ATyS g M
r uc Automatic Transfer Switching Equipment
Inst ual
Man
EN
www.socomec.com
www.socomec.com
www.socomec.com/en/atys-g-m
To download, brochures, catalogues and technical manuals :
This manual is available for download in French, English, German, Italian, Spanish, Dutch, Portugese, Russian, Polish, Turkish and Chinese.
2. INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1. The ATyS family product range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.2. The ATyS M Range Key Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.2.1. Selection guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.3. Quick Start ATyS g M (2P). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.4. Quick Start ATyS g M (4P). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3. ATyS g M versions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.1. Product presentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.2. Specifications and advantages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.3. Supply types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4. Optional accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
5. Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
6. Environmental conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
7. Product installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
7.1. Changing the padlocking configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
7.2. Recommanded orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
7.3. Dimensions of the single phase product . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
7.4. Back plate mounted single phase product. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
7.5. Dimensions of the three phase product. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
7.6. Back plate mounted three phase product . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
7.7. DIN rail mounted. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
12. OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
12.1. Presentation of the product interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
12.1.1. 2P product interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
12.1.2. 4P product interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
12.1.3. Reset. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
12.2. Manual mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
12.2.1. Manual switching. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
12.3. Padlocking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
12.4. Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
12.4.1. Single phase version. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
12.4.2. Three phase version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
12.4.3. Sealable configuration cover. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
12.5. Automatic mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
12.5.1. Sealable Auto/Manual cover. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
12.6. Possible actions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
12.7. Manual & Automatic Mode / Mains restoration conditions. . . . . . . . . . . . . . . . . . . . . . . 41
12.7.1. Mode 1: Automatic retransfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
12.7.2. Mode 2a: Controlled retransfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
12.7.3. Mode 2b: Controlled transfer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
12.7.4. Mode 3: Network - Network application with priority. . . . . . . . . . . . . . . . . . . . . . . . 46
12.7.5. Mode 4: Network - Network application without priority. . . . . . . . . . . . . . . . . . . . 48
• As a minimum the ATyS M comply with the following international standards:
- IEC 60947-6-1 - IEC 60947-3
- GB 14048-11 - IS 13947-3
- EN 60947-6-1 - EN 60947-3
- VDE 0660-107 - NBN EN 60947-3
- BS EN 60947-6-1 - BS EN 60947-3
- NBN EN 60947-6-1
he information provided in this instruction manual is subject to change without notice, remains for general
T
information only and is non-contractual.
40A - 160A
Back to Back
Configuration
ATyS p ATyS p M
Power / Genset Evolved Genset
Management Management
ATyS g M
40A - 125A
ATyS g
Simple Genset Simple Genset
Management Management
ATyS t M
ATyS t Transformer (building)
Transformer Management
Management
ATyS d S ATyS d M
Small Genset ATyS d RTSE (DPS)
with DPS RTSE (DPS)
Side by Side
ATyS S (RTSE) ATyS r ATyS
(1)
Configuration
Small Genset RTSE RTSE
(1)
The UL version of ATyS r is available from 100 - 400A
160 A
40 A
Communication*
tripping**
* Specific version. ** Return to zero without external energy source.
