EtherNet/IP
Compatible Network Unit
NU-EP1
User’s Manual
Read this manual before using the product in order to
achieve maximum performance.
Keep this manual in a safe place for future reference.
Compatible with FS-N40 Series, FS-N10 Series,
LV-N10 Series, PS-N10 Series, AP-N10 Series,
LR-T Series, LR-W Series and FD-Q Series.
Introduction
This manual describes the basic operations and hardware functions of the NU-EP1. Read
the manual carefully to ensure safe performance and function of the NU-EP1.
Keep this manual in a safe place for future reference.
Ensure that the end user of this product receives this manual.
Symbols
The following symbols alert you to matters concerning the prevention of injury and product
damage.
DANGER
It indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
WARNING
It indicates a hazardous situation which, if not avoided, could result
in death or serious injury.
The system names and product names used in this manual are the trademark or
registered trademark of the respective companies.
EtherNet/IP is a trademark of ODVA. inc.
Safety Information for NU-EP1
General Precautions
Do not turn off the power while you are setting any item.
NOTICE
Doing this may cause loss of data settings.
704GB 1
Safety Information for NU-EP1
Equipment Environment
For safe, trouble-free operation of this product, the product must not be installed in the
following locations:
• Humid, dusty, or poorly ventilated.
• Exposed to direct sunlight or heat source.
• Exposed to corrosive or flammable gases.
• Exposed directly to vibration or shock.
• Exposed to water, oil, or chemical splashes.
• Exposed to static electricity.
Noise Protection
If this product is installed in a location near a noise source, e.g., power source or high-
voltage line, it may malfunction or fail because of noise. Take protective measures,
such as using a noise filter or running the cables separately.
UL Certificate
This product is an UL/C-UL Listed product.
• UL File No. E222809
• Category QUYX, QUYX7
Be sure to consider the following specifications when using this product as an UL/C-
UL Listed Product.
• Use this product with one of the following power supplies.
• UL/CSA certified power supply that provides Class 2 output as defined in the
NFPA70 (NEC: National Electrical Code) and CEC (Canadian Electrical Code).
• UL/CSA certified power supply that has been evaluated as a Limited Energy cir-
cuit as defined in UL61010-1 and CAN/CSA-C22.2 No. 61010-1.
• For wiring to the power supply connector, use the AWG 12-24 copper wire with
temperature rating 65 °C or more. The marking on the power supply connector
intends to warn this instruction.
• Use this product under pollution degree 2.
• Use this product at the altitude of 2000 m or less.
• Indoor use only.
Manuals related
to CPU unit
PLC CPU unit
EtherNet/IP unit
Manuals related to
EtherNet/IP unit
Sensor amplifiers
Manuals for each
sensor amplifier unit
1
This chapter provides an overview of the NU-EP1
Before Using and describes its part names and functions.
1
This chapter explains the procedures for connecting
2
Connection and sensor amplifiers to the NU-EP1 and how to
Configuration communicate.
2
This chapter explains the configuration of
5
This chapter provides the parameter list, as well as
Appendix
troubleshooting instructions.
5
Chapter 3 Communication
Chapter 4 Specifications
Chapter 5 Appendix
Term Description
Sensor A sensor amplifier
Scanner The EtherNet/IP scanner device
Adaptor The EtherNet/IP adaptor device
A sensor amplifier that has a power line and can operate
Main unit
alone
A sensor amplifier that does not have a power line and
Expansion unit
must be connected to a main unit
The name of KEYENCE's wiring-saving system for sensor
amplifiers
N-bus
The digital fiber sensor FS-N Series, etc., is supported
with this system
Programmable logic controller, an electronic device which
PLC
can freely control the devices by changing the programs
Ladder program A program which controls the PLC
1 Overview
communication, the ON/OFF output signals and current values of the sensors and
amplifiers connected to the NU-EP1 can be output to a PLC, etc.
The NU-EP1 supports EtherNet/IP cyclic communication (Implicit messaging) and
message communication (Explicit messaging). With cyclic communication, data can
be exchanged without ladder programs. With message communication, the sensor
amplifier's parameters can be read and written, and operation commands for the sen-
sor amplifier can be executed.
N-bus compatible
sensor amplifier
Before using the NU-EP1, verify that the following equipment and accessories are
included in the package.
We have thoroughly inspected the package contents before shipment. However, in 1
the event of defective or broken items, contact your nearest KEYENCE office.
Before Using
Package Contents
This section describes the part names and functions of the NU-EP1.
1
Before Using
Name Description
(1) RJ-45 connector Attach the network cable to this connector.
(2) Reset switch When held down for three seconds or longer, the
NU-EP1 settings will be reset to the default set-
tings.
(3) Link/activity indicator Normal: Green LED lights up or blinks
(green) For details, see "Troubleshooting" (page 5-3)
(4) Module status indicator
(green/red) Normal: Green LED lights up
(5) Network status indicator For details, see "Troubleshooting" (page 5-3)
(green/red)
(6) Sensor communication Indicates the communication status between NU-
indicator (green/red) EP1 and the sensor amplifier.
Normal: Green LED lights up
For details, see "Troubleshooting" (page 5-3)
(7) MAC address MAC address for the NU-EP1
(8) Power supply connector Attach the power connection cable to this connec-
tor.
(9) Sensor amplifier connector Attach the sensor amplifier to this connector.
A protective cover is attached when shipped from
the factory.
This section explains the steps for preparing to use the NU-EP1.
2. Wiring
Connecting the Communication Cable (page 2-6)
This chapter provides the procedures for installing the NU-EP1 on a DIN rail and con-
necting sensor amplifiers.
* If the NU-EN8N is installed, the green N-bus LED may not flash, even if the total
number of occupied IDs is more than 16.
Point Even if the number of occupied ID numbers does not exceed 16, the
number of connectable units may be restricted by conditions such
as the type of connected sensor amplifier or unit. For details, refer
to each sensor amplifier's specifications or the check the amount of
current which can be supplied from the NU-EP1 to the sensor
amplifier. ( "Specifications" (page 4-2))
This section explains the methods for connecting the sensor amplifier expansion unit
to the NU-EP1.
2 NOTICE Turn off the power before connecting the NU-EP1 and sensor amplifiers.
Connection and Configuration
1 Align the claw on the bottom of the NU-EP1 with the DIN rail. While push-
ing the amplifier in the direction of arrow (1), press down in the direction
of arrow (2).
(3)
(2)
(1)
Reference
To remove the NU-EP1, raise the amplifier in the direction of arrow
(3) while pushing the NU-EP1 in the direction of arrow (1).
If the sensor amplifier connector has an expansion protective cover, remove the
cover before connecting the amplifier.
NU-EP1
Expansion connector
Sensor amplifier
Point Ensure that the NU-EP1 and sensor amplifiers are connected
securely. If they are connected improperly or not inserted com-
pletely, they may be damaged when the power is turned on.
3 Mount the end units (OP-26751: a two-unit set shipped with the NU-EP1)
on both sides of the NU-EP1 and the sensor amplifier. Then, fix the end
units with the screws on the top of each end unit. (Tightening torque: 0.6
N•m or less)
Reference The power for each sensor amplifier is supplied from the NU-EP1.
NOTICE Always turn the power off before starting the wiring work.
Use the following procedures to connect the NU-EP1 to the communication cable
Connection and Configuration
Usable cables
The usable cable differs according to whether the system is structured with 10BASE-
T or 100BASE-TX.
2 Connect the modular jack on one end of the STP/UTP cable to the
10BASE-T/100BASE port on the Ethernet switch being used.
Insert the jack until a "click" is heard. The modular jack and connector port will
lock.
3 Connect the other modular jack of the STP/UTP cable to the NU-EP1 con-
nector port.
Insert the jack until a "click" is heard. The modular jack and connector port will
lock.
Power Supply
This section explains the method for supplying power to the NU-EP1.
In addition to supplying power from the power connector, power can be supplied from
2 the Ethernet port using the PoE (Power over Ethernet) function.
• Always supply the power with one of the following methods. For
example, do not supply from a PoE power sourcing equipment
Connection and Configuration
Reference The power to each sensor amplifier is supplied from the NU-EP1.
10 mm
Plug the connector into the NU-EP1 and secure it with the screws on each end.
(Tightening torque: 0.2 to 0.3 N•m)
The PoE function is used to supply power to the NU-EP1 from a PoE compatible
Ethernet switch, etc., over an STP cable or a Category 5 or higher UTP cable.
2 KV-EP21V
Connection and Configuration
Ver.2
TM
EtherNet/IP
Use the following configuration procedures for connecting the NU-EP1 to the Ether-
Net/IP system.
NU-EP1 Settings
The configuration of the NU-EP1 communication settings are explained below.
2
IP address settings
The IP address is set after wiring the NU-EP1 and supplying the power.
Devices, such as the NU-EP1, connected to the network and for which the IP
address has not been set will appear.
Click the [Scan EtherNet/IP devices (A)] button to display the devices for which
the IP address is set.
Point
- EtherNet/IP Compatible Network Unit NU-EP1 User's Manual - 2-11
2-4 Configuring Communication with NU-EP1
The network status indicator (NS) must be off (IP address not
assigned) to display "Not Set" for the IP address. To un-assign an IP
address, hold down the NU-EP1's reset switch for three seconds or
longer.
2
2 Select the device for which the IP address is to be set, and click on [Setup
IP addr.(I)]. [Setup IP addr.] will open.
Connection and Configuration
Set an IP address which is not currently used in "IP addr.(required)(I)", and click
on the [OK] button.
Reference Open IP addresses can be searched for by using the [Search available IP
addresses (F)] button.
Via Ethernet
This section explains the scanner configurations for connecting the NU-EP1 to the
EtherNet/IP system.
When communicating with an Allen-Bradley PLC (EtherNet/IP scanner), refer to the
"Procedures for Communicating with an Allen-Bradley ControlLogix PLC" (page 5-
7) for additional details.
2 Setting the Scanner
Connection and Configuration
The following settings are required when connecting the NU-EP1 to the EtherNet/IP
scanner.
Reference
This manual explains only the EtherNet/IP scanner functions and settings
required for communication with the NU-EP1. For details on the functions
and settings for the EtherNet/IP scanner or CPU unit, refer to the manuals
enclosed with the scanner or CPU unit.
2-14 - EtherNet/IP Compatible Network Unit NU-EP1 User's Manual -
Communication
This chapter explains the configuration of memory linked with the
EtherNet/IP unit, and the communication time chart. 3
3-1 What Is EtherNet/IP?.......................................... 3-2
3-2 NU-EP1 EtherNet/IP Communication Function......3-3
3-3 Cyclic Communication........................................ 3-6
3-4 Message Communication......................................3-24
3-5 Parameter List........................................................3-35
What Is EtherNet/IP?
Before starting EtherNet/IP communication, one of the devices must open a commu-
Communication
nication line called a "connection" with the other device. The side which opens the
connection is called the "scanner", and the opened side is called the "adaptor". (The
NU-EP1 is an adaptor.)
Scanner
Regular speed
(Communication cycle: 100 ms)
Sensor amplifier
Output
Output
・・・・・・
Error information
Current value Operation mode
3
IN area Cyclic communication
・・・・・・ ・・・・・・
Communication
Output Output
Error informationSetting value
Current value Current value
Operation modeCalibration
Error information ・・・・・・ ・・・・・・
Error information Setting value ・・・・・・
OUT area Cyclic communication ・・・・・・
Operation modeCalibration
External input ・・・・・・
IN area Message communication Setting value ・・・・・・
・・・・・・
Calibration
Cyclic communication
This function exchanges data between the scanner and the NU-EP1 at the set RPI
(Requested Packet Interval). Data such as the sensor amplifier's output signals and
judgment values and error status can be exchanged without ladder programs.
Message communication
Message communication can be used for applications which do not require a punctu-
ality like cyclic communication.
Various parameters, including data which can be exchanged with cyclic communica-
tion, can be read and written. The sensor amplifier calibration function, etc., can also
be executed.
Multiple sensor amplifiers can be connected to the NU-EP1. ID numbers are assigned
to each sensor amplifier for identification.
ID number 7 8 9 10 11 12 13 14
Unit occupying 8 ID numbers NU-EN8N Output 1 2 3 4 5 6 7 8
ID number 6
Unit occupying 1 ID numbers
d Output 1
Communication
ID number 1
Unit occupying 1 ID numbers a Output 1
ID number 0
NU-EP1 Output -
This section explains the cyclic communication function and its usage methods.
3 Ver.2
Communication
TM
EtherNet/IP
RPI=10 (ms)*
RPI=5 (ms)*
* RPI (Requested Packet Interval) can be set individually for each connection.
Point The configurations such as RPI and data size for cyclic communica-
tion are set according to the scanner size.
In a network which has many connected devices, including EtherNet/
IP devices, a delay or packet loss could occur if a large load is con-
stantly or temporarily applied on the network. Verify the settings care-
fully before starting use.
With cyclic communication, one device opens a logical communication line called a
"connection" with the other device. When successfully opened, data is exchanged.
The side which opens the connection is called the "scanner", and the opened side is
called the "adaptor". (The NU-EP1 is an adaptor.)
Communication is started with the following procedures.
(1) The scanner requests the adaptor to open the connection.
(2) The compatibility is checked on the adaptor side.
(3) If there is no error in the compatibility, the connection is opened.
(* If an error is found during the compatibility check, the connection is not opened.)
"Checking the Device Compatibility" (page 3-23)
KV-EP21V
3
Communication
Ver.2
(1) Request connection open
(2) Check compatibility
The exchange of data between the EtherNet/IP scanner, NU-EP1 and each sensor
amplifier is shown below.
Output data
IN area
Data reflected in the
scanner
Cyclic communication Data between
sensors is
refreshed
Input data
OUT area
The data output from the
Cyclic communication scanner is stored by the Data between
NU-EP1. sensors is
refreshed
The following settings are required to execute cyclic communication with the NU-EP1.
[NU-EP1]
No settings are required for the NU-EP1.
[Scanner]
(1) Set the connection to be used.
3 (2) Set the devices used in cyclic communication.
Refer to the scanner manual for details on the settings.
(* A ladder program is not required when using cyclic communication.)
Communication
Usable Connections
The data communicated differs for each connection. Select the necessary connec-
tions.
RPI
Connection Communication Input/ Assembly Size Application Reference
No. RANGE
Name data Output Instance (Byte)
(in 0.5 ms)
type page 3
Output,
Communication
current value, Input
64H
setting value NU-EP1 to 128 3-11
Monitor Data (100)
and operating scanner Exclusive
1 And External
status Owner
Input
Output
65H
External input Scanner to 4 3-17
(101)
NU-EP1
Output,
current value, Input
64H 0.5 ms to
setting value NU-EP1 to 128 3-11
Monitor (100) 10000 ms Input
and operating scanner
2 Data (Input
status Only
Only)
Output
FEH
- Scanner to 0 -
(254)
NU-EP1
Input
66H
Sensor Out- Sensor output 2 3-13
NU-EP1 to
(102) Input
scanner
3 put (Input
Output Only
Only) FEH
- Scanner to 0 -
NU-EP1
(254)
Reference
• Each connection's trigger timing is executed cyclically. The connection
type supports both point-to-point and multicast.
• The details of each application type are explained below.
Exclusive Owner:
This connection allows data sent from the scanner to the NU-
EP1 and data sent from the NU-EP1 to the scanner to be set
simultaneously. This is set when the scanner not only monitors
the adaptor (NU-EP1) data, but also when it issues external
inputs and rewrites the settings, etc. Multiple "Exclusive Owner"
3 connections cannot be opened to one adaptor (NU-EP1).
Input Only:
Communication
This connection can only allow data sent from the NU-EP1 to the
scanner. This is set when the scanner only monitors the adaptor
(NU-EP1) data. Multiple scanners can open an "Input Only" con-
nection simultaneously to one adaptor (NU-EP1).
* When simultaneously opening connections from multiple
scanners, set the Connection Type to Multicast.
• Designate "1" for the instance ID of "Assembly Object", and "0" for the
size when using the respective PLC which requires the designation of
"Configuration".
The data from the NU-EP1 is assigned to the EtherNet/IP scanner's IN area.
Reference
If the data extends over multiple byte, such as 16-bit data, the data is
stored into an area which starts with an even address in order from the low-
order byte.
Example)
Communication
Ver.2
Address 20 to 21
16-bit data 23 22 21 20
Address 22 to 23 56H 78H 56H 78H 12H 34H
TM
EtherNet/IP
Address
Name bit7 bit6 bit5 bit4 bit3 bit2 bit1 bit0
(Byte)
NU-EP1
0 Reserved for system
Error Status
Status Reserved Sensor Sensor
Sensor
Warning Sensor External Updating Sensor
1 Error Status for Setting EEPROM
Status Ready Input Setting
system Error Busy
Busy
Error Error
Sensor 2 •••••
(ID number 8) (ID number 1)
Error
Status Error Error
3 •••••
(ID number 16) (ID number 9)
Warning Warning
Sensor 4 •••••
(ID number 8) (ID number 1)
Warning
Status Warning Warning
5 •••••
(ID number 16) (ID number 9)
L-on/D-on L-on/D-on
6 (N.O./N.C.) ••••• (N.O./N.C.)
L-on/D-on (ID number 8) (ID number 1)
(N.O./
N.C.) L-on/D-on L-on/D-on
7 (N.O./N.C.) ••••• (N.O./N.C.)
(ID number 16) (ID number 9)
Current Value Current Value
Current 8 Over Range ••••• Over Range
Value (ID number 8) (ID number 1)
Over Current Value Current Value
Range 9 Over Range ••••• Over Range
(ID number 16) (ID number 9)
Address
Name bit7 bit6 bit5 bit4 bit3 bit2 bit1 bit0
(Byte)
Current Value Current Value
Current 10 Under Range ••••• Under Range
Value (ID number 8) (ID number 1)
Under Current Value Current Value
Range 11 Under Range ••••• Under Range
(ID number 16) (ID number 9)
Current Value Current Value
12 Invalid ••••• Invalid
Current (ID number 8) (ID number 1)
Value
Current Value Current Value
3 Invalid
13 Invalid
(ID number 16)
••••• Invalid
(ID number 9)
Output*1
Output Output
15 •••••
(ID number 16) (ID number 9)
Reserved
16 to 17 Reserved for system
for system
External Input External Input
18 Response ••••• Response
External (ID number 8) (ID number 1)
Input
Response External Input External Input
19 Response ••••• Response
(ID number 16) (ID number 9)
Error ID 20
Number Current Error ID Number. (16-bit unsigned integer)
21
Error 22
Current Error Code (16-bit unsigned integer)
Code 23
Warning 24
ID Number Current Warning ID Number (16-bit unsigned integer)
25
Warning 26
Current Warning Code (16-bit unsigned integer)
Code 27
Setting 28
Error ID Setting Error ID Number (16-bit unsigned integer)
Number 29
30
Current Value (ID number 1) (16-bit signed/unsigned integer)
31
Current
: :
Value*1
60
Current Value (ID number 16) (16-bit signed/unsigned integer)
61
62
Setting Value 1 (ID number 1) (16-bit signed/unsigned integer)
63
Setting
: :
Value 1*1
92
Setting Value 1 (ID number 16) (16-bit signed/unsigned integer)
93
Address
Name bit7 bit6 bit5 bit4 bit3 bit2 bit1 bit0
(Byte)
94
Setting Value 2 (ID number 1) (16-bit signed/unsigned integer)
95
Setting
: :
Value 2*1
124
Setting Value 2 (ID number 16) (16-bit signed/unsigned integer)
125
Reserved 126 to
Reserved for system
for system 127
Communication
Address
Name (Byte) bit7 bit6 bit5 bit4 bit3 bit2 bit1 bit0
*1 To confirm the data assigned to "Output (Fast output)", "Current Value", "Setting
Value 1/2" "Cyclic communication data assignment" (page 3-18)
Parameter list
Item Description
Outputs the NU-EP1's error status.
NU-EP1 Error
ON: Error is occurring.
Status
OFF: Error is not occurring.
When the settings have been changed with communication or key operations, this
Updating Sensor is output until the sensor amplifier settings have been changed.
Setting ON: One sensor amplifier has outdated settings.
OFF: All sensor amplifier settings are current.
When the sensor amplifier settings have been changed, this is output until writing to
3 Sensor EEPROM
Busy
the EEPROM is completed.
ON: One sensor amplifier has setting data which has not been written to the EEPROM.
OFF: The setting data for all sensor amplifiers has been written to the EEPROM.
This is output when an external input signal is sent. If the external input signal is
Communication
Sensor External activated, the external input cannot be set via communication.
Input Busy ON: The external input signal is activated.
OFF: The external input signal is not activated.
This is output when there is an incorrect combination in the sensor amplifier set-
tings. The ID number which caused the sensor setting error can be confirmed by
Sensor Setting
the "Setting Error ID Number".
Error
ON: There is an incorrect setting combination in one of the sensor amplifiers.
OFF: All sensor amplifiers are running with the correct settings.
This is output when the sensor amplifier is running normally.
Sensor Ready ON: The sensor amplifier is running normally.
OFF: The sensor amplifier is starting up.
The warning status for the NU-EP1 or connected sensor amplifiers is output.
When ON, a value is stored in "Warning ID Number" and "Warning Code", and
Warning Status when OFF, 0 is stored in "Warning ID Number" and "Warning Code".
ON: A warning is occurring in the NU-EP1 or a sensor amplifier.
OFF: A warning is not occurring in the NU-EP1 or any sensor amplifier.
The error status for the NU-EP1 or connected sensor amplifiers is output. When
ON, a value is stored in "Error ID Number" and "Error Code", and when OFF, 0 is
Error Status stored in the "Error ID Number" and "Error Code".
ON: An error is occurring in the NU-EP1 or a sensor amplifier.
OFF: An error is not occurring in the NU-EP1 or any sensor amplifier.
The target ID number bit is output when an error is occurring in the sensor amplifier.*1
Sensor Error
ON: An error is occurring in the target ID number sensor amplifier.
Status
OFF: An error is not occurring in the target ID number sensor amplifier.
The target ID number bit is output when a warning is occurring in the sensor amplifier.*1
Sensor Warning
ON: A warning is occurring in the target ID number sensor amplifier.
Status
OFF: A warning is not occurring in the target ID number sensor amplifier.
L-on/D-on The L-on/D-on or N.O./N.C. state of the sensor amplifier is output.*1, *2, *3
(N.O./N.C.) ON: The target ID number sensor amplifier is in the D-on or N.C. state.
OFF: The target ID number sensor amplifier is in the L-on or N.O. state.
This is output when the sensor amplifier's current value is larger than the measure-
ment upper limit.*1, *2, *3, *4
Current Value ON: The target ID number sensor amplifier's current value is larger than the
Over Range measurement upper limit.
OFF: The target ID number sensor amplifier's current value is less than the
measurement upper limit.
Item Description
This is output when the sensor amplifier's current value is less than the measure-
ment lower limit.*1, *2, *3, *4
Current Value ON: The target ID number sensor amplifier's current value is less than the mea-
Under Range surement lower limit.
OFF: The target ID number sensor amplifier's current value is larger than the
measurement lower limit.
Current Value This is output when the sensor amplifier's current value is invalid.*1, *2, *3, *4
Invalid ON: The target ID number sensor amplifier's current value is not normal.
OFF: The target ID number sensor amplifier's current value is normal.
Output
The sensor amplifier's ON/OFF state is output.*5, *6
ON: The sensor amplifier output is on.
OFF: The sensor amplifier output is off.
3
"Cyclic communication data assignment" (page 3-18)
Communication
This is output when an external input has been made via communication. The ID
number is output even if it does not have an external input.*3
External Input ON: The external input request turned ON.
Response OFF: The external input request turned OFF.
Refer to "External Input Request" (page 3-17) for details.
If the "Error Status" is ON, the ID number of the NU-EP1 or the sensor amplifier
connected to the NU-EP1 in which the error is occurring is displayed. (ID number 0
for NU-EP1.) 0 is stored if an error is not occurring. If an error is occurring at multi-
ple IDs, the ID number of the NU-EP1 or sensor amplifier with the highest priority
error is stored.
