Abstract:
This paper integrates information on process, principles and practices followed in
Hemant Gor
M.Tech (IITB)
design and execution of Tall Buildings. This paper describes various lateral load
resisting system used in Tall building and how to manage biggest enemy of tall
building-Wind loading. Tall building projects are outcome of collaborative
approach among multi-discipline expertise and problem-solving attitude.
Introduction
Tall building project brings together high strength materials, experienced
professionals and innovations. Burj Khalifa which signifies human ambition to rise
higher reflects an integration of these three critical aspects:
l High strength concrete till 601m and 227m steel spire at top
l Collaboration among Architect, Structural Engineer, Wind Engineer, Building
Facility Engineers, Façade Engineer, Geotech Engineer and Construction
l Innovation in concrete technology, lateral load resisting system and elevator
This paper presents following key aspects of tall building projects:
l Design Stages
l Lateral Load Resisting Systems
l Strategies to manage wind load
l Design challenges
Design Stages
Design of Tall buildings have following three stages
1. Conceptual Design(Competition Stage) (CD)
2. Preliminary Design (PD)
3. Detailed Design (DD)
Figure 4 – Aon Center, Framed Tube – Closely spaced perimeter Figure 5 – Sears tower, Bundled Tube – Closely spaced perimeter
columns tied together with beams columns tied together with beams
Fig 10-a: Plan of Burj Khalifa showing Lower Impact wind Figure 10-b: Orientation of nose of Burj Khalifa along extreme wind
direction(Reference 3) direction
Tall building Challenges
Concrete for Tall Buildings
Figure 11 demonstrates challenges faced by Structural
Traditionally, compressive strength tests are performed at 28
engineer in tall building projects.
days, but many high-rise buildings now requiring high strength
concrete (HSC) employ a construction schedule whereby the
structural elements in the lower floors are not fully loaded for
Structural periods of a year or more. Under these circumstances, it is
lateral reasonable to specify compressive strengths based on either
strength and 56- or 90-day results, thereby taking advantage of the strength
stiffness gain that occurs after 28 days. For Burj Khalifa compressive
Differential strength of wall at the lower floor was specified Cube
Hoisting of axial compressive strength 80MPa and Young's modulus 43,800MPa
materials shortening at 90 Days.
Concrete provides following advantages in the tall building:
Tall Building
Challenges · The mass and rigidity of concrete provides twice the
dampening effect compared to steel, reducing forces on
Motion super-tall buildings due to wind and the cost of
(acceleration) construction
Wind loading perceptions · Structural concrete is naturally fire resistant and sound
at higher insulation
Setting out levels
· Advancements in concrete pumping technology, including
and the introduction of placing booms, make easy, fast delivery
Verticality of concrete possible, freeing tower cranes for other work.
· Improvements in concrete mixes, including strength and
modulus of elasticity (E) have made high-rise construction
more attractive. Self-consolidating concrete (SCC) is
Figure 11: Tall Building the Structural Engineering Challenges increasing in use too.
References
1. Tall Buildings, A working group of the Concrete Centre and fib Task Group 1.6
2. Design of High-Rise Building:Past, Present and Future, K Kayvani, 23rd Australian Conference on Mechanics of Structures
and Materials
3. Engineering the World's Tallest – Burj Dubai, William F. Baker, D. Stanton Korista and Lawrence C Novak, CTBUH 8th World
Congress 2008
4. Structural Design of Reinforced Concrete Tall Buildings, Ali Sherif S Rizk, CTBUH Journal,2010 Issue
5. Wind Tunnel Methods, D Boggs and A Lepage, ACI SP 240-6
6. The Design and Construction of the World's Tallest Building: The Burj Khalifa, Dubai, Bill Baker, James Pawlikowski,
Structural Engineering International, 4/2015
7. Council on Tall Buildings and Urban Habitat. Tall Building Database. www.ctbuh.org. and www.skyscrapercenter.com
8. Structural Developments in Tall Buildings: Current Trends and Prospects, Mir M. Ali and Kyoung Sun Moon, Architectural
Science Review, Volume 50.3, pp 205-223
9. Tall Building Initiative, Guidelines for Performance Based Seismic Design of Tall Buildings, PEER, April 2017
10. Tall Buildings, Concrete Quarterly Special Issue No 1, The Concrete Centre
11. Case history Report, the world's tallest concrete skyscrapers. Bulletin No 40, CRSI
Introduction
As India experiences rapid development, cities will continue to see huge spurt
in the demand for affordable housing and commercial real estate, not just in the
metro cities but also in tier 2,3 and 4 cities. In response to this need, the urban
development ministries of the states have increased the allowable built up area
on land by means of augmenting Floor Area Ratio (FAR or FSI). Most cities now
typically have new buildings of 15 storeys and higher (50m+) to consume the
Alpa Sheth available FAR. The structural engineering community across the country was
Managing Director,
VMS Consultants Pvt. Ltd. not geared to the sudden increase in building heights and there were gaps in the
vmsb@vakilmehtasheth.com conceptualisation and design process of tall buildings. Unlike low-rise
buildings, design of taller buildings are driven not by gravity loads alone; lateral
loads such as wind and earthquake play a defining role in conceptualising the
design.
A standardized design protocol to ensure acceptable performance of tall
structures in terms of safety and serviceability was needed. Such a Standard
Code of Practice did not exist in India for design of tall buildings. Hence a new
Standard for Criteria for Structural Safety of Tall Concrete Buildings was
developed.
