Академический Документы
Профессиональный Документы
Культура Документы
Drive:
Electric drive:
The aggregate of the electric motor, the energy transmitting shaft and the control equipment
by which the motor characteristics are adjusted and their operating conditions with respect to
mechanical load varied to suit practical requirements is called as electric drive.
Power modulators regulate the power flow from source to the motor to enable the motor to
develop the torque speed characteristics required by the load.
They contain and control the source and motor currents with in permissible limits during
the transient operations such as starting, braking, speed reversal etc.
They convert the input electrical energy into the form as required by the motors.
Adjusts the mode of operation of the motor that is motoring, braking are regenerative.
Variable impedance
Converters
AC to DC rectifiers
DC to DC choppers
AC to AC choppers
AC to AC –AC voltage controllers (voltage level is controlled)
Switching circuits
Changing motor circuits parameters in discrete steps for automatic starting and braking
control.
For operating motors and drives according to a predetermine sequence
To provide inter locking their by preventing maloperation
PLC in sequencing and inter locking operation, solid state relays etc.
Variable impedance
Variable resisters are commonly used for AC and DC drives and also needed for
dynamic braking of drives
Semiconductors switch in parallel with a fixed resistance is used where step less
variation is needed. inductors employed to limit starting current of ac motors.
Answer
SCADA (Supervisory Control and Data Acquisition) systems are extensively used to control
geographically distributed processes, which are often scattered over thousands of kilometers
and where centralized data acquisition and control is necessary to perform system operation.
Architecture of SCADA
A typical architecture of a SCADA system is shown in below figure which describes the
general configuration and major components of the SCADA. In this, control area or master
station house main server which acts as MTU and communication routers.
Also, the control area includes engineering workstations, HMI stations, data servers, and data
historians, which are all connected by local area network (LAN). The master station is
responsible for monitoring and controlling various remote stations.
Remote stations are equipped with one or more RTUs/ PLCs which performs local monitoring
through sensors (such as voltage, current, temperature and pressure) and local controlling
through actuators (such as pumps, relays, and valves). The field site devices are connected
through WAN network to perform remote diagnostics.
The communication or transferring of information between field sites and control center is
carried through proprietary communication protocols over serial communications using
telemetry techniques such as cable, telephone line and RF.
Components of SCADA or Block Diagram of SCADA:
The major components of SCADA include
Master Terminal Unit (MTU)
It is the heart of the SCADA system, which can be a dedicated computer, a Programmable
Logic Controller (PLC), or a network server that communicates with remote field side RTUs.
It initiates all communication, collects the data, stores the data in database, provides interfaces
to operators and sends the information to other systems.
It allows the users to perform controlling functions on field devices such as breakers, switches
and other actuators depending on the gathered data. It continuously communicates with other
devices in master station so as to facilitate data logging, alarm processing, trending and
reporting, graphical interface and security system.
Remote Terminal Units (RTUs)
RTUs gather the information from various field sites in which they are employed. Each RTU
is connected with various sensors and actuators that manage local process or field equipment.
It collects the information from various sensors and sends the information to the MTU. Also,
it receives the control commands from MTU and correspondingly controls the various
actuators.
Remote Terminal Units
Many RTUs store the data in their database and waits for a request from the MTU to send or
transmit the data. In sophisticated systems, PLCs are used as RTUs which directly transfers
the field data and controls the parameters without a request from the MTU. It uses a local area
network to communication with various field intelligent devices.
Communication Equipment/Network
It provides the link between RTUs (in the field) to MTU (in the control center). The
communication can be wired or wireless or through internet which provides bidirectional and
uninterrupted communication between RTU and MTU.
SCADA systems can be connected using various communication mediums including twisted
pair cables, coaxial metal cables, fiber optic cables, satellites, high frequency radio, telephone
lines, and microwave radio.
The topology of the SCADA system network depends on the type of system or application it
is intended for. Mostly redundant topology is recommended for critical control applications.
SCADA Software
It is an important aspect of every SCADA system which presents the information to the user
and also allows the user to intervene in the process control. Many SCADA systems use
commercial proprietary software upon which SCADA system is developed.
When one prime mover or motor is used for the number of machine tools on common
shaft then the drive is called as group drive . it is also sometimes called as line shaft drive.
Cost of group drive is less for given capacity of load. cost of one motors of given capacity
is less than the cost of many motors of the same capacity.
Total H.P of motor used in group drive may be less than the sum of the H.P of individual
machines since all the machines may not be working at same time.