Error ID Number Error priority:
(1) NU-EP1 error (Excluding error code 56)
(2) Sensor amplifier error (Smallest error code number has priority)*
* If the same error code is occurring in multiple sensor amplifiers, the error
with the smallest ID number has the priority.
(3) NU-EP1 error (Error code 56)
If the "Error Status" is ON, the error code is stored. 0 is stored if an error is not
occurring. If an error is occurring at multiple IDs, the error code of the NU-EP1 or
sensor amplifier with the highest priority error is stored.
Error priority:
(1) NU-EP1 error (Excluding error code 56)
Error Code
(2) Sensor amplifier error (Smallest error code number has priority)*
* If the same error code is occurring in multiple sensor amplifiers, the error
with the smallest ID number has the priority.
(3) NU-EP1 error (Error code 56)
"Error code list" (page 3-21)
If the "Warning Status" is ON, the ID number of the NU-EP1 or the sensor amplifier
Warning ID connected to the NU-EP1 in which the warning is occurring is displayed. 0 is
Number stored if a warning is not occurring. If a warning is occurring at multiple IDs, the
smallest ID number is stored. (Priority: 00 > 01 > to > 16)
If the "Warning Status" is ON, the warning code is stored. 0 is stored if "Warning
Status" is OFF. If a warning is occurring at multiple ID numbers, the warning code
Warning Code with the smallest ID number is stored. (Priority: 00 > 01 > to > 16)
"Warning list" (page 3-22)
If the "Sensor Setting Error" is ON, the ID number of the sensor amplifier in which
the sensor setting error is occurring is stored. 0 is stored if a setting sensor error is
Setting Error ID not occurring. If an error is occurring at multiple IDs, the smallest ID number is
Number stored. (Priority: 00 > 01 > to > 16)
"Functions which Cannot be Set in Duplicate" (page 3-22)
Item Description
This is the sensor amplifier's current value. 0 is stored if there is no current value.
Current Value
"Cyclic communication data assignment" (page 3-18)
This is the sensor amplifier setting value 1 data.
Setting Value 1 0 is stored if setting value 1 does not exist.
"Cyclic communication data assignment" (page 3-18)
This is the sensor amplifier setting value 2 data.
Setting Value 2 0 is stored if setting value 2 does not exist.
"Cyclic communication data assignment" (page 3-18)
The sensor amplifier's ON/OFF status is output.
3 Fast Output ON: The sensor amplifier output is on.
OFF: The sensor amplifier output is off.
*1 If the sensor occupies more than two ID numbers, the status is output to all occu-
Communication
pied ID numbers.
*2 The status is not output to an ID number for which each item does not exist.
*3 When using the NU-EN8N sensor amplifier, the status is not output to the occu-
pied ID number.
*4 For details, refer to "Current Value Property of the Sensor" (page 4-11).
*5 The output can be switched between "Fast output" and "Current Value Sync. Out-
put".
Change the NU object attribute B3H. (The instance ID is 00H.)
"What is Fast Output?" (page 3-13)
*6 With the NU-EN8N, the output is only sent when the output is set to "Fast output".
The data to the sensor amplifier is assigned to the EtherNet/IP scanner's OUT area.
Address
Name Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
(Byte)
0
External Input
Request •••••
External Input
Request
3
External (ID number 8) (ID number 1)
Communication
Input
Request External Input External Input
1 Request ••••• Request
(ID number 16) (ID number 9)
Reserved
2 to 3 Reserved for system
for system
Parameter list
Item Description
The sensor amplifier's external input is activated via communica-
tion. If a signal is input on the external input terminal, the external
input request will be ignored.
External Input
ON: External input is activated via communication. "External
Request
Input Response" turns ON when input is accepted.
OFF: "External Input Response" turns OFF.
"Cyclic communication data assignment" (page 3-18)
ON
Sensor External input OFF
For NU-EP1, data such as the sensor "output" and "current value" can be obtained via
data communication, but the meaning of "output" and "current value" differs according
to the sensor.
For details, refer to the table below.
3 Connected sensor
1st 2nd
ID number
3rd ••• 8th
FS-N40/N42* Output - - ••• -
Communication
Current Value
ID number
Connected sensor
1st 2nd 3rd ••• 8th
FS-N40/N42* Current value - - ••• -
FS-N44* Current value Not used - ••• -
FS-N10/N12* Current value - - ••• -
FS-N14* Current value Not used - ••• -
LV-N10/N12C* Current value - - ••• -
LV-N12* Current value Not used - ••• -
PS-N10/N12* Current value - - ••• -
AP-N10
AP-N10D
Current Pressure Value -
Current Pressure Value Raw Pressure Value
-
-
•••
•••
-
-
3
MU-N/LR-T Current Distance Not used Not used ••• -
Communication
1-Output Current value of
Not used Not used ••• -
16-Bank the selected bank
Current value of Current value of Current value of
MU-N/ 4-Output
output 1 of the output 2 of the output 3 of the ••• -
2-Bank
LR-W selected bank selected bank selected bank
Number of the out- Current value of
Binary put with the high- the selected out- Not used ••• -
est matching rate put number
MU-N/FD-Q Instantaneous flow Integrated flow Not used ••• -
NU-EN8N Not used Not used Not used ••• Not used
External Input
ID number
Connected sensor
1st 2nd 3rd ••• 8th
FS-N40/N42* External input - - ••• -
FS-N44* External input Not used - ••• -
FS-N10/N12* External Input - - ••• -
FS-N14* External Input Not used - ••• -
LV-N10/N12C* External Input - - ••• -
LV-N12* External Input Not used - ••• -
PS-N10/N12* External Input - - ••• -
AP-N10 External Input - - ••• -
AP-N10D External Input Not used - ••• -
MU-N/LR-T External Input Not used Not used ••• -
1-Output
External Input Not used Not used ••• -
16-Bank
MU-N/
4-Output
LR-W External Input Not used Not used ••• -
2-Bank
Binary External Input Not used Not used ••• -
MU-N/FD-Q External Input Not used Not used ••• -
NU-EN8N Not used Not used Not used ••• Not used
Setting Value 1
ID number
Connected sensor
1st 2nd 3rd ••• 8th
Setting value
FS-N40/N42* - - ••• -
(Output / Area Hi)
Setting value Setting value
FS-N44* - ••• -
(Output 1 / Area Hi) (Output 2)
Setting Value
FS-N10/N12* - - ••• -
(Output / Area Hi)
Setting Value Setting Value
FS-N14* - ••• -
(Output 1 / Area Hi) (Output 2)
3 LV-N10/N12C*
Setting Value
(Output / Area Hi)
- - ••• -
Setting Value Setting Value (Output 2
LV-N12* - ••• -
(Output 1 / Area Hi) / Counter Setting Value)
Communication
Setting Value
PS-N10/N12* - - ••• -
(Output / Area Hi)
AP-N10 Setting Value (P1) - - ••• -
AP-N10D Setting Value (P1) Setting Value (P2) - ••• -
Setting Value (Output1 Setting Value (Output2
MU-N/LR-T Not used ••• -
/ Output1 Area Near) / Output2 Area Near)
1-Output Bank 1 setting Bank 2 setting Bank 3 setting
••• -
16-Bank value value value
MU-N/
4-Output Bank 1, Output 1 Bank 1, Output 2 Bank 1, Output 3
LR-W ••• -
2-Bank Setting value Setting value Setting value
Binary Output 1 Setting value Output 2 Setting value Output 3 Setting value ••• -
Setting Value (Output1 Setting Value (Output2
MU-N/FD-Q Not used ••• -
/ Output1 Area Lower) / Output2 Area Lower)
NU-EN8N - - - ••• -
Setting Value 2
ID number
Connected sensor
1st 2nd 3rd ••• 8th
FS-N40/N42* Setting value (Area Low) - - ••• -
FS-N44* Setting value (Area Low) Not used - ••• -
FS-N10/N12* Setting Value (Area Low) - - ••• -
FS-N14* Setting Value (Area Low) Not used - ••• -
LV-N10/N12C* Setting Value (Area Low) - - ••• -
LV-N12* Setting Value (Area Low) Not used - ••• -
PS-N10/N12* Setting Value (Area Low) - - ••• -
AP-N10 Not used - - ••• -
Setting Value Setting Value
AP-N10D - ••• -
(Area Upper: Hi) (Area Low: Lo)
Setting Value Setting Value
MU-N/LR-T Not used ••• -
(Output1 Area Far) (Output2 Area Far)
1-Output Bank 4 setting Bank 5 setting Bank 6 setting
••• -
16-Bank value value value
MU-N/
4-Output Bank 1, Output 4 Bank 2, Output 1 Bank 2, Output 2
LR-W ••• -
2-Bank Setting value Setting value Setting value
Binary Output 4 Setting value Output 5 Setting value Output 6 Setting value ••• -
Setting Value Setting Value
MU-N/FD-Q Not used ••• -
(Output1 Area Upper) (Output2 Area Upper)
NU-EN8N - - - ••• -
Error ID
Code Details Cause Actions
number
0 No error
51 System error Sensor ID assignment error
A sensor was disconnected
Confirm that the NU-EP1 is
Number of sen- during use. Only the NU-EP1
53 securely connected to the
sors down was reset. Data is being read
sensor. Turn the power on
from sensor.
again.
54
Number of sen-
sors down
A sensor was disconnected
during use.
3
Confirm that the NU-EP1 is
A sensor was connected dur-
Communication
securely connected to the
Number of sen- ing operation. Sensors for
56 sensor. Make sure that sen-
sors up more than 17 outputs were
sors for 16 outputs or less
connected.
are connected.
Confirm that the NU-EP1 is
Constant operation communi- securely connected to the
57 System error
0 cation error sensor. Turn the power on
again.
Check the IP address and
IP address dupli- The IP address is the same change it so it is not dupli-
70
cate error as another device. cated. Then, turn the power
on again.
100 System error An IP setting error occurred.
A default gateway setting
101 System error
error occurred.
102 System error An EEPROM error occurred.
103 System error Protocol stack start error Contact your nearest
Keyence office.
104 System error Flash ROM hardware error
150 System error Number of held IDs error
151 System error Number of sensor units error
152 System error Initial read error
• Check whether the load
resistance value is too
An overcurrent was detected through the
1 low.
control output. ()
• Check whether the wire is
shortcircuited.
Check the following matters
and turn the power OFF and
(FS-N40/N10 Series) ON.
1-16 Does not occur. • Check that the sensor
(Sensor) head is connected.
2
(Models other than FS-N40/N10 Series) • Check that the sensor
Signals from the sensor head are not conveyed head cable is not broken.
properly. () • Securely crimp the head
cable connector with a
pair of pliers, etc.
Cycle power. If operation is
3 The internal data write/read failed. not recovered, initialize the
settings.
Error ID
Code Details Cause Actions
number
• Check whether the
The DATUM warning output turned ON while received light amount has
using the DATUM function. dropped.
• The received light amount is less than the • Adjust the DATUM warn-
6
DATUM warning output level. ing output level.
• The raw received light amount value is 50 or • Adjust the raw received
less light amount to be 50 or
more.
• Set the APC function to
3 1-16
(Sensor)
(FS-N40/N10 Series) OFF.
The LED light amount drop exceeds the APC com- • Replace the sensor if
pensation limit. advanced detection (APC
function) is required.
Communication
7 (LV-N10/PS-N10/AP-N10 Series)
-
No error occurred.
Refer to the sensor User's
(LR-T/LR-W/FD-Q Series)
manual and complete the ini-
The settings do not match between the sensor and
tial setting (synchronization
MU-N.
of the sensor and MU-N).
8 Communication error between sensors -
Warning list
There are no warnings which occur with the NU-EP1.
The following warnings may occur with the sensor.
Type of warning
Refer to each sensor amplifier's manual for details on the Limit Detection function.
Procedures to confirm the warning
Read "Sensor Warning Status" (page 3-11) which is assigned to the cyclic com-
munication's IN area.
The compatibility check is a function executed when the sensor communicates with
the NU-EP1. This function checks that the device set with the scanner matches the
NU-EP1 to prevent communicating with the wrong device. This function is executed at
the moment the connection is opened.
Refer to the respective scanner manual for details on using the scanner.
Communication
This section explains the message communication function and usage methods.
Reference
The NU-EP1 message communication function supports CIP defined
UCMM (unconnected) and Class 3 (connected) message communication.
The following settings are required to execute message communication with the NU-
EP1.
[NU-EP1]
No settings are required for the NU-EP1.
[Scanner]
Set the applicable service, Class ID, Instance ID, Attribute ID and service data, and 3
send the command used for message communication.
Communication
"Objects and Services" (page 3-26)
Refer to the scanner manual for details on the setting methods and applicable com-
mands.
When (1) a service is executed to an NU-EP1 object, actions such as (2) data output,
(3) parameter changes or (4) designated operation execution are performed.
3 (1)
Object
(3)
Service Parameter change
Communication
For example with the NU Object, one instance is prepared for each sensor amplifier
connected to the NU-EP1. By reading the attributes which correspond to each
instance's current incoming light amount value, the current incoming light amount
value for each sensor amplifier corresponding to that instance can be read out.
NU Object
(Class ID: 66H)
Reference
With the EtherNet/IP (CIP), a method called "object modeling" is used to
express the device. The device is handled as a group of objects. Objects
abstractly express the configuration elements in the device. The class is a
group of objects for expressing the same type of configuration elements.
An instance actually expresses a specific object contained in a class. Each
instance in the class has the same attribute group, but each uses a unique
attribute value.
Reference
To execute a service to the NU-EP1, send a command from the scanner.
The NU-EP1 then returns the service execution results as a response.
Commands require a service, class ID, instance ID, attribute ID *, and set-
ting value (service data)* when writing parameters.
Command Response
Communication
・Service data*
A list of objects which can be used with the NU-EP1 is provided in this section.
EtherNet/IP unit
KV-EP21V
NU Identity Assembly
Command Object Object Object
Ver.2
Reference
Object name Class ID Description
page
This object provides the status of the NU-EP1 or sen-
sor amplifier connected to the NU-EP1, and writes/
NU Object 66H 3-30
reads the parameters. This object is unique to the NU-
EP1.
This object provides the identification information,
Identity Object 01H 5-19
general information and reset service.
Message Router This object provides the connection point for message
02H 5-22
Object communication.
This object provides access to the devices exchanged
Assembly Object 04H with cyclic communication. Data cannot be sent to a 5-23
device which does not support cyclic communication.
Connection This object is used for connection type communica-
06H 5-25
Manager Object tion.
Reference
Object name Class ID Description
page
This object provides the structure for setting the TCP/
TCP/IP Interface
F5H IP network interface. The IP address, subnet mask 5-27
Object
and gateway, etc., can be set.
Ethernet Link Object F6H This object provides the Ethernet status information. 5-31
Commands
• Command format
Item Description
*1
Service code Designates the service code to be used.
Class ID Designates the class ID according to the service*1 being used.
Instance ID Designates the instance ID according to the service*1 being used.
Attribute ID Designates the attribute ID according to the service*1 being used.
Service data Designates the service according to the service*1 being used.
*1 Refer to "How to Use NU Objects" (page 3-30) or "Objects for Use with
the NU-EP1" (page 5-18) for details on the usable services.
Responses
• Response format
Item Description
Returns a general status in respect to the command. 00H is returned when
General status
normal.
Additional status Returns the additional status.
Service response
Returns the service response data in respect to the command.
data
Communication
returned as general status
No
Yes
This section explains how to carry out message communication using NU Objects.
Item Value
Service code (HEX) 0EH (Get Attribute Single)
Class ID (HEX) 66H
00 : NU
Instance ID (DEC) 01 to 16 : Sensor ID number
"Assigning the Sensor ID Number" (page 3-4)
Attribute ID (HEX) "Parameter List" (page 3-35)
Service data -
Response format
Item Value
Item Value
Service code (HEX) 10H (Set Attribute Single)
Class ID (HEX) 66H
00 : NU
3
Instance ID (DEC) 01 to 16 : Sensor ID number
Communication
"Assigning the Sensor ID Number" (page 3-4)
Attribute ID (HEX) "Parameter List" (page 3-35)
Service data "Parameter List" (page 3-35)
Response format
Item Value
Item Value
Response format
Item Value
Item Value
Service code (HEX) 4CH
Class ID (HEX) 66H
Instance ID (DEC)
Attribute ID (HEX)
00 : NU
-
3
00H : Key lock cancel
Communication
01H : Key lock execute
Service data
02H : PIN key lock execute
03H : Communication key lock execute
Reference PIN key lock: The PIN set in thesensor amplifier is required to cancel this
setting from the sensor amplifier.
Communication key lock: This cannot be canceled from the sensor ampli-
fier.
Response format
Item Value
General status
The responses made when using each service are shown below.
(1) Parameter read: Service code 0EH
(2) Parameter write: Service code 10H
(3) Operation command: Service code 4BH
(4) Batch lock setting: Service code 4CH
This section explains the attribute IDs and operation commands used for each sensor
amplifier's message communication, including error codes and warning codes.
Communication
Output Select from fast output or current WORD R
(105) ID number 1 to 16
value continuous output.
Item Description
(1) Attribute ID Expresses the attribute ID as a hexadecimal (decimal).
(2) Name Indicates the attribute name.
Describes the attribute, and indicates the read data, and the range of parame-
(3) Description
ters which can be set.
(4) Data type Indicates the attribute data type.
Indicates the direction of services on the attribute ID.
R (Read): The attribute values can be read using Get_Attribute_Single and
(5) Attribute
Get_Attributes_All.
W (Write): Can write a value into the attributes using Set_Attribute_Single.
(6) Value Describes the parameter value which can be set.
Data type
The data type is defined in the following manner by the EtherNet/IP specifications.
Range
Data type Description
Minimum Maximum
INT Signed 16-bit integer -32768 32767
UINT Unsigned 16-bit integer 0 65535
WORD Bit string: 16-bit - -
Character string (2-byte length
STRING information + 1-byte - -
per 1-character array)
NU-EP1
NU-EP1
Communication
84H Reserved for
- - - -
(132) system
Indicates the status of the
85H 2byte Bit0 to 15: ID number 1 to 16
Sensor Ready Sensor Ready bit of each R
(133) WORD sensor ready status
amplifier.
86H
(134) to Reserved for
- - - -
8CH system
(140)
Indicates the current value Bit0 to 15: ID number 1 to 16
8DH Current Value 2byte
invalid status of each sen- R
(141) Invalid
sor amplifier.
WORD current value invalid status*1
NU-EP1
0310H Error Code Indicates the error code of 2byte "Parameter List" (page
R
(784) (ID number 16) ID number 16. UINT 3-35)
Communication
*1 For details, refer to "Current Value Property of the Sensor" (page 5-40).
FS-N40/N42*/N44*
Refer to ""How to Use NU Objects"" (page 3-30) for how to use the parameters.
Designate the ID number of the installed sensor for the instance ID.
: Default value
Communication
ON.
Bit6: APC Error
Bit7: Sensor Communication
Error
Indicates warning informa-
0322H Warning Infor- tion. When a warning 2byte
R Bit0: Limit Detection
(802) mation occurs, the corresponding WORD
bit is turned ON.
Indicates the operating sta-
tus of the warning function.
0323H Warning Func- 2byte
When the warning function R Bit0: Limit Detection
(803) tion WORD
is operating, the corre-
sponding bit is turned ON.
Indicates the output status
0324H of the sensor. When the 2byte Bit0: Out 1
Output R
(804) output is ON, the corre- WORD Bit1: Out2 *1
sponding bit is turned ON.
0325H Indicates the current value 2byte
Current Value R 0 to 65535
(805) of received light intensity. UINT
0326H
Reserved - - - -
(806)
0327H
Reserved - - - -
(807)
Indicates the received light
0328H intensity before correction 2byte
Raw Value R 0 to 65535
(808) with the Preset, DATUM, or UINT
Zero-shift functions.
Indicates the peak value (or
the max bottom value) of
0329H Peak-Hold 2byte
received light intensity R 0 to 65535
(809) Value UINT
(depending on the settings
of Hold display).
Indicates the bottom value
(or the min peak value) of
032AH Bottom-Hold 2byte
received light intensity R 0 to 65535
(810) Value UINT
(depending on the settings
of Hold display).
032BH
Reserved - - - -
(811)
Indicates the lowest value
among max values of
Peak-Hold received light intensity dur-
032CH 2byte
Minimum ing the time period when R 0 to 65535
(812) UINT
Value the setting value of
received light intensity is
exceeded.
FS-N40/N42*/N44*
: Default value
3 (816)
Canceling sta-
tus
Saturation Cancel function. INT
R
1: On
0: Normal Operation
0331H Operation Indicates the current opera- 2byte 1: LED off
R
(817) Mode tion mode of the sensor. INT 2: Sleep
Communication
3: Pause
0: Normal Operation
0332H Operation Set the operation mode of 2byte 1: LED off
R/W
(818) Mode Setting the sensor. INT 2: Sleep
3: Pause
0333H
(819) to
Reserved - - - -
033FH
(831)
Indicates the number of
0340H Group2 Entry 2byte
entries that can be set in R 9
(832) count UINT
Group 2.
Indicates the setting value
Setting Value of the output 1. The upper
0341H 2byte
(Output 1/ limit of the setting value is R/W 0 to 65535 (Default: 100)
(833) UINT
Area Hi) displayed when in Area
Detection mode.
0342H Setting Value Indicates the setting value 2byte
R/W 0 to 65535 (Default: 100)
(834) (Output2) of Output 2. UINT
0343H
Reserved - - - -
(835)
Indicates the lower limit of
0344H Setting Value 2byte
the setting value in Area R/W 0 to 65535 (Default: 100)
(836) (Area Low) UINT
Detection mode.
0345H
Reserved - - - -
(837)
0346H
Reserved - - - -
(838)
0347H Limit Detec- Indicates if Limit Detection 2byte 0: Off
R/W
(839) tion is enabled. INT 1: On
Indicates the Limit Detec-
0348H Limit Detec- tion point as a ratio defining 2byte
R/W 0 to 100 (Default: 5)
(840) tion Point the setting value (output 1) INT
as "100".
Limit Detec-
0349H Indicates the reset method 2byte 0: User reset
tion Reset R/W
(841) of the Limit Detection. INT 1: Auto reset
Method
034AH
(842) to
Reserved - - - -
034FH
(847)
[Custom] Indicates the number of
0350H 2byte
Group2 Entry entries that can be set in R 9
(848) UINT
count Group 2 custom save area.
FS-N40/N42*/N44*
: Default value
0355H
(853)
(Area Low)
Reserved - - - -
3
0356H
Reserved - - - -
Communication
(854)
0357H [Custom]Limit Custom save area for "Limit 2byte 0: Off
R/W
(855) Detection Detection". INT 1: On
[Custom]Limit
0358H Custom save area for "Limit 2byte
Detection R/W 0 to 100 (Default: 5)
(856) Detection Point". INT
Point
0359H [Custom] Custom save area for 2byte 0: User reset
R/W
(857) Reset Method "Reset Method". INT 1: Auto reset
035AH
(858) to
Reserved - - - -
035FH
(863)
Indicates the number of
0360H Group3 Entry 2byte
entries that can be set in R 10
(864) count UINT
Group 3.
0: Unlock
0361H Key Lock Sta- Indicates the status of the 2byte 1: Key Lock
R/W
(865) tus Key Lock. INT 2: PIN Code Lock
3: Communication Lock
0362H Indicates the password for 2byte
PIN Code R/W 0 to 9999 (Default: 0)
(866) Key Lock. INT
Indicates lock status of the
Slide Switch. When locked,
0363H Slide Switch the Slide Switch is dis- 2byte 0: Unlock
R/W
(867) Lock abled, with the value INT 1: Lock
always being "SEL" (When
using FS-N44*, "1".).
Indicates whether the out-
put is ON for light (L-on) or Bit0: Output 1
0364H L-on/D-on 2byte
(868) (N.O./N.C.)
ON for dark (D-on). The
WORD
R/W Bit1: Output 2 *1
corresponding bit is turned (Default: 0)
ON for D-on or N.C..
