ABB ACS 1000 Training

ACS 1000 Operation and ACS1000


Maintenance
Power Electronic HW
Course G700
Air Cooled Unit
ACS 1000 Training –RevC1
© ABB Ltd - 1 -

© ABB Ltd Page 1


ABB ACS 1000 Training

Power
Electronic HW Training objectives

Upon completion of this part the student will be able to handle the
hardware including:
 Characteristic of ACS1000 family
 Main circuit diagram
 Function of Components (Rectifier, DC-Link, Inverter)
 Protection functions
 Function of Output Sine Filter
 Function of Common Mode Choke (option)
 Location of main components in air cooled version
ACS 1000 Training –Rev.C1
© ABB Ltd - 2 -

© ABB Ltd Page 2


ABB ACS 1000 Training

Power
Electronic HW Introduction of ACS 1000 Family
 New Design of
Control Buttons
& Labels
ACS 1000 Training –Rev.C1
© ABB Ltd - 3 -

ACS1000 Introduction:
• ACS 1000 is a converter drive for three phase squirrel cage
induction motors.
• Standard applications are the control of fans, pumps, conveyors
and compressors in petrochemical, mining, water, pulp & paper,
cement industries and power generation.
• Sophisticated microprocessor circuitry is used for monitoring the
motor electromagnetic status. This data and Direct Torque Control
(DTC) enables state-of-the-art sensorless motor control.
• Nearly sinusoidal converter output voltage allows the use of
ACS1000 also for retrofit applications with existing standard MV
induction motors without derating.
• ACS 1000 is equipped with hardware and software protection
features to protect the AC drive system against faults and damages
due to improper operation and an equipment malfunction.
• The standard ACS 1000 cabinet is rated as IP21 for air-cooled and
IP31 for water-cooled units. Higher IP ratings are available optionally.
• ACS 1000 meets all common standards including IEC and EN.
• In addition, ACS 1000 converter adequately meets the requirements
of the international harmonic standards, such as IEEE 519-1992.
• Depending on the power, ACS1000 is equipped either air-cooled or
water-cooled cooling system.

© ABB Ltd Page 3


ABB ACS 1000 Training
Product
overview ACS1000 Air cooled
ACS 1000 Training –Rev.C1
Cooling Fan Inverter
© ABB Ltd - 4 -

Control cabinet Sine Filter Choke Rectifier DC Link and


Filter capacitors

© ABB Ltd Page 4


ABB ACS 1000 Training
Product
overview ACS1000 Air cooled

Air cooling circuit specification type of ACS 1000


-A1 -A2/-A3
max. heat transfer to the ambient 1.8 % of rated 1.8 % of rated
apparent drive apparent drive
power power
ACS 1000 Training –Rev.C1

nominal cooling air flow 1.7 m3/sec 2.5m3/sec


ambient temperature min. 0 °C min. 0 °C
max. 40 °C max. 40 °C
(up to 45°C (up to 45°C
with derating) with derating)
© ABB Ltd - 5 -

© ABB Ltd Page 5


ABB ACS 1000 Training

Power
Electronic HW
ACS 1000 Training –Rev.C1
© ABB Ltd - 6 - Rating Plate of ACS 1000 Family

The drive plate of ACS 1000:

Type: ACS 1000 type code includes 36 digits


(code is indispensable for software update)
(for details see Appendix E - ACS 1000 Type Code Sheet in
the Technical Catalog)
Rated for: Nominal motor power
(for the basic 4-pole motor) in kW and hp
U1: Nominal ACS 1000 input voltage
I1: Maximum input current (including overload capability)
f1: Nominal input frequency (mains frequency)
Weight: Weight of the ACS 1000 in kg and lbs
FAUF: Production reference number
U2: Output voltage of ACS 1000
I2: Maximum output current at 40°C
(including overload capability; above 40°C,
the maximum possible output current decreases)
f2: Output frequency

© ABB Ltd Page 6


ABB ACS 1000 Training

Power
Electronic HW Power Electrical Circuit Diagram
Main circuit diagram of the ACS1000 converter
Standard 12-pulse input rectifier bridge + optional common mode choke (Lcom)

(*)
Transformer
ACS 1000 Training –Rev.C1

Rectifier DC Bus Inverter Sine-filter


© ABB Ltd - 7 -

(*) Resistor (Re) used only in water cooled converters.