This standard provides prescriptive requirements for design of reinforced
concrete tall buildings. The following salient aspects, which are based on the
prescriptive approach, are addressed in this standard:
a) Structural systems that can be adopted in tall building;
b) General requirements including;1) height limitations of different
structural systems, 2) elevation and plan aspect ratios, 3) lateral drift, 4)
storey stiffness and strength, 5) density of buildings,6) modes of vibration,
7) floor systems, 8) materials, and 9) progressive collapse mechanism;
c) Wind and seismic effects:1) load combinations, and 2) acceptable
serviceability criteria for lateral accelerations;
d) Methods of structural analysis to be adopted, and section properties (in
cracked and uncracked states) of reinforced concrete member to be
considered in analysis;
It has been generally found that an aspect ratio H/b (height analysis. As noted by F Naeim in his paper "The performance-
versus least plan dimension) exceeding 10 results in very based alternative procedure requires an in-depth
slender buildings that may require some damping device to understanding of ground shaking hazards, structural materials
reduce heightened perception of motion (akin to sea or car- behavior, and nonlinear dynamic structural response. In
sickness). IS 16700 has thus restricted aspect ratio to 10. It particular, the implementation of this procedure requires
may be pertinent to mention that there has been in recent proficiency in structural and earthquake engineering including
times, a trend, however limited, of super-tall buildings with very knowledge of: seismic hazard analysis and the selection and
high aspect ratio, also called "Pencil Towers". This trend is scaling of ground motions; nonlinear dynamic behavior of
prevalent in New York and in recent times in cities such as structural and foundation systems; mathematical modeling
Boston and Melbourne. None of the above mentioned cities capable of reliable prediction of nonlinear behavior; capacity
have a severe or very severe seismic hazard. Los Angeles (LA) design principles; and detailing of elements to resist cyclic
and San Francisco (SF) which have very severe seismic hazard inelastic demands, and assessment of element strength,
do not have such pencil towers. Buildings in LA and SF that do deformation and deterioration under cyclic inelastic loading.”ii
not follow the prescriptive codes of ASCE 7, ACI 318 and other 2.3 Building Modes Under Seismic Loads
codes mandated by the local authority are required to follow
special, non-prescriptive procedures as mandated by Los The IS 16700 code does not allow for torsion irregularity. It
Angeles Tall Buildings Structural Design Council (LATBSDC) "An stipulates that the first two modes of vibration should be
Alternative Procedure For Seismic Analysis And Design Of Tall translational modes and the torsion mode cannot be earlier
Buildings Located In The Los Angeles Region" and by SEAONC, than the third mode of vibration with a mode spacing of at least
2007, "Recommended Administrative Bulletin on the Seismic 10% between consecutive modes. This requirement is in line
Design & Review of Tall Buildings Using Non-Prescriptive with the revised IS 1893 code definition of torsional and vertical
Procedures" respectively. The requirements are complex and irregularities. This requirement creates a challenge for
need a detailed performance based design using non-linear buildings symmetrical across both principal axes where the two
Type A damage — major damage to structure. Type B damage — roof planks slipped.
Type C damage — minor dislocation of roof planks. Type D damage — minor opening of grouted joints.
They code identifies the different cases when backstay effect 2.9 Foundations
will occur and requires the backstay floor diaphragms to be
IS 16700 has made significant changes in design of
modeled considering their actual in-plane and out-of- plane
Foundations for Tall Buildings. It has specified factor of safety of
stiffness shall be designed for the maximum of forces derived
1.5 for unfactored wind and gravity loads and 2.5 for design
from sensitivity analysis.
earthquake and unfactored gravity loads. Modelling raft
For plan irregularity as per Table 5 of IS 1893 (Part 1) of Type i, foundations will require use of zoned spring constants or
Type ii and Type iv as well as Type iv of Table 6 (vertical zoned modulus of sub-grade reaction for dead load + live load
irregularities) seismic forces shall be amplified by a factor of 1.5 condition. For buildings taller than 150 m, a soil-structure
in the design of connections of diaphragms to vertical elements interaction study to conducted
and to collectors; and for design of collectors and their
Further the allowable deformation of mats has been relaxed to
connections.
125 mm (50 mm in rock) subject to angular distortion being
For irregularity of Type iii (diaphragm discontinuity), seismic within 1/500. These limits are in keeping with international
forces to be amplified by an over-strength factor of 2.5. practice. The depth of foundation is required to be min 1/15 in
Backstay diaphragms have to be designed for maximum forces raft and 1/20 for piled foundations to account for uplift issues.
obtained from sensitivity analysis and must be minimum 150 The requirement may be relaxed when there is not net uplift
thick with two layers of steel in each direction and 0.25% anywhere in the foundation.
reinforcement in each direction. The soil investigation requirements are stringent. Minimum 3
There are many more detailed requirements provided in the boreholes are required in each tower with depth of minimum
code for design of backstay elements. 1.5 times width of foundation and 30 m in rock. While borehole
investigation in rock of 30m may seem excessive, there are
2.8.2 Structural Walls regions in India where rock is underlain by soft layers and this 30
The code has revised minimum thickness of structural walls as m is meant to capture such situation.
160 mm (200 mm in seismic zones IV and V) to align with fire 2.10 Non-Structural Elements
code requirements (min 2 hours rating). It has further identified
cut-out sizes in walls that may be ignored in analysis and design IS 16700 has detailed design guidelines for securing of non-
beyond which they will need to be modelled. Minimum structural elements. The underpinning rational and design
reinforcement of 0.4 % in each direction (in two layers) is to be background is available in another documentv . The discussion
provided . of non-structural elements has its genesis in the fact that there
Reference
i
John Zils and John Viise: "An Introduction to High-Rise Design", S T R U C T U R E m a g a z i n e November 2 0 0 3
