Characteristics :

Reference ATV630D75N4
Hardware Type IP21/IP21Z
Supply Voltage 380...480V/ThreePhase
Nominal Power 75kW/100HP
Nominal Current 145A
Structure :
Device ATV630D75N4
Serial Number 4005500JM163600976
Version V1.3IEXX
Control Board
Serial Number 4005500JM163600976
Version V1.3IE07
Power Board
Serial Number 4005500JM163600976
Version V0.3IE07
Configurations :
Software Release 1.6.0.0
Device Name

SimplyStart

Current Default Min Max Logical


Code Long Label
Value Value Value Value address
60Hz
BFR Motor Standard 50Hz IEC 3015
NEMA
NPR Nominal motor power 100 HP 100 HP 30 HP 150 HP 9613
UNS Nominal motor voltage 440 V 460 V 200 V 500 V 9601
NCR Nominal motor current 119 A 114 A 36.2 A 217.5 A 9603
Nominal Motor
FRS 60 Hz 60 Hz 40 Hz 500 Hz 9602
Frequency
65535
NSP Nominal motor speed 1775 rpm 1771 rpm 0 rpm 9604
rpm
COS Motor 1 Cosinus Phi 0.88 0.85 0.5 1 9606
2-wire 2-wire
TCC 2/3-wire control 11101
control control
TFR Max frequency 72 Hz 72 Hz 10 Hz 500 Hz 3103
Motor Thermal
ITH 119 A 114 A 29 A 159.5 A 9622
Current
Acceleration ramp
ACC 80 s 10 s 0s 999.9 s 9001
time
Deceleration ramp
DEC 100 s 10 s 0s 999.9 s 9002
time
LSP Low Speed 35 Hz 0 Hz 0 Hz 60 Hz 3105
HSP High Speed 60 Hz 60 Hz 35 Hz 72 Hz 3104
Acceleration ramp
ACC 80 s 10 s 0s 999.9 s 9001
time
Deceleration ramp
DEC 100 s 10 s 0s 999.9 s 9002
time
LSP Low Speed 35 Hz 0 Hz 0 Hz 60 Hz 3105
HSP High Speed 60 Hz 60 Hz 35 Hz 72 Hz 3104

MacroConfiguration

Min Max Logical


Code Long Label Current Value Default Value
Value Value address
Application Generic fan control Generic Pump
APPT 15699
selection application Control

MotorParam

Min Max Logical


Code Long Label Current Value Default Value
Value Value address
DRT Dual rating state Normal duty Normal duty 3010
Motor control U/F VC U/F VC
CTT 9607
type Quadratic Quadratic
BFR Motor Standard 60Hz NEMA 50Hz IEC 3015
Nominal motor
NPR 100 HP 100 HP 30 HP 150 HP 9613
power
Nominal motor
UNS 440 V 460 V 200 V 500 V 9601
voltage
Nominal motor
NCR 119 A 114 A 36.2 A 217.5 A 9603
current
Nominal Motor
FRS 60 Hz 60 Hz 40 Hz 500 Hz 9602
Frequency
Nominal motor 65535
NSP 1775 rpm 1771 rpm 0 rpm 9604
speed rpm
Motor parameter Nominal motor Nominal motor
MPC 9614
choice Power Power
Motor 1 Cosinus
COS 0.88 0.85 0.5 1 9606
Phi
AsyncMotor 0 6553.5
RSA 84.6 mOhm 0 mOhm 9642
Stator resistance mOhm mOhm
Magnetizing 6553.5
IDA 24.5 A 0A 0A 9652
Current A
Low Flow 65535
LFA 1347 µH 0 µH 0 µH 9662
Warning µH
Rotor time 65535
TRA 367 ms 0 ms 0 ms 9667
constant ms
Sync motor
NCRS 125 A 125 A 36.2 A 217.5 A 9670
nominal current
Nominal
15996
NSPS synchronous 1500 rpm 1500 rpm 0 rpm 9671
rpm
Rotor time 65535
TRA 367 ms 0 ms 0 ms 9667
constant ms
Sync motor
NCRS 125 A 125 A 36.2 A 217.5 A 9670
nominal current
Nominal
15996
NSPS synchronous 1500 rpm 1500 rpm 0 rpm 9671
rpm
motor speed
Nominal motor 6553.5
TQS 460 Nm 460 Nm 0.1 Nm 9684
torque Nm
Pole pairs
PPNS 3 3 1 50 9672
number (sync)
Pulse Signal Pulse Signal
Auto angle setting
AST Injection - Injection - 13925
type
Optimized Optimized
Sync. EMF 0 6553.5
PHS 186.4 mV/rpm 0 mV/rpm 9673
constant mV/rpm mV/rpm
Calculated
0 6553.5
RSAS SyncMotor Stator 84.6 mOhm 0 mOhm 9682
mOhm mOhm
R
Sync motor d 65535
LDS 1347 µH 0 µH 0 µH 9674
inductance µH
Sync motor q 65535
LQS 1347 µH 0 µH 0 µH 9675
inductance µH
Synchronous
FRSS motor nominal 75 Hz 75 Hz 75 Hz 75 Hz 9679
freq
Maximum current
MCR AUTO AUTO 0% 300 % 15607
of PSI alignment
Filter time of the
CRTF Auto Auto 0 ms 100 ms 9116
current
Internal currents
CRFA 7.9 ms 0 ms 0 ms 100 ms 9118
filter time
% error EMF 6553.5
RDAE 0% 0% 0% 9676
sync %
Response to
TNL Freewheel stop Freewheel stop 7012
Autotuning error
Autotuning input
TUL Not assigned Not assigned 9610
assignment
Automatic
AUT No No 9615
autotune
STUN Tune selection Default Default 9617
Pulse Signal Pulse Signal
Auto angle setting
AST Injection - Injection - 13925
type
Optimized Optimized
Maximum current
MCR AUTO AUTO 0% 300 % 15607
of PSI alignment
Alignment
RCL Rotational Current 75 % 75 % 10 % 300 % 13928
Level
Alignment
RTC Rotational Torque 0% 0% 0% 75 % 13929
Alignment
RCL Rotational Current 75 % 75 % 10 % 300 % 13928
Level
Alignment
RTC Rotational Torque 0% 0% 0% 75 % 13929
Current
Motor Thermal
ITH 119 A 114 A 29 A 159.5 A 9622
Current
Motor thermal
THT Self cooled motor Self cooled motor 9612
monitoring mode
Motor overtemp
OLL Freewheel stop Freewheel stop 7009
error response
CLI Current limitation 159.5 A 159.5 A 0A 159.5 A 9201
SOP Attenuation time 8 µs 8 µs 12602
Sinus filter
OFI No No 3109
activation
Output short
STRT No Yes 3112
circuit test
Activation of the
TH2S thermal monitoring No No 13210
on AI2
Configuration of
AI2T Current Voltage 4403
AI2
Response to
TH2B thermal error for Ramp stop Ramp stop 13240
AI2
Thermal error
TH2F 230 °F 230 °F 5 °F 392 °F 13230
level for AI2
Thermal warning
TH2A 194 °F 194 °F 5 °F 392 °F 13220
level for AI2
AI2 thermal
TH2V 0 °F 0 °F 5 °F 392 °F 13250
value
Activation of the
TH3S thermal monitoring No No 13211
on AI3
Configuration of
AI3T Current Current 4404
AI3
Response to
TH3B thermal error for Ramp stop Ramp stop 13241
AI3
Thermal error
TH3F 230 °F 230 °F 5 °F 392 °F 13231
level for AI3
Thermal warning
TH3A 194 °F 194 °F 5 °F 392 °F 13221
level for AI3
AI3 thermal
TH3V 0 °F 0 °F 5 °F 392 °F 13251
value
Activation of the
TH4S thermal monitoring No No 13212
on AI4
Configuration of AI bipolar volts
AI4T Current 4405
AI4 selected
Response to
Activation of the
TH4S thermal monitoring No No 13212
on AI4
Configuration of AI bipolar volts
AI4T Current 4405
AI4 selected
Response to
TH4B thermal error for Ramp stop Ramp stop 13242
AI4
Thermal error
TH4F 230 °F 230 °F 5 °F 392 °F 13232
level for AI4
Thermal warning
TH4A 194 °F 194 °F 5 °F 392 °F 13222
level for AI4
AI4 thermal
TH4V 0 °F 0 °F 5 °F 392 °F 13252
value
Activation of the
TH5S thermal monitoring No No 13213
on AI5
AI bipolar volts
AI5T AI5 type Current 4406
selected
Response to
TH5B thermal error for Ramp stop Ramp stop 13243
AI5
Thermal error
TH5F 230 °F 230 °F 5 °F 392 °F 13233
level for AI5
Thermal warning
TH5A 194 °F 194 °F 5 °F 392 °F 13223
level for AI5
AI5 thermal
TH5V 0 °F 0 °F 5 °F 392 °F 13253
value
LFF Fall back speed 0 Hz 0 Hz 0 Hz 500 Hz 7080
UFR IR compensation 100 % 100 % 0% 200 % 9623
Slip
SLP 0% 0% 0% 300 % 9625
Compensation
PFL U/F Profile 30 % 30 % 0% 100 % 9624
Volt point 1 on
U1 0V 0V 0V 800 V 12403
5pt V/F
Volt point 2 on
U2 0V 0V 0V 800 V 12405
5pt V/F
Volt point 3 on
U3 0V 0V 0V 800 V 12407
5pt V/F
Volt point 4 on
U4 0V 0V 0V 800 V 12409
5pt V/F
Volt point 5 on
U5 0V 0V 0V 800 V 12411
5pt V/F
Freq point 1on
F1 0 Hz 0 Hz 0 Hz 500 Hz 12404
5pt V/F
Freq point 2 on
F2 0 Hz 0 Hz 0 Hz 500 Hz 12406
5pt V/F
Freq point 3 on
F3 0 Hz 0 Hz 0 Hz 500 Hz 12408
5pt V/F
Freq point 4 on
F4 0 Hz 0 Hz 0 Hz 500 Hz 12410
5pt V/F
5pt V/F
Freq point 3 on
F3 0 Hz 0 Hz 0 Hz 500 Hz 12408
5pt V/F
Freq point 4 on
F4 0 Hz 0 Hz 0 Hz 500 Hz 12410
5pt V/F
Freq point 5 on
F5 0 Hz 0 Hz 0 Hz 500 Hz 12412
5pt V/F
Output phase A - B - C phase A - B - C phase
PHR 13401
rotation rotation rotation
SPGU Inertia factor 40 % 40 % 0% 1000 % 9629
BOA Boost activation Inactive Inactive 13910
BOO Boost 0% 0% 0% 0% 13912
FAB Frequency Boost 0 Hz 0 Hz 0 Hz 0 Hz 13911
Switching
SFR 2.5 kHz 2.5 kHz 1 kHz 8 kHz 3102
frequency
Motor Noise
NRD No No 3107
Reduction
Switching Switch.frequency Switch.frequency
SFT 3101
frequency type type 1 type 1
Motor surge
SVL No No 12601
limitation
SOP Attenuation time 8 µs 8 µs 12602

CommandRefParam

Min Max Logical


Code Long Label Current Value Default Value
Value Value address
Configuration
FR1 reference frequency AI2 Analog input AI1 Analog input 8413
1
Configuration ref.
FR1B Not configured Not configured 8415
1B
Reference Reference
Select switching (1
RCB frequency channel frequency channel 8412
to 1B)
1 1
Reverse direction
RIN Yes Yes 3108
disable
Control mode Combined channel
CHCF I/O mode 8401
configuration mode
Command Command channel Command channel
CCS 8421
switching 1 1
Command channel
CD1 Terminal block Terminal block 8423
1 assign
Command channel Modbus
CD2 Local HMI 8424
2 assign communication
Reference Reference
Freq Switching
RFC frequency channel frequency channel 8411
Assignment
1 1
Configuration
FR2 reference frequency Not configured Not configured 8414
Reference Reference
Freq Switching
RFC frequency channel frequency channel 8411
Assignment
1 1
Configuration
FR2 reference frequency Not configured Not configured 8414
2
COP Copy Ch.1-Ch.2 No copy No copy 8402
Forced Local Reference
FLOC frequency Frequency via Not configured 8432
assignment remote terminal
Time-out forc.
FLOT 10 s 10 s 0.1 s 30 s 8433
local
Forced local
FLO Not assigned Not assigned 8431
assignment
Reverse
RRS Not assigned Not assigned 11105
assignment
TCC 2/3-wire control 2-wire control 2-wire control 11101
Type of 2-wire
TCT Transition Transition 11102
control
PST Stop key enable Yes Yes 64002
Cmd/ref copied on
BMP HMI command Disabled 13529
c/over

