Академический Документы
Профессиональный Документы
Культура Документы
CONCENTRATE STORAGE BUILDING DUST COLLECTOR - ZERO SPEED SENSOR INSTRUMENT DATA SHEET
EQUIP NO. 0530-SSL-53082A & 0530-SSL-53082B
CHANGES
REVIEW DATE DESCRIPTION
A 2019-02-26 For Internal review
B 2019-03-05 Issued For Customer Review
B1 2019-06-03 For Internal review
APPROVAL
DESCRIPTION NAME ROLE DATE SIGNATURE
Prepared by J. HERRERA Project Engineer 2019-06-03
Review by A. VARGAS Engineering Manager 2019-06-03
Approved by R. ORDENES Project Manager 2019-06-03
FEATURES: -
001 Stopped motion detection - YES
002 Totally sealed contruccion (submersible) - YES
003 Microprocessor Accuracy - YES
004 LED Indication - YES
TECHNICAL SPECIFICATIONS
005 Power Supply V 24-240 VAC/VDC
006 Switching Capacity mA 200 Maximum
007 Saturation Voltage V 8 Maximum (Output On)
008 Leakage Current mA 1.6 Maximum (Output Off)
009 Operating Temperature °C -25 to 70
010 Relative Humidity % 90 RH
- Ferrous Target - 5/16 Inch Maximum
011 Sensing Range
- Non-Ferrous Target - 3/16 Maximum
012 Enclosure - Nylon ISO Thread 18mm by 1 mm
013 Cable m 2 2 Conductor
- Normally Closed (Volt Drop 8 Volts Max.)
014 Output State
- Normally Open (Leakage current 1.6 Max.)
015 Input Pulse Range ppm 20 to 2000 Maximum
016 Start Up Delay s 4
017 Trip Point - YES Stopped motion if no input
- Red (input) Target sensed
018 LED Indicators (2)
- Green (Output) Closed Circuit
019 Protection - IP67
CSA Class II Division 1 Group E,F and G (USA & Canada) ATEX
020 Approvals -
& CE Versions Avaible (Europe)
MANUFACTURER'S DATA
021 Manufacturer - 4B Components Limited
022 Model N° - M100
023 Part Number - M1001V10F
CONCENTRATE STORAGE BUILDING DUST COLLECTOR - LOW/HIGH LEVEL SENSOR INSTRUMENT DATA SHEET
EQUIP NO. 0530-LSL-53083A, 0530-LSL-53083B, 0530-LSH-53084A & 0530-LSH-53084B
CHANGES
REVIEW DATE DESCRIPTION
A 2019-02-26 For Internal review
B 2019-03-05 Issued For Customer Review
B1 2019-06-03 For Internal review
APPROVAL
DESCRIPTION NAME ROLE DATE SIGNATURE
Prepared by J. HERRERA Project Engineer 2019-06-03
Review by A. VARGAS Engineering Manager 2019-06-03
Approved by R. ORDENES Project Manager 2019-06-03
TECHNICAL DATA
001 Housing - NEMA Type 4/4X Aluminium IP 66
002 Process Temperature Range °C -40 to 600
003 Pressure Range bar -0.9 to 10
004 Sensivity g/I min. 15 Adjustable in 3 settings
G 1(1/4)"
G 1(1/2)"
005 Process Connection - NPT 1(1/2)" Other flanges avaibles
Triclamp 2"
Flange DN100 PN16
006 1.4305(303)
007 1.4301(304)
Process Connection Material - Aluminium o Stainless Steel
008 1.4541(321L)
009 1.4404(316L)
010 1.4301(SS304)
011 Measuring Vane/Shaft Material - 1.4305(303) Aluminium o Stainless Steel
012 1.4404(316L)
optional in optional in stainless
013 Bearing/Seal - Dust-proof ball-bearing steel or radial shaft seal in in
NBR rubber, FPM or PTFE
V 24/48/115/230 AC
014 Supply Voltage
V 24 DC
Relay SPDT contact
015 Signal Output - Microswitch
Relay DPDT contact
016 Functional safety - SIL 2
with universal voltage
017 Switchable Signal Output - FSH/FSL electronics integrated; with AC
Electronics as avaible option
with universal electronics is an
018 Signal Delay - YES integrated adjustable time delay
of the signal output
Monitoring of
Optional fur universal
019 motor/transmission/electronics/
Voltage
Fail Safe Alarm - power
ATEX, IEC-Ex, FM, CSA, INMETRO,
020 YES
Certificates - EHEDG
MANUFACTURER'S DATA
021 Manufacturer - UWT
022 Model N° - RN6004-E
023 Part Number - 60004AN11FQ1B3D
CONCENTRATE STORAGE BUILDING DUST COLLECTOR - VIBRATION SENSOR INSTRUMENT DATA SHEET
EQUIP NO. 0530-VSH-53081
CHANGES
REVIEW DATE DESCRIPTION
A 2019-02-26 For Internal review
B 2019-03-05 Issued For Customer Review
B1 2019-06-03 For Internal review
APPROVAL
DESCRIPTION NAME ROLE DATE SIGNATURE
Prepared by J. HERRERA Project Engineer 2019-06-03
Review by A. VARGAS Engineering Manager 2019-06-03
Approved by R. ORDENES Project Manager 2019-06-03
SPECIFICATIONS
001 Full-Scale Range in/sec 0.0-1.0 or 0.0-3.0 Field selectable
002 Frequency Response Hz 3-1000
003 Dual Set Point - Two customer selectable Field adjustable from 5 to
004 Time Delay s 0-20 Field Adjustable
005 Relays (Solid-State Triacs) - YES two solid-state relays rated
