Вы находитесь на странице: 1из 12

This article was published in ASHRAE Journal, June 2012. Copyright 2012 ASHRAE. Posted at www.ashrae.org.

This article may not be copied


and/or distributed electronically or in paper form without permission of ASHRAE. For more information about ASHRAE Journal, visit www.
ashrae.org.

Basics of
Atrium Smoke Control
By John H. Klote, Ph.D., P.E., Fellow/Life Member ASHRAE Design Scenarios

S
A design scenario is the outline of
moke is recognized as the major killer in building fires. Smoke control events and conditions that are critical
to determining the outcome of alter-
in large-volume spaces is based on a long history of experience nate situations or designs. In addition
to the fire location and heat release rate
and research going back to the 1881 Ring Theater fire in Vienna that (HRR), a design scenario may include
many other conditions such as the mate-
killed 449 people. After that fire, the Austrian Society of Engineers rials being burned, the weather, the sta-
tus of the HVAC system, and doors that
conducted reduced-scale fire tests that showed how roof vents over are opened and closed. A design analy-
sis should include a number of design
the stage would have protected the audience from smoke. Thirty years scenarios to provide a level of assurance
that the smoke control system will oper-
later, such smoke vents worked as intended in the Palace Theater fire
ate as intended.
in Edinburgh, Scotland. Design fires need to be realistically
selected as discussed in Chapter 5. In
In addition to such natural smoke neric sense to mean any large-volume general, a design analysis needs to in-
venting, today there are a number of space. clude design fires located in the atrium
design approaches to deal with smoke This article is adapted from part of and in communicating spaces. A com-
in large-volume spaces. A large-vol- Chapter 15 of the new ASHRAE publi- municating space is one that has an open
ume space is a space that is at least two cation, Handbook of Smoke Control En-
stories high such as an atrium, a sports gineering.1 In this article, when a chap- About the Author
arena, or an airplane hangar. In this ar- ter number is mentioned, it is a chapter John H. Klote, Ph.D., P.E., is is an expert in smoke
ticle the term atrium is used in a ge- in this new handbook. control technology in Leesburg, Va.

36 ASHRAE Journal a s h r a e . o r g June 2012


A B Smoke Layer

Separated
Space

Atrium Plume
Separated
Space (Large-Volume Space)
Smoke Exhaust
Communicating Is Not Shown
Space

Communicating
Space

Spaces Related to Atriums Fire in the Atrium

C Smoke Layer D Smoke Layer

Smoke Exhaust Window Plume


Is Not Shown Smoke Exhaust
Balcony Is Not Shown
Spill Plume

This Room is Fully Involved in Fire

Fire in a Communicating Space Fully Developed Fire in a Room Open to the Atrium
Figure 1: Fire locations for atrium smoke control analysis.

pathway to an atrium so that smoke from a fire either in the fore it reaches the fire. Information about the interaction of
atrium or the communicating space can move from one to the sprinklers with the smoke layer is in the Handbook of Smoke
other without restriction. Figure 1A illustrates these spaces. Control Engineering. For information about design fires, see
A separated space is one that is isolated from the atri- Chapter 5.
um by smoke barriers (Figure 1A). For this handbook, a Smoke from a fire in a communicating space can flow
smoke barrier is a continuous membrane, either vertical into the atrium and form a balcony spill plume as shown
or horizontal, that is designed and constructed to restrict in Figure 1C. This figure shows smoke blocking of parts
the movement of smoke in conjunction with a smoke con- of balconies above the fire. It is beyond the capability of
trol system. Smoke movement at these smoke barriers can smoke control technology to prevent such smoke block-
be controlled by pressurization or by compartmentation ing, but the balcony is not blocked away from the balcony
alone. spill plume (Figure 2).The comments earlier regarding the
Figure 1B shows a fire in the atrium with smoke rising minimum distance that a person can be from a fire also
above the fire to form a smoke layer under the ceiling of the apply here. For a scenario with the fire in a communicat-
atrium. The most widely used approach to atrium smoke con-
trol is smoke exhaust, but other approaches can also be used. Smoke exhaust through a plenum with a suspended
Regardless of the smoke control approach, there is a distance ceiling not recommended. The pressures produced by the
around the fire where occupants cannot go because of the in- exhaust flow through a plenum with a suspended ceiling
tensity of the fire. To determine the minimum distance that a can be high enough to lift ceiling tiles out of their frames.
person can be from a fire for a few minutes without unbearable Such relocation of ceiling tiles could have an
pain see Chapter 6. adverse impact on the performance of the
For a scenario with the fire in the atrium, the design fire smoke exhaust system. The effort involved
does not normally take into account any benefit of sprinklers. with periodic testing of such a smoke exhaust
In spaces with high ceilings, the temperature of the smoke system can be significantly increased due to the
plume can drop so much that sprinklers may not activate or need for repair of suspended ceilings after testing.
activation may be so delayed that the spray may evaporate be-

