Вы находитесь на странице: 1из 4

TECHNICAL PAPER

Ultimate Limit State design to


Eurocode 7 using numerical methods
Part I: methodology and theory
Colin Smith & Matthew Gilbert, Department of Civil and Structural
Engineering, University of Sheffield
(Part II will appear in the next edition of GE)

Summary geotechnical failure (termed STR to be used in conjunction with a difference between the actual and
Assessment of the Ultimate Limit and GEO in Eurocode 7). Issues generally applicable numerical ULS state can then be considered as
State (ULS) in Eurocode 7 is to be relevant to each of the three design analysis procedure, the ideal would a measure of Factor of Safety (FoS).
carried out using “Design Approach approaches (DA) specified in the be one that is “problem agnostic” (ie In many conventional analyses
1” in the UK. In most cases this Eurocode will be considered. Each is the same irrespective of whether this process is carried out implicitly.
involves two design checks, one design approach may be broadly the problem involves evaluation For example, when designing a
which primarily involves an “action classified as follows: of the stability of a foundation, retaining wall, active or passive
factor” approach (Design Approach n DA1 This approach requires two a retaining wall, a slope etc.). earth pressures are typically
1, Combination 1, termed DA1/1) design combinations (DC) to be Additionally, the methodology assumed to act on the wall.
and one which primarily involves a examined should, if possible, not require However, when using a general
“material factor” approach (Design n DC1 Factors on actions (loads) user intervention at intermediate numerical analysis procedure,
Approach 1, Combination 2, termed (DA1/1) stages during the calculations, this process must be carried out
DA1/2). The latter is generally n DC2 Factors on material strength and should provide a consistent, explicitly. Three main ways of
straightforward to implement in (DA1/2) safe and mechanically reasonable explicitly driving a system to the
numerical analysis procedures, n DA2 Factors on actions and assessment. ULS are listed in Table 1.
but the former is potentially more resistances In this paper the authors: In many current numerical
challenging. n DA3 Factors on actions and n Examine the challenges and analysis procedures, increasing
A survey of the current literature material strength. requirements for applying numerical an existing load to drive the
on Eurocode 7 indicates differences In general only one of these three analysis procedures to “material system to collapse (ie Method A
of opinion on how best to undertake design approaches is permitted factor” and “action/resistance in Table 1) is already an inherent
DA1/1 checks (the same differences by the National Application factor” type ULS checks. (The feature. Thus a supplementary
of opinion also apply to the document of each nation (in the “action factor” approach will be load factor, henceforth referred
“action/resistance factor” Design UK, Design Approach 1, DA1 is considered as a special case of the to as an “adequacy factor”, λA,
Approach 2, DA2, checks). This to be used). Whichever approach “action/resistance” factor approach can be applied to one or more
can lead to inconsistent application is used, one of the Eurocode’s with a resistance factor of unity.) unfavourable loads, and the
of Eurocode 7 when undertaking strengths is that it provides a very n Propose a simple and consistent magnitude of λA required to achieve
a numerical analysis, which in general methodology which can be methodology which allows “action/ collapse can then be found using
turn can lead to differences in the applied flexibly by engineers. This resistance factor” type design the numerical analysis procedure.
resulting design solutions. allows an appropriate margin of approaches to be undertaken Considering Method B in Table 1, it
In this two-part paper, a simple safety to be achieved in a design, in conjunction with numerical is alternatively possible to iteratively
and consistent methodology for while simultaneously ensuring that analysis procedures. This builds on reduce soil strengths within a
undertaking “action/resistance unreasonable or impossible modes the methodology put forward in numerical analysis procedure, by a
factor” design checks using of response in the accompanying Smith & Gilbert (2010), where the factor λB, until failure is achieved.
numerical methods is proposed mechanical analysis are not salient issues involved in applying It should be noted that the
in Part I, while in Part II the introduced. numerical analysis procedures to actual collapse mode identified
methodology is used to develop a However, this flexibility can load and resistance factor design by an analysis will in general vary
general-purpose design procedure also be viewed as a weakness. For (LRFD) problems were briefly according to where λ is applied, and
which is then applied to a number example, a survey of the current examined. only when λ = 1 for each of the three
of example problems. literature on Eurocode 7 indicates In Part II of the paper a simple methods can the collapse modes
differences of opinion as to when framework for applying the above
Introduction and how to introduce partial in the context of Eurocode 7 is Method Description
There exists a large body of factors in DA1/1 and DA2. Much described and then illustrated with a
literature in which Eurocode 7 (BSI discussion on this issue may be number of worked examples. A Increase an existing
2004) is applied to geotechnical found in the literature, such as load in the system
design problems using conventional Simpson (1997), Schuppener et al. Ultimate Limit State
“hand calculation” type methods. (1998), Simpson & Driscoll (1998), assessment B Reduce the soil
However, significantly less attention Orr & Farrell (1999), Simpson In general, a given design solution strength
appears to have been paid to use (2000), Farrell & Orr (1998), will normally be inherently stable, C Impose an additional
of Eurocode 7 in conjunction with Driscoll & Simpson (2001), Frank and is by implication therefore not load (or group of
numerical analysis procedures. et al. (2004), Driscoll et al. (2005), close to its ultimate limit state. In
loads) in the system
This paper seeks to address this Simpson (2007), Driscoll et al. an ULS assessment the goal is to
for the Ultimate Limit State (ULS) (2008), Bond & Harris (2008). drive the system to collapse by some Table 1: Common ways of
assessment of structural and When seeking a methodology means (in a theoretical sense). The driving a system to the ULS

