POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

Service Block - Basement


Booster Pumps 2
On/Off Status 2 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS
Trip Status 2 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS

Water Tank (Fire, Potable water Tank ) 3


High Level Alarm 3 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS
Low Level Alarm 3 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS

Sprinkler - Electric Pump 3


On/Off Status 3 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS
Trip Status 3 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS
Power Failure 1

Hydrant Pump 3
On/Off Status 3 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS
Trip Status 3 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS
Power Failure 1

Wet Riser Pump 3


On/Off Status 3 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS
Trip Status 3 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS
Power Failure 1

Horse Reel Pump 2


On/Off Status 2 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS
Trip Status 2 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS
Power Failure 1

FAF 3
(SB-FAF-B1-01~ 03) Auto/Manual Status 3 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 3 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 3 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Alarm 3 Volt Free Contact HVAC HVAC HVAC/BMS

EAF 3
(SB-EAF-B1-01 ~03) Auto/Manual Status 3 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 3 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 3 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Alarm 3 Volt Free Contact HVAC HVAC HVAC/BMS

Catch Pits Pumps 6


On/Off Status 6 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS
Trip Status 6 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS

Sewer Pumps
On/Off Status 12 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS
Trip Status 12 Volt Free Contact
Plumbing Con. Plumbing Con. Plumbing/BMS

DDC- SB-B -01 90 6 0 0 0

Service Block - Ground Floor


POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

Transformer 7
(Transformer Room) High Temperature Alarm 7 Volt Free Contact ELEC ELEC ELEC/BMS
Common Fault 7 Volt Free Contact ELEC ELEC ELEC/BMS

Chiller 4
(Chiller Pant Room) Water Return/Entering Temperature 4 BACnet/ MSTP, IP , Mobbus RTU HVAC HVAC BMS
Water Leaving Temperature 4 BACnet/ MSTP, IP , Mobbus RTU HVAC HVAC BMS
Voltage 4 BACnet/ MSTP, IP , Mobbus RTU HVAC HVAC BMS
Power Factor 4 BACnet/ MSTP, IP , Mobbus RTU HVAC HVAC BMS
Oil Tank Temperature 4 BACnet/ MSTP, IP , Mobbus RTU HVAC HVAC BMS
Oil Differentials Pressure 4 BACnet/ MSTP, IP , Mobbus RTU HVAC HVAC BMS
Manual Reset Alarm 4 BACnet/ MSTP, IP , Mobbus RTU HVAC HVAC BMS
kWh 4 BACnet/ MSTP, IP , Mobbus RTU HVAC HVAC BMS
Fault Code 4 BACnet/ MSTP, IP , Mobbus RTU HVAC HVAC BMS
Evaporator Temperature 4 BACnet/ MSTP, IP , Mobbus RTU HVAC HVAC BMS
Evaporator Refrigerant Pressure 4 BACnet/ MSTP, IP , Mobbus RTU HVAC HVAC BMS
Demand Limit Set point 4 BACnet/ MSTP, IP , Mobbus RTU HVAC HVAC BMS
Current 4 BACnet/ MSTP, IP , Mobbus RTU HVAC HVAC BMS
COW Return/Entering Temperature 4 BACnet/ MSTP, IP , Mobbus RTU HVAC HVAC BMS
COW Leaving Temperature 4 BACnet/ MSTP, IP , Mobbus RTU HVAC HVAC BMS
Cooling Output (kW) 4 BACnet/ MSTP, IP , Mobbus RTU HVAC HVAC BMS
Condensers Temperature 4 BACnet/ MSTP, IP , Mobbus RTU HVAC HVAC BMS
Condenser Refrigerant Pressure 4 BACnet/ MSTP, IP , Mobbus RTU HVAC HVAC BMS
Compressor Discharge Temperature 4 BACnet/ MSTP, IP , Mobbus RTU HVAC HVAC BMS
Communication Status 4 BACnet/ MSTP, IP , Mobbus RTU HVAC HVAC BMS
CHW Set point 4 BACnet/ MSTP, IP , Mobbus RTU HVAC HVAC BMS
Auto Reset Alarm 4 BACnet/ MSTP, IP , Mobbus RTU HVAC HVAC BMS
% RLA 4 BACnet/ MSTP, IP , Mobbus RTU HVAC HVAC BMS

Chiller Auto/Manual Status 4 Volt Free Contact HVAC HVAC HVAC/BMS


Chiller On/Off Status 4 Volt Free Contact HVAC HVAC HVAC/BMS
Chiller Trip Alarm 4 Volt Free Contact HVAC HVAC HVAC/BMS
Chiller Start/Stop Command 4 Volt Free Contact HVAC HVAC HVAC/BMS
Emergency Stop Status 4 Volt Free Contact HVAC HVAC HVAC/BMS
CHW Leaving Flow Status 4 Volt Free Contact BMS HVAC BMS
CW Leaving Flow Status 4 Volt Free Contact BMS HVAC BMS
CHW Leaving Temperature 4 10K BMS HVAC BMS
CHW Entering Temperature 4 10K BMS HVAC BMS
CW Leaving Temperature 4 10K BMS HVAC BMS
CW Entering Temperature 4 10K BMS HVAC BMS

VSD Control 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS


VSD Feedback 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

Motorized Butterfly Valves @ Chiller 8


(Chiller Plant Room) Butterfly Valve On/Off Control 8 Volt Free Contact HVAC HVAC HVAC/BMS
Butterfly Valve Open/Close Status 8 Volt Free Contact HVAC HVAC HVAC/BMS

CHW Pumps 4
(Chiller Plant Room) Auto/ Manual Status 4 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 4 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 4 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 4
POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

VSD Speed Control 4 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS


VSD Speed Feed back 4 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
CHW Header Pressure 1 4-20mA BMS HVAC BMS

COW Pumps 4
(Chiller Plant Room) Auto/ Manual Status 4 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 4 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 4 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 4 Volt Free Contact HVAC HVAC HVAC/BMS
COW Header Pressure 1 4-20mA BMS HVAC BMS

2
VSD Control 4-20mA HVAC HVAC HVAC/BMS
VSD Feedback 2 4-20mA HVAC HVAC HVAC/BMS

Air Conditioning Supply and Return Pipes


(Chiller Plant Room) CHW Supply Temperature 1 10K BMS HVAC BMS
CHW Return Temperature 1 10K BMS HVAC BMS
CHW Supply Pressure 1 4-20mA BMS HVAC BMS
CHW Return Pressure 1 4-20mA BMS HVAC BMS

CHW Supply Flow rate 1 4-20mA BMS HVAC BMS

By Pass Valve 1
(Chiller Plant Room) By Pass Valve Control 1 0-10VDC HVAC HVAC HVAC/BMS
By Pass Valve Position Feedback 1 2-10VDC HVAC HVAC HVAC/BMS
CHW Differential Pressure 2 4-20mA BMS HVAC BMS

11KV Switchgear 1
On Off Status 1 4-20mA Electrical Electrical BMS

Volt Free Contact


Trip Status 1 Electrical Electrical BMS

FAF
(SB-FAF-GD-01 ~ 3 ) 3
Auto/Manual Status 3 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 3 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 3 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Alarm 3 Volt Free Contact HVAC HVAC HVAC/BMS

EAF
(SB-EAF-GD-01 ~ 5 ) 5
Auto/Manual Status 5 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 5 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 5 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Alarm 5 Volt Free Contact HVAC HVAC HVAC/BMS

FCU 5
(Plant room-3, LT room & HT room) Space Temperature 5 BACnet/MSTP BMS BMS BMS
Start/Stop Command 5 BACnet/MSTP BMS BMS BMS
On/Off Status 5 BACnet/MSTP BMS BMS BMS
Fan Speed 01 5 BACnet/MSTP BMS BMS BMS
Fan Speed 02 5 BACnet/MSTP BMS BMS BMS
Fan Speed 03 5 BACnet/MSTP BMS BMS BMS
POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

DDC-SB-GF-01 101 48 39 9 92

Service Block - 1st Floor

Generator 4
(Generator Room)
BACnet / MSTP / MODbus GEN GEN GEN/BMS
Common Alarm 4 BACnet / MSTP / MODbus GEN GEN GEN/BMS
Voltage 4 BACnet / MSTP / MODbus GEN GEN GEN/BMS
Amperage 4 BACnet / MSTP / MODbus GEN GEN GEN/BMS
kW 4 BACnet / MSTP / MODbus GEN GEN GEN/BMS
kWh 4 BACnet / MSTP / MODbus GEN GEN GEN/BMS
RPM 4 BACnet / MSTP / MODbus GEN GEN GEN/BMS
Battery Charger Level-Alarm 4 BACnet / MSTP / MODbus GEN GEN GEN/BMS
Oil Pressure Alarm 4 BACnet / MSTP / MODbus GEN GEN GEN/BMS
Oil Temperature Alarm 4 BACnet / MSTP / MODbus GEN GEN GEN/BMS
Coolent Temperature Alarm 4 BACnet / MSTP / MODbus GEN GEN GEN/BMS

Fuel Pump-GEN 2
On Off Status 2 Volt Free Contact GEN GEN GEN/BMS
Trip Syatus 2 Volt Free Contact GEN GEN GEN/BMS

Day Tank Low Level 1 Volt Free Contact GEN GEN GEN/BMS
High Level 1 Volt Free Contact GEN GEN GEN/BMS

Bulk Tank Low Level 1 Volt Free Contact GEN GEN GEN/BMS
High Level 1 Volt Free Contact GEN GEN GEN/BMS

Potable Water Tank 02 1


High Level Alarm 1 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS
Low Level Alarm 1 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS

EAF
(SB-EAF-L1-01 ~ 02 ) 2
Auto/Manual Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 2 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Alarm 2 Volt Free Contact HVAC HVAC HVAC/BMS

