THIS DRAWING, WHICH CONTAINS PROPRIETARY INFORMATION, IS

84B540865AB THE PROPERTY OF GENERAL ELECTRIC COMPANY. IT SHALL NOT BE

CONT ON SHT 3 SHT 2 Device Locations SECT A1 GenSet / Engine / Auxiliaries REPRODUCED IN ANY MANNER NOR DISCLOSED TO THIRD PARTIES
WITHOUT WRITTEN PERMISSION OF GENERAL ELECTRIC COMPANY.

GenSet Device Locations


B

Loose Shipped Items

JB1
C

N
D ACCESSORY
D ALT ENGINE
E
E RACK

JB2
Number of Fans (10-16) Dependent
D
Upon Engine Model and Power

*Note: Optional GE provided items. 12V228 10 Radfans


Refer to GE scope of supply as defined in the 16V228 10 Radfans
purchase agreement 12V250 12 Radfans
16V250 16 Ranfans
E

ITEM DESCRIPTION

BATT CHRG BATTERY CHARGER 24VDC

DC BATT DC BATTERIES

NGR NEUTRAL GROUNDING RESISTANCE

AIR TANKS AIR RECEIVER TANKS (FOR COMPRESSED AIR STARTING SYSTEM)
Radiator*
AIR COMP AIR COMPRESSOR (FOR COMPRESSED AIR STARTING SYSTEM) ACCESSORY
ENGINE RACK
Radiator F
S/G MEDIUM VOLTAGE SWITCHGEAR ALTERNATOR Junct
Box
MCC/LV MOTOR CONTROL CENTER (WITH INTEGRATED LV PANEL)

ECP ENGINE CONTROL PANEL

GCP GENSET CONTROL PANEL

0 1 2 3 4 5 6 7 8 9
SECT A1
0
REVISIONS TITLE SCHEMATIC DIAGRAM MADE BY E. Sader 01.25.2013 APPROVAL STATIONARY ERIE 84B540865AB
PLANT
FIRST MADE FOR STANDARD UNENCLOSED GENSET ISSUE
E. Sader
GENERAL ELECTRIC CO. CONT ON SHT 3 SHT 2
RC
THIS DRAWING, WHICH CONTAINS PROPRIETARY INFORMATION, IS
84B540865AB THE PROPERTY OF GENERAL ELECTRIC COMPANY. IT SHALL NOT BE

CONT ON SHT 4 SHT 3 Device Locations SECT A2 ECP REPRODUCED IN ANY MANNER NOR DISCLOSED TO THIRD PARTIES
WITHOUT WRITTEN PERMISSION OF GENERAL ELECTRIC COMPANY.

Engine Control Panel (ECP)


Left Side Rear Component Mounting Right Side
Enclosure Enclosure Enclosure Door
ECP PLC

ERR
SR
LMR1
M0 M1 M2 M3* M4* M5 M6 M7 M8* M9 M10* LMR2 CFD
EFR
(SDIS)
ELRR

F1E
T EMS F2E T
F3E
B POWER F4E B ESPB
SUPPLY**
E F5E E
1 1 D

72

D1E
D2E
CB1
CB2
CB3
CB4
E
R1E
R2E
R3E
ECU
G
N
D
F

ECPH***
B
L
K

18 36

DIN Rail NOTES:


* Slot M8 for V250 Engines Only; Slots M3, M4 and M10 optional
Panduit Channel depending upon generator set configuration.
** EMS Power Supply heat-sink mounting per 84A230763EA. H

*** Engine Control Panel heaters optional.


7
0 1 2 3 4 5 6 8 9
SECT A2
0 B
REVISIONS TITLE SCHEMATIC DIAGRAM MADE BY E. SADER 01.25.2013 APPROVAL STATIONARY ERIE 84B540865AB
E. SADER PLANT
A FIRST MADE FOR STANDARD UNENCLOSED GENSET ISSUE GENERAL ELECTRIC CO. CONT ON SHT 4 SHT 3
RC
THIS DRAWING, WHICH CONTAINS PROPRIETARY INFORMATION, IS
84B540865AB THE PROPERTY OF GENERAL ELECTRIC COMPANY. IT SHALL NOT BE

CONT ON SHT 5 SHT 4 Device Locations SECT A3 GCP REPRODUCED IN ANY MANNER NOR DISCLOSED TO THIRD PARTIES
WITHOUT WRITTEN PERMISSION OF GENERAL ELECTRIC COMPANY.

Generator Control Panel


Left Side (GCP) Rear Component Right Side
Enclosure Mounting Enclosure
Enclosure Door
GCP PLC

M0 M1 M2 M3 M4

P&SC HMI
ES

TBG1 TBG1
SSC
***

RFR13**
RFR14**
RFR15**
RFR16**
D

NGRR

RFR11*
RFR12*
RFR10
SDR
PRR
WDR
BLR

RFR1

RFR7
RFR8
RFR9
CBR

RFR2
RFR3
RFR4
RFR5
RFR6
72
OPEN CLOSED PROCESSOR
NOT RUNNING

CS SS ESTOP

DPC
VFR1
EPHR

EFPR

CR
VFR2

VFR4
VFR3
EPLR

TR
VRSR
AVRR
R1G
E

A
D1 D2 D3 D4 D5 D6 CB1/CB2 F1 F2 F3 F4 F5 F6 F7 F8 F9 F10
V
STB1 R

STB2
FDT*** GCPH*** F

GND TB
STB3 PDB+ PDB-

STB4

18 36
G

DIN Rail
* Relays used for 12V250 & 16V250 Engines Only. Otherwise, provided as Spare.
** Relays used for 16V250 Engines Only. Otherwise, provided as Spare.
Panduit Channel *** Control Panel Heater, Fire Detect Transformer and Synchroscope are optional.

0 1 2 3 4 5 6 7 8 9
SECT A3
0 B
REVISIONS TITLE SCHEMATIC DIAGRAM MADE BY E. SADER 01.25.2013 APPROVAL STATIONARY ERIE 84B540865AB
PLANT
A C CO-172854 April 2016
FIRST MADE FOR STANDARD UNENCLOSED GENSET ISSUE
E. SADER
GENERAL ELECTRIC CO. CONT ON SHT 5 SHT 4
RC
THIS DRAWING, WHICH CONTAINS PROPRIETARY INFORMATION, IS
84B540865AB THE PROPERTY OF GENERAL ELECTRIC COMPANY. IT SHALL NOT BE

CONT ON SHT 6 SHT 5 Conventions/Legend SECT A4 Conventions/Legend REPRODUCED IN ANY MANNER NOR DISCLOSED TO THIRD PARTIES
WITHOUT WRITTEN PERMISSION OF GENERAL ELECTRIC COMPANY.

Convention
A
RadFan1
Relay/Contactor Coil with free-wheel diode
400V 50 Hz
M 7.2 FLA Three phase motor
3 HP, 2.2 kW

1. Diesel Engine is not running


Relay/Contactor normally open contact
2. Level switches are shown below their respective switch thresholds
AC AC Lighting

3. All relays are shown de-energized Relay/Contactor normally closed contact


B

4. Synchroscope switch (SS) is shown in the OFF position


Pushbutton normally closed contacts
DC
DC Lighting
5. Close Breaker switch (CS) is shown in the AUTO position

6. E-stop push button shown is shown in the non actuated position Pushbutton normally open contacts

C
Indication Lamp

Circuit breaker

Connector
Device Identification

-
Fuel Injection solenoid
+ D

TR Shield Wiring
A2 A1

Electrical outlet (Ground fault interrupting)

Surge Arrestor
Terminal Identification

Thermocouple (Type K) E
TR
11 12
MV-1210
Off Sheet/Section Reference
Level Switch (Normally open contacts)

Harnessl Identification Terminal Identification 24 VDC


Power feed (see Power distribution for details)

CMR-25
Thermistor (PT100)
F

Power return (see Power distribution for details)


Connector Socket Connector Plug/Pin Com Rtn

Transformer
BusBar/Power conductor

Control/Signal/Control Power conductor


Terminal Board G

Internal Genset Interface conductor

Customer Interface conductor (Customer Provided)


Device Terminal (for Power Distribution details)

Chassis Ground

Device not provided with GenSet


Neutral Ground

0 1 2 3 4 5 6 7 8 9
SECT A4
0
REVISIONS TITLE SCHEMATIC DIAGRAM MADE BY E. SADER 01.25.2013 APPROVAL STATIONARY ERIE 84B540865AB
PLANT
FIRST MADE FOR STANDARD UNENCLOSED GENSET ISSUE
E. SADER
GENERAL ELECTRIC CO. CONT ON SHT 6 SHT 5
RC
THIS DRAWING, WHICH CONTAINS PROPRIETARY INFORMATION, IS
84B540865AB THE PROPERTY OF GENERAL ELECTRIC COMPANY. IT SHALL NOT BE

CONT ON SHT 7 SHT 6 Block Diagram SECT A5 Block Diagram REPRODUCED IN ANY MANNER NOR DISCLOSED TO THIRD PARTIES
WITHOUT WRITTEN PERMISSION OF GENERAL ELECTRIC COMPANY.

GenSet

ECP GCP Switchgear Generator B

HMI

ES Off Board Data


(Eth COMM)
Power Power
Alt Cyl Fuel Lvl Pre-Heat Start Louver MCC MCC Management Management Remote C

Floats Perm Req Cntrl Control Status Control Status Start

Gen Breaker
Status
ECP PLC GCP PLC

Inc/Dec
D
Ethernet Spd
Idle/Rated
Comm Inc/Dec
Voltage
P&SC
Init Sync

CFD (SDIS)
Close

E
Trip
DG Breaker
Voltage
RS485 Bias
ArcNet

DPC
Solenoid
Firing Speed Bias Neut CT
ECU
Engine F
Sensors

AVR

Alt Field G

0 1 2 3 4 5 6 7 8 9
SECT A5
0
REVISIONS TITLE SCHEMATIC DIAGRAM MADE BY E. SADER 01.25.2013 APPROVAL STATIONARY ERIE 84B540865AB
PLANT
A
FIRST MADE FOR STANDARD UNENCLOSED GENSET ISSUE
E. SADER
GENERAL ELECTRIC CO. CONT ON SHT 7 SHT 6
RC
THIS DRAWING, WHICH CONTAINS PROPRIETARY INFORMATION, IS
84B540865AB THE PROPERTY OF GENERAL ELECTRIC COMPANY. IT SHALL NOT BE

CONT ON SHT 8 SHT 7 One Line Diagram SECT A6 Aux Voltage Distribution REPRODUCED IN ANY MANNER NOR DISCLOSED TO THIRD PARTIES
WITHOUT WRITTEN PERMISSION OF GENERAL ELECTRIC COMPANY.

MCC/LV PANEL BACKUP


400Vac, 50Hz 400Vac, 50Hz TRIP MV Circuit
(or 480Vac, 60Hz) (or 480Vac, 60Hz) 52-DG1
A

Auxiliary GCP SWITCHGEAR


Transformer (Optional)
(Optional) FEEDER1 FEEDER2
(backup) P&SC
Voltmeter Voltmeter
Indication Indication
On Off Trip A B C A B C On Off Trip
Select Select
Lamp Test Switch
Lamp Test
Switch

MCB28 MCB29 B
4-Pole 200A (mechanical interlock) 4-Pole 200A
P&SC
52-DG1
CLOSE
52-DG1
Motor Control Center*** (MCC) TRIP
52-DG1

DPC

MCB17 MCB18 MCB19 MCB20 MCB21 MCB22 MCB23 MCB24 MCB25 MCB26
10A 10A 25A 25A 25A 25A 25A 50A 100A 100A C

MC17 MC18 MC19 MC20 MC21 MC22 MC23 MC24

OL17 OL18 OL19 OL20 OL21 OL22 OL23 OL24


12-38A 12-38A 12-38A 12-38A 12-38A 12-38A 12-38A 12-38A
TRIP
52-DG1 ECP
D

AC Prime Spare VentFan1** VentFan2** VentFan3** Prelube Spare Air Fluid AVR ECP PLC
Pump** (Optional) (Optional) (Optional) Pump** Compressor Preheater DG
(Optional) (Optional) TRIP
10 HP 52-DG1
1.0 HP 6.9 HP 6.9 HP 6.9 HP 8.2 HP 15 FLA 60.0 FLA
1.0 FLA 10.3 FLA 10.3 FLA 10.3 FLA 9.0 FLA

MCB27
100A MAIN
MCB1 MCB2 MCB3 MCB4 MCB5 MCB6 MCB7 MCB8 MCB9 MCB10 MCB11 MCB12 MCB13 MCB14 MCB15 CB16
16A 16A NGR
16A 16A 16A 16A 16A 16A 16A 16A 16A 16A 16A 16A 16A 16A
(Optional)

Jumper for 50Hz application


MC1 MC2 MC3 MC4 MC5 MC6 MC7 MC8 MC9 MC10 MC11 MC12 MC13 MC14 MC15 MC16
(50Hz) (60Hz)
F
480V
ORL1 ORL2 ORL3 ORL4 ORL5 ORL6 ORL6 ORL7 ORL8 ORL10 ORL11 ORL12 ORL13 ORL14 ORL15 ORL16
0.1-13A 0.1-13A 0.1-13A 0.1-13A 0.1-13A 0.1-13A 0.1-13A 0.1-13A 0.1-13A 0.1-13A 0.1-13A 0.1-13A 0.1-13A Aux. LV
0.1-13A 0.1-13A 0.1-13A
30Kva, 60Hz
208V

RadFan1 RadFan2 RadFan3 RadFan4 RadFan5 RadFan6 RadFan7 RadFan8 RadFan9 RadFan10 RadFan11* RadFan12* RadFan13* RadFan14* RadFan15* RadFan16*
250A MAIN

3 HP 3 HP 3 HP 3 HP 3 HP 3 HP 3 HP 3 HP 3 HP 3 HP 3 HP 3 HP 3 HP 3 HP 3 HP
3 HP
7.2 FLA 7.2 FLA 7.2 FLA 7.2 FLA 7.2 FLA 7.2 FLA 7.2 FLA 7.2 FLA 7.2 FLA 7.2 FLA 7.2 FLA 7.2 FLA 7.2 FLA 7.2 FLA 7.2 FLA
7.2 FLA
G
LV Panel *** (Integrated to MCC)
NOTES:
A B C A B C A B C A B C A B C A B C A B
* MCC Radiator Fan Application Chart

Radfan# 12V228 16V228 12V250 16V250 CB1 CB2 CB3 CB4 CB5 CB6 CB7 CB8 CB9 CB10 CB11 CB12 CB13 CB14 CB15 CB16 CB17 CB18 CB19 CB20
Radfan11 X X 230V/50Hz 10A 10A 10A 10A 10A 10A 6A 6A 6A 6A 6A 10A 10A 10A 6A 6A 10A 6A 10A 10A
Radfan12 X X (20A) (20A) (20A) (20A) (20A)
(120V/60Hz) (20A) (10A) (10A) (10A) (10A) (10A) (20A) (20A) (20A) (10A) (10A) (20A) (10A) (20A) (20A)
Radfan13 X
Radfan14 X
Radfan15 X
Eng/Alt Aux Elect Elect Eng/Alt Eng/Alt Fire Detect ECP Spare
Radfan16 X NGR H
Module Module Module Module Module Module Panel** Heater
Ext. Lighting** Contactor
Outlets** Eng/Alt Outlets** Elect Air Cond** Lighting** Aux Lighting**
** If Optional items are not equipped, use as SPARE Battery Elect Alternator
Module Module Module Switchgear GCP Fuel MCC
Charger Module
Outlets** Outlets** LIghting** Heater Heater Heater Filter Heater
*** Above is the MCC diagram if provided by GE. Otherwise, use as TYPICAL subject to Customer provided MCC diagram Ext. LIghting**
(V250 only)
0 1 2 3 4 5 6 7 8 9
SECT A6
0 C CO-172854 April 2016
REVISIONS TITLE SCHEMATIC MADE BY E. SADER 01.25.2013 APPROVAL STATIONARY ERIE 84B540865AB
PLANT
A FIRST MADE FOR STANDARD UNENCLOSED GENSET ISSUE
E. SADER
GENERAL ELECTRIC CO. CONT ON SHT 8 SHT 7
RC
THIS DRAWING, WHICH CONTAINS PROPRIETARY INFORMATION, IS
84B540865AB THE PROPERTY OF GENERAL ELECTRIC COMPANY. IT SHALL NOT BE

CONT ON SHT 9 SHT 8 High Voltage System SECT B 50 Hz Voltage Distribution REPRODUCED IN ANY MANNER NOR DISCLOSED TO THIRD PARTIES
WITHOUT WRITTEN PERMISSION OF GENERAL ELECTRIC COMPANY.