FS-N40/N42*/N44*
: Default value
3 6: MEGA
(Response Time 16ms)
7: TERA
(Response Time 64ms)
0366H
Communication
Reserved - - - -
(870)
Indicates target value of
Percentage percentage calibration
0367H 2byte
Calib. Target when the Sensitivity Setting R/W -99 to 99 (Default: -10)
(871) INT
Value is set to Percentage Cali-
bration.
Indicates the target value
for percentage calibration
when the Sensitivity setting
0368H Area % Set- 2byte
is set to percentage calibra- R/W 1 to 99 (Default: 10)
(872) ting INT
tion and the Detection
mode is set to Area detec-
tion mode.
0: Level 1
1: Level 2
0369H Indicates the hysteresis 2byte
Hysteresis R/W 2: Level 3
(873) setting. INT
3: Level 4
4: Level 5
036AH Indicates if the Bar Graph is 2byte 0: Off
Display Bar R/W
(874) enabled on the display. INT 1: On
Indicates the method of Key
036BH Key Lock 2byte 0: Normal
Lock when being set via the R/W
(875) Method INT 1: PIN Code
buttons on the sensor.
036CH
(876) to
Reserved - - - -
036FH
(879)
[Custom] Indicates the number of
0370H 2byte
Group3 Entry entries that can be set in R 10
(880) UINT
count Group 3 custom save area.
0: Unlock
0371H [Custom]Key Custom save area for "Key 2byte 1: Key Lock
R/W
(881) Lock Status Lock Status". INT 2: PIN Code Lock
3: Communication Lock
0372H [Custom]PIN Custom save area for "PIN 2byte
R/W 0 to 9999 (Default: 0)
(882) Code Code". INT
0373H [Custom]Slide Custom save area for "Slide 2byte 0: Unlock
R/W
(883) Switch Lock Switch Lock". INT 1: Lock
[Custom]L-on/ Bit0: Output 1
0374H Custom save area for "Lon/ 2byte
(884)
D-on (N.O./
D-on (N.O./N.C.)". INT
R/W Bit1: Output 2 *1
N.C.) (Default: 0)
FS-N40/N42*/N44*
: Default value
Communication
Reserved - - - -
(886)
[Custom]Per- Custom save area for the
0377H 2byte
centage Carib. "Percentage Calib.Target R/W -99 to 99 (Default: -10)
(887) INT
Target Value Value".
0378H [Custom]Area Custom save area for the 2byte
R/W 1 to 99 (Default: 10)
(888) % Setting "Area Percentage Setting". INT
0: Level 1
1: Level 2
0379H [Custom] Custom save area for the 2byte
R/W 2: Level 3
(889) Hysteresis "Hysteresis". UINT
3: Level 4
4: Level 5
037AH [Custom]Dis- Custom save area for the 2byte 0: Off
R/W
(890) play Bar "Display Bar". INT 1: On
037BH [Custom]Key Custom save area for the 2byte 0: Normal
R/W
(891) Lock Method "Key Lock Method". INT 1: PIN Code
037CH
(892) to
Reserved - - - -
037FH
(895)
Indicates the number of
0380H Group4 Entry 2byte
entries that can be set in R 9
(896) count UINT
Group 4.
0: Timer Off
1: Off-delay Timer
0381H Output Timer Indicates the settings for 2byte 2: On-delay Timer
R/W
(897) (Output 1) the Output 1 timer. INT 3: One-shot Timer
4: On-delay Off-delay
5: On-delay One-shot
Indicates the Timer Dura-
tion for the Output 1 timer.
Indicates the Timer Dura-
0382H Timer Dura- tion for the "On-delay" 2byte
R/W 1 to 9999 (Default: 10)
(898) tion (Output 1) when the "Output timer INT
(Output 1)" is set to "On-
delay Off-delay" or "On-
delay One shot". (Unit: ms)
Indicates the Timer Dura-
tion for the "Off-delay" or
Timer Dura- the "One-shot" when the
0383H 2byte
tion 2 "Output timer (Output 1)" is R/W 1 to 9999 (Default: 10)
(899) INT
(Output 1) set to "On-delay Off-delay"
or "On-delay One shot".
(Unit: ms)
FS-N40/N42*/N44*
: Default value
3 0385H
(901)
DATUM Speed
Indicates the DATUM cor-
rection speed.
2byte
INT
R/W 1: Level2: (Normal)
2: Level3: (Fast)
0386H DATUM Warn- Indicates the DATUM alarm 2byte
R/W 0 ot 100 (Default: 50)
(902) ing Level output level. INT
Communication
0: Not use
1: External Calibration
2: Zero-shift
0387H Indicates the control input 2byte
External Input R/W 3: Reset
(903) settings. INT
4: Transmission OFF
5: Pause Mode
6: Sleep Mode
0: Always Off
0388H Sets the output status of 2byte
Pause Mode R/W 1: Always On
(904) the sensor to Pause mode. INT
2: Keep Output
0389H 2byte
Attenuation Switch the lighting power. R/W 1 to 100 (Default: 100)
(905) INT
038AH
(906) to
Reserved - - - -
038FH
(911)
[Custom] Indicates the number of
0390H 2byte
Group4 Entry entries that can be set in R
(912) UINT
count Group 4 custom save area.
0: Timer Off
1: Off-delay Timer
[Custom]Out-
0391H Custom save area for "Out- 2byte 2: On-delay Timer
put Timer R/W
(913) put Timer (Output1)". INT 3: One-shot Timer
(Output 1)
4: On-delay Off-delay
5: On-delay One-shot
[Custom] Custom save area for
0392H 2byte
Timer Dura- "Timer Duration (Output R/W 1 to 9999 (Default: 10)
(914) INT
tion (Output 1) 1)".
[Custom]
Custom save area for
0393H Timer Dura- 2byte
"Timer Duration 2 (Output R/W 1 to 9999 (Default: 10)
(915) tion 2 (Output INT
2)".
1)
0: Normal Detection Mode
1: PREST
2: Percentage Calibration
3: Zero-shift Calibration
[Custom] Custom save area for 4: Area Detection Mode
0394H 2byte
Detection "Detection Mode R/W 5: Area % Mode
(916) INT
Mode (Output1)". 6: DATUM Mode
7: Rising Edge Detection
Mode
8: Falling Edge Detection
Mode
0: Level1: (Slow)
0395H [Custom] Custom save area for 2byte
R/W 1: Level2: (Normal)
(917) DATUM Speed "DATUM Speed". INT
2: Level3: (Fast)
FS-N40/N42*/N44*
: Default value
0399H
Pause Mode
[Custom]
"Pause Mode".
2byte
R/W
2: Keep Output
Communication
039AH
(922) to
Reserved - - - -
039FH
(927)
Indicates the number of
03A0H Group5 Entry 2byte
entries that can be set in R 4
(928) count UINT
Group 5.
0: Timer Off
1: Off-delay Timer
03A1H Output Timer Indicates the settings of the 2byte 2: On-delay Timer
R/W
(929) (Output 2) *1 Output 2 timer. INT 3: One-shot Timer
4: On-delay Off-delay
5: On-delay One-shot
Indicates the Timer Dura-
tion for the Output 2 timer.
Indicates the Timer Dura-
Timer tion for the "On-delay"
03A2H Duration 2byte
when the "Output timer R/W 1 to 9999 (Default: 10)
(930) INT
(Output 2) *1 (Output 2)" is set to "On-
delay Off-delay" or "On-
delay One shot". (Unit: ms)
(Unit: ms)
Indicates the Timer Dura-
tion for the "Off-delay" or
Timer the "One-shot" when the
03A3H Duration 2 2byte
"Output timer (Output 2)" is R/W 1 to 9999 (Default: 10)
(931) INT
(Output 2) *1 set to "On-delay Off-delay"
or "On-delay One shot".
(Unit: ms)
Detection
03A4H Mode Indicates the detection 2byte 0: Normal Detection Mode
R/W
(932) mode of Output 2. INT 1: Warning Output
(Output 2) *1
03A5H
(933) to
Reserved - - - -
03AFH
(943)
[Custom] Indicates the number of
03B0H 2byte
Group5 Entry entries that can be set in R 4
(944) UINT
count Group 5 custom save area.
0: Timer Off
[Custom] 1: Off-delay Timer
03B1H Output Timer Custom area for "Output- 2byte 2: On-delay Timer
R/W
(945) Timer (Output 2)". INT 3: One-shot Timer
(Output 2) *1 4: On-delay Off-delay
5: On-delay One-shot
FS-N40/N42*/N44*
: Default value
(949) to
Reserved - - - -
03BFH
Communication
(959)
Indicates the number of
03C0H Group6 Entry 2byte
entries that can be set in R 14
(960) count UINT
Group 6.
03C1H Indicates the display 2byte 0: Normal
Flip Display R/W
(961) reverse setting. INT 1: Reverse
0: Off
1: Excess Gain(%)
03C2H Indicates the sub display 2byte
Sub Display R/W 2: Display Hold
(962) details. INT
3: Gain(%) Hold
4: TAG Strings
0: Normal
Indicates hold details when 1: Peak Max. / Peak Min.
03C3H 2byte
Display Hold the Display Hold is selected R/W 2: Bottom Max. / Bottom Min.
(963) INT
under the Sub-display. 3: Peak Min. / Bottom Max.
4: Peak Max. / Bottom Min.
03C4H
Reserved - - - -
(964)
03C5H Preset Satura- Indicates the Preset satura- 2byte
R/W 100 to 200 (Default: 110)
(965) tion Level tion level. INT
0: Normal
03C6H Current Dis- Indicates the current dis- 2byte
R/W 1: Bar
(966) play play. INT
2: Sub
03C7H
Reserved - - - -
(967)
0: Brightness 1
03C8H Display Bright- Indicates the display bright- 2byte
R/W 1: Brightness 2
(968) ness ness for the sensor. INT
2: Brightness 3
03C9H
Reserved - - - -
(969)
0: Disable
Active-
03CAH Indicates the operation set- 2byte 1: Output Link
Receiver Set- R/W
(970) ting for the Active receiver. INT 2: Reversed Operation
ting
3: Always On
03CBH
(971) to
Reserved - - - -
03CDH
(973)
0: English
03CEH Indicates the selected lan- 2byte 1: Japanese
Language R/W
(974) guage for the display. INT 2: Chinese
3: Deutsch
03CFH
Reserved - - - -
(975)
FS-N40/N42*/N44*
: Default value
Communication
03D4H
Reserved - - - -
(980)
Custom save area for "Pre-
[Custom]Pre-
03D5H set SaturationLevel". Indi- 2byte
set Saturation R/W 100 to 200 (Default: 110)
(981) cates the value from INT
Level
custom save execution.
0: Normal
03D6H [Custom]Cur- Custom save area for "Cur- 2byte
R/W 1: Bar
(982) rent Display rent Display". INT
2: Sub
03D7H
Reserved - - - -
(983)
[Custom]Dis- 0: Brightness 1
03D8H Custom save area for "Dis- 2byte
play Bright- R/W 1: Brightness 2
(984) play Brightness". INT
ness 2: Brightness 3
03D9H
Reserved - - - -
(985)
[Custom] 0: Disable
03DAH Active- Custom save area for 2byte 1: Output Link
R/W
(986) Receiver Set- "Active-Receiver Setting". INT 2: Reversed Operation
ting 3: Always On
03DBH
(987) to
Reserved - - - -
03DDH
(989)
0: English
03DEH [Custom]Lan- Custom save area for "Lan- 2byte 1: Japanese
R/W
(990) guage guage". INT 2: Chinese
3: Deutsch
03DFH
Reserved - - - -
(991)
Indicates the number of
03E0H Group7 Entry 2byte
items (entries) that can be R 10
(992) count UINT
set in Group 7.
03E1H
Reserved - - - -
(993)
03E2H Indicates the TAG character 8byte 8 characters or less
TAG Strings R/W
(994) string. STRING (Default: "") *2
03E3H
(995) to
Reserved - - - -
03E5H
(997)
0: Off
03E6H Indicates operating status 2byte 1: On
ECO R/W
(998) of the power save function. INT 2: Full
3: All
FS-N40/N42*/N44*
: Default value
3 03EBH
(1003) to
with the external input.
Reserved - - - -
03EFH
Communication
(1007)
[Custom] Indicates the number of
03F0H 2byte
Group7 Entry entries that can be set in R 10
(1008) UINT
count Group 7 custom save area.
03F1H
Reserved - - - -
(1009)
03F2H [Custom]TAG Custom save area for "TAG 2byte 8 characters or less
R/W
(1010) Strings strings". STRING (Default: "") *2
03F3H
(1011) to
Reserved - - - -
03F5H
(1013)
0: Off
03F6H [Custom] Custom save area for 2byte 1: On
R/W
(1014) Power Save "Power Save". INT 2: Full
3: All
03F7H Custom save area for 2byte 0: Off
[Custom]APC R/W
(1015) "APC". INT 1: On
03F8H [Custom]Dis- Custom save area for "Dis- 2byte 0: Standard
R/W
(1016) play Gain play Gain". INT 1: Full
[Custom]Inter-
03F9H Custom save area for 2byte 0: Standard
ference Pre- R/W
(1017) "Interference Prevention". INT 1: Double
vention
[Custom]
Custom save area for
03FAH Parameter 2byte 0: No
"Parameter Save by Ext. R/W
(1018) Save by Ext. INT 1: Yes
Input".
Input
03FBH
(1019) to
Reserved - - - -
03FFH
(1023)
Indicates the number of
0400H Group8 Entry 2byte
items (entries) that can be R 9
(1024) count UINT
set in Group 8.
0401H ID Number Indicates number of used 2byte FS-N40/42* : 1
R
(1025) Count IDs. INT FS-N44* : 2
0402H
Reserved - - - -
(1026)
0403H
Reserved - - - -
(1027)
0404H 2byte FS-N40/N42* : 2025
Product Code Indicates product code. R
(1028) INT FS-N44* : 2026
FS-N40/N42*/N44*
Communication
0410H 2byte
Device Type Indicates device type. R 0
(1040) INT
0411H
(1041) to
Reserved - - - -
041FH
(1055)
Reference
• [Custom]*** represents parameters that can be saved and recalled the
FS-N40 series “custom save” function.
• “Entry count” indicates the number of parameters in the same group.
FS-N40/N42*/N44*
FS-N10/N12
Refer to "How to Use NU Objects" (page 3-30) for details on using the parame-
ters.
Designate the ID number of the installed sensor for the instance ID.
: Default value
Communication
Indicates error informa-
Bit3 to 4: Reserve
0321H Error Infor- tion. When an error 2byte
R Bit5: DATUM Correction
(801) mation occurs, the correspond- WORD
Error
ing bit is turned ON.
Bit6: APC Error
Bit7: Sensor Communica-
tion Error
Indicates warning informa-
0322H Warning tion. When a warning 2byte
R Bit0: Limit Detection
(802) Information occurs, the corresponding WORD
bit is turned ON.
Indicates operating status
of the warning function.
0323H Warning 2byte
When the warning function R Bit0: Limit Detection
(803) Function WORD
is operating, the corre-
sponding bit is turned ON.
Indicates output status of
the sensor. When the
0324H 2byte
Output output is ON, the corre- R Bit0: Output
(804) WORD
sponding bit is turned
ON.
0325H Current Indicates current value of 2byte
R 0 to 9999
(805) Value received light intensity. INT
0326H
(806) to Reserved for
- - - -
0327H system
(807)
Indicates the received
light intensity before cor-
0328H 2byte
Raw Value rection with Preset, R 0 to 65535*1
(808) UINT
DATUM, or Zero-shift
functions.
Indicates the peak value
(or the max bottom value) 2byte
0329H Peak-Hold
of received light intensity R 0 to 9999
(809) Value INT
(depending on the set-
tings of Hold display).
Indicates the bottom
value (or the min peak
032AH Bottom-Hold value) of received light 2byte
R 0 to 9999
(810) Value intensity (depending on INT
the settings of Hold
display).
032BH Reserved for
- - - -
(811) system
FS-N10/N12
: Default value
032FH Slide Switch Indicates the status of the 2byte 0: Selecting SEL
R
(815) Status amplifier Slide Switch. INT 1: Selecting MEGA
Indicates the status of the
0330H Saturation 2byte 0: Not Active
saturation canceling R
(816) Canceling INT 1: Active
function.
0: RUN
Indicates the current
0331H Operation 2byte 1: LED_OFF
operation mode of the R
(817) Mode INT 2: SLEEP
sensor.
3: PAUSE
0: RUN
0332H Operation Set the operation mode 2byte 1: LED_OFF
R/W
(818) Mode Setting of the sensor. INT 2: SLEEP
3: PAUSE
0: Initialize
1: Custom
Select the Recipe to be 2: Fall
0333H Recipe used when executing an 2byte 3: Percentage Calibration
R/W
(819) Select operating command (Load INT 4: Zero-shift
Recipe Data). 5: MEGA
6: Area Detection*2
7: 0 DATUM*2
0334H
(820) to Reserved for
- - - -
033FH system
(831)
Indicates the number of
0340H Group2 Entry 2byte
entries that can be set in R 14
(832) count INT
Group 2.
Indicates the setting
Setting Value value. The upper limit of
0341H 2byte
(Output / the setting value is dis- R/W 0 to 9999 (Default: 50)
(833) INT
Area High) played when in Area
Detection mode.
0342H
(834) to Reserved for
- - - -
0343H system
(835)
Indicates the lower limit
0344H Setting Value 2byte
of the setting value in R/W 0 to 9999 (Default:50)
(836) (Area Low) INT
Area detection mode.
0345H
(837) to Reserved for
- - - -
0346H system
(838)
FS-N10/N12
: Default value
[Custom]
Group 2.
Custom save area for
3
0351H Setting Value "Setting Value". Indi- 2byte
R/W
(849) (Output/Area cates the value from cus- INT
Communication
High) tom save execution.
0352H
(849) to Reserved for
- - - -
0353H system
(850)
Custom save area for
[Custom] "Setting Value (Area
0354H 2byte
Setting Value Low)". Indicates the R/W
(852) INT
(Area Low) value from custom save
execution.
0355H
(853) to Reserved for
- - - -
0356H system
(854)
Custom save area for
[Custom]
0357H "Limit Setting Value". 2byte
Limit Setting R/W
(855) Indicates the value from INT
Value
custom save execution.
0358H
(856) to Reserved for
- - - -
035FH system
(863)
Indicates the number of
0360H Group3 Entry 2byte
items (entries) that can R 7
(864) count INT
be set in Group 3.
0: Unlock
0361H Key Lock Indicates status of Key 2byte 1: Key Lock
R/W
(865) Status lock. INT 2: PIN Code Lock
3: Communication Lock
0362H Indicates password for 2byte
PIN Code R/W 0 to 9999 (Default:0)
(866) Key lock. INT
Indicates lock status of
Slide Switch. When
0363H Slide Switch 2byte 0: Unlock
locked, the Slide Switch R/W
(867) Lock*3 INT 1: Lock
is disabled, with the value
always being "SEL".
Indicates whether the out-
put is ON for light (L-on) or
0364H L-on/D-on 2byte 0: L-on (N.O.)
ON (D-on) for dark. The R/W
(868) (N.O./N.C.) INT 1: D-on (N.C.)
corresponding bit is turned
ON for D-on or N.C..
FS-N10/N12
: Default value
0: HIGH SPEED
(Response Time 50µs)
1: FINE (Response Time
250µs)
2: TURBO (Response Time
0365H Indicates the Power 2byte 500µs)
Power Mode R/W
(869) mode. INT 3: SUPER (Response Time
1ms)
4: ULTRA (Response Time
4ms)
5: MEGA (Response Time
16ms)
3 0366H Sensitivity Indicates the sensitivity 2byte
0: Normal Sensitivity Set-
ting
R/W
(870) Setting setting method. INT 1: Percentage Calibration
Communication
2: Zero-shift Calibration
Indicates target value of
Percentage percentage calibration
0367H 2byte
Calib. Target when the Sensitivity Set- R/W -99 to 99 (Default: -10)
(871) INT
Value ting is set to Percentage
Calibration.
0368H
(872) to Reserved for
- - - -
036FH system
(879)
Indicates the number of
[Custom]
0370H items (entries) that can 2byte
Group3 Entry R 7
(880) be custom saved in INT
count
Group 3.
Custom save area for "Key
0371H [Custom] Key Lock Status". Indicates the 2byte
R/W
(881) Lock Status value from custom save INT
execution.
Custom save area for "PIN
0372H [Custom] PIN Code". Indicates the value 2byte
R/W
(882) Code from custom save execu- INT
tion.
Custom save area for
[Custom]
0373H "Slide Switch Lock". Indi- 2byte
Slide Switch R/W
(883) cates the value from cus- INT
Lock*3
tom save execution.
Custom save area for "L-
[Custom] L-
0374H on/D-on (N.O./N.C.)". 2byte
on/D-on R/W
(884) Indicates the value from INT
(N.O./N.C.)
custom save execution.
Custom save area for
0375H [Custom] "Power Mode". Indicates 2byte
R/W
(885) Power Mode the value from custom INT
save execution.
Custom save area for
[Custom]
0376H "Sensitivity Setting". Indi- 2byte
Sensitivity R/W
(886) cates the value from cus- INT
Setting
tom save execution.
Custom save area for
[Custom]
"Percentage Calib.Target
0377H Percentage 2byte
Value". Indicates the R/W
(887) Calib. Target INT
value from custom save
Value
execution.
FS-N10/N12
: Default value
0378H
(888) to Reserved for
- - - -
037FH system
(895)
Indicates the number of
0380H Group4 Entry 2byte
items (entries) that can R 9
(896) count INT
be set in Group 4.
0: Timer off
0381H Indicates the settings of 2byte 1: Off-delay Timer
Output Timer R/W
(897) the Output timer. INT 2: On-delay Timer
3: One-shot Timer
0382H
(898)
Timer Value Indicates the timer value.
2byte
INT
R/W 1 to 9999 (Default:10) 3
0383H Reserved for
- - - -
Communication
(899) system
0: Normal Detection Mode
1: DATUM1 Mode
2: DATUM2 Mode
0384H Detection Indicates the detection 2byte 3: Area Detection Mode
R/W
(900) Mode mode. INT 4: Rising Edge Detection
Mode
5: Falling Edge Detection
Mode
0: Level1 (Slow)
0385H DATUM Indicates the DATUM 2byte
R/W 1: Level2 (Normal)
(901) Speed correction speed. INT
2: Level3 (Fast)
DATUM
0386H Indicates the DATUM 2byte
Warning R/W 0 to 100 (Default: 50)
(902) alarm output level. INT
Level
0: Not use
1: External Calibration
2: Preset
0387H Indicates the control input 2byte 3: Zero-shift
Control Input R/W
(903) settings. INT 4: Reset
5: Transmission OFF
6: PAUSE Mode Transition
7: SLEEP Mode Transition
Sets the output status of 0: Always OFF
0388H PAUSE 2byte
the sensor to PAUSE R/W 1: Always ON
(904) Mode INT
mode. 2: Keep Output
0389H Light Emis- 2byte
Switch the lighting power. R/W 1 to 100 (Default: 100)
(905) sion Power INT
038AH
(906) to Reserved for
- - - -
038FH system
(911)
Indicates the number of
[Custom]
0390H items (entries) that can 2byte
Group4 Entry R 9
(912) be custom saved in INT
count
Group 4.
Custom save area for
0391H [Custom] "Output Timer". Indicates 2byte
R/W
(913) Output Timer the value from custom INT
save execution.
Custom save area for
0392H [Custom] "Timer Value". Indicates 2byte
R/W
(914) Timer Value the value from custom INT
save execution.
FS-N10/N12
: Default value
FS-N10/N12
: Default value
03B6H
(950) to Reserved for
- - - -
03BFH system
(959)
Indicates the number of
03C0H Group6 Entry 2byte
items (entries) that can R 7
(960) count INT
be set in Group 6.