June 2012 ASHRAE Journal 37


ing space, the growth of the design fire generally stops
upon sprinkler activation. Smoke Layer
Figure 1D shows a fully developed fire and smoke form-
ing a window plume. A fully developed fire would not happen
when a sprinkler system is operating properly. Because most
new commercial buildings in the United States are fully sprin- Balcony
klered, design fire scenarios that include a fully developed fire Spill Plume
are uncommon in the United States. In countries where fully
sprinklered buildings are uncommon, design fire scenarios
may include fully developed fires. It is also possible that some Smoke exhaust
building owners or building managers may want the very high is not shown.
level of protection associated with a smoke control system
that can handle even a fully developed fire. Figure 2: Front view of balcony spill plume.

Design Approaches include the times needed for recognition, validation and pre-
Design approaches that have been used for atrium smoke movement as discussed in Chapter 4.
control are (1) natural smoke filling, (2) steady mechanical
smoke exhaust, (3) unsteady mechanical smoke exhaust, Steady Mechanical Smoke Exhaust
(4) steady natural smoke venting, and (5) unsteady natural This is the most commonly used approach in North Amer-
smoke venting. These approaches are discussed later. Air- ica. This system consists of mechanical smoke exhaust sized
flow can also be used to control smoke flow in conjunction to keep the bottom of the smoke layer at the predetermined
with these approaches, but care must be exercised because height for the design fire.
airflow has the potential to provide combustion air to the
fire. Unsteady Mechanical Smoke Exhaust
Many design approaches are intended to prevent occupants This approach also uses mechanical smoke exhaust, but the
from coming into contact with smoke. The idea is to control flow rate of the exhaust is less than steady mechanical exhaust
smoke so that it descends only to a predetermined height dur- such that the exhaust only slows the rate of smoke layer de-
ing the operation of the smoke control system. In many lo- scent for a time that allows occupants to safely egress from the
cations, there are code requirements for the predetermined space. This method needs to maintain at least the predetermined
height. This height is often in the range from 6 to 10 ft (1.83 to height mentioned previously for the time it takes the occupants
3.05 m) above the highest walking surface that forms a portion to safely evacuate. The considerations about calculation evacua-
of a required egress in the atrium. tion time for natural smoke filling systems also apply here.
Other design approaches are intended to maintain a ten-
able environment when people come into contact with smoke. Steady Natural Venting
When the products of combustion are sufficiently diluted, the As previously mentioned, this kind of venting has a history
resulting diluted smoke can be tenable, and tenability analyses going back to the Ring Theater fire of 1881. This approach is
routinely deal with reduced visibility and exposure to toxic not common in the United States, but it is common in Europe,
gases, heat and thermal radiation. See Chapter 6 for more in- Australia, New Zealand and Japan. Rather than exhaust fans,
formation about tenability. this approach uses non-powered smoke vents at or near the top
The following discussion of design approaches address of the atrium. Often this kind of venting is called gravity vent-
systems that are intended to prevent occupant contact with ing because the smoke is vented due to buoyancy.
smoke, but these systems can be modified to ones that address The flow rate of the smoke through the vents needs to be such
tenability. that the bottom of the smoke layer is kept at the predetermined
height for an indefinite time. The previous comments regard-
Natural Smoke Filling ing the predetermined height also apply here. An equation for
This approach consists of allowing smoke to fill the atrium the steady mass flow rate through a natural vent is discussed
without any smoke exhaust or other smoke removal. For some later. It is recommended that steady natural venting systems be
spaces the smoke filling time with the design fire is more than analyzed with the aid of a computational fluid dynamics (CFD)
sufficient for evacuation. The smoke filling time is the time model, discussed in Chapter 20.
from ignition until the smoke descends to the predetermined
height. Applications that are appropriate for natural smoke Unsteady Natural Venting
filling are not common, because there needs to a very large This approach is like steady natural venting except the
space above the highest occupied level of the atrium. Any smoke venting rate is such that it only slows the rate of smoke
of the methods of analysis discussed below can be used for layer descent for a time that allows occupants to safely egress
this system. It is essential that calculations of evacuation time from the space. This method needs to maintain at least the