GenericFunction

Min Max Logical


Code Long Label Current Value Default Value
Value Value address
LSP Low Speed 35 Hz 0 Hz 0 Hz 60 Hz 3105
HSP High Speed 60 Hz 60 Hz 35 Hz 72 Hz 3104
Reference frequency Standard ref Standard ref
BSP 3106
template selection template template
RPT Type of Ramp Linear ramp Linear ramp 9004
INR Ramp increment 0.1 0.1 9020
Acceleration ramp
ACC 80 s 10 s 0s 999.9 s 9001
time
Deceleration ramp
DEC 100 s 10 s 0s 999.9 s 9002
time
Start ACC ramp
TA1 10 % 10 % 0% 100 % 9005
rounding
End ACC ramp
TA2 10 % 10 % 0% 90 % 9006
rounding
Start DEC ramp
TA3 10 % 10 % 0% 100 % 9007
rounding
End DEC ramp
TA4 10 % 10 % 0% 90 % 9008
rounding
BRA Decel ramp adaptation Yes Yes 9003
Ramp 2 frequency
FRT 0 Hz 0 Hz 0 Hz 500 Hz 9011
threshold
Ramp switching
RPS Not assigned Not assigned 9010
Assignment
End DEC ramp
TA4 10 % 10 % 0% 90 % 9008
rounding
BRA Decel ramp adaptation Yes Yes 9003
Ramp 2 frequency
FRT 0 Hz 0 Hz 0 Hz 500 Hz 9011
threshold
Ramp switching
RPS Not assigned Not assigned 9010
Assignment
Acceleration 2 ramp
AC2 5s 5s 0.1 s 999.9 s 9012
time
DE2 Deceleration 2 5s 5s 0.1 s 999.9 s 9013
STT Type of stop On ramp On ramp 11201
NST Freewheel stop Not assigned Not assigned 11202
Freewheel stop
FFT 0.2 Hz 0.2 Hz 0.2 Hz 500 Hz 11220
threshold
FST Fast stop assignment Not assigned Not assigned 11204
Fast Stop Ramp
DCF 4 4 0 10 11230
Divider
DC Injection
DCI Not assigned Not assigned 11203
Assignment
159.5
IDC DC injection level 1 101.5 A 101.5 A 14.5 A 11210
A
TDI DC injection time 1 0.5 s 0.5 s 0.1 s 30 s 11213
101.5
IDC2 DC injection level 2 72.5 A 72.5 A 14.5 A 11212
A
TDC DC injection time 2 0.5 s 0.5 s 0.1 s 30 s 11211
Type of SwitchOn
DOTD Ramp stop Ramp stop 8652
Disable Stop
Automatic DC No DC No DC
ADC 10401
Injection injection injection
Auto DC injection level 159.5
SDC1 101.5 A 101.5 A 0A 10403
1 A
Auto DC injection time
TDC1 0.5 s 0.5 s 0.1 s 30 s 10402
1
Auto DC injection level 159.5
SDC2 72.5 A 72.5 A 0A 10405
2 A
Auto DC injection time
TDC2 0s 0s 0s 30 s 10404
2
Not
SA2 Summing input 2 Not configured 11801
configured
Not
SA3 Summing input 3 Not configured 11802
configured
Subtract reference Not
DA2 Not configured 11811
frequency 2 configured
Subtract reference Not
DA3 Not configured 11812
frequency 3 configured
Reference frequency 2 Not
MA2 Not configured 11821
multiply configured
Reference frequency 3 Not
MA3 Not configured 11822
multiply configured
2 Preset Freq
PS2 Digital Input 2 Not assigned 11401
assignment
frequency 3 configured
Reference frequency 2 Not
MA2 Not configured 11821
multiply configured
Reference frequency 3 Not
MA3 Not configured 11822
multiply configured
2 Preset Freq
PS2 Digital Input 2 Not assigned 11401
assignment
4 Preset Freq
PS4 Digital Input 3 Not assigned 11402
assignment
8 Preset Freq
PS8 Not assigned Not assigned 11403
assignment
16 Preset Freq
PS16 Not assigned Not assigned 11404
assignment
SP2 Preset speed 2 40.3 Hz 10 Hz 0 Hz 500 Hz 11410
SP3 Preset speed 3 60 Hz 15 Hz 0 Hz 500 Hz 11411
SP4 Preset speed 4 60 Hz 20 Hz 0 Hz 500 Hz 11412
SP5 Preset speed 5 0 Hz 25 Hz 0 Hz 500 Hz 11413
SP6 Preset speed 6 0 Hz 30 Hz 0 Hz 500 Hz 11414
SP7 Preset speed 7 0 Hz 35 Hz 0 Hz 500 Hz 11415
SP8 Preset speed 8 0 Hz 40 Hz 0 Hz 500 Hz 11416
SP9 Preset speed 9 45 Hz 45 Hz 0 Hz 500 Hz 11417
SP10 Preset speed 10 50 Hz 50 Hz 0 Hz 500 Hz 11418
SP11 Preset speed 11 55 Hz 55 Hz 0 Hz 500 Hz 11419
SP12 Preset speed 12 60 Hz 60 Hz 0 Hz 500 Hz 11420
SP13 Preset speed 13 70 Hz 70 Hz 0 Hz 500 Hz 11421
SP14 Preset speed 14 80 Hz 80 Hz 0 Hz 500 Hz 11422
SP15 Preset speed 15 90 Hz 90 Hz 0 Hz 500 Hz 11423
SP16 Preset speed 16 100 Hz 100 Hz 0 Hz 500 Hz 11424
USP + speed assignment Not assigned Not assigned 11501
DSP - speed assignment Not assigned Not assigned 11502
Reference frequency
STR No save No save 11503
save
JPF Skip frequency 0 Hz 0 Hz 0 Hz 500 Hz 11301
JF2 Skip frequency 2 0 Hz 0 Hz 0 Hz 500 Hz 11302
JF3 3rd Skip Frequency 0 Hz 0 Hz 0 Hz 500 Hz 11303
JFH Skip Freq. Hysteresis 1 Hz 1 Hz 0.1 Hz 10 Hz 11311
TOCT Type of control NA NA 11919
PID controller Not
PIF Not configured 11901
feedback configured
AI1T Configuration of AI1 Voltage Voltage 4402
AI1 voltage scaling
UIL1 0V 0V 0V 10 V 4412
parameter of 0%
AI1 voltage scaling
UIH1 10 V 10 V 0V 10 V 4422
parameter of 100%
AI1 current scaling
CRL1 0 mA 0 mA 0 mA 20 mA 4432
parameter of 0%
AI1 current scaling
CRH1 20 mA 20 mA 0 mA 20 mA 4442
parameter of 100%
parameter of 100%
AI1 current scaling
CRL1 0 mA 0 mA 0 mA 20 mA 4432
parameter of 0%
AI1 current scaling
CRH1 20 mA 20 mA 0 mA 20 mA 4442
parameter of 100%
AI2T Configuration of AI2 Current Voltage 4403
AI2 voltage scaling
UIL2 0V 0V 0V 10 V 4413
parameter of 0%
AI2 voltage scaling
UIH2 10 V 10 V 0V 10 V 4423
parameter of 100%
AI2 current scaling
CRL2 4 mA 0 mA 0 mA 20 mA 4433
parameter of 0%
AI2 current scaling
CRH2 20 mA 20 mA 0 mA 20 mA 4443
parameter of 100%
AI3T Configuration of AI3 Current Current 4404
AI3 voltage scaling
UIL3 0V 0V 0V 10 V 4414
parameter of 0%
AI3 voltage scaling
UIH3 10 V 10 V 0V 10 V 4424
parameter of 100%
AI3 current scaling
CRL3 0 mA 0 mA 0 mA 20 mA 4434
parameter of 0%
AI3 current scaling
CRH3 20 mA 20 mA 0 mA 20 mA 4444
parameter of 100%
AI bipolar volts
AI4T Configuration of AI4 Current 4405
selected
AI4 voltage scaling
UIL4 0V 0V 0V 10 V 4415
parameter of 0%
AI4 voltage scaling
UIH4 10 V 10 V 0V 10 V 4425
parameter of 100%
AI4 current scaling
CRL4 0 mA 0 mA 0 mA 20 mA 4435
parameter of 0%
AI4 current scaling
CRH4 20 mA 20 mA 0 mA 20 mA 4445
parameter of 100%
AI bipolar volts
AI5T AI5 type Current 4406
selected
AI5 voltage scaling
UIL5 0V 0V 0V 10 V 4416
parameter of 0%
AI5 voltage scaling
UIH5 10 V 10 V 0V 10 V 4426
parameter of 100%
AI5 current scaling
CRL5 0 mA 0 mA 0 mA 20 mA 4436
parameter of 0%
AI5 current scaling
CRH5 20 mA 20 mA 0 mA 20 mA 4446
parameter of 100%
Minimum PID
PIF1 100 100 0 1000 11904
feedback
Maximum PID
PIF2 1000 1000 100 32767 11905
feedback
RPF PID feedback 0 0 100 1000 11981
Minimum feedback
PAL 100 100 100 1000 11961
level Warning
Maximum feedback
PAH 1000 1000 100 1000 11962
Maximum PID
PIF2 1000 1000 100 32767 11905
feedback
RPF PID feedback 0 0 100 1000 11981
Minimum feedback
PAL 100 100 100 1000 11961
level Warning
Maximum feedback
PAH 1000 1000 100 1000 11962
level Warning
PII Internal PID reference No No 11908
Configuration reference AI2 Analog AI1 Analog
FR1 8413
frequency 1 input input
PIP1 Minimum PID process 150 150 100 900 11906
Maximum PID
PIP2 900 900 150 1000 11907
process
RPI Internal PID reference 150 150 150 900 11920
Auto/Manual select
PAU Not assigned Not assigned 11970
input
Not
PIM Manual PID reference Not configured 11954
configured
Predictive speed Not
FPI Not configured 11950
reference configured
PSR PID speed input % ref 100 % 100 % 1% 100 % 11951
2 PID Preset
PR2 Not assigned Not assigned 11909
assignment
4 PID Preset
PR4 Not assigned Not assigned 11910
assignment
2nd PID preset
RP2 300 300 150 900 11921
reference
3rd PID preset
RP3 600 600 150 900 11922
reference
4th PID preset
RP4 900 900 150 900 11923
reference
RPG PID Proportional gain 1 1 0.01 100 11941
PID controller integral
RIG 1 1 0.01 100 11942
gain
RDG PID derivative gain 0 0 0 100 11943
PRP PID ramp 0s 0s 0s 99.9 s 11984
PIC PID inversion No No 11940
PID controller min. -500
POL 0 Hz 0 Hz 500 Hz 11952
output Hz
PID controller max.
POH 60 Hz 60 Hz 0 Hz 500 Hz 11953
output
PER PID error Warning 100 100 0 65535 11963
PIS PID integral disabled Not assigned Not assigned 11944
ACCP PID acceleration time 5s 5s 0.1 s 999.9 s 11985
SFS PID start ref frequency 0 Hz 0 Hz 0 Hz 500 Hz 11955
PID Feedback
PFMM No No 11930
monitoring activation
PFMR PID Feedback Range 3% 3% 0% 100 % 11931
PID Feedback error
PFMD 10 s 10 s 0s 3600 s 11932
delay
SFS PID start ref frequency 0 Hz 0 Hz 0 Hz 500 Hz 11955
PID Feedback
PFMM No No 11930
monitoring activation
PFMR PID Feedback Range 3% 3% 0% 100 % 11931
PID Feedback error
PFMD 10 s 10 s 0s 3600 s 11932
delay
PID Feedback error
PFMB Ramp stop Ramp stop 11933
response
Low Current Threshold 159.5
CTDL 0A 0A 0A 11010
A
159.5
CTD High current threshold 145 A 145 A 0A 11001
A
FTDL Low Freq. Threshold 0 Hz 0 Hz 0 Hz 500 Hz 11011
Motor frequency
FTD 60 Hz 60 Hz 0 Hz 500 Hz 11003
threshold
2 Frequency
F2DL 0 Hz 0 Hz 0 Hz 500 Hz 11012
Threshold
F2D Frequency threshold 2 60 Hz 60 Hz 0 Hz 500 Hz 11004
Motor thermal
TTD 100 % 100 % 0% 118 % 11002
threshold
Reference high
RTD 0 Hz 0 Hz 0 Hz 500 Hz 11013
threshold
Reference low
RTDL 0 Hz 0 Hz 0 Hz 500 Hz 11014
threshold
Mains contactor
LLC Not assigned Not assigned 13602
control
LES Drive lock assignment Not assigned Not assigned 13601
Time-out after cont.
LCT 5s 5s 5s 999 s 13603
activ.
Reverse direction
RIN Yes Yes 3108
disable
TLA Torque limit. activation Not assigned Not assigned 9210
Maximum power in
TPMM 300 % 300 % 10 % 300 % 9216
motor mode
Maximum power in
TPMG 300 % 300 % 10 % 300 % 9217
generator mode
TLS Low speed timeout 0s 0s 0s 999.9 s 11701

GenericProtections

Default Min Max Logical


Code Long Label Current Value
Value Value Value address
Underld T. Delay
ULT 0s 0s 0s 100 s 14411
Detect.
Unld.Thr. at Nom.
LUN 60 % 60 % 20 % 100 % 14416
speed
LUL Unld.Thr. at O speed 0% 0% 0% 60 % 14415
Unld. Freq.Thr.
RMUD 0 Hz 0 Hz 0 Hz 500 Hz 14414
Detection
Unld.Thr. at Nom.
LUN 60 % 60 % 20 % 100 % 14416
speed
LUL Unld.Thr. at O speed 0% 0% 0% 60 % 14415
Unld. Freq.Thr.
RMUD 0 Hz 0 Hz 0 Hz 500 Hz 14414
Detection
SRB Hysteresis Frequency 0.3 Hz 0.3 Hz 0.3 Hz 500 Hz 14401
Freewheel
UDL Underload Management Freewheel stop 14412
stop
Unld Time Before
FTU 0 min 0 min 0 min 6 min 14413
Restart
TOL Overload Time Detect. 0s 0s 0s 100 s 14421
Ovld Threshold
LOC 110 % 110 % 70 % 150 % 14425
Detection
SRB Hysteresis Frequency 0.3 Hz 0.3 Hz 0.3 Hz 500 Hz 14401
Ovld.Proces Freewheel
ODL Freewheel stop 14422
Management stop
FTO Ovld time Before Restart 0 min 0 min 0 min 6 min 14423
Stall monitoring
STPC No No 9270
activation
STP1 Motor stall max time 60 s 60 s 0s 200 s 9271
Stall monitoring current
STP2 150 % 150 % 0% 150 % 9272
level
Stall monitoring
STP3 2 Hz 2 Hz 0 Hz 500 Hz 9273
frequency level
Activation of the thermal
TH2S No No 13210
monitoring on AI2
AI2T Configuration of AI2 Current Voltage 4403
Response to thermal
TH2B Ramp stop Ramp stop 13240
error for AI2
Thermal error level for
TH2F 230 °F 230 °F 5 °F 392 °F 13230
AI2
Thermal warning level for
TH2A 194 °F 194 °F 5 °F 392 °F 13220
AI2
TH2V AI2 thermal value 0 °F 0 °F 5 °F 392 °F 13250
Activation of the thermal
TH3S No No 13211
monitoring on AI3
AI3T Configuration of AI3 Current Current 4404
Response to thermal
TH3B Ramp stop Ramp stop 13241
error for AI3
Thermal error level for
TH3F 230 °F 230 °F 5 °F 392 °F 13231
AI3
Thermal warning level for
TH3A 194 °F 194 °F 5 °F 392 °F 13221
AI3
TH3V AI3 thermal value 0 °F 0 °F 5 °F 392 °F 13251
Activation of the thermal
TH4S No No 13212
monitoring on AI4
AI bipolar volts
AI4T Configuration of AI4 Current 4405
selected
Response to thermal
TH4B Ramp stop Ramp stop 13242
error for AI4
monitoring on AI4
AI bipolar volts
AI4T Configuration of AI4 Current 4405
selected
Response to thermal
TH4B Ramp stop Ramp stop 13242
error for AI4
Thermal error level for
TH4F 230 °F 230 °F 5 °F 392 °F 13232
AI4
Thermal warning level for
TH4A 194 °F 194 °F 5 °F 392 °F 13222
AI4
TH4V AI4 thermal value 0 °F 0 °F 5 °F 392 °F 13252
Activation of the thermal
TH5S No No 13213
monitoring on AI5
AI bipolar volts
AI5T AI5 type Current 4406
selected
Response to thermal
TH5B Ramp stop Ramp stop 13243
error for AI5
Thermal error level for
TH5F 230 °F 230 °F 5 °F 392 °F 13233
AI5
Thermal warning level for
TH5A 194 °F 194 °F 5 °F 392 °F 13223
AI5
TH5V AI5 thermal value 0 °F 0 °F 5 °F 392 °F 13253
LFF Fall back speed 0 Hz 0 Hz 0 Hz 500 Hz 7080

Fan

Default Min Max Logical


Code Long Label Current Value
Value Value Value address
Not
INH Disable Error Detection Not assigned 7125
assigned
ATR Automatic Fault reset No No 7122
FLR Catch on fly No No 3110
TOCT Type of control NA NA 11919
PID controller Not
PIF Not configured 11901
feedback configured
AI1T Configuration of AI1 Voltage Voltage 4402
AI1 voltage scaling
UIL1 0V 0V 0V 10 V 4412
parameter of 0%
AI1 voltage scaling
UIH1 10 V 10 V 0V 10 V 4422
parameter of 100%
AI1 current scaling
CRL1 0 mA 0 mA 0 mA 20 mA 4432
parameter of 0%
AI1 current scaling
CRH1 20 mA 20 mA 0 mA 20 mA 4442
parameter of 100%
AI2T Configuration of AI2 Current Voltage 4403
AI2 voltage scaling
UIL2 0V 0V 0V 10 V 4413
parameter of 0%
AI2 voltage scaling
UIH2 10 V 10 V 0V 10 V 4423
parameter of 100%
AI2 current scaling
CRL2 4 mA 0 mA 0 mA 20 mA 4433
AI2T Configuration of AI2 Current Voltage 4403
AI2 voltage scaling
UIL2 0V 0V 0V 10 V 4413
parameter of 0%
AI2 voltage scaling
UIH2 10 V 10 V 0V 10 V 4423
parameter of 100%
AI2 current scaling
CRL2 4 mA 0 mA 0 mA 20 mA 4433
parameter of 0%
AI2 current scaling
CRH2 20 mA 20 mA 0 mA 20 mA 4443
parameter of 100%
AI3T Configuration of AI3 Current Current 4404
AI3 voltage scaling
UIL3 0V 0V 0V 10 V 4414
parameter of 0%
AI3 voltage scaling
UIH3 10 V 10 V 0V 10 V 4424
parameter of 100%
AI3 current scaling
CRL3 0 mA 0 mA 0 mA 20 mA 4434
parameter of 0%
AI3 current scaling
CRH3 20 mA 20 mA 0 mA 20 mA 4444
parameter of 100%
AI bipolar volts
AI4T Configuration of AI4 Current 4405
selected
AI4 voltage scaling
UIL4 0V 0V 0V 10 V 4415
parameter of 0%
AI4 voltage scaling
UIH4 10 V 10 V 0V 10 V 4425
parameter of 100%
AI4 current scaling
CRL4 0 mA 0 mA 0 mA 20 mA 4435
parameter of 0%
AI4 current scaling
CRH4 20 mA 20 mA 0 mA 20 mA 4445
parameter of 100%
AI bipolar volts
AI5T AI5 type Current 4406
selected
AI5 voltage scaling
UIL5 0V 0V 0V 10 V 4416
parameter of 0%
AI5 voltage scaling
UIH5 10 V 10 V 0V 10 V 4426
parameter of 100%
AI5 current scaling
CRL5 0 mA 0 mA 0 mA 20 mA 4436
parameter of 0%
AI5 current scaling
CRH5 20 mA 20 mA 0 mA 20 mA 4446
parameter of 100%
Minimum PID
PIF1 100 100 0 1000 11904
feedback
Maximum PID
PIF2 1000 1000 100 32767 11905
feedback
RPF PID feedback 0 0 100 1000 11981
Minimum feedback level
PAL 100 100 100 1000 11961
Warning
Maximum feedback
PAH 1000 1000 100 1000 11962
level Warning
PII Internal PID reference No No 11908
Configuration reference AI2 Analog AI1 Analog
FR1 8413
frequency 1 input input
PIP1 Minimum PID process 150 150 100 900 11906
Maximum feedback
PAH 1000 1000 100 1000 11962
level Warning
PII Internal PID reference No No 11908
Configuration reference AI2 Analog AI1 Analog
FR1 8413
frequency 1 input input
PIP1 Minimum PID process 150 150 100 900 11906
PIP2 Maximum PID process 900 900 150 1000 11907
RPI Internal PID reference 150 150 150 900 11920
Auto/Manual select Not
PAU Not assigned 11970
input assigned
Not
PIM Manual PID reference Not configured 11954
configured
Predictive speed Not
FPI Not configured 11950
reference configured
PSR PID speed input % ref 100 % 100 % 1% 100 % 11951
2 PID Preset Not
PR2 Not assigned 11909
assignment assigned
4 PID Preset Not
PR4 Not assigned 11910
assignment assigned
2nd PID preset
RP2 300 300 150 900 11921
reference
3rd PID preset
RP3 600 600 150 900 11922
reference
4th PID preset
RP4 900 900 150 900 11923
reference
RPG PID Proportional gain 1 1 0.01 100 11941
PID controller integral
RIG 1 1 0.01 100 11942
gain
RDG PID derivative gain 0 0 0 100 11943
PRP PID ramp 0s 0s 0s 99.9 s 11984
PIC PID inversion No No 11940
PID controller min. -500
POL 0 Hz 0 Hz 500 Hz 11952
output Hz
PID controller max.
POH 60 Hz 60 Hz 0 Hz 500 Hz 11953
output
PER PID error Warning 100 100 0 65535 11963
Not
PIS PID integral disabled Not assigned 11944
assigned
ACCP PID acceleration time 5s 5s 0.1 s 999.9 s 11985
SFS PID start ref frequency 0 Hz 0 Hz 0 Hz 500 Hz 11955
PID Feedback
PFMM No No 11930
monitoring activation
PFMR PID Feedback Range 3% 3% 0% 100 % 11931
PID Feedback error
PFMD 10 s 10 s 0s 3600 s 11932
delay
PID Feedback error
PFMB Ramp stop Ramp stop 11933
response
JPF Skip frequency 0 Hz 0 Hz 0 Hz 500 Hz 11301
JF2 Skip frequency 2 0 Hz 0 Hz 0 Hz 500 Hz 11302
delay
PID Feedback error
PFMB Ramp stop Ramp stop 11933
response
JPF Skip frequency 0 Hz 0 Hz 0 Hz 500 Hz 11301
JF2 Skip frequency 2 0 Hz 0 Hz 0 Hz 500 Hz 11302
JF3 3rd Skip Frequency 0 Hz 0 Hz 0 Hz 500 Hz 11303
JFH Skip Freq. Hysteresis 1 Hz 1 Hz 0.1 Hz 10 Hz 11311