FAF
(SB-FAF-L1-01) 1
Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Alarm 1 Volt Free Contact HVAC HVAC HVAC/BMS

DDC-SB-1F-01 19 3 0 0 40

Service Block - 2nd Floor


Elevator 1
Lift status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Lift up 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Lift Down 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Lift Level Indication 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

lift ELV Communication Failure 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Normal Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Fire Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
ATT Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Parking Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Full Load Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Over Load Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Car Door opening Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Car Door closing Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS

Cooling Tower 4
Auto/Manual Status 4 Volt Free Contact HVAC HVAC HVAC/BMS
Start/ Stop Command 4 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 4 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 4
CW Leaving Temperature 4 10K BMS HVAC BMS
CW Entering Temperature 4 10K BMS HVAC BMS
Water Low Level Alarm 4 Volt Free Contact HVAC HVAC HVAC/BMS
Water High Level Alarm 4 Volt Free Contact HVAC HVAC HVAC/BMS

Motorized Butterfly Valves 16


(@ CT) Butterfly Valve On/Off Control 16 Volt Free Contact HVAC HVAC HVAC/BMS
Butterfly Valve Open/Close Status 16 Volt Free Contact HVAC HVAC HVAC/BMS

Makeup Water Tank 4


High Level Alarm 4 Volt Free Contact HVAC HVAC HVAC/BMS
Low Level Alarm 4 Volt Free Contact HVAC HVAC HVAC/BMS

DDC-SB-2F-01 57 20 8 0 0

Hospital Ground floor

AHU G2 1
Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 1 Volt Free Contact BMS BMS BMS
Return Air Temperature 2 10K-RTD BMS BMS BMS
Supply Air Temperature 1 10K-RTD BMS BMS BMS
CO2 Level 1 4-20mA BMS BMS BMS
Valve Control 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Duct Static Pressure 1 4-20mA BMS BMS BMS
VSD Control 1 0-10VDC / 4-20mA BMS HVAC BMS
VSD Feedback 1 0-10VDC / 4-20mA BMS HVAC BMS
Air Flow rate 2 0-10VDC / 4-20mA BMS BMS BMS
Damper Control 2
Damper Feedback 2

Electrical Panels( Zone 1) 2


MDB/G/Z1/A&E&CA Fault Status 2 Volt Free Contact ELEC ELEC ELEC/BMS
EMDB/G/Z1/A&E&CA

FCU 2
POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

FCU-G-1,2 Space Temperature 2 BACnet/MSTP BMS BMS BMS


Start/Stop Command 2 BACnet/MSTP BMS BMS BMS
On/Off Status 2 BACnet/MSTP BMS BMS BMS
Fan Speed 01 2 BACnet/MSTP BMS BMS BMS
Fan Speed 02 2 BACnet/MSTP BMS BMS BMS
Fan Speed 03 2 BACnet/MSTP BMS BMS BMS

DDC-HB-GF-01 & 02 8 9 13 4 0

AHU G5 1
Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 1 Volt Free Contact BMS BMS BMS
Return Air Temperature 1 10K BMS BMS BMS
Supply Air Temperature 1 10K BMS BMS BMS
CO2 Level 1 4-20mA BMS BMS BMS
Valve Control 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

AHU G4 1
Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 1 Volt Free Contact BMS BMS BMS
Return Air Temperature 3 10K BMS BMS BMS
Supply Air Temperature 1 10K BMS BMS BMS
CO2 Level 1 4-20mA BMS BMS BMS
Valve Control 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Duct Static Pressure 1 4-20mA BMS BMS BMS
Air Flow rate 3 0-10VDC / 4-20mA BMS HVAC BMS
VSD Control 1 0-10VDC / 4-20mA BMS HVAC BMS
VSD Feedback 1 0-10VDC / 4-20mA BMS BMS BMS
Damper Control 3 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Damper Feedback 3 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

Electrical Panels( Zone 1) 4


MDB/G/Z1/ADMIN&CARD, MDB/G/Z1/M1 Fault Status 4 Volt Free Contact ELEC ELEC ELEC/BMS
EMDB/G/Z1/ADMIN&CARD, EMDB/G/Z1/M1

Common Area Lighting (Zone 1) 8


DB/G/Z1/A&E/CA-S1, EDB/G/Z1/A&E/CA-S1,
EDB/G/Z1/CA-S1, DB/G/Z1/CA-S1, EDB/G/Z1/ADMIN/CA-
S1, DB/G/Z1/ADMIN/CA-S1, DB/G/Z1/CARD/CA-S1,
EDB/G/Z1/CARD/CA-S1, Start/ Stop Command 8 Volt Free Contact ELEC ELEC ELEC/BMS
UDB/G/Z1/A&E/CA-S1 1

DDC-HB-GF-03 12 11 18 6 0

AHU G3,AHU G6 , AHU G7 3


Auto/Manual Status 3 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 3 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 3 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 3 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 3 Volt Free Contact BMS BMS BMS
Return Air Temperature 3 10K BMS BMS BMS
Supply Air Temperature 3 10K BMS BMS BMS
POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

CO2 Level 3 4-20mA BMS BMS BMS


Valve Control 3 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 3 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

PHEUMATIC TUBE SYSTEM 1


System Healthy Status 1 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS
Common Fault 1 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS

Hot Water Temperature 1 10k Plumbing Con. Plumbing Con. Plumbing/BMS


Hot Water Pressure 1 4-20mA Plumbing Con. Plumbing Con. Plumbing/BMS

Heat Pumps 6
On Off Status 6 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS
Trip Status 6 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS

Common Area Lighting 2


DB/G/SER/CA-S1, EDB/G/SER/CA-S1, Start/ Stop Command 2 Volt Free Contact ELEC ELEC ELEC/BMS

FAF 4
(FAF-GD-01,02, 03& 04) Auto/Manual Status 4 Volt Free Contact HVAC HVAC HVAC/BMS
Start/ Stop Command 4 Volt Free Contact HVAC HVAC HVAC/BMS
On/ Off Status 4 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Alarm 4 Volt Free Contact HVAC HVAC HVAC/BMS

EAF 4
(EAF-GD-01,02,03 & 04) Auto/Manual Status 4 Volt Free Contact HVAC HVAC HVAC/BMS
Start/ Stop Command 4 Volt Free Contact HVAC HVAC HVAC/BMS
On/ Off Status 4 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Alarm 4 Volt Free Contact HVAC HVAC HVAC/BMS

Fire Detection Panel 1


Fire Alarm 1 Modbus Fire Fire Fire/BMS
Panel Alarm 1 Modbus Fire Fire Fire/BMS

FCU 2
FCU-G-3,4 Space Temperature 2 BACnet/MSTP BMS BMS BMS
Start/Stop Command 2 BACnet/MSTP BMS BMS BMS
On/Off Status 2 BACnet/MSTP BMS BMS BMS
Fan Speed 01 2 BACnet/MSTP BMS BMS BMS
Fan Speed 02 2 BACnet/MSTP BMS BMS BMS
Fan Speed 03 2 BACnet/MSTP BMS BMS BMS

MSB -LV switch room 6


On Off Status 6 Volt Free Contact ELEC ELEC ELEC/BMS
Trip Status 6 Volt Free Contact ELEC ELEC ELEC/BMS

Capacitor Bank 1
Common Alarm 1 Volt Free Contact ELEC ELEC ELEC/BMS
Power Factor 1 0-10V or 4-20mA ELEC ELEC ELEC/BMS

Power Supply- Hospital Building Power consumption 1


A 1
KWH 1
V 1
DDC-HB-GF-04 67 21 17 3 3

AHU G-8 1
Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

On/Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS


Trip Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 1 Volt Free Contact BMS BMS BMS
Return Air Temperature 2 10K BMS BMS BMS
Supply Air Temperature 1 10K BMS BMS BMS
CO2 Level 1 4-20mA BMS BMS BMS
Valve Control 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Duct Static Pressure 1 0-10VDC / 4-20mA BMS HVAC BMS
Air Flow rate 2 0-10VDC / 4-20mA BMS HVAC BMS
VSD Control 1 0-10VDC / 4-20mA BMS BMS BMS
VSD Feedback 1 0-10VDC / 4-20mA BMS BMS BMS
Damper Control 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Damper Feedback 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
EMDB/G/Z4/MRI

Electrical Panels( Zone 4) 3


MDB/G/Z4/RAY, Fault Status 1 Volt Free Contact ELEC ELEC ELEC/BMS

EMDB/G/Z4/MRI,MDB/G/Z4/CT SCAN 2

Common Area Lighting (Zone 4) 4


DB/G/Z4/IMAG/CA-S1,EDB/G/Z4/IMAG/CA-S1,
DB/G/Z4/CA-S1, EDB/G/Z4/CA-S1 Start/ Stop Command 4 Volt Free Contact ELEC ELEC ELEC/BMS

Electrical Panels 4
MDB/G/Z4/M1 ,MDB/G/Z4/IMAG&CA Fault Status 4 Volt Free Contact ELEC ELEC ELEC/BMS
EMDB/G/Z4/IMAG&CA, EMDB/G/Z4/M1

AFAF 1
AFAF-GD-01 Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/ Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
On/ Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Alarm 1 Volt Free Contact HVAC HVAC HVAC/BMS

FCU 1
FCU-G-5 Space Temperature 1 BACnet/MSTP BMS BMS BMS
Start/Stop Command 1 BACnet/MSTP BMS BMS BMS
On/Off Status 1 BACnet/MSTP BMS BMS BMS
Fan Speed 01 1 BACnet/MSTP BMS BMS BMS
Fan Speed 02 1 BACnet/MSTP BMS BMS BMS
Fan Speed 03 1 BACnet/MSTP BMS BMS BMS