GCTA2
High voltage distribution wiring (for 50Hz applications only)
GCTB2
GCTC2
A
GCTN1
P&S Controller
Differential Protection Gen CT Inputs
Controller BCTN1 STB2-4 BCTN Switchgear Assembly SG (Optional) GCTA2
A
73 74
B14 C BCTC1 STB2-3 B GCTN2
B13 BCTC GCTB2
75 76
B12 B BCTB1 STB2-2 BCTB C GCTN3
B11 GCTC2
BCTA1 77 78
A STB2-1 BCTA
B10 B9 GCTN1
S1 S1 S1
Bus CT Inputs Note: Ensure CT S2's and P2's are grounded (not S1's and P1's) Note: S2 S2 S2

Note: See BCTA BCTB BCTC


Ensure unused CT Table P2 P2 P2

Ensure used CT Alternator Assembly (ALT) 1 secondaries are shorted P1 P1 P1


B

secondaries are VCB


For Customer GENA A
not shorted GCT's A A
Use (optional)
See Table
GENB B
Customer
Gen CT Inputs GCTN1 S2 X5-7
A STB1-1
X5-1
GCTA-1
P2
GCTA-2
B Load
GCTA1 GCTA S1 X5-10
B2 B1
GCTB1 GCTB
X5-4 GENC
C
C Cables
B4 B3 X5-5 GCTA X5-11
B STB1-2 GCTN2 GCTB-1 P1 GCTB-2 VBIAS1+
X5-2 X5-8 B-F2 66 (+)
C GCTC Voltage
GCTC1 P1
B6 B5 X5-6 VBIAS1- Bias Output
STB1-3 GCTN3 GCTC-1 B-F2 67 (-) C
X5-3 P1
GCTC GCTB BPT VT2
C B A ***
STB1-4 P2 See Table VT2 BPTA TBG1-7
GCTN1 GCTN Junction Box
S1 BPTA1 1 F4G 2 BPTA2 85 PHA
S1 X5-12 A
Frame Ground S2 GCTC-2
S2 BPTB TBG1-8 BPTB1 1 F5G 2 BPTB2 87 PHB
X5-9 B Bus PT
P2
C BPTC TBG1-9 BPTC1 1 F6G 2 BPTC2 89 PHC Inputs
C
B BPTN TBG1-10 BPTN1
GND 88 NEU
VT1 ***
Neut CT 2 GPT VT1 GPTN TBG1-14 GPTN1
STB4-1
N C B A GND 84 NEU
NCT1 NCT See Table
B8 B7 GPTA TBG1-11 GPTA1 1 F1G 2 GPTA2

+
X5-13 A 79 PHA Gen PT
NCTN1 STB4-2 NCTN GCTN GCTN GPTB TBG1-12 GPTB1 1 F2G 2 GPTB2 81 PHB Inputs D
B
-
X5-14
DPC GND 600:5A GPTC TBG1-13 GPTC1 1 F3G 2 GPTC2
GND C 83 PHC
NCTN1 Junction Box
Frame Ground N.O. Auxiliary Contact
3 (closes with breaker)
3 NC TBG1-5
AVR F7G 1
VRSR TBG1-15 1CBRA2 CBRA2
AVRPA2 2 AVR1 14 11 AVRPA1 AVRPA 5
INPUT 4 X2-UH2R A2
POWER TBG1-16
F8G 1 24 11 POWER VCB
AVRPB2 2 AVR2 AVRPB1 AVRPB CBR
5 X2-UH1 STATUS TBG1-6
CR 1CBRA1 CBRA1 A1
TBG1-1 6
TBG1-17 11 14 CR1B CR1B1
PH A E1 AVRSA AVRSA1
X3.1 1U 1 E
AVR SENSING VCB
Voltage TBG1-18 AVRSB2 TBG1-2
PH B E2 AVRSB Ratio Varies CR1A CR1A1 CLOSE 24_SWG
Sensing X3.1 5W 24VDC
2 24 VDC
PH C E3 AVRSB1 TR CONTROL 2G_SWG
11 14 TR1B TBG1-3 TR1B1 CIRCUIT Com Rtn
STB3-1 3
FIELD+ EF+ VCB
F+ X2-J1R TBG1-4
Field Excitation TR1A TR1A1 TRIP
Field 4 LV12-L1
Output STB3-2 230VAC H12 C3-E4
F- FIELD- EF-
X2-K1R HEATER LV12-N1
VBIAS2+ COILS N12 C3-E4
VBIAS1+
A (+) B-C8 LV14-L1 X4-1 230VAC LV12-G1
1 C3-F1 G C3-H3
Voltage Bias LV14-N1 HEATER
R1G C3-F1 X4-3 F

Input LV14-G1 COIL


C3-H3 G N
B (-)
VBIAS2- 2 GN
VBIAS1-
B-C8
52L
Unit/Parallel X1 GN1
52M
AVRJ1
C3-F4
LV17-L1
1 230VAC
NGR
52J
AVRJ2 C3-F4
LV17-N1
3 Contactor Asm CT and PT Ratio Reference Table *** SYNCHROSCOPE
Var/PF 52K LV17-G1 Coil (optional)
C3-H3 G (Optional) 12/16V228 12/16V228 12/16V228 12V250 16V250 12/16V250 12/16V250
X2 DEVICE 50Hz, 11KV 50Hz, 6.6KV 50Hz, 3.3KV 50Hz, 11KV 50Hz, 11KV 50Hz, 6.6KV 50Hz, 3.3KV
CT1 NC NGR11 TBG1-130 NGRC1 SSC
Droop 11 4 TBG1-7
CT2 NC GCTs SSCBA A
NGRR Close 250:5 400:5 800:5 300:5 400:5 1200:5
G

NGR14 TBG1-131 NGRC2 600:5 TBG1-8 Bus


14 5 5P10, 15VA SSCBB
H2 B
NGR
X2 CONTROLLER BCTs
NGR21 TBG1-132 NGRT1 250:5 400:5 800:5 300:5 400:5 600:5 1200:5 TBG1-11
24VDC 21 6 760C Max Temp 5P10, 15VA SSCGA
A
NGRR Trip Rise for 10 Sec Gen
NGR22 TBG1-133 NGRT2 TBG1-12
24_AVRAL 22 NCT 600:5
SSCGB B
7 600:5 600:5 600:5 600:5 600:5 600:5
TBG1-23
5P10, 15VA
AL1
GCP PLC RG
AVRALM1
AVR Alarm 24VDC 11Kv / 3 : 6.6Kv / 3 : 3.3Kv / 3 : 11Kv / 3 : 11Kv / 3 : 6.6Kv / 3 : 3.3Kv / 3 :
TBG1-24 GPT
AL2 AVRALM2 AVR 110V / 3 110V / 3 110V / 3 110V / 3 110V / 3 110V / 3 110V / 3
AVRALM3
M2-B7 Alarm
TBG1-21 XT1 3P, 25VA
24_NGRST NGRSTA
9 Contactor
11Kv / 3 : 6.6Kv / 3 : 3.3Kv / 3 : 11Kv / 3 : 11Kv / 3 : 6.6Kv / 3 : 3.3Kv / 3 : H
AVR GND NGR Status BPT
GND NGRST NGRSTB 110V / 3 110V / 3 110V / 3 110V / 3 110V / 3 110V / 3 110V / 3
Contactor M2-B11 10 (NO) 3P, 25VA
Status TBG1-22

NG
0 1 2 3 4 5 6 7 8 9 SECT B
0 B
REVISIONS TITLE SCHEMATIC DIAGRAM MADE BY E. SADER 01.25.2013 APPROVAL STATIONARY ERIE 84B540865AB
PLANT
A C CO-172854 April 2016
FIRST MADE FOR STANDARD UNENCLOSED GENSET ISSUE
E. SADER
GENERAL ELECTRIC CO. CONT ON SHT 9 SHT 8
RC
Note: Ensure CT S2's and P2's are grounded (not S1's and P1's) Note:
Note: Ensure unused CT
Ensure used CT Alternator Assembly (ALT) secondaries are shorted
secondaries are
not shorted

N.O. Auxiliary Contact


(closes with breaker)
THIS DRAWING, WHICH CONTAINS PROPRIETARY INFORMATION, IS
84B540865AB THE PROPERTY OF GENERAL ELECTRIC COMPANY. IT SHALL NOT BE

CONT ON SHT 11 SHT 10 High Voltage System SECT B2 Breaker, Excitation, & Power Control REPRODUCED IN ANY MANNER NOR DISCLOSED TO THIRD PARTIES
WITHOUT WRITTEN PERMISSION OF GENERAL ELECTRIC COMPANY.

D3G
TR8 + - TR9
Trip Output C6
DPC 24 VDC
24VDC SDR A
24G_216 11 14
TR10

24GCP5 D1G CS TR
C1 SD3 + - SD4 3B A2 A1
24G_217 4B TR11 TTR TRA2
24GCP6 Alarm C2
C3 TBG1-104 TBG1-105
GCESPB 2G_210
24GCP7 C5 GCP PLC Shutdown M2-A2 SD1 +
D2G
- SD2
24G_218 3A 4A TR12
24GCP8 C7 Output Com Rtn
24GCP9 C9 D4G
OCNT Genset Breaker TRA1 + TR4
50/51 PH_TR Phase Over -
C4 M2-B14 Trip Command M2-A3
Output 1 Current Status
Output 24 VDC TR23 B
24 VDC
DOCNT Phase Differential 11 BLR 14 M2 EFR
87 TR C8 M2-B13 Current Fault Status 49 Fixed PF P&SC 24E_301 21 22 TR20
Output 3 M3
BLR 51 Fixed P
GF 24G-24
11 12 MM1 ECESPB
50/51 G_TR M2-B15 Ground Fault 48 TBE1-162
C10 P Load Share 24E_302 3A 4A TR21
Output 4 Status MM2 52 Q Load Share
CBR 24E_303 24E_303C TR22
41 42 GPESPB
Gen Breaker 2GCP5 24G-219 CBR4A 24E_303B
3A
CBR2B 26 Breaker Open Status 4A TR22C TR22B
C18 Input C17
CBR4B TBE1-160 TJ2-17** TJ-22* TJ-23* TJ2-18** TBE1-161
23 Alarm Inhibit (No GPESPB if no Gauge Panel)
24G_222 24 VDC
Com Rtn
43 Remote Mode C
24G_220 24G_27 21
24 VDC 54 Blackout Sync
24G_223 15 GB Trip COM WDR
SD7 22 SDR
WDR Generator Failure
24G-28 SD5 A2 A1
24G-22 11 14 WDG1B 12 11
WatchDog
M2-B1
Status 2G_28 24VDC 24VDC
Controller Status WDR
24G-26
4 WDRA2 A2 A1
3 2G_27
24_IPC
Com Rtn 24_IPP
CBR (Closed if Healthy)
41 44 11 11 21
CBR4C 27 Breaker Close Status D
CR
24G-215 D6G CBR CBR PRR
24 VDC SYNC3 + - SYNC2 CRA2 A2 A1
18 17 22
2G_211 14 12
1A Sync
SS
CBR IPC_A IPB_A IPP_A
21 24 CBR2B 2A
SYNC6A SYNC5
24G_23 3C
CBR CS BREAKER BREAKER PROCESSOR
21 22 CS CLOSE OPEN NOT RUNNING
4C
M2-B2 Genset Breaker
CBRS 1A 2A SYNC4
SYNC1 SYNC7
Status Input Sync Command M2-A4 25 Activate Sync Input
Output
CS IPC_C IPB_C IPP_C E