03C1H Display Indicates the display 2byte 0: Normal
R/W
(961) Reverse reverse settings. INT 1: Reverse
0: None
1: Extension
03C2H
Sub Display
Indicates the sub display 2byte
R/W
2: Bar
3: Excess Gain (%)
3
(962) details. INT 4: Light Intensity HOLD
5: Excess Gain HOLD (%)
Communication
6: L-on/D-on
7: TAG Strings
0: Normal
Indicates hold details
1: Peak Max. / Peak Min.
when the received light
03C3H 2byte 2: Bottom Max. / Bottom
Hold Display intensity hold display is R/W
(963) INT Min.
selected under the Sub
3: Peak Min. / Bottom Max.
display.
4: Peak Max. / Bottom Min.
Indicates whether the
current value of received
03C4H Preset Satu- 2byte 0: Off
light intensity is satu- R/W
(964) ration INT 1: On
rated when the Preset or
DATUM function is used.
03C5H Preset Satu- Indicates the Preset satu- 2byte
R/W 100 to 200 (Default:110)
(965) ration Level ration level. INT
03C6H Current Dis- Indicates the current dis- 2byte 0: Normal
R/W
(966) play play. INT 1: Sub
03C7H
(967) to Reserved for
- - - -
03CFH system
(975)
Indicates the number of
[Custom]
03D0H items (entries) that can 2byte
Group6 Entry R 7
(976) be custom saved in INT
count
Group 6.
Custom save area for the
03D1H [Custom] Dis- "Display Reverse". Indi- 2byte
R/W
(977) play Reverse cates the value from cus- INT
tom save execution.
Custom save area for
03D2H [Custom] Sub "Sub Display". Indicates 2byte
R/W
(978) Display the value from custom INT
save execution.
Custom save area for
03D3H [Custom] "Hold Display". Indicates 2byte
R/W
(979) Hold Display the value from custom INT
save execution.
Custom save area for
[Custom]
03D4H "Preset Saturation". Indi- 2byte
Preset Satu- R/W
(980) cates the value from cus- INT
ration
tom save execution.
FS-N10/N12
: Default value
FS-N10/N12
: Default value
Communication
execution.
Custom save area for
03F8H [Custom] Dis- "Display Gain". Indicates 2byte
R/W
(1016) play Gain the value from custom INT
save execution.
Custom save area for
[Custom] "Interference
03F9H 2byte
Interference Prevention". Indicates the R/W
(1017) INT
Prevention value from custom save
execution.
Custom save area for
[Custom]
"Parameter Save by Ext-
03FAH Parameter 2byte
input". Indicates the R/W
(1018) Save by Ext- INT
value from custom save
Input
execution.
03FBH
(1019) to Reserved for
- - - -
03FFH system
(1023)
Indicates the number of
0400H Group8 Entry 2byte
items (entries) that can R 20
(1024) count INT
be set in Group 8.
0401H ID number Indicates number of used 2byte
R 1
(1025) Count IDs. INT
0402H
(1026) to Reserved for
- - - -
0403H system
(1027)
0404H Product 2byte
Indicates product code. R 2000
(1028) Code INT
Indicates revision, with
the upper bytes
0405H representing the major 2byte
Revision R 0101H to FFFFH
(1029) revision and the lower INT
bytes representing the
minor revision.
0406H Product Indicates model designa-
STRING R "FS-N10/N12 *"
(1030) Name tion of the sensor.
0407H
(1031) to Reserved for
- - - -
040DH system
(1037)
FS-N10/N12
: Default value
040EH 2byte
Series Code Indicates series code. R 2000
(1038) INT
040FH Series 2byte
Indicates series version. R 1
(1039) Version INT
0410H 2byte
Device Type Indicates device type. R 0
(1040) INT
0411H
(1041) to Reserved for
- - - -
041FH system
(1055)
3 *1 The FS-N10 Series shipped on March 10, 2011 or before will have the range from
0 to 9999.
*2 This cannot be set with the FS-N10 Series shipped on March 10, 2011 or before.
Communication
*3 If the slide switch is set to “MEGA” while locked, [] will flash on the sensor
amplifier.
FS-N10/N12
Communication
0305H(773)
Calibration (1st) bration.
Two-point Calibra- Starts calibration the 2nd point of 2-point cali-
0306H(774)
tion (2nd) bration.
Positioning Cali- Starts calibration the 1st point of positioning
0305H(773)
bration (1st) calibration.
Positioning Cali- Starts calibration the 2nd point of positioning
0307H(775)
bration (2nd) calibration.
Full Auto Calibra-
0308H(776) Starts fully automatic calibration.
tion start
Full Auto Calibra-
0309H(777) Ends fully automatic calibration.
tion end
030AH(778) Zero-shift start Executes zero shift.
030BH(779) Zero-shift end Cancels zero shift.
030CH(780) Preset start Executes preset.
030DH(781) Preset end Cancels preset.
Saturation
030EH(782) Executes saturation canceling.
Canceling start
Saturation
030FH(783) Cancels saturation canceling.
Canceling end
0310H(784) Reset Hold Value Resets the held value.
Work-Preset
0311H (785) Executes workpiece preset.
Request*1
Full Auto Preset: Starts fully automatic (or maximum sensitivity)
0312H(786)
Start*1 preset.
Full Auto Preset: Ends fully automatic (or maximum sensitivity)
0313H(787)
Finish*1 preset.
Maximum Sensi- Executes maximum sensitivity preset. (Preset
0314H(788) tivity Preset: can be executed without specifying the start
Request*1 and end.)
*1 This cannot be set with the FS-N10 Series shipped on March 10, 2011 or before.
FS-N14
Refer to "How to Use NU Objects" (page 3-30) for how to use the parameters.
Designate the ID number of the installed sensor for the instance ID.
: Default value
Error
ON.
Bit6: APC Error
Bit7: Sensor Communica-
tion Error
Indicates warning infor-
0322H Warning mation. When a warning 2byte
R Bit0: Limit Detection
(802) Information occurs, the correspond- WORD
ing bit is turned ON.
Indicates the operating
status of the warning func-
0323H Warning tion. When the warning 2byte
R Bit0: Limit Detection
(803) Function function is operating, the WORD
corresponding bit is turned
ON.
Indicates the output sta-
tus of the sensor. When
0324H 2byte Bit0: Output1
Output the output is ON, the cor- R
(804) WORD Bit1: Output2
responding bit is turned
ON.
Indicates the current
0325H Current 2byte
value of received light R 0 to 9999
(805) Value INT
intensity.
0326H
(806) to Reserved for
- - - -
0327H system
(807)
Indicates the received
light intensity before cor-
0328H 2byte
Raw Value rection with the Preset, R 0 to 65535*1
(808) UINT
DATUM, or Zero-shift
functions.
Indicates the peak value
(or the max bottom value)
0329H Peak-Hold 2byte
of received light intensity R 0 to 9999
(809) Value INT
(depending on the set-
tings of Hold display).
Indicates the bottom value
(or the min peak value) of
032AH Bottom-Hold 2byte
received light intensity R 0 to 9999
(810) Value INT
(depending on the set-
tings of Hold display).
032BH Reserved for
- - - -
(811) system
FS-N14
: Default value
Communication
032FH Slide Switch Indicates the status of the 2byte 0: Selecting CH1
R
(815) Status Slide Switch. INT 1: Selecting CH2
Indicates the status of the
0330H Saturation 2byte 0: Not Active
saturation canceling R
(816) Canceling INT 1: Active
function.
0: RUN
Indicates the current
0331H Operation 2byte 1: LED_OFF
operation mode of the R
(817) Mode INT 2: SLEEP
sensor.
3: PAUSE
0: RUN
0332H Operation Set the operation mode 2byte 1: LED_OFF
R/W
(818) Mode Setting of the sensor. INT 2: SLEEP
3: PAUSE
0: Initialize
1: Custom
Select the Recipe to be 2: Fall
0333H Recipe used when executing an 2byte 3: Percentage Calibration
R/W
(819) Select operating command INT 4: Zero-shift
(Load Recipe Data). 5: MEGA
6: Area Detection*2
7: 0 DATUM*2
0334H
(820) to Reserved for
- - - -
033FH system
(831)
Indicates the number of
0340H Group2 Entry 2byte
entries that can be set in R 14
(832) count INT
Group 2.
Indicates the setting
Setting Value value of Output 1. The
0341H 2byte
(Output1/ upper limit of the setting R/W 0 to 9999 (Default:50)
(833) INT
Area High) value is displayed when
in Area Detection mode.
0342H Setting Value Indicates the setting 2byte
R/W 0 to 9999 (Default: 50)
(834) (Output2) value of Output 2. INT
0343H Reserved for
- - - -
(835) system
Indicates the lower limit
0344H Setting Value 2byte
of the setting value in R/W 0 to 9999 (Default:50)
(836) (Area Low) INT
Area detection mode.
0345H
(837) to Reserved for
- - - -
0346H system
(838)
FS-N14
: Default value
[Custom]
area.
Custom save area for
"Setting Value (Output
0351H Setting Value 2byte
1)". Indicates the value R/W
Communication
FS-N14
: Default value
Communication
1 ms)
4: ULTRA (Response Time
4 ms)
5: MEGA (Response Time
16 ms)
0: Normal Sensitivity Set-
0366H Sensitivity Indicates the sensitivity 2byte ting
R/W
(870) Setting setting method. INT 1: Percentage Calibration
2: Zero-shift Calibration
Indicates target value of
Percentage percentage calibration
0367H 2byte
Calib. Target when the Sensitivity Set- R/W -99 to 99 (Default: -10)
(871) INT
Value ting is set to Percentage
Calibration.
0368H
(872) to Reserved for
- - - -
036FH system
(879)
Indicates the number of
[Custom]
0370H entries that can be set in 2byte
Group 3 R 7
(880) Group 3 custom save INT
Entry count
area.
Custom save area for
0371H [Custom] Key "Key Lock Status". Indi- 2byte
R/W
(881) Lock Status cates the value from cus- INT
tom save execution.
Custom save area for
0372H [Custom] PIN "PIN Code". Indicates the 2byte
R/W
(882) Code value from custom save INT
execution.
Custom save area for
[Custom]
0373H "Slide Switch Lock". Indi- 2byte
Slide Switch R/W
(883) cates the value from cus- INT
Lock*3
tom save execution.
Custom save area for "L-
[Custom] L-
0374H on/D-on (N.O./N.C.). Indi- 2byte
on/D-on R/W
(884) cates the value from cus- INT
(N.O./N.C.)
tom save execution.
Custom save area for the
0375H [Custom] "Power Mode". Indicates 2byte
R/W
(885) Power Mode the value from custom INT
save execution.
FS-N14
: Default value
FS-N14
: Default value
Communication
Custom save area for
[Custom]
"Detection Mode (Output
0394H Detection 2byte
1)". Indicates the value R/W
(916) Mode INT
from custom save execu-
(Output1)
tion.
Custom save area for
[Custom]
0395H "DATUM Speed". Indi- 2byte
DATUM R/W
(917) cates the value from cus- INT
Speed
tom save execution.
Custom save area for
[Custom]
"DATUM Warning
0396H DATUM 2byte
Level". Indicates the R/W
(918) Warning INT
value from custom save
Level
execution.
Custom save area for
0397H [Custom] "Control Input". Indicates 2byte
R/W
(919) Control Input the value from custom INT
save execution.
Custom save area for
[Custom]
0398H "PAUSE Mode". Indi- 2byte
PAUSE R/W
(920) cates the value from cus- INT
Mode
tom save execution.
Custom save area for
[Custom]
0399H "Light Emission Power". 2byte
Light Emis- R/W
(921) Indicates the value from INT
sion Power
custom save execution.
039AH
(922) to Reserved for
- - - -
039FH system
(927)
Indicates the number of
03A0H Group5 Entry 2byte
entries that can be set in R 6
(928) count INT
Group 5.
0: Timer off
03A1H Output Timer Indicates the settings of 2byte 1: Off-delay Timer
R/W
(929) (Output2) the Output 2 timer. INT 2: On-delay Timer
3: One-shot Timer
03A2H Timer Value Indicates the timer value 2byte
R/W 1 to 9999 (Default:10)
(930) (Output2) for the Output 2 timer. INT
03A3H Reserved for
- - - -
(931) system
FS-N14
: Default value
FS-N14
: Default value
Communication
03D0H entries that can be set in 2byte
Group 6 R 7
(976) Group 6 custom save INT
Entry count
area.
Custom save area for the
03D1H [Custom] Dis- "Display Reverse". Indi- 2byte
R/W
(977) play Reverse cates the value from cus- INT
tom save execution.
Custom save area for
03D2H [Custom] Sub "Sub Display". Indicates 2byte
R/W
(978) Display the value from custom INT
save execution.
Custom save area for
03D3H [Custom] "Hold Display". Indicates 2byte
R/W
(979) Hold Display the value from custom INT
save execution.
Custom save area for
[Custom]
03D4H "Preset Saturation". Indi- 2byte
Preset Satu- R/W
(980) cates the value from cus- INT
ration
tom save execution.
Custom save area for
[Custom] "Preset Saturation
03D5H 2byte
Preset Satu- Level". Indicates the R/W
(981) INT
ration Level value from custom save
execution.
Custom save area for
[Custom]
03D6H "Current Display". Indi- 2byte
Current Dis- R/W
(982) cates the value from cus- INT
play
tom save execution.
03D7H
(983) to Reserved for
- - - -
03DFH system
(991)
Indicates the number of
03E0H Group7 Entry 2byte
items (entries) that can R 11
(992) count INT
be set in Group 7.
Indicates the settings of
the disabled warning
03E1H Warning Dis- 2byte
function. When the bit is R/W Bit0: Limit Detection
(993) able WORD
ON, the corresponding
warning does not occur.
03E2H Indicates the TAG char- 8 characters or less
TAG Strings STRING R/W
(994) acter string. (Default : "")
FS-N14
: Default value
FS-N14
: Default value
0401H
count
ID number
be set in Group 8.
Indicates number of used
INT
2byte
R 2
3
(1025) Count IDs. INT
Communication
0402H
(1026) to Reserved for
- - - -
0403H system
(1027)
0404H Product 2byte
Indicates product code. R 2001
(1028) Code INT
Indicates revision, with
the upper bytes repre-
0405H senting the major revision 2byte
Revision R 0101H to FFFFH
(1029) and the lower bytes rep- INT
resenting the minor revi-
sion.
0406H Product Indicates model designa-
STRING R "FS-N14"
(1030) Name tion of the sensor.
0407H
(1031) to Reserved for
- - - -
040DH system
(1037)
040EH 2byte
Series Code Indicates series code. R 2001
(1038) INT
040FH Series Ver- 2byte
Indicates series version. R 1
(1039) sion INT
0410H 2byte
Device Type Indicates device type. R 0
(1040) INT
0411H
(1041) to Reserved for
- - - -
041FH system
(1055)
*1 The FS-N10 Series shipped on March 10, 2011 or before will have the range from
0 to 9999.
*2 This cannot be set with the FS-N10 Series shipped on March 10, 2011 or before.
*3 If the slide switch is set to “2ch” while locked, [] will flash on the sensor
amplifier.
FS-N14
*1 This cannot be set with the FS-N10 Series shipped on March 10, 2011 or before.
LV-N10/N12/N12C
Refer to "How to Use NU Objects" (page 3-30) for details on reading the table
and using the parameters.
Designate the ID number of the installed sensor for the instance ID.
: Default value
Communication
0321H Error Infor- When an error occurs, the 2byte Bit4: Reserve
R
(801) mation corresponding bit is turned WORD Bit5: DATUM Correction
ON. Error
Bit6: Reserve
Bit7: Sensor Communica-
tion Error
Indicates warning infor-
0322H Warning mation. When a warning 2byte
R Bit0: Limit Detection
(802) Information occurs, the correspond- WORD
ing bit is turned ON.
Indicates the operating
status of the warning func-
0323H Warning tion. When the warning 2byte
R Bit0: Limit Detection
(803) Function function is operating, the WORD
corresponding bit is turned
ON.
Indicates the output sta-
0324H tus of the sensor. When 2byte Bit0: Output1
Output the output is ON, the cor- R
(804)
responding bit is turned
WORD Bit1: Output2*1
ON.
Indicates the current
0325H Current 2byte
value of received light R 0 to 9999
(805) Value INT
intensity.
0326H
(806) to Reserved for
- - - -
0327H system
(807)
Indicates the received
light intensity before cor-
0328H 2byte
Raw Value rection with the Preset, R 0 to 65535
(808) UINT
DATUM, or Zero-shift
functions.
Indicates the peak value
(or the max bottom value)
0329H Peak-Hold 2byte
of received light intensity R 0 to 9999
(809) Value INT
(depending on the set-
tings of Hold display).
Indicates the bottom value
(or the min peak value) of
032AH Bottom-Hold 2byte
received light intensity R 0 to 9999
(810) Value INT
(depending on the set-
tings of Hold display).
032BH Reserved for
- - - -
(811) system
LV-N10/N12/N12C
: Default value
LV-N10/N12/N12C
: Default value
[Custom]
Indicates the number of
3
0350H entries that can be set in 2byte
Group 2 R 14
(848) Group 2 custom save INT
Communication
Entry count
area.
Custom save area for
[Custom]
"Setting Value (Output 1/
0351H Setting Value 2byte
Area High)". Indicates the R/W
(849) (Output 1/ INT
value from custom save
Area High)
execution.
Custom save area for
[Custom] "Setting Value (Output 2/
Setting Value
0352H
(Output 2/ Counter Setting Value)*1 2byte
R/W
(850) ". Indicates the value INT
Counter Set-
ting Value) from custom save execu-
tion.
0353H Reserved for
- - - -
(851) system
Custom save area for
[Custom] "Setting Value (Area
0354H 2byte
Setting Value Low)". Indicates the R/W
(852) INT
(Area Low) value from custom save
execution.
0355H
(853) to Reserved for
- - - -
0356H system
(854)
Custom save area for
[Custom]
0357H "Limit Setting Value". 2byte
Limit Setting R/W
(855) Indicates the value from INT
Value
custom save execution.
0358H
(856) to Reserved for
- - - -
035FH system
(863)
Indicates number of
0360H Group3 Entry 2byte
entries that can be set in R 7
(864) count INT
Group 3.
0: Unlock
0361H Key Lock Indicates status of the 2byte 1: Key Lock
R/W
(865) Status Key lock. INT 2: PIN Code Lock
3: Communication Lock
0362H Indicates password for 2byte
PIN Code R/W 0 to 9999 (Default:0)
(866) Key lock. INT
LV-N10/N12/N12C
: Default value
0: HIGH SPEED
(Response Time 80 s)
1: FINE (Response Time
250 s)
2: TURBO (Response Time
0365H 2byte 500 s)
Power Mode Indicates Power mode. R/W
(869) INT 3: SUPER (Response Time
1 ms)
4: ULTRA (Response Time
4 ms)
5: MEGA (Response Time
16 ms)
0: Normal Sensitivity Set-
0366H Sensitivity Indicates setting method 2byte ting
R/W
(870) Setting of Sensitivity. INT 1: Percentage Calibration
2: Zero-shift Calibration
Indicates target value of
Percentage percentage calibration
0367H 2byte
Calib. Target when the Sensitivity Set- R/W -99 to 99 (Default: -10)
(871) INT
Value ting is set to Percentage
Calibration.
0368H
(872) to Reserved for
- - - -
036FH system
(879)
Indicates the number of
[Custom]
0370H entries that can be set in 2byte
Group 3 R 7
(880) Group 3 custom save INT
Entry count
area.
Custom save area for
0371H [Custom] Key "Key Lock Status". Indi- 2byte
R/W
(881) Lock Status cates the value from cus- INT
tom save execution.
Custom save area for
0372H [Custom] PIN "PIN Code". Indicates the 2byte
R/W
(882) Code value from custom save INT
execution.
Custom save area for
[Custom]
0373H "Slide Switch Lock". Indi- 2byte
Slide Switch R/W
(883) cates the value from cus- INT
Lock
tom save execution.
LV-N10/N12/N12C
: Default value
[Custom]
tom save execution.
Custom save area for the
3
"Percentage Calib.
0377H Percentage 2byte
Target Value". Indicates R/W
Communication
(887) Calib. Target INT
the value from custom
Value
save execution.
0378H
(888) to Reserved for
- - - -
037FH system
(895)
Indicates the number of
0380H Group4 Entry 2byte
entries that can be set in R 9
(896) count INT
Group 4.
0: Timer off
0381H Output Timer Indicates settings of Out- 2byte 1: Off-delay Timer
R/W
(897) (Output1) put 1 timer. INT 2: On-delay Timer
3: One-shot Timer
0382H Timer Value Indicates time of Output 1 2byte
R/W 1 to 9999 (Default: 10)
(898) (Output1) timer (unit: ms). INT
0383H Reserved for
- - - -
(899) system
0: Normal Detection Mode
1: DATUM1 Mode
2: DATUM2 Mode
Detection
0384H Indicates detection mode 2byte 3: Area Detection Mode
Mode R/W
(900) of Output 1. INT 4: Rising Edge Detection
(Output1)
Mode
5: Falling Edge Detection
Mode
0: Level1 (Slow)
0385H DATUM Indicates correction 2byte
R/W 1: Level2 (Normal)
(901) Speed speed of DATUM. INT
2: Level3 (Fast)
DATUM
0386H Indicates alarm output 2byte
Warning R/W 0 to 100 (Default:50)
(902) level of DATUM. INT
Level
0: Not use
1: External Calibration
2: Preset
0387H External Indicates settings of 2byte 3: Zero-shift
R/W
(903) Input external input. INT 4: Reset
5: Transmission OFF
6: PAUSE Mode Transition
7: SLEEP Mode Transition
Set up the output status 0: Always OFF
0388H PAUSE 2byte
of the sensor in PAUSE R/W 1: Always ON
(904) Mode INT
mode. 2: Keep Output
LV-N10/N12/N12C
: Default value
LV-N10/N12/N12C
: Default value
Communication
(944) Group 5 custom save INT
Entry count
area.
Custom area for "Output
[Custom]
03B1H Output Timer Timer (Output 2)*1". Indi- 2byte
R/W
(945) cates the value from cus- INT
(Output 2)*1
tom save execution.
Custom save area for
[Custom]
03B2H Timer Value "Timer Value (Otput 2)*1". 2byte
R/W
(946) Indicates the value from INT
(Output2)*1
custom save execution.
03B3H Reserved for
- - - -
(947) system
Custom save area for
[Custom]
"Detection Mode (Output
03B4H Detection 2byte
(948) Mode 2)*1". Indicates the value INT
R/W
from custom save execu-
(Output2)*1
tion.
Custom save area for
[Custom] 2byte
03B5H "Limit Output Mode". Indi-
Limit Output R/W
(949) cates the value from cus- INT
Mode
tom save execution.
Custom save area for
03B6H [Custom] "Counter Type*1". Indicates 2byte
R/W
(950) Counter Type*1 the value from custom save INT
execution.
03B7H
(951) to Reserved for
- - - -
03BFH system
(959)
Indicates the number of
03C0H Group6 Entry 2byte
entries that can be set in R 7
(960) count INT
Group 6.
03C1H Display Indicates settings of dis- 2byte 0: Normal
R/W
(961) Reverse play reverse. INT 1: Reverse
0: None
1: Extension
2: Bar
03C2H Indicates details of the 2byte 3: Excess Gain (%)
Sub Display R/W
(962) sub display. INT 4: Light Intensity HOLD
5: Excess Gain HOLD (%)
6: L-on/D-on
7: TAG Strings
LV-N10/N12/N12C
: Default value
3 03C5H
(965)
Preset Satu-
ration Level
Indicates saturation level
of Preset.
2byte
INT
R/W 100 to 200 (Default:110)
LV-N10/N12/N12C
: Default value
Communication
Indicates operating sta-
03E6H 2byte 1: ON
Power Save tus of power save func- R/W
(998) INT 2: FULL
tion.
3: ALL
03E7H Reserved for
- - - -
(999) system
03E8H Indicates display gain 2byte 0: Standard
Display Gain R/W
(1000) setting. INT 1: Full
Indicates that whether
03E9H Interference number of interference 2byte 0: Normal
R/W
(1001) Prevention prevention devices is INT 1: Double
doubled.