DDC-HB-GF-05 15 10 12 4 0

AHU G9 1
Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 1
Filter Clog Status 1 Volt Free Contact BMS BMS BMS
Return Air Temperature 3 10K BMS BMS BMS
Supply Air Temperature 1 10K BMS BMS BMS
CO2 Level 1 4-20mA BMS BMS BMS
Valve Control 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Duct Static Pressure 1 0-10VDC / 4-20mA BMS HVAC BMS
Air Flow rate 3 0-10VDC / 4-20mA BMS HVAC BMS
VSD Control 1 0-10VDC / 4-20mA BMS BMS BMS
POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

VSD Feedback 1 0-10VDC / 4-20mA BMS BMS BMS


Damper Control 3 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Damper Feedback 3 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

AHU G 10 1
Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 1 Volt Free Contact BMS BMS BMS
Return Air Temperature 3 10K BMS BMS BMS
Supply Air Temperature 1 10K BMS BMS BMS
CO2 Level 1 4-20mA BMS BMS BMS
Valve Control 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Duct Static Pressure 1 0-10VDC / 4-20mA BMS HVAC BMS
Air Flow rate 3 0-10VDC / 4-20mA BMS BMS BMS
VSD Control 1 0-10VDC / 4-20mA BMS BMS BMS
VSD Feedback 1 0-10VDC / 4-20mA BMS BMS BMS
Damper Control 3 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Damper Feedback 3 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

Common Area Lighting (Zone 2) 6


DB/G/MAMMO/CA-S1, EDB/G/MAMMO/CA-S1,
DB/G/BLOB/CA-S1, EDB/G/BLOB/CA-S1, DB/G/Z2/CA-
S1, EDB/G/Z2/CA-S1 Start/ Stop Command 6 Volt Free Contact ELEC ELEC ELEC/BMS

Electrical Panels( Zone 2) 4


MDB/G/MAMMO&BLOB&CA, MDB/G/Z2/M1 Fault Status 4 Volt Free Contact ELEC ELEC ELEC/BMS
EMDB/G/MAMMO&BLOB&CA, EMDB/G/Z2/M1
DDC-HB-GF-06 12 8 28 10 0

AHU G11 1
Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 1 Volt Free Contact BMS BMS BMS
Return Air Temperature 3 10K BMS BMS BMS
Supply Air Temperature 1 10K BMS BMS BMS
CO2 Level 1 4-20mA BMS BMS BMS
Valve Control 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Duct Static Pressure 1 0-10VDC / 4-20mA BMS HVAC BMS
Air Flow rate 3 0-10VDC / 4-20mA BMS BMS BMS
VSD Control 1 0-10VDC / 4-20mA BMS BMS BMS
VSD Feedback 1 0-10VDC / 4-20mA BMS BMS BMS
Damper Control 3 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Damper Feedback 3 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

FCU 3
FCU-G-06,18,19 Space Temperature 3 BACnet/MSTP BMS BMS BMS
Start/Stop Command 3 BACnet/MSTP BMS BMS BMS
On/Off Status 3 BACnet/MSTP BMS BMS BMS
Fan Speed 01 3 BACnet/MSTP BMS BMS BMS
Fan Speed 02 3 BACnet/MSTP BMS BMS BMS
Fan Speed 03 3 BACnet/MSTP BMS BMS BMS

Common Area Lighting (Zone 5) 6


POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

DB/G/Z5/ENDO/CA-S1, EDB/G/Z5/ENDO/CA-S1,
DB/G/Z5/CA-S1, EDB/G/Z5/CA-S1, DB/G/Z5/EXHEA/CA-
S1, EDB/G/Z5/EXHEA/CA-S1 Start/ Stop Command 6 Volt Free Contact ELEC ELEC ELEC/BMS

Electrical Panels( Zone 5) 4


MDB/G/Z5/M1, MDB/G/Z5/EXHEA&ENDO&CA Fault Status 4 Volt Free Contact ELEC ELEC ELEC/BMS
EMDB/G/Z5/EXHEA&ENDO&CA, EMDB/G/Z5/M1

Electrical Panels 2
MDB/G/Z5/X-RAY, MDB/G/Z5/ERCP Fault Status 2 Volt Free Contact ELEC ELEC ELEC/BMS

DDC-HB-GF-07 13 19 17 5 0

AHU G12 1
Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 1 Volt Free Contact BMS BMS BMS
Return Air Temperature 3 10K BMS BMS BMS
Supply Air Temperature 1 10K BMS BMS BMS
CO2 Level 1 4-20mA BMS BMS BMS
Valve Control 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Duct Static Pressure 1 0-10VDC / 4-20mA BMS HVAC BMS
Flow Rate 3 0-10VDC / 4-20mA BMS BMS BMS
VSD Control 1 0-10VDC / 4-20mA BMS BMS BMS
VSD Feeedback 1 0-10VDC / 4-20mA BMS BMS BMS
Damper Control 3 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Damper Feedback 3 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

AHU G13 1
Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 1 Volt Free Contact BMS BMS BMS
Return Air Temperature 1 10K BMS BMS BMS
Supply Air Temperature 1 10K BMS BMS BMS
CO2 Level 1 4-20mA BMS BMS BMS
Valve Control 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

AHU G14 1
Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 1 Volt Free Contact BMS BMS BMS
Return Air Temperature 3 10K BMS BMS BMS
Supply Air Temperature 1 10K BMS BMS BMS
CO2 Level 1 4-20mA BMS BMS BMS
Valve Control 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Duct Static Pressure 1 0-10VDC / 4-20mA BMS HVAC BMS
Flow Rate 3 0-10VDC / 4-20mA BMS BMS BMS
VSD Control 1 0-10VDC / 4-20mA HVAC HVAC BMS
VSD Feedback 1 0-10VDC / 4-20mA HVAC HVAC BMS
POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

Damper Control 3 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS


Damper Feedback 3 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

Electrical Panels( Zone 6) 4


MDB/G/Z6/NEUGY&CA, MDB/G/Z6/M1 Fault Status 4 Volt Free Contact ELEC ELEC ELEC/BMS
EMDB/G/Z6/NEUGY&CA,E MDB/G/Z6/M1

Common Area Lighting (Zone 6) 4


DB/G/Z6/NEUGY/CA-S1, DB/G/Z6/CA-S1,
EDB/G/Z6/NEUGY/CA-S1, EDB/G/Z6/CA-S1 Start/ Stop Command 4 Volt Free Contact ELEC ELEC ELEC/BMS

DDC-HB-GF-08 16 7 32 11 0

AHU G15, AHU G16 2


Auto/Manual Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 2 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 2 Volt Free Contact BMS BMS BMS
Return Air Temperature 6 10K BMS BMS BMS
Supply Air Temperature 2 10K BMS BMS BMS
CO2 Level 2 4-20mA BMS BMS BMS
Valve Control 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Duct Static Pressure 2 0-10VDC / 4-20mA BMS HVAC BMS
Flow Rate 6 0-10VDC / 4-20mA BMS BMS BMS
VSD Control 2 0-10VDC / 4-20mA BMS BMS BMS
VSD Feedback 2 0-10VDC / 4-20mA BMS BMS BMS
Damper Control 6 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Damper Feedback 6 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

Electrical Panels( Zone 3) 2


MDB/G/Z3/NEUSC&ORTHA&CA, MDB/G/Z3/M1 Fault Status 2 Volt Free Contact ELEC ELEC ELEC/BMS
EMDB/G/Z3/NEUSC&ORTHA&CA, EMDB/G/Z3/M1

Common Area Lighting (Zone 3) 2


DB/G/Z3/CA-S1, EDB/G/Z3/CA-S1, Start/ Stop Command 2 Volt Free Contact ELEC ELEC ELEC/BMS

Common Area Lighting 4


DB/G/NEUSC/CA-S1, EDB/G/NEUSC/CA-S1,
DB/G/ORTHA/CA-S1, EDB/G/ORTHA/CA-S1 Start/ Stop Command 4 Volt Free Contact ELEC ELEC ELEC/BMS

Electrical Panels 3
MDB/G/Z2/MAMMO1, MDB/G/Z2/ULTRAS,
MDB/G/Z2/MAMMO2 Fault Status 3 Volt Free Contact ELEC ELEC ELEC/BMS

FCU 1
FCU-G-07 Space Temperature 1 BACnet/MSTP BMS BMS BMS
Start/Stop Command 1 BACnet/MSTP BMS BMS BMS
On/Off Status 1 BACnet/MSTP BMS BMS BMS
Fan Speed 01 1 BACnet/MSTP BMS BMS BMS
Fan Speed 02 1 BACnet/MSTP BMS BMS BMS
Fan Speed 03 1 BACnet/MSTP BMS BMS BMS

DDC-HB-GF-09 14 12 29 10 0

AHU G17, AHU G18 2


POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

Auto/Manual Status 2 Volt Free Contact HVAC HVAC HVAC/BMS


Start/Stop Command 2 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 2 Volt Free Contact BMS BMS BMS
Return Air Temperature 5 10K BMS BMS BMS
Supply Air Temperature 2 10K BMS BMS BMS
CO2 Level 2 4-20mA BMS BMS BMS
Valve Control 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Duct Static Pressure 2 0-10VDC / 4-20mA BMS HVAC BMS
Flow Rate 5 0-10VDC / 4-20mA BMS BMS BMS
VSD Control 2 0-10VDC / 4-20mA BMS BMS BMS
VSD Feedback 2 0-10VDC / 4-20mA BMS BMS BMS
Damper Control 5 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Damper Feedback 5 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

Electrical Panels( Zone 7) 4


MDB/G/Z7/PSYC&REHA&CA, MDB/G/Z7/M1 Fault Status 4 Volt Free Contact ELEC ELEC ELEC/BMS
EMDB/G/Z7/PSYC&REHA&CA, EMDB/G/Z7/M1