InputOuput

Min Max Logical


Code Long Label Current Value Default Value
Value Value address
Reference frequency Standard ref Standard ref
BSP 3106
template selection template template
DI5 Pulse Input
PI5A Not assigned Not assigned 4875
assignment
DI6 Pulse Input
PI6A Not assigned Not assigned 4876
assignment
Reference
AI1A AI1 assignment Not assigned 4821
frequency 1
Reference
AI2A AI2 assignment Not assigned 4822
frequency 1
AI3A AI3 assignment Not assigned Not assigned 4823
AI4A AI4 assignment Not assigned Not assigned 4824
AI5 functions
AI5A Not assigned Not assigned 4825
assignment
AV1A AIV1 assignment Not assigned Not assigned 4861
L1L DI1 Low assignment Not assigned Not assigned 4831
L1H DI1 High assignment Not assigned Not assigned 4801
L2L DI2 Low assignment Not assigned Not assigned 4832
Select 2 preset
L2H DI2 High assignment Not assigned 4802
speeds
L3L DI3 Low assignment Not assigned Not assigned 4833
Select 4 preset
L3H DI3 High assignment Not assigned 4803
speeds
L4L DI4 Low assignment Not assigned Not assigned 4834
L4H DI4 High assignment Fault Reset Fault Reset 4804
L5L DI5 Low assignment Not assigned Not assigned 4835
L5H DI5 High assignment Not assigned Not assigned 4805
L6L DI6 Low assignment Not assigned Not assigned 4836
L6H DI6 High assignment Not assigned Not assigned 4806
L11L DI11 Low assignment Not assigned Not assigned 4841
L11H DI11 High assignment Not assigned Not assigned 4811
L12L DI12 Low assignment Not assigned Not assigned 4842
L12H DI12 High assignment Not assigned Not assigned 4812
L13L DI13 Low assignment Not assigned Not assigned 4843
L13H DI13 High assignment Not assigned Not assigned 4813
L12L DI12 Low assignment Not assigned Not assigned 4842
L12H DI12 High assignment Not assigned Not assigned 4812
L13L DI13 Low assignment Not assigned Not assigned 4843
L13H DI13 High assignment Not assigned Not assigned 4813
L14L DI14 Low assignment Not assigned Not assigned 4844
L14H DI14 High assignment Not assigned Not assigned 4814
L15L DI15 Low assignment Not assigned Not assigned 4845
L15H DI15 High assignment Not assigned Not assigned 4815
L16L DI16 Low assignment Not assigned Not assigned 4846
L16H DI16 High assignment Not assigned Not assigned 4816
L1L DI1 Low assignment Not assigned Not assigned 4831
L1H DI1 High assignment Not assigned Not assigned 4801
200
L1D DI1 Delay 0 ms 0 ms 0 ms 4001
ms
L2L DI2 Low assignment Not assigned Not assigned 4832
Select 2 preset
L2H DI2 High assignment Not assigned 4802
speeds
200
L2D DI2 Delay 0 ms 0 ms 0 ms 4002
ms
L3L DI3 Low assignment Not assigned Not assigned 4833
Select 4 preset
L3H DI3 High assignment Not assigned 4803
speeds
200
L3D DI3 Delay 0 ms 0 ms 0 ms 4003
ms
L4L DI4 Low assignment Not assigned Not assigned 4834
L4H DI4 High assignment Fault Reset Fault Reset 4804
200
L4D DI4 Delay 0 ms 0 ms 0 ms 4004
ms
L5L DI5 Low assignment Not assigned Not assigned 4835
L5H DI5 High assignment Not assigned Not assigned 4805
200
L5D DI5 Delay 0 ms 0 ms 0 ms 4005
ms
L6L DI6 Low assignment Not assigned Not assigned 4836
L6H DI6 High assignment Not assigned Not assigned 4806
200
L6D DI6 Delay 0 ms 0 ms 0 ms 4006
ms
L11L DI11 Low assignment Not assigned Not assigned 4841
L11H DI11 High assignment Not assigned Not assigned 4811
200
L11D DI11 Delay 0 ms 0 ms 0 ms 4011
ms
L12L DI12 Low assignment Not assigned Not assigned 4842
L12H DI12 High assignment Not assigned Not assigned 4812
200
L12D DI12 Delay 0 ms 0 ms 0 ms 4012
ms
L13L DI13 Low assignment Not assigned Not assigned 4843
L13H DI13 High assignment Not assigned Not assigned 4813
200
L13D DI13 Delay 0 ms 0 ms 0 ms 4013
200
L12D DI12 Delay 0 ms 0 ms 0 ms 4012
ms
L13L DI13 Low assignment Not assigned Not assigned 4843
L13H DI13 High assignment Not assigned Not assigned 4813
200
L13D DI13 Delay 0 ms 0 ms 0 ms 4013
ms
L14L DI14 Low assignment Not assigned Not assigned 4844
L14H DI14 High assignment Not assigned Not assigned 4814
200
L14D DI14 Delay 0 ms 0 ms 0 ms 4014
ms
L15L DI15 Low assignment Not assigned Not assigned 4845
L15H DI15 High assignment Not assigned Not assigned 4815
200
L15D DI15 delay 0 ms 0 ms 0 ms 4015
ms
L16L DI16 Low assignment Not assigned Not assigned 4846
L16H DI16 High assignment Not assigned Not assigned 4816
200
L16D DI16 delay 0 ms 0 ms 0 ms 4016
ms
DI5 Pulse Input
PI5A Not assigned Not assigned 4875
assignment
DI5 PulseInput Low 30000
PIL5 0 Hz 0 Hz 0 Hz 13320
Frequency Hz
PulseInput DI5 High 30
PIH5 30 kHz 30 kHz 0 kHz 13322
Frequency kHz
1000
PFI5 DI5 Frequency filter 0 ms 0 ms 0 ms 13324
ms
DI6 Pulse Input
PI6A Not assigned Not assigned 4876
assignment
DI6 PulseInput Low 30000
PIL6 0 Hz 0 Hz 0 Hz 13340
Frequency Hz
DI6 PulseInput High 30
PIH6 30 kHz 30 kHz 0 kHz 13342
Frequency kHz
1000
PFI6 DI6 Frequency filter 0 ms 0 ms 0 ms 13344
ms
DO11 DO11 assignment Not assigned Not assigned 5033
60000
D11D DQ11 activation delay 0 ms 0 ms 0 ms 4283
ms
DQ11 status (output
D11S 1 1 4263
active level)
9999
D11H DQ11 holding delay 0 ms 0 ms 0 ms 4273
ms
DO12 DO12 assignment Not assigned Not assigned 5034
60000
D12D DQ12 activation delay 0 ms 0 ms 0 ms 4284
ms
DQ12 status (output
D12S 1 1 4264
active level)
9999
D12H DQ12 holding delay 0 ms 0 ms 0 ms 4274
ms
Reference
AI1A AI1 assignment Not assigned 4821
frequency 1
active level)
9999
D12H DQ12 holding delay 0 ms 0 ms 0 ms 4274
ms
Reference
AI1A AI1 assignment Not assigned 4821
frequency 1
AI1T Configuration of AI1 Voltage Voltage 4402
AI1 voltage scaling
UIL1 0V 0V 0V 10 V 4412
parameter of 0%
AI1 voltage scaling
UIH1 10 V 10 V 0V 10 V 4422
parameter of 100%
AI1 current scaling
CRL1 0 mA 0 mA 0 mA 20 mA 4432
parameter of 0%
AI1 current scaling
CRH1 20 mA 20 mA 0 mA 20 mA 4442
parameter of 100%
AI1F AI1 filter 0s 0s 0s 10 s 4452
AI1 intermediate point
AI1E 0% 0% 0% 100 % 4462
X
AI1 intermediate point
AI1S 0% 0% 0% 100 % 4472
Y
Reference
AI2A AI2 assignment Not assigned 4822
frequency 1
AI2T Configuration of AI2 Current Voltage 4403
AI2 voltage scaling
UIL2 0V 0V 0V 10 V 4413
parameter of 0%
AI2 voltage scaling
UIH2 10 V 10 V 0V 10 V 4423
parameter of 100%
AI2 current scaling
CRL2 4 mA 0 mA 0 mA 20 mA 4433
parameter of 0%
AI2 current scaling
CRH2 20 mA 20 mA 0 mA 20 mA 4443
parameter of 100%
AI2F AI2 filter 0s 0s 0s 10 s 4453
AI2 intermediate point
AI2E 0% 0% 0% 100 % 4463
X
AI2 intermediate point
AI2S 0% 0% 0% 100 % 4473
Y
AI3A AI3 assignment Not assigned Not assigned 4823
AI3T Configuration of AI3 Current Current 4404
AI3 voltage scaling
UIL3 0V 0V 0V 10 V 4414
parameter of 0%
AI3 voltage scaling
UIH3 10 V 10 V 0V 10 V 4424
parameter of 100%
AI3 current scaling
CRL3 0 mA 0 mA 0 mA 20 mA 4434
parameter of 0%
AI3 current scaling
CRH3 20 mA 20 mA 0 mA 20 mA 4444
parameter of 100%
AI3F AI3 filter 0s 0s 0s 10 s 4454
AI3 intermediate point
AI3E 0% 0% 0% 100 % 4464
X
AI3 intermediate point
AI3S 0% 0% 0% 100 % 4474
Y
AI3F AI3 filter 0s 0s 0s 10 s 4454
AI3 intermediate point
AI3E 0% 0% 0% 100 % 4464
X
AI3 intermediate point
AI3S 0% 0% 0% 100 % 4474
Y
AI4A AI4 assignment Not assigned Not assigned 4824
AI bipolar volts
AI4T Configuration of AI4 Current 4405
selected
AI4 voltage scaling
UIL4 0V 0V 0V 10 V 4415
parameter of 0%
AI4 voltage scaling
UIH4 10 V 10 V 0V 10 V 4425
parameter of 100%
AI4 current scaling
CRL4 0 mA 0 mA 0 mA 20 mA 4435
parameter of 0%
AI4 current scaling
CRH4 20 mA 20 mA 0 mA 20 mA 4445
parameter of 100%
AI4F AI4 filter 0s 0s 0s 10 s 4455
AI4 intermediate point
AI4E 0% 0% 0% 100 % 4465
X
AI4 intermediate point
AI4S 0% 0% 0% 100 % 4475
Y
AI5 functions
AI5A Not assigned Not assigned 4825
assignment
AI bipolar volts
AI5T AI5 type Current 4406
selected
AI5 voltage scaling
UIL5 0V 0V 0V 10 V 4416
parameter of 0%
AI5 voltage scaling
UIH5 10 V 10 V 0V 10 V 4426
parameter of 100%
AI5 current scaling
CRL5 0 mA 0 mA 0 mA 20 mA 4436
parameter of 0%
AI5 current scaling
CRH5 20 mA 20 mA 0 mA 20 mA 4446
parameter of 100%
AI5 cutoff time of the
AI5F 0s 0s 0s 10 s 4456
low-filter
AI5 delinearization input
AI5E 0% 0% 0% 100 % 4466
level
AI5 delinearization
AI5S 0% 0% 0% 100 % 4476
output level
Motor Motor
AO1 AQ1 assignment 5021
frequency frequency
AO1T AQ1 Type Current Current 4601
AOL1 AQ1 min output value 4 mA 0 mA 0 mA 20 mA 4641
AOH1 AQ1 max output value 20 mA 20 mA 0 mA 20 mA 4651
UOL1 AQ1 minimum output 0V 0V 0V 10 V 4621
UOH1 AQ1 maximum output 10 V 10 V 0V 10 V 4631
ASL1 Scaling AQ1 min 0% 0% 0% 100 % 4661
ASH1 Scaling AQ1 max 100 % 100 % 0% 100 % 4671
AO1F AQ1 filter 0s 0s 0s 10 s 4611
AO2 AQ2 assignment Motor current Motor current 5022
ASL1 Scaling AQ1 min 0% 0% 0% 100 % 4661
ASH1 Scaling AQ1 max 100 % 100 % 0% 100 % 4671
AO1F AQ1 filter 0s 0s 0s 10 s 4611
AO2 AQ2 assignment Motor current Motor current 5022
AO2T Configuration of AQ2 Current Current 4602
AOL2 AQ2 min output value 0 mA 0 mA 0 mA 20 mA 4642
AOH2 AQ2 max output value 20 mA 20 mA 0 mA 20 mA 4652
UOL2 AQ2 minimum output 0V 0V 0V 10 V 4622
UOH2 AQ2 maximum output 10 V 10 V 0V 10 V 4632
ASL2 Scaling AQ2 min 0% 0% 0% 100 % 4662
ASH2 Scaling AQ2 max 100 % 100 % 0% 100 % 4672
AO2F AQ2 filter 0s 0s 0s 10 s 4612
AV1A AIV1 assignment Not assigned Not assigned 4861
Channel assignment for
AIC1 virtual Analog Input Not configured Not configured 5282
AIV1
Drive in Drive in
R1 R1 Assignment operating state operating state 5001
Fault Fault
R1D R1 Delay time 0 ms 0 ms 0 ms 0 ms 4241
R1S R1 Active level 1 1 4201
R1H R1 Holding time 0 ms 0 ms 0 ms 0 ms 4221
R2 R2 Assignment Drive running Not assigned 5002
60000
R2D R2 Delay time 0 ms 0 ms 0 ms 4242
ms
R2S R2 Active level 1 1 4202
9999
R2H R2 Holding time 0 ms 0 ms 0 ms 4222
ms
R3 R3 Assignment Not assigned Not assigned 5003
60000
R3D R3 Delay time 0 ms 0 ms 0 ms 4243
ms
R3S R3 Active level 1 1 4203
9999
R3H R3 Holding time 0 ms 0 ms 0 ms 4223
ms
R4 R4 Assignment Not assigned Not assigned 5004
60000
R4D R4 Delay time 0 ms 0 ms 0 ms 4244
ms
R4S R4 Active level 1 1 4204
9999
R4H R4 Holding time 0 ms 0 ms 0 ms 4224
ms
R5 R5 Assignment Not assigned Not assigned 5005
60000
R5D R5 Delay time 0 ms 0 ms 0 ms 4245
ms
R5S R5 Active at 1 1 4205
9999
R5H R5 Holding time 0 ms 0 ms 0 ms 4225
ms
R6 R6 assignment Not assigned Not assigned 5006
60000
R5D R5 Delay time 0 ms 0 ms 0 ms 4245
ms
R5S R5 Active at 1 1 4205
9999
R5H R5 Holding time 0 ms 0 ms 0 ms 4225
ms
R6 R6 assignment Not assigned Not assigned 5006
60000
R6D R6 activation delay time 0 ms 0 ms 0 ms 4246
ms
R6 status (output active
R6S 1 1 4206
level)
9999
R6H R6 holding delay time 0 ms 0 ms 0 ms 4226
ms