Indicates that whether
the Preset/Zero-shift set-
Parameter
03EAH tings are stored in 2byte 0: No
Save by Ext- R/W
(1002) EEPROM when execut- INT 1: Yes
Input
ing Preset/Zero-shift with
external input.
03EBH 2byte 0: Standard
Sensitivity Set up the Sensitivity. R/W
(1003) INT 1: High Resolution
03ECH
(1004) to Reserved for
- - - -
03EFH system
(1007)
Indicates the number of
[Custom]
03F0H entries that can be set in 2byte
Group 7 R 11
(1008) Group 7 custom save INT
Entry count
area.
Custom save area for
[Custom]
03F1H "Warning Disable". Indi- 2byte
Warning Dis- R/W
(1009) cates the value from cus- INT
able
tom save execution.
Custom save area for
03F2H [Custom] "TAG Strings". Indicates
STRING R/W
(1010) TAG Strings the value from custom
save execution.
03F3H
(1011) to Reserved for
- - - -
03F5H system
(1013)
Custom save area for
03F6H [Custom] "Power Save". Indicates 2byte
R/W
(1014) Power Save the value from custom INT
save execution.
LV-N10/N12/N12C
: Default value
Input
execution.
Custom save area for
03FBH [Custom] "Sensitivity". 2byte
R/W
(1019) Sensitivity Indicates the value from INT
custom save execution.
03FCH
(1020) to Reserved for
- - - -
03FFH system
(1023)
Indicates the number of
0400H Group8 Entry 2byte
items (entries) that can R 20
(1024) count INT
be set in Group 8.
0401H ID number Indicates number of used 2byte (LV-N10/N12C*) 1
R
(1025) Count IDs. INT (LV-N12*) 2
1: LV-S71
2: LV-S61
3: LV-S72
4: LV-S62
5: LV-S41/LV-S41L
0402H Indicates connected 2byte 6: LV-S31
Head Type R
(1026) head type. INT 8: LV-S63
9: LV-NH37/NH42
10: LV-NH32/NH35
11: LV-NH100/NH110
12: LV-NH300
13: LV-NH62
0403H Reserved for
- - - -
(1027) system
0404H Product 2byte (LV-N10/N12C*) 2003
Indicates product code. R
(1028) Code INT (LV-N12) 2004
Indicates revision, with the
upper bytes representing
0405H 2byte
Revision the major revision and the R 0101H to FFFFH
(1029) INT
lower bytes representing
the minor revision.
(LV-N10/N12C*) "LV-N10/
0406H Product Indicates model designa-
STRING R N12C*"
(1030) Name tion of the sensor.
(LV-N12*) "LV-N12*"
0407H
(1031) to Reserved for
- - - -
040DH system
(1037)
040EH 2byte (LV-N10/N12C*) 2003
Series Code Indicates series code. R
(1038) INT (LV-N12) 2004
LV-N10/N12/N12C
: Default value
Communication
Reference
series "custom save" and "user reset function".
• "Entry count" indicates the number of parameters in the same group.
LV-N10/N12/N12C
bration tivity.
Two-point/Pos. Starts calibration the 1st point of 2-point calibra-
0305H(773)
Calibration: 1st tion.
Two-point Cali- Starts calibration the 2nd point of 2-point cali-
0306H(774)
bration: 2nd bration.
Positioning Cali- Starts calibration the 1st point of positioning cal-
0305H(773)
bration: 1st ibration.
Positioning Cali- Starts calibration the 2nd point of positioning
0307H(775)
bration: 2nd calibration.
Full Auto Cali-
0308H(776) Starts fully automatic calibration.
bration: Start
Full Auto Cali-
0309H(777) Ends fully automatic calibration.
bration: Finish
Zero-shift
030AH(778) Executes zero shift.
Request
030BH(779) Zero-shift Cancel Cancels zero shift.
030CH(780) Preset Request Executes preset.
030DH(781) Preset Cancel Cancels preset.
Reset Hold
0310H(784) Resets the held value.
Value
Work-Preset
0311H (785) Executes workpiece preset.
Request
Full Auto Preset: Starts fully automatic (or maximum sensitivity)
0312H(786)
Start preset.
Full Auto Preset: Ends fully automatic (or maximum sensitivity)
0313H(787)
Finish preset.
Maximum Sensi- Executes maximum sensitivity preset. (Preset
0314H(788) tivity Preset: can be executed without specifying the start
Request and end.)
Reset Counter
0315H (789) Resets the counter value. (Cable type only)
Value
PS-N10/N12
Refer to "How to Use NU Objects" (page 3-30) for how to use the parameters.
Designate the ID number of the installed sensor for the instance ID.
: Default value
Communication
ON. Error
Bit6: Reserve
Bit7: Sensor Communica-
tion Error
Indicates warning infor-
0322H Warning mation. When a warning 2byte
R Bit0: Limit Detection
(802) Information occurs, the correspond- WORD
ing bit is turned ON.
Indicates the operating
status of the warning func-
0323H Warning tion. When the warning 2byte
R Bit0: Limit Detection
(803) Function function is operating, the WORD
corresponding bit is turned
ON.
Indicates the output sta-
0324H tus of the sensor. When
2byte
Output the output is ON, the cor- R Bit0: Output
(804) WORD
responding bit is turned
ON.
Indicates the current
0325H Current 2byte
value of received light R 0 to 9999
(805) Value INT
intensity.
0326H
(806) to Reserved for
- - - -
0327H system
(807)
Indicates the received
light intensity before cor-
0328H 2byte
Raw Value rection with the Preset, R 0 to 65535
(808) UINT
DATUM, or Zero-shift
functions.
Indicates the peak value
(or the max bottom value)
0329H Peak-Hold 2byte
of received light intensity R 0 to 9999
(809) Value INT
(depending on the set-
tings of Hold display).
Indicates the bottom value
(or the min peak value) of
032AH Bottom-Hold 2byte
received light intensity R 0 to 9999
(810) Value INT
(depending on the set-
tings of Hold display).
032BH Reserved for
- - - -
(811) system
PS-N10/N12
: Default value
3 032EH
(814)
Display Cus-
tomize
Indicates operating sta-
tus of the Reading Cor-
rection function.
2byte
INT
R
1: Preset
2: Zero-shift
3: Work preset
4: Work preset (Reverse)
032FH Slide Switch Indicates status of the 2byte 0: Selecting ch
Communication
R
(815) Status Slide Switch. INT 1: Selecting ch
0330H Reserved for
- - - -
(816) system
0: RUN
0331H Operation Indicates current opera- 2byte 1: LED_OFF
R
(817) Mode tion mode of the sensor. INT 2: SLEEP
3: PAUSE
0: RUN
0332H Operation Set up the operation 2byte 1: LED_OFF
R/W
(818) Mode Setting mode of the sensor. INT 2: SLEEP
3: PAUSE
0: Initialize
1: Custom
Select Recipe to be used 2: Fall
0333H Recipe when executing operat- 2byte 3: Percentage Calibration
R/W
(819) Select ing command (Load Rec- INT 4: Zero-shift
ipe Data). 5: MEGA
6: AREA
7: 0 DATUM
0334H
(820) to Reserved for
- - - -
033FH system
(831)
Indicates the number of
0340H Group2 Entry 2byte
entries that can be set in R 14
(832) count INT
Group 2.
Indicates setting value of
Setting Value Output. The upper limit of
0341H 2byte
(Output/Area the setting value is dis- R/W 0 to 9999 (Default:50)
(833) INT
High) played when the "Detec-
tion Mode" is Area.
0342H
(834) to Reserved for
- - - -
0343H system
(835)
Indicates lower limit of
0344H Setting Value 2byte
setting value in Area R/W 0 to 9999 (Default:50)
(836) (Area Low) INT
detection mode.
0345H
(837) to Reserved for
- - - -
0346H system
(838)
PS-N10/N12
: Default value
[Custom]
area.
Custom save area for
3
"Setting Value (Output/
0351H Setting Value 2byte
Area High)". Indicates the R/W
Communication
(849) (Output/Area INT
value from custom save
High)
execution.
0352H
(850) to Reserved for
- - - -
0353H system
(851)
Custom save area for
[Custom] "Setting Value (Area
0354H 2byte
Setting Value Low)". Indicates the R/W
(852) INT
(Area Low) value from custom save
execution.
0355H
(853) to Reserved for
- - - -
0356H system
(854)
Custom save area for
[Custom]
0357H "Limit Setting Value". 2byte
Limit Setting R/W
(855) Indicates the value from INT
Value
custom save execution.
0358H
(856) to Reserved for
- - - -
035FH system
(863)
Indicates number of
0360H Group3 Entry 2byte
entries that can be set in R 7
(864) count INT
Group 3.
0: Unlock
0361H Key Lock Indicates status of the 2byte 1: Key Lock
R/W
(865) Status Key lock. INT 2: PIN Code Lock
3: Communication Lock
0362H Indicates password for 2byte
PIN Code R/W 0 to 9999 (Default:0)
(866) Key lock. INT
Indicates lock status of
Slide Switch. When being
0363H Slide Switch 2byte 0: Unlock
locked, the Slide Switch R/W
(867) Lock INT 1: Lock
is disabled, with the value
always being.*1
Indicates that whether
0364H L-on/D-on 2byte 0: L-on (N.O.)
output is ON for light (L- R/W
(868) (N.O./N.C.) INT 1: D-on (N.C.)
on) or ON (D-on) for dark.
PS-N10/N12
: Default value
PS-N10/N12
: Default value
Communication
0384H Detection Indicates detection mode 2byte 3: Area Detection Mode
R/W
(900) Mode of Output. INT 4: Rising Edge Detection
Mode
5: Falling Edge Detection
Mode
0: Level1 (Slow)
0385H DATUM Indicates correction 2byte
R/W 1: Level2 (Normal)
(901) Speed speed of DATUM. INT
2: Level3 (Fast)
DATUM
0386H Indicates alarm output 2byte
Warning R/W 0 to 100 (Default:50)
(902) level of DATUM. INT
Level
0: Not use
1: External Calibration
2: Preset
0387H External Indicates settings of 2byte 3: Zero-shift
R/W
(903) Input external input. INT 4: Reset
5: Transmission OFF
6: PAUSE Mode Transition
7: SLEEP Mode Transition
Set up the output status 0: Always OFF
0388H PAUSE 2byte
of the sensor in PAUSE R/W 1: Always ON
(904) Mode INT
mode. 2: Keep Output
389H
(905) to Reserved for
- - - -
038FH system
(911)
Indicates the number of
[Custom]
0390H entries that can be set in 2byte
Group 4 R 9
(912) Group 4 custom save INT
Entry count
area.
Custom save area for
0391H [Custom] "Output Timer". Indicates 2byte
R/W
(913) Output Timer the value from custom INT
save execution.
Custom save area for
0392H [Custom] "Timer Value". Indicates 2byte
R/W
(914) Timer Value the value from custom INT
save execution.
0393H Reserved for
- - - -
(915) system
Custom save area for
[Custom]
0394H "Detection Mode". Indi- 2byte
Detection R/W
(916) cates the value from cus- INT
Mode
tom save execution.
PS-N10/N12
: Default value
PAUSE R/W
(920) cates the value from cus- INT
Mode
tom save execution.
0399H
(921) to Reserved for
- - - -
039FH system
(927)
Indicates the number of
03A0H Group5 Entry 2byte
entries that can be set in R 6
(928) count INT
Group 5.
03A1H
(929) to Reserved for
- - - -
03A4H system
(932)
03A5H Limit Output Indicates reset method of 2byte 0: Manual
R/W
(933) Mode limit output. INT 1: Auto
03A6H
(934) to Reserved for
- - - -
03AFH system
(943)
Indicates the number of
[Custom]
03B0H entries that can be set in 2byte
Group 5 R 6
(944) Group 5 custom save INT
Entry count
area.
03B1H
(945) to Reserved for
- - - -
03B4H system
(948)
Custom save area for
[Custom]
03B5H "Limit Output Mode". Indi- 2byte
Limit Output R/W
(949) cates the value from cus- INT
Mode
tom save execution.
03B6H
(950) to Reserved for
- - - -
03BFH system
(959)
Indicates the number of
03C0H Group6 Entry 2byte
entries that can be set in R 6
(960) count INT
Group 6.
03C1H Display Indicates settings of dis- 2byte 0: Normal
R/W
(961) Reverse play reverse. INT 1: Reverse
PS-N10/N12
: Default value
Communication
the current value of
03C4H Preset Satu- 2byte 0: Off
received light intensity is R/W
(964) ration INT 1: On
saturated when Preset or
DATUM function is used.
03C5H Preset Satu- Indicates saturation level 2byte
R/W 100 to 200 (Default:110)
(965) ration Level of Preset. INT
03C6H Current Dis- 2byte 0: Normal
Indicates current display. R/W
(966) play INT 1: Sub
03C7H
(967) to Reserved for
- - - -
03CFH system
(975)
[Custom] Indicates the number of
03D0H 2byte
Group 6 entries that can be set in R 6
(976) INT
Entry count Group 6 custom save area.
Custom save area for the
03D1H [Custom] Dis- "Display Reverse". Indi- 2byte
R/W
(977) play Reverse cates the value from cus- INT
tom save execution.
Custom save area for
03D2H [Custom] Sub "Sub Display". Indicates 2byte
R/W
(978) Display the value from custom INT
save execution.
Custom save area for
03D3H [Custom] "Hold Display". Indicates 2byte
R/W
(979) Hold Display the value from custom INT
save execution.
Custom save area for
[Custom]
03D4H "Preset Saturation". Indi- 2byte
Preset Satu- R/W
(980) cates the value from cus- INT
ration
tom save execution.
Custom save area for
[Custom] "Preset Saturation
03D5H 2byte
Preset Satu- Level". Indicates the R/W
(981) INT
ration Level value from custom save
execution.
Custom save area for
[Custom]
03D6H "Current Display". Indi- 2byte
Current Dis- R/W
(982) cates the value from cus- INT
play
tom save execution.
03D7H
(983) to Reserved for
- - - -
03DFH system
(991)
PS-N10/N12
: Default value
PS-N10/N12
: Default value
Communication
Custom save area for
[Custom]
"Parameter Save by Ext-
03FAH Parameter 2byte
input". Indicates the R/W
(1018) Save by Ext- INT
value from custom save
Input
execution.
03FBH Reserved for
- - - -
(1019) system
Custom save area for
[Custom] “Long Distance Mode”
03FCH 2byte
Long Dis- The value when the cus- R/W
(1020) INT
tance Mode tom save is performed is
stored.
03FDH
(1021) to Reserved for
- - - -
03FFH system
(1023)
Indicates the number of
0400H Group8 Entry 2byte
items (entries) that can R 20
(1024) count INT
be set in Group 8.
0401H ID number Indicates number of used 2byte
R 1
(1025) Count IDs. INT
0402H
(1026) to Reserved for
- - - -
0403H system
(1027)
0404H Product 2byte
Indicates product code. R 2005
(1028) Code INT
Indicates revision, with
the upper bytes repre-
0405H senting the major revision 2byte
Revision R 0101H to FFFFH
(1029) and the lower bytes rep- INT
resenting the minor revi-
sion.
0406H Product Indicates model designa-
STRING R PS-N10/N12*
(1030) Name tion of the sensor.
0407H
(1031) to Reserved for
- - - -
040DH system
(1037)
040EH 2byte
Series Code Indicates series code. R 2005
(1038) INT
040FH Series Ver- 2byte
Indicates series version. R 1
(1039) sion INT
PS-N10/N12
: Default value
*1 If the slide type DIP switch is set to MEGA while locked, [] will flash on the
sensor amplifier.
3 Reference
• [Custom]*** is a parameter can save and read settings using the PS-N10
series "custom save" and "user reset function".
• "Entry count" indicates the number of parameters in the same group.
Communication
PS-N10/N12
Communication
bration tivity.
Two-point/Pos. Starts calibration the 1st point of 2-point calibra-
0305H(773)
Calibration: 1st tion.
Two-point Cali- Starts calibration the 2nd point of 2-point cali-
0306H(774)
bration: 2nd bration.
Positioning Cali- Starts calibration the 1st point of positioning cal-
0305H(773)
bration: 1st ibration.
Positioning Cali- Starts calibration the 2nd point of positioning
0307H(775)
bration: 2nd calibration.
Full Auto Cali-
0308H(776) Starts fully automatic calibration.
bration: Start
Full Auto Cali-
0309H(777) Ends fully automatic calibration.
bration: Finish
Zero-shift
030AH(778) Executes zero shift.
Request
030BH(779) Zero-shift Cancel Cancels zero shift.
030CH(780) Preset Request Executes preset.
030DH(781) Preset Cancel Cancels preset.
Reset Hold
0310H(784) Resets the held value.
Value
Work-Preset
0311H (785) Executes workpiece preset.
Request
Full Auto Preset: Starts fully automatic (or maximum sensitivity)
0312H(786)
Start preset.
Full Auto Preset: Ends fully automatic (or maximum sensitivity)
0313H(787)
Finish preset.
Maximum Sensi- Executes maximum sensitivity preset. (Preset
0314H(788) tivity Preset: can be executed without specifying the start
Request and end.)
AP-N10/N10D
Refer to "How to Use NU Objects" (page 3-30) for how to use the parameters.
Designate the ID number of the installed sensor for the instance ID.
: Default value
3 Indicates error
bit0 : Reserve
bit1 : Sensor-Head Error
bit2 : EEPROM Error
information. When an bit3 : Reserve
0321H Error 2byte
Communication
AP-N10/N10D
: Default value
Communication
(unit: 0.1kPa) -1400~1400
(default value : -500)
▌AP-48
-1400~1400
(default value : 500)
▌AP-41M/41
-1200~200
(default value : 50)
▌AP-43
Indicates the setting -2000~12000
0342H Setting Value value of Output1. (default value : -500)
2byte INT R/W
(834) P2*1 (Standard mode) ▌AP-44
(unit: 0.1kPa) -1400~1400
(default value : 50)
▌AP-48
-1400~1400
(default value : -50)
0343H
Reserved - - - -
(835)
▌AP-41M/41
-1200~200
(default value : -600)
▌AP-43
Indicates the upper limit
-2000~12000
of the setting value.
0344H Setting Value (default value : 6000)
(Window mode, Leak test 2byte INT R/W
(836) Area Hi ▌AP-44
mode)
-1400~1400
(unit: 0.1kPa)
(default value : -500)
▌AP-48
-1400~1400
(default value : 500)
▌AP-41M/41
-1200~200
(default value : -200)
▌AP-43
Indicates the lower limit
-2000~12000
of the setting value.
0345H Setting Value (default value : 2000)
(Window mode, Leak test 2byte INT R/W
(837) Area Lo ▌AP-44
mode)
-1400~1400
(unit: 0.1kPa)
(default value : 500)
▌AP-48
-1400~1400
(default value : -500)
0346H
Reserved - - - -
(838)
AP-N10/N10D
: Default value
(845)
▌AP-41M/41
Communication
-1013~30
Indicates the zero shift
034EH Reference ▌AP-43
reference value. 2byte INT R/W
(846) Value -300~10000
(unit: 0.1kPa)
▌AP-44/48
-1013~1013
▌AP-41M/41
Indicates the atmosphere -60~60
Pressure
034FH pressure correction ▌AP-43
Correction 2byte INT R/W
(847) value. -600~600
Value
(unit: 0.1kPa) ▌AP-44/48
-110~110
0350H
(848)
to Reserved - - - -
035FH
(863)
Indicates the number of
0360H Group 3 2byte
entries that can be set in R 15
(864) Entry count UINT
Group 3.
0 : Unlock
0361H Key Lock Indicates the status of 1 : Key Lock
2byte INT R/W
(865) Status Key lock. 2 : PIN Code Lock
3 : Communication Lock
0362H Indicates the password
Password 2byte INT R/W 0 to 9999 (default vaule : 0)
(866) for Key lock.
0363H
Reserved - - - -
(867)
bit0 : Output 1
0 : N.O.
Indicates whether the 1 : N.C.
0364H outputs are NO or NC. 2byte
(868)
N.O./N.C.
The corresponding bit WORD
R/W bit1 : Output 2*1
turns ON in NC. 0 : N.O.
1 : N.C.
(default value : 0)
0 : 1ms
1 : 2.5ms
Response
2 : 5ms
0365H Time Indicates the response
2byte INT R/W 3 : 100ms
(869) (Chatter time (chatter prevention).
4 : 500ms
prevention)
5 : 1000ms
6 : 5000ms
AP-N10/N10D
: Default value
Communication
(895)
Indicates the number of
0380H Group 4 2byte
entries that can be set in R 4
(896) Entry count UINT
Group 4.
0381H
(897)
to Reserved - - - -
0383H
(899)
0 : Standard Mode
1 : Window Mode
0384H Detection Indicates the detection 2 : Suction Confirmation
2byte INT R/W
(900) Mode mode.
Mode*1
3 : Leak Test Mode*1
0385H
(901)
to Reserved - - - -
039FH
(927)
Indicates the number of
03A0H Group 5 2byte
entries that can be set in R 0
(928) Entry count UINT
Group 5.
03A1H
(929)
to Reserved - - - -
03BFH
(959)
Indicates the number of
03C0H Group 6 2byte
entries that can be set in R 13
(960) Entry count UINT
Group 6.
03C1H
(961)
to Reserved - - - -
03CCH
(972)
03CDH Display Indicates the display 0 : Standard
2byte INT R/W
(973) resolution resolution setting. 1 : High Resolution Mode
03CEH
(974)
to Reserved - - - -
03DFH
(991)
AP-N10/N10D
: Default value
AP-N10/N10D
0306H(774)
Two-point Starts calibration the 2nd point of 2-point 3
Calibration: 2nd calibration.
Communication
Atmosphere
030EH(782) Pressure Executes the atmosphere pressure correction.
Correction
Reset
Atmosphere
030FH(783) Resets the atmosphere pressure correction.
Pressure
Correction
Reset Hold
0310H(784) Resets the hold value.
Value
MU-N/LR-T
Refer to "How to Use NU Objects" (page 3-30) for how to use the parameters.
Designate the ID number of the installed sensor for the instance ID.
When the MU-N/LR-T is used for the first time after purchase, initial setting should be
completed by either of the following methods:
(1) By operating the button of the MU-N
(2) Via communication
3 Point When the settings of the MU-N and LR-T are different (such as when
only the LR-T is replaced), the settings must be synchronized by but-
Communication
ton operation of the MU-N. For details, refer to "MU-N Series User's
Manual (Using LR-T)".
bit0 : NPN/PNP
0 : NPN
1 : PNP
bit1 : I/O Function
Output 1+Output 2
03EFH Indicates the changes of 2byte
Basic setting changes R/W Outupt 1+Input
(1007) "Basic settings". INT
bit2-3 : Distance Unit
0 : mm
1 : inch
2 : feet
(Default value : 0)
MU-N/LR-T
Reference
To check the input/output function being set, read the data from Attribute ID
: 0335H "Basic settings".
This completes the "basic settings". Refer to starting on the next page to perform
communication.
: Default value
Attribute Data
Name Description Attribute Value
ID type
Communication
Indicates error informa-
bit3 : Reserved
0321H tion. When an error 2byte
Error Information R bit4 : Reserved
(801) occurs, the correspond- WORD
bit5 : Reserved
ing bit is turned ON.
bit6 : Sensor/Controller
Unsynchronized
bit7 : Communication Error
0322H
(802) to
Reserved - - - -
0323H
(803)
Indicates the output sta-
tus of the sensor. When
0324H 2byte bit0 : Output1
Output the output is ON, the cor- R
(804) WORD bit1 : Output2
responding bit is turned
ON.
Indicates the raw value of
0325H 2byte
Current Distance the current distance R 50 to 9999
(805) INT
value.
0326H
(806) to
Reserved - - - -
0327H
(807)
Indicates the raw value of
0328H 2byte 0 : Low (instability)
Light Intensity the current distance R
(808) INT 1 : High
value.