Common Area Lighting (Zone 7) 6


DB/G/Z7/CA-S1, DB/G/Z7/PSYC/CA-S1, EDB/G/Z7/CA-
S1, EDB/G/Z7/PSYC/CA-S1, DB/G/Z7/REHA/CA-S1,
EDB/G/Z7/REHA/CA-S1 Start/ Stop Command 6 Volt Free Contact ELEC ELEC ELEC/BMS

DDC-HB-GF-10 12 8 25 9 0

AHU G19 1
Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 1 Volt Free Contact BMS BMS BMS
Return Air Temperature 2 10K BMS BMS BMS
Supply Air Temperature 1 10K BMS BMS BMS
CO2 Level 1 4-20mA BMS BMS BMS
Valve Control 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Duct Static Pressure 1 0-10VDC / 4-20mA BMS HVAC BMS
Flow Rate 2 0-10VDC / 4-20mA BMS BMS BMS
VSD Cotrol 1 0-10VDC / 4-20mA BMS BMS BMS
VSD Feedback 1 0-10VDC / 4-20mA BMS BMS BMS
Damper Control 2
Damper Feedback 2

Common Area Lighting 2


DB/G/Z8/CA-S1, EDB/G/Z8/CA-S1 Start/ Stop Command 2 Volt Free Contact Elec Elec Elec

DDC-HB-GF-11 4 3 11 4 0

AHU G20 1
Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 1 Volt Free Contact BMS BMS BMS
Return Air Temperature 3 10K BMS BMS BMS
Supply Air Temperature 1 10K BMS BMS BMS
POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

CO2 Level 1 4-20mA BMS BMS BMS


Valve Control 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Duct Static Pressure 1 0-10VDC / 4-20mA BMS HVAC BMS
Flow Rate 3 0-10VDC / 4-20mA BMS BMS BMS
VSD Control 1 0-10VDC / 4-20mA BMS BMS BMS
VSD Feedback 1 0-10VDC / 4-20mA BMS BMS BMS
Damper Control 3 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Damper Feedback 3 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

Electrical Panels( Zone 8) 4


MDB/G/Z8/PHD&CA, MDB/G/Z8/M1 Fault Status 4 Volt Free Contact ELEC ELEC ELEC/BMS
EMDB/G/Z8/PHD&CA , EMDB/G/Z8/M1

Common Area Lighting (Zone 8) 2


EDB/G/Z8/PHD/CA-S1, DB/G/Z8/PHD/CA-S1, Start/ Stop Command 2 Volt Free Contact ELEC ELEC ELEC/BMS

DDC-HB-GF-12 8 3 14 5 0

AHU G21 1
Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 1 Volt Free Contact BMS BMS BMS
Return Air Temperature 1 10K BMS BMS BMS
Supply Air Temperature 1 10K BMS BMS BMS
CO2 Level 1 4-20mA BMS BMS BMS
Valve Control 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

DDC-HB-GF-13 4 1 4 1 0

AHU G22 , AHU G23 2


Auto/Manual Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 2 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 2 Volt Free Contact BMS BMS BMS
Return Air Temperature 2 10K BMS BMS BMS
Supply Air Temperature 2 10K BMS BMS BMS
CO2 Level 2 4-20mA BMS BMS BMS
Valve Control 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

FCU 2
FCU-G-10, 8 Space Temperature 2 BACnet/MSTP BMS BMS BMS
Start/Stop Command 2 BACnet/MSTP BMS BMS BMS
On/Off Status 2 BACnet/MSTP BMS BMS BMS
Fan Speed 01 2 BACnet/MSTP BMS BMS BMS
Fan Speed 02 2 BACnet/MSTP BMS BMS BMS
Fan Speed 03 2 BACnet/MSTP BMS BMS BMS

DDC-HB-GF-14 10 10 10 2 0
Ground Floor 462 199 277 83 135

First Floor
AHU L1-1 1
Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

On/Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS


Trip Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 1 Volt Free Contact BMS BMS BMS
Return Air Temperature 1 10K BMS BMS BMS
Supply Air Temperature 1 10K BMS BMS BMS
CO2 Level 1 4-20mA BMS BMS BMS
Valve Control 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

Electrical Panels( Zone1) 4


MDB/L1/Z1/M1, MDB/L1/Z1/WARD&LABO&CA, Fault Status 4 Volt Free Contact ELEC ELEC ELEC/BMS
EMDB/L1/Z1/M1, EMDB/L1/Z1/WARD&LABO&CA

Common Area Lighting (Zone 1) 6


DB/L1/Z1/WARD/CA-S1, EDB/L1/Z1/WARD/CA-S1,
EDB/L1/Z1/LABO/CA-S1, DB/L1/Z1/LABO/CA-S1,
DB/L1/Z1/CA-S1, EDB/L1/Z1/CA-S1 Start/ Stop Command 6 Volt Free Contact ELEC ELEC ELEC/BMS

FCU 4
FCU-L1-1/2/3/5 Space Temperature 4 BACnet/MSTP BMS BMS BMS
Start/Stop Command 4 BACnet/MSTP BMS BMS BMS
On/Off Status 4 BACnet/MSTP BMS BMS BMS
Fan Speed 01 4 BACnet/MSTP BMS BMS BMS
Fan Speed 02 4 BACnet/MSTP BMS BMS BMS
Fan Speed 03 4 BACnet/MSTP BMS BMS BMS

DDC-HB-1F-01 12 23 8 1 0

AHU L1-7 ,2, 3,4 4


Auto/Manual Status 4 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 4 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 4 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 4 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 4 Volt Free Contact BMS BMS BMS
Return Air Temperature 4 10K BMS BMS BMS
Supply Air Temperature 4 10K BMS BMS BMS
CO2 Level 4 4-20mA BMS BMS BMS
Valve Control 4 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 4 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

AHU L1-8 1
Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 1 Volt Free Contact BMS BMS BMS
Return Air Temperature 1 10K BMS BMS BMS
Supply Air Temperature 1 10K BMS BMS BMS
CO2 Level 1 4-20mA BMS BMS BMS
Valve Control 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Duct Static Pressure 1 0-10VDC / 4-20mA BMS HVAC BMS
Flow rate 1 0-10VDC / 4-20mA BMS BMS BMS
VSD Control 1 0-10VDC / 4-20mA BMS BMS BMS
VSD Feedback 1 0-10VDC / 4-20mA BMS BMS BMS
Damper Control 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Damper Feedback 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

Electrical Panels( Zone 2) 6


MDB/L1/Z2/OBG&CA, MDB/L1/Z2/M1, Fault Status 4 Volt Free Contact ELEC ELEC ELEC/BMS
EMDB/L1/Z2/OBG&CA, EMDB/L1/Z2/M1,
POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

MDB/L1/Z2/IVF,EMDB/L1/Z2/IVF 2

Common Area Lighting (Zone 2) 4


DB/L1/Z2/CA-S1, EDB/L1/Z2/CA-S1, DB/L1/Z2/OBG/CA-
S1, EDB/L1/Z2/OBG/CA-S1, 4 Volt Free Contact ELEC ELEC ELEC/BMS

Common Area Lighting 2


DB/L1/Z2/IVF/CA-S1, EDB/L1/Z2/IVF/CA-S1 Start/ Stop Command 2 Volt Free Contact ELEC ELEC ELEC/BMS

DDC-HB-1F-02 26 11 24 7 0

AHU L1-5, 1
Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 1 Volt Free Contact BMS BMS BMS
Return Air Temperature 1 10K BMS BMS BMS
Supply Air Temperature 1 10K BMS BMS BMS
CO2 Level 1 4-20mA BMS BMS BMS
Valve Control 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

Common Area Lighting 2


DB/L1/Z4/PHAR/CA-S1, EDB/L1/Z4/PHAR/CA-S1, Start/ Stop Command 2 Volt Free Contact ELEC ELEC ELEC/BMS

FCU 1
FCU-L1-8 Space Temperature 1 BACnet/MSTP BMS BMS BMS
Start/Stop Command 1 BACnet/MSTP BMS BMS BMS
On/Off Status 1 BACnet/MSTP BMS BMS BMS
Fan Speed 01 1 BACnet/MSTP BMS BMS BMS
Fan Speed 02 1 BACnet/MSTP BMS BMS BMS
Fan Speed 03 1 BACnet/MSTP BMS BMS BMS

DDC-HB-1F-03 5 7 5 1 0

AHU L1-6 1
Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 1 Volt Free Contact BMS BMS BMS
Return Air Temperature 1 10K BMS BMS BMS
Supply Air Temperature 1 10K BMS BMS BMS
CO2 Level 1 4-20mA BMS BMS BMS
Valve Control 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

AFAF 1
AFAF-L1-01 Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/ Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
On/ Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Alarm 1 Volt Free Contact HVAC HVAC HVAC/BMS

Electrical Panels( Zone4) 6


MDB/L1/Z4/LAB&CA, MDB/L1/Z4/M1 Fault Status 4 Volt Free Contact ELEC ELEC ELEC/BMS
EMDB/L1/Z4/M1,EMDB/L1/Z4/LAB&CA,
MDB/L1/Z4/CSSD, EMDB/L1/Z4/CSSD, 2

Common Area Lighting (Zone 4) 4


POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

DB/L1/Z4/CA-S1, EDB/L1/Z4/CA-S1 Start/ Stop Command 2 Volt Free Contact ELEC ELEC ELEC/BMS
DB/L1/Z4/CSSD/CA-S1, EDB/L1/Z4/CSSD/CA-S1, 2

DDC-HB-1F-04 13 4 4 1 0

AHU L1-9, 10A,22,23 4


Auto/Manual Status 4 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 4 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 4 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 4 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 4 Volt Free Contact BMS BMS BMS
Return Air Temperature 4 10K BMS BMS BMS
Supply Air Temperature 4 10K BMS BMS BMS
CO2 Level 4 4-20mA BMS BMS BMS
Valve Control 4 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 4 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