Group drive has high overload capacity.
Speed control of individual machine is very difficult.
Answer
It does not give good appearances due to use of line shafting pulleys and belts.
Group drives are less safe to operate.
Flexibility of layout of the various machines is lost in group drive since machines have to
be installed to suit the layout of the line shafting.
Extension of the process by installing new machine is limited.
The breakdown of main motor causes stoppage of all the operations. Considerable power
loss takes place in the energy transmitting system.
It is used in the process where stoppage of one operation requires the stoppage of
sequence of operations as in case of textile mills.
Individual Drive:
In individual drive an electric motor used for transmitting motion to various parts or
mechanism belonging to single equipment. For example, such drive are used to rotate the
spindle, moves the feed and with the help of gears imparts motion to lubricating and
cooling pumps in lathe.
In application, individual drive consist of motor which is specifically designed to form an
integral part of the machine.
In individual drive, the energy is transmitted to different parts of same mechanism by
means of mechanical parts like gear, pulley, etc. hence occurs some power loss.
Multimotor Drive:
The multimotor drive consists of several individual motor which serve to one of many
motions or mechanism in some production unit. For example, in travelling crane, there are
three motors used.
One for hoisting, other for long travel motion and third for cross travel motion. Such a
drive is essential in complicated metal cutting machine, paper making machine, rolling
mills, rotary printing machine, etc.
The use of multimotor drive is expanding in modern industries due to their advantage
outweighs increase in capital cost compared to the group drive.
CHARACTERISTIC
AC DRIVES DC DRIVES
S
Locational use Are used in almost all the are used in very few locations
locations.
Power & Control Power and control circuits Power and control circuits are
Circuitry are difficult and quite simple to design and less expensive
complex in design. s compared to their counter-parts.
Corrosive and Wet Can be used in such Cannot be used because sparks can
Environment environment since their be produced in brushes easily.
operation is spark free
Motor speed Can reach up to 10000 RPM Can reach up to 2500 RPM
Dynamic response Offer high dynamic response Offer low dynamic response
Starting torque Do not produce high starting Produces high starting torque
torque
sinking and sourcing First you will notice that the diagrams on this page are associated with
only DC circuits and not AC, because of the reference to (+) and (-) polarities. Therefore,
sinking and sourcing terminology applies only to DC input and output circuits. Input and
output points that are sinking or sourcing can conduct current in one direction only. This
means it is possible to connect the external supply and field device to the I/O point, with
current trying to flow in the wrong direction, and the circuit will not operate. However, the
supply and field device can be connected every time based on an understanding of sourcing
Answer
and sinking.
The figure below depicts a sinking input. To properly connect the external supply, it must be
connected so the input provides a path to supply common (-). So, start at the PLC input
terminal, follow through the input sensing circuit, exit at the common terminal, and connect
the supply (-) to the common terminal. By adding the switch between the supply (+) and the
input, the circuit is completed. Current flows in the direction of the arrow when the switch is
closed.
Sink/source I/O circuits combine sinking and sourcing capabilities. This means that the I/O
circuitry in the PLC will allow current to flow in either direction, as shown below. The
common terminal connects to one polarity, and the I/O point connects to the other polarity
(through the field device). This provides flexibility in making connections to your field power
supply. Please note:
Wire all I/O points with a shared common as either sinking or sourcing.
8 4 List any four input & Output devices that can be connected to PLC.
1. Mechanical Switches
2. Proximity Switches
3. Photoelectric Sensors and Switches
4. Temperature Sensors
5. Position/Displacement Sensors
6. Strain Gauges
7. Pressure Sensors
Answer 8. Liquid-Level Detectors
9. Fluid Flow Measurement
10. Smart Sensors
Output devices that can be connected to PLC:
1. Relay
2. Directional Control Valves
3. Motors- AC / DC Motor
4. Stepper Motor
5. Display Devices
Write a PLC ladder diagram for following motor sequence:
i) Start button starts motor M1.
ii) After 10 sec M1 is off and M2 is ON.
9 4
iii) After 5 sec motor M2 is off.
iv) Stop push button stops M1, M2, if pressed any time during process.
Draw a neat block diagram of PLC and describe the working of its parts.
13 4
1) Input Module: Input Module works as an interface between the CPU and the real
world input devices attached to input module .The devices connected to input module
are called as input devices. It accepts the incoming signal and converts this signal in
Answer
the form which is compatible with CPU.