38 ASHRAE Journal a s h r a e . o r g June 2012


www.info.hotims.com/41640-69
A Ceiling Jet
B Exhaust

Uniform Smoke Layer

Smoke Layer
Interface
Transition Zone Plume
Plume

Smoke Exhaust
Not Shown

Fire Fire

Atrium Fire Zone Model Idealization of an Atrium Fire

Figure 3: Sketch of an idealized zone model representation of an atrium fire.

predetermined height mentioned previously for the time it into and out of it. In a real fire, the temperature and concentra-
takes the occupants to safely evacuate. It also is recommended tion of contaminants vary throughout the smoke layer with the
that unsteady natural venting systems be analyzed with the aid highest values tending to be near top of the smoke layer. In real
of a CFD model. The considerations about calculation evacu- fires, there is also a gradual transition zone between the smoke
ation time for natural smoke filling systems also apply here. layer and the lower layer as shown in Figure 3A.
In a zone fire model, the smoke layer has a uniform tem-
Methods of Analysis perature and uniform concentrations. This means that the tem-
The methods that can be used for analysis of atrium smoke perature at any place in the smoke layer is the same as every-
control systems are algebraic equations, zone fire modeling, where else in the smoke layer, and the same can be said about
CFD modeling and scale modeling. the concentration of each contaminant.
Zone fire models do not simulate the transition zone, but the
Algebraic Equations bottom of the smoke layer is simulated as a horizontal plane
Atrium smoke control makes use of many algebraic equa- called the smoke layer interface as shown in Figure 3B. The
tions. Some of these are based on the fundamental principles zone model considers the air a fraction of an inch (or centime-
of engineering, and others are empirical correlations based on ter) below the smoke layer interface to be as free of smoke as
experimental data. Equations for smoke filling, natural vent- the rest of the lower layer. Occupants in the lower layer near
ing and the airflow velocity to prevent smoke backflow are the smoke layer interface will actually be in the transition zone
discussed later in the chapter. exposed to some smoke. Unfortunately, neither zone fire mod-
Chapter 16 addresses the algebraic equations for steady me- els nor the algebraic equations of Chapter 16 can be used to
chanical smoke exhaust, and these equations are based on the evaluate this smoke exposure. It is believed that in many situ-
zone fire model concepts discussed in the next section. In the ations, conditions in the transition zone may be tenable. CFD
following section on zone fire modeling, the discussion about modeling can be used to evaluate tenability at this location.
smoke exposure in the transition zone also applies to systems Zone fire models do not simulate the time it takes for the
designed with the algebraic equations of Chapter 16. plume to reach the ceiling, which is small in a normal size
When another method of analysis is used, algebraic equations room but larger in an atrium. Empirical equations for this lag
are often used to determine starting points for the analysis. time are discussed later in this Chapter. Zone fire models do
not simulate plume flow, but they use empirical equations to
Zone Fire Modeling calculate plume temperature and the mass flow.
In an atrium fire, smoke flows upward in a plume that en- Even with the previous limitations, zone fire models have
trains air as it rises. When the plume reaches the ceiling, it proven to be very useful tools for many applications, but they
turns and becomes a ceiling jet that flows under the ceiling must be used with care. Chapter 18 has more detailed infor-
(Figure 3A). Figure 3B shows an idealized zone model repre- mation about zone fire models.
sentation of an atrium fire.
Zone fire models are simple models that consider a fire com- CFD Modeling
partment to be divided into two zones: (1) a smoke layer and (2) CFD consists of dividing a space of interest such as an atri-
a lower layer that is free or nearly free of combustion products. um into a large number of cells, and using a computer pro-
The smoke layer can change in size based on the mass flowing gram to solve the governing equations for each cell. CFD is