FCU 1
FCU-L1-10 Space Temperature 1 BACnet/MSTP BMS BMS BMS
Start/Stop Command 1 BACnet/MSTP BMS BMS BMS
On/Off Status 1 BACnet/MSTP BMS BMS BMS
Fan Speed 01 1 BACnet/MSTP BMS BMS BMS
Fan Speed 02 1 BACnet/MSTP BMS BMS BMS
Fan Speed 03 1 BACnet/MSTP BMS BMS BMS

Electrical Panels( Zone5) 6

MDB/L1/Z5/M1, MDB/L1/Z5/MMD&CA,
MDB/L1/Z5/KITC, Fault Status 6 Volt Free Contact ELEC ELEC ELEC/BMS
EMDB/L1/Z5/M1, EMDB/L1/Z5/MMD&CA,
EMDB/L1/Z5/KITC

Common Area Lighting (Zone 5) 6


EDB/L1/Z5/CA-S1, DB/L1/Z5/CA-S1 Start/ Stop Command 2 Volt Free Contact ELEC ELEC ELEC/BMS
DB/L1/Z5/MMD/CA-S1, EDB/L1/Z5/MMD/CA-S1,
DB/L1/Z5/KITC/CA-S1, EDB/L1/Z5/KITC/CA-S1 4

DDC-HB-1F-05 23 14 17 4 0

AHU L1-11 ,24 2


Auto/Manual Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 2 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 2 Volt Free Contact BMS BMS BMS
Return Air Temperature 2 10K BMS BMS BMS
Supply Air Temperature 2 10K BMS BMS BMS
CO2 Level 2 4-20mA BMS BMS BMS
Valve Control 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

Electrical Panels( Zone6) 4


MDB/L1/Z6/M1, MDB/L1/Z6/STFC Fault Status 4 Volt Free Contact ELEC ELEC ELEC/BMS
EMDB/L1/Z6/M1, EMDB/L1/Z6/STFC

Common Area Lighting (Zone 6) 2


DB/L1/Z6/STFC/CA-S1, EDB/L1/Z6/STFC/CA-S1 Start/ Stop Command 2 Volt Free Contact ELEC ELEC ELEC/BMS

DDC-HB-1F-06 12 4 8 2 0

AHU L1-12, 13 2
POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

Auto/Manual Status 2 Volt Free Contact HVAC HVAC HVAC/BMS


Start/Stop Command 2 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 2 Volt Free Contact BMS BMS BMS
Return Air Temperature 4 10K BMS BMS BMS
Supply Air Temperature 2 10K BMS BMS BMS
CO2 Level 2 4-20mA BMS BMS BMS
Valve Control 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Duct Static Pressure 2 0-10VDC / 4-20mA BMS HVAC BMS
Flow rate 4 0-10VDC / 4-20mA BMS BMS BMS
VSD Control 2 0-10VDC / 4-20mA BMS BMS BMS
VSD Feedback 2 0-10VDC / 4-20mA BMS BMS BMS
Damper Control 4 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Damper Feedback 4 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

AHU L1-25 1
Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 1 Volt Free Contact BMS BMS BMS
Return Air Temperature 1 10K BMS BMS BMS
Supply Air Temperature 1 10K BMS BMS BMS
CO2 Level 1 4-20mA BMS BMS BMS
Valve Control 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

Electrical Panels( Zone3) 4


MDB/L1/Z3/PAED&ENT&CA, MDB/L1/Z3/M1, Fault Status 4 Volt Free Contact ELEC ELEC ELEC/BMS
EMDB/L1/Z3/PAED&ENT&CA, EMDB/L1/Z3/M1

Common Area Lighting (Zone 3) 4


DB/L1/Z3/ENT/CA-S1, EDB/L1/Z3/ENT/CA-S1,
DB/L1/Z3/CA-S1, EDB/L1/Z3/CA-S1 Start/ Stop Command 4 Volt Free Contact ELEC ELEC ELEC/BMS

Common Area Lighting 2


DB/L1/Z3/PAED/CA-S1, EDB/L1/Z3/PAED/CA-S1 Start/ Stop Command 2 Volt Free Contact ELEC ELEC ELEC/BMS

Common Area Lighting 2


DB/L1/Z4/LAB/CA-S1, EDB/L1/Z4/LAB/CA-S1 Start/ Stop Command 2 Volt Free Contact ELEC ELEC ELEC/BMS

DDC-HB-1F-07 16 11 26 9 0

AHU L1-14, AHU L1-16 2


Auto/Manual Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 2 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 2 Volt Free Contact BMS BMS BMS
Return Air Temperature 2 10K BMS BMS BMS
Supply Air Temperature 2 10K BMS BMS BMS
CO2 Level 2 4-20mA BMS BMS BMS
Valve Control 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

AHU L1-15, 1
Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

Trip Status 1 Volt Free Contact HVAC HVAC HVAC/BMS


Filter Clog Status 1 Volt Free Contact BMS BMS BMS
Return Air Temperature 2 10K BMS BMS BMS
Supply Air Temperature 1 10K BMS BMS BMS
CO2 Level 1 4-20mA BMS BMS BMS
Valve Control 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Duct Static Pressure 1 0-10VDC / 4-20mA BMS HVAC BMS
Flow Rate 2 0-10VDC / 4-20mA BMS BMS BMS
VSD Control 1 0-10VDC / 4-20mA BMS BMS BMS
VSD Feedback 1 0-10VDC / 4-20mA BMS BMS BMS
Damper Control 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Damper Feedback 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

Electrical Panels( Zone7) 4


MDB/L1/Z7/M1, MDB/L1/ONCO&CA, Fault Status 4 Volt Free Contact ELEC ELEC ELEC/BMS
EMDB/L1/Z7/M1, EMDB/L1/ONCO&CA

Common Area Lighting (Zone 7) 2


DB/L1/Z7/CA-S1, EDB/L1/Z7/CA-S1 Start/ Stop Command 2 Volt Free Contact ELEC ELEC ELEC/BMS

Common Area Lighting 2


DB/L1/Z7/ONCO/CA-S1, EDB/L1/Z7/ONCO/CA-S1 Start/ Stop Command 2 Volt Free Contact ELEC ELEC ELEC/BMS

AFAF-02 1
Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/ Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
On/ Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Alarm 1 Volt Free Contact HVAC HVAC HVAC/BMS

DDC-HB-1F-08 19 8 19 6 0

AHU L1-17 1
Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 1 Volt Free Contact BMS BMS BMS
Return Air Temperature 1 10K BMS BMS BMS
Supply Air Temperature 1 10K BMS BMS BMS
CO2 Level 1 4-20mA BMS BMS BMS
Valve Control 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

AHU L1-18 1
Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 1 Volt Free Contact BMS BMS BMS
Return Air Temperature 1 10K BMS BMS BMS
Supply Air Temperature 1 10K BMS BMS BMS
CO2 Level 1 4-20mA BMS BMS BMS
Valve Control 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Duct Satic Pressure 1 0-10VDC / 4-20mA BMS HVAC BMS
Flow rate 2 0-10VDC / 4-20mA BMS BMS BMS
VSD Control 1 0-10VDC / 4-20mA BMS BMS BMS
VSD Feedback 1 0-10VDC / 4-20mA BMS BMS BMS
Damper Control 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

Damper Feedback 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

Electrical Panels( Zone8) 4


MDB/L1/Z8/ADMIN&DENT, MDB/L1/Z8/M1 Fault Status 4 Volt Free Contact ELEC ELEC ELEC/BMS
EMDB/L1/Z8/ADMIN&DENT, EMDB/L1/Z8/M1

Common Area Lighting (Zone 8) 4

DB/L1/Z8/DENT/CA-S1, EDB/L1/Z8/DENT/CA-
S1,DB/L1/Z8/ADMIN/CA-S1, EDB/L1/Z8/ADMIN/CA-S1 Start/ Stop Command 4 Volt Free Contact ELEC ELEC ELEC/BMS

Elevator 1
(Lift Motor Room) Lift Level Indication 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
lift ELV Communication Failure 1
Normal Status 1
Fire Status 1
ATT Status 1
Parking Status 1
Full Load Status 1
Over Load Status 1
Car Door opening Status 1
Car Door closing Status 1
Lift Up Status 1
Lfit down status 1
Lift Alarm 1

DDC-HB-1F-09 25 6 14 5 0

AHU L1-19,20,21, 3
Auto/Manual Status 3 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 3 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 3 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 3 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 3 Volt Free Contact BMS BMS BMS
Return Air Temperature 3 10K BMS BMS BMS
Supply Air Temperature 3 10K BMS BMS BMS
CO2 Level 3 4-20mA BMS BMS BMS
Valve Control 3 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 3 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

FCU 2
FCU-l1-11/13 Space Temperature 2 BACnet/MSTP BMS BMS BMS
Start/Stop Command 2 BACnet/MSTP BMS BMS BMS
On/Off Status 2 BACnet/MSTP BMS BMS BMS
Fan Speed 01 2 BACnet/MSTP BMS BMS BMS
Fan Speed 02 2 BACnet/MSTP BMS BMS BMS
Fan Speed 03 2 BACnet/MSTP BMS BMS BMS

Common Area Lighting 2


DB/L1/Z8/CA-S1, EDB/L1/Z8/CA-S1, Start/ Stop Command 2 Volt Free Contact ELEC ELEC ELEC/BMS

DDC-HB-1F-10 14 13 14 3 0
165 101 139 39 0

Second Floor

AHU L2-2 1
Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

Start/Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS


On/Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 1 Volt Free Contact BMS BMS BMS
Return Air Temperature 1 10K BMS BMS BMS
Supply Air Temperature 1 10K BMS BMS BMS
CO2 Level 1 4-20mA BMS BMS BMS
Valve Control 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

