USER MANUAL
SECTION 1: INTRODUCTION
1.
1. General
4. Installation
During their operation, frequency converters can have
The installation and cooling must be in accordance with
live, rotating or moving parts and their surfaces may
the relevant documentation.
become hot, depending on the protection class involved.
All converters must be protected against undue
There can be serious risk(s) of severe physical injury or
mechanical shocks or stress. In particular no
material damage if any of the enclosures are removed or
components may be bent and/or no insulation spacing
if the unit is installed, used or operated incorrectly.
may be altered during transport and handling. Do not
Further details are given in the documentation. touch electronic components or contacts.
All system design, transport, installation, commissioning Converters contain components susceptible to
and maintenance work etc must be carried out by the electrostatic discharge (ESD), which can be easily
qualified specialist personnel only (according to IEC damaged by static electricity or incorrect handling. Do
60364, CENELEC HD 384 or DIN VDE 0100 and EN not damage mechanically or destroy electrical
50110 and national safety regulations). components (health hazard(s) possible).
The technical data and the connection conditions are Do not touch any bare parts of the equipment which may
shown on the rating plate and in the documentation. They be live or any power connections even after the
must be observed. converter has been isolated from the electricity supply,
as capacitors may remain charged. Follow the
3. Transportation and storage instructions given on warning labels.
All instructions for transportation, storage and correct All covers and doors must be kept closed during
handling must be observed. operation.
1.
TABLE OF ILLUSTRATIONS
Figure 1-1 Typical Converteam MV7000 Drive: MV7306 example, skid assembly ........................................1-5
Figure 1-2 MV7000 Main Components, MV7306 S A DFE 12 p example ......................................................1-6
Figure 1-3 Three Level NPC Principle.............................................................................................................1-8
1.
OVERVIEW OF USER
SECTION 1: MANUAL AND MV7000
Introduction
Electrical Drawings
COMMISSIONING Hardware Module
INITIAL START-UP Configuration Document
SECTION 4:
Operating Instructions
Remote Control
NORMAL
Functional Specification
OPERATION
SECTION 5:
DIAGNOSTIC
Protection & Diagnostic
SECTION 6: SHUT-DOWN
Maintenance & Safety MAINTENANCE
1.
1.1.1 ARCHITECTURE
Converteam MV7000 series are medium-voltage variable frequency drives. The topology is a 3-
level NPC (Neutral point clamped), voltage source inverter (VSI) using pulse width modulation
(PWM) for generating the output voltage. It comprises the new generation press pack IGBTs
(Insulated Gate Bipolar Transistors) or IEGTs (Injection Enhanced Gate Transistors). Flat pack
technology is used for lower ratings.
Note: In this user manual, we will use IGBT as a generic term covering both IGBT and IEGT types.
A Converteam MV7000 Drive consists of several cubicles either mounted on a single skid as shown
in Figure 1-1 or made of several sections that are assembled at site.
V OIR MA NUE L DE MA IN T E NA
N CE
V OIR MA NUE L DE MA IN T N
E A NCE V OI R MA NUE L DE MA
IN T E NA NC
E RE F E R T OUS E R GUID E
RE F R
E T OUS E R GUID E RE F E R T OUS E R GUI E
D
Figure 1-1 Typical Converteam MV7000 Drive: MV7306 example, skid assembly
1.
-AP
+
-U1
Transformer -V1
-C
-W1
-R
-VC
-U
-AP
-V
-W
M
3~
-U2
-C
-V2
-R
-W2
Precharge &
premagnetization
Raw Water
(Air as an option)
De-ionized Water
• Rectifier: generates the DC link voltage; based on either diode type 12 pulses or 24 pulses,
or, as an option, active front end (AFE) based on IGBT.
• Precharge & premagnetization transformer: used to precharge the DC link, and to magnetize
the main transformer in order to avoid inrush current.
• Inverter: 3-level Neutral Point Clamped (NPC) Press-Pack IGBT type. The grounding switch
is located in inverter cubicle.
• dV/dt filter: optional for MV7306 / MV7308, reduces switching transients to allow operation
with long motor cables. Equipped as standard for MV7312 / MV7316 / MV76xx.
1.
• Cooling Unit: provides deionized water for cooling inverter and rectifier to transfer drive
losses to external raw water circuit (optional air / de-ionized water heat exchanger).
• Sinus filter (option): converts the PWM Voltage output to a sinusoidal wave, which enhances
the motor capacity, reduces THD and allows a maximum output frequency above 90 Hz.
1.
DC +
0V 0V 0V Output voltage
= 100% VDC
U
VDC 0V V
W
MOTOR
0V 0V 0V
Level 3
DC -
0V 0V 0V Output voltage 1
= 50% VDC
U Level 2
0V V 0.5
W
0V 0V 0V
0
DC -
-0.5
DC +
0V 0V 0V
Output voltage Level 1 -1
= 0% VDC 0 0.2 0.4 0.6 0.8 1
U
V
0V W
0V 0V 0V
DC -
1.
The user shall be solely responsible for the proper and correct use
of the MV7000 frequency converter. CONVERTEAM disclaims any
liability whatsoever for improper or incorrect installation or use.
Training
CONVERTEAM offers training programs for additional and
supplementary system knowledge.
Without our prior approval, this document shall not be copied or disclosed to any third party in any manner
whatsoever. The recipient hereof or any third party shall not use this document for any improper purpose
whatsoever. Translation to any foreign language is not permitted. Any data, dimensions, weights, illustrations
and other technical information shall be subject to change without notice, particularly in the interest of further
perfecting our equipment. The data and specifications agreed to in the event of an order shall be generally
deemed as being the binding basis.