Non-critical
U
ATyS p M
P
loads
S
Critical
loads
Non-critical Non-critical
U
U
P
loads loads
S
Critical Critical
loads loads
Applications
Normal / Backup without automatic controller •
Normal / Backup with built-in automatic controller • • •
Stable positions • • • •
Load changeover •
FUNCTIONS
Power supply
External •
Integrated • • •
Operation
Backup manual operation of the 3 positions • • • •
Electrical (dry contact) control of positions I, 0
• •*
and II
Automatic control of positions I, 0 and II • • •
Return to 0 position feature upon loss of source •
Monitoring
3 voltages on networks I and II • • •
Frequency on networks I and II • • •
Phase rotation on networks I and II •
Asymmetry of networks I and II •
Automatic controller configura-
tion
By potentiometer and micro-switch • •
By screen + keyboard •
Vn, Fn, V threshold, F threshold • • •
Driving with or without priority • • •
Adjustable operating timers • • •
Control type (impulse or switch / contactor) •
Display
Position, fully visualised breaking • • • •
LED: source status, automatic mode, fault LED • • •
LED: switch positions, supply, tests, control •
V, F, timers, number of operations, last event •
REMOTE CONTROL
Outputs
Generator start / stop order • •
Product availability
• •*
(not fault and not manual mode)
Source available • •*
Programmable output (source, availability, fault) •*
Inputs
Test on load • •*
Retransfer • •*
Automatic mode inhibit • • •*
Position O order • •*
Priority • • •
Other programmable inputs
•*
(test off-load, p osition control, etc.)
Remote control
Human / Machine Interface (D10 and D20) •
RS485 communication (MODBUS) •**
* 3 inputs / 3 outputs (programmable).
** Product reference is different: communication by RS485 connection (MODBUS) allows up to 31 ATyS M to be connected to a PC or a PLC over 1500 m.
ATyS g M
STEP 1 STEP 2 STEP 3 STEP 4 STEP 5
Cabinet / Back Connecting the CONTROL / CHECK Programming STEP 6B
Plate Installation POWER section AUX POWER Emergency Manual
terminal Operation
connections
Automatic STEP 6C
Transfer Switching Equipment
Padlocking
Preliminary operations
Check the following upon delivery and after removal of the
packaging:
n Packaging and contents are in good condition.
n The product reference corresponds to the order.
n Contents should include:
Qty 1 x ATyS M
Qty 1 x Emergency handle extension ROD
Qty 1 x Set of terminals
Quick Start instruction sheet
2 clips de verrouillage
2 clips de verrouillage
Warning
Risk of electrocution, burns or injury to persons and /
or damage to equipment.
This Quick Start is intended for personnel trained in the
installation and commissioning of this product. For further
details refer to the product instruction manual available on
the SOCOMEC website.
n This product must always be installed and commissioned
by qualified and approved personnel.
n Maintenance and servicing operations should be
performed by trained and authorised personnel.
n Do not handle any control or power cables connected to
the product when voltage may be, or may become present
on the product, directly through the mains or indirectly
through external circuits.
n Always use an appropriate voltage detection device to
confirm the absence of voltage.
n Ensure that no metal objects are allowed to fall in the OK
cabinet (risk of electrical arcing).
Failure to observe good enginering practises as well as to OK
follow these safety instructions may expose the user and
others to serious injury or death.
Source priority 2
Dry potential free
Network-Genset. contact
Stop the test on load
13 26 13 26
The ATyS M is delivered with
Recommended orientation 18 18 padlocking configured to the
O position.
350
143
350
143
245
245
45
45
MAX : 2 MAX : 2
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK OK
OK
OK
OK
OK
OK OK
Recommended Ok Ok Ok Ok Ok 46
53
73,5
46
53
73,5
!
Posidriv PZ2
Tighten to avoid 235
224
STEP 1 STEP 3
IEC 60715
OK !! Posidriv PZ2
Posidriv PZ2 2,2 lb-in 0,25 Nm
! Posidriv PZ2
131,5
131,5
47
STEP 1 STEP 3 2X
STEP 2 STEP 4
the OK
ATyS M as follows before OK !
llage
Posidriv PZ1 4 mounting brackets 2X installation. (Screw is located
1 Nm 6x M6 screw - 2,5 Nm at the back of the product).
STEP 2
OK STEP 4
Posidriv PZ2
Posidriv PZ2
Step
STEP 11 STEP 3
Voltage taps provide 2x ≤ 1.5mm connections. 2
! OK !