Electrical Panels( Zone1) 6

MDB/L2/Z1/WARD, MDB/L2/Z1/M1, MDB/L2/Z1/ICU-1 Fault Status 6 Volt Free Contact ELEC ELEC ELEC/BMS
EMDB/L2/Z1/WARD, EMDB/L2/Z1/M1,
EMDB/L2/Z1/ICU-1

Common Area Lighting (Zone 1) 4


DB/L2/WARD/CA-S1, EDB/L2/WARD/CA-S1, DB/L2/ICU-
1/CA-S1, EDB/L2/ICU-1/CA-S1 Start/ Stop Command 4 Volt Free Contact ELEC ELEC ELEC/BMS

FCU 19
FCU/L2-1,2,4,6, 7, 8,9,10,11,12,13,14, 15, 19, 20, 21,
19
24,25,26 Space Temperature BACnet/MSTP BMS BMS BMS
Start/Stop Command 19 BACnet/MSTP BMS BMS BMS
On/Off Status 19 BACnet/MSTP BMS BMS BMS
Fan Speed 01 19 BACnet/MSTP BMS BMS BMS
Fan Speed 02 19 BACnet/MSTP BMS BMS BMS
Fan Speed 03 19 BACnet/MSTP BMS BMS BMS

UPS-Main 1
General Failure 1 BACnet MSTP/Modbus RTU Elec Elec Elec/BMS
Power Supply Failure 1 BACnet MSTP/Modbus RTU Elec Elec Elec/BMS
Inverter Status 1 BACnet MSTP/Modbus RTU Elec Elec Elec/BMS
Converter Status 1 BACnet MSTP/Modbus RTU Elec Elec Elec/BMS
Status of the battery Charger 1 BACnet MSTP/Modbus RTU Elec Elec Elec/BMS
Load 1 BACnet MSTP/Modbus RTU Elec Elec Elec/BMS
Voltage 1 BACnet MSTP/Modbus RTU Elec Elec Elec/BMS
Frequency 1 BACnet MSTP/Modbus RTU Elec Elec Elec/BMS

UPS Mode 1 BACnet MSTP/Modbus RTU Elec Elec Elec/BMS


Battery Changing status 1 BACnet MSTP/Modbus RTU Elec Elec Elec/BMS
UPS Load On 1 BACnet MSTP/Modbus RTU Elec Elec Elec/BMS
UPS remaining time 1 BACnet MSTP/Modbus RTU Elec Elec Elec/BMS
UPS Output Voltage U12 1 BACnet MSTP/Modbus RTU Elec Elec Elec/BMS
UPS Output Voltage U23 1 BACnet MSTP/Modbus RTU Elec Elec Elec/BMS
UPS Output Voltage U31 1 BACnet MSTP/Modbus RTU Elec Elec Elec/BMS
UPS Output CUrrunt L1 1 BACnet MSTP/Modbus RTU Elec Elec Elec/BMS
UPS Output CUrrunt L2 1 BACnet MSTP/Modbus RTU Elec Elec Elec/BMS
UPS Output CUrrunt L3 1 BACnet MSTP/Modbus RTU Elec Elec Elec/BMS
UPS Active Power L1 1 BACnet MSTP/Modbus RTU Elec Elec Elec/BMS
UPS Active Power L2 1 BACnet MSTP/Modbus RTU Elec Elec Elec/BMS
UPS Active Power L3 1 BACnet MSTP/Modbus RTU Elec Elec Elec/BMS
UPS Apparent Power L1 1 BACnet MSTP/Modbus RTU Elec Elec Elec/BMS
UPS Apparent Power L2 1 BACnet MSTP/Modbus RTU Elec Elec Elec/BMS
UPS Apparent Power L3 1 BACnet MSTP/Modbus RTU Elec Elec Elec/BMS
UPS output Frequency 1 BACnet MSTP/Modbus RTU Elec Elec Elec/BMS
UPS Ambient Temperature 1 BACnet MSTP/Modbus RTU Elec Elec Elec/BMS
UPS Battery Capacity 1 BACnet MSTP/Modbus RTU Elec Elec Elec/BMS

Opearation Theatres 20
POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

Theatre Temperature 20
Theatre Humidity 20
System status 20
Temperature Set point 20
Humidity setpoint 20
Eletric heaters status 20
Pre Heaters Temperature 20
MODbus RTU OT OT OT
compressor status 20
Reheating fan status 20
Hepa filters status 20
Bag filters status 20
Supply fan status 20
Supply fan fault status 20
Fire alarm status 20

DDC-HB-2F-01 318 81 41 1 0

AHU L2-3, AHU L2-4 2


Auto/Manual Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 2 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 2 Volt Free Contact BMS BMS BMS
Return Air Temperature 2 10K BMS BMS BMS
Supply Air Temperature 2 10K BMS BMS BMS
CO2 Level 2 4-20mA BMS BMS BMS
Valve Control 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

Electrical Panels( Zone4) 4


MDB/L2/Z4/M1, MDB/L2/Z4/CA Fault Status 4 Volt Free Contact ELEC ELEC ELEC/BMS
EMDB/L2/Z4/M1, EMDB/L2/Z4/CA

Common Area Lighting (Zone 4) 3

DB/L2/Z4/CA-S2, EDB/L2/Z4/CA-S2, DB/L2/Z4/CA-S1, Start/ Stop Command 3 Volt Free Contact ELEC ELEC ELEC/BMS
EDB/L2/Z4/CA-S1 1

Electrical Panels( Zone2) 4


MDB/L2/Z2/M1, MDB/L2/Z2/REC&CA, Fault Status 4 Volt Free Contact ELEC ELEC ELEC/BMS
EMDB/L2/Z2/M1, EMDB/L2/Z2/REC&CA

Common Area Lighting (Zone2) 2


DB/L2/Z3/CA-S1, EDB/L2/Z3/CA-S1, Start/ Stop Command 2 Volt Free Contact ELEC ELEC ELEC/BMS

Electrical Panels 2
MDB/L2/Z4/OT Fault Status 1 Volt Free Contact ELEC ELEC ELEC/BMS
EMDB/L2/Z4/OT 1

Common Area Lighting (Roof) 1


MDB/Z2/R1/CA-S1 Start/ Stop Command 1 Volt Free Contact ELEC ELEC ELEC/BMS

FCU 1
FCU/L2-31 Space Temperature 1 BACnet/MSTP BMS BMS BMS
Start/Stop Command 1 BACnet/MSTP BMS BMS BMS
On/Off Status 1 BACnet/MSTP BMS BMS BMS
Fan Speed 01 1 BACnet/MSTP BMS BMS BMS
Fan Speed 02 1 BACnet/MSTP BMS BMS BMS
Fan Speed 03 1 BACnet/MSTP BMS BMS BMS
POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

EAF/R1-2/21/23/22 4
Auto/Manual Status 4 Volt Free Contact HVAC HVAC HVAC/BMS
Start/ Stop Command 4 Volt Free Contact HVAC HVAC HVAC/BMS
On/ Off Status 4 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Alarm 4 Volt Free Contact HVAC HVAC HVAC/BMS
DDC-HB-2F-02 31 17 9 2 0

AHU L2-7, AHU L2-8, AHU L2-9 3


Auto/Manual Status 3 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 3 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 3 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 3 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 3 Volt Free Contact BMS BMS BMS
Return Air Temperature 3 10K BMS BMS BMS
Supply Air Temperature 3 10K BMS BMS BMS
CO2 Level 3 4-20mA BMS BMS BMS
Valve Control 3 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 3 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

Electrical Panels( Zone5) 6


MDB/L2/Z5/CA&DSUR, Fault Status 6 Volt Free Contact ELEC ELEC ELEC/BMS
EMDB/L2/Z5/M1,
EMDB/L2/Z5/CA&DSUR,MDB/L2/Z5/M1
MDB/L2/Z5/LAU,EMDB/L2/Z5/LAU

Common Area Lighting (Zone 5) 2


DB/L2/Z5/CA-S1, EDB/L2/Z5/CA-S1, Start/ Stop Command 2 Volt Free Contact ELEC ELEC ELEC/BMS

Electrical Panels( Zone6) 4


MDB/L2/Z6/CA, MDB/L2/Z6/M1 Fault Status 4 Volt Free Contact ELEC ELEC ELEC/BMS
EMDB/L2/Z6/CA, EMDB/L2/Z6/M1

Common Area Lighting (Zone6) 2


DB/L2/Z6/CA-S1, EDB/L2/Z6/CA-S1, Start/ Stop Command 2 Volt Free Contact ELEC ELEC ELEC/BMS

FCU 3
FCU-L2-34/35/44 Space Temperature 3 BACnet/MSTP BMS BMS BMS
Start/Stop Command 3 BACnet/MSTP BMS BMS BMS
On/Off Status 3 BACnet/MSTP BMS BMS BMS
Fan Speed 01 3 BACnet/MSTP BMS BMS BMS
Fan Speed 02 3 BACnet/MSTP BMS BMS BMS
Fan Speed 03 3 BACnet/MSTP BMS BMS BMS

EAF/R1-11/12/13 3
Auto/Manual Status 3 Volt Free Contact HVAC HVAC HVAC/BMS
Start/ Stop Command 3 Volt Free Contact HVAC HVAC HVAC/BMS
On/ Off Status 3 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Alarm 3 Volt Free Contact HVAC HVAC HVAC/BMS

DDC-HB-2F-03 34 22 15 3 0

AHU L2-05, AHU L2-6 2


Auto/Manual Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 2 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 2 Volt Free Contact BMS BMS BMS
Return Air Temperature 2 10K BMS BMS BMS
Supply Air Temperature 2 10K BMS BMS BMS
POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