4A UNLD Genset Breaker D5G


24G_213 3A CS Close/Trip Unload Outp M2-A6 TR1
M2-B4 Breaker Input 53 Unload + - TR3
Trip Relay 14
AACK Output Com Rtn Com Rtn Com Rtn
SS Alarm Ack Outp M2-A5 24 Alarm Acknowledge
3A 4A SS INCV
24G_214 M2-B6 Sync Scope
Input Inc Volts Outp M2-A9 46 Inc Volts
DECV
Dec Volts Outp M2-A10 47 Dec Volts
Customer Inputs (optional)*** INCF
TBG1-112
Inc Freq Outp M2-A7 44 Inc Freq SYNCHRONOUS SWITCH (SS) CLOSE BREAKER SWITCH (CS)
SM4B11
M4-B11 Ext Fixed Power Enable DECF
(%I01043) Dec Freq Outp M2-A8 45 Dec Freq POSITION 1A - 2A 3A - 4A POSITION 1A - 2A 3A - 4A 3B - 4B 3C - 4C F
TBG1-113
SM4B12 Ext Load Share Enable BRST
M4-B12 50 Bias Reset OFF AUTO X
(%I01044) Bias Reset Outp M2-A11
Customer Relays (optional)
TBG1-114 ON
SM4B13 Ext NGR Control Plant Fixed Power Relay X X CLOSE X X
M4-B13 P adjust
(%I01045) TRIP/
TBG1-25 Common X X
Note: X = Closed Contact LOCKOUT
RST_IN Plant Load Share Relay TBG1-301
Remote Control M2-B5 Remote Start NGRR F adjust 40 Freq/P Set Point
Signals (%I01005) A2 A1 ESV (+/- 10V Analog)
TBG1-26 NGR M2-A1 TBG1-302 Customer
(SCADA) RTR_IN 2G_22
Remote Trip Contactor Close NGRR1 Common 41 Common External
M2-B9 ESC
(%I01009) Set Point
TBG1-303
TBG1-27
RSH_IN Remote VRSR V adjust 42 Volt/Q Set Point Inputs G
M2-B16 Cooldown/Shutdown A2 A1 ESF
AVR M2-A13 (+/- 10V Analog) (optional)***
2G_23 TBG1-304
VRSR1
TBG1-28 RSYNC_IN
(%I01016) Enable Output External Set Point Enable 55 External Set Point TBG1-100
ESE Enable*** SBIAS+ SBIAS1+
M2-B10 Remote Sync (+24VDC Digital) (+) 70 D-A2
PRR
TBG1-106 FR1
(%I01010) A2 A1
Freq/Speed
SBIAS- TBG1-101 GCP to ECP
Procc M2-A14 Bias Output SBIAS1-
M2-B8 Fire Detection PRRA2 2G_24 (-) 71 D-A2
Active Output
(%I01008)
TBG1-97
2G_218
BLR 28 Real 37 LS1
Base Load A2 A1
Output
M2-A15
BLRA2 2G_25 2G_217
Load Share LSCMN TBG1-98 GenSet to GenSet
Lines Common 38
NOTES:
* TJ termination is in GAUGE PANEL on the Generator Set Skid.
56
TBG1-99
Load Share Lines H
LS2
** TJ2 termination is in DC JUNCTION BOX 2 on Generator Set Skid. Reactive 39
*** Dry contacts required with common sides tied to GenSet +24VDC
and relay contacts tied to the Customer Input TB's as shown. Com Rtn
Com Rtn
0 1 2 3 4 5 6 7 8 9 SECT B2
0 CO-149467 January 2013 B CO-164146 January 2015
REVISIONS TITLE SCHEMATIC DIAGRAM MADE BY E. SADER 01.25.2013 APPROVAL STATIONARY ERIE 84B540865AB
PLANT
A CO-153582 July 2013 C CO-172854 April 2016
FIRST MADE FOR STANDARD UNENCLOSED GENSET ISSUE
E. SADER
GENERAL ELECTRIC CO. CONT ON SHT 11 SHT 10
RC
THIS DRAWING, WHICH CONTAINS PROPRIETARY INFORMATION, IS
84B540865AB THE PROPERTY OF GENERAL ELECTRIC COMPANY. IT SHALL NOT BE

CONT ON SHT 12 SHT 11 High Voltage System SECT B3 Alternator Thermal Monitoring REPRODUCED IN ANY MANNER NOR DISCLOSED TO THIRD PARTIES
WITHOUT WRITTEN PERMISSION OF GENERAL ELECTRIC COMPANY.

Alternator Assembly B

ALT ECP PLC

X4-4 APAT1+ TBE1-150 APATX


M3-19
Alternator Stator
APAT APAT+
M3-20 Phase A Temp
X4-6 APAT1- TBE1-151 APAT-
M3-22

X4-7 APBT1+ TBE1-152 APBTX


M3-3
Alternator Stator
APBT APBT+ M3-4 Phase B Temp
X4-9 APBT1- TBE1-153 APBT-
M3-6

X4-10 TBE1-154 APCTX


APCT1+
M3-23
Alternator Stator D
APCT APCT+
M3-24 Phase C Temp
X4-12 APCT1- TBE1-155 APCT-
M3-26

X4-22 ANDEBT1+ TBE1-156ANDEBTX


M3-7
Alternator Non Drive
ANDEBT ANDEBT+ End Bearing Temp
M3-8 E
X4-24 ANDEBT1- TBE1-157
ANDEBT-
M3-10

X4-25 ADEBT1+ TBE1-158 ADEBTX


M3-27
Alternator Drive End
ADEBT+ Bearing Temp
ADEBT M3-28
X4-27 ADEBT1- TBE1-159 ADEBT-
M3-30

0 1 2 3 4 5 6 7 8 9 SECT B3
0
REVISIONS TITLE SCHEMATIC DIAGRAM MADE BY E. SADER 01.25.2013 APPROVAL
STATIONARY
ERIE 84B540865AB
PLANT
FIRST MADE FOR STANDARD UNENCLOSED GENSET ISSUE
E. SADER
GENERAL ELECTRIC CO. CONT ON SHT 12 SHT 11
RC
THIS DRAWING, WHICH CONTAINS PROPRIETARY INFORMATION, IS
84B540865AB THE PROPERTY OF GENERAL ELECTRIC COMPANY. IT SHALL NOT BE

CONT ON SHT 13 SHT 12 Auxiliary System SECT C Voltage Distribution REPRODUCED IN ANY MANNER NOR DISCLOSED TO THIRD PARTIES
WITHOUT WRITTEN PERMISSION OF GENERAL ELECTRIC COMPANY.

GenSet MCC*** RadFan1 Radiator Assembly


MCB OLR A U1
AR2 V1 RF1 RadFan1
Main1 GenSet MCC*** AY2 B
W1 M 3 HP A

AB2 C 7.2 FLA @400V/50Hz


A1 1 RadFan2
MCB OLR A U1
B1 2
BR2
V1 RF2 RadFan2
CUSTOMER VentFan1 V1L1 BY2 B
W1 M 3 HP
BB2 C 7.2 FLA @400V/50Hz
FEEDER1 C1 3 MCB OLR VF1A VentFan1**
400V, 50Hz
SR2 VF1B V1L2 VF1** RadFan3
N1 N1 SY2 6.85 HP
SB2 VF1C V1L3 M MCB OLR U1
(or 480V, 60Hz) 10.3 FLA @400V/50Hz CR2 A RF3 RadFan3
CY2 B V1 3 HP
VentFan2 V2L1 CB2 C
W1 M 7.2 FLA @400V/50Hz
B
VF2A
MCB OLR TR2 VF2B V2L2 VF2** VentFan2** RadFan4
TY2 MCB OLR U1 RadFan4
TB2 VF2C V2L3 M 6.85 HP DR2 A V1 RF4
10.3 FLA @400V/50Hz DY2 3 HP
B
W1 M 7.2 FLA @400V/50Hz
VentFan3 V3L1
DB2 C

MCB OLR VF3A RadFan5


UR2 V3L2 VF3** VentFan3** U1
Main2 UY2
VF3B
VF3C M 6.85 HP
MCB OLR ER2 A
V1 RF5 RadFan5
UB2 V3L3 EY2 B 3 HP
A2 1
10.3 FLA @400V/50Hz EB2 W1 M 7.2 FLA @400V/50Hz
C

CUSTOMER B2 2
RadFan6
MCB OLR U1 C

BACKUP FR2 A
V1 RF6 RadFan6
C2 3 FY2 B 3 HP
FEEDER2 W1 M
Air Compressor FB2 C 7.2 FLA @400V/50Hz
400V, 50Hz N2 N2
MCB OLR
X02-U
ACOA L1
AC Air Compressor RadFan7
(or 480V, 60Hz) ACOB L2 10 HP MCB OLR U1
X02-V ACOC L3 M GR2 A
V1
RF7 RadFan7
X02-W 15.0 FLA @400V/50Hz GY2 B
W1 M 3 HP
GB2 C 7.2 FLA @400V/50Hz
Prelube Pump RadFan8
MCB OLR PLPA L1 MCB U1 RadFan8
PLPR PLP** Prelube Pump** OLR HR2 A
PLPB L2 8.2 HP HY2 V1 RF8 3 HP
PLPY B D

PLPB
PLPC L3 M 9.0 FLA @400V/50Hz HB2 W1 M 7.2 FLA @400V/50Hz
C
Fuel Priming Pump RadFan9
MCB OLR IR2 A U1 RadFan9
MCB OLR FPPR
FPPA L1
Fuel Priming Pump** V1 RF9
FPPB L2 FPP** IY2 B 3 HP
FPPY
FPPC L3 1.0 HP IB2 W1 M 7.2 FLA @400V/50Hz
FPPB M 1.0 FLA @400V/50Hz C
RadFan10
U1
Fluid Pre-Heater MCB OLR JR2 A V1 RF10 RadFan10
JY2 B 3 HP
L1 Fluid Pre-Heat W1 M
MCCB FPHA JB2 7.2 FLA @400V/50Hz
FPHR FPHB System C E
L2 FPH
FPHY
FPHB
FPHC L3 60 FLA @400V/50Hz RadFan11*
MCB OLR KR2 U1
A
V1
RF11 RadFan11*
KY2 B
LV Panel*** KB2 W1 M 3 HP
7.2 FLA @400V/50Hz
C
(Integrated) RadFan12*
MCCB LVPA C3-A5 U1
MCB OLR LR2 RadFan12*
LVPB A V1 RF12
C3-A5 LY2 3 HP
LVPC Internal B
C3-A5
to MCC LB2 W1 M 7.2 FLA @400V/50Hz
C
NEUTRAL LVPN C3-A5
RadFan13* F
GROUND MCB OLR A U1 RadFan13*
MR2
V1 RF13
MY2 B 3 HP
NOTES: W1 M
Spare 18 MB2 C 7.2 FLA @400V/50Hz
* MCC Radiator Fan Application Chart
MCCB OLR
RR2 NC Radfan# 12V228 16V228 12V250 16V250
RadFan14*
RY2 MCB OLR NR2 A U1
RB2
NC Radfan11 X X V1 RF14 RadFan14*
NC Radfan12 X X NY2 B 3 HP
NB2 W1 M 7.2 FLA @400V/50Hz
Radfan13 X C
Radfan14 X
Spare 23 Radfan15 X
RadFan15*
MCB OLR A U1
MCCB OLR
Radfan16 X OR2
V1
RF15 RadFan15*
WR2 NC OY2 B 3 HP G

WY2 NC ** If Optional items are not equipped, use as SPARE OB2 W1 M


C 7.2 FLA @400V/50Hz
WB2 NC
*** Above is the MCC diagram if provided by GE. Otherwise, RadFan16*
use as TYPICAL subject to Customer provided MCC diagram MCB OLR U1 RadFan16*
PR2 A RF16
V1 3 HP
PY2 B
PB2
W1 M 7.2 FLA @400V/50Hz
C

NEUTRAL NEUTRAL
GROUND GROUND
NEUTRAL
GROUND
H

0 1 2 3 4 5 6 7 8 9
SECT C
0 CO-149467 January 2013
REVISIONS TITLE SCHEMATIC DIAGRAM MADE BY E. SADER 01.25.2013 APPROVAL STATIONARY ERIE 84B540865AB
PLANT
A CO-153582 July 2013 FIRST MADE FOR STANDARD UNENCLOSED GENSET ISSUE
E. SADER
GENERAL ELECTRIC CO. CONT ON SHT 13 SHT 12
RC
THIS DRAWING, WHICH CONTAINS PROPRIETARY INFORMATION, IS
84B540865AB THE PROPERTY OF GENERAL ELECTRIC COMPANY. IT SHALL NOT BE

CONT ON SHT 14 SHT 13 Auxiliary System SECT C1 Control REPRODUCED IN ANY MANNER NOR DISCLOSED TO THIRD PARTIES
WITHOUT WRITTEN PERMISSION OF GENERAL ELECTRIC COMPANY.

GenSet MCC GCP PLC


TBG1-30 (TBX10.1) (TBX10.1) TBG1-68 TBG1-118
RFR1A RFR1A1 (Note: One TBX10.1 TB per MCC bucket) RF1FB1 RF1FB
Spare M2-A12
A5 (10) M3-B1 RadFan1 SM2A12
11 RadFan1 (13) A11
RadFan1 On/Off Status Feedback DO
RFR1 TBG1-31 Status
RFR1B RFR1B2 TBG1-119 A
14 A6 (11) TBG1-69 (Reserved
RF2FB1 RF2FB RadFan2 Spare SM2A16
TBG1-32 RFR2A1 RadFan2 (13) B11 M3-B2 M2-A16 for AVR
RFR2A Status Feedback DO
GCP PLC B5 (10) Status Watchdog)
Com Rtn 11
RFR2 RadFan2 On/Off TBG1-120
TBG1-108
RFR1 TBG1-33 RFR2B2
TBG1-70 SM4A3
FAN1 A2 A1 FANR1 RFR2B RF3FB1 RF3FB RadFan3 Spare M4-A3
(Reserved for AVR SM2B12 Spare RadFan 1 M3-A4 14 B6 (11) RadFan3 (13) C11 M3-B3
M2-B12 Status Status Feedback DO
Watchdog) DI Outp TBG1-34
RFR3A RFR3A1
11 C5 (10) TBG1-121
RFR2 RF4FB1 TBG1-71
RF4FB RadFan4 Spare SM4A8
TBG1-109 A2 A1 FANR2 RFR3 RadFan3 On/Off M3-B4 M4-A8
SM4B8 Spare RadFan 2
M3-A5
FAN2
RFR3B
TBG1-35 RFR3B2 RadFan4 (13) D11 Status Feedback DO
M4-B8 Outp 14 C6 (11) Status
DI TBG1-122
TBG1-72 RF5FB SM4A9
TBG1-36 RFR4A1 RF5FB1 RadFan5 Spare M4-A9
RFR3 RFR4A RadFan5 (13) E11 M3-B5
TBG1-110 11 D5 (10) Status Feedback DO B
SM4B9 Spare RadFan 3 FAN3 A2 A1 FANR3 Status
M4-B9 M3-A6 RFR4 TBG1-37 RadFan4 On/Off
DI Outp RFR4B RFR4B2 TBG1-73 RadFan6 TBG1-123
14 D6 (11) RF6FB1 RF6FB Spare SM4A10
RFR4 RadFan6 (13) F11 M3-B6 Status Feedback DO
M4-A10
TBG1-111 A2 A1 TBG1-38 RFR5A1
SM4B10 Spare RadFan 4 FAN4 FANR4 RFR5A Status
M4-B10 M3-A7 11 E5 (10) TBG1-124
DI Outp TBG1-74 RadFan7 SM4A11
RFR5 TBG1-39 RadFan5 On/Off RF7FB1 RF7FB Spare M4-A11
RFR5B RFR5B2 (13) G11 M3-B7 Status Feedback
14 E6 (11) RadFan7 DO
TBG1-112 RFR5
SM4B11 Spare FAN5 A2 A1 FANR5 TBG1-40 Status
RadFan 5 RFR6A RFR6A1
RadFan8
M4-B11 DI M3-A8 F5 (10) TBG1-125
Outp 11 TBG1-75 Spare SM4A12
RF8FB1 RF8FB Status Feedback M4-A12
RFR6 TBG1-41 RadFan6 On/Off RadFan8 (13) H11 M3-B8 DO
RFR6B RFR6B2 Status
TBG1-113
SM4B12 Spare A2 RFR6 A1 FANR6 14 F6 (11)
RadFan 6 FAN6 TBG1-76
M4-B12 TBG1-42 RF9FB TBG1-126 C
DI Outp M3-A9 RFR7A RFR7A1 RF9FB1 RadFan9 Spare SM4A13
RadFan9 (13) I11 M3-B9 Status Feedback
11 G5 (10)
Status DO M4-A13
RFR7 RFR7 TBG1-43 RadFan7 On/Off
TBG1-114 RFR7B RFR7B2
SM4B13 Spare A2 A1 FANR7 14 G6 (11) TBG1-77 TBG1-127
M4-B13 RadFan 7 M3-A10 FAN7 RF10FB1 RF10FB RadFan10 Spare SM4A14
DI
Outp RFR8A TBG1-44 RFR8A1
RadFan10 (13) J11 M3-B10 Status Feedback DO M4-A14
H5 (10)
Status
11
TBG1-115 A2 RFR8 A1 RFR8 TBG1-45 RFR8B2
RadFan8 On/Off TBG1-78 TBG1-128
SM4B14 Spare RadFan 8 M3-A11 FAN8 FANR8 RFR8B RF11FB1 RF11FB RadFan11 Spare SM4A15
M4-B14 14 H6 (11) RadFan11 * (13) K11 M3-B11 Status Feedback M4-A15
DI Outp DO
TBG1-46
Status
RFR9A RFR9A1
RFR9 11 I5 (10) TBG1-79 TBG1-129
TBG1-116 A2 A1 FANR9 RF12FB1 RadFan12 Spare SM4A16
SM4B15 Spare RadFan 9 FAN9 RFR9 RadFan9 On/Off RadFan12 * (13) L11
RF12FB M4-A16
M3-A12 RFR9B
TBG1-47 RFR9B2 M3-B12 Status Feedback DO D
M4-B15 DI Outp 14 I6 (11) Status
TBG1-48 RFR10A1 TBG1-80 RF13FB
RFR10A RF13FB1 RadFan13
TBG1-117 A2 RFR10 A1 11 J5 (10) RadFan13 ** (13) M11 M4-B4 Status Feedback
SM4B16 FAN10 FANR10
Spare RadFan 10 RFR10 RadFan10 On/Off Status
M4-B16 TBG1-49
DI Outp M3-A13 14
RFR10B RFR10B2
J6 (11) TBG1-81
RF14FB1 RF14FB RadFan14
TBG1-50 RFR11A1 RadFan14 ** (13) N11 M4-B5 Status Feedback
RFR11 RFR11A
FAN11 A2 A1 FANR11 11 K5 (10) Status
RadFan 11 *
Outp M3-A14 RFR11* TBG1-51 RadFan11 On/Off *
RFR11B RFR11B2 TBG1-82
14 K6 (11) RF15FB1 RF15FB RadFan15
RadFan15 ** (13) O11 M4-B6 Status Feedback
A2 RFR12 A1 TBG1-52 Status
RadFan 12 * FAN12 FANR12 RFR12A RFR12A1
L5 (10)
Outp M3-A15 11
TBG1-83
E