http://www.structuremag.org/wp-content/uploads/2014/10/highrise.pdf
ii
F. Naeim et al: "An Alternative Procedure for Seismic Analysis and Design of Tall Buildings", 15WCEE 2012.
iii
Jain S K et al: "Bhuj, India, Earthquake of January 26, 2001, Chapter 14, Hospitals and Schools", Earthquake Spectra 18:Sup A (Jul 2002)
http://www.iitk.ac.in/nicee/skj/Research_Papers/2002_spectra_Bhuj_Hospitals&Schools.pdf
iv
Murty CVR et al: "Some Concepts in Earthquake Behaviour of Buildings", Gujarat State Disaster Management Authority 2013
http://www.iitk.ac.in/nicee/IITK-GSDMA/EBB_001_30May2013.pdf
v
Murty CVR et al: "Introduction to Earthquake Protection of Non-Strucural Elements" , Gujarat State Disaster Management Authority 2013
http:// www.iitk.ac.in/nicee/IITK-GSDMA/NSE_002_31May2013.pdf
ABSTRACT
India has never had a specialized seismic code for hospital
buildings and, hence, in the event of an earthquake, it is
Amir Gilani, PhD
expected that most if not all hospitals structures will have
serious structural damage and many will even collapse. The
pancake collapse of the Bhuj Hospital on 26Jan2001, wherein
the patients and the hospital staff died after getting buried in
the building debris, is still fresh in the minds of many. This paper
presents a simple performance-based approach for upgrading
existing multi-story hospital buildings. The procedures given
are simple to design and easy to execute on site. The paper also
specifies how the designer needs to select more stringent
performance objectives in terms of flexure hinge demand than
the minimum specified in the code/guidelines literature for
important structures like a hospital building. The case study
Kit Miyamoto, PhD presented in this paper deals with a steel building, however the
same principles can equally be applied to concrete buildings
also. The same design methodology can also be used to design
new steel buildings and will be significantly less expensive than
if energy dissipation (dampers) were not used.
This paper presents a performance based approach to upgrade
the seismic performance of a multi-story hospital structure
located in Southern California. The uppermost eight stories of
the superstructure use steel framed construction, whereas
reinforced concrete framing is used for the lowestfloor (L2) and
the four sub-grade parking stories. The building is rectangular in
Sandeep Shah plan, has a typical story height of 3.6 m (11.8 ft) and a total floor
Miyamoto International, area of 12,000 m2(130,000 ft2).In both lateral directions, steel
Inc.West SacramentoCA/USA moment-resisting frames using Pre-Northridge connection
Program-default hinges were used, because plastic hinge FVDs have been successfully utilized in upgrading the seismic
rotations are limited to small amount for the upgraded performance of structures. This methodology is one of the
structure. For verification, provisions of FEMA 273 [FEMA 1997] recommended practices [FEMA 2000] and has been
were used to separate a second model. The comparison of successfully implemented in both new construction
building responses validated that the program-default flexural [Miyamoto et. al, 2003-2] and in seismic rehabilitation
hinges were adequate. Nonlinear flexural hinges were placed [Miyamoto et. al. 2003-1] by the authors. The proposed seismic
0
0.4
-1
0.0
-2
0 5 10 15 20 25
5 10 15 20
Time, sec Roof displacement, in.
1 10
BSC, %g
Drift, %
0 0
-1 -10
-2 -20
5 10 15 20 5 10 15 20
Time, sec Time, sec
the exact formulation. As shown in Table 4, the computed drift hysteretic energy dissipated by this damper. This energy was
demands are below or slightly above 1% radian and as such the obtained by integrating the area under the force-displacement
design satisfies the requirements for drift limits. The entries of curve. Note that significant seismic energy is dissipated by a
this table correspond to the computed drift at the center of single damper. Similar results were noted for all dampers. In the
mass of the structure. absence of dampers, the seismic energy absorbed by FVDs
would have to be dissipated by the yielding of steel frame
The maximum seismic demand (force, velocity, and
deformation) on FVDs was evaluated. Figure 7 presents the members, resulting in unacceptable large flexural rotations in
these members.
axial-force-axial displacement hysteresis response for a typical
FVD obtained from analysis. Also shown in the figure is the Table 4. Computed story drifts (% radian).
3000 400
2000
1000
Axial force, kN
Energy, KJ
0
200
1000
-2000
-3000
-60 -30 0 30 60 0
Axial displacement, mm 5 10 Time, sec 15 20
a. Existing b. Retrofitted
SUMMARY AND CONCLUSIONS was then modified by the addition of a limited number of FVDs.
In the upgraded structure, the story drifts and member
Seismic response of a multi-story hospital building using
nonlinear rotational demands were below the target values
unreinforced steel beam-to-column connections was
specified in the design criteria. As such the upgraded structure
evaluated by analysis. It was seen that the structure did not
meets the design criteria and is anticipated to perform well in
meet the Life Safety requirements of FEMA 1997. The structure
seismic events.
REFERENCES
AISC 1980, Manual of Steel Construction, Allowable Stress Design, Vol. 1, 9th Ed., American Institute of Steel Construction,
Inc.
AISC 2001, Manual of Steel Construction, Load & Resistance Factor Design, Vol. 1, 3rd Ed., American Institute of Steel
Construction, Inc.
AISC 2002, Seismic Provisions for Structural Steel Buildings, American Institute of Steel Construction, Inc.
CBC2001, CaliforniaBuilding Code, CCR, Title 24, Part2, Vol. 2, CaliforniaBuilding Standards Commission.
ABSTRACT
Codes and Standards are integral part of a structural engineer's tool-kit. In
highway sector, for quite a few years now, perhaps caused by the transition from
the working stress philosophy to limit state philosophy in IRC codes, heated
debate on the complexity, content and size of codes has been going on. There
are two distinct school of thoughts, one in favour of keeping the codes simple
and prescriptive and the other in favour of bringing modernity in the codes and
Alok Bhowmick
standards, at par with the international codes, which are growingly becoming
MD, B&S Engineering Consultants
Pvt. Ltd., Noida (U.P), India more and more complex and voluminous. The important question that comes
to our mind is whether the codes and standards in its present form is helping the
structural engineers to develop their engineering skills or is it stifling their
creativity? The objective of this paper is to share author's own experience, both
as a code-user as well as a code-maker, on the status of present codes, what they
should be, how they should be upgraded, how they should be treated in
education, practice and how domestic research should affect them.