CO2 Level 2 4-20mA BMS BMS BMS


Valve Control 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

FCU 1
FCU-L2-33 Space Temperature 1 BACnet/MSTP BMS BMS BMS
Start/Stop Command 1 BACnet/MSTP BMS BMS BMS
On/Off Status 1 BACnet/MSTP BMS BMS BMS
Fan Speed 01 1 BACnet/MSTP BMS BMS BMS
Fan Speed 02 1 BACnet/MSTP BMS BMS BMS
Fan Speed 03 1 BACnet/MSTP BMS BMS BMS

Electrical Panels( Zone3) 4


MDB/L2/Z3/ICU-, MDB/L2/Z3/M1 Fault Status 4 Volt Free Contact ELEC ELEC ELEC/BMS
EMDB/L2/Z3/ICU- EMDB/L2/Z3/M1

Common Area Lighting (Zone3) 2


DB/L2/Z3/CA-S1, EDB/L2/Z3/CA-S1 Start/ Stop Command 2 Volt Free Contact ELEC ELEC ELEC/BMS

EAF R1-4 1
Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/ Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
On/ Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Alarm 1 Volt Free Contact HVAC HVAC HVAC/BMS

DDC-HB-2F-04 16 9 9 2 0

AHU L2-1, AHU L2-10 2


Auto/Manual Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 2 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 2 Volt Free Contact BMS BMS BMS
Return Air Temperature 2 10K BMS BMS BMS
Supply Air Temperature 2 10K BMS BMS BMS
CO2 Level 2 4-20mA BMS BMS BMS
Valve Control 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

FCU 9
FCU-L2-37,51,52,53,54,55,56,57,58 Space Temperature 9 BACnet/MSTP BMS BMS BMS
Start/Stop Command 9 BACnet/MSTP BMS BMS BMS
On/Off Status 9 BACnet/MSTP BMS BMS BMS
Fan Speed 01 9 BACnet/MSTP BMS BMS BMS
Fan Speed 02 9 BACnet/MSTP BMS BMS BMS
Fan Speed 03 9 BACnet/MSTP BMS BMS BMS

EAF/R1-,5,20,14,40 4
Auto/Manual Status 4 Volt Free Contact HVAC HVAC HVAC/BMS
Start/ Stop Command 4 Volt Free Contact HVAC HVAC HVAC/BMS
On/ Off Status 4 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Alarm 4 Volt Free Contact HVAC HVAC HVAC/BMS

FAF/R1-3 1
Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/ Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
On/ Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Alarm 1 Volt Free Contact HVAC HVAC HVAC/BMS

AFAF L2-1 1
Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

Start/ Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS


On/ Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Alarm 1 Volt Free Contact HVAC HVAC HVAC/BMS

Common Area Lighting (roof Level 3)


MDB/Z8/R1/CA-S1 Start/ Stop Command 1 Volt Free Contact ELEC ELEC ELEC/BMS

Electrical Panels(roof-l3) 1
MDB/Z8/R1/CA-S1 Fault Status 1 Volt Free Contact ELEC ELEC ELEC/BMS

DDC-HB-2F-05 36 45 17 2 0

AHU L2-11, AHU L2-12 2


Auto/Manual Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 2 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 2 Volt Free Contact BMS BMS BMS
Return Air Temperature 2 10K BMS BMS BMS
Supply Air Temperature 2 10K BMS BMS BMS
CO2 Level 2 4-20mA BMS BMS BMS
Valve Control 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

FCU 6
FCU-L2-48,49,50,42,41,40 Space Temperature 6 BACnet/MSTP BMS BMS BMS
Start/Stop Command 6 BACnet/MSTP BMS BMS BMS
On/Off Status 6 BACnet/MSTP BMS BMS BMS
Fan Speed 01 6 BACnet/MSTP BMS BMS BMS
Fan Speed 02 6 BACnet/MSTP BMS BMS BMS
Fan Speed 03 6 BACnet/MSTP BMS BMS BMS

Electrical Panels( Zone7) 4


MDB/L2/Z7/M1, MDB/L2/Z7/ICU-5&CA Fault Status 4 Volt Free Contact ELEC ELEC ELEC/BMS
EMDB/L2/Z7/M1, EMDB/L2/Z7/ICU-5&CA

Common Area Lighting (Zone7) 2


DB/L2/Z7/CA-S1, EDB/L2/Z7/CA-S1 Start/ Stop Command 2 Volt Free Contact ELEC ELEC ELEC/BMS

Isolation Room 8
Room differential pressure 8 0-10VDC / 4-20mA BMS BMS BMS

DDC-HB-2F-06 18 28 22 2 0

Elevator 2
(Lift Motor Room) Lift status 2 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Lift up 2 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Lift Down 2 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Lift Level Indication 2 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
lift ELV Communication Failure 2 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Normal Status 2 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Fire Status 2 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
ATT Status 2 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Parking Status 2 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Full Load Status 2 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Over Load Status 2 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Car Door opening Status 2 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Car Door closing Status 2 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

EAF-R1-29,30,31,32,33,34,.35,36 18
24,25,26,3,15,18,19,1,16,17 Auto/Manual Status 18 HVAC HVAC HVAC/BMS
Start/Stop Command 18 HVAC HVAC HVAC/BMS
On/Off Status 18 HVAC HVAC HVAC/BMS
Trip Alarm 18 HVAC HVAC HVAC/BMS

EAF 5
(EAF-R1-,6,7,8,9,10) Auto/Manual Status 5 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 5 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 5 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Alarm 5 Volt Free Contact HVAC HVAC HVAC/BMS

KEAF 4
(KEAF-R1-1,2,3,4) Auto/Manual Status 4 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 4 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 4 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Alarm 4 Volt Free Contact HVAC HVAC HVAC/BMS

DDC-HB-2F-07 107 27 0 0 0

560 229 113 12 0

Third Floor

3rd Floor Public Light 2


DB/L3/CA-S1, EDB/L3/CA-S1 Start/Stop Command 2 Volt Free Contact Electrical Electrical ELECTRICAL/BMS

3rd Floor Breaker 4


MDB/L3/WARD, EMDB/L3/Z1/M1 Breakers On/ Off Status 4 Volt Free Contact Electrical Electrical ELECTRICAL/BMS

FCU 6
LIFT Loby Space Temperature 6 BACnet/MSTP BMS BMS BMS
Start/Stop Command 6 BACnet/MSTP BMS BMS BMS
On/Off Status 6 BACnet/MSTP BMS BMS BMS
Fan Speed 01 6 BACnet/MSTP BMS BMS BMS
Fan Speed 02 6 BACnet/MSTP BMS BMS BMS
Fan Speed 03 6 BACnet/MSTP BMS BMS BMS

DDC-HB-L3_01 10 26 6 0 0

AHU L3-01, AHU L3-02 2


Auto/Manual Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 2 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 2 Volt Free Contact BMS BMS BMS
Return Air Temperature 2 10K BMS BMS BMS
Supply Air Temperature 2 10K BMS BMS BMS
CO2 Level 2 4-20mA BMS BMS BMS
Valve Control 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 2 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

FCU 8
FCU-L3-30,31,32,33,34,35,36,37 Space Temperature 8 BACnet/MSTP BMS BMS BMS
Start/Stop Command 8 BACnet/MSTP BMS BMS BMS
On/Off Status 8 BACnet/MSTP BMS BMS BMS
Fan Speed 01 8 BACnet/MSTP BMS BMS BMS
Fan Speed 02 8 BACnet/MSTP BMS BMS BMS
Fan Speed 03 8 BACnet/MSTP BMS BMS BMS
POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

Electrical Panels 4
MDB/L3/Z9/M1 , MDB/L3/Z9/AUDI

Fault Status 4 Volt Free Contact ELEC ELEC ELEC/BMS


EMDB/L3/Z9/M1 , EMDB/L3/Z9/AUDI

Common Area Lighting 4


DB/L3/AUDI/CA-S1, EDB/L3/AUDI/CA-S1,
DB/L3/AUDI/CA-S2, EDB/L3/AUDI/CA-S2

Start/ Stop Command 4 Volt Free Contact ELEC ELEC ELEC/BMS

EAF-R1-28/27/39/38/37 5
Auto/Manual Status 5 Volt Free Contact HVAC HVAC HVAC/BMS
Start/ Stop Command 5 Volt Free Contact HVAC HVAC HVAC/BMS
On/ Off Status 5 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Alarm 5 Volt Free Contact HVAC HVAC HVAC/BMS

EAF-R1-2a 1
Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/ Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
On/ Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Alarm 1 Volt Free Contact HVAC HVAC HVAC/BMS

Elevator 5
Lift status 5 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Lift up 5 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Lift Down 5 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Lift Level Indication 5 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
lift ELV Communication Failure 5 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Normal Status 5 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Fire Status 5 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
ATT Status 5 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Parking Status 5 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Full Load Status 5 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Over Load Status 5 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Car Door opening Status 5 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Car Door closing Status 5 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS

DDC-HB-L3_02 103 44 16 2 0

Elevator 2
(Lift Motor Room) Lift status 2 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Lift up 2 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Lift Down 2 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Lift Level Indication 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
lift ELV Communication Failure 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Normal Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Fire Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
ATT Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Parking Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Full Load Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Over Load Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Car Door opening Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Car Door closing Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

Electrical Panels 1
MDB/R1/Z5/CA-S1 Fault Status 1 Volt Free Contact ELEC ELEC ELEC/BMS

Common Area Lighting 1


MDB/R1/Z5/CA-S1 Start/ Stop Command 1 Volt Free Contact ELEC ELEC ELEC/BMS

DDC-HB-L3-03 17 1 0 0 0

Electrical Panels 2
Fault Status 2 Volt Free Contact ELEC ELEC ELEC/BMS

Common Area Lighting 2


Start/ Stop Command 2 Volt Free Contact ELEC ELEC ELEC/BMS

Hot Water Recirculating Pumps 6


On Off Status 0 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS
Trip Alarm 0 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS

