Академический Документы
Профессиональный Документы
Культура Документы
206
Pg206 to 230 /12-25-01 1/3/02 3:42 PM Page 207
instance, if a conductor is rated to carry 20 amperes, a 20 Unlike electro-mechanical inertial devices (circuit breakers), it is a
ampere fuse is the largest that should be used. However, there simple matter to selectively coordinate fuses of modern design.
are some specific circumstances in which the ampere rating is By maintaining a minimum ratio of fuse-ampere ratings between
permitted to be greater than the current carrying capacity of the an upstream and downstream fuse, selective coordination is
circuit. A typical example is the motor circuit; dual-element fuses assured.
generally are permitted to be sized up to 175% and non-time- Current Limitation – Component Protection
delay fuses up to 300% of the motor full-load amperes. As a rule,
Areas within waveform
the ampere rating of a fuse and switch combination should be loops represent destructive
energy impressed upon
selected at 125% of the continuous load current (this usually circuit components
corresponds to the circuit capacity, which is also selected at
125% of the load current). There are exceptions, such as when
the fuse-switch combination is approved for continuous opera-
tion at 100% of its rating. Normal
load current
Interrupting Rating
Circuit breaker trips
A protective device must be able to withstand the destructive and opens short-circuit
energy of short-circuit currents. If a fault current exceeds the Initiation of in about 1 cycle
short-circuit
capability of the protective device, the device may actually rup- current
ture, causing additional damage. Thus, it is important when
A non-current-limiting protective device, by permitting a short-
applying a fuse or circuit breaker to use one which can sustain circuit current to build up to its full value, can let an immense amount of
the largest potential short-circuit currents. The rating which destructive short-circuit heat energy through before opening the circuit.
defines the capacity of a protective device to maintain its integ-
rity when reacting to fault currents is termed its “interrupting
rating”. The interrupting rating of most branch-circuit, molded
case, circuit breakers typically used in residential service entrance
panels is 10,000 amperes. (Please note that a molded case
circuit breaker’s interrupting capacity will typically be lower than
its interrupting rating.) Larger, more expensive circuit breakers
may have interrupting ratings of 14,000 amperes or higher. In
contrast, most modern, current-limiting fuses have an interrupt-
Fuse opens and clears
ing rating of 200,000 or 300,000 amperes and are commonly short-circuit in less
used to protect the lower rated circuit breakers. The National than cycle
Electrical Code, Section 110-9, requires equipment intended to A current-limiting fuse has such a high speed of response that it cuts off a
short-circuit long before it can build up to its full peak value.
break current at fault levels to have an interrupting rating sufficient
for the current that must be interrupted. If a protective device cuts off a short-circuit current in less than
Selective Coordination – Prevention of Blackouts one-quarter cycle, before it reaches its total available (and highly
The coordination of protective devices prevents system power destructive) value, the device is a “current-limiting” device. Most
outages or blackouts caused by overcurrent conditions. When modern fuses are current-limiting. They restrict fault currents to
only the protective device nearest a faulted circuit opens and such low values that a high degree of protection is given to circuit
larger upstream fuses remain closed, the protective devices are components against even very high short-circuit currents. They
“selectively” coordinated (they discriminate). The word “selective” permit breakers with lower interrupting ratings to be used. They
is used to denote total coordination…isolation of a faulted circuit can reduce bracing of bus structures. They minimize the need of
by the opening of only the localized protective device. other components to have high short-circuit current “withstand”
ratings. If not limited, short-circuit currents can reach levels of
30,000 or 40,000 amperes or higher in the first half cycle (.008
LPS-RK
LPS-RK 200SP seconds, 60 hz) after the start of a short-circuit. The heat that
KRP-C 600SP
1200SP can be produced in circuit components by the immense energy
2:1 (or more) of short-circuit currents can cause severe insulation damage or
even explosion. At the same time, huge magnetic forces
2:1 (or more)
developed between conductors can crack insulators and distort
This diagram shows the minimum ratios of ampere ratings of LOW-PEAK and destroy bracing structures. Thus, it is important that
YELLOW fuses that are required to provide “selective coordination” a protective device limit fault currents before they reach their
(discrimination) of upstream and downstream fuses.
full potential level.