Pump Functions

Min Max Logical


Code Long Label Current Value Default Value
Value Value address
Pump System
MPSA Mono-Pump Mono-Pump 16500
architecture selection
MPPN Number of pumps 1 1 1 1 16503
MPPC Pump cycling mode Pump runtime Pump runtime 16505
Lead pump
MPLA Deactivated Deactivated 16506
alternation
MPID Pump ready delay 0s 0s 0s 3600 s 16507
Response to
MPFB Freewheel stop Freewheel stop 16508
Multipump error
Command assignment
MPO1 Not assigned Not assigned 16521
for pump 1
Pump 1 ready to
MPI1 Not assigned Not assigned 16511
operate assignment
Command assignment
MPO2 Not assigned Not assigned 16522
for pump 2
Pump 2 ready to
MPI2 Not assigned Not assigned 16512
operate assignment
Command assignment
MPO3 Not assigned Not assigned 16523
for pump 3
Pump 3 ready to
MPI3 Not assigned Not assigned 16513
operate assignment
Command assignment
MPO4 Not assigned Not assigned 16524
for pump 4
Pump 4 ready to
MPI4 Not assigned Not assigned 16514
operate assignment
Command assignment
MPO5 Not assigned Not assigned 16525
for pump 5
Pump 5 ready to
MPI5 Not assigned Not assigned 16515
operate assignment
Command assignment
MPO6 Not assigned Not assigned 16526
for pump 6
Pump 6 ready to
MPI6 Not assigned Not assigned 16516
operate assignment
for pump 5
Pump 5 ready to
MPI5 Not assigned Not assigned 16515
operate assignment
Command assignment
MPO6 Not assigned Not assigned 16526
for pump 6
Pump 6 ready to
MPI6 Not assigned Not assigned 16516
operate assignment
BCM Booster Control No No 16600
Booster stage/destage
BSDT 15 s 15 s 0s 999.9 s 16601
time interval
Booster stage/destage
BSDC Feedback Feedback 16610
condition
Booster working
BCWA 2% 2% 1% 100 % 16615
range
BSS Booster stage speed 60 Hz 60 Hz 0 Hz 500 Hz 16611
Booster destage
BDS 48 Hz 48 Hz 0 Hz 500 Hz 16612
speed
BSD Booster stage delay 10 s 10 s 0s 999.9 s 16613
Booster destage
BDD 10 s 10 s 0s 999.9 s 16614
delay
Booster override
BCOA No No 0% 100 % 16616
range
Booster stage/destage
BSDM Feedback Feedback 16620
control
Booster stage bypass
BSBS 54 Hz 54 Hz 0 Hz 500 Hz 16621
speed
Booster stage bypass
BSBT 3s 3s 0s 999.9 s 16622
time
Booster stage ramp
BSRD 1s 1s 0s 999.9 s 16623
delay
Booster destage
BDBS 60 Hz 60 Hz 0 Hz 500 Hz 16624
bypass speed
Booster destage
BDBT 1s 1s 0s 999.9 s 16625
bypass time
Booster destage ramp
BDRD 0s 0s 0s 999.9 s 16626
delay
Feed Forward stage
FFSD 1s 1s 0s 999.9 s 16627
delay
Feed Forward
FFDD 0s 0s 0s 999.9 s 16628
destage delay
Feed Forward
FFG 20 % 20 % 0% 100 % 11986
disturbance gain
Feed Forward
FFTG 3s 3s 0s 99.9 s 11987
disturbance time
Pump System
MPSA Mono-Pump Mono-Pump 16500
architecture selection
MPPN Number of pumps 1 1 1 1 16503
MPPC Pump cycling mode Pump runtime Pump runtime 16505
Lead pump
MPLA Deactivated Deactivated 16506
alternation
MPID Pump ready delay 0s 0s 0s 3600 s 16507
MPPN Number of pumps 1 1 1 1 16503
MPPC Pump cycling mode Pump runtime Pump runtime 16505
Lead pump
MPLA Deactivated Deactivated 16506
alternation
MPID Pump ready delay 0s 0s 0s 3600 s 16507
Response to
MPFB Freewheel stop Freewheel stop 16508
Multipump error
Command assignment
MPO1 Not assigned Not assigned 16521
for pump 1
Pump 1 ready to
MPI1 Not assigned Not assigned 16511
operate assignment
Command assignment
MPO2 Not assigned Not assigned 16522
for pump 2
Pump 2 ready to
MPI2 Not assigned Not assigned 16512
operate assignment
Command assignment
MPO3 Not assigned Not assigned 16523
for pump 3
Pump 3 ready to
MPI3 Not assigned Not assigned 16513
operate assignment
Command assignment
MPO4 Not assigned Not assigned 16524
for pump 4
Pump 4 ready to
MPI4 Not assigned Not assigned 16514
operate assignment
Command assignment
MPO5 Not assigned Not assigned 16525
for pump 5
Pump 5 ready to
MPI5 Not assigned Not assigned 16515
operate assignment
Command assignment
MPO6 Not assigned Not assigned 16526
for pump 6
Pump 6 ready to
MPI6 Not assigned Not assigned 16516
operate assignment
LCM Level control mode Deactivated Deactivated 16630
Level control sensor
LCNT Level Switches Level Switches 16631
type
LCST Level control strategy Switches Switches 16632
Level Sensor
LCSA Not configured Not configured 15720
Assignment
Minimum level switch
LCWL Not assigned Not assigned 16638
assignment
Maximum level switch
LCWH Not assigned Not assigned 16639
assignment
Tank volume to be 32767
LCTV 0 gal 0 gal 0 gal 16634
filled or emptied gal
Level control low
LCLS 35 Hz 35 Hz 0 Hz 500 Hz 16635
speed
Level control random
LCRX 0% 0% 0% 100 % 16633
factor
Each pump Each pump
Level control stop
LCPM stopped stopped 16636
mode
individually individually
speed
Level control random
LCRX 0% 0% 0% 100 % 16633
factor
Each pump Each pump
Level control stop
LCPM stopped stopped 16636
mode
individually individually
-
Empty Tank Level 32767
LCTJ 0 psi 0 psi 32767 16641
Sensor Value psi
psi
-
Full Tank Level 32767
LCTK 0 psi 0 psi 32767 16642
Sensor Value psi
psi
Level control : delivery 327.67
LCDH 0m 0m 0m 16687
height m
Level control error
LCFB Ramp stop Ramp stop 16637
response
AI1T Configuration of AI1 Voltage Voltage 4402
AI1 voltage scaling
UIL1 0V 0V 0V 10 V 4412
parameter of 0%
AI1 voltage scaling
UIH1 10 V 10 V 0V 10 V 4422
parameter of 100%
AI1 current scaling
CRL1 0 mA 0 mA 0 mA 20 mA 4432
parameter of 0%
AI1 current scaling
CRH1 20 mA 20 mA 0 mA 20 mA 4442
parameter of 100%
-
AI1J AI1 Lowest Process 0 0 32767 4502
32767
-
AI1K AI1 Highest Process 0 0 32767 4512
32767
AI2T Configuration of AI2 Current Voltage 4403
AI2 voltage scaling
UIL2 0V 0V 0V 10 V 4413
parameter of 0%
AI2 voltage scaling
UIH2 10 V 10 V 0V 10 V 4423
parameter of 100%
AI2 current scaling
CRL2 4 mA 0 mA 0 mA 20 mA 4433
parameter of 0%
AI2 current scaling
CRH2 20 mA 20 mA 0 mA 20 mA 4443
parameter of 100%
-
AI2J AI2 Lowest Process 0 0 32767 4503
32767
-
AI2K AI2 Highest Process 0 0 32767 4513
32767
AI3T Configuration of AI3 Current Current 4404
AI3 voltage scaling
UIL3 0V 0V 0V 10 V 4414
parameter of 0%
AI3 voltage scaling
UIH3 10 V 10 V 0V 10 V 4424
parameter of 100%
AI3 current scaling
CRL3 0 mA 0 mA 0 mA 20 mA 4434
parameter of 0%
AI3 current scaling
CRH3 20 mA 20 mA 0 mA 20 mA 4444
parameter of 100%
parameter of 100%
AI3 current scaling
CRL3 0 mA 0 mA 0 mA 20 mA 4434
parameter of 0%
AI3 current scaling
CRH3 20 mA 20 mA 0 mA 20 mA 4444
parameter of 100%
-
AI3J AI3 Lowest Process 0 0 32767 4504
32767
-
AI3K AI3 Highest Process 0 0 32767 4514
32767
AI bipolar volts
AI4T Configuration of AI4 Current 4405
selected
AI4 voltage scaling
UIL4 0V 0V 0V 10 V 4415
parameter of 0%
AI4 voltage scaling
UIH4 10 V 10 V 0V 10 V 4425
parameter of 100%
AI4 current scaling
CRL4 0 mA 0 mA 0 mA 20 mA 4435
parameter of 0%
AI4 current scaling
CRH4 20 mA 20 mA 0 mA 20 mA 4445
parameter of 100%
-
AI4J AI4 Lowest Process 0 0 32767 4505
32767
-
AI4K AI4 Highest Process 0 0 32767 4515
32767
AI bipolar volts
AI5T AI5 type Current 4406
selected
AI5 voltage scaling
UIL5 0V 0V 0V 10 V 4416
parameter of 0%
AI5 voltage scaling
UIH5 10 V 10 V 0V 10 V 4426
parameter of 100%
AI5 current scaling
CRL5 0 mA 0 mA 0 mA 20 mA 4436
parameter of 0%
AI5 current scaling
CRH5 20 mA 20 mA 0 mA 20 mA 4446
parameter of 100%
-
AI5J AI5 Lowest Process 0 0 32767 4506
32767
-
AI5K AI5 Highest Process 0 0 32767 4516
32767
Channel assignment
AIC1 for virtual Analog Input Not configured Not configured 5282
AIV1
AIV1 Lowest -
AV1J 0 0 32767 4522
Process 32767
AIV1 Highest -
AV1K 0 0 32767 4532
Process 32767
Level switch 1
LCW1 Not assigned Not assigned 16651
assignment
Level switch 2
LCW2 Not assigned Not assigned 16652
assignment
Level switch 3
LCW3 Not assigned Not assigned 16653
assignment
Level switch 4
LCW4 Not assigned Not assigned 16654
assignment
assignment
Level switch 2
LCW2 Not assigned Not assigned 16652
assignment
Level switch 3
LCW3 Not assigned Not assigned 16653
assignment
Level switch 4
LCW4 Not assigned Not assigned 16654
assignment
Level switch 5
LCW5 Not assigned Not assigned 16655
assignment
Level switch 6
LCW6 Not assigned Not assigned 16656
assignment
Level to start first
LRL1 0% 0% 0% 100 % 16661
pump
Level to stop first
LPL1 0% 0% 0% 100 % 16671
pump
Level to reach first
LHL1 0% 0% 0% 100 % 16681
pump high speed
Level to start second
LRL2 0% 0% 0% 100 % 16662
pump
Level to stop second
LPL2 0% 0% 0% 100 % 16672
pump
Level to reach second
LHL2 0% 0% 0% 100 % 16682
pump high speed
Level to start third
LRL3 0% 0% 0% 100 % 16663
pump
Level to stop third
LPL3 0% 0% 0% 100 % 16673
pump
Level to reach third
LHL3 0% 0% 0% 100 % 16683
pump high speed
Level to start fourth
LRL4 0% 0% 0% 100 % 16664
pump
Level to stop fourth
LPL4 0% 0% 0% 100 % 16674
pump
Level to reach fourth
LHL4 0% 0% 0% 100 % 16684
pump high speed
Level to start fifth
LRL5 0% 0% 0% 100 % 16665
pump
Level to stop fifth
LPL5 0% 0% 0% 100 % 16675
pump
Level to reach fifth
LHL5 0% 0% 0% 100 % 16685
pump high speed
Level to start sixth
LRL6 0% 0% 0% 100 % 16666
pump
Level to stop sixth
LPL6 0% 0% 0% 100 % 16676
pump
Level to reach sixth
LHL6 0% 0% 0% 100 % 16686
pump high speed
TOCT Type of control NA NA 11919
PID controller
PIF Not configured Not configured 11901
feedback
AI1T Configuration of AI1 Voltage Voltage 4402
Level to reach sixth
LHL6 0% 0% 0% 100 % 16686
pump high speed
TOCT Type of control NA NA 11919
PID controller
PIF Not configured Not configured 11901
feedback
AI1T Configuration of AI1 Voltage Voltage 4402
AI1 voltage scaling
UIL1 0V 0V 0V 10 V 4412
parameter of 0%
AI1 voltage scaling
UIH1 10 V 10 V 0V 10 V 4422
parameter of 100%
AI1 current scaling
CRL1 0 mA 0 mA 0 mA 20 mA 4432
parameter of 0%
AI1 current scaling
CRH1 20 mA 20 mA 0 mA 20 mA 4442
parameter of 100%
AI2T Configuration of AI2 Current Voltage 4403
AI2 voltage scaling
UIL2 0V 0V 0V 10 V 4413
parameter of 0%
AI2 voltage scaling
UIH2 10 V 10 V 0V 10 V 4423
parameter of 100%
AI2 current scaling
CRL2 4 mA 0 mA 0 mA 20 mA 4433
parameter of 0%
AI2 current scaling
CRH2 20 mA 20 mA 0 mA 20 mA 4443
parameter of 100%
AI3T Configuration of AI3 Current Current 4404
AI3 voltage scaling
UIL3 0V 0V 0V 10 V 4414
parameter of 0%
AI3 voltage scaling
UIH3 10 V 10 V 0V 10 V 4424
parameter of 100%
AI3 current scaling
CRL3 0 mA 0 mA 0 mA 20 mA 4434
parameter of 0%
AI3 current scaling
CRH3 20 mA 20 mA 0 mA 20 mA 4444
parameter of 100%
AI bipolar volts
AI4T Configuration of AI4 Current 4405
selected
AI4 voltage scaling
UIL4 0V 0V 0V 10 V 4415
parameter of 0%
AI4 voltage scaling
UIH4 10 V 10 V 0V 10 V 4425
parameter of 100%
AI4 current scaling
CRL4 0 mA 0 mA 0 mA 20 mA 4435
parameter of 0%
AI4 current scaling
CRH4 20 mA 20 mA 0 mA 20 mA 4445
parameter of 100%
AI bipolar volts
AI5T AI5 type Current 4406
selected
AI5 voltage scaling
UIL5 0V 0V 0V 10 V 4416
parameter of 0%
AI5 voltage scaling
UIH5 10 V 10 V 0V 10 V 4426
parameter of 100%
AI5 current scaling
CRL5 0 mA 0 mA 0 mA 20 mA 4436
parameter of 0%
AI5 current scaling
CRH5 20 mA 20 mA 0 mA 20 mA 4446
parameter of 0%
AI5 voltage scaling
UIH5 10 V 10 V 0V 10 V 4426
parameter of 100%
AI5 current scaling
CRL5 0 mA 0 mA 0 mA 20 mA 4436
parameter of 0%
AI5 current scaling
CRH5 20 mA 20 mA 0 mA 20 mA 4446
parameter of 100%
Minimum PID
PIF1 100 100 0 1000 11904
feedback
Maximum PID
PIF2 1000 1000 100 32767 11905
feedback
RPF PID feedback 0 0 100 1000 11981
Minimum feedback
PAL 100 100 100 1000 11961
level Warning
Maximum feedback
PAH 1000 1000 100 1000 11962
level Warning
Internal PID
PII No No 11908
reference
Configuration AI2 Analog AI1 Analog
FR1 8413
reference frequency 1 input input
Minimum PID
PIP1 150 150 100 900 11906
process
Maximum PID
PIP2 900 900 150 1000 11907
process
Internal PID
RPI 150 150 150 900 11920
reference
Auto/Manual select
PAU Not assigned Not assigned 11970
input
Manual PID
PIM Not configured Not configured 11954
reference
Predictive speed
FPI Not configured Not configured 11950
reference
PID speed input %
PSR 100 % 100 % 1% 100 % 11951
ref
2 PID Preset
PR2 Not assigned Not assigned 11909
assignment
4 PID Preset
PR4 Not assigned Not assigned 11910
assignment
2nd PID preset
RP2 300 300 150 900 11921
reference
3rd PID preset
RP3 600 600 150 900 11922
reference
4th PID preset
RP4 900 900 150 900 11923
reference
PID Proportional gain
RPG 1 1 0.01 100 11941