2) Output Module: Output module works as an interface or link between the CPU and
the real world devices attached to the output module. The main function of output
module is to take control signal from CPU and based on signal received from CPU it
3) Central processing unit: The CPU is the main part of any PLC .The CPU solves the
user program logic, by using real time input status from input module and updates the
4) Power supply: Power supply is the part of PLC which is used to supply required
user and PLC. The programming device helps the user to enter and modify the required
program into the PLC memory and troubleshoot PLC ladder logic program.
6) Memory: PLC memory is divided in two part, Data memory and User memory. Data
memory is used to store data associated with instruction address and user memory is
Using 3 counters together with the flag of M1013 (1s clock pulse) to operate a 24-
hour clock.
program is executed, C0 will count once per second. When the counted number
reaches 60(1 minute), C0 = ON. C1 will count once, and C0 will be reset at the same
time; similarly, when the counted number in C1 reaches 60(1 hour), C1 = ON. C2 will
count once, and C1 will be reset at the same time. Furthermore, when the present value
in C2 reaches 24, C2 will be reset, and the 24-hour counting process will start again.
The 24-hour clock operates by using C0 to count “second”, C1 to count “minute” and
C2 to count “hour.” In this clock, the value of “second”, “minute” and “hour” can be
read by C0, C1 and C2 correspondingly. When the set value of C2 is 12, the clock will
be a 12-hour clock.
Describe the working of UP counter with neat diagram and waveform.
15 4
Explanation:
When i/p to count up counter goes true the Acc value will be increased by 1 , not matter how
long the i/p is true. So every true rung condition acc will increment by 1.
When acc value reaches the preset value the counter DN bit will be set.
For example as shown in figure, IN example preset value is 5 , in waveform when /p goes
high then CU bit also goes high and Acc values is incremented by one .
When Next high i/p arises at counter i/p then CU bit also goes high and Acc is incremented by
1. Like this when Acc value becomes equal to preset value then DN bit is set and related o/p
device is ON. This DN bit remains high until counter is reset by reset instruction. When reset
instruction is executed counter gets reset and DN bit also goes low and Acc also goes to zero.
Waveform:
2) Time base 1.0: This bit indicates processor increments accumulated values in 1 second
intervals.
4) Accumulator value gives current value of the timer as 0 which increases up to the
preset value
5) I:010/5 : It is the input to the timer
8) DN : This bit is set when accumulator value becomes equal to preset value and then
Explanation of Bits:
1) T4:0 : This bit indicates timer file4,timer 0 ,it stores timer information
2) Time base 1.0: This bit indicates processor increments accumulated values in 1 second
intervals.
3) Preset: It indicates delay for timer
4) Accumulator value gives current value of the timer as 0 which increases up to the preset
value
5) I:010/5 : It is the input to the timer
6) EN : This bit is set ,when input is true
7) TT: This bit is set when timer is running other is reset
8) DN : This bit is set when accumulator value becomes equal to preset value and then
respective output becomes ON.
17 4 Draw Automation hierarchy and explain.
Answer Figure show the Hierarchy arrangement of the Automation systems consisting of different
layers.
LEVEL 0 (FIELD LEVEL)
This lowest level is where all field devices and hardware stands. All these devices are directly
or indirectly connected to automated control mechanism where they respond to the signals
(outputs) they receive and they generate feedback signals (inputs) that reflect the actual
condition on field. For example devices like motors, pneumatic systems reside at this level
and are activated with output signals from PLCs. Similarly devices like sensors, switches,
instruments reside at this level and generate input signals that are received and processed by
PLCs.
Write a ladder diagram for traffic light control with following conditions: i) Red light
19 4 – 25sec, ii) Green light – 20 sec, iii) Yellow light – 5 sec, iv) Repeat the sequence.
25
Answer
20
List different PLC programming languages. Explain any one with example.
20 4
List different editors in SCADA (any four) and describe the functions of each.
21 6
SAGE is an add-on feature for Inkscape to enable real-time mimic graphic animation in SVG
running with IntegraXor SCADA animation engine. Animation effects incorporated such as
"Bar", "Color", "Rotate", "Opacity", "Zoom", "Slider", etc.
ii. Generic Logic: Generic Logic Inc. is a premier provider of Real-Time Graphics, Data
Visualization, HMI SCADA and custom GIS Solutions for software developers around the
world. Its products are used to visualize and control real-time and mission-critical processes in
a variety of industries, from producing silicon wafers and controlling chemical plants to
launching satellites into space and monitoring airport security.