0329H
(809) to
Reserved - - - -
0334H
(820)
bit0 : NPN/PNP
0 : NPN
1 : PNP
0335H Indicates the basic set- 2byte
Basic setting R bit1 : I/O Function
(821) tings of the sensor. INT
0 : Output 1 + Output 2
1 : Output 1 + Input
(Default value : 0)
0336H
(822) to
Reserved - - - -
0338H
(824)
MU-N/LR-T
: Default value
Attribute Data
Name Description Attribute Value
ID type
0 : IDLE
0339H Indicates status of Initial- 2byte
Initialization status R 1 : EXE
(825) ization request. INT
2 : FINISH
033AH
(826) to
Reserved - - - -
033FH
(831)
Indicates the number of
0340H 2byte
Group2 Entry count entries that can be set in R 15
3 (832)
Group2.
Indicates the setting
UINT
0341H Setting Value(Output1 / lower limit of the setting 2byte 0 to 9999 (Default vaule :
R/W
(833) Output1 Area Near) value is displayed when INT 500)
the "Detection Mode" is
Area.
Indicates the setting
value of Output2. The
0342H Setting Value(Output2 / lower limit of the setting 2byte 0 to 9999 (Default vaule :
R/W
(834) Output2 Area Near) value is displayed when INT 500)
the "Detection Mode" is
Area.
0343H
Reserved - - - -
(835)
Indicates the upper limit
0344H Setting Value(Output1 of setting value of 2byte 0 to 9999 (Default vaule :
R/W
(836) Area Far) Output1 when the INT 1000)
"Detection Mode" is Area.
Indicates the upper limit
0345H Setting Value(Output2 of setting value of 2byte 0 to 9999 (Default vaule :
R/W
(837) Area Far) Output2 when the INT 1000)
"Detection Mode" is Area.
0346H
(838) to
Reserved - - - -
0347H
(839)
Indicates the value of
0348H 2byte 0 to 9999 (Default vaule :
Hysteresis Value hysteresis when Hystere- R/W
(840) UINT 10)
sis Setting is "Custom".
0349H
(841) to
Reserved - - - -
034EH
(846)
034FH Indicates the offset value 2byte
DATUM Offset R/W 0 to 9999 (Default vaule : 0)
(847) in DATUM mode. INT
0350H
(848) to
Reserved - - - -
035FH
(863)
Indicates the number of
0360H 2byte
Group3 Entry count entries that can be set in R 15
(864) INT
Group3.
MU-N/LR-T
: Default value
Attribute Data
Name Description Attribute Value
ID type
0 : Unlock
0361H Indicates the status of 2byte 1 : Key Lock
Key Lock Status R/W
(865) Key lock. INT 2 : PIN Code Lock
3 : Communication Lock
0362H Indicates the password 2byte
Password R/W 0 to 9999 (Default vaule : 0)
(866) for Key lock. INT
0363H
Reserved - - - -
(867)
Communication
0 : N.O.
NC.
1 : N.C.
(Default value : 0)
Laser Class2 type
0 : 7ms
1 : 15ms
2 : 30ms
3 : 105ms
0365H Indicates the Response 2byte 4 : 1000ms
Response Time R/W
(869) Time. INT Laser Class1 type
0 : 8ms
1 : 25ms
2 : 55ms
3 : 205ms
4 : 2000ms
0366H
(870) to
Reserved - - - -
0368H
(872)
0369H Indicates the setting 2byte 0 : Standard
Hysteresis Setting R/W
(873) mode of hysteresis. INT 1 : Custom
036AH
Reserved - - - -
(874)
036BH Indicates the detection 2byte 0 : Distance mode
Detection Mode R/W
(875) mode. INT 1 : DATUM mode
0 : Channel 1
Indicates the laser emis-
036CH 2byte 1 : Channel 2
Interference Channel sion channel for interfer- R/W
(876) INT 2 : Channel 3
ence prevention.
3 : Channel 4
0 : Low
036DH Received Light Sensi- Indicates the received 2byte
R/W 1 : Mid
(877) tivity light sensitivity setting. INT
2 : High
Indicates the number of
036EH 2byte
Stability Filter samples used when R/W 1 to 100 (Default vaule : 5)
(878) INT
determining stability.
036FH Indicates the selected 2byte 0 : Output1
Switching Out1/Out2 R/W
(879) output. INT 1 : Output2
0370H
(880) to
Reserved - - - -
037FH
(895)
MU-N/LR-T
: Default value
Attribute Data
Name Description Attribute Value
ID type
MU-N/LR-T
: Default value
Attribute Data
Name Description Attribute Value
ID type
Communication
03C7H
(967) to
Reserved - - - -
03CEH
(974)
03CFH Indicates Graphic mode 2byte 0 : On Trigger
Graphic Mode R/W
(975) setting. INT 1 : Trend Graph
03D0H
(976) to
Reserved - - - -
03DFH
(991)
Indicates the number of
03E0H 2byte
Group7 Entry count entries that can be set in R 15
(992) INT
Group7.
03E1H
(993) to
Reserved - - - -
03E5H
(997)
0 : 100%
03E6H Indicates screen bright- 2byte
Brightness R/W 1 : OFF
(998) ness. INT
2 : 30%
03E7H
(999) to
Reserved - - - -
03EAH
(1002)
03EBH
User Tag0
(1003)
Indicates User Tag.Avail-
03ECH 2byte
User Tag1 able as an area to put R/W 0 to FFFFh
(1004) UINT
optional data.
03EDH
User Tag2
(1005)
03EEH
Reserved - - - -
(1006)
MU-N/LR-T
: Default value
Attribute Data
Name Description Attribute Value
ID type
bit0 : NPN/PNP
0 : NPN
1 : PNP
bit1 : I/O Function
Output 1+Output 2
03EFH Indicates the changes of 2byte
Basic setting changes R/W Outupt 1+Input
(1007) "Basic setting". INT
bit2-3 : Distance Unit
0 : mm
1 : inch
2 : feet
3 03F0H
(Default value : 0)
(1008)
to Reserved - - - -
Communication
03FFH
(1023)
Indicates the number of
0400H 2byte
Group8 Entry count entries that can be set in R 16
(1024) UINT
Group8.
0401H Indicates the number of 2byte
ID Number Count R 3
(1025) used IDs. INT
0402H
Reserved - - - -
(1026)
Indicates Multi Controller
revisions, with the upper
0403H Multi Controller Revi- bytes representing the 2byte
R 0 to FFFFh
(1027) sion major revisions and the INT
lower bytes representing
the minor revisions.
0404H Indicates the product 2byte
Product Code R 2012
(1028) code. INT
Indicates Sensor revi-
sions, with the upper
0405H bytes representing the 2byte
Sensor Revision R 0 to FFFFh
(1029) major revisions and the INT
lower bytes representing
the minor revisions.
0406H Indicates the model des- STRIN
Product Name R "LR-T**"
(1030) ignation of the sensor. G
0407H
(1031)
to Reserved - - - -
040DH
(1037)
040EH 2byte
Series Code Indicates the series code. R 2012
(1038) INT
040FH Indicates the series ver- 2byte
Series Version R 1
(1039) sion. INT
0410H 2byte
Device Type Indicates the device type. R 0
(1040) INT
MU-N/LR-T
: Default value
Attribute Data
Name Description Attribute Value
ID type
0411H
(1041)
to Reserved - - - -
041FH
(1055)
Communication
Attribute
Name Description
ID
0301H
Initialization request Initializes all settings, except for "Basic setting".
(769)
0302H Basic setting set
Changes the "Basic setting" in accordance with "Basic setting changes"
(770) request
0303H
1-Point Calibration Executes 1-point calibration.
(771)
0305H 2-Point Calibration
Starts calibration: the 1st point of 2-point calibration.
(773) (1st)
0306H 2-Point Calibration
Starts calibration: the 2nd point of 2-point calibration.
(774) (2nd)
0308H Full Auto Calibration
Starts Full auto calibration.
(776) start
0309H Full Auto Calibration
Ends Full auto calibration.
(777) end
031EH
DATUM Preset Executes reference surface update.
(798)
031FH
DATUM Calibration Executes DATUM Calibration
(799)
MU-N/LR-W
Refer to "How to Use NU Objects" (page 3-30) for how to use the parameters.
Designate the ID number of the installed sensor for the instance ID.
When the MU-N/LR-W is used for the first time after the purchase, the initial setting
should be completed in either of the following methods:
(1) By operating the button of the MU-N
(2) Via communication
3
Point When the settings of the MU-N and LR-W are different (such as when
Communication
Attribute
Data
ID Name Description Attribute Value
type
(HEX)
bit0 : NPN/PNP
0 : NPN
1 : PNP
bit1-2 : Output Mode
0 : 1-Output, 16-Bank
03EFH Indicates the changes of 2byte 1 : 4-Output, 2-Bank
Basic setting changes R/W
(1007) "Basic settings". INT 2 : Binary
bit3-4 : Line 2 Function
0 : Off
1 : Input
2 : Output
(Default value : 0)
MU-N/LR-W
Excute the operation commands for the following address of MU-N/LR-W. (Service
code: 4BH, instance ID: 01H to 10H (sensor ID number))
Attribute
Name Description
ID
0302H Basic settings set
Changes the "Basic settings" in accordance with "Basic settings changes".
(770) request
To check the input/output function being set, read the data from Attribute
Reference
ID: 0335h "Basic settings".
This completes the "basic settings". Refer to the following indices to perform
3
communication.
Communication
: Default value
Attribute
Data
ID Name Description Attribute Value
type
(HEX)
Indicates the number of
0320H 2byte
Group 1 Entry count entries that can be set in R 31
(800) UNIT
Group 1.
bit0 : Over Current Error
bit1 : Head Error
Indicates error bit2 : EEPROM Error
information. When an bit3 : Reserved
0321H 2byte
Error Information error occurs, the R bit4 : Reserved
(801) WORD
corresponding bit is bit5 : Reserved
turned ON. bit6 : Sensor/Controller
Unsynchronized
bit7 : Communication Error
0322H
Reserved - - - -
(802)
0323H
Reserved - - - -
(803)
Indicates the output
status of the sensor. bit0 : Output 1
0324H 2byte
Output When the output is ON, R :
(804) WORD
the corresponding bit is bit14: Output 15
turned ON.
Indicates the current
value. Current value is
Matching rate when
0325H detection mode is Auto or 2byte
Current Value R 0 to 999
(805) C or C+I mode, received INT
light intensity when
detection mode is I
mode.
0326H Indicates the rate of red 2byte
Light intensity ratio Red R 0 to 9999
(806) received light. INT
0327H Light intensity ratio Indicates the rate of 2byte
R 0 to 9999
(807) Green green received light. INT
0328H Light intensity ratio Indicates the rate of blue 2byte
R 0 to 9999
(808) Blue received light. INT
0329H Indicates the peak value 2byte
Peak-Hold Value R 0 to 999
(809) of the current values. INT
MU-N/LR-W
: Default value
Attribute
Data
ID Name Description Attribute Value
type
(HEX)
Indicates the bottom
032AH 2byte
Bottom-Hold Value value of the current R 0 to 999
(810) INT
values.
032BH
(811)-
Reserved - - - -
0334H
(820)
bit0 : NPN/PNP
0 : NPN
3 1 : PNP
bit1-2 : Output Mode
0 : 1-Output, 16-Bank
0335H Indicates the basic 2byte 1 : 4-Output, 2-Bank
Basic setting R
(821) settings of the sensor. INT 2 : Binary
Communication
MU-N/LR-W
: Default value
Attribute
Data
ID Name Description Attribute Value
type
(HEX)
0341H
Setting Value 1
(833)
0342H
Setting Value 2
(834)
0343H Indicates the setting
Setting Value 3
(835) value of each outputs.
0344H
Setting Value 4
(836) 1-Output 16-bank
0345H Seting Value 1 : Bank 1
(837)
0346H
Setting Value 5
Setting Value 6
setting value
:
Setting value 16 : Bank
3
(838) 16 Setting value
Communication
0347H
Setting Value 7
(839) 4-Output 2-bank
0348H Setting value 1 : Bank 1,
Setting Value 8 Output 1 Setting value
(840) 2byte 0 to 999 (Default value :
Setting value 2 : Bank 1, R/W
0349H INT 999)
Setting Value 9 Output 2 Setting value
(841) :
034AH Setting value 7 : Bank 2,
Setting Value 10
(842) Output 3 Setting value
034BH Setting value 8 : Bank 2,
Setting Value 11 Output 4 Setting value
(843)
034CH Binary Output
Setting Value 12
(844) Setting value 1 : Output 1
034DH Setting value
Setting Value 13
(845) :
034EH Setting value 15 : Output
Setting Value 14 15 Setting value
(846)
034FH
Setting Value 15
(847)
0350H
Setting Value 16
(848)
Indicates the fixed setting
0351H Master Calibration 2byte 0 to 999 (Default value :
value for Master R/W
(849) setting value INT 950)
calibration.
Indicates the setting
Difference Monitoring
0352H value when SPOT/MODE 2byte 0 to 999 (Default value :
setting valule R/W
(850) selection is "Difference INT 100)
(Only LR-W70)
Monitoring".
0353H
(851)-
Reserved - - - -
035FH
(863)
Indicates the number of
0360H 2byte
Group 3 Entry count entries that can be set in R 31
(864) UINT
Group 3.
0 : Unlock
0361H Indicates the status of 2byte 1 : Key Lock
Key Lock Status R/W
(865) Key lock. INT 2 : PIN Code Lock
3 : Communication Lock
0362H Indicates the password 2byte
Password R/W 0 to 9999 (Default vaule : 0)
(866) for Key lock. INT
MU-N/LR-W
: Default value
Attribute
Data
ID Name Description Attribute Value
type
(HEX)
bit0 : Output1
Indicates the output bit1 : Output2
0363H logic(NO/NC). The 2byte :
NO/NC R/W
(867) corresponding bit turns WORD bit14 : Output15
ON in NC. bit15 : Output16
(Defaule value : 0)
0364H
Reserved - - - -
(868)
0365H Indicates the Response 2byte
Response Time R/W *1
3 (869)
2byte 0 : NO
R/W
(870) Stability output) output and Stability INT 1 : NC
Communication
output.
0367H
Reserved - - - -
(871)
0 : Bank1
0368H Indicates the selected 2byte 1 : Bank2
(872) Bank selection*2 bank number. INT
R/W
:
15 : Bank16
0369H
(873)-
Reserved - - - -
036BH
(875)
0 : 1-Spot Mode
036CH Spot/Mode Selection Indicates the Spot/Mode 2byte
R/W 1 : Difference Monitoring
(876) (Only LR-W70) selection. INT
2 : 2-Point Matching
Indicate the selected
036DH Interference Reduction frequency mode, in 2byte 0 : Mode A
R/W
(877) Function mutual interference INT 1 : Mode B
reduction function.
036EH Indicates the selected 2byte
Cannel Selection R/W 0 to 14 (Default vaule : 0)
(878) output channel. INT
0 : Auto
1 : C+I
036FH Indicates the detection 2byte
Detection Mode (ALL) R/W 2:C
(879) mode of all the outputs. INT
3:I
4 : Setting individually
MU-N/LR-W
: Default value
Attribute
Data
ID Name Description Attribute Value
type
(HEX)
0370H
Detection Mode 1
(880)
0371H
Detection Mode 2
(881) Indicates the detection
0372H mode of each outputs
Detection Mode 3 when the "Detection
(882)
Mode (ALL)" is Setting
0373H
Detection Mode 4 individually.
(883)
0374H 1-Output 16-bank
(884)
0375H
Detection Mode 5
Detection Mode 6
Detection Mode 1 : Bank
1 mode
3
(885) :
Detection Mode 16 :
Communication
0376H
Detection Mode 7 Bank 16 mode
(886)
0377H 4-Output 2-bank 0 : Auto
Detection Mode 8
(887) Detection Mode 1 : Bank 2byte 1 : C+I
R/W
0378H 1, Output 1 mode INT 2:C
Detection Mode 9 Detection Mode 2 : Bank 3:I
(888)
1, Output 2 mode
0379H
Detection Mode 10 :
(889)
Detection Mode 7 : Bank
037AH 2, Output 3 mode
Detection Mode 11
(890) Detection Mode 8 : Bank
037BH 2, Output 4 mode
Detection Mode 12
(891)
Binary Output
037CH
Detection Mode 13 Detection Mode 1 :
(892)
Output 1 mode
037DH :
Detection Mode 14
(893) Detection Mode 15 :
037EH Output 15 mode
Detection Mode 15
(894)
037FH
Detection Mode 16
(895)
Indicates the number of
0380H 2byte
Group 4 Entry count entries that can be set in R 31
(896) UINT
Group 4.
0381H
(897)-
Reserved - - - -
0386H
(902)
0 : Off
0387H Indicates the settings of 2byte
External Input Function R/W 1 : Calibration input
(903) the external input. INT
2 : LED Off
0388H
(904)-
Reserved - - - -
038EH
(910)
0 : Off
038FH Indicates the function of 2byte
Output2 Function R/W 1 : Error output
(911) Output2. INT
2 : Stability output
MU-N/LR-W
: Default value
Attribute
Data
ID Name Description Attribute Value
type
(HEX)
0390H
Timer Mode 1
(912)
0391H
Timer Mode 2
(913)
0392H
Timer Mode 3
(914)
0393H
Timer Mode 4
(915)
0394H Indicates the timer mode
3 (916)
0395H
Timer Mode 5
Timer Mode 6
of each outputs.
1-Output 16-bank
(917) Timer Mode 1 : Bank 1
Communication
0396H mode
Timer Mode 7
(918) :
0397H Timer Mode 16 : Bank 16
Timer Mode 8 0 : Off
(919) mode
2byte 1 : On delay
R/W
0398H INT 2 : Off delay
Timer Mode 9 4-Output 2-bank
(920) 3 : One-shot
Timer Mode 1 : Bank 1
0399H mode
Timer Mode 10
(921) Timer Mode 2 : Bank 2
039AH mode
Timer Mode 11
(922)
Binary Output
039BH Timer Mode 1 : Output 1
Timer Mode 12
(923) to 15 mode
039CH
Timer Mode 13
(924)
039DH
Timer Mode 14
(925)
039EH
Timer Mode 15
(926)
039FH
Timer Mode 16
(927)
Indicates the number of
03A0H 2byte
Group 5 Entry count entries that can be set in R 31
(928) UINT
Group 5.
03A1H
(929)-
Reserved - - - -
03ADH
(941)
03AEH Sensor Indicator Indicates the operation of 2byte 0 : Off
R/W
(942) Blinking Function the sensor indicator. INT 1 : Flush
03AFH Indicates the setting of 2byte 0 : Off
LED On/Off R/W
(943) LED On/Off. INT 1 : On
MU-N/LR-W
: Default value
Attribute
Data
ID Name Description Attribute Value
type
(HEX)
03B0H
Timer Setting 1
(944)
03B1H
Timer Setting 2
(945)
03B2H
Timer Setting 3
(946)
03B3H
Timer Setting 4
(947)
03B4H Indicates the time of
(948)
03B5H
Timer Setting 5
Timer Setting 6
output timer. (Unit : ms)
1-Output 16-bank
3
(949) Timer Setting 1 : Bank 1
Communication
03B6H mode
Timer Setting 7
(950) :
03B7H Timer Setting 16 : Bank
Timer Setting 8 16 mode
(951) 2byte
R/W 1 to 999 (Default value : 10)
03B8H INT
Timer Setting 9 4-Output 2-bank
(952) Timer Setting 1 : Bank 1
03B9H mode
Timer Setting 10
(953) Timer Setting 2 : Bank 2
03BAH mode
Timer Setting 11
(954)
Binary Output
03BBH Timer Setting 1 : Output 1
Timer Setting 12
(955) to 15 mode
03BCH
Timer Setting 13
(956)
03BDH
Timer Setting 14
(957)
03BEH
Timer Setting 15
(958)
03BFH
Timer Setting 16
(959)
Indicates the number of
03C0H 2byte
Group 6 Entry count entries that can be set in R 31
(960) UINT
Group 6.
03C1H
(961)-
Reserved - - - -
03CEH
(974)
03CFH Indicates Graphic mode 2byte 0 : On Trigger
Graphic Mode R/W
(975) setting. INT 1 : On Peak
MU-N/LR-W
: Default value
Attribute
Data
ID Name Description Attribute Value
type
(HEX)
03D0H Detection Light Source
(976) 1
03D1H Detection Light Source
(977) 2
03D2H Detection Light Source
(978) 3
03D3H Detection Light Source
(979) 4 Indicates the light source
03D4H Detection Light Source for the detection when
3 (980)
03D5H
5
Detection Light Source
using "Super I Mode".
1-Output 16-bank
(981) 6 Light selection 1 : Bank 1
Communication
MU-N/LR-W
: Default value
Attribute
Data
ID Name Description Attribute Value
type
(HEX)
bit0 : NPN/PNP
0 : NPN
1 : PNP
bit1-2 : Output Mode
0 : 1-Output, 16-Bank
03EFH Indicates the changes of 2byte 1 : 4-Output, 2-Bank
Basic setting changes R/W
(1007) "Basic setting". UINT 2 : Binary
bit3-4 : Line 2 Function
0 : Off
1 : Input
2 : Output
(Default value : 0) 3
03F0H
(1008)-
Communication
Reserved - - - -
03FFH
(1023)
Indicates the number of
0400H 2byte
Group8 Entry count entries that can be set in R 16
(1024) UINT
Group8
0401H Indicates number of used 2byte
ID Number Count R 3
(1025) IDs. INT
0402H
Reserved - - - -
(1026)
Indicates Multi Controller
revision, with the upper
0403H Multi Controller bytes representing the 2byte
R 0 to FFFFh
(1027) Revision major revision and the INT
lower bytes representing
the minor revision.
0404H 2byte
Product Code Indicates product code. R 2010
(1028) INT
Indicates Sensor
revision, with the upper
0405H bytes representing the 2byte
Sensor Revision R 0 to FFFFh
(1029) major revision and the INT
lower bytes representing
the minor revision.
Indicates model
0406H STRIN
Product Name 1,0 designation of the R "LR-W**"
(1030) G
sensor.
0407H
(1031)-
Reserved - - - -
040DH
(1037)
040EH 2byte
Series Code Indicates series code. R 2010
(1038) INT
040FH 2byte
Series Version Indicates series version. R 1
(1039) INT
0410H 2byte
Device Type Indicates device type. R 0
(1040) INT
0411H
(1041)-
Reserved - - - -
041FH
(1055)
MU-N/LR-W
*1 Response time
LR-W500
1-Output 4-Output 2-bank
Value
16-bank Binary Output
0 300 µs 2 ms
1 1.1 ms 3 ms
2 11 ms 11 ms
3 100 ms 100 ms
4 500 ms 500 ms
3 LR-W70
Value 1-Output 16-bank 4-Output 2-bank Binary Output
Difference 2-Point Difference Monitoring
1-Spot Mode 1-Spot Mode
Communication
LR-WF10
1-Output 4-Output 2-bank
Value
16-bank Binary Output
0 350 µs 3 ms
1 1.2 ms 4 ms
2 13 ms 14 ms
3 120 ms 120 ms
4 600 ms 600 ms
*2 During key lock, switching between banks via data communication is not possible.
To switch between banks via data communication, cancel the key lock (attribute
ID: 865) beforehand.
MU-N/LR-W
Communication
0304H (772) Ends 1-point calibration.
tion end
2-point Calibra- Starts calibration: the 1st point of 2-point cali-
0305H (773)
tion (1st) bration.
2-point Calibra- Starts calibration: the 2nd point of 2-point cali-
0306H (774)
tion (2nd) bration.
Full Auto Calibra-
0308H (776) Starts Full auto calibration.
tion Start
Full Auto Calibra-
0309H (777) Ends Full auto calibration.
tion End
Adjust Light Inten-
030EH (782) Executes Adjust light Intensity.
sity
Maximum Sensi-
0316H (790) tivity Calibration Starts Maximum sensitivity calibration.
Start
Maximum Sensi-
0317H (791) tivity Calibration Ends Maximum sensitivity calibration.
End
Fiber Status Init-
0319H(793) ilization Initialize the fiber unit status.
(only LR-WF10)
2-Point Matching
031BH (795) Calibration Executes 2-Point Matching Calibration.
(Only LR-W70)
Master Addition
031CH (796) Starts Master addition calibration.