INTRODUCTION
Large scale construction and rapid urbanisation are an integral part of India's
growth process. Unplanned, un-regulated and non-engineered structures are
allowed to be built in India due to lack of regulation of engineering profession,
which puts millions of lives, livelihoods and assets at great risk. Adoption of
certain minimum standards and following the available codes of practices is
therefore necessary, as it aims to mitigate this risk, and loss of investment in built
environment. It helps manage multiple risks to infrastructure as well as
increasing functionality in its day-to-day operation. Thecodes of practices for
structural design influence the professional activities of all structural engineers.
Whilst few will be involved with their creation, adaptation and updating, the
great majority of practicing structural engineers are code-users, who will utilise
their contents – some imaginatively and as an aid, some in a prescribed and
unthinking fashion, a few in a defensive and negative way. Attitudes amongst
users widely vary (supportive, puzzled, irritated, grateful etc). To the same
individual they may well, at different times, be helpful, informative, restrictive or
troublesome. Many user abuse the codal clauses, to suit their contractual
position in a project, depending upon which side of the table they are in and
which agency they represent.
STRUCTURAL ENGINEERING DIGEST / JULY-SEPTEMBER, 2018 | 31
Making the built environment resilient and robust requires not designs through the prism of codal compliance route.
only constant development and upgradation of the codes and The legal status of Codes varies from country to country. It is
standards, but also ensuring that changes brought about in the enshrined in law in some countries, while it is merely advisory
codes is well understood by the practicing structural
and optional in others. The perception about their legal
engineers, academia, as well as the software developers, so standing is even more wide-ranging (and often
that the industry is able to quickly adapt themselves to the misunderstood), with structural engineers often believing
changing mode of development. This is of-course easier said
codes to be more influential than is actually the case. There is
than followed. It is a huge challenge and aiming to achieve this of course a considerable variation in the quality of codes in
would require brain-storming sessions between all the different countries, which varies from 'lucid', 'polished' and
stakeholders. Important issues that the government of the day,
'highly relevant and valuable' documents to 'unclear',
the policy makers, the academia, the structural engineering
'ambiguous' and 'misleading' offerings.
fraternity together must address in this respect are the
following : Expectations from the code also widely varies depending upon
the person who is looking at it. A practicing structural engineer
a. What is the role of Codes / Standards? Is there enough
with little insight into the subject will plead for simplicity in a
clarity on the subject to the practicing structural
code both for speed of application and to enable it to be used
engineers?
by engineers with limited experience. Some structural
b. Are the existing codes and standards easily understood by engineers would treat the code as text book and expect
the practicing engineers and fully implemented? Is there solution in the code for every problem that he is likely to face in
any improvement needed in the way codes are developed? design. Others with wide experience and having deep
c. Does our codes and standards stifle creativity? Should the knowledge on the subject would expect the code to address
format and content of codes be changed to promote only the fundamental knowledge when designing and would
lateral thinking? expect the code to give freedom for creativity and innovation in
d. Are our codes and standards at par with the international design. Those competing for worldwide markets would require
standards? If not, what needs to be done to narrow this the code to be at par with the international codes so that
gap? structural engineering practice becomes universal and
e. Are our structures by and large code compliant? Is there practicing in global market becomes easy. Researchers and
any way by which we can ensure compliance to code and academicians on the contrary desire a code to be technically
thereby fix accountability for design faults, if any? perfect and comprehensive, making use of the most recent
research results. They would not like (over)simplification in the
f. Does India have the internal capacity (both in terms of
code.
quality and quantity) to quickly upgrade our codes and
standards and keep pace with International standards ? If The correct and ideal approach for any structural engineer,
not, what should be done to enhance capacity? should be to treat the available codes and standards as only
'one of the many' portfolio of material, which is to be used for
An attempt has been made by the author in this paper to
structural design. Designers are expected to understand the
address all the above issues on the basis of author's own
background of codal clauses, to look beyond the code as they
experience.
grow in the profession and also read international codes of
ROLE OF CODES practices to better understand the codal provisions of the
Structural codes typically contain a mix of information, country. Manufacturers' literature, design guides, computer
software, textbooks, manuals, volumes of worked examples
including factual data, design rules, advice on good practice
and specific references elsewhere. Although their precise etcall should form a part of structural engineers tool-kit while
status varies in different parts of the world, it is generally performing designing and detailing.
accepted that the easiest way to demonstrate structural DEVELOPMENT PROCESS FOR CODES & STANDARDS IN
adequacy (and thus to gain an approval from client) is to show INDIA
that the methods used in design agree with the provisions of
In India, there are several code making bodies such as :
the current local Code. Codes also comes very handy in case of
any failure, where the court of law looks at the adequacy of a) Bureau of Indian Standards (BIS),
REFERENCES
1. Presentation of Alok Bhowmick titled "Implementation of Codes and Standards in India's Transport Sector"at the Round
table on "Standards for Infrastructure Development in India's Transport Sector" organised by National Institute of Public
Finance & Policy
2. Paper titled "DO STRUCTURAL CODES STIFLE CREATIVITY?" by D. A. Nethercot, Department of Civil and Environmental
Engineering, Imperial College London, published in IABSE Spring Conference, Kualalumpur, April 2018
ABSTRACT
Taking note of non-availability and difficulty in having coarse
Dr. A.K. Mullick
Former Director General, and fine aggregate for concrete from natural sources in some
National Council for Cement and parts of the country and need of effective management of
Building Materials waste materials, BIS has recently permitted use of recycled
concrete aggregate (RCA), iron and steel slag, copper slag and
bottom ash. These have been called 'manufactured' aggregate
in IS:383-2016. The decision is in line with results of copious
R&D carried out in the country, some of which are described in
the paper.
Keywords: Aggregate, concrete, C&D wastes, industrial
wastes, standardisation.
INTRODUCTION
Aggregates, coarse and fine, occupy nearly 75 percent of
volume of concrete. Next to water, concrete is the most widely
used material the world over. One of the reasons for this wide
acceptance is that the ingredients of concrete are either
naturally occurring, or made from naturally occurring raw
materials. Industrial waste materials also find increasing
acceptance in making cement and concrete.