207
Pg206 to 230 /12-25-01 1/3/02 3:42 PM Page 208
208
Pg206 to 230 /12-25-01 1/3/02 3:42 PM Page 209
209
Pg206 to 230 /12-25-01 1/3/02 3:42 PM Page 210
110
100
.04
90
80 .03
Affect on
70 Opening Time .02
60
50
40
.01
8,000
100
200
300
400
600
800
1,000
2,000
3,000
4,000
6,000
10,000
30
–76°F –40°F –4°F –32°F 68°F 104°F 140°F 176°F 212°F
(–60°C) (–40°C) (–20°C) (0°C) (20°C) (40°C) (60°C) (80°C) (100°C)
210
Pg206 to 230 /12-25-01 1/3/02 3:42 PM Page 211
211
Primary Primary at code max. of
250% or next standard size (Note: Components on the secondary still need overcurrent protection.)
212
Protection
Only if 250% does not correspond
to a standard rating.
Secondary Over 600V Secondary at code max.
Supervised of 250%.
Installations Transformer Impedance Primary at code max.
Less Than or Equal to 6%. of 300% Secondary 600V or Secondary at code max.
Primary
and Below of 250%.
Pg206 to 230 /12-25-01
Secondary
Protection Transformer Impedance Primary at code max. Secondary at code max.
Greater Than 6% But Less of 300% Secondary Over 600V of 225%.
Over
600V Than 10%.
Secondary 600V or Secondary at code max. Fuse
Nominal
1/3/02
2750/5500V JCW
250% or next standard size if 5500V JCE, JCQ, JCY, JCU,
Secondary Over 600V 250% does not correspond to
a standard rating. 5.5 ABWNA, 5.5 AMWNA, 5.5 FFN
Primary at code max. of 300%
or next standard size if 300% 7200V 7.2 ABWNA, 7.2 SDLSJ, 7.2 SFLSJ
3:42 PM
Above 600V overload relay curve. The size fuse which is selected 4800V JCL, JCL-A, JCG
should be such that short-circuit protection is provided 7200V JCR, 7.2 WKMSJ
by the fuse and overload protection is provided by the
FUSE SIZED FOR: controller overload relays.
Motor Backup Overload
1/3/02
Only fuse may be sized up to 225% or next size smaller. 0-600V LPJ_SP
0-250V KTN-R, NON
Protected by Non- Max. of 300%* of motor F.L.A. or next size larger. If this will not allow motor to start due 0-300V JJN
Short-Circuit
Time-Delay Fuses to higher than normal inrush currents or longer than normal acceleration times (5 sec. or 251-600V KTS-R, NOS
Only
greater), fuses through 600 amps may be sized up to 400% or next size smaller. 301-600V JJS
Fuse Diagnostic Chart
0-250V MDL ⁄Ω¡§-8, MDA ¤Ω¡º-20, FNM ⁄Ω¡º-10, FNW 12-30, MDQ ⁄Ω¡ºº-7
Supplementary
Size at 125% or next size larger.
Fuses 0-500 FNQ ⁄Ω¡º-30
213
214
Pg206 to 230 /12-25-01
Fuse
0-250V LPN-RK_SP, FRN-R, NON
Electric Space Heating Size at 125% or next size larger but in no case larger than 60 amperes for each subdivided load.