The overall functionality of TRACE MODE® has already overgrown the traditional
HMI/SCADA software, and nevertheless, HMI is still the most demanded part of the TRACE
MODE. In addition to the standard HMI functionality, TRACE MODE® 6 has a number of
features, which distinguish it from the ordinary HMI/SCADA software.
First of all, TRACE MODE has an integrated development environment (IDE), combining in
itself more than 10 different editors. The IDE has a free version. The HMI features of TRACE
MODE 6 SCADA software are so deeply merged with SOFTLOGIC controllers’
programming tool and with economical modules of T-FACTORY (MES-EAM-HRM), that
one can hardly distinguish them.
iv. UCanCode: UCanCode provides a complete set of services, consisting of design tools
and a software development kit (SDK), for developers who want to create a user interface for
industrial monitoring and process control drawing SCADA applications. These displays
feature highly customized graphical objects that connect to underlying real-world data. E-
XD++ is a complete suite of all VC++ and .NET products for SCADA and HMI applications.
Develop a ladder program for Traffic light control system with following conditions:
i) Red light ON for 30 sec, ii) green light ON for 25 sec, and
22 6 iii) Yellow light on for 05 sec. iv) Repeat the sequence until stop push button is
pressed.
Marking
Scheme Device Selection: 3 marks, Explain:3 Marks
Answer
Draw a neat wiring diagram (interfacing diagram) of following I/O devices with
appropriate PLC module: i) Proximity sensor – 24VDC, ii) Limit switch, iii) Lamp -
24 6 24VDC, iv) Fan – 230VAC.
Answer
There are four outputs A, B, C, D. Draw the ladder diagram for following condition:
i) A goes off when stop switch is pressed. ii) B goes off 7 seconds after A.
25 6 iii) C goes off 6 seconds after B. iv) D goes off 2 seconds after C.
Answer
Draw Ladder diagram for automatic bottle filling system. Assume suitable system
26 6
design for the same.
Answer condition of the bottle. After the bottle is filled ,the buzzer sounds and the control program
will again wait for 0.7 secs. before moving to the next bottle .Until the limit switch signals
,the feed motor,M1 runs while there are fixed rollers which carries the filled bottles.
Motor,M2 keeps running after the process has been started.
Once the start button is pressed the green light (L1) turns ON and remains ON until stop
button is pressed.As light turns ON out feed motor(M2) starts running.After M2 runs and if
either limit switch(LS) has not signalled or filled bottle condition is fulfilled motor(M1)
starts.After limit switch has signalled timer,T1 gets activated. After T1 gives done (DN)signal
and photo detector (PE) is disabled ,solenoid valve gets in operation.As PE signals solenoid
stops and buzzer(B1) sounds after which timer,T2 gets enabled which stops the process for
0.7 seconds. Once the filled bottle condition is activated the cycle starts again. The ladder
diagram was successfully checked in the PLC simulator and all the prescribed conditions were
observed completely.
Draw the ladder diagram as shown in Fig. l for elevator system
27 6
Logic
(i) When the start button is pushed the platform is driven to the down position.
(ii) When stop push button is pressed the platform is halted at whatever
position it occupies at that time.
(iii) When up button is pushed, the platform if it is not in down motion is
driven to the up position.
(iii)When the down button is pushed, the platform if it is not in up
motion is driven to down position.
Marking Correct Ladder diagram : 6 Marks.
Scheme
Answer
2. Modular PLC:
Small PLC- Less than 100 I/O additional can be added (20 Input and 12 outputs mounted
locally with the process)
3. There is one fixed, non-removable screw terminal strip containing all input screw terminals
and another screw containing all output control signal screw terminals.
Modular PLC:
Explanation:
1. A modular PLC does not have a terminal strip built into the processor unit.
2. Modular PLC’S have their I/O points on plug in type, removable units called I/O modules.
3. PLC’s with modular inputs and outputs consists chasis, rack or baseplate where power
supply, CPU and all input, output modules are separate hardware items.
4. The power supply is modular is typically hooked up to line voltage on the chasis.
Classify the following devices into input and output devices w.r.t. PLC, pressure
switch, Thermocouple, Motor, push button, Relay coil, toggle switch, Stepper
28 6
motor, level switch, Alarm, RTD, Lamp, Sensor.
Answer
List the different counter instructions ofPLC and explain anyone in detail.
29 4
1.Up Counter:
Answer
Waveform:
Explanation:
Up counter instruction is three word instruction.
CU Bit: This status bit is true when UP counter instruction is true.