RFR12* TBG1-53 RadFan12 On/Off * RF16FB1 RF16FB RadFan16


RFR12B RFR12B2 RadFan16 ** (13) P11 M4-B7 Status Feedback
RFR13 14 L6 (11)
Status
RadFan 13 ** FAN13 A2 A1 FANR13 TBG1-54
RFR13A RFR13A1
Outp M4-A4 11 M5 (10)
TBG1-84 VF1FB
RFR13 ** RadFan13 On/Off ** VF1FB1 VentFan1
RFR13B
TBG1-55 RFR13B2 VentFan1 (13) S11 M3-B13
A2 RFR14 A1 14 M6 (11) Status Feedback
RadFan 14 ** FAN14 FANR14 Status
Outp M4-A5 RFR14A TBG1-56 RFR14A1
11 N5 (10)
VentFan2 TBG1-85 VentFan2
RFR15 RFR14 ** TBG1-57 RadFan14 On/Off ** VF2FB1 VF2FB
FAN15 A2 A1 FANR15 RFR14B RFR14B2 Status (13) T11 M3-B14 Status Feedback
RadFan 15 ** 14 N6 (11)
M4-A6
Outp TBG1-58
F
RFR15A RFR15A1
11 O5 (10) TBG1-86
A2 RFR16 A1 FANR16 RFR15 ** RadFan15 On/Off ** VentFan3 (13) U11 VF3FB1 VF3FB
M3-B15 VentFan3
RadFan 16 ** FAN16 TBG1-59 RFR15B2
RFR15B Status Status Feedback
O6 (11)
Outp M4-A7
14

RFR16A TBG1-60 RFR16A1


11 P5 (10) TBG1-87
COMPFB1 COMPFB
VFR1 RFR16 ** TBG1-61 RadFan16 On/Off ** Air Compressor (13) M3-B16 Air Compressor
VFAN1 A2 A1 VFANR1 RFR16B RFR16B2 X11
VentFan 1 14 P6 (11) Status Status Feedback
Outp M3-A16 DC JBOX
VFR1A TBG1-62 VFR1A1
11 S5 (10) ACRUN1 ACRUN1A
A2 VFR2 A1 (10) X5
VentFan 2 VFAN2 VFANR2 VFR1 TBG1-63 VentFan1 On/Off 1
VFR1B VFR1B2 L1 G
Outp M4-A1 14 S6 (11)
M1 Air Pressure
TBG1-64 VFR2A1 M2 Switch
VFR3 VFR2A
A2 A1 11 T5 (10) Air Compressor APS
VentFan 3 VFAN3
VFR2 VentFan2 On/Off On/Off L2 MCC to Air
Outp M4-A2 VFR2B
TBG1-65 VFR2B2 ACRUN2
2G_213 14 T6 (11)
A Oil Level Compressor Asm
VFR3A TBG1-66 VRF3A1 Switch
11 U5 (10) 3 B OLS
ACRUN3 ACRUN3A
Com Rtn VFR3 VentFan3 On/Off (11) X6
TBG1-67 VFR3B2
VFR3B
14 U6 (11)
Spare
Status (13) R11
NOTES: NC
NC
R5 (10)
R6 (11)
Spare 18 On/Off
Spare
H

1. * 12/16V250 require Radfans 11-12 NC W5 (10)


Status (13) W11
W6 (11) Spare 23 On/Off MCC24+ TBG1-24A
2. ** 16V250 require Radfans 11-16 NC
(12) 24DC+
3. All Radfan relays applied to all GCP types (Note: 24DC connected to terminal (12) of all TBX10.1 TBs)
0 1 2 3 4 5 6 7 8 9 SECT C1
0 CO-149467 January 2013 C CO-172854 April 2016
REVISIONS TITLE SCHEMATIC DIAGRAM MADE BY E. SADER 01.25.2013 APPROVAL
STATIONARY
ERIE 84B540865AB
PLANT
A CO-153582 July 2013 FIRST MADE FOR STANDARD UNENCLOSED GENSET ISSUE
E. SADER
GENERAL ELECTRIC CO. CONT ON SHT 14 SHT 13
RC
THIS DRAWING, WHICH CONTAINS PROPRIETARY INFORMATION, IS
84B540865AB THE PROPERTY OF GENERAL ELECTRIC COMPANY. IT SHALL NOT BE

CONT ON SHT 15 SHT 14 Auxiliary System SECT C2 Control / Battery Charging REPRODUCED IN ANY MANNER NOR DISCLOSED TO THIRD PARTIES
WITHOUT WRITTEN PERMISSION OF GENERAL ELECTRIC COMPANY.

Battery Charger BC24V+


(Optional) BATT+

X1-1-L Batt Batt

BATT- BC24V-
LMR2
A2 A1
ECP PLC X1-2-N B

GR2 2ECP4

LMR1
TBE1-178 GR1 A2 A1
2ECP5
Xi-3-G GCP PLC
SM7-15 Spare Louver** M6-7
M7-15
Input Output
EPHR
EPHRA2 A2 A1 2G_212
ENGINE M3-A1
PREHEAT
EPLR
TBE1-179 TBE1-180 Com Rtn A2 A1 2G_214
Spare Spare SM6-8 24VDC EPLRA2
SM7-16 M6-8 ENGINE M3-A2 C
M7-16 Output
Input PRELUBE **
TBG1-24A
24G_301A 24G_301 EFPR
COM EFPRA2 A2 A1 2G_216
ENGINE FUEL M3-A3
Fault PRIME**
TBG1-88
1BCH1 BCH1
CMF M2-B3 Battery Charger
Fault
Com Rtn

24VDC 24 VDC

FPH 24G_40 FPH


11 24G_41
11
Fluid Pre-Heat System 21
Fluid Pre-Heat System EPHR
GCP PLC
EPHR (DLV Type) EPHR
14 TBG1-89
(DV Type) 12 TBG1-89
EPHRB EPHP EPHRB EPHP 24
TB1-1 TB2-9 E
TJ2-1 TJ2-1
Engine Preheat Engine Preheat EPHFB Engine Preheat
Run Permissive TBG1-90 Run Permissive M4-B1
EPHRA
TBG1-90 2G_40 EPHPR Status Feedback
EPHPR
TB1-2 TB2-10
TJ2-2 TJ2-2

Com Rtn

MCC***
F
EPLRA TBG1-91 EPLRA1 V5
11
EPLR Engine Prelube On/Off ** TBG1-95
EPLFB1 EPLFB Engine Prelube OLR
EPLRB TBG1-92 EPLRB1 Engine Prelube V11 M4-B2
14
V6 Status Feedback **
Status **
EFPRA TBG1-93 EFPRA1
Q5
11
EFPR Engine Fuel Prime On/Off** TBG1-96
Engine Fuel Prime EFPFB1 EFPFB Engine Fuel Prime OLR
14 EFPRB TBG1-94 EFPRB1
Q6 Status** Q11 M4-B3
Status Feedback**

NOTES:
* MCC Radiator Fan Application Chart
** If Optional items are not equipped, use as SPARE
*** Above is the MCC diagram if provided by GE. Otherwise, use as TYPICAL subject to Customer provided MCC diagram
H

0 1 2 3 4 5 6 7 8 9
SECT C2
0 CO-149467 January 2013 B CO-164146 January 2015
TITLE SCHEMATIC DIAGRAM MADE BY E. SADER 01.25.2013 APPROVAL STATIONARY ERIE 84B540865AB
REVISIONS
PLANT
A CO-153582 July 2013 C CO-172854 April 2016 FIRST MADE FOR STANDARD UNENCLOSED GENSET ISSUE
E. SADER
GENERAL ELECTRIC CO. CONT ON SHT 15 SHT 14
RC
THIS DRAWING, WHICH CONTAINS PROPRIETARY INFORMATION, IS
84B540865AB THE PROPERTY OF GENERAL ELECTRIC COMPANY. IT SHALL NOT BE

CONT ON SHT 16 SHT 15 Auxiliary System SECT C3 Low Voltage / Gauge Panel REPRODUCED IN ANY MANNER NOR DISCLOSED TO THIRD PARTIES
WITHOUT WRITTEN PERMISSION OF GENERAL ELECTRIC COMPANY.

Below LV Panel diagram if provided by GE. Otherwise, use as TYPICAL subject to Customer provided LV Panel
A

Internal
to MCC

TBE1-24A TJ2-19

TBE1-2A TJ2-20

TJ2-21

0 1 2 3 4 5 6 7 8 9 SECT C3
0 CO-149467 January 2013 B CO-164146 January 2015
REVISIONS TITLE SCHEMATIC DIAGRAM MADE BY E. SADER 01.25.2013 APPROVAL STATIONARY ERIE 84B540865AB
PLANT
A CO-153582 July 2013 C CO-172854 April 2016
FIRST MADE FOR STANDARD UNENCLOSED GENSET ISSUE
E. SADER
GENERAL ELECTRIC CO. CONT ON SHT 16 SHT 15
RC
THIS DRAWING, WHICH CONTAINS PROPRIETARY INFORMATION, IS
84B540865AB THE PROPERTY OF GENERAL ELECTRIC COMPANY. IT SHALL NOT BE

CONT ON SHT 17 SHT 16 Auxiliary System SECT C4 Fire Detection System REPRODUCED IN ANY MANNER NOR DISCLOSED TO THIRD PARTIES
WITHOUT WRITTEN PERMISSION OF GENERAL ELECTRIC COMPANY.

Sheet intentionally left blank


E

0 1 2 3 4 5 6 7 8 9
SECT C4
0 CO-149467 January 2013
REVISIONS TITLE SCHEMATIC DIAGRAM MADE BY E. SADER 01.25.2013 APPROVAL STATIONARY ERIE 84B540865AB
PLANT
A CO-153582 July 2013 FIRST MADE FOR STANDARD UNENCLOSED GENSET ISSUE
TS OLESKI
GENERAL ELECTRIC CO. CONT ON SHT 17 SHT 16
RC
THIS DRAWING, WHICH CONTAINS PROPRIETARY INFORMATION, IS
84B540865AB THE PROPERTY OF GENERAL ELECTRIC COMPANY. IT SHALL NOT BE

CONT ON SHT 19 SHT 18 Engine System SECT D Control & Fuel Injection REPRODUCED IN ANY MANNER NOR DISCLOSED TO THIRD PARTIES
WITHOUT WRITTEN PERMISSION OF GENERAL ELECTRIC COMPANY.