PID controller integral


RIG 1 1 0.01 100 11942
gain
RDG PID derivative gain 0 0 0 100 11943
PRP PID ramp 0s 0s 0s 99.9 s 11984
PIC PID inversion No No 11940
PID controller integral
RIG 1 1 0.01 100 11942
gain
RDG PID derivative gain 0 0 0 100 11943
PRP PID ramp 0s 0s 0s 99.9 s 11984
PIC PID inversion No No 11940
PID controller min. -500
POL 0 Hz 0 Hz 500 Hz 11952
output Hz
PID controller max.
POH 60 Hz 60 Hz 0 Hz 500 Hz 11953
output
PER PID error Warning 100 100 0 65535 11963
PIS PID integral disabled Not assigned Not assigned 11944
ACCP PID acceleration time 5s 5s 0.1 s 999.9 s 11985
PID start ref
SFS 0 Hz 0 Hz 0 Hz 500 Hz 11955
frequency
Sleep Detection
SLPM No No 11750
Mode
Sleep Switch
SLPW Not assigned Not assigned 11751
Assignment
Installation Flow
FS1A Not configured Not configured 15703
Sensor Assignment
0 32767
SLNL Sleep Flow Level No No 11752
GPM GPM
Outlet Pressure
PS2A Not configured Not configured 15702
Sensor Assignment
32767
SLPL Sleep Pressure Level No No 0 psi 11762
psi
Sleep Minimum Speed
SLSL No No 0 Hz 500 Hz 11753
Level
100
SLPR Sleep Power Level No No 0 HP 11754
HP
SLPD Sleep Delay 20 s 20 s 0s 3600 s 11755
AI1T Configuration of AI1 Voltage Voltage 4402
AI1 voltage scaling
UIL1 0V 0V 0V 10 V 4412
parameter of 0%
AI1 voltage scaling
UIH1 10 V 10 V 0V 10 V 4422
parameter of 100%
AI1 current scaling
CRL1 0 mA 0 mA 0 mA 20 mA 4432
parameter of 0%
AI1 current scaling
CRH1 20 mA 20 mA 0 mA 20 mA 4442
parameter of 100%
-
AI1J AI1 Lowest Process 0 0 32767 4502
32767
-
AI1K AI1 Highest Process 0 0 32767 4512
32767
AI2T Configuration of AI2 Current Voltage 4403
AI2 voltage scaling
UIL2 0V 0V 0V 10 V 4413
parameter of 0%
AI2 voltage scaling
UIH2 10 V 10 V 0V 10 V 4423
parameter of 100%
AI2 current scaling
CRL2 4 mA 0 mA 0 mA 20 mA 4433
AI2T Configuration of AI2 Current Voltage 4403
AI2 voltage scaling
UIL2 0V 0V 0V 10 V 4413
parameter of 0%
AI2 voltage scaling
UIH2 10 V 10 V 0V 10 V 4423
parameter of 100%
AI2 current scaling
CRL2 4 mA 0 mA 0 mA 20 mA 4433
parameter of 0%
AI2 current scaling
CRH2 20 mA 20 mA 0 mA 20 mA 4443
parameter of 100%
-
AI2J AI2 Lowest Process 0 0 32767 4503
32767
-
AI2K AI2 Highest Process 0 0 32767 4513
32767
AI3T Configuration of AI3 Current Current 4404
AI3 voltage scaling
UIL3 0V 0V 0V 10 V 4414
parameter of 0%
AI3 voltage scaling
UIH3 10 V 10 V 0V 10 V 4424
parameter of 100%
AI3 current scaling
CRL3 0 mA 0 mA 0 mA 20 mA 4434
parameter of 0%
AI3 current scaling
CRH3 20 mA 20 mA 0 mA 20 mA 4444
parameter of 100%
-
AI3J AI3 Lowest Process 0 0 32767 4504
32767
-
AI3K AI3 Highest Process 0 0 32767 4514
32767
AI bipolar volts
AI4T Configuration of AI4 Current 4405
selected
AI4 voltage scaling
UIL4 0V 0V 0V 10 V 4415
parameter of 0%
AI4 voltage scaling
UIH4 10 V 10 V 0V 10 V 4425
parameter of 100%
AI4 current scaling
CRL4 0 mA 0 mA 0 mA 20 mA 4435
parameter of 0%
AI4 current scaling
CRH4 20 mA 20 mA 0 mA 20 mA 4445
parameter of 100%
-
AI4J AI4 Lowest Process 0 0 32767 4505
32767
-
AI4K AI4 Highest Process 0 0 32767 4515
32767
AI bipolar volts
AI5T AI5 type Current 4406
selected
AI5 voltage scaling
UIL5 0V 0V 0V 10 V 4416
parameter of 0%
AI5 voltage scaling
UIH5 10 V 10 V 0V 10 V 4426
parameter of 100%
AI5 current scaling
CRL5 0 mA 0 mA 0 mA 20 mA 4436
parameter of 0%
AI5 current scaling
CRH5 20 mA 20 mA 0 mA 20 mA 4446
parameter of 100%
-
AI5J AI5 Lowest Process 0 0 32767 4506
parameter of 100%
AI5 current scaling
CRL5 0 mA 0 mA 0 mA 20 mA 4436
parameter of 0%
AI5 current scaling
CRH5 20 mA 20 mA 0 mA 20 mA 4446
parameter of 100%
-
AI5J AI5 Lowest Process 0 0 32767 4506
32767
-
AI5K AI5 Highest Process 0 0 32767 4516
32767
DI5 PulseInput Low 30000
PIL5 0 Hz 0 Hz 0 Hz 13320
Frequency Hz
PulseInput DI5 High
PIH5 30 kHz 30 kHz 0 kHz 30 kHz 13322
Frequency
-
PI5J DI5 Min process 0 0 32767 13332
32767
-
PI5K DI5 Max process 0 0 32767 13334
32767
DI6 PulseInput Low 30000
PIL6 0 Hz 0 Hz 0 Hz 13340
Frequency Hz
DI6 PulseInput High
PIH6 30 kHz 30 kHz 0 kHz 30 kHz 13342
Frequency
-
PI6J DI6 Min process 0 0 32767 13352
32767
-
PI6K DI6 Max process 0 0 32767 13354
32767
Channel assignment
AIC1 for virtual Analog Input Not configured Not configured 5282
AIV1
AIV1 Lowest -
AV1J 0 0 32767 4522
Process 32767
AIV1 Highest -
AV1K 0 0 32767 4532
Process 32767
AI1T Configuration of AI1 Voltage Voltage 4402
AI1 voltage scaling
UIL1 0V 0V 0V 10 V 4412
parameter of 0%
UIH1 AI1 voltage scaling 10 V 10 V 0V 10 V 4422
parameter of 100%
AI1 current scaling
CRL1 0 mA 0 mA 0 mA 20 mA 4432
parameter of 0%
AI1 current scaling
CRH1 20 mA 20 mA 0 mA 20 mA 4442
parameter of 100%
-
AI1J AI1 Lowest Process 0 0 32767 4502
32767
-
AI1K AI1 Highest Process 0 0 32767 4512
32767
AI2T Configuration of AI2 Current Voltage 4403
AI2 voltage scaling
UIL2 0V 0V 0V 10 V 4413
parameter of 0%
AI2 voltage scaling
UIH2 10 V 10 V 0V 10 V 4423
parameter of 100%
AI2 current scaling
CRL2 4 mA 0 mA 0 mA 20 mA 4433
AI2 voltage scaling
UIL2 0V 0V 0V 10 V 4413
parameter of 0%
AI2 voltage scaling
UIH2 10 V 10 V 0V 10 V 4423
parameter of 100%
AI2 current scaling
CRL2 4 mA 0 mA 0 mA 20 mA 4433
parameter of 0%
AI2 current scaling
CRH2 20 mA 20 mA 0 mA 20 mA 4443
parameter of 100%
-
AI2J AI2 Lowest Process 0 0 32767 4503
32767
-
AI2K AI2 Highest Process 0 0 32767 4513
32767
AI3T Configuration of AI3 Current Current 4404
AI3 voltage scaling
UIL3 0V 0V 0V 10 V 4414
parameter of 0%
AI3 voltage scaling
UIH3 10 V 10 V 0V 10 V 4424
parameter of 100%
AI3 current scaling
CRL3 0 mA 0 mA 0 mA 20 mA 4434
parameter of 0%
AI3 current scaling
CRH3 20 mA 20 mA 0 mA 20 mA 4444
parameter of 100%
-
AI3J AI3 Lowest Process 0 0 32767 4504
32767
-
AI3K AI3 Highest Process 0 0 32767 4514
32767
AI bipolar volts
AI4T Configuration of AI4 Current 4405
selected
AI4 voltage scaling
UIL4 0V 0V 0V 10 V 4415
parameter of 0%
AI4 voltage scaling
UIH4 10 V 10 V 0V 10 V 4425
parameter of 100%
AI4 current scaling
CRL4 0 mA 0 mA 0 mA 20 mA 4435
parameter of 0%
AI4 current scaling
CRH4 20 mA 20 mA 0 mA 20 mA 4445
parameter of 100%
-
AI4J AI4 Lowest Process 0 0 32767 4505
32767
-
AI4K AI4 Highest Process 0 0 32767 4515
32767
AI bipolar volts
AI5T AI5 type Current 4406
selected
AI5 voltage scaling
UIL5 0V 0V 0V 10 V 4416
parameter of 0%
AI5 voltage scaling
UIH5 10 V 10 V 0V 10 V 4426
parameter of 100%
AI5 current scaling
CRL5 0 mA 0 mA 0 mA 20 mA 4436
parameter of 0%
AI5 current scaling
CRH5 20 mA 20 mA 0 mA 20 mA 4446
parameter of 100%
-
AI5J AI5 Lowest Process 0 0 32767 4506
parameter of 100%
AI5 current scaling
CRL5 0 mA 0 mA 0 mA 20 mA 4436
parameter of 0%
AI5 current scaling
CRH5 20 mA 20 mA 0 mA 20 mA 4446
parameter of 100%
-
AI5J AI5 Lowest Process 0 0 32767 4506
32767
-
AI5K AI5 Highest Process 0 0 32767 4516
32767
Channel assignment
AIC1 for virtual Analog Input Not configured Not configured 5282
AIV1
AIV1 Lowest -
AV1J 0 0 32767 4522
Process 32767
AIV1 Highest -
AV1K 0 0 32767 4532
Process 32767
SLBS Sleep Boost Speed No No 0 Hz 500 Hz 11756
SLBT Sleep Boost Time No No 0s 3600 s 11757
Advanced Sleep
ASLM No No 11780
Mode
Advanced Sleep
ASLC Check Speed 0 Hz 0 Hz 0 Hz 60 Hz 11781
Condition
Advanced Sleep
ASLD 20 s 20 s 0s 9999 s 11782
Check Delay
Advanced Sleep
ASLR Check Reference 0 Hz 0 Hz 0 Hz 60 Hz 11783
Speed
WUPM Wake Up Mode FeedBack FeedBack 11758
Wake Up Process
WUPF 0 0 0 1000 11759
level
Wake UP Process
WUPE 0 0 0 1000 11760
Error level
Outlet Pressure
PS2A Not configured Not configured 15702
Sensor Assignment
Wake Up Pressure 32767
WUPL 0 psi 0 psi 0 psi 11763
level psi
AI1T Configuration of AI1 Voltage Voltage 4402
AI1 voltage scaling
UIL1 0V 0V 0V 10 V 4412
parameter of 0%
AI1 voltage scaling
UIH1 10 V 10 V 0V 10 V 4422
parameter of 100%
AI1 current scaling
CRL1 0 mA 0 mA 0 mA 20 mA 4432
parameter of 0%
AI1 current scaling
CRH1 20 mA 20 mA 0 mA 20 mA 4442
parameter of 100%
-
AI1J AI1 Lowest Process 0 0 32767 4502
32767
-
AI1K AI1 Highest Process 0 0 32767 4512
32767
AI2T Configuration of AI2 Current Voltage 4403
parameter of 100%
-
AI1J AI1 Lowest Process 0 0 32767 4502
32767
-
AI1K AI1 Highest Process 0 0 32767 4512
32767
AI2T Configuration of AI2 Current Voltage 4403
AI2 voltage scaling
UIL2 0V 0V 0V 10 V 4413
parameter of 0%
AI2 voltage scaling
UIH2 10 V 10 V 0V 10 V 4423
parameter of 100%
AI2 current scaling
CRL2 4 mA 0 mA 0 mA 20 mA 4433
parameter of 0%
AI2 current scaling
CRH2 20 mA 20 mA 0 mA 20 mA 4443
parameter of 100%
-
AI2J AI2 Lowest Process 0 0 32767 4503
32767
-
AI2K AI2 Highest Process 0 0 32767 4513
32767
AI3T Configuration of AI3 Current Current 4404
AI3 voltage scaling
UIL3 0V 0V 0V 10 V 4414
parameter of 0%
AI3 voltage scaling
UIH3 10 V 10 V 0V 10 V 4424
parameter of 100%
AI3 current scaling
CRL3 0 mA 0 mA 0 mA 20 mA 4434
parameter of 0%
AI3 current scaling
CRH3 20 mA 20 mA 0 mA 20 mA 4444
parameter of 100%
-
AI3J AI3 Lowest Process 0 0 32767 4504
32767
-
AI3K AI3 Highest Process 0 0 32767 4514
32767
AI bipolar volts
AI4T Configuration of AI4 Current 4405
selected
AI4 voltage scaling
UIL4 0V 0V 0V 10 V 4415
parameter of 0%
AI4 voltage scaling
UIH4 10 V 10 V 0V 10 V 4425
parameter of 100%
AI4 current scaling
CRL4 0 mA 0 mA 0 mA 20 mA 4435
parameter of 0%
AI4 current scaling
CRH4 20 mA 20 mA 0 mA 20 mA 4445
parameter of 100%
-
AI4J AI4 Lowest Process 0 0 32767 4505
32767
-
AI4K AI4 Highest Process 0 0 32767 4515
32767
AI bipolar volts
AI5T AI5 type Current 4406
selected
AI5 voltage scaling
UIL5 0V 0V 0V 10 V 4416
parameter of 0%
AI5 voltage scaling
UIH5 10 V 10 V 0V 10 V 4426
parameter of 100%
selected
AI5 voltage scaling
UIL5 0V 0V 0V 10 V 4416
parameter of 0%
AI5 voltage scaling
UIH5 10 V 10 V 0V 10 V 4426
parameter of 100%
AI5 current scaling
CRL5 0 mA 0 mA 0 mA 20 mA 4436
parameter of 0%
AI5 current scaling
CRH5 20 mA 20 mA 0 mA 20 mA 4446
parameter of 100%
-
AI5J AI5 Lowest Process 0 0 32767 4506
32767
-
AI5K AI5 Highest Process 0 0 32767 4516
32767
Channel assignment
AIC1 for virtual Analog Input Not configured Not configured 5282
AIV1
AIV1 Lowest -
AV1J 0 0 32767 4522
Process 32767
AIV1 Highest -
AV1K 0 0 32767 4532
Process 32767
PID Feedback
PFMM No No 11930
monitoring activation
PFMR PID Feedback Range 3% 3% 0% 100 % 11931
PID Feedback error
PFMD 10 s 10 s 0s 3600 s 11932
delay
PID Feedback error
PFMB Ramp stop Ramp stop 11933
response
Select which curve
Disable pump Disable pump
PCM data are managed and 15770
characteristics characteristics
will be entered on
Pump Flow Sensor
FS2A Not configured Not configured 15704
Assignment
Pump Curve
PCA No No 15771
Activation
Pump Characteristics
PCS None None 15750
Status
Pump speed for which 32767
PCSP 0 rpm 0 rpm 0 rpm 15751
curves are entered rpm
0 32767
PCBQ Flow at BEP 0 GPM 0 GPM 15768
GPM GPM
32767
PCBH BEP Head 0 psi 0 psi 0 psi 15767
psi
3276.7
PCBP BEP Power 0 HP 0 HP 0 HP 15769
HP
Flow rate entered at
0 32767
PCQ1 point x (for HQ and 0 GPM 0 GPM 15752
GPM GPM
PQ curves)
Head entered at y (for 32767
PCH1 0 psi 0 psi 0 psi 15757
HQ curve) psi
Mechanical power 3276.7
PCP1 0 HP 0 HP 0 HP 15762
entered at point y HP
PQ curves)
Head entered at y (for 32767
PCH1 0 psi 0 psi 0 psi 15757
HQ curve) psi
Mechanical power 3276.7
PCP1 0 HP 0 HP 0 HP 15762
entered at point y HP
Flow rate entered at
0 32767
PCQ2 point x (for HQ and 0 GPM 0 GPM 15753
GPM GPM
PQ curves)
Head entered at y (for 32767
PCH2 0 psi 0 psi 0 psi 15758
HQ curve) psi
Mechanical power 3276.7
PCP2 0 HP 0 HP 0 HP 15763
entered at point y HP
Flow rate entered at
0 32767
PCQ3 point x (for HQ and 0 GPM 0 GPM 15754
GPM GPM
PQ curves)
Head entered at y (for 32767
PCH3 0 psi 0 psi 0 psi 15759
HQ curve) psi
Mechanical power 3276.7
PCP3 0 HP 0 HP 0 HP 15764
entered at point y HP
Flow rate entered at
0 32767
PCQ4 point x (for HQ and 0 GPM 0 GPM 15755
GPM GPM
PQ curves)
Head entered at y (for 32767
PCH4 0 psi 0 psi 0 psi 15760
HQ curve) psi
Mechanical power 3276.7
PCP4 0 HP 0 HP 0 HP 15765
entered at point y HP
Flow rate entered at
0 32767
PCQ5 point x (for HQ and 0 GPM 0 GPM 15756
GPM GPM
PQ curves)
Head entered at y (for 32767
PCH5 0 psi 0 psi 0 psi 15761
HQ curve) psi
Mechanical power 3276.7
PCP5 0 HP 0 HP 0 HP 15766
entered at point y HP
-100
HEO Head Static Offset 0% 0% 100 % 16004
%
HEG Head Dynamic Gain 0% 0% 0% 100 % 16003
Estimated Pump head
SLHV 0 psi 0 psi 0 psi 0 psi 16012
value
Flow Estimation Disable pump Disable pump
FEM 16000
Mode characteristics characteristics
HEG Head Dynamic Gain 0% 0% 0% 100 % 16003
-100
HEO Head Static Offset 0% 0% 100 % 16004
%
-100
PEG Power Dynamic Gain 0% 0% 100 % 16005
%
-100
PEO Power Static Offset 0% 0% 100 % 16006
%
0 32767
FS2V Pump Flow Value 0 GPM 0 GPM 15716
GPM GPM
Estimated Pump flow 0
SLFV 0 GPM 0 GPM 0 GPM 16007
value GPM
LSP Low Speed 35 Hz 0 Hz 0 Hz 60 Hz 3105
%
0 32767
FS2V Pump Flow Value 0 GPM 0 GPM 15716
GPM GPM
Estimated Pump flow 0
SLFV 0 GPM 0 GPM 0 GPM 16007
value GPM
LSP Low Speed 35 Hz 0 Hz 0 Hz 60 Hz 3105
HSP High Speed 60 Hz 60 Hz 35 Hz 72 Hz 3104
Acceleration ramp
ACC 80 s 10 s 0s 999.9 s 9001
time
Deceleration ramp
DEC 100 s 10 s 0s 999.9 s 9002
time
ACCS Acceleration on Start No No 0s 999.9 s 9040
DECS Deceleration on Stop No No 0s 999.9 s 9044
Deceleration while
DECV check valve is closing No No 0s 999.9 s 9041
(Smooth)
Speed Level up to
CVLS which check-valve 0 Hz 0 Hz 0 Hz 0 Hz 9043
ramp is used
Speed level from
CVHS which check-valve 0 Hz 0 Hz 0 Hz 60 Hz 9042