What is an ACS1000 ?

• ACS 1000 is a converter family for industrial adjustable speed drive


applications for motor voltages 2.3 kV, 3.3 kV and 4.16 kV, either
50Hz or 60Hz.
• ACS 1000 covers motor powers 110 kW - 5000 kW (150 HP - 6500
HP).
• ACS 1000 is based on the three-level voltage source inverter
technology with a 12 pulses (24 pulses as an option) input rectifier.
• The Output LC-filter called “sine-filter” provides nearly sinusoidal
output waveform, this allows to use standard motor cables without
any length limitation and motors without derating.
• As inverter switches IGCTs (Integrated Gate Commutated Thyristor)
are used in the ACS1000. This Semiconductor Type combines the
strength of latest GTO and IGBT technology.
The freewheeling diodes are integrated together with the IGCT on
the same wafer, that results in a very compact design.
• ABB developed Direct Torque Control (DTC) to simultaneously
incorporate high performance flux control and direct control of motor
torque. The result is a unique sensorless flux vector control that does
not compromise on torque or speed performance.

© ABB Ltd Page 7


ABB ACS 1000 Training

Power
Electronic HW Input Rectifier Bridge: Diodes
 Rectifier diodes
 2 types for air-cooled units
 1 type for water-cooled units

Uac1

~ 0,2V
Udc

Uac2
ACS 1000 Training –Rev.C1

Umot Uac1/2 Udc

2300 1327 3400


3300 1903
© ABB Ltd - 8 -

4875
4000 2305 5908

Input Rectifier Bridges / Diodes:

• The input rectifier bridges provide rectified voltage and current to the
DC link.
• Two standard bridges are wired in series such that their voltages can
be added.
• All DC bus current flows through both bridges due to the series
connection.

• Rectifier diodes for air-cooled unit:


• 32mm / 3,8kV for 2,3kV units
• 38mm / 6,0kV for 3,3kV & 4,16kV units

• Rectifier diodes for water-cooled unit:


• 50mm / 6,0kV for 3,3kV & 4,16kV units

© ABB Ltd Page 8


ABB ACS 1000 Training

Power
Electronic HW Input Rectifier Bridge: Protection
 Varistor (Fm)  Protection capacitors
 440V / 10 kA  Different types

Fm

 Snubber capacitor Cr1 / Cr2


 2,2µF / 300V
 Resistors
 Different types
ACS 1000 Training –Rev.C1
© ABB Ltd - 9 -

Cm

Input Rectifier Bridges / Protections:

• Protection RC circuit (Rr, Cr) protects the rectifier diodes against


high voltage transients when protection IGCTs are turned off.

• Snubber circuit (Rm, Cm) protects the rectifier diodes during normal
commutation of a diode bridge.

• Varistor (Fm) and resistor (Rsym) protect the snubber circuit in a


case of short circuit in the DC link.

• CR1 & CR2 are mounted on the same common module, different
types exist:
• Water-cooled unit = 2x140uF/3230Vdc
• Air-cooled unit 2,3 kV = 2x70uF/1860Vdc
• Air-cooled unit 3,3 kV = 2x55uF/2660Vdc
• Air-cooled unit 4,16 kV = 2x40uF/3230Vdc