STEP 2
STEP 1 STEP 3
Power Terminal Connections They can be fitted in any terminals on the source Posidriv PZ2
supply side. Do not use on the load side when
equipped with a bridging bar. STEP 1 ! STEP 3
Posidriv PZ2
It is essential to tighten all used Load side 10 to 70 mm2
# 8 to # 00 AWG Posidriv PZ2
Posidriv PZ2
Posidriv
2,2 PZ2 Nm
lb-in 0,25
2,2 lb-in 0,25 Nm
2x
terminals, with cables and/or bridging bar. 10 to 70 mm2 *
# 8 to # 00 AWG
2X Posidriv PZ2
160A: 1309 2016 Posidriv PZ2
2X
2,2 lb-in 0,25 Nm
STEP 2 STEP 4
OK Step
STEP 22 STEP 4
2X
OK
Hexagonal Metric STEP 2 STEP 4 OK
OK !!
!
Allen size 4
10 to 70 mm2
Hexagonal Metric
# 8 to # 00 AWG
10 to 70 mm * 2
44.1 lb-in 5,0 Nm
X4
Allen size 4 # 8 to # 00 AWG
5,0 Nm 15 mm / 0,59 " Posidriv PZ2
OK OK !
STEP 1 Step
STEP 3
3 2x
10 to
OK Slotted head 3,5 mm
70 mm² 0,45 Nm
15mm 0,5 to 2,5 mm²
Posidriv PZ2
Hexagonal Metric
Posidriv PZ2 2,2 lb-in 0,25 Nm
0,5 to 1,5 mm²
!
Allen size 4
44.1 lb-in 5,0 Nm
X4
Source supply side 6 mm
2X
STEP 2 STEP 4
Ensure that the product is in Manual
LOAD Mode (front cover open).
OK !
11 1411 12
1114 14
12 12 11 1411 1214 12
11 14 12
O1 O2 O1 O2
Recommended Auxiliary contacts: Fitting of auxiliary contacts: 1309 0001 or 1309 0011
Type Terminal no. Status of
the contact Description Output
characteristics connection
cross-section To fit an AC, the switch must first be put in position 0. An auxiliary contact module comprises: one NO/
Capacité de raccordement
0,5 to 2,5 mmNC
2
changeover contact
Slotted head for each position (I-0-II). To install use the long screws supplied with the module.
3 mm
Auxiliary contact 14 250V AC 5A AC1 # 20 to # 14 AWG 3,97 lb-in 0,5 Nm
11/12/14 11 12 Changeover switch in position I
block 30 Vdc 5 A 0,5 to 1,5 mm 2
# 20 to # 16 AWG
1309 0001 24 250V AC 5A AC1 6 mm / 0,236 "
21/22/24 21 Changeover switch in position II
22 30 Vdc 5 A !
01/02/04 04 250V AC 5A AC1 0.5 to 2.5 mm²
01 02 Changeover switch in position 0 (rigid)
30 Vdc 5 A
Auxiliary contact 14 250V AC 5A AC1 0.5 to 1.5 mm²
11/12/14 11 12 Changeover switch in position I Use 20mm Use 35mm
block 30 Vdc 5 A (stranded) screws for screws for
1309 0011 24 250V AC 5A AC1 1 module 2 modules
21/22/24 21 22 Changeover switch in position II
30 Vdc 5 A
Pozidriv PZ2 - 1 Nm
01/02/04 04 250V AC 5A AC1
01 Changeover switch in position 0
02 30 Vdc 5 A
Whilst in manual mode, check the The LED signalling and operation is only active when the product supply is available.
wiring and if ok power up the To set the dip switches, it is necessary to open the Auto/Manual cover.
product. Commissioning must always result in having at least 1 LED source available on.
(Therefore, the voltage and frequency must be within the defined thresholds).
Any action on the potentiometers will change the settings, even when the cover is closed.