Air Source Heat Pump


Fans On off status 8

DDC-HB-L3-04 10 2 0 0 0

Fourth Floor

Common Area Lighting 2


DB/L4/CA-S1, EDB/L4/CA-S1 Start/Stop Command 2 Volt Free Contact Electrical Electrical ELECTRICAL/BMS

Electrical Panels 4
MDB/L4/WARD, EMDB/L4/Z1/M1 Breakers On/ Off Status 4 Volt Free Contact Electrical Electrical ELECTRICAL/BMS

FCU 4
Lift Lobby Space Temperature 4 BACnet/MSTP BMS BMS BMS
Start/Stop Command 4 BACnet/MSTP BMS BMS BMS
On/Off Status 4 BACnet/MSTP BMS BMS BMS
Fan Speed 01 4 BACnet/MSTP BMS BMS BMS
Fan Speed 02 4 BACnet/MSTP BMS BMS BMS
Fan Speed 03 4 BACnet/MSTP BMS BMS BMS

DDC-HB-4F-01 8 18 4 0 0

Fifth Floor
Common Area Lighting 2
DB/L5/CA-S1, EDB/L5/CA-S1 Start/Stop Command 2 Volt Free Contact Electrical Electrical ELECTRICAL/BMS

Electrical Panels 2
MDB/L5/WARD, EMDB/L5/Z1/M1 Breakers Fault Status 2 Volt Free Contact Electrical Electrical ELECTRICAL/BMS

FCU 4
Lift Lobby Space Temperature 4 BACnet/MSTP BMS BMS BMS
Start/Stop Command 4 BACnet/MSTP BMS BMS BMS
On/Off Status 4 BACnet/MSTP BMS BMS BMS
Fan Speed 01 4 BACnet/MSTP BMS BMS BMS
Fan Speed 02 4 BACnet/MSTP BMS BMS BMS
Fan Speed 03 4 BACnet/MSTP BMS BMS BMS

DDC-HB-5F-01 6 18 4 0 0
POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

Sixth Floor

Common Area Lighting 2


DB/L6/CA-S1, EDB/L6/CA-S1 Start/Stop Command 2 Volt Free Contact Electrical Electrical ELECTRICAL/BMS

Electrical Panels 2
MDB/L6/WARD, MDB/L6/Z1/M1 Breakers Fault Status 2 Volt Free Contact Electrical Electrical ELECTRICAL/BMS

FCU 4
Lift Lobby Space Temperature 4 BACnet/MSTP BMS BMS BMS
Start/Stop Command 4 BACnet/MSTP BMS BMS BMS
On/Off Status 4 BACnet/MSTP BMS BMS BMS
Fan Speed 01 4 BACnet/MSTP BMS BMS BMS
Fan Speed 02 4 BACnet/MSTP BMS BMS BMS
Fan Speed 03 4 BACnet/MSTP BMS BMS BMS

DDC-HB-6F-01 6 18 4 0 0

Seventh Floor

Common Area Lighting 2


DB/L7/CA-S1, EDB/L7/CA-S1 Start/Stop Command 2 Volt Free Contact Electrical Electrical ELECTRICAL/BMS

Electrical Panels 2
MDB/L7/WARD, EMDB/L7/Z1/M1 Breakers Fault Status 2 Volt Free Contact Electrical Electrical ELECTRICAL/BMS

FCU 4
Lift Lobby Space Temperature 4 BACnet/MSTP BMS BMS BMS
Start/Stop Command 4 BACnet/MSTP BMS BMS BMS
On/Off Status 4 BACnet/MSTP BMS BMS BMS
Fan Speed 01 4 BACnet/MSTP BMS BMS BMS
Fan Speed 02 4 BACnet/MSTP BMS BMS BMS
Fan Speed 03 4 BACnet/MSTP BMS BMS BMS

DDC-HB-7F-01 6 18 4 0 0

Eighth Floor

Common Area Lighting 2


DB/L8/CA-S1, EDB/L8/CA-S1 Start/Stop Command 2 Volt Free Contact Electrical Electrical ELECTRICAL/BMS

Electrical Panels 2
MDB/L8/WARD, MDB/L8/Z1/M1 Breakers Fault Status 2 Volt Free Contact Electrical Electrical ELECTRICAL/BMS

FCU 4
Lift Lobby Space Temperature 4 BACnet/MSTP BMS BMS BMS
Start/Stop Command 4 BACnet/MSTP BMS BMS BMS
On/Off Status 4 BACnet/MSTP BMS BMS BMS
Fan Speed 01 4 BACnet/MSTP BMS BMS BMS
Fan Speed 02 4 BACnet/MSTP BMS BMS BMS
Fan Speed 03 4 BACnet/MSTP BMS BMS BMS

DDC-HB-8F-01 6 18 4 0 0

Nineth Floor
POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

Common Area Lighting 2


DB/L9/CA-S1, EDB/L9/CA-S1 Start/Stop Command 2 Volt Free Contact Electrical Electrical ELECTRICAL/BMS

Electrical Panels 2
MDB/L9/WARD, EMDB/L9/Z1/M1 Breakers Fault Status 2 Volt Free Contact Electrical Electrical ELECTRICAL/BMS

FCU 36
Space Temperature 36 BACnet/MSTP BMS BMS BMS
Start/Stop Command 36 BACnet/MSTP BMS BMS BMS
On/Off Status 36 BACnet/MSTP BMS BMS BMS
Fan Speed 01 36 BACnet/MSTP BMS BMS BMS
Fan Speed 02 36 BACnet/MSTP BMS BMS BMS
Fan Speed 03 36 BACnet/MSTP BMS BMS BMS

DDC-HB-9F-01 38 146 36 0 0

ROOF
PAHU (Out Door Type) 1
PAHU-RF-1 Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Status 1
Filter Clog Status 1 Volt Free Contact BMS BMS BMS
Supply Air Temperature 1 10K BMS BMS BMS
Valve Control 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS

Out Door Condition


Outdoor Temperature 1 10K BMS BMS BMS
Outdoor RH 1 10K BMS BMS BMS

Elevator 1
(Lift Motor Room) Lift status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Lift up 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Lift Down 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Lift Level Indication 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
lift ELV Communication Failure 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Normal Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Fire Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
ATT Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Parking Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Full Load Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Over Load Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Car Door opening Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Car Door closing Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS

Common Area Lighting 2


DB/RF/CA-S3, DB/RF/CA-S2 Start/ Stop Command
2 Volt Free Contact ELEC ELEC ELEC/BMS
FAF/RF2 1A,1B 2
Auto/Manual Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 2 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Alarm 2 Volt Free Contact HVAC HVAC HVAC/BMS

EAF/RF2-1A,B,C,D 4
Auto/Manual Status 4 Volt Free Contact HVAC HVAC HVAC/BMS
POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

Start/Stop Command 4 Volt Free Contact HVAC HVAC HVAC/BMS


On/Off Status 4 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Alarm 4 Volt Free Contact HVAC HVAC HVAC/BMS

TEAF/RF2-1A,B 2
Auto/Manual Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 2 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Alarm 2 Volt Free Contact HVAC HVAC HVAC/BMS

Hot Water Recirculating Pumps A (High Zone) 4


On Off Status 4 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS
Trip Status 4 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS

Potable Water tank


High Level Alarm 2 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS
Low Level Alarm 2 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS

Heat Pump 2
On Off Status 2 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS
Trip Status 2 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS

Air Source Heat Pump


Fans On off status 6 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS

Elevator 1
(Lift Motor Room) Lift status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Lift up 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Lift Down 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Lift Level Indication 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
lift ELV Communication Failure 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Normal Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Fire Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
ATT Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Parking Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Full Load Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Over Load Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Car Door opening Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Car Door closing Status 1 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS

Potable Water Booster Pumps 3


( Duty -2, Stand by – 1) On Off Status 3 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS
Trip Status 3 Volt Free Contact Plumbing Con. Plumbing Con. Plumbing/BMS

Electrical Panels 4
MDB/RF/Z1/M1, MDB/RF/Z1/ROOF Breakers Fault Status 4 Volt Free Contact Electrical Electrical ELECTRICAL/BMS
EMDB/RF/Z1/M1, EMDB/RF/Z1/M2

DDC-HB-RT-01 86 11 4 1 0

PAHU (Out Door Type) 1


PAHU-RF-2 Auto/Manual Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 1 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 1 Volt Free Contact HVAC HVAC HVAC/BMS
Filter Clog Status 1 Volt Free Contact BMS BMS BMS
Supply Air Temperature 1 10K BMS BMS BMS
Valve Control 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
Valve Position 1 0-10VDC / 4-20mA HVAC HVAC HVAC/BMS
POINT TYPE

NO OF SUPPLY OF TESTING &


SYSTEM DETAILS OF THE POINT TYPE OF INTERFACE INSTALLATION
ITEMS DI DO AI AO SW EQUIPMENT COMMISSIONING

Elevator 13
(Lift Motor Room 03) Lift status 13 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Lift up 13 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Lift Down 13 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Lift Level Indication 13 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
lift ELV Communication Failure 13 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Normal Status 13 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Fire Status 13 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
ATT Status 13 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Parking Status 13 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Full Load Status 13 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Over Load Status 13 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Car Door opening Status 13 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS
Car Door closing Status 13 BACnet / MSTP / MODbus Lift Con. Lift Con. Lift Con./BMS

Common Area Lighting


DB/RF/CA-S1 Start/ Stop Command 1 Volt Free Contact ELEC ELEC ELEC/BMS

TEAF/RF3-A,B 2
Auto/Manual Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Start/Stop Command 2 Volt Free Contact HVAC HVAC HVAC/BMS
On/Off Status 2 Volt Free Contact HVAC HVAC HVAC/BMS
Trip Alarm 2 Volt Free Contact HVAC HVAC HVAC/BMS

178 4 2 1 0