© ABB Ltd Page 9


ABB ACS 1000 Training

Power
Electronic HW DC-Bus: Grounding Isolator
+
 Grounding Isolator

N
ACS 1000 Training –Rev.C1

Q2
© ABB Ltd - 10 -

Grounding isolator:
• A safety grounding switch guarantees personal safety when drive
maintenance is performed.
• The safety grounding switch connects the plus, minus, and neutral
DC busses to ground. That ensures that the power has been
removed and all energy stored in the DC link capacitors has been
discharged before having access to the power parts.
The power section doors are interlocked with the safety
grounding switch.
• A yellow light “GND SWITCH UNLOCKED” (located on the control
section door) indicates when the DC busses are discharged to a safe
level. This releases the (electromagnetic) locking mechanism and it’s
possible to close the grounding switch and open the doors.
Locking mechanism and yellow light “GND SWITCH
UNLOCKED” are connected in parallel and controlled from
IOEC1 (output relay 1.4).
Never try to move grounding isolator without yellow
light on !
• Energize / de-energize procedure is described in detail on User’s
Manual chapter 5 .
• Danger: The cooling water system may start automatically even if
the converter is de-energized. In order to shut down the cooling
system, the auxiliary voltage has to be switched off (Q11/Q12).

© ABB Ltd Page 10


ABB ACS 1000 Training

Power
Electronic HW DC-Bus: Protection & Precharching
 Varistor (Fs1/Fs2)
 Different types (2,3 / 3,3 / 4,16kV)

Fs1 / Fs2

 Resistor (Rpre, Rdis...)


 Different types
ACS 1000 Training –Rev.C1
© ABB Ltd - 11 -

Only with optional breaking chopper

Protection IGCTs & Precharge Resistors:


• Between rectifier bridges and dc-link capacitors, two protection IGCTs
are situated.
In case of an inverter fault, these IGCTs (Vs1 / Vs2) disconnect
the rectifier immediately from the DC-link and stop the energy flow
from the mains into the drive. Fuses on the line side are not needed.
• These protection IGCTs immediately isolate the inverter of the drive
system from the power supply side within 25 microseconds, thus
making it 1000 times faster than the operational performance of
fuses.
• Varistor (Fs1 / Fs2) protect the protection-IGCT against over-
voltages, during a full DC-link shortage due to an inverter fault or
when the IGCT is turned off.
• Two protection IGCTs are identical to the inverter IGCTs.

© ABB Ltd Page 11


ABB ACS 1000 Training

Power
Electronic HW DC-Bus: Charching - Discharching

MAX
Charging time Parameter 2.7 DC Voltage Udc1+2 = 102 %
Values

Discharging time

MIN
00:00:12.81 00:00:32.81
ACS 1000 Training –Rev.C1

 ACS 1000 Charging time : <20 s


© ABB Ltd - 12 -

 ACS 1000 Discharging time : <10 min

Charging / discharging sequence:


• At the beginning the protection IGCTs are open. When power is
applied, the DC link (capacitors C1, C2) will be charged through the
precharge resistors (Rpre).
• The pre-charge resistors (Rpre) limit the current flowing into the main
DC link capacitors when power is connected.
• After fixed delay (Gr115.6, Charge Time), software checks the DC
bus voltage. If DC bus voltage reaches 85% of its nominal value,
two protection IGCTs start firing, and the drive is “READY TO RUN” ;
otherwise “CHARGING FAULT” occurs.
• After IGCT switches are closed, they provide the main connection
between the input rectifier bridges and the DC link.
• After the capacitors have been precharged and the protection IGCTs
are closed, the precharge resistors don’t provide any further function.
• Discharge resistors (Rdis) convert electrical energy of the DC
capacitors (C1, C2) to heat when unit is switched off by opening the
MCB.
• After fixed delay (Gr115.5) software checks the DC bus voltage. If
DC bus voltage reaches the value below about 50 V within a time
limit, the grounding isolator is released (GND SWITCH UNLOKED) ;
otherwise DSCHARGING FAULT occurs.

© ABB Ltd Page 12


ABB ACS 1000 Training

Power
Electronic HW DC-Bus: Capacitors & Connections
 DC Capacitor (C1 / C2)
 Different types (2*500µF…2*2300 µF)

C1 / C2
ACS 1000 Training –Rev.C1
© ABB Ltd - 13 -

Only with optional breaking chopper

DC Link Filter Capacitors:

• The DC link capacitors C1, C2 filter the output of the bridge rectifiers
and provide a low impedance source of voltage at the DC link.
• For balancing the DC voltage between the two capacitors during
charging, there is a high ohmic resistor Rdis parallel to both of the
capacitors.
• Another task of these resistors is the discharging of the capacitors
when unit is switched off by opening the MCB. In this case, the
electrical energy of the DC capacitors (C1, C2) is converted to heat
(Pj=RI²).
• For the smaller units, it is possible to get both of the DC-link capacitors
in one common case with three terminals.
• See charging / discharging sequence on page 16.
• Remark : the ambient temperature of the capacitors has a great
influence on their life time.