24VDC
24E_222
TBE1-130 Right Bank
Wireway
BOS+
SBIAS1+
TBE1-138
SBIAS2+ SBIAS3+ 4-1 (SIG+)
ECU (V228)(V250) A
B2-G7 FIRP1+ TBE1-1
1 3-34 HPPS1+ V F A
(V250) (V228) (STATIONARY)
a a GCP to ECP TBE1-139
R1E Right1
FIRP1- TBE1-2
+
FIRP1
U R SPEED BIAS Solenoid 3-31 HPPS1- U A B -
SBIAS1- 2
B2-G7 4-6 (SIG-)
SBIAS2- SBIAS3- FIRP2+ TBE1-3
A HPPS2+ T C A 24VDC
4-12 (SHD) Right2 3-29 TBE1-4
+
BOS
ECP PLC ECESPB
(No GPESPB if no Gauge Panel)
GPESPB GCESPB
Solenoid
3-35
FIRP2- HPPS2- S D B - FIRP2
24E_24
B TBG1-103
1A 2A TBE1-163
TJ2-15 1A 2A TJ2-16 TBE1-189 TBG1-102 1A 2A FIRP3+ TBE1-5 HPPS3+
Sol Enable Outp M6-2 SOLE SOLE4C R F A
SOLE4 SOLE4A 549 549X SOLE4B SOLE4B1 SOLE4B1 SOLE4B2 Right3 3-23 + 11
FIRP3- TBE1-6 HPPS3- FIRP3
(V250) (V228) Install jumper if SOLEJMP Solenoid P A B - SR
T P no Gauge Panel EFR 3-30
Z Z E-STOP 11 14 TBE1-7 14 B
FIRP4+ HPPS4+
M7-13
SOLE4D
5-22 Solenoid enable N C A SS4
Feedback SOLE4G SOLE5
Right4 3-16 + 11
BOS- TBE1-131
TBE1-165
FIRP4- TBE1-8 HPPS4- FIRP4
Solenoid M D B - ERR
3-24
BOS1 12
M7-12 Bar-Over Switch FIRP5+ TBE1-9 HPPS5+ L F A
24VDC
31
EFR Right5 3-17 TBE1-10
+
32 FIRP5- HPPS5- K B FIRP5 SS5
M7-14 EFR Feedback Solenoid 3-18 A -
24_EFR-FD EFR-FD

TBE1-11 TBE1-134
FIRP6+ HPPS6+
3-10 J C A
Right6 +
FIRP6- TBE1-12 FIRP6
ECP PLC Solenoid 3-11
HPPS6- H D B - (V250) (V228)
W W
(STATIONARY)
TBE1-176 FIRP7+ TBE1-13 HPPS7+ d 15
G F A C
Right7 ** 3-5
Gov Run RPERM RPERM1 +
M6-3 5-7 Run Perm TBE1-14
Permissive Outp FIRP7- HPPS7- B FIRP7 **
Solenoid 3-6 F A -
TBE1-177 SAS+
GRST GRST1 TBE1-15
Gov Reset Outp M6-4 5-19 Reset FIRP8+ HPPS8+ E C A
Right8 ** 3-1 + Start
TBE1-16
SRA2
A2
SR
A1
2E_21 Solenoid 3-2 FIRP8- HPPS8- D D B - FIRP8 ** Solenoid ECP to Air
Start Relay Outp M6-5
RGND1 TBE1-132
SSOL Starter
3-26 C
SAS-
ELRRA2 ELRR 2E_22 RGND2
Engine Loc/Rem M6-6 A2 A1
Relay Outp Left Bank (V250) (V228) D

Wireway e 16
V V
(V228)(V250)
Com Rtn FILP1+ TBE1-17 HPPS1+ V F A
1-34 + TBE1-135
Left1 FILP1- TBE1-18 FILP1
Solenoid 1-31 HPPS1- U A B -
24VDC 2E_217

FILP2+ TBE1-19 HPPS2+ T C A


1-29 + COM RTN
24E_22 Left2 TBE1-20
FILP2- HPPS2- S D B - FILP2
Solenoid 1-35
FILP3+ TBE1-21 HPPS3+
Install Jumper for 8/16 Cylinder R F A
Leave Open for 6/12 Cylinder
1-23 +
Left3 TBE1-22 E
FILP3- HPPS3- P A B - FILP3
TBE1-33 Solenoid 1-30
12_16
5-21 12/16 cyl (Dig Inp6) FILP4+ TBE1-23 HPPS4+ N C A
1-16 +
Left4 TBE1-24
FILP4- HPPS4- M D B - FILP4
5V_JMP2 5V_JMP1 Solenoid 1-24
4-29
(+5V)
ENGINE ENGINE TYPE VOLTAGE R2E R3E FILP5+ TBE1-25 HPPS5+ L F A
MODEL JUMPER INPUT 8.2K 33.2K TBE1-35 Left5 1-17 +
5V_JMP4 V228_12 FILP5- TBE1-26 FILP5
12V250 NOT APPLIED 0 VOLTS 4-34 (SIG) Engine Configuration Solenoid 1-18 HPPS5- K A B -
16V250 NOT APPLIED 0 VOLTS V228_16
(33K Ohm Internal Pull-down)
FILP6+ TBE1-27 HPPS6+
12V228 V228_12 2.5 VOLTS TBE1-34 J C A
4-30 (COM) 1-10 +
16V228 V228_16 4.0 VOLTS 5V_JMP3 Left6 TBE1-28
FILP6- HPPS6- B FILP6
Solenoid 1-11 H D - F

FILP7+ TBE1-29 HPPS7+ G F A


24VDC Left7 ** 1-5 TBE1-30
+
FILP7- HPPS7- FILP7 **
Solenoid 1-6 F A B -
24E_21
FILP8+ TBE1-31 HPPS8+
11 1-1 E C A
ELRR Left8 ** +
FILP8- TBE1-32 HPPS8-
12 Solenoid 1-2 D D B - FILP8 **

ISPD 5-8 Inc Spd LGND1 TBE1-133


C
1-26
DSPD 5-9 Dec Spd LGND2 G

2E_28
5-15 Solenoid enable return
Engine Fail A2 EFR A1
2E_27 EFRA2 2E_214
5-2 Run Perm Return Relay 5-1
2E_29
5-3 Inc Spd Return * 12V250 and 12V228 Only
2E_210 ** 16V250 and 16V228 Only
5-4 Dec Spd Return Engine Run ERR
ERRA2 A2 A1
Relay 2E_215
2E_211 5-6
5-12 Reset Return
2E_212
5-13 CW Rotation Return COM RTN
H
2E_213 *Install Jumper for 8/16 Cylinder)
5-14 8/16 Cyl Return* *Leave Open for 6/12 Cylinder)
2E_24
5-20 CCW Rotation Return

Com Rtn
0 1 2 3 4 5 6 7 8 9 SECT D
0 B
REVISIONS TITLE SCHEMATIC DIAGRAM MADE BY E. Sader APPROVAL STATIONARY
ERIE 84B540865AB
PLANT
A FIRST MADE FOR STANDARD UNENCLOSED GENSET ISSUE
TS OLESKI
GENERAL ELECTRIC CO. CONT ON SHT 19 SHT 18
RC
THIS DRAWING, WHICH CONTAINS PROPRIETARY INFORMATION, IS
84B540865AB THE PROPERTY OF GENERAL ELECTRIC COMPANY. IT SHALL NOT BE

CONT ON SHT 20 SHT 19 Engine System SECT D1 Cooling System Monitoring REPRODUCED IN ANY MANNER NOR DISCLOSED TO THIRD PARTIES
WITHOUT WRITTEN PERMISSION OF GENERAL ELECTRIC COMPANY.

ECU
V250 (ECU-A) TBE1-49
(L) ELPP+ ELPPX
J 4-15 (+5V)
(B) ENIGNE LUBE OIL
H (M) TBE1-50 ELPP+ PUMP OUTLET PRESSURE
ELPP SIG
ELPP* (C) 4-9 (SIG) SENSOR*
K (K) TBE1-51 ELPP-
ELPP-
(A) 4-14 (COM)
G TBE1-52 ELPPSHD
ELPP SHLD
4-13 (SHD)
B

TBE1-53 ELOT+
D (F) ELOT+
(A) 6-22 (SIG+)
ELOT* E (E) TBE1-54 ELOT- ENGINE LUBE OIL OUTLET
(B) ELOT- 6-21 (SIG-) TEMPERATURE*
TBE1-55
L ELOT SHD ELOTSHD
6-20 (SHD)

(V228)
TBE1-56 ELIT+
(R) U (T) ELIT+
(A) 6-2 (SIG+)
ELIT (S) c TBE1-57 ELIT- ENGINE LUBE OIL INLET C

(B) (S) ELIT-


6-3 (SIG-) TEMPERATURE
ECU (H)
b 6-7 (SHD)
(V228) V250 (ECU-B) TBE1-36
(D) K (22) EWIP + EWIPX
(B) 4-37 (+5V)
TBE1-37 EWIP+
(C) L (21) EWIP SIG
EWIP (C) 4-33 (SIG) ENGINE WATER INLET
TBE1-38 EWIP- PRESSURE SENSOR
(E) E (23) EWIP -
(A) 4-32 (COM)
(V228) (ECU-A)
TBE1-39 EWIPSHD V250 TBE1-58 ELIPS
M EWIP SHLD (23) ELIP +
4-27 (SHD) B (b) 4-4 (+5V)
(B) D

C TBE1-59 ELIP+
(24) (c) ELIP SIG ENGINE LUBE OIL INLET
(C) 4-3 (SIG)
ELIP PRESSURE
(V228) V250 (ECU-A) TBE1-40 A (a) TBE1-60 ELIP-
(A) (27) ELIP -
(L) d (W) EWOT+ EWOT+ 4-8 (COM)
(A) 6-9 (SIG+)
TBE1-41 TBE1-61 ELIPSHD
EWOT b (V) ENGINE WATER OUTLET (17) D ELIP SHLD
(M) EWOT- EWOT- 6-4 (SIG-) 4-7 (SHD)
(B) TEMPERATURE
TBE1-42
(A) a EWOT SHLD EWOTSHD 6-8 (SHD)
(V228) V250 (ECU-A) TBE1-62 CAPX
(3) H (e) COP +
(B) 4-28 (+5V)
G TBE1-63 CAP+ CRANKCASE AIR PRESSURE
E

(ECU-A) (4) (f) COP SIG


TBE1-43 CAP (C) 4-22 (SIG)
A (H) EWIT+ EWIT+
(A) 6-15 (SIG+) (2) J (d) TBE1-64 CAP-
(A) COP - 4-21 (COM)
EWIT* TBE1-44 ENGINE WATER INLET
B (G) EWIT- EWIT-
(B) 6-14 (SIG-) TEMPERATURE* TBE1-65 CAPSHD
(5) F COP SHLD
TBE1-45 4-20 (SHD)
C EWIT SHLD EWITSHD
6-13 (SHD)
ECUN
ECU G (ground lug)

24VDC
24VDC

TJ2-7 TBE1-66 24E_25


TBE1-46 24E_28
ECP PLC
ECP PLC
DLOP
LWLS1 TJ2-8 TBE1-67
E-24A4 Differential
(LSL-100) TJ2-10 TBE1-47 (C) (NO) M7-3
TJ2-9 E-67 DLOP2 Lube Oil
E-LWL(+) E-LWL1 LWLS1 M7-1 Low Water Level
Pressure G
HT System
LWLS2
TJ2-11 (LSL-200) TJ2-12 TBE1-48
2E-LWL(+) E-LWL2 LWLS2 Low Water level
M7-2
LT System

* V250 Engines Only

0 1 2 3 4 5 6 7 8 9
SECT D1
0 CO-149467 January 2013
REVISIONS TITLE SCHEMATIC DIAGRAM
MADE BY E. Sader 1.25.2013 APPROVAL STATIONARY ERIE 84B540865AB
PLANT
A CO-153582 July 2013 FIRST MADE FOR STANDARD UNENCLOSED GENSET ISSUE
TS OLESKI
GENERAL ELECTRIC CO. CONT ON SHT 20 SHT 19
RC
THIS DRAWING, WHICH CONTAINS PROPRIETARY INFORMATION, IS
84B540865AB THE PROPERTY OF GENERAL ELECTRIC COMPANY. IT SHALL NOT BE

CONT ON SHT 21 SHT 20 Fuel System Monitor SECT D2 Air Intake & Fuel Monitoring REPRODUCED IN ANY MANNER NOR DISCLOSED TO THIRD PARTIES
WITHOUT WRITTEN PERMISSION OF GENERAL ELECTRIC COMPANY.

(V228) V250
ECU
(ECU-B)
TBE1-68 MAT+
(28) N (20) MAT+
(A) 6-28 (SIG+)
MAT
TBE1-69
(25) P (19) MAT- MAT- MANIFOLD AIR TEMPERATURE
(B) 6-27 (SIG-)
TBE1-70 MATSHD
(26) MAT SHLD
R 6-26 (SHD)

B
TBE1-71 MAPX
(K) X (17) MAP +
4-35 (+5V)
(V228) V250 (ECU-A) ECU MAP
(B)
TBE1-72 MAP+
TBE1-83 (L) W (16) MAP SIG MANIFOLD AIR PRESSURE
(P) Z (m) EFT+ EFT+
(C) 4-36 (SIG)
(A) 6-5 (SIG+) TBE1-73
(J) Z (18) MAP - MAP-
EFT (C) Y (k) EFT- (A) 4-31 (COM)
(TT-310) (B) EFT-
6-1 (SIG-) ENGINE FUEL TEMPPERATURE
(M) Y
TBE1-84 4-26 (SHD)
X 6-6 (SHD)

(V228) V250
(ECU-B) TBE1-85 C
(B) V (27) EFP+ EFPX
(B) 4-16 (+5V)
EFP U (26) TBE1-86 (ECU-A)
(G) EFP SIG EFP+ V250 TBE1-74
(C) 4-23 (SIG) F (N) ICWT+ ICWT+
ENGINE FUEL (A) 6-23 (SIG+)
W (28) TBE1-87 PRESSURE
(A) (A) EFP- EFP- ICWT* TBE1-75 INTERCOOLER WATER
4-17 (COM) M (P) ICWT- ICWT-
(B) 6-24 (SIG-) TEMPERATURE*
TBE1-88
(F) T EFP SHLD EFPSHD
4-24 (SHD) N 6-25 (SHD)

TBE1-76 ICWPX
R (Z) ICWP +
(B) 4-5 (+5V) D

TBE1-77
24 VDC S (X) ICWP SIG ICWP+
ICWP* (C) 4-10 (SIG) INTERCOOLER
TBE1-78 WATER PRESSSURE
(A) P (R) ICWP - ICWP-
24E_27 4-11 (COM) SESOR*
TBE1-89 TBE1-79
24E_27A T ICWPSHD
ICWP SHLD
4-18 (SHD)

LLFLS
LLFL
ECP PLC
E-LLF Low Low Fuel ECUNN
M7-4 6-19 (GND)
TFS-1 TFS-2 TBE1-90 Level
Unenclosed GenSet
E
Standard
LFLS (V228)
E-LF(+) E-LF LFL V250 (STATIONARY)
M7-5 Low Fuel (7) k (N) SAP+
TFS-3 TFS-4 TBE1-91 (2)
Level SAP
(at Air Starter) (6) m (P) SAP-
(1)
HFLS
E-HF(+) E-HF
HFL
M7-6 High Fuel j ECP PLC
TFS-5 TFS-6 TBE1-92 Level 24 VDC

HHFLS Optional
E-HHF(+) E-HHF HHFL 24E_SAP
M7-7 High High Fuel SAP+ TBE1-136 F

TFS-7 TFS-8 TBE1-93 Level (2)


SAP
(at Reservoir) SAP- TBE1-137
FLDS SAPX
E-FLD(+) E-FLD FLD Fuel Leak (1) M3-16 (SIG+)
M7-8
Detected
TFS-9 TFS-10 TBE1-94 TBE1-2A Air Reservoir
2SAP- M3-17 (iRTN) Pressure
TBE1-2A M3-18 (SIG-)
2E_SAP
24 VDC

Com Rtn
G

TJ2-3 TBE1-95 24E_210


24 VDC

E-24A2 24E_DAIP
DFOP TJ2-5 TBE1-140
E-24A3
(DPS-310) TJ2-4 TBE1-96 Differential
(C) (NO) E-96 DFOP1 M7-10 Fuel Oil
* V250 Engines Only Differential
Pressure TJ2-6 TBE1-148
DAIP1 DAIP1 Air Intake
E-24A3-1
(C) (NC) M7-11 Pressure

0 1 2 3 4 5 6 7 8 9 SECT D2
0 CO-149467 January 2013 B CO-164146 January 2015
REVISIONS
TITLE SCHEMATIC DIAGRAM MADE BY E. Sader 01.25.2013 APPROVAL STATIONARY ERIE 84B540865AB
PLANT
A CO-153582 July 2013 FIRST MADE FOR STATIONARY UNENCLOSED GENSET ISSUE
TS OLESKI
GENERAL ELECTRIC CO. CONT ON SHT 21 SHT 20
RC
THIS DRAWING, WHICH CONTAINS PROPRIETARY INFORMATION, IS
84B540865AB THE PROPERTY OF GENERAL ELECTRIC COMPANY. IT SHALL NOT BE

CONT ON SHT 22 SHT 21 Engine System SECT D3 Main Bearing, Speed, & Position Monitoring REPRODUCED IN ANY MANNER NOR DISCLOSED TO THIRD PARTIES
WITHOUT WRITTEN PERMISSION OF GENERAL ELECTRIC COMPANY.