Most project specifications prescribe aggregate from natural
sources. In particular, it is required that coarse aggregate shall
consist of clean, hard, strong, dense, non-porous and durable
pieces of crushed stone, crushed gravel, natural gravel or
combination. Fine aggregate shall be natural sand, crushed
stone, crushed gravel and combination, and Grading of Zone I, II
and III are preferred.
In fact, all the properties of concrete dependant on the surface processing of the RCA. Recent research on use of recycled
characteristics of coarse aggregate are affected. Such concrete aggregate in M75 grade concrete, after due
properties are; compressive and tensile strength, workability, processing and improved mixing techniques have been
elastic modulus; and durability characteristics like water published (4, 5). The effects of removal of adhered mortar are
absorption, sorptivity, drying shrinkage, abrasion resistance summarised below.
and chloride ion penetration [5].
Materials used in this investigation were Portland pozzolana
R & D on use as Coarse Aggregate cement conforming to IS: 1489 – Part I, fine aggregate (river
All the above-mentioned properties of concrete containing sand) and virgin coarse aggregate (10mm and 20mm sizes)
recycled concrete aggregate can be improved by proper conforming to IS: 383, Silica fume conforming to IS: 15388 and
RCA,
(500 Compressive strength( MPa) Flexural strength( MPa) Split tensile strength( MPa)
rev.)
7- 28- 56- 90- 180- 7- 28- 56- 90- 180- 7- 28- 56- 90- 180-
day day day day day day day day day day day day day day day
0% 70.69 85.43 93.81 99.33 120.1 8.87 14.93 15.67 16.73 18.13 4.44 5.25 6.65 7.02 7.60
10% 65.71 81.92 89.69 95.18 115.6 8.07 13.60 14.60 15.40 16.86 4.09 4.94 6.58 6.67 7.46
20% 63.04 80.51 87.90 92.50 110.1 7.73 13.00 13.73 13.80 16.20 3.97 4.80 6.40 6.44 7.40
30% 59.41 78.34 85.68 90.01 108.8 7.46 12.5 12.93 13.20 15.86 3.90 4.73 6.31 6.37 7.34
40% 58.43 75.40 83.22 87.68 106.2 6.93 11.53 12.33 12.80 15.20 3.86 4.63 6.08 6.21 7.19
50% 55.52 73.23 82.01 84.41 102.0 6.66 11.26 12.20 12.53 14.80 3.80 4.60 6.04 6.11 6.95
60% 54.76 71.30 80.60 82.47 99.58 6.46 10.80 12.00 12.06 14.20 3.78 4.51 6.03 6.08 6.69
70% 52.23 68.79 79.30 80.36 94.25 6.07 10.13 11.40 11.80 13.73 3.68 4.39 5.93 5.98 6.51
80% 50.00 65.43 78.37 79.85 90.19 5.80 9.60 11.00 11.26 12.93 3.57 4.29 5.89 5.95 6.42
90% 47.96 63.03 75.41 76.84 88.95 5.53 9.00 10.13 11.00 12.26 3.46 4.13 5.51 5.93 6.35
100% 45.89 62.30 74.82 75.98 84.42 5.40 8.07 9.20 10.26 11.80 3.36 3.98 5.47 5.82 6.23
Table 4. Properties of fine aggregate from RCA (6) The target slump of 75 mm was reduced to 65 mm (M30 grade)
and 59 mm in M40 grade, when 50 percent of natural sand
S. No. Material Water Absorption Specific Gravity
was replaced by RCA. This lowering of workability can be
1 Natural Sand 0.21 2.6 offset by use of chemical admixtures and using the aggregate
2 RCA 6.2 2.41. in saturated surface dry condition. Compressive strength
Two control concrete mixes viz. M30, M40 grades were of concrete of M30 and M40 grades were continuously
designed using virgin aggregates. Further mixes were obtained decreasing with the increase in replacement percentages of
by replacing the fine aggregate fraction with RCA in steps of 10 natural sand by RCA. Results for M40 grade concrete are shown
percent, up to 50 percent. No other changes were made. in Figure 3.
60
50
40 7 days
30 28 days
20 56 days
10 90 days
0
M40R00 M40R10 M40R20 M40R30 M40R40 M40R50
Figure 3. Compressive strength of M40 concrete with sand replaced by RCA (6)
Mix Natural Coarse Aggregate replaced by BF 28 – day compressive 28 –day split tensile
slag, % strength, MPa strength, MPa
1 0 (Reference mix) 69.16 3.17
2 10 69.54 3.50
3 20 70.03 2.17
4 30 71.52 3.30
Use as Fine Aggregate Unlike crushed rock sand, the proportion of fine fractions (<
150µ) was comparable to natural sand (<4.6%).
Coarser particles of BF slag of sand sizes have been envisaged as
part replacement of natural sand in concrete (2). Starting with Results of compressive strength of M40 grade concrete, in
larger pieces of granulated slag as feed material, it is crushed which natural sand was replaced in full or part by slag sand, as
and sieved in a manner similar to obtain crushed rock sand. well as combinations with crushed rock sand or crusher dust are
given in Table 6 (2). Addition of slag sand improved the
The resulting product conformed to grading zone II of IS: 383
compressive strength. Workability was satisfactory; in fact,
(Figure 4) and particle shapes were similar to river sand (sub-
mixing with crushed sand helped in achieving favourable
angular to sub-rounded). Any excess of elongated particles will
proportion of fine fractions.
need processing in a Vertical Shaft Impactor (VSI) crusher.
COPER SLAG AS FINE AGGREGATE
Sand-sized fraction of copper slag has been investigated as part
replacement of natural sand in concrete [8]. In this investigation,
copper slag conformed to grading limits, but the size fraction
below 1 mm was greater than in natural sand (Figure 5).