0-300V JJN
Electric 0-480V SC
1/3/02
GLQ
GMF HLR HLQ
GMQ
GRF
Indoor
All Other BAF KTK-R
HPS-RR HPF-EE
(Mercury, Consult fixture manufacturer for size and type. BAN FNQ-R SC -0-15
HPF-RR HPS-EE
Page 214
Capacitors Fuse
(N.E.C. 460) Protected by 0-250V LPN-RK_SP, FRN-R
150% to 175%
Time-Delay of full load current 251-600V LPS-RK_SP, FRS-R
Fuses 0-600V FNQ-R, LPJ_SP, LP-CC
0-250V KTN-R, NON
Protected by 250% to 300% 0-300V JJN
Non-Time Delay of full load current 251-600V KTS-R, NOS
Fuses 0-600V JKS, KTK-R
301-600V JJS
215
Pg206 to 230 /12-25-01 1/3/02 3:42 PM Page 216
AMPERE
RATING B
300 400,000 6,000
5,000
AMPERE
RATING
10 10,000
TIME IN SECONDS
1,000
1,000
10,000
100,000
200,000
1
.1
.01
100,000
200,000
1,000
10,000
CURRENT IN AMPERES
216
Pg206 to 230 /12-25-01 1/3/02 3:42 PM Page 217
60A
100A
200A
400A
600A
AMPERE
15A
15/100
1-1/4
2-1/2
6-1/4
RATING
8/10 6/10
300
4/10 1/2
10
4
1-6/10
3-2/10
LPN-RK_SP (250V)
1/10
2/10
3/10
AMPERE
12
RATING
5
8
300
100
LPN-RK_SP (250V)
10 10
TIME IN SECONDS
TIME IN SECONDS
1
.1
.1
.01
.1
10
100
1,000
CURRENT IN AMPERES
.01
20
100
1,000
10,000
LPN-RK_SP (250V)
AMPERE
RATING
100,000
600
400
200
100
60
10,000
30
1,000
1,000
10,000
100,000
200,000
217
Pg206 to 230 /12-25-01 1/3/02 3:42 PM Page 218
200A
400A
600A
6.25
1.25
AMPERE
20A
30A
60A
2.5
.15
.5
RATING
300
1.6
3.2
10
12
AMPERE RATING
.1
.2
.3
.4
.6
.8
1
4
5
8
LPS-RK 300
(600V)
100
100
10
TIME IN SECONDS
10
1
TIME IN SECONDS
1
.1
.01
.1
100
1
1,000
10
.1
RMS SYMMETRICAL CURRENT IN AMPERES
LPS-RK
(600V)
AMPERE
RATING
.01
30
100
1,000
10,000
20,000
100,000
600
CURRENT IN AMPERES
400
200
100
60
10,000
30
1,000
100,000
200,000
1,000
10,000
218
Pg206 to 230 /12-25-01 1/3/02 3:42 PM Page 219
15/100
1-1/4
2-1/2
6-1/4
8/10 6/10
100A
200A
400A
600A
4/10 1/2
15A
30A
60A
10
AMPERE
4
1-6/10
3-2/10
RATING
300
1/10
2/10
3/10
AMPERE
12
RATING
5
8
FRN-R 300
(250V)
FRN-R (250V)
100
100
10
10
TIME IN SECONDS
TIME IN SECONDS
.1
.1
.01
1,000
10
.1
100
1
CURRENT IN AMPERES
10,000
20,000
100
1,000
B
400,000
CURRENT IN AMPERES
INSTANTANEOUS PEAK LET-THRU CURRENT AMPERES
AMPERE
RATING
FRN-R (250V)
100,000
600
400
200
100
60
10,000 30
1,000
1,000
10,000
100,000
200,000
219
Pg206 to 230 /12-25-01 1/3/02 3:42 PM Page 220
3-2/10
1-1/4
6-1/4
2/10
6/10
100A
200A
400A
600A
4/10 1/2
15A
30A
60A
AMPERE
10
15/100
2
1-6/10
RATING
2-1/2
300
1/10