MBT
Left Bank Plug
Wireway MBT Harness
V250 ECP PLC A

B 2 U BT1- TBE1-109 MBTS1-


M8-22 (SIG-)
MBTS1 # A 1 V BT1+ TBE1-110 Main Bearing 1
MBTS1+
M8-20 (SIG+) Temperature #
MBTS1X
M8-19 (EXC)

2 S BT2- TBE1-111
B MBTS2-
M8-6 (SIG-)
MBTS2 # 1 T TBE1-112 Main Bearing 2
A BT2+ MBTS2+ B
M8-4 (SIG+) Temperature #
MBTS2X
M8-3 (EXC)

2 P BT3- TBE1-113 MBTS3-


B
M8-26 (SIG-) 24VDC
MBTS3 # 1 R TBE1-114 Main Bearing 3
A BT3+ MBTS3+
M8-24 (SIG+) Temperature #
MBTS3X
M8-23 (EXC) (V228) V250 (ECU-B)
TBE1-97
ECU
A (15) EC1S+ CPS1+ C
(15) 2-25 (SIG+)
(A) 24E_29
CPS1 TBE1-98 CPS1- ENGINE SPEED 5-5
(14) B (14) EC1S-
(B) 2-30 (SIG-) CRANK SENSOR NO.1 24E_211
B 2 M BT4- TBE1-115 MBTS4- TBE1-99 CPS1SHD 5-11
M8-10 (SIG-) EC1S SHLD
C 2-19 (SHD) 24E_212
MBTS4 # A 1 N TBE1-116 Main Bearing 4
BT4+ MBTS4+ 5-16
M8-8 (SIG+) Temperature #
MBTS4X TBE1-100 24E_213
M8-7 (EXC) A (13) CPS2+
(13) EC2S+ 2-32 (SIG+) 5-23
(A)
CPS2 TBE1-101 CPS2- ENGINE SPEED 24E_214
(12) B (12) EC2S-
(B) 2-36 (SIG-) CRANK SENSOR NO.2 5-24
TBE1-102 CPS2SHD
D
TBE1-117 EC2S SHLD
B 2 K BT5- MBTS5- C 2-27 (SHD)
M8-30 (SIG-)
MBTS5 # A L BT5+ TBE1-118 Main Bearing 5
1 MBTS5+ M8-28 (SIG+) Temperature #
MBTS5X
M8-27 (EXC)

(V228) V250 (ECU-A) TBE1-127


EPS+ EPSP
(18) V (j) 2-17 (SIG)
(A)
EPS** TBE1-128 EPSR ENGINE POSITION
(19) U (h) EPS-
(B) 2-23 (COM) SENSOR** (v228 Only)
2 H BT6- TBE1-119 MBTS6-
B EPS SHLD TBE1-129
M8-14 (SIG-) (20) EPSSHD
MBTS6 # 1 T 2-11 (SHD) E

A J BT6+ TBE1-120 MBTS6+ Main Bearing 6


M8-12 (SIG+) Temperature #
MBTS6X
M8-11 (EXC)

(V228) (ECU-B)
TLS+ TBE1-103 TSLX
(B) a (25)
(1) 2-7 (+5V)
TBE1-121 TSL TBE1-104 TURBO SPEED
B 2 F BT7- MBTS7- (N) Z (24) TLS- TSL+
M8-34 (SIG-) (2) 2-3 (SIG) SENSOR LEFT * G1
MBTS7 # A 1 BT7+ TBE1-122 Main Bearing 7 TLS SHLD TBE1-105 TSLSHD (GND) 5-35
G MBTS7+ (U)
M8-32 (SIG+) Temperature # Y 2-10 (SHD)
MBTS7X G2
M8-31 (EXC) (GND) 5-36
F

TBE1-106 (GND) 5-37 G3


W (4) TRS+ TSRX
(1) 2-14 (+5V)
TSR * V TBE1-107 TSR+ TURBO SPEED
(3) TRS-
(2) 2-9 (SIG) SENSOR RIGHT *
d TBE1-108 TSRSHD
2 TBE1-123 TRS SHLD
B D BT8- MBTS8- 2-20 (SHD)
M3-14 (SIG-)
MBTS8 ## A 1 E BT8+ TBE1-124 MBTS8+ Main Bearing 8
M3-12 (SIG+) Temperature ##
MBTS8X
M3-11 (EXC)

2 B BT9- TBE1-125 MBTS9-


B
M3-34 (SIG-)
MBTS9 ## A 1 BT9+ TBE1-126 Main Bearing 9
C MBTS9+
M3-32 (SIG+) Temperature ##
MBTS9X
M3-31 (EXC)

TBE1-181 SPCM8-
M8-18 (SIG-) H

TBE1-182 NOTE: MAIN BEARING TEMPERATURES


SPCM8+ Spare
M8-16 (SIG+) Temperature FOR V250 ENGINES ONLY
SPCM8X # 12v250 Engines
M8-15 (EXC)
## 12 & 16V250 Engines
0 1 2 3 4 5 6 7 8 9 SECT D3
0 CO-149467 January 2013
REVISIONS TITLE SCHEMATIC DIAGRAM MADE BY E. SADER 01.25.2013 APPROVAL STATIONARY ERIE 84B540865AB
PLANT
A CO-153582 July 2013 FIRST MADE FOR STANDARD UNENCLOSED GENSET ISSUE
E. SADER
GENERAL ELECTRIC CO. CONT ON SHT 22 SHT 21
RC
THIS DRAWING, WHICH CONTAINS PROPRIETARY INFORMATION, IS
84B540865AB THE PROPERTY OF GENERAL ELECTRIC COMPANY. IT SHALL NOT BE

CONT ON SHT 23 SHT 22 Engine System SECT D4 Exhaust Monitoring REPRODUCED IN ANY MANNER NOR DISCLOSED TO THIRD PARTIES
WITHOUT WRITTEN PERMISSION OF GENERAL ELECTRIC COMPANY.

Left Bank Left


EGT Plug EGT Harness
Wireway
(EGT) ECP PLC A

1 (A) EGT1-
M4-22 Left1
L1Temp
2 (B) Cylinder Temp ECU
EGT1+
M4-20 (ECU-A) TBE1-142
2 (J) PTLT+ PTL+
6-30 (SIG+)
1 (C) PTLTemp
EGT2- TBE1-143 LEFT PRE-TURBO
L2Temp M4-6 Left2 1 (D) PTLT- PTL-
6-34 (SIG-) TEMPERATURE
2 (D) EGT2+ Cylinder Temp
M4-4 TBE1-144
PTLSHD
6-29 (SHD)
1 (J) PTLT SHLD
EGT3- Left3
L3Temp M4-26
Cylinder Temp TBE1-145 B
2 (H) EGT3+ 2 (B) PTRT+ PTR+
6-31 (SIG+)
M4-24 PTRTemp
TBE1-146 RIGHT PRE-TURBO
1 1 (A) PTRT- PTR-
(G) EGT4- 6-35 (SIG-) TEMPERATURE
M4-10 Left4
L4Temp TBE1-147
2 (F) Cylinder Temp PTRSHD
EGT4+ 6-36 (SHD)
M4-8
PTRT SHLD
TBE1-80
1 (E) EGT5- M4-30 (U) TCMP+ TCMP+
Left5 6-10 (SIG+)
L5Temp
2 Cylinder Temp TBE1-81
(K) EGT5+ THERMOCOUPLE
M4-28 TCMP- TCMP-
6-11 (SIG-) COMPENSATION
1 TBE1-82
(L) EGT6- M4-14 Left6 TCMPSHD
6-12 (SHD) C
L6Temp Cylinder Temp
2 (M) EGT6+ TCMP SHLD
M4-12

1 (N) EGT7- M4-34 Left7*


L7Temp* 2 (P) Cylinder Temp
EGT7+
M4-32

1 (Q) EGT8- M4-18 Left8*


L8Temp* (V) Cylinder Temp
2 EGT8+
M4-16 D

Right
Right Bank EGT Plug
Wireway EGT Harness
(EGT)
1 (A) EGT1-
M5-22 Right1
R1Temp
2 (B) EGT1+ Cylinder Temp
M5-20

1 (C) EGT2- E

M5-6 Right2
R2Temp
2 (D) EGT2+ Cylinder Temp
M5-4

1 (J) EGT3-
R3Temp M5-26 Right3
2 (H) EGT3+ Cylinder Temp
M5-24
1 (G) EGT4-
M5-10 Right4
R4Temp
2 (F) EGT4+ Cylinder Temp
M5-8 F

1 (E) EGT5-
M5-30 Right5
R5Temp
2 (K) EGT5+ Cylinder Temp
M5-28
1 (L) EGT6-
M5-14 Right6
R6Temp
2 (M) EGT6+ Cylinder Temp
M5-12

1 (N) EGT7- M5-34 Right7*


R7Temp* Cylinder Temp G
2 (P) EGT7+
M5-32

1 (Q) EGT8- M5-18 Righty8*


R8Temp* Cylinder Temp
2 (V) EGT8+
M5-16

* 16V228 and 16V250 only


H

0 1 2 3 4 5 6 7 8 9 SECT D4
0 CO-149467 January 2013 B CO-164146 January 2015
REVISIONS
TITLE SCHEMATIC DIAGRAM MADE BY E. SADER 01.25.2013 APPROVAL STATIONARY ERIE 84B540865AB
PLANT
A CO-153582 July 2013 FIRST MADE FOR STANDARD UNENCLOSED GENSET ISSUE
E. SADER
GENERAL ELECTRIC CO. CONT ON SHT 23 SHT 22
RC
THIS DRAWING, WHICH CONTAINS PROPRIETARY INFORMATION, IS
84B540865AB THE PROPERTY OF GENERAL ELECTRIC COMPANY. IT SHALL NOT BE

CONT ON SHT 24 SHT 23 GenSet SECT E Control Power Distribution REPRODUCED IN ANY MANNER NOR DISCLOSED TO THIRD PARTIES
WITHOUT WRITTEN PERMISSION OF GENERAL ELECTRIC COMPANY.

GCP ECP
PDB+
BC24V+ 24G 24E
Battery 24 VDC + A
24G1 24E1
1 1

GCP CB1 ECP CB1

2 2

24GCP4 24ECP1 24ECP4


24GCP1
24GCP2 24ECP2
24GCP3 24ECP3

TBG1-24A TBG1-24A TBE1-24A TBE1-24A


TBG1-24A TBE1-24A
24G_11 24G_12 24G_22 24G_27 24G_31 M2-A18 24E_11 24E_12 24E_21 24E_31 24E_32 M6-1
P&SC 1 M1(+) (sh.10) WDR-11 WDR-21 (sh.10) M4-A18 24G_32 (sh.24) EMS PS 1-C M0(+) (sh.18) ELRR-11 M6-11 B

24G_13 24G_14 DPC-A2 (sh.10) BLR-11 24G_24 24G_23 CBR-21 (sh.10) (sh.14) EPHR-11 24G_40 24G_33 M3-A18 24E_24 SR-11 (sh.18)
ES-V1(+)
TBG1-24A TBG1-24A TBG1-24A TBE1-24A TBE1-24A TBE1-24A
24G_301A MCC24 24G_26 24G_41 24E_25 24_EFR-FD 24E_SAP
(sh.14) BC-COM MCC-24VDC (sh.10) P&SC-3 (sh.14) EPHR-21 (sh.18) TBE1-124 (sh.18) EFR-31 TBE1-136 (sh.20)
24G_HMI GE-24L 24GCP5 24GCP6 (sh.20) TBE1-89 24E_27 24E_28
HMI(+) DCLB-875 (sh.10) DPC-C1 DPC-C3 (sh.10) TBE1-46 (sh.19)
TBG1-24A TBG1-24A TBG1-24A TBE1-24A TBE1-24A TBE1-24A
24G_302 GE-24L1 24GCP7 24GCP8 24E_29 24E_210 24E_DAIP
(sh.16) FDS-C DCLB-885 (sh.10) DPC-C5 DPC-C7 (sh.10) ECU 5-5 TBE1-95 (sh.20) (sh.20) TBE1-140
24_SWG 24GCP9 24E_211 24E_212
(sh.10) DPC-C9 ECU 5-11 ECU 5-16
SG+24V
TBG1-24A TBG1-24A TBE1-24A TBE1-24A
TBG1-24A 24G_214 24G_213 24E_213 24E_214
(sh.10) SS-3A CS-3A (sh.10) ECU 5-23 ECU 5-24
C
24G_216 24G_215 24_IPC 24E_215 24E_217
(sh.10) SDR-11 SS-1A (sh.10) (sh.10) CBR-11 (sh.14) F1E-1 F3E-1 (sh.14)
TBG1-24A TBG1-24A TBE1-24A TBE1-24A
24G_218 24G_217 24_IPP 24_NGRST (sh.14) F2E-1 24E_216 24E_218
(sh.10) GCESPB-3A CS-3B (sh.10) (sh.10) PRR-21 TBG1-21 (sh.8) F4E-1 (sh.14)