The concrete mixes had cement content 384 Kg/m 3 ,
water/cement ratio 0.6, coarse aggregate and fine aggregate
contents 1136 and 712.6 kg/m3 respectively constant, except
that the fine aggregate was made up of natural sand being
replaced by copper slag in increments of 20 percent. Results of
Figure 4. Comparison of Sieve analyses of natural sand (NS) and
slump and compressive strength are shown in Table 7 (8).
slag sand (GBFS) (2)
constitute about 20 percent of total ash content of the coal fed Sieve sizes(mm)
into the boilers. In view of substantial amount generated each Figure 6. Combined grading of mix of bottom ash and natural
year and already accumulated mixed with pond ash, it merits sand (9).
consideration.
The details of concrete mixes and results of slump and
Results of a comprehensive experimental investigations on use compressive strength are in Table 8. In order to maintain the
of bottom ash in cement and concrete, both as pozzolanic same workability at the same water content, the dosage of the
additive, and as replacement of natural sand as fine aggregate, superplasticiser had to be increased from 1% (in case of river
has been reported [9]. In this series of tests, as-received bottom sand) to 1.75% in case of 20 percent bottom ash. It was noticed
ash was used in part replacement of natural sand as fine that with 20 percent bottom ash replacing sand, the
aggregate. It conformed to grading zone II of IS: 383, had lower compressive strength of concrete at 28 days and later were
density and higher water absorption. At replacement levels up greater than with natural sand alone [9]. This was possibly due to
to 20 percent, the combination with natural sand was within the pozzolanic property of bottom ash, albeit much lower than fly
stipulated grading limits of zone II (Figure 6). ash from the same source.
REFERENCES
1. Mullick, A. K., Viable Alternatives to Natural Fine and Coarse Aggregate in Concrete, International Seminar on 'Emerging
Building Materials and Construction Technologies', BMTPC, New Delhi, March 2016, Proc., pp. 7 – 20.
2. Mullick, A. K., Alternatives to Natural Sand for Concrete and Mortar, Indian Concrete Journal, Vol. 89, No. 3, March 2015, pp.
10-21.
3. Indian Concrete Institute, Guidelines on Recycling, Use and Management of C&D Wastes, Report ICI/TC/05 – 01, October
2015, 58 p.
4. Babu, V. S., Mullick, A. K., Jain, K. K. and Singh, P. K., Strength and durability characteristics of high strength concrete with
recycled aggregate - Influence of processing, Journal of Sustainable Cement–based Materials (Taylor and Francis), October
2014.
5. Mullick, A. K. and V. Sarath Babu, Enhancement of Aggregate-Rerated Characteristics of High Strength Concrete with
Recycled Aggregate, 6th International Conference, Asian Concrete Federation, ACF 2014, Seoul, South Korea. Sept. 2014.
6. Parag Agrawal, Naman Dube, Mullick, A. K., and Babu, V., S., Fine fractions of recycled concrete as sand replacement, Indian
Concrete Journal, Vol. 88, No. 10, October 2014, pp.80 - 86.
7. Singh, V. P., High Performance Concrete Using Blast Furnace slag as coarse aggregate, Recent Advances in Energy,
Environment and Materials, pp. 90 – 94, ISBN: 978 – 1 -61804 – 250 – 7.
8. Alnuaimi, A. S., Effects of Copper Slag as a Replacement for Fine Aggregate on the behavior and ultimate strength of
reinforced concrete slender columns, TJER 2012, Vol. 9, No. 2, 90-102.
9. Mullick, A. K., Akash Jain, Anchit Lakhanpal and Krishna Murari, Pozzolanic Properties and Utilisation of Bottom Ash in
Cement and Concrete, Lead Paper, 6th International Conference, Asian Concrete Federation, ACF 2014, Seoul, South Korea.
Sept. 2014, Collection of Invited Papers, pp. 76 – 81.
FACT FILE
CLIENTS NAME : TATPADAM UPVAN, MIRAJ GROUP
NATHDWARA(RAJ)
SCULPUTOR : Mr. NARESH KUMAWAT, TEMPLESMAC,
GURGAON
STRUCTURAL CONSULTANT: SKELETON CONSULTANTS PVT.
LTD.
PROJECT COST : INR 100 Crores
CONSTRUCTION STATUS: ON GOING
PROJECT BRIEF:
A Gigantic 351-feet high Shiv statue is under construction at the
top of a 50m high hillock in the sitting position at Nathdwara
near Udaipur in Rajasthan. The base of the main statue approx.
60mx45m rectangular shape is representing a hill top.
This is one of the world's tallest in-situ concrete statues, being
fourth after Statue of Unity India 182m, Spring Temple Buddha
China 153m, Ushiku Daibutsu Japan 120m, this is 107m tall. As
per mandate from project Sponsors MIRAJ group Nathdwara,
the design life is 250+ years.
STRUCTURAL GEOMETRICS
The shape of statue is irregular & unsymmetrical. It falls in high
importance factor category as per IS1893.
Wind tunnel testing has been done in simulated wind
environment on scaled model of statue and surrounding
topography, at WindTech Consultants, Sydney Australia. The
ABSTRACT:
When liquefaction occurs, the soil loses its stiffness and
Prof. Mahesh Tandon
Managing Director, strength and can not only deform but also flow laterally. In-situ
Tandon Consultants Pvt. Ltd. testing is relied upon to assess the liquefaction potential of
New Delhi- 110014 soils due to the difficulties in obtaining and laboratory testing of
E-mail : mahesh.tandon@tcpl.com
undisturbed samples. The Standard Penetration Test (SPT) and
the Cone Penetration Test (CPT) are the two most frequently
used field investigations for determining the characteristics of
soils. In this paper SPT values have been used as they remain by
far the most popular and economical method of subsurface
investigation in India. The methods suitable for design offices in
the Indian context have received special attention in this paper
which examines the effects of liquefaction on piled bridge
foundations.
Keywords: Liquefaction, Inertial Effects, Kinematic Effects,
Evaluation
1. Introduction
IS 1893 Part 1 (2016) defines liquefaction as a state primarily in
saturated cohesionless soils wherein the effective shear
strength is reduced to negligible value for all engineering
purposes, when the pore pressure approaches the total
confining pressure during earthquake shaking. In this condition
the soil tends to behave like a fluid mas.