A Dip switch settings B Hysteresis settings C Timer settings D Source supply voltage
and frequency
Auto-Configuration
Loss of priority source timer
U/F
Ensure that the supply
[HYST] voltage is available and
within the following limits:
Un: 176-288VAC
Fn: 45-65Hz
[HYST]
FT
Stop in 0 position: E-F FT: 0-60 sec.
• E: No stop in O position
• F: 2s stop in O position
Return of priority source timer
Type of application: G-H HYST: 20 %DU/F Press PROG for ≥ 2s
• G: Network - Genset DU: 5-20% U/F
• H: Network - Network DF: 3-10%
E LED info
Fault reset
Close the front cover as shown to put the • Open the front cover as shown to put • In order to padlock put the product in
product into automatic mode. into manual mode. manual mode.
• Use the handle situated in the front • Pull the locking mechanism and insert
panel under the cover to operate the a padlock as shown.
transfer switch. • As standard padlocking in the 0 position.
• Check the changeover switch position Configurable to I-0-II (see step 1).
on the indicator before operating.
90º 90º
Extension
II
To simplify operation
use the handle with the
extension provided.
(Max 8 Nm) 1x 4-8 mm
o
I
ATyS g M
STEP 1 STEP 2 STEP 3 STEP 4 STEP 5
Cabinet / Back Connecting the CONTROL / CHECK Programming STEP 6B
Plate Installation POWER section AUX POWER Emergency Manual
terminal Operation
connections
Automatic STEP 6C
Transfer Switching Equipment Padlocking
Preliminary operations
Check the following upon delivery and after removal of the
packaging:
n Packaging and contents are in good condition.
n The product reference corresponds to the order.
n Contents should include:
Qty 1 x ATyS M
Qty 1 x Emergency handle extension ROD
Qty 1 x Set of terminals
Quick Start instruction sheet
2 clips de verrouillage
Warning
Risk of electrocution, burns or injury to persons and /
or damage to equipment.
This Quick Start is intended for personnel trained in the
installation and commissioning of this product. For further
details refer to the product instruction manual available on
the SOCOMEC website.
n This product must always be installed and commissioned
by qualified and approved personnel.
n Maintenance and servicing operations should be
performed by trained and authorised personnel.
n Do not handle any control or power cables connected to
the product when voltage may be, or may become present
on the product, directly through the mains or indirectly
through external circuits.
n Always use an appropriate voltage detection device to
confirm the absence of voltage.
n Ensure that no metal objects are allowed to fall in the
cabinet (risk of electrical arcing).
Failure to observe good enginering practises as well as to
follow these safety instructions may expose the user and
others to serious injury or death.
Source priority 2
Dry potential free
O1 O2
Network-Genset. Stop the test on load contact
207208 209 210 63 64 73 74
Test on load / 0.5 to 2.5 mm²
I1 I2 I3 (rigid)
I3: 207 / 210 Network-Network or AUTO mode
Network-Generating Dry potential free
0.5 to 1.5 mm²
set Automatic mode inhibition contact Type
(stranded)
Capacité d
0,5 t
Outputs O1: 63 / 64 Network-Network or Product not available : Auxiliary
# 20 to
Network-Generating - Manual mode Resistive load
block
0,5 to
www.socomec.com set - Command default 2A 30 Vdc # 20 t
1309
www.socomec.com/en/atys-g-m 0.5A 230Vac 6 00
mm
- Electronic default
To download, brochures, catalogues and technical manuals. - No source Pmax : 60W or 125VA
Printing informations: 1 color Black. White paper 90g/m2. Umax : 30Vdc or
Printing size: 420x297. Final size 210x297. This page visible first. Product available 230Vac
A separate sheet for each language. Auxiliary
O2: 73 / 74 Network-Genset. No start command genset Resistive load
block
2A 30 Vdc
CORPORATE HQ CONTACT:
Generating set starting 1309 00
0.5A 230Vac
SOCOMEC SAS, 1-4 RUE DE WESTHOUSE, 67235 BENFELD, FRANCE
Pmax : 60W or 125VA
Umax : 30Vdc or
230Vac
Non contractual document.