ramp is used
Reference frequency Standard ref Standard ref
BSP 3106
template selection template template
Pipe Fill Activation
PFM No No 15800
Mode
Outlet Pressure
PS2A Not configured Not configured 15702
Sensor Assignment
Pipe Fill Activation
PFEC Yes Yes 15801
Source
PFWU Pipe Fill on wake up Yes Yes 15806
PFHS Pipe Fill SPeed 25 Hz 25 Hz 0 Hz 500 Hz 15803
Pipe Fill Pressure 32767
PFHP 0 psi 0 psi 0 psi 15804
Level psi
32767
PFHT Pipe Fill TiMe 10 s 10 s 0s 15802
s
AI1T Configuration of AI1 Voltage Voltage 4402
AI1 voltage scaling
UIL1 0V 0V 0V 10 V 4412
parameter of 0%
AI1 voltage scaling
UIH1 10 V 10 V 0V 10 V 4422
parameter of 100%
AI1 current scaling
CRL1 0 mA 0 mA 0 mA 20 mA 4432
parameter of 0%
AI1 current scaling
CRH1 20 mA 20 mA 0 mA 20 mA 4442
parameter of 100%
-
AI1J AI1 Lowest Process 0 0 32767 4502
32767
-
AI1K AI1 Highest Process 0 0 32767 4512
32767
AI2T Configuration of AI2 Current Voltage 4403
AI2 voltage scaling
parameter of 100%
-
AI1J AI1 Lowest Process 0 0 32767 4502
32767
-
AI1K AI1 Highest Process 0 0 32767 4512
32767
AI2T Configuration of AI2 Current Voltage 4403
AI2 voltage scaling
UIL2 0V 0V 0V 10 V 4413
parameter of 0%
AI2 voltage scaling
UIH2 10 V 10 V 0V 10 V 4423
parameter of 100%
AI2 current scaling
CRL2 4 mA 0 mA 0 mA 20 mA 4433
parameter of 0%
AI2 current scaling
CRH2 20 mA 20 mA 0 mA 20 mA 4443
parameter of 100%
-
AI2J AI2 Lowest Process 0 0 32767 4503
32767
-
AI2K AI2 Highest Process 0 0 32767 4513
32767
AI3T Configuration of AI3 Current Current 4404
AI3 voltage scaling
UIL3 0V 0V 0V 10 V 4414
parameter of 0%
AI3 voltage scaling
UIH3 10 V 10 V 0V 10 V 4424
parameter of 100%
AI3 current scaling
CRL3 0 mA 0 mA 0 mA 20 mA 4434
parameter of 0%
AI3 current scaling
CRH3 20 mA 20 mA 0 mA 20 mA 4444
parameter of 100%
-
AI3J AI3 Lowest Process 0 0 32767 4504
32767
-
AI3K AI3 Highest Process 0 0 32767 4514
32767
AI bipolar volts
AI4T Configuration of AI4 Current 4405
selected
AI4 voltage scaling
UIL4 0V 0V 0V 10 V 4415
parameter of 0%
AI4 voltage scaling
UIH4 10 V 10 V 0V 10 V 4425
parameter of 100%
AI4 current scaling
CRL4 0 mA 0 mA 0 mA 20 mA 4435
parameter of 0%
AI4 current scaling
CRH4 20 mA 20 mA 0 mA 20 mA 4445
parameter of 100%
-
AI4J AI4 Lowest Process 0 0 32767 4505
32767
-
AI4K AI4 Highest Process 0 0 32767 4515
32767
AI bipolar volts
AI5T AI5 type Current 4406
selected
AI5 voltage scaling
UIL5 0V 0V 0V 10 V 4416
parameter of 0%
AI5 voltage scaling
UIH5 10 V 10 V 0V 10 V 4426
parameter of 100%
selected
AI5 voltage scaling
UIL5 0V 0V 0V 10 V 4416
parameter of 0%
AI5 voltage scaling
UIH5 10 V 10 V 0V 10 V 4426
parameter of 100%
AI5 current scaling
CRL5 0 mA 0 mA 0 mA 20 mA 4436
parameter of 0%
AI5 current scaling
CRH5 20 mA 20 mA 0 mA 20 mA 4446
parameter of 100%
-
AI5J AI5 Lowest Process 0 0 32767 4506
32767
-
AI5K AI5 Highest Process 0 0 32767 4516
32767
Channel assignment
AIC1 for virtual Analog Input Not configured Not configured 5282
AIV1
AIV1 Lowest -
AV1J 0 0 32767 4522
Process 32767
AIV1 Highest -
AV1K 0 0 32767 4532
Process 32767
FLCM Mode Selection Inactive Inactive 15840
Installation Flow
FS1A Not configured Not configured 15703
Sensor Assignment
-
32767
FLH0 Static compensation 0 psi 0 psi 32767 15844
psi
psi
-
Flow Rate Working 32767
FLQ1 0 GPM 0 GPM 32767 15843
Point GPM
GPM
-
Compensation at Point 32767
FLH1 0 psi 0 psi 32767 15842
1 psi
psi
FLDA Alpha 2 2 0 2 15841
AI1T Configuration of AI1 Voltage Voltage 4402
AI1 voltage scaling
UIL1 0V 0V 0V 10 V 4412
parameter of 0%
AI1 voltage scaling
UIH1 10 V 10 V 0V 10 V 4422
parameter of 100%
AI1 current scaling
CRL1 0 mA 0 mA 0 mA 20 mA 4432
parameter of 0%
AI1 current scaling
CRH1 20 mA 20 mA 0 mA 20 mA 4442
parameter of 100%
-
AI1J AI1 Lowest Process 0 0 32767 4502
32767
-
AI1K AI1 Highest Process 0 0 32767 4512
32767
AI2T Configuration of AI2 Current Voltage 4403
AI2 voltage scaling
UIL2 0V 0V 0V 10 V 4413
parameter of 0%
AI2 voltage scaling
UIH2 10 V 10 V 0V 10 V 4423
parameter of 100%
AI2T Configuration of AI2 Current Voltage 4403
AI2 voltage scaling
UIL2 0V 0V 0V 10 V 4413
parameter of 0%
AI2 voltage scaling
UIH2 10 V 10 V 0V 10 V 4423
parameter of 100%
AI2 current scaling
CRL2 4 mA 0 mA 0 mA 20 mA 4433
parameter of 0%
AI2 current scaling
CRH2 20 mA 20 mA 0 mA 20 mA 4443
parameter of 100%
-
AI2J AI2 Lowest Process 0 0 32767 4503
32767
-
AI2K AI2 Highest Process 0 0 32767 4513
32767
AI3T Configuration of AI3 Current Current 4404
AI3 voltage scaling
UIL3 0V 0V 0V 10 V 4414
parameter of 0%
AI3 voltage scaling
UIH3 10 V 10 V 0V 10 V 4424
parameter of 100%
AI3 current scaling
CRL3 0 mA 0 mA 0 mA 20 mA 4434
parameter of 0%
AI3 current scaling
CRH3 20 mA 20 mA 0 mA 20 mA 4444
parameter of 100%
-
AI3J AI3 Lowest Process 0 0 32767 4504
32767
-
AI3K AI3 Highest Process 0 0 32767 4514
32767
AI bipolar volts
AI4T Configuration of AI4 Current 4405
selected
AI4 voltage scaling
UIL4 0V 0V 0V 10 V 4415
parameter of 0%
AI4 voltage scaling
UIH4 10 V 10 V 0V 10 V 4425
parameter of 100%
AI4 current scaling
CRL4 0 mA 0 mA 0 mA 20 mA 4435
parameter of 0%
AI4 current scaling
CRH4 20 mA 20 mA 0 mA 20 mA 4445
parameter of 100%
-
AI4J AI4 Lowest Process 0 0 32767 4505
32767
-
AI4K AI4 Highest Process 0 0 32767 4515
32767
AI bipolar volts
AI5T AI5 type Current 4406
selected
AI5 voltage scaling
UIL5 0V 0V 0V 10 V 4416
parameter of 0%
AI5 voltage scaling
UIH5 10 V 10 V 0V 10 V 4426
parameter of 100%
AI5 current scaling
CRL5 0 mA 0 mA 0 mA 20 mA 4436
parameter of 0%
AI5 current scaling
CRH5 20 mA 20 mA 0 mA 20 mA 4446
parameter of 100%
-
AI5J AI5 Lowest Process 0 0 32767 4506
parameter of 100%
AI5 current scaling
CRL5 0 mA 0 mA 0 mA 20 mA 4436
parameter of 0%
AI5 current scaling
CRH5 20 mA 20 mA 0 mA 20 mA 4446
parameter of 100%
-
AI5J AI5 Lowest Process 0 0 32767 4506
32767
-
AI5K AI5 Highest Process 0 0 32767 4516
32767
DI5 PulseInput Low 30000
PIL5 0 Hz 0 Hz 0 Hz 13320
Frequency Hz
PulseInput DI5 High
PIH5 30 kHz 30 kHz 0 kHz 30 kHz 13322
Frequency
-
PI5J DI5 Min process 0 0 32767 13332
32767
-
PI5K DI5 Max process 0 0 32767 13334
32767
DI6 PulseInput Low 30000
PIL6 0 Hz 0 Hz 0 Hz 13340
Frequency Hz
DI6 PulseInput High
PIH6 30 kHz 30 kHz 0 kHz 30 kHz 13342
Frequency
-
PI6J DI6 Min process 0 0 32767 13352
32767
-
PI6K DI6 Max process 0 0 32767 13354
32767
Channel assignment
AIC1 for virtual Analog Input Not configured Not configured 5282
AIV1
AIV1 Lowest -
AV1J 0 0 32767 4522
Process 32767
AIV1 Highest -
AV1K 0 0 32767 4532
Process 32767
Select the Jockey
JP Not assigned Not assigned 15830
Pump
Pressure threshold to
JPRP 0 psi 0 psi 0 psi 0 psi 15831
start the Jockey Pump
Delay to start the
JPRD 0s 0s 0s 3600 s 15832
Jockey Pump
Pressure threshold to 32767
JPSP 0 psi 0 psi 0 psi 15833
stop the Jockey Pump psi
Delay to wake up the
JPWD system when pressure No No 0s 3600 s 15835
feedback stays low
Pump reference speed
JPRS when VSP is selected 58 Hz 60 Hz 35 Hz 60 Hz 15834
as Jockey Pump
Priming Pump
PPOA Not assigned Not assigned 15820
Assignment
Primed Switch
PPWA Not assigned Not assigned 15823
Assignment
Primed Inlet Pressure 32767
PPIL No No 0 psi 15824
Level psi
as Jockey Pump
Priming Pump
PPOA Not assigned Not assigned 15820
Assignment
Primed Switch
PPWA Not assigned Not assigned 15823
Assignment
Primed Inlet Pressure 32767
PPIL No No 0 psi 15824
Level psi
Inlet Pressure Sensor
PS1A Not configured Not configured 15701
Assignment
Primed Condition
PPFD 0s 0s 0s 60 s 15825
Delay
Delay before starting
PPSD 30 s 30 s 0s 3600 s 15821
the lead pump
AI1T Configuration of AI1 Voltage Voltage 4402
AI1 voltage scaling
UIL1 0V 0V 0V 10 V 4412
parameter of 0%
AI1 voltage scaling
UIH1 10 V 10 V 0V 10 V 4422
parameter of 100%
AI1 current scaling
CRL1 0 mA 0 mA 0 mA 20 mA 4432
parameter of 0%
AI1 current scaling
CRH1 20 mA 20 mA 0 mA 20 mA 4442
parameter of 100%
-
AI1J AI1 Lowest Process 0 0 32767 4502
32767
-
AI1K AI1 Highest Process 0 0 32767 4512
32767
AI2T Configuration of AI2 Current Voltage 4403
AI2 voltage scaling
UIL2 0V 0V 0V 10 V 4413
parameter of 0%
AI2 voltage scaling
UIH2 10 V 10 V 0V 10 V 4423
parameter of 100%
AI2 current scaling
CRL2 4 mA 0 mA 0 mA 20 mA 4433
parameter of 0%
AI2 current scaling
CRH2 20 mA 20 mA 0 mA 20 mA 4443
parameter of 100%
-
AI2J AI2 Lowest Process 0 0 32767 4503
32767
-
AI2K AI2 Highest Process 0 0 32767 4513
32767
AI3T Configuration of AI3 Current Current 4404
AI3 voltage scaling
UIL3 0V 0V 0V 10 V 4414
parameter of 0%
AI3 voltage scaling
UIH3 10 V 10 V 0V 10 V 4424
parameter of 100%
AI3 current scaling
CRL3 0 mA 0 mA 0 mA 20 mA 4434
parameter of 0%
AI3 current scaling
CRH3 20 mA 20 mA 0 mA 20 mA 4444
parameter of 100%
-
AI3J AI3 Lowest Process 0 0 32767 4504
32767
-
AI3K AI3 Highest Process 0 0 32767 4514
parameter of 0%
AI3 current scaling
CRH3 20 mA 20 mA 0 mA 20 mA 4444
parameter of 100%
-
AI3J AI3 Lowest Process 0 0 32767 4504
32767
-
AI3K AI3 Highest Process 0 0 32767 4514
32767
AI bipolar volts
AI4T Configuration of AI4 Current 4405
selected
AI4 voltage scaling
UIL4 0V 0V 0V 10 V 4415
parameter of 0%
AI4 voltage scaling
UIH4 10 V 10 V 0V 10 V 4425
parameter of 100%
AI4 current scaling
CRL4 0 mA 0 mA 0 mA 20 mA 4435
parameter of 0%
AI4 current scaling
CRH4 20 mA 20 mA 0 mA 20 mA 4445
parameter of 100%
-
AI4J AI4 Lowest Process 0 0 32767 4505
32767
-
AI4K AI4 Highest Process 0 0 32767 4515
32767
AI bipolar volts
AI5T AI5 type Current 4406
selected
AI5 voltage scaling
UIL5 0V 0V 0V 10 V 4416
parameter of 0%
AI5 voltage scaling
UIH5 10 V 10 V 0V 10 V 4426
parameter of 100%
AI5 current scaling
CRL5 0 mA 0 mA 0 mA 20 mA 4436
parameter of 0%
AI5 current scaling
CRH5 20 mA 20 mA 0 mA 20 mA 4446
parameter of 100%
-
AI5J AI5 Lowest Process 0 0 32767 4506
32767
-
AI5K AI5 Highest Process 0 0 32767 4516
32767
Channel assignment
AIC1 for virtual Analog Input Not configured Not configured 5282
AIV1
AIV1 Lowest -
AV1J 0 0 32767 4522
Process 32767
AIV1 Highest -
AV1K 0 0 32767 4532
Process 32767
FLM Flow limitation Mode No No 14515
Installation Flow
FS1A Not configured Not configured 15703
Sensor Assignment
Flow Limit Threshold 0 32767
CHT 0 GPM 0 GPM 14512
active GPM GPM
Flow Limit Thd 0 32767
RCHT 0 GPM 0 GPM 14513
disable GPM GPM
Flow limit
DFL 5s 5s 0.1 s 999.9 s 14514
Deceleration
active GPM GPM
Flow Limit Thd 0 32767
RCHT 0 GPM 0 GPM 14513
disable GPM GPM
Flow limit
DFL 5s 5s 0.1 s 999.9 s 14514
Deceleration
AI1T Configuration of AI1 Voltage Voltage 4402
AI1 voltage scaling
UIL1 0V 0V 0V 10 V 4412
parameter of 0%
AI1 voltage scaling
UIH1 10 V 10 V 0V 10 V 4422
parameter of 100%
AI1 current scaling
CRL1 0 mA 0 mA 0 mA 20 mA 4432
parameter of 0%
AI1 current scaling
CRH1 20 mA 20 mA 0 mA 20 mA 4442
parameter of 100%
-
AI1J AI1 Lowest Process 0 0 32767 4502
32767
-
AI1K AI1 Highest Process 0 0 32767 4512
32767
AI2T Configuration of AI2 Current Voltage 4403
AI2 voltage scaling
UIL2 0V 0V 0V 10 V 4413
parameter of 0%
AI2 voltage scaling
UIH2 10 V 10 V 0V 10 V 4423
parameter of 100%
AI2 current scaling
CRL2 4 mA 0 mA 0 mA 20 mA 4433
parameter of 0%
AI2 current scaling
CRH2 20 mA 20 mA 0 mA 20 mA 4443
parameter of 100%
-
AI2J AI2 Lowest Process 0 0 32767 4503
32767
-
AI2K AI2 Highest Process 0 0 32767 4513
32767
AI3T Configuration of AI3 Current Current 4404
AI3 voltage scaling
UIL3 0V 0V 0V 10 V 4414
parameter of 0%
AI3 voltage scaling
UIH3 10 V 10 V 0V 10 V 4424
parameter of 100%
AI3 current scaling
CRL3 0 mA 0 mA 0 mA 20 mA 4434
parameter of 0%
AI3 current scaling
CRH3 20 mA 20 mA 0 mA 20 mA 4444
parameter of 100%
-
AI3J AI3 Lowest Process 0 0 32767 4504
32767
-
AI3K AI3 Highest Process 0 0 32767 4514
32767
AI bipolar volts
AI4T Configuration of AI4 Current 4405
selected
AI4 voltage scaling
UIL4 0V 0V 0V 10 V 4415
parameter of 0%
AI4 voltage scaling
UIH4 10 V 10 V 0V 10 V 4425
parameter of 100%
AI4 current scaling
CRL4 0 mA 0 mA 0 mA 20 mA 4435
selected
AI4 voltage scaling
UIL4 0V 0V 0V 10 V 4415
parameter of 0%
AI4 voltage scaling
UIH4 10 V 10 V 0V 10 V 4425
parameter of 100%
AI4 current scaling
CRL4 0 mA 0 mA 0 mA 20 mA 4435
parameter of 0%
AI4 current scaling
CRH4 20 mA 20 mA 0 mA 20 mA 4445
parameter of 100%
-
AI4J AI4 Lowest Process 0 0 32767 4505
32767
-
AI4K AI4 Highest Process 0 0 32767 4515
32767
AI bipolar volts
AI5T AI5 type Current 4406
selected
AI5 voltage scaling
UIL5 0V 0V 0V 10 V 4416
parameter of 0%
AI5 voltage scaling
UIH5 10 V 10 V 0V 10 V 4426
parameter of 100%
AI5 current scaling
CRL5 0 mA 0 mA 0 mA 20 mA 4436
parameter of 0%
AI5 current scaling
CRH5 20 mA 20 mA 0 mA 20 mA 4446
parameter of 100%
-
AI5J AI5 Lowest Process 0 0 32767 4506
32767
-
AI5K AI5 Highest Process 0 0 32767 4516
32767
DI5 PulseInput Low 30000
PIL5 0 Hz 0 Hz 0 Hz 13320
Frequency Hz
PulseInput DI5 High
PIH5 30 kHz 30 kHz 0 kHz 30 kHz 13322
Frequency
-
PI5J DI5 Min process 0 0 32767 13332
32767
-
PI5K DI5 Max process 0 0 32767 13334
32767
DI6 PulseInput Low 30000
PIL6 0 Hz 0 Hz 0 Hz 13340
Frequency Hz
DI6 PulseInput High
PIH6 30 kHz 30 kHz 0 kHz 30 kHz 13342
Frequency
-
PI6J DI6 Min process 0 0 32767 13352
32767
-
PI6K DI6 Max process 0 0 32767 13354
32767
Channel assignment
AIC1 for virtual Analog Input Not configured Not configured 5282
AIV1
AIV1 Lowest -
AV1J 0 0 32767 4522
Process 32767
AIV1 Highest -
AV1K 0 0 32767 4532
Process 32767
AIV1
AIV1 Lowest -
AV1J 0 0 32767 4522
Process 32767
AIV1 Highest -
AV1K 0 0 32767 4532
Process 32767