24 ground engineering october 2011 ground engineering october 2011 25


TECHNICAL PAPER
through increasing an unfavourable occurs because the stresses are (see figure 2), where factors may be induce the anticipated failure (ie in some cases alternatively be used.
a b c load by a factor λA, (where this in reality not at their limiting, applied between the soil mass and the direction of the active pressure), This approach is described in detail
factor is applied as a multiplier) or failure, condition (ie the soil can the wall, the direct approach does with H passing through the centroid in Appendix II.
by reducing soil strength across the be considered to be only mobilising not work and it is necessary to adopt of the wall to avoid applying
model by a factor λB (where this part of its strength). However in a an alternative procedure. additional moments. This is a Application of proposed
factor is applied as a divisor). If after ULS plastic limit analysis both yield straightforward calculation for most methodology: retaining wall
the analysis λA,B ≥ 1 then the system and equilibrium conditions must be A proposed methodology numerical analysis procedures (and example
can be taken to be inherently stable. satisfied, at least when an upper- for action/resistance factor “natural” in the case of a numerical Consider the retaining wall shown
Alternatively, if λA,B < 1 then the bound limit analysis approach is design limit analysis approach). in Figure 3, for which a combined
system is inherently unstable (where being used. Once failure has been achieved, bearing/sliding failure is to be
λA,B denotes either λA or λB). Development of appropriate “passive” and “active” checked. Here it has been decided
Figure 1: Three possible failure modes for a combined foundation and embedded retaining wall, It is therefore reasonable to n A second problem relates to the methodology zones are generated on either that equation 1 will be checked in
dependent on specific soil and structural properties: (a) rotation of wall as rigid body, (b) formation of expect that any action effect (Ed) nature of the failure mode. In order Consider again the problem shown side of the wall, as assumed in a an “equilibrium direction” 15˚ to
plastic hinge in wall, (c) local failure of foundation. and resistance (Rd) pair within a to apply partial factors, the locations in Figure 2. To induce the required conventional hand analysis. It is then the horizontal, so that the externally
system will satisfy Ed ≤ Rd when λA,B of action effects and resistances active and passive pressures, and straightforward to determine the applied force (H) acts at an angle of
design (ie factored) actions or action ≥ 1 (although strictly speaking this must be known. the base shear resistance on the active force (A) and passive and base 15˚ as indicated. Components of the
effects (denoted Ed) must be less than is only true when plastic collapse This in turn requires advance boundaries of a real wall, it would resistance forces (P and S) predicted self weight (W) and the resultant
or equal to the corresponding design governs the ULS). knowledge of the collapse mode, be necessary to cause it to slide by by the analysis, and to incorporate loads (A) and resistances (P and
resistance (Rd) at the ultimate limit which in turn requires that introducing some external agent. these when evaluating equation S) arising from the forced failure
Sliding state, ie: Action factor and action/ the analysis has already been The required ULS action effects 1. Note that the magnitude of the mechanism acting parallel to the
resistance factor design performed. However, the form of and resistances then become force H required to cause failure is “equilibrium direction” are given in
Ed ≤ Rd (1) approaches collapse mode will depend on where available, partial factors can be not used when assessing safety. It is Table 3 (overleaf). Fully frictional
“Action factor” and “action/ the partial factors are applied, and applied and subsequently equation evident that this approach addresses soil/wall interfaces are assumed.
Active earth pressure Note that this key Eurocode resistance factor” design a circular argument ensues. Only in 1 evaluated. both concerns raised previously, i.e. The solution shown was
resultant A equation is an inequality, and approaches (such as DA1/1 and simple cases, for example involving It is suggested that this is the key actions and resistances do not need identified using the LimitState:
Passive earth pressure provides no measure of the degree DA2 in Eurocode 7) typically bearing capacity of a foundation or to performing “action/resistance to be defined in advance of the GEO software (LimitState, 2009)
resultant P of over-design. require that action effects and sliding failure of a retaining wall, factor” design in conjunction with numerical analysis, and equilibrium and can be used to illustrate how