3/10
8/10
AMPERE
12
RATING
4
5
8
FRS-R 300
600V
FRS-R
100
(600V)
100
10
10
TIME IN SECONDS
TIME IN SECONDS
.1
.1
.01
.1
10
100
1,000
CURRENT IN AMPERES
100
1,000
10,000
30,000
B
400,000
AMPERE
RATING
INSTANTANEOUS PEAK LET THRU CURRENT AMPERES
100,000
600
400
200
100
60
30
10,000
1,000
1,000
10,000
100,000
200,000
220
Pg206 to 230 /12-25-01 1/3/02 3:42 PM Page 221
100A
200A
400A
600A
AMPERE
30A
60A
400,000 B
RATING
300
KTN-R
AMPERE
RATING
(250V)
100 100,000
600
400
200
100
10,000
10 60
30
A
TIME IN SECONDS
1,000
1,000
10,000
100,000
200,000
1
.1
.01
40
100
1,000
10,000
221
Pg206 to 230 /12-25-01 1/3/02 3:42 PM Page 222
200A
400A
600A
AMPERE B
30A
60A
400,000
AMPERE
RATING
KTS-R
(600V) 100,000
100
600
400
200
100
10,000
60
10 30
A
TIME IN SECONDS
1,000
1,000
10,000
100,000
200,000
1
RMS SYMMETRICAL CURRENTS IN AMPERES
A–B=ASYMMETRICAL AVAILABLE PEAK (2.3 X SYMM RMS AMPS)
.1
.01
40
100
1,000
10,000
222
Pg206 to 230 /12-25-01 1/3/02 3:42 PM Page 223
225A
100A
125A
200A
400A
600A
AMPERE 100,000 B
10A
15A
20A
30A
40A
50A
60A
3A
5A
RATING
300
LPJ 600A
LPJ 400A
100 200A
100A
60A
10,000 50A
40A
30A
20A
10 15A
AMPERE
RATING
TIME IN SECONDS
1,000
1
A
100
100
1,000
10,000
100,000
200,000
.1
PROSPECTIVE SHORT-CIRCUIT CURRENT
SYMMETRICAL RMS AMPS
.01
100
1
1,000
10
10,000
223
Pg206 to 230 /12-25-01 1/3/02 3:42 PM Page 224
200A
400A
600A
100A
200A
400A
500A
800A
AMPERE AMPERE
15A
30A
60A
10A
15A
30A
60A
1A
3A
5A
RATING RATING
300 300
JJS
JJN
(300V) 100 (600V)
100
10
TIME IN SECONDS
10
1
TIME IN SECONDS
.1
1
.01
1
10
100
1,000
10,000
CURRENT IN AMPERES
.1
.01
20
100
1,000
10,000
RATING
JJN JJS
AMPERE
RATING
(300V) (600V)
100,000 100,000
1200
1200 800
800 600
600
400 400
200 200
100 10,000 100
10,000
60 60
30 30
15
1,000 1,000
A A
200 200
100
1,000
10,000
100,000
200,000
100
1,000
10,000
100,000
200,000
224
Pg206 to 230 /12-25-01 1/3/02 3:42 PM Page 225
7-1/2
AMPERE
AMPERE
3⁄Ω™
4⁄Ω™
1⁄Ω¢
flꭧ
°Ω¡º
1/2
10
12
15
20
25
30
RATING
⁄Ω™
3
4
6
8
RATING
5
3
200 100
LP-CC FNQ-R
100
10
10
TIME IN SECONDS
TIME IN SECONDS
1
1
.1
.1
.01
.01
.4
10
100
200
100
1
1000
10
.4
225
Pg206 to 230 /12-25-01 1/3/02 3:42 PM Page 226
10A
15A
20A
30A
AMPERE
1A
2A
3A
5A
8A
RATING
300
KTK-R
100
10
TIME IN SECONDS
.1
.01
1
10
100
400
226
Pg206 to 230 /12-25-01 1/3/02 3:42 PM Page 227
227
Pg206 to 230 /12-25-01 1/3/02 3:42 PM Page 228
228