VAC 120-220
006 Input Power Customer Selectable
VDC 24
007 DC Analog Output mA 4-20 DC, proportional to overall
mV/in/sec 100 Field selectable, velocity
008 AC Signal Output
mV/g 100 (mV/in/sec) or Acceleration (
009 Temperature Range °C -31.67 to 71.1
010 Measurement Mode - Velocity
011 Housing - NEMA 4X
012 Weight Kg 2.5
013 the nema 4 and 4x 438a should be mounted using
MANUFACTURER'S DATA
014 Manufacturer - VITEC
015 Model N° - 438A
016 Part Number - 438A
CONCENTRATE STORAGE BUILDING DUST COLLECTOR - LOW PRESSURE SENSOR INSTRUMENT DATA SHEET
EQUIP NO. 0530-PSL-53089
CHANGES
REVIEW DATE DESCRIPTION
A 2019-02-26 For Internal review
B 2019-03-05 Issued For Customer Review
B1 2019-06-03 For Internal review
APPROVAL
DESCRIPTION NAME ROLE DATE SIGNATURE
Prepared by J. HERRERA Project Engineer 2019-06-03
Review by A. VARGAS Engineering Manager 2019-06-03
Approved by R. ORDENES Project Manager 2019-06-03
SPECIFICATIONS
Compatible Gases and
001 Service -
Liquids
002 Accuracy % 0.25 Full scale accuracy
003 Temperature Limit °C -18 to 93
004 Compensated Temperature Range °C -18 to 79
005 Thermal Effect % +/- 0.2 FS/°F (includes zero and span)
006 Pressure limits psi 0 to 150
Optional 4-1/2 digit LCD
007 Display -
field attachable display
10 to 35 VDC (for 4 to 20 mA
008 Power Requirement V 10 to 35
with -CB option)
009 Output Signal mA 4 to 20
010 Response Time ms 300
0 to 1250 Ohms max. Rmax =
011 Loop Resistance - YES 50(Vps-10) Ohms (4 to 20 mA
output with -CB option)
012 Stability % 1 FS/Year (typ)
maximum (for 4 to 20 mA
013 Current Consumption mA 38
output)
014 Housing - CB Conduit box housing
015 Electrical Connections - 1/2˝ female NPT conduit
016 Process Connections - 1/4˝ male NPT
017 Enclosure Rating - NEMA 4X
018 Weight g 283
Standard: CE; Optional:
001 Agency Approvals - YES NSF/ANSI 61/372, ANSI/UL 218,
ANSI/UL 508, NEPA 20
MANUFACTURER'S DATA
036 Manufacturer - Dwyer
037 Model N° - Series 626-CB
038 Part Number - 626-11-CB-P1-E5-S1
CONCENTRATE STORAGE BUILDING DUST COLLECTOR - BROKEN SLEEVE SENSOR INSTRUMENT DATA SHEET
EQUIP NO. 0530-XSX-53090
CHANGES
REVIEW DATE DESCRIPTION
A 2019-02-26 For Internal review
B 2019-03-05 Issued For Customer Review
B1 2019-06-03 For Internal review
APPROVAL
DESCRIPTION NAME ROLE DATE SIGNATURE
Prepared by J. HERRERA Project Engineer 2019-06-03
Review by A. VARGAS Engineering Manager 2019-06-03
Approved by R. ORDENES Project Manager 2019-06-03
KEY FEATURES:
6-Digit readout and lockable keypad (no trim pots or
001 - YES
knobs)
002 Convenient loop test and alarm setting features - YES
003 Removable electronics module - YES
TECHNICAL DATA
004 Resolution pA 0.5 Monitoring and Detection
005 Minimum Detection mg/m3 1-5
006 Process Pressure (Max) PSI 10
007 Process Temperature °C -20 to 232
008 Ambient Temperature °C -25 to 60
009 Hazardous Areas - Class II Div.II (Zone 22)
010 Power V Loop powered
011 Output mA 4-20
012 Wire un 2
013 Functionality - Standard
014 Probe Lenght (1/2 Duct Diameter) cm 30.5
015 Process Mount In 1.5 Quick Clamp
016 Process Mount Kit (optional) - YES
017 Sensor Additional - None
018 Enclosure - NEMA 4X
019 Approvals - Ordinary/General Porpuse
MANUFACTURER'S DATA
020 Manufacturer FilterSense
021 Model N° Dynacharge PM1
022 Part Number PM1-T
CONCENTRATE STORAGE BUILDING DUST COLLECTOR - DIFFERENTIAL PRESSURE SENSOR WITH INDICATOR
INSTRUMENT DATA SHEET
EQUIP NO. 0530-PDIT-53085
CHANGES
REVIEW DATE DESCRIPTION
A 2019-02-26 For Internal review
B 2019-03-05 Issued For Customer Review
B1 2019-06-03 For Internal review
APPROVAL
DESCRIPTION NAME ROLE DATE SIGNATURE
Prepared by J. HERRERA Project Engineer 2019-06-03
Review by A. VARGAS Engineering Manager 2019-06-03
Approved by R. ORDENES Project Manager 2019-06-03
SPECIFICATIONS
MANUFACTURER'S DATA
026 Manufacturer - Ametek
027 Model N° - Dustronix
028 Part Number - DNC-PS700-A10
CHANGES
REVIEW DATE DESCRIPTION
A 2019-02-26 For Internal review
B 2019-03-05 Issued For Customer Review
B1 2019-06-03 For Internal review
APPROVAL
DESCRIPTION NAME ROLE DATE SIGNATURE
Prepared by J. HERRERA Project Engineer 2019-06-03
Review by A. VARGAS Engineering Manager 2019-06-03
Approved by R. ORDENES Project Manager 2019-06-03