It can be seen from Table 2 that resistances, considered at some will the positions of the actions numerical analysis. A failure mode is preserved at all times. the loads (actions and action effects)
Base friction S
in Eurocode 7 the numerical value internal location within the and resistances remain unchanged must first be proposed. This failure In simple terms the method and resistances acting on the wall
of a given partial factor is dependent problem (for example at a soil/ during the analysis. must be induced in the model by can be considered analogous to can be determined by application of
Figure 2: Conventional assumption made in the analysis of a gravity on the specific situation. e.g. the structure boundary), are factored. While the second of the two an external agent, and stability can “pushing” the construction in a the hypohetical external force. Table
retaining wall against sliding. value of a partial factor depends on When using numerical analysis challenges listed above could then be evaluated. In a numerical range of directions. 3 indicates that, when considering
whether it is applied to an action / procedures, two challenges potentially be dealt with by using analysis procedure the wall could The direction that requires the the factored actions and resistances
be expected to match (assuming that 1997-1, 2.1(1)P]. To render the action effect, or to a resistance, and immediately present themselves: a sophisticated, perhaps iterative, be forced to move in a specific least effort to trigger instability is the in the direction of the external force,
the problem does not have several probability of a ULS occurring in the case of an action, whether analysis procedure, the first is direction (“kinematic forcing”) critical direction and the magnitude this wall is unsafe.
equally critical collapse modes). sufficiently small, the general this is permanent or variable and n The first challenge can be inherently intractable and cannot or the equilibrium relations could of the “push” required relates to the A number of observations on this
It may be observed that the approach in Eurocode 7 is to apply favourable or unfavourable. illustrated by considering a be circumvented in a numerical be modified in that direction margin of safety. A “small” push approach can be made:
ULS is often assumed to be factors on uncertainties at their conventional ULS check of a gravity analysis procedure without violating (“equilibrium forcing”). In this indicates a low margin of safety
synonymous with plastic collapse, source in the calculation, rather Eurocode 7 with numerical retaining wall against sliding, as fundamental mechanical principles. paper it is suggested that the latter while a “large” push indicates a n The “equilibrium direction” needs
though according to the Eurocode than applying them to the whole analysis: observations shown in Figure. 2. Note that for very simple problems is preferable as it is in the same form high margin of safety. “Large” and to be stated in advance of an analysis
definitions other types of ULS calculation. Thus factors may Such a check is typically carried (for example the bearing capacity of as equation 1. “small” are quantified by comparing to allow the externally applied force
failure are also possible. be applied to one or more of the Material factor design out by assuming that active and a surface footing) the first challenge To achieve this it is necessary to them to the magnitudes of the other H to be applied correctly. Thus the
Since plastic limit analysis following characteristic parameters approaches passive Rankine pressures act on does not arise since the factors are apply a hypothetical unfavourable forces acting on the construction at “action/resistance factor” approach
methods are commonly used (characteristic values are defined “Material factor” design approaches opposite sides of the wall. These effectively applied at an interface external force H parallel to the failure. is inherently less flexible when
by geotechnical engineers, the in the Eurocode as “a cautious (for example DA1/2 and DA3 in would be designated as an action between an externally applied load “equilibrium direction” to be The same basic methodology used in conjunction with numerical
arguments developed in this paper estimate of the value affecting Eurocode 7) generally only require effect and resistance respectively in and the soil/structure domain. checked, and to then increase this can also be used to assess internal analysis procedures than “material
are primarily presented in the the occurrence of the limit state” that parameters known in advance this problem. Therefore violation of internal until failure occurs. For example, structural stability, for example factor” approaches, in which
context of plastic limit analysis. In [EN 1997-1, 2.4.5.2(2)P], and are of an analysis are factored. These The design check (equation 1) equilibrium is not encountered. for a horizontal equilibrium check bending failure in a sheet pile wall, the critical collapse mode can be