IS 1893 Part 1 (2016) stipulates the types of strata that should
be investigated to evaluate its potential for liquefaction.
The Caltrans Geotechnical Manual (2014) suggests that soils
with the characteristics shown in Table 1 are not liquefiable.
(13)
5. Conclusions
The paper highlights the methodology that should be
employed in bridge design offices in the Indian context while
determining the potential of liquefaction using SPT field tests.
The frequently used codal provisions have been reviewed.
Some differences between the two codes/guidelines, i.e., IS
1893 Part 1 (2016) and RDSO Guidelines (2015), have been
highlighted. Some of the missing provisions in these codes
have been discussed.
In many situations the liquefied layer is overlain by non
liquefied strata. The bridge site may be located on sloping
ground or near a water front, in which case Lateral Spreading
Fig. 5 Epicenters of Past-Earthquakes (from IS 1893) would occur creating significant lateral forces on the piles. A
MSF is determined from equation (11). simplified approach to account for the same has been
identified. Both inertial effects and kinematic effects of
(11)
liquefaction has been discussed in the paper.
References
Bhattacharya, S., Bolton, M., D., Madabhushi, S., P., G., (2005) A Reconsideration of the Safety of Piled Bridge Foundations in
Liquefiable Soils, Soils and Foundations, Japanese Geotechnical Society, Vol. 45, No. 4, 13-25, Aug.
Ghosh, B., Mian, J., Lubkowski, Z. A., (2012) Design of piles in liquefiable soil: A review of design codes and methodologies, 15 WCEE
LISBOA
Haigh, S. K. (2002). "Effects of earthquake-induced liquefaction on pile foundations in sloping ground." Ph.D. dissertation,
Cambridge University, UK
Idriss, I. M., and Boulanger, R. W. (2010), SPT-Based Liquefaction Triggering Procedures, Department of Civil & Environmental
Engineering, Report no. Center for Geotechnical Modeling UCD/CGM-10/02, December
Kavazanjian E., Martin, G. R., Dickenson S. E., Hung C. J., Lam, I., Shamsabadi, A., (2011) LRFD Seismic Analysis And Design Of
Transportation Geotechnical Features And Structural Foundations, NHI Course no. 130094, Reference Manual
Geotechnical Engineering Circular No. 3, Aug
Abstract
A large rail-cum-road double-deck multi-span steel truss bridge over
the mighty river Brahmaputra is considered in this study. The bridge is in
Nirmalendu Debnath service for more than fifty years and moreover situated in the highest
Department of Civil Engg., seismic zone of India. Thus, while monitoring the structural health of
IIT Guwahati this bridge is an important issue, the study of modal parameters of this
unique bridge structure is also a matter of great interest. The present
work deals with operational modal analysis (OMA) of the bridge using
measured acceleration responses under ambient vibration. Sensor
locations are suitably identified for effectively extracting the major
modes of this large bridge using limited sensors. Major modes are
identified for this large bridge using standard identification techniques.
Keywords: Truss bridge, Operational modal analysis, Accelerometer,
Ambient vibration.
1. Introduction
Anjan Datta OMA using output-only response data is usually performed for large
Department of Civil Engg., structures to identify modal parameters due to difficulties to perform
IIT Guwahati experimental modal analysis (EMA). Modal parameters identified at
different points of time are useful for structural health monitoring
(SHM). Further, identified modal parameters are required to update a
numerical model for better prediction of response and effective design
of control devices. Various real life structures are found to be
investigated for OMA e.g. Tsing Ma Bridge1, Alfred Zampa Memorial
Bridge2, Gi-Lu bridge3, FRP composite pedestrian truss bridge4, North
Grand Island Bridge5, Cumberland River Bridge6, Shanghai World
Financial Center7. Moreover, effects of temperature, traffic loading and
wind speed on modal and dynamic behaviour of structure are also
found to be analyzed8.
Presently, many techniques exist for OMA in time domain. Natural
S.K. Deb
Department of Civil Engg., excitation technique (NExT)9,a major development in time domain,
IIT Guwahati establishes the similarity between cross-correlation function (CF) of
ambient vibration responses measured at two locations and the
(a)
(b)
Fig. 2 Significant eigen mode shapes along (a) transverse and (b) vertical directions
4. Identified Modal Parameters: Central Tendency and (a) Appropriate use of limited numbers of accelerometers for
Dispersion acquisition of ambient vibration response for the large
bridge has yielded consistent modal parameters. Major
Modal parameters identified based on all the 55 data-sets transverse, vertical and torsional modes could be
employing all the techniques are taken into account for identified for the bridge.
statistical characterization. This approach can ensure better
acceptability in view of the probable presence of measurement (b) All the three identification techniques are observed to be
noise as well as leakages in signal processing and the fact that consistent in OMA for this large bridge structure.
the measured acceleration responses due to ambient vibration (c) A statistical approach in identification of modal
may differ from theoretical assumption of white noise induced parameters using multiple techniques both in time and
vibration. Statistical analysis includes: (a) histogram frequency domains can ensure higher reliability in view of
observation on natural frequencies and damping ratios (b) likely presence of measurement noise, leakage in signal
central tendencies of natural frequencies, damping ratios and processing and deviations in theoretical requirement of
mode shapes (c) measure of dispersion and confidence field ambient vibration being induced from white noise
intervals (CIs) of natural frequencies and damping ratios. excitations.
Table 2. MAC values between identified mean mode shapes using three techniques.