DC Link Output Connections:

• Three DC output (-, N, +) connections are added in case of optional


breaking chopper.

© ABB Ltd Page 13


ABB ACS 1000 Training

ACS1000i
DC-Link Capacitors
 Long-life capacitors
 Advanced, environmental friendly, natural oil-filled foil capacitors
have a substantially longer lifetime than electrolytic capacitors
 ‘State of the art’ technology, highly reliable, also used in heavy
duty applications, such as railway traction systems
 Self healing !
Self
Selfhealing:
healing:
If a dielectric breakdown between capacitor foils occurs the
If a dielectric breakdown between capacitor foils occurs the
energy, released by the arc discharge in the breakdown channel,
energy, released by the arc discharge in the breakdown channel,
is sufficient to totally evaporate the thin metal coating in the
is sufficient to totally evaporate the thin metal coating in the
vicinity of the channel. The rapid expansion of the plasma in the
vicinity of the channel. The rapid expansion of the plasma in the
breakdown channel causes it to cool after a few microseconds,
breakdown channel causes it to cool after a few microseconds,
thus quenching the discharge. The insulated region thus resulting
thus quenching the discharge. The insulated region thus resulting
around the former faulty area will cause the capacitor to regain its
around the former faulty area will cause the capacitor to regain its
full operation ability.
full operation ability.
ACS 1000 Training –Rev.C1
© ABB Ltd - 14 -

Lowest
Lowestlifetime
lifetimecosts
costs!!

© ABB Ltd Page 14


ABB ACS 1000 Training

ACS1000i
DC-Link Capacitors
 Lifetime expectancy
 under nominal conditions (i.e. 40°C ambient) > 15 year
 under typical operating conditions (30° C ambient) > 20 years
 ABB recommends preventive replacement after 12 years
of operation in order to maintain a high product
availability (AC and DC power capacitors)
 virtually no aging during storage, no “formatting”
(like for electrolytic caps) required
ACS 1000 Training –Rev.C1
© ABB Ltd - 15 -

© ABB Ltd Page 15


ABB ACS 1000 Training

Power
Electronic HW DC Bus: di/dt Limiting Choke

 di/dt DC Choke (Ls)


 Different types
 3,4µH…24µH

Ls1 / Ls2

 Clamping Resistor (Rs)


 Different types
ACS 1000 Training –Rev.C1

Rs
© ABB Ltd - 16 -

di/dt Limiting Choke:

• Two chokes (Ls1, Ls2) are included to limit the current rise time at
the upper and lower DC busses.
• Needed to protect the freewheeling diodes inside the IGCTs
from excessive di/dt.
• After the disconnection of IGCT from the DC, current drawn from the
DC link increases rapidly. For a short period of time (several
microseconds) this develops a voltage across the choke, that’s why
the choke construction must withstand the large forces caused by
the surge current (di/dt stress caused by the switching IGCTs).
• Also in a case IGCT fails, di/dt chokes limit the surge current.

Clamping circuit:

• A combination diode (Vcl1, Vcl2), resistor (Rs1, Rs2), capacitor (Ccl1,


Ccl2) associated with each choke discharges the energy stored in the
choke by the above process and prevents excessive voltages from
being applied to the inverter IGCTs when an IGCT turns off. Diodes Vcl1,
Vcl2 are identical to neutral point diodes.

Remark:

• On air-cooled units Ls1, Ls2, Rs1, Rs2, Ccl1, Ccl2 are mounted in
the rear of the inverter section. Thus they are not visible from front of
the drive but still accessible by removing the fan.