40 ASHRAE Journal a s h r a e . o r g June 2012


www.info.hotims.com/41640-70
capable of highly realistic simulations. The plume, ceiling jet, Minimum Smoke
Ceiling Jet Layer Depth is 20% of
smoke layer and the transition zone are all simulated by the Floor-to-Ceiling Height
CFD model. CFD models are capable of simulating plughol-
ing, and they can simulate any adverse effects of makeup air
velocity on plume formation. Plugholing is discussed later.
CFD modeling requires a level of knowledge and experi-
ence beyond that of zone fire modeling, and CFD simulations
typically require hours and sometimes days of computer time. Flow Under
For more information about this kind of modeling, see Chap- Plume Ceiling Jet

ter 20.

Scale Modeling
Scale modeling is capable of highly realistic simulations.
This kind of modeling consists of conducting fire tests in a
small model of the atrium or other facility, and converting the
data from those tests to the full scale facility. Scale modeling
is addressed in Chapter 21. Figure 4: Minimum smoke layer depth.

Atrium Temperature mechanical fans or by openings to the outside. Makeup air


For systems that rely on mechanical smoke exhaust, the has to be provided so that the exhaust fans can remove the
temperature of the air below the smoke layer quickly ap- design quantities of smoke and that the door opening force
proaches the outdoor temperature. This is because of the very requirements are not exceeded. Makeup air must be supplied
large amounts of makeup air that enter the atrium. For design far enough below the smoke layer interface so that it does not
analysis of systems using mechanical smoke exhaust, the out- disrupt the smoke layer.
side design temperature should be used for the ambient tem- When providing makeup air through openings to the out-
perature of the atrium. side, some air also flows by way of leakage paths. The large
As the gas temperatures increase, the density of the gas openings (such as vents, doors and windows) need to open
decreases, and the volumetric flow rate needed to maintain automatically on system activation. The leakage paths con-
a constant mass flow increases. Atrium exhaust fans need to sist of construction cracks, gaps around closed doors, gaps
be sized for the maximum volumetric flow needed to control around closed windows, and other similar small paths. The
smoke for the design conditions. This maximum volumetric large openings should be sized to provide about 85% to 95%
flow will happen when the summer outside design tempera- of the makeup air with the rest coming through the leakage
ture is used for the ambient temperature of the atrium. For this paths.
reason, smoke exhaust fans need to be sized with an ambient When makeup air is provided by mechanical fans, the
temperature of the atrium equal to the summer outside design makeup air should be less than the mass flow rate of the me-
temperature. chanical smoke exhaust. It is recommended that makeup air
for fan powered smoke exhaust systems be designed at 85% to
Minimum Smoke Layer Depth 95% of the exhaust. The idea is that the remaining air (5% to
The minimum smoke layer depth needs to be 20% of the 15%) will enter the large-volume space through leakage paths
floor-to-ceiling height except when an engineering analysis us- preventing positive pressurization of the atrium.
ing full scale data, scale modeling, or CFD modeling indicates The makeup air must not exceed 200 fpm (1.02 m/s) where
otherwise. The formation of the minimum smoke layer depth the makeup air could come into contact with the plume unless
is shown in Figure 4. When a smoke plume reaches the ceil- a higher makeup air velocity is supported by an engineering
ing, the smoke flows away from the point of impact in a radial analysis. The primary reason for this 200 fpm (1.02 m/s) limit
direction forming a ceiling jet. When the ceiling jet reaches a is to prevent significant deflection of the plume and disrup-
wall the smoke flow turns down and flows back under the ceil- tion of the smoke layer.2 Deflection of the plume results in
ing jet. The ceiling jet has a depth of about 10% of the floor-to- increased air entrainment that can cause smoke control sys-
ceiling height, and the smoke flow under the ceiling jet is also tem failure. A secondary reason for this velocity restriction is
about 10% of the floor-to-ceiling height. This means that the that it reduces the potential for fire growth and spread due to
smoke layer depth is about 20% of the floor-to-ceiling height. airflow.
The 200 fpm (1.02 m/s) limitation is not relevant in commu-
Makeup Air nicating spaces one story high that are sprinklered. At these
Makeup air is outdoor air either supplied by openings to locations, successfully sprinklered fires do not form plumes
the outside or by mechanical fans. For systems that have fan as they would in the atrium, and successfully sprinklered fires
powered smoke exhaust, makeup air needs to be provided by limit fire growth. However, air introduced in a communicat-