particular, the Discontinuity Layout identified by subscript k): actions parameters are either material therefore requires that: However, when applied for on a retaining wall, H would be and a slightly more convenient determined automatically.
Optimisation (DLO) computational (F); action effects (E); material properties or externally applied example to retaining wall problems applied in a direction expected to “inverse-factor” method can in
limit analysis procedure (Smith properties (X); resistances (R); actions. Factors of 1.0 are applied γEA < S + P (2) n Suitable locations need to be
γR,S γR,P
& Gilbert 2007), as implemented geometrical parameters (a). to action effects (as defined in in chosen to enable evaluation of
in the LimitState:GEO software It is, of course, necessary to Appendix I) and resistances. Parameter Symbol DA1/1 DA1/2 DA2 DA3 action effects and resistances (for
(LimitState 2009), will be used to distinguish properly between these When used in conjunction with a where the forces A, S and P are as example interfaces between soil
provide solutions to the example parameters before applying the general purpose numerical analysis indicated in Fig. 2, γE is the partial Action/ Permanent Unfavourable γG 1.35 1.0 1.35 1.0/1.35* and structure). For investigation
problems presented. partial factors, and unambiguous procedure this type of approach has factor for unfavourable permanent of a pure translational failure
While solutions to ULS problems definitions of what is meant by an the significant advantage that the actions, γR,S is the partial factor action effect Favourable γG 1.0 1.0 1.0 1.0 mode, H itself should be applied
are generally more straightforward action, action effect and a resistance analysis will automatically identify for sliding resistance and γR,P is the to the centroid of the structure to
to obtain using computational are proposed in Appendix I for the critical collapse mechanism, partial factor for passive resistance. Variable Unfavourable γQ 1.5 1.3 1.5 1.3/1.5* be assessed, to avoid applying an
limit analysis techniques, the basic use in a numerical analysis of a there being no need to consider This contrasts with a conventional additional moment to the structure.
methodology proposed is applicable geotechnical stability problem. manually a variety of prescribed computation of the factor of safety, Favourable γQ 0.0 0.0 0.0 0.0
to a broad range of numerical Once the partial factors have been potential failure modes, anticipated as the ratio of resisting forces to n In this method it is proposed that
analysis tools. (Though there can be applied, design values (identified by or otherwise. disturbing forces: R = (P + S)/A. Resistance γR 1.0 1.0 1.1/1.4† 1.0 the numerical analysis is carried
additional challenges in determining subscript “d”) are obtained, and For example, Figure 1 illustrates The challenge when using an out using characteristic values
the ULS, for example when using are used in subsequent stability three different failure modes “action/resistance factor” design Soil c’ γ c’ 1.0 1.25 1.0 1.25 of all actions (excepting variable
finite element models employing calculations. Factors to be applied for a problem which involves a approach in conjunction with a parameters actions, which will be considered in
complex constitutive soil models; to actions, action effects, material foundation and embedded retaining numerical analysis procedure arises Part II of the paper). This ensures
these are not considered here.) properties and resistances are given wall, the most critical of which because the above system is only in tan φ’ γtan φ’ 1.0 1.25 1.0 1.25 that the analysis is conducted
in Table 2. would automatically be identified equilibrium if the ratio of resisting without compromising fundamental
The role of partial factors Note that factors applied to using a general numerical analysis forces to disturbing forces R = 1. cu γ cu 1.0 1.4 1.0 1.4 principles of mechanics. Once
In Eurocode 7 it is stated that: “For geometric parameters will, for the procedure. For example, if R > 1 then the the results from the analysis are
each geotechnical design situation sake of brevity, not be considered As has been mentioned earlier, passive earth pressure and base available only those actions, action
*DA3 values for actions are given for geotechnical/structural actions. † Factors on resistance depend on resistance type.
it shall be verified that no relevant in this paper. To prevent limit state in a general numerical analysis, friction will exceed the active earth effects and resistances directly
limit state ... is exceeded” [EN STR or GEO from occurring, the ULS may be achieved either pressure. In practice equilibrium Table 2: Eurocode 7 partial factors for STR and GEO. applied to the body (usually a