Pump Monitoring

Min Max Logical


Code Long Label Current Value Default Value
Value Value address
Pump Cycle Pump Cycle
Pump cycle monitoring
PCPM monitoring monitoring 15900
mode
disabled disabled
Pump cycle maximum
PCPN 6 6 1 99 15901
allowed starts
3600
PCPT Pump cycle timeframe 60 min 60 min 0 min 15902
min
Response to Pump
PCPB Ramp stop Ramp stop 15903
cycle error
LFF Fall back speed 0 Hz 0 Hz 0 Hz 500 Hz 7080
External Anti-Jam
JETC Not assigned Not assigned 15920
trigger
Automatic Anti-Jam
JATC No No 15921
trigger
Inactive time before
JTCT 24 h 24 h 0h 9999 h 15922
triggering Anti-Jam
JTCL Anti-Jam torque level 110 % 110 % 10 % 150 % 15923
Delay before triggering
JTCD Anti-Jam in torque 10 s 10 s 0s 3600 s 15924
mode
Anti-Jam Forward
JACC 3s 3s 0s 300 s 15927
Acceleration
Anti-Jam Forward
JDEC 3s 3s 0s 300 s 15925
Deceleration
Anti-Jam Reverse
JACR 3s 3s 0s 300 s 15928
Acceleration
Anti-Jam Reverse
JDER 3s 3s 0s 300 s 15926
Deceleration
Anti-Jam Forward
JFDS 58 Hz 0 Hz 35 Hz 60 Hz 15931
Speed
Anti-Jam Reverse
JRVS 58 Hz 0 Hz 35 Hz 60 Hz 15932
Speed
Anti-Jam Forward
JFDT 1s 1s 0s 300 s 15929
Time
JRVT Anti-Jam Reverse Time 1s 1s 0s 300 s 15930
Anti-Jam stop time
JZST between forward and 0s 0s 0s 300 s 15933
reverse
JNBC Anti-Jam cycle number 10 10 1 100 15934
Maximum allowed
Anti-Jam stop time
JZST between forward and 0s 0s 0s 300 s 15933
reverse
JNBC Anti-Jam cycle number 10 10 1 100 15934
Maximum allowed
JAMN consecutive Anti-Jam 2 2 1 99 15936
sequences
Time interval to define
JAMT two Anti-Jam sequences 60 s 60 s 0s 3600 s 15937
as consecutive
Response to Anti-Jam Freewheel Freewheel
JAMB 15938
error stop stop
DRYM Dry Run Mode No No 15950
DRYW Dry Run Switch Select Not assigned Not assigned 15951
-
Motor mechanical 3276.7
OPRW 0 HP 0 HP 3276.7 3292
power estimation HP
HP
NFLP No Flow Low Power 0 HP 0 HP 0 HP 100 HP 15961
NFLS No Flow Low Speed 0 Hz 0 Hz 0 Hz 60 Hz 15960
NFHP No Flow High Power 0 HP 0 HP 0 HP 100 HP 15963
NFHS No Flow High Speed 0 Hz 0 Hz 0 Hz 60 Hz 15962
DRYX Dry Run Factor 90 % 90 % 0% 100 % 15954
Dry Run error time
DRYD 5s 5s 0s 3600 s 15952
delay
Dry Run restart time
DRYR 60 s 60 s 10 s 3600 s 15953
delay
Pump Low Flow
PLFM No No 15970
monitoring mode
Pump Low Flow digital
PLFW Not assigned Not assigned 15971
input assignment
Pump Flow Sensor Not Not
FS2A 15704
Assignment configured configured
Pump Low Flow 0 32767
PLFL 0 GPM 0 GPM 15972
minimum level GPM GPM
-
Motor mechanical 3276.7
OPRW 0 HP 0 HP 3276.7 3292
power estimation HP
HP
NFLS No Flow Low Speed 0 Hz 0 Hz 0 Hz 60 Hz 15960
NFHS No Flow High Speed 0 Hz 0 Hz 0 Hz 60 Hz 15962
NFLP No Flow Low Power 0 HP 0 HP 0 HP 100 HP 15961
NFHP No Flow High Power 0 HP 0 HP 0 HP 100 HP 15963
Pump Low Flow power
PLFX 110 % 110 % 100 % 500 % 15973
factor
PLFA Pump Low Flow 10 s 10 s 0s 3600 s 15974
Pump Low Flow error
PLFD 10 s 10 s 0s 3600 s 15975
delay
Response to pump Low Freewheel Freewheel
PLFB 15976
Flow error stop stop
LFF Fall back speed 0 Hz 0 Hz 0 Hz 500 Hz 7080
Pump Low Flow restart
PLFR 0s 0s 0s 3600 s 15977
delay
Response to pump Low Freewheel Freewheel
PLFB 15976
Flow error stop stop
LFF Fall back speed 0 Hz 0 Hz 0 Hz 500 Hz 7080
Pump Low Flow restart
PLFR 0s 0s 0s 3600 s 15977
delay
AI1T Configuration of AI1 Voltage Voltage 4402
AI1 voltage scaling
UIL1 0V 0V 0V 10 V 4412
parameter of 0%
AI1 voltage scaling
UIH1 10 V 10 V 0V 10 V 4422
parameter of 100%
AI1 current scaling
CRL1 0 mA 0 mA 0 mA 20 mA 4432
parameter of 0%
AI1 current scaling
CRH1 20 mA 20 mA 0 mA 20 mA 4442
parameter of 100%
-32767
AI1J AI1 Lowest Process 0 0 32767 4502

-32767
AI1K AI1 Highest Process 0 0 32767 4512

AI2T Configuration of AI2 Current Voltage 4403


AI2 voltage scaling
UIL2 0V 0V 0V 10 V 4413
parameter of 0%
AI2 voltage scaling
UIH2 10 V 10 V 0V 10 V 4423
parameter of 100%
AI2 current scaling
CRL2 4 mA 0 mA 0 mA 20 mA 4433
parameter of 0%
AI2 current scaling
CRH2 20 mA 20 mA 0 mA 20 mA 4443
parameter of 100%
-32767
AI2J AI2 Lowest Process 0 0 32767 4503

-32767
AI2K AI2 Highest Process 0 0 32767 4513

AI3T Configuration of AI3 Current Current 4404


AI3 voltage scaling
UIL3 0V 0V 0V 10 V 4414
parameter of 0%
AI3 voltage scaling
UIH3 10 V 10 V 0V 10 V 4424
parameter of 100%
AI3 current scaling
CRL3 0 mA 0 mA 0 mA 20 mA 4434
parameter of 0%
AI3 current scaling
CRH3 20 mA 20 mA 0 mA 20 mA 4444
parameter of 100%
-32767
AI3J AI3 Lowest Process 0 0 32767 4504

-32767
AI3K AI3 Highest Process 0 0 32767 4514

AI bipolar
AI4T Configuration of AI4 Current 4405
volts selected
AI4 voltage scaling
UIL4 0V 0V 0V 10 V 4415
parameter of 0%
AI4 voltage scaling
UIH4 10 V 10 V 0V 10 V 4425
parameter of 100%
AI bipolar
AI4T Configuration of AI4 Current 4405
volts selected
AI4 voltage scaling
UIL4 0V 0V 0V 10 V 4415
parameter of 0%
AI4 voltage scaling
UIH4 10 V 10 V 0V 10 V 4425
parameter of 100%
AI4 current scaling
CRL4 0 mA 0 mA 0 mA 20 mA 4435
parameter of 0%
AI4 current scaling
CRH4 20 mA 20 mA 0 mA 20 mA 4445
parameter of 100%
-32767
AI4J AI4 Lowest Process 0 0 32767 4505

-32767
AI4K AI4 Highest Process 0 0 32767 4515

AI bipolar
AI5T AI5 type Current 4406
volts selected
AI5 voltage scaling
UIL5 0V 0V 0V 10 V 4416
parameter of 0%
AI5 voltage scaling
UIH5 10 V 10 V 0V 10 V 4426
parameter of 100%
AI5 current scaling
CRL5 0 mA 0 mA 0 mA 20 mA 4436
parameter of 0%
AI5 current scaling
CRH5 20 mA 20 mA 0 mA 20 mA 4446
parameter of 100%
-32767
AI5J AI5 Lowest Process 0 0 32767 4506

-32767
AI5K AI5 Highest Process 0 0 32767 4516

DI5 PulseInput Low 30000


PIL5 0 Hz 0 Hz 0 Hz 13320
Frequency Hz
PulseInput DI5 High
PIH5 30 kHz 30 kHz 0 kHz 30 kHz 13322
Frequency
-32767
PI5J DI5 Min process 0 0 32767 13332

-32767
PI5K DI5 Max process 0 0 32767 13334

DI6 PulseInput Low 30000


PIL6 0 Hz 0 Hz 0 Hz 13340
Frequency Hz
DI6 PulseInput High
PIH6 30 kHz 30 kHz 0 kHz 30 kHz 13342
Frequency
-32767
PI6J DI6 Min process 0 0 32767 13352

-32767
PI6K DI6 Max process 0 0 32767 13354

Channel assignment for


Not Not
AIC1 virtual Analog Input 5282
configured configured
AIV1
-32767
AV1J AIV1 Lowest Process 0 0 32767 4522

-32767
AV1K AIV1 Highest Process 0 0 32767 4532
Channel assignment for
Not Not
AIC1 virtual Analog Input 5282
configured configured
AIV1
-32767
AV1J AIV1 Lowest Process 0 0 32767 4522