24G_220 24G_219 24_AVRAL 24E_219 24E_222


(sh.10) P&SC-54 CBR-41 (sh.10) (sh.8) TBG1-23 (sh.14) F5E-1 TBE1-130 (sh.18)
TBG1-24A TBG1-24A TBE1-24A TBE1-24A
24G_222 24G_28 24E_301 24E_302 ECESPB-3A (sh.10)
(sh.10) P&SC-43 P&SC-12 (sh.10) (sh.10) EFR-21
24G_223 24E_303 24E_22
(sh.10) P&SC-15 (sh.10) TBE1-160 TBE1-33
TBG1-24A TBG1-24A TBE1-24A
TBE1-24A

VFANR3 VFANR2
VFR3-A1 VFR2-A1
TBG1-2A
VFANR1
VFR1-A1
FANR15 FANR16
RFR15-A1 RFR16-A1
TBG1-2A
FANR13 FANR14
RFR13-A1 RFR14-A1
E
FANR11 FANR12 2E_LM12 2E_LM22
RFR11-A1 RFR12-A1 (sh.14) TBE1-167 TBE1-169 (sh.14)
TBG1-2A TBE1-2A TBE1-2A
TBG1-2A TBG1-2A
FANR9 FANR10 2E_LM32 2E_LM42
RFR9-A1 RFR10-A1 (sh.14) TBE1-171 TBE1-173 (sh.14)
FANR7 FANR8 2ECP4 2E_LM212
RFR7-A1 RFR8-A1 (sh.14) LMR2-A1 (sh.14) TBE1-175

TBG1-2A TBG1-2A TBG1-2A TBE1-2A TBE1-2A


FANR5 FANR6 (sh.14) LMR1-A1
2ECP5
RFR5-A1 RFR6-A1 Breaker
FANR3 2G_218 2G_217 Breaker IPC_C IPB_C Open Lamp- 2E_217
FANR4 TBE1-135 (sh.18)
RFR3-A1 RFR4-A1 (sh.10) P&SC-28 P&SC-56 (sh.10) Close Lamp- Common Return (sh.10)
TBG1-2A (sh.10) Common Return TBG1-2A TBE1-2A TBE1-2A
TBG1-2A Processor not
FANR1 FANR2 2G_216 IPP_C 2E_215
RFR1-A1 RFR2-A1 (sh.14) EFPR-A1 running Lamp- ERR-A1 (sh.18)
Common Return (sh.10)
2G_214 2G_213 2GCP5 2E_214 2E_213 F
(sh.14) EPLR-A1 VFR3-A1 (sh.13) (sh.10) DPC-C17 (sh.18) EFR-A1 ECU 5-14 (sh.18)
TBG1-2A TBG1-2A TBG1-2A TBE1-2A TBE1-2A
2G_212 2G_211 2E_212 2E_211
(sh.14) EPHR-A1 CR-A1 (sh.10) (sh.18) ECU 5-13 ECU 5-12 (sh.18)
2G_SWG 2G_210 2G_40 2G_39 2E_210 2E_29
(sh.10) TR-A1 (sh.14) TBG1-90 M3-A17 (sh.18) ECU 5-4 ECU 5-3 (sh.18)
SG-24V
TBG1-2A TBG1-2A TBG1-2A TBE1-2A TBE1-2A TBE1-2A
GE-2L 2G_28 2G_27 2G_38 2G_37 2E_28 2E_27 2E_SAP 2SAP-
DCLB-2 (sh.10) SDR-A1 WDR-A1 (sh.10) M4-A17 M2-A17 (sh.18) ECU 5-15 ECU 5-2 (sh.18) (sh.20) M3-18 M3-17
2G_13 GE2L1 2G_25 2G_36 2G_35 2E_36 2E_35
ES-V1(-) DCLB-2 BLR-A1 (sh.10) M4-B18 M4-B17 M7-36 M7-27
TBG1-2A TBG1-2A TBG1-2A TBE1-2A TBE1-2A TBE1-2A
2G_14 2G_24 2G_23 2G_34 2G_33 2E_24 2E_34 2E_33
2G_HMI
HMI(-) DPC-A3 (sh.10) PRR-A1 VRSR-A1 (sh.10) M3-B18 M3-B17 ECU 5-20 M7-18 M7-9
2G_11 2G_12 2G_22 2G_32 2G_31 2E_11 2E_12 2E_22 2E_21 2E_32 2E_31
P&SC 2 (sh.10) NGRR-A1 M2-B18 (sh.24) EMS PS 1-D M6-20
M1(-) M2-B17 M0(-) (sh.18) ELRR-A1 SR-A1 (sh.18) M6-10 G
TBG1-2A TBG1-2A TBE1-2A TBE1-2A
TBG1-2A TBE1-2A

2GCP3 2ECP3 2ECP4


2GCP1 2GCP4 2ECP1
2GCP2 2ECP2

2 2

GCP CB2 ECP CB2

1 1
2G 2E
Battery 24 VDC - H
BC24V- 2G1 2E1

PDB-

0 1 2 3 4 5 6 7 8 9
SECT E
0 CO-149467 January 2013 B CO-164146 January 2015
TITLE SCHEMATIC DIAGRAM MADE BY E. SADER 01.25.2013 APPROVAL STATIONARY ERIE 84B540865AB
REVISIONS
PLANT
A CO-153582 July 2013 FIRST MADE FOR STANDARD UNENCLOSED GENSET ISSUE
E. SADER
GENERAL ELECTRIC CO. CONT ON SHT 24 SHT 23
RC
THIS DRAWING, WHICH CONTAINS PROPRIETARY INFORMATION, IS
84B540865AB THE PROPERTY OF GENERAL ELECTRIC COMPANY. IT SHALL NOT BE

CONT ON SHT 25 SHT 24 GenSet SECT E1 EMS Control Power Distribution REPRODUCED IN ANY MANNER NOR DISCLOSED TO THIRD PARTIES
WITHOUT WRITTEN PERMISSION OF GENERAL ELECTRIC COMPANY.

EMS POWER SUPPLY CFD


EMSPS (SDIS)
48R1
P-3 (-)
(-)
2-D
48V
48V
TBE1-141 INPUT
OUTPUT 48P1 48P2
2-C P-1 (+)
(+)
ECP CB3
1 2
48P3 48P4
P-2 CONTROL
TBE1-24A
CFDGND D

1-C (+) GND


E-B5
24E_11 24V
TBE1-2A INPUT
E-G5 1-D
2E_11 (-)
ECU
28P1 1 2
2-A 28P2
P-1
(+) ECP CB4 (+)
28P3 28P4
2-J P-2
28V 28V
OUTPUT 28N1 INPUT E

2-K P-3
(-) 28N2 (-)
2-M P-4
EMSGND
GND

0 1 2 3 4 5 6 7 8 9 SECT E1
0 CO-149467 January 2013
REVISIONS TITLE SCHEMATIC DIAGRAM MADE BY E. SADER 01.25.2013 APPROVAL STATIONARY ERIE 84B540865AB
PLANT
A CO-153582 July 2013 FIRST MADE FOR STANDARD UNENCLOSED GENSET ISSUE
E. SADER
GENERAL ELECTRIC CO. CONT ON SHT 25 SHT 24
RC
THIS DRAWING, WHICH CONTAINS PROPRIETARY INFORMATION, IS
84B540865AB THE PROPERTY OF GENERAL ELECTRIC COMPANY. IT SHALL NOT BE

CONT ON SHT 26 SHT 25 GenSet SECT E2 Control Communication Network REPRODUCED IN ANY MANNER NOR DISCLOSED TO THIRD PARTIES
WITHOUT WRITTEN PERMISSION OF GENERAL ELECTRIC COMPANY.

ECP PLC
M9
PORT B
GCP B

ETHERNET SWITCH
ES

ECU
CFD (SDIS)
HMI
1CAT 5 84A216808P191 84A216072P182
PORT A PORT 1 PORT 5 CH2 ECU B C

ETHERNET
HMIGND
5CAT 5
GND
84A216072P181
PORT A
CH3
ETHERNET
84A216072P180 D
ECP PLC PORT B ECU A
M9 2CAT 5
PORT 2 PORT 6
PORT A
EPLCG
GND

GCP PLC P&SC


3CAT 5
M0 7CAT 5
PORT 3 PORT 7 PORT A
PORT A
GPLCG
GND
F

OFFBOARD
8CAT 5 N
PORT 4 PORT 8 PORT A
G

GND ES GND

0 1 2 3 4 5 6 7 8 9 SECT E2
0 CO-149467 January 2013
REVISIONS TITLE SCHEMATIC DIAGRAM MADE BY E. SADER 01.25.2013 APPROVAL STATIONARY ERIE 84B540865AB
PLANT
A CO-153582 July 2013 FIRST MADE FOR STANDARD UNENCLOSED GENSET ISSUE
E. SADER
GENERAL ELECTRIC CO. CONT ON SHT 26 SHT 25
RC
THIS DRAWING, WHICH CONTAINS PROPRIETARY INFORMATION, IS
84B540865AB THE PROPERTY OF GENERAL ELECTRIC COMPANY. IT SHALL NOT BE

CONT ON SHT 33 SHT 32 Relay Locations SECT H Relay Locations REPRODUCED IN ANY MANNER NOR DISCLOSED TO THIRD PARTIES
WITHOUT WRITTEN PERMISSION OF GENERAL ELECTRIC COMPANY.

Device Coil GenSet


Name Description Part Number Ohms Loc Coil Pole1 Pole2 Pole3 Pole4 Pole5
BLR Base Load Relay 700-HL-T22Z24 GCP B2-H4 B2-B4
CBR Circuit Breaker Relay IDECRU4S-D-D24 GCP B-E8 B2-D8 B2-E1 B2-C4
CR Close Relay 700-HL-T22Z24 GCP B2-F8 B-E4
EFPR Engine Fuel Prime Relay 700-HL-T22Z24 GCP C2-C5 C2-F5 B

EFR Engine Fail Relay IDECRU4S-D-24 ECP D-G6 D-B3 B2-B7 D-B0
ELRR Engine Local/Remote Relay 700-HL-T22Z24 ECP D-D2 D-F3
EPHR Engine Pre Heat Relay 700-HL-T22Z24 GCP C2-C8 C2-E5 C2-E8
EPLR Engine Pre Lube Relay 700-HL-T22Z24 GCP C2-C8 C2-F5
ERR Engine Run Relay 700-HL-T22Z24 ECP D-H6 D-B8
LMR1 Louver Motor1 Relay IDECRU4S-D-24 ECP C2-B2 C

LMR2 Louver Motor2 Relay 700-HL-T22Z24 ECP C2-B2


PRR Processor Running Relay 700-HL-T22Z24 GCP B2-G4 B2-D9
RFR1 Radfan1 Relay 700-HL-T22Z24 GCP C1-A2 C1-F4
RFR10 Radfan10 Relay 700-HL-T22Z24 GCP C1-D2 C1-D4
RFR11 Radfan11 Relay 700-HL-T22Z24 GCP C1-E2 C1-E4
D
RFR12 Radfan12 Relay 700-HL-T22Z24 GCP C1-E2 C1-E4
RFR13 Radfan13 Relay 700-HL-T22Z24 GCP C1-E2 C1-E4
RFR14 Radfan14 Relay 700-HL-T22Z24 GCP C1-F2 C1-F4
RFR15 Radfan15 Relay 700-HL-T22Z24 GCP C1-F2 C1-F4
RFR16 Radfan16 Relay 700-HL-T22Z24 GCP C1-F2 C1-G4
RFR2 Radfan2 Relay 700-HL-T22Z24 GCP C1-B2 C1-A4
E

RFR3 Radfan3 Relay 700-HL-T22Z24 GCP C1-B2 C1-B4


RFR4 Radfan4 Relay 700-HL-T22Z24 GCP C1-B2 C1-B4
RFR5 Radfan5 Relay 700-HL-T22Z24 GCP C1-C2 C1-C4
RFR6 Radfan6 Relay 700-HL-T22Z24 GCP C1-C2 C1-C4
RFR7 Radfan7 Relay 700-HL-T22Z24 GCP C1-C2 C1-C4
RFR8 Radfan8 Relay 700-HL-T22Z24 GCP C1-D2 C1-D4 F

RFR9 Radfan9 Relay 700-HL-T22Z24 GCP C1-D2 C1-D4


SDR Shut Down Relay 700-HL-T22Z24 GCP B2-A7 B2-C7
SR Start Relay 700-HL-T22Z24 ECP D-D2 D-B8
TR Trip Relay 700-HL-T22Z24 GCP B2-A8 B-E4
VFR1 VentFan1 Relay 700-HL-T22Z24 GCP C1-G2 C1-G4
VFR2 VentFan2 Relay 700-HL-T22Z24 GCP C1-G2 C1-G4 G

VFR3 VentFan3 Relay 700-HL-T22Z24 GCP C1-G2 C1-H4


VRSR Voltage Regulator Speed Relay 700-HL-T22Z24 GCP B2-G4 B-E1 B-E1
WDR Watch Dog Relay 700-HL-T22Z24 GCP B2-D6 B2-D1 B2-C6
NGRR Neutral Ground Relay 700-HL-T22Z24 GCP B2-G4 B-G2 B-G2

0 1 2 3 4 5 6 7 8 9
SECT H
0 CO-149467 January 2013 B CO-164146 January 2015
REVISIONS

TITLE SCHEMATIC DIAGRAM MADE BY E. SADER 01.25.2013 APPROVAL STATIONARY ERIE 84B540865AB
PLANT
A CO-153582 July 2013
FIRST MADE FOR STANDARD UNENCLOSED GENSET ISSUE
E. SADER
GENERAL ELECTRIC CO. CONT ON SHT 33 SHT 32
RC
THIS DRAWING, WHICH CONTAINS PROPRIETARY INFORMATION, IS
84B540865AB THE PROPERTY OF GENERAL ELECTRIC COMPANY. IT SHALL NOT BE

CONT ON SHT 34 SHT 33 Device Table SECT J Device Table REPRODUCED IN ANY MANNER NOR DISCLOSED TO THIRD PARTIES
WITHOUT WRITTEN PERMISSION OF GENERAL ELECTRIC COMPANY.

