Tree touchings in the HT line shall be cleared.

Fencing shall be provided for the transformer station.

Danger notice boards and name boards shall be provided for the transformer station.

The AB switch operating handle shall be earthed using braided copper conductor and shall be kept
under lock and key.

Guarding shall be provided at the road crossing portion of the HT line as per Regulation 73 of
CEA(MRS&ES) Regulations, 2010.

Earthing shall conform to IS:3043/87

Required values of Insulation Resistances and Earth Resistance shall be ensured before energising
the installation.

The LT cables shall be clamped properly.

Transformer: Unipower, 100kVA, 11kV/433V


AB Switch: 400A
Earth Electrodes: 4 Nos

DB/Inspectorate/19-20/AE/ES/IJK-2/1