DN bit: This bit is true when accumulated value is equal to or greater than
the present value of the counter.
OV(Overflow) bit: when counter count value exceeds 32,767,this bit
becomes true.
UN(Underflow):It will go true when counter counts below -32,768.
Reset instruction resets accumulated value to zero.
OR
2.Down counter:
CD Bit: This status bit is true when DOWN counter instruction is true.
DN bit: This bit is true when accumulated value is equal to or greater than the
present value of the counter.
OV(Overflow) bit: when counter count value exceeds 32,767,this bit becomes
true.
UN(Underflow):It will go true when counter counts below -32,768.
Reset instruction resets accumulated value to zero.
This counter is similar to the CTU; however the high speed counter
instruction is only enabled by the rung on which resides.
This instruction is used to count pulses that are too fast separately from
normal input points and modules.
Most fixed PLCs will have a high speed set of input points that allow
interface to high speed inputs.
Signals from an incremental encoder would be a typical high speed input.
4.Counter Reset:
The Reset instruction resets the counter’s accumulated value back to zero
When I:1/6 is pressed C20:7 counter will reset i.e its accumulated value becomes
zero.
30 6 Draw the block diagram of AC input module. State the function of each.
Marking Draw : 3 Marks, function: 3 Marks.
Scheme
Explanation:
Answer Power conversion:The power conversion section usually consists of resistors and
bridge rectifier. The bridge rectifier converts the incoming AC signal to a pulsating
DC level. The DC level is passed through filters and other logic circuits in order to
deliver a clean, denounced, DC input signal. The filtered DC signal goes on to the
threshold detector.
Threshold detection:Threshold detection circuitry detects if the incoming signal has
reached or exceeded a predetermined value for a predetermine time, and whether it
should be classified as valid ON or OFF signal.
Isolation:Isolation section of the input ckt. Is usually made up of an optical isolator,
or opt coupler. In a 120VAC input module, isolation separates the high voltage,
120VAC input signal from the CPUs low voltage control logic.
Logic section:DC signal from the opto coupler are used by the logic section to pass
the input signal to the module’s input address LED and the CPU and then on to the
input status file.
Draw the ladder diagram to verify the truth table of following logic gates.
(i) AND
31 4 (ii) NOT
(iii) EXOR
(iv) OR
Marking
Scheme
Answer
32 4 State the name of specialityI/0 modules of PLC. Explain anyone.
Marking 2M for listing, 2M for explanation
Scheme
Specialty I/0 modules:
1. Communication module
2. High speed encoder input modules
3. Resistance Temperature Detector (RTD) Input modules
4. Stepper control modules
5. Thermocouple/millivolt input module.
Explanation:
1. Communication module:
ASCII I/O Modules: ASCII I/O modules allow the interfacing of bar code readers,
meters, printers, and data terminals to a PLC. ASCII modules, which accept only
valid ASCII data, are not used as extensively as they once were. Today, the RS-232
module is the module of choice in many applications.
RS-232CInterface Modules: Communication modules are available that reside in a
PLC chassis and enable you to connect a PLC to telephone lines using a modem.
PLCs connected to phone lines allow central control room operators to examine
ladder programs to modify or edit program operation at remote PLC sites. Today
many remote oil, gas, and wastewater applications are unmanned. Remote access by
way of phone lines saves maintenance personnel from driving to remote sites each
time a PLC encounters aproblem or a program change is necessary. .
Answer
OR
2.High-Speed Encoder Input Modules
When input pulses come in faster than a discrete input module can handle them, a highspeed
input module is used. High-speed counters are also used to interface encoders to a PLC.
OR
Resistance Temperature Detector (RTD) lnput Modules
A resistance temperature detector (RTD) input module interfaces a PLC to RTD
temperature-sensing elements and other types of resistance input devices such as
potentiometers. The RTD input module converts analog input signals from a
potentiometer or. RTD into input signals understood by the PLC. These values are
stored in the PLC input table.
OR
Stepper Motor Control Modules
A stepper module is an intelligent module that resides in a PLC chassis and provides
a digital output pulse train for microstepping stepper motor applications.
Thermocouple/Millivolt Input Module
The thermocouple/millivolt input module converts inputs from various thermocouple
or millivolt devices into values that can be input and stored into PLC data tables.
This module greatly enhances the flexibility of a PLC system by interfacing
thermocouples, thus eliminating expensivethermocouple transmitters.Using an RTD
module ,PLCs can thus be used for interface applications requiring temperature and
measurement control.