542 932 C - 12/16 - EN Subject to change without notice.
350
143
350
143
245
245
45
45
MAX : 2 MAX : 2
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK OK
OK
OK
OK
OK
OK OK
Recommended Ok Ok Ok Ok Ok 46
53
73,5
46
53!
73,5
IEC 60715
OK !! Posidriv PZ2
Posidriv PZ2 2,2 lb-in 0,25 Nm
! Posidriv PZ2
131,5
131,5
47
STEP 1 STEP 3 2X
STEP 2 STEP 4
the OK
ATyS M as follows before OK !
Posidriv PZ1 6 mounting brackets 2X installation. (Screw is located
1 Nm 6x M6 screw - 2,5 Nm at the back of the product).
STEP 2
OK STEP 4
Posidriv PZ2
Posidriv PZ2
Step
STEP 11 STEP 3
Voltage taps provide 2x ≤ 1.5mm connections. 2
! OK !
STEP 2
STEP 1 STEP 3
Power Terminal Connections They can be fitted in any terminals on the source Posidriv PZ2
supply side. Do not use on the load side when
equipped with a bridging bar. STEP 1 ! STEP 3
Posidriv PZ2
It is essential to tighten all used Load side 10 to 70 mm2
# 8 to # 00 AWG
Posidriv PZ2
Posidriv PZ2
Posidriv
2,2 PZ2 Nm
lb-in 0,25
2,2 lb-in 0,25 Nm
2x
terminals, with cables and/or bridging bar. 6 to 70 mm 2*
# 10 to # 00 AWG
bridging bars, before use. 125A: 1309 4006 15 mm / 0,59 "
2X Posidriv PZ2
160A: 1309 4016 Posidriv PZ2
2X
2,2 lb-in 0,25 Nm
STEP 2 STEP 4
Step
STEP 22 STEP 4
Hexagonal Metric 2X
Allen size 4
OK
44,1 lb-in 5,0 Nm
! STEP
X82 STEP 4 OK
OK !!
Hexagonal Metric
Allen size 4 10 to 70 mm2
5,0 Nm # 8 to # 00 AWG Posidriv PZ2
6 to 70 mm *
2
# 10 to # 00 AWG
OK !
15 mm / 0,59 "
STEP 1 Step
STEP 3
3 2x
10 to
Slotted head 3,5 mm
70 mm² 0,45 Nm
15mm 0,5 to 2,5 mm²
Posidriv PZ2
Hexagonal Metric Posidriv PZ2 2,2 lb-in 0,25 Nm
Allen size 4 0,5 to 1,5 mm²
STEP 2 STEP 4
1 5 A AC1
c 250 Vac
5 A AC1
5 A AC1 5 A AC1
5 A AC1
2 4 6 8 2 4 6 8 250 Vac
250 Vac
22 24 21
250 Vac
250 Vac
O1 O2
Ensure that the product is in 230/127V~
207208 209 210 63 64 73 74 Manual Mode (front cover 3ph 4wires
230/127V~
/ open). 3ph 3wires
I1 I2 I3
Recommended Auxiliary contacts: Fitting of auxiliary contacts: 1309 0001 or 1309 0011
Type Terminal no. Status of
the contact Description Output
characteristics connection
Capacité de raccordement cross-section To fit an AC, the switch must first be put in position 0. An auxiliary contact module comprises: one NO/
0,5 to 2,5 mm 2 Slotted head 3 mm NC changeover contact for each position (I-0-II). To install use the long screws supplied with the module.
Auxiliary
# 20 tocontact
# 14 AWG 3,97 lb-in 0,5 Nm 14 250V AC 5A AC1
11/12/14 11 12 Changeover switch in position I
block
0,5 to 1,5 mm 2 30 Vdc 5 A
# 20 to # 16 AWG
1309 6 0001
mm / 0,236 " 24 250V AC 5A AC1
21/22/24 21 Changeover switch in position II
22 30 Vdc 5 A !