Device Name Description Part Number GenSet Location Schematic Location Device Name Description Part Number GenSet Location Schematic Location
ADEBT Alternator Drive End Temperature Sensor later Alternator Asm B3 Gauge Panel Engine Gauge Panel (optional) later Engine Acc Rack C3, G A

AC Air Compressor 84A213514ACP1 Enclosure C GCP CB1/CB2 Circuit Breaker, 15 Amp Altec Corp 2B15UM (or equivalent) GCP E
ALT Alternator various Baseframe B GCP PLC M0 PLC Ethernet Module GE Fanuc IC200EBI001 GCP E2
ANDEBT Alternator Non-Drive End Temperature Sensor later Alternator Asm B3 GCP PLC M1 PLC Power Supply GE Fanuc IC200PWR002 GCP E
APAT Alternator Ph A Temperature Sensor later Alternator Asm B3 GCP PLC M2 PLC Mixed Digital I/O Module GE Fanuc IC200MDD844 GCP B, B2, C1, C2, E
APBT Alternator Ph B Temperature Sensor later Alternator Asm B3 GCP PLC M3 PLC Mixed Digital I/O Module GE Fanuc IC200MDD844 GCP C1, C2, E
APCT Alternator Ph C Temperature Sensor later Alternator Asm B3 GCP PLC M4 PLC Mixed Digital I/O Module GE Fanuc IC200MDD844 GCP C1, C2, E
APS Air Pressure Switch later Air Compressor Asm C1 GCTs Generator CTs various Alternator Asm B
AVR Alternator Voltage Regulator BASLER DECS 100 GCP B, B2 GPTs Generator PTs various Alternator Asm B
GMCC Genset Motor Control Center Eaton RK510616Y005-0001 Enclosure C, C1, C2, C3, G
BATT Battery 84A230763BTP1 Enclosure G GND BAR Ground Bar Square D PK12GTA ECP E
BCH Battery Charger later Enclosure G GPESPB Emergency Stop Push Button GECR104PTR20AOR B
Gage Panel B2, D
BCTs BUS CTs various Switchgear Asm B GRD BAR Ground Bar Square D PK12GTA GCP
BLR Base Load Relay Allen Bradley 700-HL-T22Z24 GCP B2, E HFLS High Fuel Level Float Switch 84A225721AJP2 Fuel Float Asm D2
BPTs BUS PTs various Switchgear Asm B HHFLS High High Fuel Level Float Switch 84A225721AJP2 Fuel Float Asm D2
ICWP Intercooler Water Pressure Sensor 41A317303ACP3 Engine D2
C Breaker Closed Indication Lamp Dialight 812-0971 GCP B ICWT Intercooler Water Temperature Sensor 41A296328AAP12 Engine D2
CAP Crankcase Air Pressure Sensor 41A317303ACP8 Engine D1 HMI Human Machine Interface GE Fanuc IC754VSF15CTD-DH GCP E, E2
CBR Circuit Breaker Relay IDEC RU4S-D-D24 GCP B, B2, E HPPS Engine HPP Harness 84A222785P5260 ECP F, F1, F2, F3
CFD (SDIS) Common Function Display (Smart Display) GET 17FM804 ECP E1, E2 L1Temp --- L8Temp Left Cylinder Thermocouple Harness/Sensor 84A219911ABP31 Engine D4
CPS1 Crank Posit ion Sensor 1 41A296328BYP5 Engine D3 LHPPS Left High Pressure Fuel Pump Harness 84A219911ABP32 Engine
CPS2 Crank Posit ion Sensor 1 41A296328BYP5 Engine D3 LFLS Low Fuel Level Float Switch D2
84A225721AJP2 Fuel Float Asm
CR Close Relay Allen Bradley 700-HL-T22Z24 GCP B, B2 D2
LLFLS Low Low Fuel Level Float Switch 84A225721AJP2 Fuel Float Asm C
CS Close Switch GE CR104PSG86B GCP B2, E
LMR1 Louver Motor Relay 1 IDECRU4S-D-24 ECP C2, E
LV PANEL Low Voltage Panel later Enclosure
D1E-D2E Diode Assembly Allen Bradley 1492-LD4DF ECP Various Enclosure
LVR Asm1 Louver Assembly 1 later
D1G-D6G Diode Assembly Allen Bradley 1492-LD4DF GCP Various, B2
LVR Asm2 Louver Assembly 2 later Enclosure
DAIP1 Differential Air Inlet Pressure Sensor 84A219939P12 Engine D2, F, F1, F2, F3
LVR Asm3 Louver Assembly 3 later Enclosure
DFOP Differential Fuel Oil Pressure Sensor DWYER DXW-11-153 Engine D2, D4, F, F1, F2, F3 Enclosure
LVR Asm4 Louver Assembly 4 later
DLOP Differential Lube Oil Pressure Sensor 84A222258ABP121 Engine D1, F, F1, F2, F3 Engine Acc Rack D1, F, F1, F2, F3
LWLS1 Low Water Level Switch 1 41A300766P1
DPC Differential Protection Cont roller BASLER BE1-CDS220 GCP B, B1, E Engine Acc Rack
LWLS2 Low Water Level Switch 2 41A300766P1 D1, F, F1, F2, F3
ECP CB1/CB2 Circuit Breaker, 15 Amp Altec Corp 2B15UM (or equivalent) ECP E ECP C2, E
LMR2 Louver Motor Relay 2 Allen Bradley 700-HL-T22Z24
ECP CB3/CB4 Circuit Breaker, 15 Amp Altec Corp 2B15UM (or equivalent) ECP E1
41A317303ACP11 Engine D2, F, F1, F2, F3
ECP PLC M 0 PLC Power Supply GE Fanuc IC695PSD040 ECP MAP Manifold Air Pressure Sensor D
MAT Manifold Air Temperature Sensor 41A296328AAP14 Engine D2, F, F1, F2, F3
ECP PLC M 1, M 2 PLC CPU GE Fanuc IC695CPE310 ECP Various
MBT Main Bearing Temperature Harness 84A222785P5430 Engine F2, F3
ECP PLC M 3 PLC Analog Input M odule GE Fanuc IC695ALG600 ECP B3, D2, D3, E
MBTS1 --- 9 Main Bearing Temperature Sensor 84A221316P1 Engine D3, F2, F3
ECP PLC M 4 PLC Analog Input M odule GE Fanuc IC695ALG600 ECP D4
GCTN Neutral Ground CT 600/5 A part of alternator NGR B2
ECP PLC M 5 PLC Analog Input M odule GE Fanuc IC695ALG600 ECP D4
NGR Neutral Ground Resistor various (optional) NGR B
ECP PLC M 6 PLC Digit al Out put M odule GE Fanuc IC694M DL740 ECP C2, D, E
NGRR Neutral Ground Relay Allen Bradley 700-HL-T22Z24 GCP B, B2, E
ECP PLC M 7 PLC Digit al Input M odule GE Fanuc IC694M DL660 ECP C2, D1, D2, E
NGRC Neutral Ground Relay Controller later NGR B
ECP PLC M 8 PLC Analog Input M odule GE Fanuc IC695ALG600 ECP D3
O Breaker Open Indication Lamp Dialight 812-0972 GCP B
ECP PLC M9 PLC Ethernet Module GE Fanuc IC695ETM001 ECP E2
OLS Oil Level Switch later Air Compressor Asm C1
ECU Engine Control Unit GET 17FM737A1 ECP D, D1~D4, E, E1, E2, F, F1, F2, F3
P&SC Paralleling&Synchronizing Controller Deif GCP-3 (options: A1, A4, A5, C2, D1, EF2, N) GCP B, B2, E, E2
ECU-A Engine ECU-A Harness 84A222785P5060 ECP D, D3, D4, F, F1, F2, F3
PDB- 24 VDC Return Power Distribution Block Square D 9080LBA263106 GCP E
ECU-B Engine ECU-B Harness 84A222785P5160 ECP D1, F, F1, F2, F3 E
PDB+ 24 VDC Power Distribution Block Square D 9080LBA263106 GCP E
FES Engine Fluid Front Sensor Harness 84A219911ABP33 Engine
PLIT Processor Not Running Indication Lamp Dialight 812-0971 GCP
RES Engine Fluid Rear Sensor Harness 84A219911ABP37 Engine
Engine Fuel Prime Relay GCP C2, E PLP Pre Lube Pump later Engine Acc Rack C
EFPR Allen Bradley 700-HL-T22Z24
EFR Engine Fail Relay ECP B2, D, E PRR Processor Running Relay Allen Bradley 700-HL-T22Z24 GCP B2, E
IDECRU4S-D-24
Engine Fuel Pressure Sensor PTLTemp Pre Turbo Left Temperature Sensor 41A296328BMP21 Engine D4
EFP 41A317303ACP19 Engine D2, F, F1, F2, F3
Engine Fuel Temperature Sensor Engine PTRTemp Pre Turbo Right Temperature Sensor 41A296328BMP22 Engine D4
EFT 41A296328AAP15 D1, F, F1, F2, F3
Engine Gas Temperature Harness R1E Resistor, 200 Ohm Allen Bradley 1492-LD4RB201 ECP D
EGT 84A222785P5460 ECP D4, F, F1, F2, F3
Engine Lube Oil Inlet Pressure Engine D1, F, F1, F2, F3 R1G Resistor, 200 Ohm Allen Bradley 1492-LD4RB201 GCP
ELIP 41A317303ACP19
R1TEMP --- R8TEMP Right Cylinder Thermocouple Harness/Sensor 84A219911ABP31 Engine D4
ELIT Engine Lube Oil Inlet Temperat ure 41A296328AAP12 Engine
Engine Lube Oil Temperat ure Sensor Engine D1 RHPPS Right High Pressure Fuel Pump Harness 84A219911ABP32 Engine D
ELOT 41A296328AAP12
ELPP Engine Lube Oil Pump Pressure Sensor 41A317303ACP19 Engine D1 SSC Synchroscope later GCP B, B1 F

ELRR Engine Local/Remote Relay Allen Bradley 700-HL-T22Z24 ECP D, E


EMSPS Engine Management System Power Supply GET 84A224283CBP3 ECP E, E1
EPHR Engine Pre-Heat Relay Allen Bradley 700-HL-T22Z24 GCP C2, E
EPLR Engine Pre-Lube Relay Allen Bradley 700-HL-T22Z24 GCP C2, E
EPS Engine Position Sensor (V228 only) later Engine D3
ERR Engine Run Relay Allen Bradley 700-HL-T22Z24 ECP D, E
ES Ethernet Switch Phoenix Contract FL SWITCH SFN 8TX 2891929 GCP E, E2
EEESPB Emergency Stop Push Button GE CR104PTR20AOR, CR104PXG15 GCP B2, D
ECESPB Emergency Stop Push Button GE CR104PTR20AOR, CR104PXG15 ECP B2, D, E
EWIP Engine Water Inlet Pressure Sensor 41A317303ACP3 Engine D1, F,F1, F2, F3
G
EWiT Engine Water Inlet Temperature Sensor 41A296328AAP12 Engine
D1
EWOT Engine Water Outlet Temperat ure Sensor 41A296328AAP12 Engine D1, F, F1, F2, F3
F1E---F5E Fuse Asm/ Fuse 5 A Allen Bradley 1492-FB1C30-L, Bussman LP-CC-5 ECP C2
F1G-F6G Fuse Asm/ Fuse 2 A Allen Bradley 1492-FB1C30-L, Bussman LP-CC-2 GCP B
FLDS Fuel Leak Detector Float Switch later Fuel Float Asm D2, D4
FPH Fluid Pre-Heater MAG PLUS 846390-106 Engine Acc Rack C, C2
FPP Fuel Priming Pump (optional) later Engine Acc Rack C
FDS Fire Detection System later
Enclosure E, G
F7G, F8G Fuse Asm/ Fuse 10 A Allen Bradley 1492-FB1M30-L, Bussman KTK10 GCP B
F9G-F10G Fuse Asm/ Fuse 10 A Allen Bradley 1492-FB1C30-L, Bussman LP-CC-10 GCP C4
H
GCESPB Emergency Stop Push Button GE CR104PTR20AOR, CR104PXG15 GCP B, B2

0 1 2 3 4 5 6 7 8 9 SECT J
0 CO-149467 January 2013 B CO-164146 January 2015 REVISIONS

TITLE SCHEMATIC DIAGRAM MADE BY E. SADER 01.25.2013 APPROVAL


STATIONARY
ERIE 84B540865AB
PLANT
A CO-153582 July 2013 C CO-172854 April 2016
FIRST MADE FOR STANDARD UNENCLOSED GENSET ISSUE
E. SADER
GENERAL ELECTRIC CO. CONT ON SHT 34 SHT 33
RC
THIS DRAWING, WHICH CONTAINS PROPRIETARY INFORMATION, IS
84B540865AB THE PROPERTY OF GENERAL ELECTRIC COMPANY. IT SHALL NOT BE

CONT ON SHT F SHT 34 Device Table SECT J1 Device Table REPRODUCED IN ANY MANNER NOR DISCLOSED TO THIRD PARTIES
WITHOUT WRITTEN PERMISSION OF GENERAL ELECTRIC COMPANY.

Device Name Description Part Number GenSet Location Schematic Location


A
RF1---16 Radfan1-16 later Radiator Asm C
RFR1---16 RadFan1-16 Relay Allen Bradley 700-HL-T22Z24 GCP C1, E
SAP System Air Pressure Sensor 84A213165AMP26 ECP D2

SDR Shut Down Relay Allen Bradley 700-HL-T22Z24 GCP B2, E


SG Switchgear various (optional) Enclosure B, E
SR Engine Start Relay Allen Bradley 700-HL-T22Z24 ECP D, E
SSOL Start Solenoid later Air Start Motor (ASM) D
SS Synchroscope Switch GE CR104PSG21B EOP B2, E
Stationary Stationary Genset Harness 84A222785P5560 ECP F, F1, F2, F3
STB1-1--4 Shorting Terminal Board 1 Bussman TB300-4 GCP B B

STB2-1--4 Shorting terminal Board 2 Bussman TB300-4 GCP B


STB3-1--2 Shorting Terminal Board 3 Bussman TB300-2 GCP B
STB4-1--2 Shorting Terminal Board 4 Bussman TB300-2 GCP B
TBE1-1---n Terminal Block, ECP Allen Bradley 1492-L3Q ECP B2, B3, C2, C3, D, D1~D4, E, E1
TBG1-1---n Terminal Block, GCP Allen Bradley 1492-L3Q GCP B, B2, C1, C2, D, E
TCMP Thermocouple Compensation Sensor 41A296328BMP18 Engine
TR Trip Relay Allen Bradley 700-HL-T22Z24 GCP B, B2, E
TSL Turbo Speed Sensor Left 41A296328BZP5 Engine D3
TSR Turbo Speed Sensor Right 41A296328BZP5 Engine D3

Enclosure C
VF1---3 Ventfan1-3 84A225721AGP1 C
VFR1---3 VentFan 1-3 Relay Allen Bradley 700-HL-T22Z24 GCP C1, E
VRSR Voltage Regulator Speed Relay Allen Bradley 700-HL-T22Z24 GCP B, B2, E

WDR W atchDog Relay Allen Bradley 700-HL-T22Z24 GCP B2, E

0 1 2 3 4 5 6 7 8 9
SECT J1
0 CO-149467 January 2013 B CO-164146 January 2015 REVISIONS

TITLE SCHEMATIC DIAGRAM MADE BY E. SADER 01.25.2013 APPROVAL STATIONARY ERIE 84B540865AB
PLANT
A CO-153582 July 2013 FIRST MADE FOR STANDARD UNENCLOSED GENSET ISSUE
E. SADER
GENERAL ELECTRIC CO. CONT ON SHT F SHT 34