42 ASHRAE Journal a s h r a e . o r g June 2012


www.info.hotims.com/41640-60
A Exhaust Fan B Exhaust Fan

Plugholing of Air Into


Smoke Exhaust

It Cannot Be Seen, But


The Fan is Still Pulling Air
Into the Smoke Exhaust

Smoke Layer Height Falling Due to Plugholing Smoke Below the Intended Height Due to Plugholing
Figure 5: Plugholing causing the smoke layer to fall below the intended height.

ing space needs to slow down to meet the 200 fpm (1.02 m/s) ings (or inlets): (1) far away from each other, and (2) such
limitation when it reaches the atrium. For example, consid- that the prevailing wind directions carry the smoke away
er makeup air supplied to the communicating space on the from makeup air openings (or inlets). When this simple ap-
ground floor of Figure 1A. The makeup air enters the commu- proach is not feasible, CFD analysis or wind tunnel analysis
nicating space at a velocity above the limitation. A jet of sup- is needed to evaluate the potential for smoke feedback into
ply air forms as it would from an HVAC diffuser. The velocity the atrium.
of this jet needs to drop to 200 fpm (1.02 m/s) or less when
it reaches the atrium space. The design calculations need to Plugholing
include velocity calculations of this makeup air jet at the point Plugholing is a phenomenon where air from below the
where it reaches the atrium. smoke layer is pulled through the smoke layer into the smoke
When makeup air is provided by openings to the outside, the exhaust. Plugholing can cause system failure, but it can be
design analysis of the system needs to address wind effects as easily prevented. Plugholing reduces the exhaust from the
discussed below. smoke layer, which tends to lower the smoke layer and expose
occupants to smoke.
Wind The following discussion of plugholing applies to steady
Atrium smoke control systems need to be designed to mini- mechanical smoke exhaust systems. Figure 5A shows a smoke
mize the potential for wind to result in: (1) velocities greater layer that is at the intended design height, but the layer is still
than 200 fpm (1.02 m/s) where the makeup air could come descending due to plugholing. As the smoke layer depth in-
into contact with the plume, and (2) smoke feedback from the creases, the buoyancy forces of the smoke layer increase, and
smoke exhaust (or smoke vents) into the makeup air. the amount of plugholing decreases. Eventually, the smoke
When makeup air openings face in different directions, layer becomes deep enough that a state of equilibrium is
wind forces can result in velocities exceeding 200 fpm (1.02 achieved with a constant smoke layer height as shown in Fig-
m/s) inside the atrium. The wind can “blow” into openings ure 5B. Plugholing has resulted in a smoke layer below what
facing one direction and out the other openings. A simple was intended.
approach for minimizing wind effects inside an atrium is to The important forces for plugholing are the kinetic forces
have all the makeup air openings face in the same direction. of the smoke exhaust and the buoyancy forces of the smoke
Another simple approach is using mechanical fans for both layer. When kinetic forces dominate, there will be plughol-
smoke exhaust and makeup air such that the impact of the ing. When the buoyancy forces dominate, there will be no
wind is minimized. When such simple approaches are not fea- plugholing. The kinetic forces depend on the flow rate of the
sible, a detailed analysis is needed that takes into account the smoke exhaust, and the buoyancy forces depend on the tem-
prevailing wind directions. Such an analysis can be done with perature and depth of the smoke layer. When these forces
a network model or a CFD model. are balanced at an exhaust inlet, the flow at that inlet is the
Smoke can be carried by the wind from the smoke ex- maximum that can be achieved without plugholing. Plughol-
haust or from smoke vents to makeup air openings or inlets. ing can be prevented by using a number of smoke exhaust
The simple approach to minimize the potential for this is to inlets such that the flow rate at each inlet is at or below this
locate the smoke exhaust (or vents) and makeup air open- maximum value.