-32767
AV1K AIV1 Highest Process 0 0 32767 4532

Activation of the thermal


TH2S No No 13210
monitoring on AI2
AI2T Configuration of AI2 Current Voltage 4403
Response to thermal
TH2B Ramp stop Ramp stop 13240
error for AI2
Thermal error level for
TH2F 230 °F 230 °F 5 °F 392 °F 13230
AI2
Thermal warning level
TH2A 194 °F 194 °F 5 °F 392 °F 13220
for AI2
TH2V AI2 thermal value 0 °F 0 °F 5 °F 392 °F 13250
Activation of the thermal
TH3S No No 13211
monitoring on AI3
AI3T Configuration of AI3 Current Current 4404
Response to thermal
TH3B Ramp stop Ramp stop 13241
error for AI3
Thermal error level for
TH3F 230 °F 230 °F 5 °F 392 °F 13231
AI3
Thermal warning level
TH3A 194 °F 194 °F 5 °F 392 °F 13221
for AI3
TH3V AI3 thermal value 0 °F 0 °F 5 °F 392 °F 13251
Activation of the thermal
TH4S No No 13212
monitoring on AI4
AI bipolar
AI4T Configuration of AI4 Current 4405
volts selected
Response to thermal
TH4B Ramp stop Ramp stop 13242
error for AI4
Thermal error level for
TH4F 230 °F 230 °F 5 °F 392 °F 13232
AI4
Thermal warning level
TH4A 194 °F 194 °F 5 °F 392 °F 13222
for AI4
TH4V AI4 thermal value 0 °F 0 °F 5 °F 392 °F 13252
Activation of the thermal
TH5S No No 13213
monitoring on AI5
AI bipolar
AI5T AI5 type Current 4406
volts selected
Response to thermal
TH5B Ramp stop Ramp stop 13243
error for AI5
Thermal error level for
TH5F 230 °F 230 °F 5 °F 392 °F 13233
AI5
Thermal warning level
TH5A 194 °F 194 °F 5 °F 392 °F 13223
for AI5
TH5V AI5 thermal value 0 °F 0 °F 5 °F 392 °F 13253
LFF Fall back speed 0 Hz 0 Hz 0 Hz 500 Hz 7080
Inlet Pressure
AI5
Thermal warning level
TH5A 194 °F 194 °F 5 °F 392 °F 13223
for AI5
TH5V AI5 thermal value 0 °F 0 °F 5 °F 392 °F 13253
LFF Fall back speed 0 Hz 0 Hz 0 Hz 500 Hz 7080
Inlet Pressure
IPPM NO NO 15910
monitoring Mode
Inlet Pressure Sensor Not Not
PS1A 15701
Assignment configured configured
Inlet Pressure high 32767
IPPH 0 psi 0 psi 0 psi 15911
threshold psi
Inlet Pressure low 32767
IPPL 0 psi 0 psi 0 psi 15912
threshold psi
Inlet Pressure maximum 32767
IPPC 0 psi 0 psi 0 psi 15913
compensated pressure psi
Response to Inlet
IPPB Ramp stop Ramp stop 15914
pressure error
LFF Fall back speed 0 Hz 0 Hz 0 Hz 500 Hz 7080
AI1T Configuration of AI1 Voltage Voltage 4402
AI1 voltage scaling
UIL1 0V 0V 0V 10 V 4412
parameter of 0%
AI1 voltage scaling
UIH1 10 V 10 V 0V 10 V 4422
parameter of 100%
AI1 current scaling
CRL1 0 mA 0 mA 0 mA 20 mA 4432
parameter of 0%
AI1 current scaling
CRH1 20 mA 20 mA 0 mA 20 mA 4442
parameter of 100%
-32767
AI1J AI1 Lowest Process 0 0 32767 4502

-32767
AI1K AI1 Highest Process 0 0 32767 4512

AI2T Configuration of AI2 Current Voltage 4403


AI2 voltage scaling
UIL2 0V 0V 0V 10 V 4413
parameter of 0%
AI2 voltage scaling
UIH2 10 V 10 V 0V 10 V 4423
parameter of 100%
AI2 current scaling
CRL2 4 mA 0 mA 0 mA 20 mA 4433
parameter of 0%
AI2 current scaling
CRH2 20 mA 20 mA 0 mA 20 mA 4443
parameter of 100%
-32767
AI2J AI2 Lowest Process 0 0 32767 4503

-32767
AI2K AI2 Highest Process 0 0 32767 4513

AI3T Configuration of AI3 Current Current 4404


AI3 voltage scaling
UIL3 0V 0V 0V 10 V 4414
parameter of 0%
AI3 voltage scaling
UIH3 10 V 10 V 0V 10 V 4424
parameter of 100%
AI3 current scaling
CRL3 0 mA 0 mA 0 mA 20 mA 4434
parameter of 0%
AI3T Configuration of AI3 Current Current 4404
AI3 voltage scaling
UIL3 0V 0V 0V 10 V 4414
parameter of 0%
AI3 voltage scaling
UIH3 10 V 10 V 0V 10 V 4424
parameter of 100%
AI3 current scaling
CRL3 0 mA 0 mA 0 mA 20 mA 4434
parameter of 0%
AI3 current scaling
CRH3 20 mA 20 mA 0 mA 20 mA 4444
parameter of 100%
-32767
AI3J AI3 Lowest Process 0 0 32767 4504

-32767
AI3K AI3 Highest Process 0 0 32767 4514

AI bipolar
AI4T Configuration of AI4 Current 4405
volts selected
AI4 voltage scaling
UIL4 0V 0V 0V 10 V 4415
parameter of 0%
AI4 voltage scaling
UIH4 10 V 10 V 0V 10 V 4425
parameter of 100%
AI4 current scaling
CRL4 0 mA 0 mA 0 mA 20 mA 4435
parameter of 0%
AI4 current scaling
CRH4 20 mA 20 mA 0 mA 20 mA 4445
parameter of 100%
-32767
AI4J AI4 Lowest Process 0 0 32767 4505

-32767
AI4K AI4 Highest Process 0 0 32767 4515

AI bipolar
AI5T AI5 type Current 4406
volts selected
AI5 voltage scaling
UIL5 0V 0V 0V 10 V 4416
parameter of 0%
AI5 voltage scaling
UIH5 10 V 10 V 0V 10 V 4426
parameter of 100%
AI5 current scaling
CRL5 0 mA 0 mA 0 mA 20 mA 4436
parameter of 0%
AI5 current scaling
CRH5 20 mA 20 mA 0 mA 20 mA 4446
parameter of 100%
-32767
AI5J AI5 Lowest Process 0 0 32767 4506

-32767
AI5K AI5 Highest Process 0 0 32767 4516

Channel assignment for


Not Not
AIC1 virtual Analog Input 5282
configured configured
AIV1
-32767
AV1J AIV1 Lowest Process 0 0 32767 4522

-32767
AV1K AIV1 Highest Process 0 0 32767 4532

Outlet Pressure
OPPM No No 15850
monitoring mode
Outlet Pressure digital
OPPW Not assigned Not assigned 15851
input assignment
-32767
AV1K AIV1 Highest Process 0 0 32767 4532

Outlet Pressure
OPPM No No 15850
monitoring mode
Outlet Pressure digital
OPPW Not assigned Not assigned 15851
input assignment
Outlet Pressure Sensor Not Not
PS2A 15702
Assignment configured configured
Outlet Pressure 32767
OPPL 0 psi 0 psi 0 psi 15852
minimum level psi
Outlet Pressure 32767
OPPH 0 psi 0 psi 0 psi 15853
maximum level psi
Outlet Pressure error
OPPD 0s 0s 0s 3600 s 15854
delay
Response to Outlet
OPPB Ramp stop Ramp stop 15855
Pressure error
LFF Fall back speed 0 Hz 0 Hz 0 Hz 500 Hz 7080
AI1T Configuration of AI1 Voltage Voltage 4402
AI1 voltage scaling
UIL1 0V 0V 0V 10 V 4412
parameter of 0%
AI1 voltage scaling
UIH1 10 V 10 V 0V 10 V 4422
parameter of 100%
AI1 current scaling
CRL1 0 mA 0 mA 0 mA 20 mA 4432
parameter of 0%
AI1 current scaling
CRH1 20 mA 20 mA 0 mA 20 mA 4442
parameter of 100%
-32767
AI1J AI1 Lowest Process 0 0 32767 4502

-32767
AI1K AI1 Highest Process 0 0 32767 4512

AI2T Configuration of AI2 Current Voltage 4403


AI2 voltage scaling
UIL2 0V 0V 0V 10 V 4413
parameter of 0%
AI2 voltage scaling
UIH2 10 V 10 V 0V 10 V 4423
parameter of 100%
AI2 current scaling
CRL2 4 mA 0 mA 0 mA 20 mA 4433
parameter of 0%
AI2 current scaling
CRH2 20 mA 20 mA 0 mA 20 mA 4443
parameter of 100%
-32767
AI2J AI2 Lowest Process 0 0 32767 4503

-32767
AI2K AI2 Highest Process 0 0 32767 4513

AI3T Configuration of AI3 Current Current 4404


AI3 voltage scaling
UIL3 0V 0V 0V 10 V 4414
parameter of 0%
AI3 voltage scaling
UIH3 10 V 10 V 0V 10 V 4424
parameter of 100%
AI3 current scaling
CRL3 0 mA 0 mA 0 mA 20 mA 4434
parameter of 0%
AI3T Configuration of AI3 Current Current 4404
AI3 voltage scaling
UIL3 0V 0V 0V 10 V 4414
parameter of 0%
AI3 voltage scaling
UIH3 10 V 10 V 0V 10 V 4424
parameter of 100%
AI3 current scaling
CRL3 0 mA 0 mA 0 mA 20 mA 4434
parameter of 0%
AI3 current scaling
CRH3 20 mA 20 mA 0 mA 20 mA 4444
parameter of 100%
-32767
AI3J AI3 Lowest Process 0 0 32767 4504

-32767
AI3K AI3 Highest Process 0 0 32767 4514

AI bipolar
AI4T Configuration of AI4 Current 4405
volts selected
AI4 voltage scaling
UIL4 0V 0V 0V 10 V 4415
parameter of 0%
AI4 voltage scaling
UIH4 10 V 10 V 0V 10 V 4425
parameter of 100%
AI4 current scaling
CRL4 0 mA 0 mA 0 mA 20 mA 4435
parameter of 0%
AI4 current scaling
CRH4 20 mA 20 mA 0 mA 20 mA 4445
parameter of 100%
-32767
AI4J AI4 Lowest Process 0 0 32767 4505

-32767
AI4K AI4 Highest Process 0 0 32767 4515

AI bipolar
AI5T AI5 type Current 4406
volts selected
AI5 voltage scaling
UIL5 0V 0V 0V 10 V 4416
parameter of 0%
AI5 voltage scaling
UIH5 10 V 10 V 0V 10 V 4426
parameter of 100%
AI5 current scaling
CRL5 0 mA 0 mA 0 mA 20 mA 4436
parameter of 0%
AI5 current scaling
CRH5 20 mA 20 mA 0 mA 20 mA 4446
parameter of 100%
-32767
AI5J AI5 Lowest Process 0 0 32767 4506

-32767
AI5K AI5 Highest Process 0 0 32767 4516

Channel assignment for


Not Not
AIC1 virtual Analog Input 5282
configured configured
AIV1
-32767
AV1J AIV1 Lowest Process 0 0 32767 4522

-32767
AV1K AIV1 Highest Process 0 0 32767 4532

High Flow detection


HFPM No No 15860
activation
Installation Flow Sensor Not Not
FS1A 15703
Assignment configured configured
-32767
AV1K AIV1 Highest Process 0 0 32767 4532

High Flow detection


HFPM No No 15860
activation
Installation Flow Sensor Not Not
FS1A 15703
Assignment configured configured
0 32767
HFPL High Flow Max Level 0 GPM 0 GPM 15861
GPM GPM
HFPD High Flow Delay 10 s 10 s 0s 3600 s 15862
Response to High Flow
HFPB Ramp stop Ramp stop 15863
error
LFF Fall back speed 0 Hz 0 Hz 0 Hz 500 Hz 7080
AI1T Configuration of AI1 Voltage Voltage 4402
AI1 voltage scaling
UIL1 0V 0V 0V 10 V 4412
parameter of 0%
AI1 voltage scaling
UIH1 10 V 10 V 0V 10 V 4422
parameter of 100%
AI1 current scaling
CRL1 0 mA 0 mA 0 mA 20 mA 4432
parameter of 0%
AI1 current scaling
CRH1 20 mA 20 mA 0 mA 20 mA 4442
parameter of 100%
-32767
AI1J AI1 Lowest Process 0 0 32767 4502

-32767
AI1K AI1 Highest Process 0 0 32767 4512

AI2T Configuration of AI2 Current Voltage 4403


AI2 voltage scaling
UIL2 0V 0V 0V 10 V 4413
parameter of 0%
AI2 voltage scaling
UIH2 10 V 10 V 0V 10 V 4423
parameter of 100%
AI2 current scaling
CRL2 4 mA 0 mA 0 mA 20 mA 4433
parameter of 0%
AI2 current scaling
CRH2 20 mA 20 mA 0 mA 20 mA 4443
parameter of 100%
-32767
AI2J AI2 Lowest Process 0 0 32767 4503

-32767
AI2K AI2 Highest Process 0 0 32767 4513

AI3T Configuration of AI3 Current Current 4404


AI3 voltage scaling
UIL3 0V 0V 0V 10 V 4414
parameter of 0%
AI3 voltage scaling
UIH3 10 V 10 V 0V 10 V 4424
parameter of 100%
AI3 current scaling
CRL3 0 mA 0 mA 0 mA 20 mA 4434
parameter of 0%
AI3 current scaling
CRH3 20 mA 20 mA 0 mA 20 mA 4444
parameter of 100%
-32767
AI3J AI3 Lowest Process 0 0 32767 4504

-32767
parameter of 0%
AI3 current scaling
CRH3 20 mA 20 mA 0 mA 20 mA 4444
parameter of 100%
-32767
AI3J AI3 Lowest Process 0 0 32767 4504

-32767
AI3K AI3 Highest Process 0 0 32767 4514

AI bipolar
AI4T Configuration of AI4 Current 4405
volts selected
AI4 voltage scaling
UIL4 0V 0V 0V 10 V 4415
parameter of 0%
AI4 voltage scaling
UIH4 10 V 10 V 0V 10 V 4425
parameter of 100%
AI4 current scaling
CRL4 0 mA 0 mA 0 mA 20 mA 4435
parameter of 0%
AI4 current scaling
CRH4 20 mA 20 mA 0 mA 20 mA 4445
parameter of 100%
-32767
AI4J AI4 Lowest Process 0 0 32767 4505

-32767
AI4K AI4 Highest Process 0 0 32767 4515

AI bipolar
AI5T AI5 type Current 4406
volts selected
AI5 voltage scaling
UIL5 0V 0V 0V 10 V 4416
parameter of 0%
AI5 voltage scaling
UIH5 10 V 10 V 0V 10 V 4426
parameter of 100%
AI5 current scaling
CRL5 0 mA 0 mA 0 mA 20 mA 4436
parameter of 0%
AI5 current scaling
CRH5 20 mA 20 mA 0 mA 20 mA 4446
parameter of 100%
-32767
AI5J AI5 Lowest Process 0 0 32767 4506

-32767
AI5K AI5 Highest Process 0 0 32767 4516

DI5 PulseInput Low 30000


PIL5 0 Hz 0 Hz 0 Hz 13320
Frequency Hz
PulseInput DI5 High
PIH5 30 kHz 30 kHz 0 kHz 30 kHz 13322
Frequency
-32767
PI5J DI5 Min process 0 0 32767 13332

-32767
PI5K DI5 Max process 0 0 32767 13334

DI6 PulseInput Low 30000


PIL6 0 Hz 0 Hz 0 Hz 13340
Frequency Hz
DI6 PulseInput High
PIH6 30 kHz 30 kHz 0 kHz 30 kHz 13342
Frequency
-32767
PI6J DI6 Min process 0 0 32767 13352

-32767
PI6K DI6 Max process 0 0 32767 13354
Frequency
-32767
PI6J DI6 Min process 0 0 32767 13352

-32767
PI6K DI6 Max process 0 0 32767 13354

Channel assignment for


Not Not
AIC1 virtual Analog Input 5282
configured configured
AIV1
-32767
AV1J AIV1 Lowest Process 0 0 32767 4522

-32767
AV1K AIV1 Highest Process 0 0 32767 4532

© Schneider Electric 2008 - 2016