Mode No. MAC
NExT-ERA/SSI NExT-ERA/FSDD SSI/FSDD
1 0.9833 0.9826 0.9915
2 0.9986 0.9992 0.9994
3 0.9726 0.6623 0.7341
4 0.9912 0.9779 0.9944
5 0.9964 0.9952 0.9925
6 0.9308 0.9238 0.9088
7 0.8879 0.9380 0.9103
8 0.9871 0.9930 0.9934
1.0 INTRODUCTION
Kolkata, the city of joy, has its own glamorous history, which
amazes just in its own perfect way starting with "what Bengal
Mainak Ghosal
PhD Research Scholar, IIEST, Shibpur thinks today, India thinks tomorrow."Among all the historic
Structural Engineer/Valuer/Consultant: possessions, this city has another first in its balance sheet-
Banking & Construction Industry underground Kolkata Metro Rail . In the last twenty years, other
cities in India have adopted the metro system. Currently Delhi,
Bangalore and Chennai have underground stations in
operation. Design & construction are in progress for
Ahmedabad, Lucknow, Mumbai, Delhi, and Chennai to name a
few.
The city of Kolkata lies in Gangetic West Bengal – about 200 km
north of the Bay of Bengal. Kolkata Metropolitan District (CMD)
with an area of 1250 sq.km and a population of more than 10
million has seen growth along the banks of Hooghly River
which separates it from the neighboring city of Howrah. Kolkata
is the major centre of industrial and commercial activity in
Eastern India and the growth of population in recent years has
put tremendous pressure on the very system it supports &
sustains - the transport system. Between 1901 and 1951, 59%
of the growth in the Kolkata urban area was in the central city
alone but over the past two decades, the central city's growth
has been minimal, adding 87,000 people from 1991 to 2011,
while the suburbs added more than 3 million new residents.
This intensifies the pattern of the last half-century where most
growth clustered close to the city core like a number of major
urban areas around the world.
The Calcutta (Kolkata) soil forms part of the Bengal basin which
was the site of continuous deposition from the Cretaceous
period on a geologic age profile. Later tertiary sediments were
STRUCTURAL ENGINEERING DIGEST / JULY-SEPTEMBER, 2018 | 59
deposited mostly by the Ajay & Damodar river systems on the load bearing piles as shown in Table 1. The terrain of Kolkata is
west and from the Assam plateau on the east. The top 100m of almost flat with a general elevation of about 5-6m above
the sediments are of recent origin consisting of successive MSL.The ground is higher near the river banks on the west but
layers of soft to firm silty clay/clayey silt followed by layers of slopes down to the low lying marshy areas in the east and these
dense sand/hard clay giving high end resistance('N' value) to areas often gets flooded during monsoon rains.
2.0 BRIEF DISCUSSION one by M/s NIKEX Hungarian Co. ,Budapest which dealt with the
There has been a growing interest among policy makers about construction of tunnels by shield tunneling method including
the relevance of rail-based systems, to address the mobility excavation of tunnel under compressed air,erection of cast iron
needs of the ever expanding population in Kolkata and with the or precast concrete lining, grouting of annular space around
meager network of road which covers no more than 10% of the lining by specialist Hungarian Technology & caulking of joints.
land area, the situation is more chaotic. Kolkata (then Calcutta) The Second one concerning specialized technology for
Metro came under consideration in 1949 when French experts manufacture of precast steam cured concrete lining segments
conducted a survey regarding which method of construction of thickness 200mm that is same as cast iron lining so that
was to be followed here. either type of lining could be used without any modification of
shield. So, steam curing technology had to be adopted so that
It was finally decided in 1972 following recommendation by
90% of 28 days strength could be gained within 24hrs &
Soviet Union Consultants that 'Cut & Cover' tunneling method
ultimately progress of tunneling could be effected.Isothermic
aided by slurry wall construction was to be used mainly due to
curing by means of saturated steam was done through a steam
the fact that India's lack, at that time, of ability to handle soft
curing chamber made out of steel plates properly lined inside
ground shield tunneling under compressed air. But, when
with fire bricks.
Calcutta Metro Project reached 'take-off' stage in 1977 Metro
decided to adopt both 'Shield Tunneling' & 'Cut & Cover' The north-south metro from Dum Dum to Tollygunj had been
methods under built-up areas in Kolkata's northern sector built almost entirely by the 'Cut & Cover' method except for a
containing underneath buried sewer lines, water mains, 1.09km stretch in the northern end which was built by Shield
electrical cables, telephone cables, tram lines, overlying traffic, Tunneling with compressed air and air locks, because the
thickly populated old buildings, tidal circular canals,etc. For alignment had to cross a railway yard near Belgachia station.
this, two specialized technologies had to be imported - the first The construction took a long time because the alignment was
3.0 ACKNOWLEDGEMENT
The author wishes to acknowledge the help extended by Consulting Engineers Association of India in organizing the Seminar on
Kolkata East West Metro – Unique Project Challenges on 14th October,2017 at Williamson Magor Hall, Bengal Chamber of Commerce
& Industry,6 N.S.Road,Kolkata-01 which was also supported by Kolkata Metro Rail Corporation Limited (KMRCL).
4.0 CONCLUSION
Though much literature is not available on construction technologies adopted during Kolkata Metro Rail construction this paper tries
to do justice in highlighting the major challenges faced then & now. With the advent of latest mechanized tunneling like TBM, various
sequence of tunnel operations unlike the then methodologies of 1970's/80's has been made possible to be concurrent & continuous
giving rise to a very high increase in the rate of progress and nevertheless imparting safety, stability and yet contributing least to the
environment carbon debits and health hazards.
REFERENCES
1. K.Subrahmanian,VCMD,AFCONS Infrastructure Ltd.,'Recall of N-S Metro(1972 onwards),Tunneling' , Seminar on Kolkata East
West Metro,14th October,2017.
2. Dr.Alvaro Casasus & Harvinder Rana,Associate Director & Design Engineer,AECOM,Gurgaon,India, 'Impact of underground
construction and TBM tunneling on surface Structures in Kolkata East-West Metro',Seminar on Kolkata East West Metro,14th
October,2017.
3. Nitin Som,Geotechnical Consultant,Former Professor of Jadavpur University,Kolkata,'Chalenges of Kolkata Metro Construction
By Cut & Cover Method', Seminar on Kolkata East West Metro,14th October,2017.