44 ASHRAE Journal a s h r a e . o r g June 2012


www.info.hotims.com/41640-32
There is an empirical equation in Chapter 16 for the maxi- modeling or CFD modeling would result in a lower num-
mum volumetric flow rate that can happen at an exhaust inlet ber of exhaust inlets than an analysis using the empirical
without plugholing. This equation and the earlier discussion equation.
also apply to systems that use natural venting.
Scale modeling and CFD modeling can simulate plughol- Stratification
ing without the use for the empirical maximum flow rate A hot layer of air can form under the ceiling of an atrium
equation of Chapter 16. This empirical equation can be due to solar radiation on the atrium roof. The temperature of
conservative, and it is possible that an analysis using scale such a layer can be 120°F (50°C) or more. When the aver-
age temperature of the plume is less
than that of the hot air layer, a stratified
smoke layer can form under the hot air
layer preventing smoke from reaching
ceiling-mounted smoke detectors. If
smoke stratification can occur, projected
beam smoke detectors should be used,
and three arrangements of these detec-
tors are discussed in the handbook.

Control and Operation


Atrium smoke control systems must
be activated automatically to quickly
provide smoke protection for the occu-
pants. For atria where smoke stratifica-
tion can happen, projected beam smoke
detectors should be used as mentioned
previously. Some other methods of
system activation are ceiling mounted
smoke detectors, heat detectors and
sprinkler water flow. The smoke control
system needs to reach full operation be-
fore conditions in the atrium reach the
design conditions. Determination of the
time for the system to become opera-
tional needs to take into account (1) the
time for detection of the fire and (2) the
HVAC system activation time including
shut-down and start-up of air-handling
equipment, opening and closing damp-
ers, and opening and closing natural
ventilation devices.
A means of manually starting and
stopping the smoke control system
needs to be provided at a location ac-
ceptable to the fire department. These
manual controls need to be able to over-
ride the automatic controls. For general
information about controls of smoke
control systems see Chapter 8.

References
1. Klote, J.H. 2012. Handbook of Smoke
Control Engineering. Atlanta: ASHRAE.
2. Hadjisophocleous, G., J. Zhou. 2008.
“Evaluation of atrium smoke exhaust make-up
air velocity.” ASHRAE Transactions, Part 1.
www.info.hotims.com/41640-22
46 A S H R A E J o u r n a l June 2012
www.info.hotims.com/41640-10

Вам также может понравиться