01/02/04 04 250V AC 5A AC1 0.5 to 2.5 mm²
01 02 Changeover switch in position 0 (rigid)
30 Vdc 5 A
Auxiliary contact 14 250V AC 5A AC1 0.5 to 1.5 mm²
11/12/14 11 12 Changeover switch in position I Use 20mm Use 35mm
block 30 Vdc 5 A (stranded) screws for screws for
1309 0011 24 250V AC 5A AC1 1 module 2 modules
21/22/24 21 22 Changeover switch in position II
30 Vdc 5 A
Pozidriv PZ2 - 1 Nm
01/02/04 04 250V AC 5A AC1
01 Changeover switch in position 0
02 30 Vdc 5 A
Whilst in manual mode, check the The LED signalling and operation is only active when the product supply is available.
wiring and if ok power up the To set the dip switches, it is necessary to open the Auto/Manual cover.
product. Commissioning must always result in having at least 1 LED source available on.
(Therefore, the voltage and frequency must be within the defined thresholds).
Any action on the potentiometers will change the settings, even when the cover is closed.
127/230 Vac version 230/400 Vac version Loss of priority source timer Source availability LED
Fault reset
Type of application: G-H RT
• G: Network - Genset HYST: 20 %DU/F
• H: Network - Network DU: 5-20% RT: 0-30 min.
DF: 3-10%
Close the front cover as shown to put the • Open the front cover as shown to put • In order to padlock put the product in
product into automatic mode. into manual mode. manual mode.
• Use the handle situated in the front • Pull the locking mechanism and insert
panel under the cover to operate the a padlock as shown.
transfer switch. • As standard padlocking in the 0 position.
• Check the changeover switch position Configurable to I-0-II (see step 1).
on the indicator before operating.
90º 90º
Extension
II
To simplify operation
use the handle with the
extension provided.
(Max 8 Nm) 1x 4-8 mm
o
I
5. Control connections.
4
3
5
2
1
CAUTION
Ensure that the load is connected
to the top of the switch with the
motorisation on the right hand side
as shown.
230 / 400 VAC Version 127 / 230 VAC Version 230 VAC Version
Umin Umax Umin Umax Umin Umax
Ph-N 176 288 176 288 176 288
Ph-Ph 305 498 305 498 / /
Bridging bars To provide a common point on the outgoing side of the Single phase product:
switch (load side). Rating ≤ 125A : 1309 2006
Rating 160A: 1309 2016
ATYSM 198 A
Three phase product:
Rating ≤ 125A : 1309 4006
Rating 160A: 1309 4016
ATYSM 025 A
Terminal Protection against direct contacts with terminals or Ref. : 2294 4016
shrouds connecting parts. Other features: Perforations allowing 2 parts/ref.
remote thermographic inspection without removal.
ATYSM 027 A
Possibility of sealing.
Enclosure Fully dedicated to ATyS M use, this polycarbonate Ref. : 1309 9006
enclosure provides easy access to a compact, enclosed
transfer switch.
ATYSM 036 A
Extension unit Combined with the polycarbonate enclosure, the Ref. : 1309 9007
extension box creates extra space for routing cables
with a larger diameter.
ATYSM 044 A
Sealable cover. It prevents access to the configuration panel of the Three phases product:
ATyS g M. Ref. : 1359 0000
Power The power connection terminals allow conversion of the Ref. : 1399 4017
connection cage terminals into bolt-on type connection terminals, For complete conversion,
terminals enabling connection of up to two 35mm² cables or order 3 times the
one 70mm² cable. Each power connection terminal is reference.
provided with separation screens.