26 ground engineering october 2011 ground engineering october 2011 27


TECHNICAL PAPER
structure) are factored, and stability stresses within the block, identical means that this type of calculation Farrell, E. & Orr, T. (1998), “Safety
Dead load 5kN/m3
is then assessed. (At the stage of using both methods) rather than cannot be used to automatically of retaining walls with high P
applying factors, equilibrium need γ=24kN/m3 GEO. identify the critical collapse mode. water loadings when designed to
not be enforced). It is considered in n Factoring P directly would mean Instead, each mode must be Eurocode 7 using partial factors”,
this calculation that these computed a step change in its magnitude as its examined separately (as is done in Ground Engineering 31(10), 36–40. α
quantities embody all uncertainties angle of inclination transitions from conventional practice). Frank, R., Baudin, C., Driscoll,
associated with the design. α < φ to α > φ. Such step changes R., Kavvadas, M., Krebs Ovesen,
Note also that assessment of are generally undesirable in a safety 4. Internal structural stability may N. & Orr, T. and Schuppener,B.
φ’=30˚ W
what constitutes a favourable and γ=16kN/m3
assessment. also be assessed directly using (2004), Designers’ guide to EN 1997:
unfavourable action need only be n The “direct approach” design the “action/resistance” design Geotechnical design - Part I: General
considered in the sense of the A φ’=30˚ check can in fact be carried out using approach. However, for common Rules, ASCE, Thomas Telford
“equilibrium direction”; application H γ=16kN/m3 the proposed methodology if the cases, such as sheet pile bending Publishing, London.
of this principle removes a key “equilibrium direction” is chosen a more convenient equivalent LimitState (2009), LimitState:GEO
P
potential source of confusion for to coincide with the direction of the “inverse-factor” method, similar to Manual VERSION 2.0, September φ’
new users of Eurocode 7. S φ’=20˚ inclined force P. a “materials factor” approach, has 2009 edn, LimitState Ltd.
γ=16kN/m3
n The modelling of, for example, been proposed. Orr, T. & Farrell, E. (1999), Figure 4: Design check against frictional sliding of a block
n It is proposed that equation 1 need Figure 3: Design check against combined sliding and bearing lateral water pressures on either Geotechnical Design to Eurocode 7, subjected to an inclined load.
only be checked in the “equilibrium capacity failure of a 4m high gravity retaining wall (translational side of an embedded wall is Acknowledgements Springer-Verlag, London.
direction” (ie the direction of mode). unaffected since they act in the same All numerical analyses described Schuppener, B., Walz, B., Eurocode 7, a commentary, BRE. to failure. The action effect should result
application of H). It could be argued “equilibrium direction”. However, herein were undertaken using WeiBenbach, A. & Hock- Smith, C. C. & Gilbert, M. (2007), in a net amount of positive work done in
that it is pragmatic to consider mechanical analysis is known to be horizontal direction being the most upthrust beneath the wall might be LimitState:GEO version 2.0; Berghaus, K. (1998), “EC7 part “Application of discontinuity layout the collapse mechanism, and will always
equation 1 in a range of directions, problematic, and can for example obvious candidate. factored differently. see: www.limitstate.com/geo I: a critical review and proposal optimization to plane plasticity be unfavourable. Due to the involvement
which is not especially onerous sometimes lead to anomalous results The characteristic shearing The above issues arise principally for improvement: a German problems,” Proceedings of the Royal of material strength, an action effect is
to do. However, it is probably when undertaking an effective stress resistance T on the block/surface because friction is involved in the References perspective”, Ground Engineering Society A: Mathematical, Physical and considered permanent.
preferable to instead consider a analysis. interface is given by: problem, leading to the resistances Bond, A. & Harris, A. (2008), 31(10), 32–35. Engineering Sciences 463, 2086 pp. An example of an action effect is
range of anticipated equilibrium and action effects in the problem Decoding Eurocode 7, Taylor and Simpson, B. (1997), “Theme 2461–2484. an active earth pressure. Note that
directions using the full procedure, Components of actions not Tk = Pk cos α tan φk (3) being functions of applied actions. Francis. lecture: Some questions about Smith, C. & Gilbert, M. (2010), there is an inconsistency here in
as is standard practice, and to aligned with the equilibrium BSI (2004), BS EN 1997-1:2004 limit state design in geotechnical Advances in computational limit Eurocode 7 where it is stated that
determine the critical direction. direction The horizontal component of Pk is Conclusions Geotechnical design. General rules. engineering, in Proceedings of the state analysis and design, in earth pressures may be considered as