Calibration Start
Master Addition
031DH (797) Ends Master addition calibration.
Calibration End
Master Calibra-
031EH (798) Starts Master calibration.
tion Start
Master Calibra-
031FH (799) Ends Master calibration.
tion End
MU-N/FD-Q
Refer to "How to Use NU Objects" (page 3-30) for how to use the parameters.
Designate the ID number of the installed sensor for the instance ID.
When the MU-N/FD-Q is used for the first time after the purchase, the initial setting
should be completed in either of the following methods:
(1) By operating the button of the MU-N
(2) Via communication
3 Point When the settings of the MU-N and FD-Q are different (such as when
only the FD-Q is replaced), the settings must be synchronized with
Communication
the button operation of the MU-N. For details, refer to "MU-N Series
User's Manual (Using FD-Q)".
bit0 : NPN/PNP
0 : NPN
1 : PNP
bit1-2 : I/O functions
0 : 1 Output
03EFH Indicates the changes of 2byte
Basic setting changes R/W 1 : 2 Output
(1007) "Basic settings". INT
2 : Output + Input
bit3 : Flow unit
0 : Liter
1 : Gallon
(Default value : 0)
MU-N/FD-Q
Reference
To check the input/output function being set, read the data from Index 53
"Basic settings".
This completes the "basic settings". Refer to starting on the next page to perform
communication.
: Default value
Attribute Data
Name Description Attribute Value
ID type
Communication
Indicates error informa- bit3 : Reserved
0321H tion. When an error 2byte bit4 : Counter Flow Error
Error Information R
(801) occurs, the correspond- WORD bit5 : Cannot receive detec-
ing bit is turned ON. tion signal
bit6 : Sensor/Contoller
Unsynchronized
bit7 : Communication Error
0322H
(802) to
Reserved - - - -
0323H
(803)
Indicates the output sta-
tus of the sensor. When
0324H 2byte bit0 : Output 1
Output the output is ON, the cor- R
(804) WORD bit1 : Output 2
responding bit is turned
ON.
0325H Indicates the instanta- 2byte
Instantaneous flow R 0 to 9999
(805) neous flow value. INT
0326H
(806) to
Reserved - - - -
0327H
(807)
0328H Indicates the integrated 2byte
Integrated flow R 0 to 9999
(808) flow value. INT
0329H Indicates the peak value 2byte
Peak-Hold Value R 0 to 9999
(809) of the current values. INT
Indicates the bottom
032AH 2byte
Bottom-Hold Value value of the current val- R 0 to 9999
(810) INT
ues.
032BH
(811) to
Reserved - - - -
032DH
(813)
When using "Origin
Adjustment" or "Condi-
032EH 2byte bit0 : Origin Adjustment
Customize Status tion Monitoring", the cor- R
(814) WORD bit1 : Condition Monitoring
responding bit is turned
ON.
MU-N/FD-Q
: Default value
Attribute Data
Name Description Attribute Value
ID type
032FH
(815) to
Reserved - - - -
0334H
(820)
bit0 : NPN/PNP
0 : NPN
1 : PNP
bit1-2 : I/O functions
0 : 1 Output
0335H Indicates the basic set- 2byte
3 (821)
Basic setting
tings of the sensor. INT
R 1 : 2 Output
2 : Output + Input
bit3 : Flow unit
0 : Liter
1 : Gallon
Communication
(Default value : 0)
0336H
(822) to
Reserved - - - -
0338H
(824)
0 : IDLE
0339H Indicates status of Initial- 2byte
Initialization status R 1 : EXE
(825) ization request. INT
2 : FINISH
0 : IDLE
Indicates the status of
033AH Origin adjustment sta- 2byte 1 : EXE
"Origin Adjustment" R
(826) tus INT 2 : SUCCESS
request.
3 : FAILURE
0 : IDLE
Indicates the status of
033BH Condition monitoring 2byte 1 : EXE
"Condition Monitoring R
(827) status INT 2 : SUCCESS
function" request.
3 : FAILURE
033CH Indicates the flow display 2byte 0 : 0.01
Flow display resolution R
(828) resolution. INT 1 : 0.1
Indicates the reference
033DH 2byte
Reference flow rate flow in Condition Monitor- R 0 to 9999
(829) INT
ing mode.
033EH Indicates the simulation 2byte 0 : Off
Simulation Mode R
(830) mode setting. INT 1 : On
0 : Direction not possible
1 : Low
033FH Indicates the signal sta- 2byte
Stability level R 2 : Medium-Low
(831) bility level. INT
3 : Medium-High
4 : High
Indicates the number of
0340H 2byte
Group2 Entry count entries that can be set in R/W 15
(832) UINT
Group2.
Indicates the setting
value of Output1. The
0341H Setting Value (Output1 lower limit of the setting 2byte
R/W 0 to 9999
(833) / Output1 Area Lower) value is displayed when INT
the "Detection Mode" is
Area.
MU-N/FD-Q
: Default value
Attribute Data
Name Description Attribute Value
ID type
Communication
Indicates the upper limit
0345H Setting Value (Output2 of the setting value of 2byte
R/W 0 to 9999
(837) Area Upper) Output2 when the INT
"Detection Mode" is Area.
0346H
(838) to
Reserved - - - -
0347H
(839)
Indicates the setting
0348H value of hysteresis when 2byte
Hysteresis Value R/W 0 to 9999
(840) the "Hysteresis Setting" UINT
is Custom.
0349H
(841) to
Reserved - - - -
034DH
(845)
Indicates the setting
034EH Integrated flow set 2byte 0 to 9999 (Default vaule :
value in Integrated flow R/W
(846) value INT 150)
mode.
034FH Indicates the Zero cut 2byte
Zero cut flow rate R/W 0 to 9999
(847) flow rate. INT
0350H
(848) to
Reserved - - - -
035FH
(863)
Indicates the number of
0360H 2byte
Group3 Entry count entries that can be set in R 15
(864) UINT
Group3.
0 : Unlock
0361H Indicates the status of 2byte 1 : Key Lock
Key Lock Status R/W
(865) Key lock. INT 2 : PIN Code Lock
3 : Communication Lock
0362H Indicates the password 2byte
Password R/W 0 to 9999 (Default vaule : 0)
(866) for Key lock. INT
0363H
Reserved - - - -
(867)
MU-N/FD-Q
: Default value
Attribute Data
Name Description Attribute Value
ID type
bit0 : Output 1
0 : N.O.
Indicates the output
1 : N.C.
0364H logic(NO/NC). The corre- 2byte
N.O./N.C. R/W bit1 : Output 2
(868) sponding bit turns ON in WORD
0 : N.O.
NC.
1 : N.C.
(Default value : 0)
0 : 0.5s
1 : 1s
3 0365H
(869)
Response Time
Indicates the Response
Time.
2byte
INT
R/W
2 : 2.5s
3 : 5s
4 : 10s
5 : 30s
6 : 60s
Communication
0366H
(870) to
Reserved - - - -
0369H
(873)
0 : 0.1 (Only Q10C,Q20C)
1:1
2 : 10
036AH Indicates the value of the 2byte
Integrated flow unit R/W 3 : 100
(874) integrated flow unit. INT
4 : 1000
5 : 10000
(Only Q32C,Q50C)
036BH Indicates the selected 2byte 0 : From left to right
Flow direction R/W
(875) flow direction. INT 1 : From right to left
FD-Q10C
0 : 1/4
1 : 3/8
FD-Q20C
0 : 1/2
1 : 3/4
036CH Selecting bore diame- Indicates the selected 2byte
R/W FD-Q32C
(876) ter of pipe bore diameter of the pipe. INT
0:1
1 : 1 1/4
FD-Q50C
0 : 1 1/2
1 : 2
(Default value : 0)
0 : No correction
036DH Correcting flow rate Indicates the corrected 2byte
R/W 1 : Selecting pipe schedule
(877) value flow rate value. INT
2 : Flow rate magnification
0 : SGP
036EH Selecting pipe sched- Indicates the selected 2byte 1 : Sch20
R/W
(878) ule pipe schedule. INT 2 : Sch40
3 : Sch80
Indicates the setting
036FH Adjusting flow rate value of Setting flow rate 2byte 10 to 250 (Default vaule :
R/W
(879) span magnification (Span). INT 100)
(Unit : ×1/100)
0370H
(880) to
Reserved - - - -
037FH
(895)
MU-N/FD-Q
: Default value
Attribute Data
Name Description Attribute Value
ID type
Communication
0385H
(901) to
Reserved - - - -
0386H
(902)
0 : Integrated flow reset
0387H Indicates the settings of 2byte input
External Input Function R/W
(903) the external input. INT 1 : Flow rate zero input
2 : Origin adjustment input
0388H
(904) to
Reserved - - - -
039FH
(927)
Indicates the number of
03A0H 2byte
Group5 Entry count entries that can be set in R 15
(928) UINT
Group5.
03A1H
(929) to
Reserved - - - -
03A3H
(931)
0 : Instantaneous flow rate
03A4H Detection Mode Indicates the detection 2byte mode
R/W
(932) (Output2) mode of Output2. INT 1 : Area mode
2 : Error output mode
03A5H
(933) to
Reserved - - - -
03ADH
(941)
03AEH Indicates the operation of 2byte 0 : Off
Sensor Indicator Flash R/W
(942) the sensor indicator. INT 1 : Flush
03AFH Indicates the setting of 2byte 0 : Off
Flow rate zero input R/W
(943) flow rate zero input. INT 1 : On
03B0H
(944) to
Reserved - - - -
03BFH
(959)
Indicates the number of
03C0H 2byte
Group6 Entry count entries that can be set in R 15
(960) UINT
Group6.
MU-N/FD-Q
: Default value
Attribute Data
Name Description Attribute Value
ID type
03C1H
(961) to
Reserved - - - -
03CCH
(972)
0 : 0.01 (Only Q10C)
03CDH Indicates the display res- 2byte
Display resolution R/W 1 : 0.1
(973) olution setting. INT
2:1
03CEH Indicates the display 2byte
Display averaging R/W 0 to 10 (Default value : 1)
(974) averaging setting. INT
3 03CFH Indicator illumination Indicates the display indi- 2byte
0 : Green - Off
1 : Off - Red
R/W
(975) mode cator illumination mode. INT 2 : Green - Red
Communication
3 : PMI
03D0H
(976) to
Reserved - - - -
03DFH
(991)
Indicates the number of
03E0H 2byte
Group7 Entry count entries that can be set in R 15
(992) UNIT
Group7.
03E1H
(993) to
Reserved - - - -
03E5H
(997)
0 : 100%
03E6H Indicates screen bright- 2byte
Brightness R/W 1 : Off
(998) ness. INT
2 : 30%
03E7H
(999) to
Reserved - - - -
03EAH
(1002)
03EBH
User Tag0
(1003)
Indicates User Tag.Avail-
03ECH 2byte
User Tag1 able as an area to put R/W 0 to FFFFh
(1004) INT
optional data.
03EDH
User Tag2
(1005)
03EEH
Reserved - - - -
(1006)
bit0 : NPN/PNP
0 : NPN
1 : PNP
bit1-2 : I/O functions
0 : 1 Output
03EFH Indicates the changes of 2byte
Basic setting changes R/W 1 : 2 Output
(1007) "Basic setting". INT
2 : Output + Input
bit3 : Flow unit
0 : Liter
1 : Gallon
(Default value : 0)
MU-N/FD-Q
: Default value
Attribute Data
Name Description Attribute Value
ID type
03F0H
(1008)
to Reserved - - - -
03FFH
(1023)
Indicates the number of
0400H 2byte
Group8 Entry count entries that can be set in R 16
(1024) UINT
Group8.
0401H Indicates the number of 2byte
(1025)
0402H
ID Number Count
used IDs. INT
R 3
3
Reserved - - - -
(1026)
Communication
Indicates Multi Controller
revisions, with the upper
0403H Multi Controller Revi- bytes representing the 2byte
R 0 to FFFFh
(1027) sion major revisions and the INT
lower bytes representing
the minor revisions.
0404H Indicates the product 2byte
Product Code R 2011
(1028) code. INT
Indicates Sensor revi-
sions, with the upper
0405H bytes representing the 2byte
Sensor Revision R 0 to FFFFh
(1029) major revisions and the INT
lower bytes representing
the minor revisions.
0406H Indicates the model des- STRIN
Product Name R "FD-Q*C"
(1030) ignation of the sensor. G
0407H
(1031)
to Reserved - - - -
040DH
(1037)
040EH 2byte
Series Code Indicates the series code. R 2011
(1038) INT
040FH Indicates the series ver- 2byte
Series Version R 1
(1039) sion. INT
0410H 2byte
Device Type Indicates the device type. R 0
(1040) INT
0411H
(1041)
to Reserved - - - -
041FH
(1055)
MU-N/FD-Q
0301H
Initialization request Initializes all settings, except for "Basic setting".
(769)
0302H Basic setting set
Changes the "Basic setting" in accordance with "Basic setting changes"
(770) request
3 030AH Performing origin
Performs origin adjustment.
(778) adjustment
Communication
4
4-1 Specifications ..................................................... 4-2
4-2 Data Processing Time ........................................ 4-3
4-3 Dimensions......................................................... 4-4
4 EtherNet/IP
RPI (Transmission cycle)
Tolerable communication
bandwidth for cyclic
0.5 to 10000 ms (in 0.5 ms)
6000 pps
communication
Specifications
*1 When using the power PoE power receiving function, use the STP cable or Category 5 or
higher UTP cable.
*2 The number of connectable units is not limited when using a switch.
*3 "N-bus" is the name of KEYENCE's wiring-saving system for sensor amplifiers.
*4 Varies with the sensor amplifiers connected.
*5 Current value which, when supplying power from the power supply connector, can be sup-
plied to the NU-EP1 or to a sensor amplifier unit connected to the NU-EP1.
*6 Power which can be supplied to the sensor amplifier when using the PoE power receiving
function.
*7 Varies according to the working ambient temperature.
(-20 to 45 °C: 360 mA or less, 45 to 50 °C: 260 mA or less, 50 to 55 °C: 140 mA or less)
*8 Does not include power supplied to connected sensor amplifier.
This section shows an example of data processing times for cyclic communication.
KV-EP21V
Ver.2
TM
EtherNet/IP
4
Maximum data processing time = (1) + (2) + (3) + (4)
(1) PLC scan time
Specifications
(2) RPI (Requested Packet Interval).
(3) NU-EP1 data communication time
(4) Sensor amplifier communication time
(2) RPI is set with the EtherNet/IP scanner in 0.5 ms increments between 0.5 ms and
10000 ms.
(3) The NU-EP1 data communication time is shown below.
Refer to each unit's manual for details on the (1) and (4) times.
29.4
15
4
38.5
(42.5)
20.3
Specifications
15
(0.2)
43.5 35.4
94.5 17.6
5
5-1 Device Profile ..................................................... 5-2
5-2 Troubleshooting .................................................. 5-3
5-3 Default Settings .................................................. 5-6
5-4 Procedures for Communicating with an Allen-Bradley
ControlLogix PLC ............................................... 5-7
5-5 Objects for Use with the NU-EP1 ..................... 5-18
5-6 Functions which Cannot be Set in Duplicate.... 5-35
5-7 Current Value Property of the Sensor .............. 5-40
5-8 List of Character String Codes ......................... 5-41
5-9 Index................................................................. 5-42
5
Appendix
The indicator lamps on the NU-EP1 are used to determine the cause of the error and
the necessary corrective actions.
Appendix
• Power is not supplied to the
nected device or Ethernet switch is
Not lit NU-EP1.
correctly connected.
• Link is not established.
• Check that the cables are correctly
connected.
• Check that the IP address is correct.
Appendix
(Error ID number/code: 00H/53) amplifiers are correctly connected, and
The number of connected sensor then turn the NU-EP1 power off and on.
amplifiers increased after power on. • Check whether a connected sensor ampli-
Solid red (Error ID number/code: 00H/54) fier is incompatible with the NU-EP1, and
The NU-EP1 and sensor amplifier then turn the NU-EP1 power off and on.
combination is not within the speci- • If the error is not resolved after checking
fied range. the above matters, contact your nearest
A system error may be occurring in Keyence office.
the NU-EP1.
Confirm that there are no sources of noise
Communication with the sensor
Flashing around the NU-EP1.
amplifier was temporarily cut off.
red (The error is automatically reset when the
(Error ID number/code: 00H/57)
cause is removed.)
• Check that the power is correctly con-
nected to the power terminal.
Not lit Power is not supplied to the NU-EP1. • When using the PoE function, check that
the power for the connected device or
Ethernet switch is correctly connected.
When the reset switch is held down for three seconds or longer, the NU-EP1 can be
reset and initialized to the default settings. This can also be done by using message
communication.
* Only the BOOTP client function can be used when the IP address is 0.0.0.0.
The IP address must be set to use any other function.
This section explains the procedures for communicating with the NU-EP1 using an
Allen-Bradley ControlLogix PLC (EtherNet/IP scanner).
Appendix
5
Appendix
Name
Set a random name. The following tags are generated based on the name set
here, and are used as the data exchanged with cyclic communication.
• (Name): I Data received from NU-EP1
• (Name): O Data sent to NU-EP1
• (Name): C Not used.
Comm Format
Designate [Data INT].
IP Address
Designate the NU-EP1's IP address.
Input (NU-EP1 send data size)
• Instance number: 100 (decimal)
• Data size: Random value up to 32
Output (NU-EP1 receive data size)
• Instance number 101 (decimal)
• Data size: Random value up to 1
Configuration
• Instance number: 1 (decimal)
• Data size: 0
5
Designate a value between 0.5 and 3200 ms.
Appendix
4 Download the settings to the PLC.
EtherNet/IP communication is enabled after the settings are downloaded and
the status is switched to online.
Sending data to multiple PLCs (InputOnly)
By connecting to multiple PLCs with the InputOnly connection format, multiple
PLCs can receive the data sent from the NU-EP1. Each PLC must be set as
shown below to use the InputOnly connection.
1 Define the following tags under the RsLogix5000 "Controller Tags" field.
• Tag for storing control information for MSG instruction (message- Message
type)
• Tag for storing data exchanged with MSG instruction (tx_param, rx_param -
INT type)
Appendix
Message Type
Select "CIP Generic".
ServiceType, Class, Instance, Attribute
Designate a value which matches the message to be sent.
• Example 1: Writing data to NU Object "Setting value (area upper limit)"
when writing data to attributes
4 Open the "Communication" tab, and change the MSG communication set-
tings.
5
Appendix
Path
Designate the device name set in "Configuration for cyclic communication". (An
example for the NUEP1 device is shown above.)
Connected, Cache Connections
• For UCMM connection: Invalidate bidirectional (default setting)
• For Class3 connection: Validate bidirectional
5 Describe the process for setting the send data and retrieving the receive
data with the ladder program, and download it to the PLC.
Point The size of attribute ID used for SLC5/05 Series is 1 byte or smaller.
The SLC5/05 Series does not support the parameter which contains 2
byte attribute ID.
Reference
• The SLC5/05 Series does not support the cyclic communication function,
but by accessing the NU-EP1's Assembly Object with messages, control
can be executed with the same data type and procedures as cyclic com-
munication.
• Up to 248 bytes can be exchanged with the SLC5/05 series message
communication.
5
- Do not exceed this size when exchanging data with message commu-
Appendix
nication.
- The Assembly Object data size is the same as the cyclic communica-
tion data size set in the NU-EP1 properties. When using the SLC5/05,
confirm that this value is 248 bytes.
Reference
Refer to the "SLC 500 Instruction Set Reference Manual" (1747-RM001),
etc., for details on the EEM instructions.
5
Appendix
3 Designate the File used in the EEM instruction defined in Step 1 for the
EEM instruction Control Block, and open the SetupScreen.
ServiceType
Item Setting value
Generic Set Attribute Single
5
ServiceCode - (Cannot be designated)
Appendix
Class 66H
Instance 0H
Attribute 85H
Data Table Address (Send data) - (Cannot be designated)
Size In Words (Send data) - (Cannot be designated)
Data Table Address (Received data) Name of file storing send data
Size In Words (Received data) 1 word (attribute size is 1)
• Example 2: To control with same format and procedure as set cycle data,
Access the Assembly Object attribute3: data.
* The message exchanged with SLC5/05 can have up to 124 words (248
bytes). Confirm that the cyclic communication data size is set to 248 in the
Appendix
NU-EP1 properties.
* The message exchanged with SLC5/05 can have up to 124 words (248
bytes). Confirm that the cyclic communication data size is set to 248 in the
NU-EP1 properties.
5 Open the "Send Data" tab and "Receive Data" tab, and check the contents
of the file containing the send and receive data.
Appendix
6 Describe the process for setting the send data and retrieving the receive
data in a ladder program, and download it to the PLC.
This section explains the objects for use with the NU-EP1.
Refer to "How to Use NU Objects" (page 3-30) for details on the NU Objects.
5
Reading Each Object Table
Appendix
Item Details
(1) Attribute ID Expresses the attribute ID as a hexadecimal.
(2) Name Indicates the attribute name.
(3) Description Describes the attribute.
Indicates the direction of services on the attribute ID.
R (Read): The attribute values can be read using Get_Attribute_Single
(4) Attribute and Get_Attributes_All.
W (Write): A value can be written into the attributes using
Set_Attribute_Single.
(5) Data type Indicates the attribute data type.
Indicates the range of the data read from the attributes or the parameters
(6) Parameter range
which can be set.
Data type
The data type is defined in the following manner by the EtherNet/IP specifications.
Range
Data type Description
Minimum Maximum
INT Signed 16-bit integer -32768 32767
UINT Unsigned 16-bit integer 0 65535
USINT Signed 8-bit integer 0 255
UDINT Unsigned 32-bit integer 0 232-1
WORD Bit string: 16-bit - -
DWORD Bit string: 32-bit - -
BYTE Bit string: 8-bit - -
Character string (1-byte length information +
SHORT_STRING - -
1-byte per 1-character array)
Character string (2-byte length information +
STRING - -
1-byte per 1-character array)
Appendix
This object provides the NU-EP1 identification information, general information and
resetting service, etc.
Class
Class service
Get_Attribute_Single (0EH) and Get_Attributes_All (01H) are supported.
Class attribute (instance ID: 00H)
Data Parameter
Attribute ID Name Description Attribute
type range
01H Revision Object revision R UINT 0001H
Maximum instance num-
02H Max Instance R UINT 0001H
ber
Number of Number of instances in
03H R UINT 0001H
Instances generated object
Maximum ID
Maximum attribute ID of
06H number Class R UINT 0007H
class attribute
Attributes
Maximum ID
Maximum ID number of
07H number Instance R UINT 0007H
instance attribute
Attributes
Instance
Instance service
Get_Attribute_Single (0EH), Get_Attributes_All (01H) and Reset service (05H) are
supported.
"Reset service" (page 5-21)
-EtherNet/IP Compatible Network Unit NU-EP1 User's Manual - 5-19
5-5 Objects for Use with the NU-EP1
Data Parameter
Attribute ID Name Description Attribute
type range
01H Vendor ID Vendor ID R UINT 016FH
02H Device Type General device type R UINT 0000
03H Product Code Product ID R UINT 09C5H
Revision IdentityObject revision Structure -
04H Major Revision Major revision R USINT 01H
Minor Revision Minor revision USINT 01H
05H Status NU-EP1 status R WORD Reference 1
06H Serial Number Serial number R UDINT Serial number
SHORT-
07H Product Name Product name R "NU-EP1"
STRING
Identity Object
Reset service
The Reset service is a CIP standard function used to emulate the same operations
which can only be executed when the power is reset. When this function is received,
the NU-EP1 stops each function, cuts off the communication and reads in the settings
again. The Reset service is used as a restart request to apply changed parameters
(e.g., IP address, Ethernet communication speed, etc.).
Execute the Reset service by designating 01H for the Identify object Instance ID.
05H Reset
reset.
Refer to "Default Settings" (page 5-6) 5
• If any other value is designated, 03H (Invalid parameter
value) will be returned to the general status.
Appendix
List of general statuses returned to each service
General Extended
Name Details
status status
Get_Attributes 00H - The process ended normally.