© ABB Ltd Page 16


ABB ACS 1000 Training

Power
Electronic HW Inverter: Introduction
+

GU GU GU

GU GU GU

NP
NP NP
GU GU GU

GU GU GU
ACS 1000 Training –Rev.C1

-
U leg V leg W leg
© ABB Ltd - 17 -

Inverter IGCTs (Integrated Gate-Commutated Thyristor) :


• Each leg of the 3-phase inverter bridge consists of a combination of
4 IGCTs with 2 neutral diodes for 3-level switching operation.
• Three-level inverter topology together with the IGCT switches &
DTC control are the heart of the drive. They provide the base for the
ACS 1000 inverter family without need for serial or parallel
connection of semiconductor devices, only 12 IGCTs for all
ACS1000 inverters.

• Multilevel Solution: 3.3kV / 2MW ACS1000 Solution:

t e
o le
b s
O M
IGBTs: 240 IGCTs: 14
Diodes: 72 Diodes: 20
Fuses: 36 Fuses: not any

© ABB Ltd Page 17


ABB ACS 1000 Training

Power
Electronic HW Inverter: Operation Principle
 Positive Current:

GU
 Negative Current: 14 IGCT’s
ACS 1000 Training –Rev.C1
© ABB Ltd - 18 -

Operation Principe :

• Switching procedure of the IGCTs at the inverter bridge determines


both, the output frequency and the magnitude of the output voltage.
• IGCTs can connect the output of the certain motor phase between:
 positive DC voltage (+),
 neutral point (NP) and
 negative DC voltage (-).

Inverter Output Voltage (before sine-filter) Motor : 1250 kVA / 4.16 kV

© ABB Ltd Page 18


ABB ACS 1000 Training

Power
Electronic HW Inverter: IGCTs (Integrated Gate Commutated Thyristor) 1
 Inverter & Protection IGCTs:
 6 types for air-cooled units
 4 types for water-cooled units
Turn-on Turn-off
circuit circuit Anode
DC/DC
converter
Supply
Supply Voltage DC
DC
X1_2 (+20V)
Optical firing
X1_1 (0V) Cathode

Optical Logic control


control input
ACS 1000 Training –Rev.C1
© ABB Ltd - 19 -

Inverter IGCTs (Integrated Gate-Commutated Thyristor) :


The IGCT joins the strengths of GTO and IGBT
• Low on-state loss due to pnpn activity
• High blocking capability (>6kV)
• Low losses due to latest wafer technology
Features:
• Transparent anode
• Buffer layer, thin Si
• Integrated reverse diode
• Optical firing

Inverter & Protection IGCTs, air-cooled unit (6 types):


• 38/51/68mm / 4,5kV for 2,3kV & 3,3kV units
• 38/51/68mm / 6,0kV for 4,16kV units

Inverter & Protection IGCTs, water-cooled unit (4 types):


• 68/91mm / 4,5kV for 3,3kV units
• 68/91mm / 6,0kV for 4,16kV units

© ABB Ltd Page 19


ABB ACS 1000 Training

Power
Electronic HW Inverter: IGCTs (Integrated Gate Commutated Thyristor) 2

 Use Multimeter  IGCT replacement tool:


 to measure the  only use on air-cooled units
 IGCTs  kit includes the two pieces
which are needed
ACS 1000 Training –Rev.C1
© ABB Ltd - 20 -

• IGCT diagnostic can be easily done by using any Multimeter


• Construction allows the easy exchange of IGCTs
(see Drive Support SW tool).

© ABB Ltd Page 20


ABB ACS 1000 Training

Power
Electronic HW Inverter: Protection of IGCTs
 Clamping Capacitor (Ccl)  Neutral Point & Clamping Diode
 6 types for air-cooled units  6 types for air-cooled units
 4 types for water-cooled units  4 types for water-cooled units
VN / VCL

~0,2V
CCL

LS1
+

GU V1U GU V1V GU V1W


RS1 VCL1

C1 CCL1
GU V2U GU V2V GU V2W

RWW
RWU

RWV
VN1U VN1V VN1W
NP

VN2U NP VN2V NP VN2W


ACS 1000 Training –Rev.C1

GU V3U GU V3V GU V3W


C2 CCL2

RS2 VCL2
© ABB Ltd - 21 -

GU V4U GU V4V GU V4W

-
LS2

IGCTs Protection:

• Balancing resistors (Rw) and neutral point diodes (VN) divide DC


voltage equal across two IGCTs and protects the components when
the other leg of IGCT is turned off.