Note that in the preceding example The proposed methodology requires always considered unfavourable (for 1. Eurocode 7 employs “material Driscoll, R., Powell, J. & Scott, Fourteenth International Conference GeoFlorida 2010: Advances in Analysis, actions (or specifically, geotechnical
the angle of 15° was used here that only those components of 0° < α < 90°). Thus the requirement factor”, “action factor”, and P. (2005), A designers simple guide on Soil Mechanics and Foundation Modeling Design (GSP 199), ASCE, actions).
purely for illustrative purposes, and actions aligned with the “equilibrium for safety (equation 1), after “action/resistance factor” type to BS EN 1997, Technical report, Engineering’, Vol. 4. p. 119. However, in a general numerical
in this specific case the most critical direction” are factored. This appears applying the action factors from design approaches. Department for Communities and Simpson, B. (2000), “Partial factors: analysis earth pressures cannot be
equilibrium direction for the wall is to run counter to the generally held DA1/1, becomes: Local Government, London, www. where to apply them?”, in LSD2000: Appendix I: Definitions of known until the critical collapse
actually close to the horizontal. view that a whole action should 2. “Material factor” design communities.gov.uk/documents/ International Workshop on Limit State Eurocode 7 actions, action mode is identified. (For hand
be factored by the same amount. 1.35Pk sin α < Tk (4) approaches (for example DA1/2 planningandbuilding/pdf/153986. Design in Geotechnical Engineering, effects and resistances calculations, the use of closed form
n To test for overturning stability of A simple example will be used to and DA3 in Eurocode 7) can pdf. Melbourne, Australia. In order for partial factors to be solutions such as Rankine’s earth
a wall (for example), a hypothetical explore this issue further. or be used without difficulty in Driscoll, R., Scott, P. & Powell, Simpson, B. (2007), Approaches correctly and consistently applied, pressure equations can serve to
moment M should instead be Figure 4 depicts a problem conjunction with general numerical J. (2008), EC7 - implications for UK to ULS design – The merits of it is important that what constitutes mask this issue.)
applied to the wall to cause failure, involving a weightless rectangular tan α < tan φk (5) analysis procedures, which will practices. Eurocode 7 Geotechnical Design Approach 1 in Eurocode an action, action effect, and a resistance
with equation 1 then formulated in block resting on a horizontal 1.35 automatically identify the critical design, CIRIA. 7, in ISGSR2007 First International is clearly defined. Resistance A resistance can only be
terms of moments. rigid surface and subjected to a collapse mode. A “material factor” Driscoll, R. & Simpson, B. (2001), Symposium on Geotechnical Safety & However Eurocode 7 itself is defined for a specific failure mechanism.
permanent load P inclined at angle This is similar to the type of safety analysis can effectively be considered “EN1997 Eurocode 7: Geotechnical Risk, Shanghai Tongji University, not fully clear on this matter, as It must involve material strength in
n One challenge for the “action/ α to the vertical. If the angle of margin that would be prescribed by to emulate the fundamental Design”, Proceedings of ICE, Civil China. evidenced by several different such a way that the mobilised strength
resistance factor” approach is friction of the interface between the DA1/2, where a factor of 1.25 is Eurocode 7 stability test Ed ≤ Rd for Engineering 144, 49–54. Simpson, B. & Driscoll, R. (1998), interpretations of these definitions opposes the specific failure mechanism
identification of suitable factors for block and rigid surface is φ’, clearly applied to tan φk: action effect and resistance pairs at in the literature. In this paper, being examined. The resistance should
combined and other non-standard the block will slide if α > φ’ and be all locations within a given problem. the following are proposed as cause a net consumption of energy
failure modes. For example, at stable if α < φ’. Stability may be tan α < tan φk (6) unambiguous definitions suitable in the collapse mechanism. It should
present Eurocode 7 DA2 specifies assessed in a number of ways. 1.25 3. “Action factor” and “action/ Value Partial Product for use in geotechnical numerical be determined using a “resistance
different factors for bearing, passive resistance factor” design approaches factor analysis: model”and is taken at a pre-specified
and sliding resistances, but it is Design check 1 (direct approach): Now the above might be (such as DA1/1 and DA2 in location within a design problem (as
unclear what factors should be used An engineer performing a Eurocode considered to violate the principle of Eurocode 7) are more challenging Action W 41.3 1.35 55.8 Action A (direct) action is a force or with action effects).