Auto- For use with ATyS M in 400 VAC three-phase Ref. : 1599 4121
transformer applications without a distributed neutral. As the ATyS
M has integrated measurement and power supply
circuits, a neutral connection is required for 400 VAC
three-phase applications. When no neutral connection
is available this autotransformer (400/230 VAC, 400
VA) provides the 230 VAC required for the ATyS M to
function.
* Possibility of reaching 125A with bigger connection cross-sections and use of the 160A bridging bar.
** AC 33iB 160A according to GB 14048.11.
This is a class A product. In a domestic environment, this product may cause radio interference in
which case the user may be required to take adequate measures.
Temperature
• -20 +40 °C without de-rating
• 40 °C < t ≤ 70 °C with de-rating (see Technical Characteristics)
Altitude
Correction factors:
2 000 m < A ≤ 3 000 m 3 000 m < A ≤ 4 000 m
UE 0.95 0.80
Ie 0.85 0.85
Storage
• 1 year maximum
• Maximum storage temperature: +55 °C
• 80 % humidity without condensation at 55 °C
IP rating
ø 1 mm
• IP41 in the SOCOMEC polycarbonate modular enclosure see page 25
• IP2x for non-enclosed modular product
!
7.1. Changing the padlocking configuration
To configure the locking in the 3 positions:
STEP1: loosen the screw at the back of the product as shown below.
STEP2: slide the! screw upwards.
STEP3: tighten! the screw ! as shown.
OKposition
! in the top
! Posidriv PZ2
STEP 1 STEP 3
OK OK
OK OK Posidriv PZ2
Posidriv PZ2 2,2 lb-in 0,25 Nm
Posidriv PZ2
Posidriv PZ2
STEP 1 STEP 3
STEP 2 STEP 4 2X
Posidriv PZ2
2X Posidriv PZ2
2,2 lb-in 0,25 Nm
OK !
STEP 2 STEP 4 STEP 2 STEP 4
OK !
7.2. Recommanded orientation
2X
STEP 2 OK ! STEP 4 OK !
OK !
OK
OK OK
OK OK
OK OK
OK OK
OK OK
OK
OK OK OK OK OK OK
Recommended Ok Ok Ok Ok Ok
7.3. Dimensions of the single phase 7.4. Back plate mounted single
product phase product
235
52 176
235
222 224
6 116
13 26
18 18
131,5
131,5
350
143
245
245
45
45
47
MAX : 2 MAX : 2
46 46
53 53
73,5 73,5
4 mounting brackets
6x M6 screw - 2,5 Nm
13 26
18 18
350
143
245
245
45
45
131,5
131,5
47
MAX : 2 MAX : 2
46 46
53 53
73,5 73,5
6 mounting brackets
6x M6 screw - 2,5 Nm
Tighten to avoid
DIN RAIL movement on the DIN rail.
IEC 60715
2 clips de verrouillage
Posidriv PZ1
1 Nm
!
Use 20mm
Use 35mm
screws for 1 Slotted head 3,5 mm
screws for 2 0,45 Nm
module
modules 0,5 to 2,5 mm²
0,5 to 1,5 mm²
Pozidriv PZ2 - 1 Nm 6 mm
Bridging
OK
bar. Allen size 4
10 to1570mmmm
# 8 to # 00 AWG
2*
/ 0,59 "
OK 10 to
1 3 5 7 1 3 5 7 OK 70 mm²
317 315 314 313 202 201 102 101 317 315 314 313 202 201 102 101
15mm Hexagonal Metric
/
!
Allen size 4
Hexagonal 44.1 lb-in 5,0 Nm
Metric
X4
!
Allen size 4
44.1 lb-in 5,0 Nm
X4
Make sure that the bridging bar is fitted to the correct set of terminals.
There are two references available: one for ratings up to 125A, and another for 160A rating.
OK NOK
LOAD Source I Source II
/ Hexagonal Metric
Load side Allen size 4
10 to 70 mm2
# 8 2to # 00 AWG
10 to 70 mm
bridging bar.
