 .302 2710 2420 1.500
Standardization Society MSS-SP-58, and to the allow- 7/8 .419 3770 3360 2.400
able stresses specified in the ANSI B31.1 code for 1 .552 4960 4420 2.670
pressure piping. 11/8 .693 6230 5560 3.380
Many TOLCO Products are also listed, approved or 11/4 .889 8000 7140 4.170
11/2 1.293 11630 10370 6.010
conform to:
13/4 1.744 15700 14000 8.180
Underwriter’s Laboratories UL-203 2 2.300 20700 18460 10.680
Factory Mutual Engineering 21/2 3.023 27200 24260 13.520
National Fire Protection Association NFPA-13, 21/2 3.719 33500 29800 16.960
NFPA-13R, NFPA-13D and NFPA-24 * Maximum recommended load based on minimum safety factor of 5.
Federal Specification WW-H-171EE

Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 909.737.5599 • Fax: 909.737.0330 Main Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 951.737.5599 • Fax: 951.737.0330
Customer Service • 800.786.5266 Customer Service • 800.786.5266 183
www.tolco.com www.tolco.com
TOLCO™ Pipe Hangers & Support Systems
Fittings
Wrot and cast copper pressure fittings • Wrot and cast copper drainage
fittings • Wrot copper PEXlink® fittings • Cast copper alloy flared fittings • Cast
copper alloy flanges • ABS and PVC DWV fittings • Schedule 40 PVC pres-
sure fittings • CPVC CTS fittings • CPVC CTS-to-metal transition fittings
• Schedule 80 PVC and CPVC systems • CPVC metric piping systems.

Valves & Actuation


Pressure-rated bronze, iron and alloy-iron gate, globe and check valves • Pressure-
rated bronze ball valves • Boiler specialty valves • Commercial and industrial butter-
fly valves • Circuit balancing valves • Carbon and stainless steel ball valves • ANSI
flanged steel ball valves • Pneumatic and electric actuators and controls • Grooved
ball and butterfly valves • UL/FM fire protection valves • Low-pressure gate, globe,
check and ball valves • Bronze specialty valves • Frostproof sillcocks • MSS speci-
fication valves • PVC ball valves • CPVC CTS ball valves.

Chemtrol®
Supporting
Ideas
Thermoplastic pipe, valves and fittings in PVC, Corzan® CPVC, polypropylene
and PVDF Kynar® • Chem-Aire® thermoplastic compressed air piping systems
• Pneumatic and electric actuation systems.
the Flow.
that flow. ™

eNIBCO®

Supporting A suite of services designed to make customers more efficient • More cost-effective
• More informed • EDI—Electronic Data Interchange • VMI—Vendor Managed
Inventory • NIBCO.com • NIBCOpartner.com • eNIBCO will continuously develop
the Flow. ™ new products to deliver the competitive advantage.

Every solution TOLCO™


Office / Manufacturing
Begins with 1375 Sampson Avenue
Corona, California 92879

TOLCO . USA
Phone: 951.737.5599
Fax: 951.737.0330
We're committed to Pipe Hangers
Customer Service:
supporting all of your flow
control needs. We can
Phone: 800.786. 5266 Supports
www.tolco.com
Pipe Hangers • Pipe Supports
TOL-Strut Channel • Seismic Bracing

provide creative solutions for Seismic Bracing
your most challenging brac- NIBCO INC.
World Headquarters
ing and support applications.
1516 Middlebury Street
Solutions that make your Elkhart, IN 46515-1167
USA
installations easier, safer
and more cost-effective. Customer Service:
Phone: 800.234.0227
Fax: 800.234.0557
For solutions that will support
your flow-control applications, Technical Service:
call on us. We're TOLCO, a Phone: 888.446.4226
product line committed to
www.nibco.com
quality, service and innovation—
Supporting the Flow.

C-TOLH-0403

Вам также может понравиться