for mechanisms that cannot clearly 7 design check, for example using factoring actions, since components to undertake using numerical load whose value is independent of the An example of a resistance is
be classified as involving bearing, DA1/1, would correctly surmise that of P are being factored differently, analysis procedures. This paper has Action effect A 65.5 1.35 85.7 collapse mechanism. Within a defined bearing resistance for a footing or
passive or sliding failure. the inclined load is a single action. and if the uncertainty is in the proposed a simple and consistent failure mechanism it may be either passive earth pressure for a retaining
Assuming φ’ = 30°, if α > 30° then magnitude of P then “all of P” methodology designed to address (kN/m) sum 104.8 141.5 favourable (if it opposes collapse by wall. Note that a resistance may
n It is also possible to use the P will be unfavourable with regard should be factored simultaneously. this. Using this methodology an consuming energy) or unfavourable (if also be a function of actions.
proposed methodology to compute to sliding, and should be factored by However, the counter argument is analysis is carried out using a pre- Resistances P 29.2 (1.0) 29.2 it assists collapse by doing positive work These source actions may or may
a conventional FoS. 1.35. However, clearly any positive that: specified “equilibrium direction”, within the mechanism). not oppose the failure mechanism.
value of P will lead to sliding failure. n As has already been chosen according to the nature of (kN/m) S 104.3 (1.0) 104.3 An example of an action is the Driscoll et al. (2008) suggest that
Discussion If α < 30°, then P will be favourable, demonstrated, no margin of safety the anticipated collapse mode (for dead weight of a foundation or an BS EN 1997-1 is rather ambiguous
and should be factored by 1.00. In can be identified using the “direct” example horizontal when sliding sum 133.5 133.5 external structural load. about the treatment of “favourable
Characteristic values in the this case no positive value of P will approach, rendering it of little value. failure of a standard retaining wall Variable loads almost always earth pressures”, and argue that a
mechanical analysis lead to sliding failure – ie the partial n The “direct” approach involves is to be checked). Outcome Ek < Rk Ed > Rd fall into this category. Static water passive pressure should be regarded
When applying the proposed factors have had no effect on the factoring of actions at a different An additional disturbing force pressures are also usually regarded as a resistance rather than a fa vourable
methodology it should be noted that assessment, and no margin of safety stage in the calculation to the in this “equilibrium direction” is Safe Unsafe as actions. action; the present authors agree and
all mechanical analyses are carried can be identified. factoring of action effects and then applied, which causes a ULS Action effect The effects of actions make the same assumption in this
out using characteristic values. The resistances. It is suggested that it is collapse mode to be induced. The Table 3: Components of “actions” (self weight, W), “action effects” can only be defined for a specific failure paper. This contrasts with some of
main argument for this is that it Design check 2 (using proposed logical to apply factors to actions, fundamental Eurocode 7 stability (active earth pressure, A) and “resistances” (passive earth mechanism and are to be taken at a the previous literature, for example
ensures that physically unreasonable methodology): action effects and resistances at one equation, Ed ≤ Rd, is then also pressure, P and base shear resistance S) arising from the forced pre-specified location within a design Orr & Farrell (1999).
scenarios are not modelled. For Now consider a design check which stage of the calculation only. evaluated in this “equilibrium failure mechanism shown in Figure 3, together with a check using problem. An action effect is derived from Note that the above definitions of
example, the factoring of pore uses the proposed methodology. In n DA1/1 typically addresses limit direction”. DA1/1. The components are resolved in the chosen “equilibrium an “action effect model” which will action effect and resistance are given
water pressures (which are regarded this case an “equilibrium direction” state STR (which would involve The requirement to have a pre- direction” (15° to the horizontal) and their type (action or typically involve actions and material in the context of the geotechnical
as actions) prior to performing a must first be prescribed, with the subsequent analysis of the internal specified “equilibrium direction” resistance) determined according to their effect in this direction. strength and will act to drive the system component of an analysis. For