_All 05H - The designated instance ID does not exist.
00H - The process ended normally.
Reset 03H - The designated reset method is incorrect.
05H - The designated instance ID does not exist.
00H - The process ended normally.
Get_Attribute_
05H - The designated instance ID does not exist.
Single
14H - The designated attribute ID does not exist.
Others 08H - The designated service is not supported.
Identity Object
Class
Class service
Get_Attribute_Single (0EH) is supported.
Class attribute (instance ID: 00H)
Data Parameter
Attribute ID Name Description Attribute
type range
01H Revision Object revisions R UINT 0001H
02H Max Instance Maximum instance number R UINT 0001H
Number of Number of instances in
03H R UINT 0001H
Instances generated object
5 06H
Maximum ID
number Class
Maximum attribute ID of
class attribute
R UINT 0007H
Attributes
Appendix
Maximum ID
number Maximum ID number of
07H R UINT 0002H
Instance instance attribute
Attributes
Instance
Instance service
Get_Attribute_Single (0EH) is supported.
Instance attribute (instance ID: 01H)
Data Parameter
Attribute ID Name Description Attribute
type range
List of supported
Object_list Structure -
objects
Number of supported
Number UINT 0007H
classes in class array
0001H
01H R 0002H
0004H
Array of
Classes List of class IDs 0006H
UINTs
00F5H
00F6H
0066H
Maximum number of
02H Number Available R UINT 0040H
connections
General Extended
Name Details
status status
00H - The process ended normally.
Get_Attribute_Single 05H - The designated instance ID does not exist.
14H - The designated attribute ID does not exist.
Others 08H - The designated service is not supported.
This object is used to directly access and control the same data as that exchanged
with cyclic communication using message communication. This can be used to send
data to a device which does not support cyclic communication.
Class
Class service 5
Get_Attribute_Single (0EH) is supported.
Appendix
Class attribute (instance ID: 00H)
Data Parameter
Attribute ID Name Description Attribute
type range
01H Revision Object revisions R UINT 0002H
Instance
Instance service
Get_Attribute_Single (0EH) and Set_Attribute_Single (10H) are supported.
Instance attribute (instance ID: 64H to 66H)
Instance ID is assigned when using instances to set tags.
Data
Attribute ID Name Description Attribute Parameter range
type
Data assigned to Instance Array of Set data assigned
03H Data R/W*1
ID BYTEs to instance ID*2*3
Set size assigned
Number of bytes assigned
04H Size R UINT to instance ID(byte
to intendance ID
unit)
Assembly Object
General Extended
Name Details
status status
00H - The process ended normally.
The designated instance ID does not
05H -
Get_Attribute_Single exist.
The designated attribute ID does not
14H -
exist.
Assembly Object
This object is used for connection type communication. Use this to establish a con-
nection with the NU-EP1.
Class
Class service/class attribute
There are no class services or class attributes.
Instance
Instance service
Forward_Close (4EH) and Forward_Open (54H) are supported. Refer to the CIP
specifications for details on the services.
Instance attribute
There are no instance attributes.
5
List of general statuses returned to each service
Appendix
General Extended
Name Details
status status
00H - The process ended normally.
Forward_ 04H - Attribute ID was not designated.
Close 05H - The designated instance ID does not exist.
13H - Length of send data is too short.
00H - The process ended normally.
0100H The designated connection is already in use.
0103H The designated trigger cannot be used.
• The target originator direction connection point desig-
nated with the ForwardOpen connection path in cyclic
0106H communication is already in use, and is Point to Point.
• The type of connection trying to be opened is Point to Point.
• The size currently in use differs from the size being opened.
Forward_ • The send direction connection is not Point to Point.
Open 0108H • The receive direction connection parameter is not Point to
01H
Point or Multicast.
The size trying to be opened is larger than the NU-EP1 con-
0109H
nection size.*1
• The time out multiplier is larger than 7.
0111H
• An RPI less than 500 µs or larger than 10s was designated.*2
0114H The Vendor ID does not match. The Product Code does not match.
0115H The DeviceType does not match.
0116H The revision does not match.
General Extended
Name Details
status status
• The ForwardOpen network connection parameter Connec-
tion Size is 0.
• The ForwardOpen Connection Point does not contain a
ConnectionPoint.
• For the ForwardOpen Connection Path class ID, a value
other than 04H was set for cyclic, or a value other than 02H
for Class 3.
• A value other than 1 was set with Class 3 for the instance
ID of the ForwardOpen Connection Path.
0315H • There is a setting unique for the product data segment.
• An illegal Connection Point was designated with cyclic
communication for the send direction of the ForwardOpen
Connection Path.
• A value other than 2 was set with cyclic communication for
the ForwardOpen send direction network connection
parameter Connection Size.
• An illegal Connection Point was designated with cyclic
communication for the receive direction of the Forwar-
dOpen Connection Path.
• An error occurred during communication between sensors.
0322H • The IP assignment failed when starting.
5 01H 0323H
• A sensor was disconnected during operation.
A sensor amplifier which is not compatible with the NU-EP1
was connected.
Appendix
*1 Successful if smaller than the NU-EP1 connection size. If this error occurs, the expansion
status is added and the data size defined in the second expansion status is returned.
*2 RPI is set in increments of 500 µs. If a value which cannot be divided by 500 µs is
set, an RPI rounded to the nearest 500 µs is set.
This object provides a system to set the TCP/IP network interface. The IP address,
subnet mask and gateway, etc., can be set.
Class
Class service
Get_Attribute_Single (0EH) and Get_Attributes_All (01H) are supported.
Class attribute (instance ID: 00H)
Data Parameter
Attribute ID Name Description Attribute
type range
01H Revision Object revisions R UINT 0001H
02H Max Instance Maximum instance number R UINT 0001H
Number of Number of instances in
03H R UINT 0001H
Instances generated object
5
Instance
Appendix
Instance service
• Get_Attribute_Single (0EH), Set_Attribute_Single (10H) and Get_Attributes_All
(01H) are supported.
• If the internal process of the previous Set_Attribute_Single is not completed, the
general status "0CH" (Object State Conflict) will be returned in response to the
Set_Attribute_Single executed to the writable AttributeID.
• Changes to the writable AttributeID are applied when executing the reset service
after power is turned on again.
Data Parameter
Attribute ID Name Description Attribute
type range
01H Status Interface status R DWORD (Reference 1)
Configuration Method of acquiring initial
02H R DWORD (Reference 2)
Capability IP address
Configuration Method device acquires
03H R/W DWORD (Reference 3)
Control default settings at start-up
PhysicalLink
Path to physical link object Structure -
Object
04H Path size Path size (byte) R UINT 0004H
Segment for designating Padded
Path 20F62401H
physical link object EPATH
Interface TCP/IP network interface
Structure -
Configuration setting
Device IP address
IP Address
(IP address)
UDINT Setting value*1
5 Network Mask
Device network mask
(subnet mask)
UDINT Setting value*1
Gateway Default gateway address
05H R/W UDINT Setting value*1
Appendix
Data Parameter
Attribute ID Name Description Attribute
type range
Mcast Config Multicast address setting Structure -
0: Automatic
Multicast address setting allocation
Alloc Control function (multicast alloca- USINT 1: User-desig-
tion method) nated alloca-
tion
Reserved Reserved USINT 00H
For automatic
allocation:
Number of multicast 0020H
09H R/W
Num Mcast addresses(Number of mul- UINT For user-desig-
ticast addresses) nated alloca-
tion: 1 to 256*1
For automatic
allocation:*2
Start multicast
Mcast Start For user-desig-
Addr
address(Allocation start
multicast address)
UDINT
nated alloca-
tion: Setting
5
value*1
Appendix
*1 If an invalid value is written in, the general status 09H (Invalid Attribute Value) is
returned.
*2 When automatically assigning, the start multicast address is calculated with
239.192.1.0+ ((IP address host section -1) * 03FF) x 32).
(Example)
When IP address is 192.168.0.10, the multicast address is as follows.
Start address = 239.192.1.0 + (((192.168.0.10 - 1) & 0x3FF) << 5)
= 239.192.1.0 + ((192.168.0.9 & 0x3FF) << 5)
= 239.192.1.0 + (0.0.0.9 << 5)
= 239.192.1.0 + 0.0.1.32
= 239.192.2.32
General Extended
Name Details
status status
00H - The process ended normally.
Get_Attributes_All
05H - The designated instance ID does not exist.
00H - The process ended normally.
Get_Attribute_Single 05H - The designated instance ID does not exist.
14H - The designated attribute ID does not exist.
00H - The process ended normally.
05H - The designated instance ID does not exist.
09H - Written value is illegal.
Set_Attribute_Single
0EH - CanÅft write to designated attribute ID.
13H - Length of send data is too short.
14H - The designated attribute ID does not exist.
Others 08H - The designated service is not supported.
Class
Class service
Get_Attribute_Single (0EH) and Get_Attributes_All (01H) are supported.
Class attribute (instance ID: 00H)
Data Parameter
Attribute ID Name Description Attribute
type range
01H Revision Object revisions R UINT 0002H
02H Max Instance Maximum instance number R UINT 0001H
Number of Number of instances in gener-
03H R UINT 0001H
Instances ated object
5
Instance
Appendix
Instance service
Get_Attribute_Single (0EH), Set_Attribute_Single (10H) and Get_Attributes_All
(01H) are supported.
Instance attribute (instance ID: 01H)
Data Parameter
Attribute ID Name Description Attribute
type range
Interface
01H Interface communication speed. R UDINT 10, 100
Speed
02H Interface Flags Interface status flag. R DWORD (Reference 1)
ARRAY
Physical Current
03H MAC layer address R of 6
Address value
USINTs
Interface Current
Interface counter -
Counters value
Number of octets received on the
interface. Includes the unneces-
Current
In Octets sary multicast packets and dis- UDINT
value
04H carded packets counted with In R
Discards.
Number of octets received on the
In Ucast interface. Does not include the Current
UDINT
Packets discarded packets counted with In value
Discards.
Data Parameter
Attribute ID Name Description Attribute
type range
Number of nonunicast packets
received on the interface. Includes
In NUcast Current
unnecessary multicast packets, UDINT
Packets value
but not discarded packets counted
with In Discards.
Number of inbound packets con-
Current
In Discards taining errors, not including dis- UDINT
value
cards.
Number of received packets con-
Current
In Errors taining errors. Is not included in In UDINT
value
Discards.
04H In Unknown Number of inbound packets with R UDINT 0 (fixed)
Protos unknown protocols.
Number of octects sent on the Current
Out Octets UDINT
interface. value
Out Ucast Number of unicast packets sent Current
UDINT
5 Packets
Out NUcast
on the interface.
Number of nonunicast packets
UDINT
value
Current
Packets sent on the interface. value
Appendix
Data Parameter
Attribute ID Name Description Attribute
type range
Number of frames for which trans-
MAC Transmit
mission failed because of internal UDINT 0 (fixed)
Errors
MAC sublayer transmit error.
Number of times carrier sense
Carrier Sense condition was lost or never Current
UDINT
Errors asserted when transmitting value
frames.
05H R
Number of received frames that
Frame Too Current
exceeded the maximum tolerable UDINT
Long value
frame size.
Number of frames lost during
MAC Receive transmission on the interface due
UDINT 0 (fixed)
Errors to an internal sublayer receive
error.
Interface Settings for following physical Following
-
Control interface. structure
06H
Control Bits
Interface control bit (Designate
AutoNego, full duplex) W
WORD (Reference 2) 5
Forced Setting
Operation speed forced by inter-
Interface UINT
Appendix
Speed
face. (Fixed to 10 Mbps, etc.) value*1
*1 The following interface speed can be set for Forced Interface Speed.
When auto-negotiation is disabled (half-duplex): 10 Mbps fixed (setting value: 10)
When auto-negotiation is enabled (half-duplex/full duplex): 100/10 Mbps auto-
matic (setting value: 0 or 100)
General Extended
Name Details
status status
00H - The process ended normally.
Get_Attributes_All
05H - The designated instance ID does not exist.
5 Get_Attribute_Single
00H
05H
-
-
The process ended normally.
The designated instance ID does not exist.
14H - The designated attribute ID does not exist.
Appendix
When functions that cannot be set or used at the same time are set via communica-
tion, the function with the lower priority will be invalidated or canceled.
Also, setting errors can be checked with the cyclic communication data byte2/bit3 of
the NU-PN1.
FS-N40 Series
Sensor
Function 2
Function 1 (Priority: High) Function 2 (Priority: Low) setting
operation
error
HSPD Interference Prevention Double Invalid state
Power Modes
S-HSPD Display Gain Full Invalid state
Preset Start Cancel
Zero-shift Start Cancel
External input invalid
External Input function Zero-shift ON
state
Rising Edge Detec-
Detection Limit Detection Setting Valid Invalid state ON
tion Mode Falling
Mode "---- ----" appears on
Edge Detection
(Output 1) Display Bar Setting Valid amplifier’ s digital ON
Mode
Sub Display
Display Hold
Gain % Hold
display.
"---- ----" appears on
amplifier’ s digital ON
5
display.
Execution not possi-
Appendix
Preset Start
ble (cancel)
Execution not possi-
Zero-shift Start
ble (cancel)
Detection
External input invalid
Mode DATUM Mode External Input function Zero-shift ON
state
(Output 1)
Preset Saturation Level Other than 101 Functions as 101.
"---- ----" appears on
Sub Display Gain % Hold amplifier’ s digital ON
display.
Limit Detection Set-
Valid Invalid state ON
Detection ting
Area Detection Mode
Mode "---- ----" appears on
Area % Mode Display Hold
(Output 1) Sub Display amplifier’ s digital ON
Gain % Hold
display.
Detection Mode Execution not possi-
Zero-shift Calibration Preset Start
(Output 1) ble
External Input Execution not possi-
Zero-shift Preset Start ON
function ble
Area Detection Mode
Area % Mode
DATUM Mode
Detection Mode Normal Detection
Rising Edge Detec- OFF
(Output 1) Mode
tion Mode
Falling Edge Detec-
Power Modes S-HSPD tion Mode
External Input function Reset Cancel ON
Limit Detection Setting Valid Invalid state ON
"---- ----" appears on
Display Hold
Sub Display amplifier’ s digital ON
Gain % Hold
display.
Power Save FULL Invalid state
FS-N10 Series
Sensor
Function 2
Function 1 (Priority: High) Function 2 (Priority: Low) setting
operation
error
Interference
Double Invalid state
Power Mode HIGH SPEED Prevention
Display Gain Full Invalid state
Preset Start Cancel
Zero-shift Start Cancel
Preset External input invalid
Rising Edge Control Input ON
Detection Zero-shift state
Detection Mode
Mode Detection Mode Operates as Normal
Falling Edge Limit Setting Output ON
(Output 1) (Output 2) Detection Mode.
Detection Mode
Bar Excess Gain (%) "---- ----" appears on
Sub Display Excess Gain HOLD amplifier’ s digital ON
(%) display.
Execution not
Preset Start
possible (cancel)
Execution not
Zero-shift Start
possible (cancel)
Detection Preset External input invalid
5 Mode
(Output 1)
DATUM 1 Mode
DATUM 2 Mode
Control Input
Preset Satuation
Level
Zero-shift
Other than 101
state
Functions as 101.
ON
LV-N10 Series
Sensor
Function 2
Function 1 (Priority: High) Function 2 (Priority: Low) setting
operation
error
Interference
Double Invalid state
Power Mode HIGH SPEED Prevention
Display Gain Full Invalid state
Preset Request / Work-Preset Request / Execution not
Maximum Sensitivity Preset: Request possible (cancel)
Execution not
Full Auto Preset: Start
possible (cancel)
Rising Edge Zero-shift Request Cancel
Detection
Detection Mode Preset External input invalid
Mode External Input ON
Falling Edge Zero-shift state
(Output 1)
Detection Mode Detection Mode Operates as Normal
Limit Setting Output ON
(Output 2) Detection Mode.
Bar Excess Gain (%) "---- ----" appears on
Sub Display Excess Gain HOLD amplifier's digital ON
(%) display.
Execution not
Preset Request
possible (cancel)
Detection
Zero-shift Request
Execution not
possible (cancel)
External input invalid
5
DATUM 1 Mode External Input Preset Zero-shift ON
Mode state
DATUM 2 Mode
Appendix
(Output 1) Preset Saturation
Other than 101 Functions as 101.
Level
"---- ----" appears on
Excess Gain HOLD
Sub Display amplifier's digital ON
(%)
display.
Detection Mode Operates as Normal
Limit Setting Output ON
Detection (Output 2) Detection Mode.
Mode Area Detection Mode Bar Excess Gain (%) "---- ----" appears on
(Output 1) Sub Display Excess Gain HOLD amplifier's digital ON
(%) display.
DATUM 1 Mode
DATUM 2 Mode
Detection Area Detection Mode
Mode Rising Edge Sensitivity Setting Zero-shift Calibration Invalid state
(Output 1) Detection Mode
Falling Edge
Detection Mode
Preset Request / Work-Preset Request / Execution not
Maximum Sensitivity Preset: Request possible (cancel)
Sensitivity Execution not
Zero-shift Calibration Full Auto Preset: Start
Setting possible (cancel)
External input invalid
External Input Preset ON
state
Execution not
External Input Preset Zero-shift Request
possible (cancel)
Preset Request / Work-Preset Request / Execution not
Maximum Sensitivity Preset: Request possible (cancel)
External Input Zero-shift
Execution not
Full Auto Preset: Start
possible (cancel)
Interference
Power Save All Double Invalid state
Prevention
For items other than listed above, some functions cannot be set depending on the
connected sensor head. Therefore, make sure to execute the initial reset (initializa-
tion) of the sensor amplifier after changing the sensor head.
PS-N10 Series
Sensor
Function 2
Function 1 (Priority: High) Function 2 (Priority: Low) setting
operation
error
Preset Request / Work-Preset Request / Execution not
Maximum Sensitivity Preset: Request possible (cancel)
Execution not
Full Auto Preset: Start
Rising Edge possible (cancel)
Detection Detection Mode Zero-shift Request Cancel
Mode Falling Edge Preset External input invalid
External Input ON
Detection Mode Zero-shift state
Bar Excess Gain (%) "---- ----" appears on
Sub Display Excess Gain HOLD amplifier’ s digital ON
(%) display.
Execution not
Preset Request
possible (cancel)
Execution not
Zero-shift Request
possible (cancel)
External input invalid
Detection DATUM 1 Mode External Input Preset Zero-shift ON
state
Mode DATUM 2 Mode
Preset Saturation
5 Level
Sub Display
Other than 101
MU-N/LR-T Series
Sensor
Function 2
Function 1 (Priority: High) Function 2 (Priority: Low) setting
operation
error
Switching Out 1/
I/O Function Output 1+Input Output 2 Output 1 ON
Out 2
Switching Out 1/
Output 2 Mode Stability Error Output 2 Output 1 ON
Out 2
4 ms (Class2)/
Response 5 ms (Class1) Received Light Sen- Low
High ON
Time 13 ms (Class2)/ sitivity Mid
23 ms (Class1)
Off delay
Output 1 timer On delay Graphic Mode On Triger Stops the graph drawing update
One-shot
5
MU-N/LR-W Series
Appendix
Sensor
Function 2
Function 1 (Priority: High) Function 2 (Priority: Low) setting
operation
error
Detection Mode
Output Mode Binary I Auto ON
(ALL, 1 to 16)
Output Mode Binary Response Time 0 1 ON
External Input
Output Mode Binary Tuning Invalid state ON
Function
Output Mode Binary Timer Mode 1 One-shot Invalid state ON
A-1 (Difference
Monitoring)
Output Mode Binary Spot/Mode Selection 1spot ON
A-2 (2-Point
Matching)
Output Mode 4-Output, 2-Bank Bank selection 2 or more 0 ON
Output Mode 4-Output, 2-Bank Cannel Selection 4 or more 0 ON
Output Mode 4-Output, 2-Bank Spot/Mode Selection A-1 (Tuning Free) 1spot ON
Timer function On delay
of the selected Off delay Graphic Mode On Peak Stops the graph drawing update
bank One-shot
Timer function On delay
of the selected Off delay Graphic Mode On Trigger Stops the graph drawing update
bank One-shot
Using the the "Current value property", you can check if the sensor connected to the
NU-EP1 is operating as intended.
There are three types of the current value property - "Disabled", "Upper limit over" and
"Lower limit over".
The current value property is assigned as the following communication data.
Communication
Assigned area
method
Cyclic communication IN Area: Address 8 to 13
Message communication Instance ID: 00H, Attribute ID: 68H, 8DH, 8EH, 8FH
When the sensor is in the following status, the bit corresponding to "Current Value
Property", "Current Value Over Range", "Current Value Under Range", or "Current
Value Invalid" turns ON.
Sensor display for the current value
Sensor Current value property
property
5 LV-N10 Series
+LV-S31
Disable
Upper limit over
Lower limit over
Disable N/A
When connecting AP-41/41M/44 :
Appendix
If the "sub display" is set to "TAG display" when a character string is stored in the "TAG
character string", the character string can be displayed on the amplifier. The following
character strings can be used.
Appendix
* If a code which is not assigned to the 7-segment display is set, the character string
will remain blank on the display.
This index provides a list of terms used in this document in alphabetical order.
C N
Checking the Package Contents ......... 1-3 NU-EP1 EtherNet/IP Communication
Package Contents ....................... 1-3 Function ...............................................3-3
Configuring Communication with Assigning the Sensor ID Number 3-4
NU-EP1 ............................................. 2-11 NU-EP1 Overview ................................1-2
NU-EP1 Settings ....................... 2-11 Overview ......................................1-2
Configuring Communication with the Types and Number of Connectable
Scanner ............................................. 2-14 Sensor Amplifiers .........................1-2
Setting the Scanner ................... 2-14
Cyclic Communication ......................... 3-6 O
Assignment to IN Area
(NU-EP1 to Scanner) ................ 3-11 Objects for Use with the NU-EP1 .......5-18
Assignment to OUT Area Assembly Object
(Scanner to NU-EP1) ................ 3-17 (Class ID: 04H) ..........................5-23
Checking the Device Compatibility .... 3-23 Connection Manager Object
(Class ID: 06H) ..........................5-25
5 Configuring Cyclic Communication ..... 3-8
Cyclic communication data Ethernet Link Object
(Class ID: F6H) ..........................5-31
assignment ................................ 3-18
Usable Connections .................... 3-9 Identify Object
Appendix
I P
Installation and Connection to Sensor Parameter List ....................................3-35
Amplifiers ............................................. 2-3 AP-N10/N10D ............................3-96
Connectable sensor amplifiers and FS-N10/N12 ...............................3-51
quantities ..................................... 2-3 FS-N14 ......................................3-62
Connecting the Sensor Amplifier ..... 2-4 FS-N40/N42*/N44* ....................3-39
LV-N10/N12/N12C .....................3-73
M MU-N/FD-Q ..............................3-122
MU-N/LR-T ..............................3-102
Message Communication .................. 3-24 MU-N/LR-W .............................3-110
Basic Format for Message NU-EP1 ......................................3-36
Communication and PS-N10/N12 ...............................3-85
Flow of Process ......................... 3-28 Reading the NU Object Table ....3-35
Configuring Message Part Names ..........................................1-4
Communication ......................... 3-25 Procedures for Communicating with an
How to Use NU Objects ............ 3-30 Allen-Bradley ControlLogix PLC ..........5-7
Objects and Services ................ 3-26 Procedures for communicating with an
Objects Usable with NU-EP1 .... 3-27 Allen-Bradley ControlLogix PLC .....5-7
Procedures for Communication with an
Allen-Bradley SLC5/05 PLC ......5-13
S
Specifications ...................................... 4-2
Steps for Preparing to
Use the NU-EP1 .................................. 2-2
Flow from Installation to
Communication Configuration ..... 2-2
T
Troubleshooting ................................... 5-3
W
What is EtherNet/IP? ........................... 3-2
What is EtherNet/IP? ................... 3-2
Wiring .................................................. 2-6
Connecting the Communication
Cable ........................................... 2-6
Power supply ............................... 2-8
5