• Clamping circuit (Vcl, Ccl, Rs) protects the inverter diodes when the
inverter IGCT is turned off.

• Neutral point & Clamping diodes, air-cooled unit (4 types):


• 38/51mm / 4,5kV for 2,3kV & 3,3kV units
• 38/51mm / 6,0kV for 4,16kV units

• Neutral point & Clamping diodes, water-cooled unit (4 types):


• 51/68mm / 4,5kV for 3,3kV units
• 51/68mm / 6,0kV for 4,16kV units

© ABB Ltd Page 21


ABB ACS 1000 Training

Power
Electronic HW Inverter: Current Transducer
 Current Transducer
 Different types
 +- 20Vdc supply
 Automatic offset calibration
(potentiometer not used)
ACS 1000 Training –Rev.C1
© ABB Ltd - 22 -

Inverter Current Measurements:


Iu
MOTOR
• There are five current transformers used Iu's

to measure the converter currents. Iv


Iw's
• Two inverter output currents (Tu, Tw)
measure the total inverter output currents. Iw
Iufil Iwfil

• Two filter currents (Tufil, Twfil) are


needed to measure the filter currents.
• One earth current measurement (Tgnd)
is used for calculations &
Earth Fault Supervision.
Ignd
• Software is able to calculate all the current
values needed for DTC control:
Iu + Iv + Iw = Iufil + Ivfil + Iwfil
Iu’ + Iv’ + Iw’ = 0
Iufil + Ivfil + Iwfil = Ignd
Iu = Iufil + Iu’s
Iu’ = Iu - 1/3 Ignd
Iv = -Iu - Iw + Ignd
Current transducer offset calibration is automatically done
after grounding isolator is closed and auxiliary power
switched on.

© ABB Ltd Page 22


ABB ACS 1000 Training

Power
Electronic HW Inverter: Output Sine Filter 1
 Sine Filter Choke (Lf)
 Different types (0,48mH…6,8mH)

Lf

 Sine Filter Capacitor (Cf)


 Different types (3*50µF...3*210µF)
ACS 1000 Training –Rev.C1

Cf
© ABB Ltd - 23 -

Output Sine Filter:

• The output sine filter


(Lf, Cf, Re) is respon-
sible for filtering the
inverter output.
With this filter, the
voltage and current
waveform applied to
the motor are nearly
sinusoidal.
• The LC filter reduces the harmonic content of the output voltage.
Therefore, standard motors can be used at their nominal ratings.
• The filter also eliminates all high dv/dt effects caused by the hard
switching IGCTs (Common Mode Voltage phenomena) and thus
voltage reflections in the motor cables and stresses to the motor
insulation are totally eliminated.
• Hence the output sine filter allows a standard motor to be applied
(retrofit) without extra component added, without extra winding
insulation requirements or without cable length limitation.
• For the smaller units, it is possible to get whole sine filter in one
common case with four terminals. For high power ACS1000-types
two cases are needed.

© ABB Ltd Page 23


ABB ACS 1000 Training

Power
Electronic HW Inverter: Output Sine Filter 2

Inverter Output Voltage (before sine-filter) Motor : 1250 kVA / 4.16 kV


ACS 1000 Training –Rev.C1
© ABB Ltd - 24 -

Motor Voltage (after output sine-filter) Motor : 1250 kVA / 4.16 kV

Sine Filter Output:


As a standard the ACS 1000 has a grounded low pass LC sine filter at its
output stage. The low pass frequency is designed to be well below the
lowest switching frequency used by the inverter output stage.
This greatly enhances the purity of both the voltage and current
waveforms applied to the motor.
This in turn provides many important benefits:
• Harmonic heating is virtually eliminated. The drive may be used to
supply standard medium voltage motors (existing or new) without
applying thermal derating factors.
• Voltage reflection and the associated occurrence of voltage doubling
at the motor input terminals is no longer an issue (the causal high
frequency content doesn’t exist). Therefore, any standard medium voltage
winding insulation system (existing or new one) is compatible.
• Motor cables of any length may be utilized without concern
(normal voltage drop issues as found in any electrical installation still
apply).
• Motor bearing failures attributable to capacitive coupled high
frequency current are no longer an issue (the causal high
frequency common mode voltage is eliminated).
• Motor insulation is not subjected to the common mode voltage
which is typical for other drive topologies.

© ABB Ltd Page 24


ABB ACS 1000 Training

Power
Electronic HW Auxiliary: Converter Fan

 Converter Fan  Differential Pressure Sensor


 Different types
 Fan runs when MCB is closed

B1 / B2
ACS 1000 Training –Rev.C1

Nominal fan speed of 1000 rpm


© ABB Ltd - 25 -

guarantees bearings life time


over 40000 hours running time.

Differential Pressure Sensor: (located in the control section)


• Sensor B1” Depression Cooling Air Supervision” (DI1.3) measures
the air pressure inside the inverter.
• Optional sensor B2 “Air Filter Supervision” (DI1.9) measures air
pressure across the optional air filter mounted on the inverter door.

Air-cooled drive:
• Standard:
1 radial cooling fan inside the middle section
Air inlet on the inverter section door
Air outlet on the top of the cabinet Control
Box Rectifier Inverter

• Optional redundant cooling fans:


Guarantees continuous operation in case a
Air Duct fan failure occurs
Automatic switch-over from the faulty to the
stand-by fan
Fans are located on the top of the converter

Control
Box Rectifier Inverter

• The construction allows easy replacement


of the fan. Fan maintenance procedure is
detailed on User’s Manual chapter 7.

© ABB Ltd Page 25


ABB ACS 1000 Training

Power
Electronic HW Inverter Section: Location of Components

 Inverter Section includes:


 DC filter capacitors
 Sine filter capacitors
 inverter IGCT
 Inverter neutral point diodes
 GUSP boards
 VLSCD boards
ACS 1000 Training –Rev.C1
© ABB Ltd - 26 -

• The control section can always be opened but must be closed to


maintain EMC performance.

Danger:

Do not access the main power circuit nor the


motor as long as the system is not grounded.

After switching off the mains and the motor has


stopped, always allow the intermediate circuit
capacitors discharge at least 5 min

 (yellow indicator ”GND SWITCH


UNLOCKED” must be on)

before grounding and starting work on the


frequency converter, the motor or the motor
cable.

ACS 1000 and attached electrical equipment


must be properly grounded before starting any
work with the drive system.

© ABB Ltd Page 26


ABB ACS 1000 Training

Power
Electronic HW Air Cooled Unit: Location of Components
Control section Middle section Inverter section

Rcom

Grounding
switch
Lcom
Common Mode
Choke Inverter:
(option) IGCTs &
Diodes
2 Protection
IGTCs +
Rectifiers Diodes
ACS 1000 Training –Rev.C1

C1 / C2
Cf DC Filter
Sine Filter
© ABB Ltd - 27 -

Rr / Rm
Lf Rpre / Rdis Cr1 / Cr2
Sine Filter Choke Cm / Fm Rectifier
Protection

Location of the main components:


• All power components (medium voltage) are located in the middle or
in the inverter section.
• In addition to the mains input / motor output cable connections, control
section doesn’t include any medium voltage.
• ACS 1000 cabinet design provides flexibility to add cabinet sections to
the drive at any time. Sections can be added in widths of 600, 800 and
1000 mm (resp. 24, 32 and 39 Inches).
• All doors are hinged and locked by carriage key locks.

Control cabinet door Inverter doors

© ABB Ltd Page 27


© ABB Ltd
ACS 1000 Training –Rev.C1
ABB

© ABB Ltd - 28 - ABB


ACS 1000 Training