28 ground engineering october 2011 ground engineering october 2011 29


TECHNICAL PAPER
internal structural design checks, it n The hypothetical external action from the Structural Eurocodes). action within the problem, and
will, for example, typically be found M applied is an unfavourable This approach may at first sight providing
that a resistance is simply a material moment applied to the cross-section. seem cumbersome in that the check
property and is unaffected by the It is increased until the ULS is must be done separately at all cross- λA ≥ 1.0 (9)
failure mechanism. reached (assumed in this case to sections in e.g. a sheet pile wall.
trigger the formation of a plastic However, it is evident that the only then the design is safe.
Appendix II: Assessment of hinge within the cross-section), i.e. quantity to be factored during the
internal structural stability the system is being perturbed by analysis is the action effect (ie the With this approach, the numerical
When checking the internal stability applying an additional moment to induced bending moment at the method can automatically identify
of a structure such as a sheet pile initiate collapse. relevant cross section at the ULS), the critical structural collapse
wall using an “action/resistance” The magnitude of this moment since the resistance is known in mechanism without recourse to
approach, it is normally necessary is used to judge the stability of advance. multiple assessments.
to check for bending failure (and in the structure. (A small additional Thus an equivalent inverse It should be pointed out that
some cases shear failure). moment is indicative of a low factoring approach can be used equations 8 and 9 are generally only
In this check, the action effect/ margin of safety whilst a large to great advantage. This is similar directly equivalent to equation 7 if
resistance pair to be compared in additional moment is indicative of to the approach recommended by the ULS involves formation of a
equation 1 is taken, for example, as a higher margin of safety). Frank et al. (2004) in the context of single plastic hinge.
bending moment/plastic moment n To undertake the design check in spring models for retaining walls, However, when multiple
of resistance in a structure. To accordance with Eurocode 7, it is and in effect turns the calculation plastic hinges form the inverse
follow the proposed “action/ necessary to determine the actual into a “material factor” type factoring approach should always
resistance” analysis procedure characteristic moment (an action calculation as follows: produce conservative results
correctly, it would be necessary to effect) Ek acting at the cross-section (cf. results obtained using the
consider separately the stability of by considering the forces/moments 1. In the numerical model, the standard “action/resistance factor”
all cross-sections in the structure as other than M acting at the induced plastic moment of resistance of approach).
follows. For any given cross-section: ULS. the structural element Mp can be
n All quantities enter the calculation n Equation 1 then takes the set to be equal to the design plastic
as characteristic values (with the following form: moment of resistance divided by γG,
exception of variable actions, which ie
will be considered in Part II of the γGEk ≤ Mp,k (7)
paper). γM Mp = Mp,d/γG = Mp,k/(γMγG) (8)
n The “equilibrium direction”
is prescribed to be rotational, to where γM is the partial factor for 2. The adequacy factor λA can then
initiate bending in the cross section. the structural material (to be taken be applied to any unfavourable

A
The Construction Information Service is an
expert knowledge tool that delivers key technical
information critical to all construction projects

Complete
in one easy-to-use on-line package.

Developed by IHS and NBS, it provides instant


full-text access to current regulations, standards,

Package technical advice and a vast array of related news


and briefings.

Fully searchable, intelligently classified and

The constantly updated, it’s an indispensable source


of key information, tailored to meet your real needs.

Construction www.uk.ihs.com/tcis02 Telephone 01344 328000

Information
Service

1432_0510WE_New Civ Eng Half ad.indd 1 06/05/2010 16:03

30 ground engineering october 2011

Вам также может понравиться