RS RJ RS RJ
5,0 Nm # 8 to # 00 AWG6 to 70 mm 2*
# 102 to # 00 AWG
6 to 70 mm *
2 4 6 8 2 4 6 8 2 4 6 8 2 4 6 8
125A: 1309 4006 # 10 to # 00 15
AWGmm / 0,59 "
15 mm / 0,59 "
160A: 1309 4016 10 to
1 3 5 7 1 3 5 7 1 3 5 7 1 3 5 7
70 mm²
15mm
207208209210 43 44 53 54 63 64 73 74 207208209210 43 44 53 54 63 64 73 74
Hexagonal Metric
/ Allen size 4
Hexagonal Metric
LOAD
Source I Source II Allen size 4 44,1 lb-in 5,0 Nm
! X8
44,1 lb-in 5,0 Nm
! X8
Make sure that the bridging bar is fitted to the correct set of terminals.
There are two references available: one for ratings up to 125A, and another for 160A rating.
°C
°K
The enclosure must be wall-mounted using screws (not supplied). Recommended size: M6 50 mm (minimum).
Weight : between 8 and 10 kg, depending on the accessories.
Only 1 aux contact block may be installed when using this enclosure.
230mm (M6)
325mm (M6)
410 mm
305 mm 150 mm
Load Mains Genset
Only 1 aux contact block may be installed when using this enclosure.
385 mm
225 mm (M6)
275 mm (M6)
385 mm
193 mm
N N N
Max cable size 25 mm²
/
Enables you to allocate additional space to the polycarobonate enclosure (ref. 1309 9006).
Hexagonal Metric
Allen size 4
5,0 Nm
10 to
70 mm²
15mm
It is essential to tighten all used terminals, with cables and/or bridging bars, before use.
21 24 22
1 3 5 7 01 04 02
OK START
POWER
N L1 N L1 NOK STOP
Pn : 5VA !
207 208 209 210 63 64 73 74 I max : 30A (35ms)
L1 N L1 N U = 176-288 Vac 45-65 Hz
L1 L2 L1 L2
AUT
U U TEST
U = 176-288 Vac 45-65 Hz AUT Priority
SI SII
5 A AC1
250 Vac
2 4 6 8 2 4 6 8 12 14 11 1BL - 1P - Position B L1 / / N
Single (dip switch
phase down) N / / L1
21 24 22
4NBL - 3P - Position L1 L2 L3 N
1 3 5 7 1 3 5 7 01 04 02
Three-phase A
with neutral (dip switch up) N L1 L2 L3
OK START
1P L1 N L1 N NOK STOP
B
207 208 209 210 63 64 73 74 3NBL - 3P - Position L1 L2 L3 Neutral
1P L1
B
N L1 N 2A 30Vdc
1A 125Vac Three-phase A transfo
63 64 0,5A 230Vac
resistive
without (dip switch
A
3P L1 L2 L3 N L1 L2 L3 N max 60W or 250VA
Neutre L3 L2 L1
AUT
A
N L1 L2 L3 N L1 L2 L3
2A 30Vdc
1A 125Vac neutral* up) transfo
3P 73 74 0,5A 230Vac
TEST resistive
max 60W or 250VA
2 4 6 8 2 4 6 8
250 Vac
2BL - 1P - Position B / L1 L2 /
12 14 11
Two-phase (dip switch
abaissé)
21 24 22 3BL - Three- 3P - Position A L1 L2 L3 /
1 3 5 7 1 3 5 7
phase without (dip switch
01 04 02
neutral abaissé) / L1 L2 L3
1P
L1 L2 L1 L2
FAULT START
4NBL - 3P - Position A L1 L2 L3 N
OK STOP
B
A 207 208 209 210 63 64 73 74 Three-phase (dip switch
3P L1 L2 L3 L1 L2 L3 2A 30Vdc
1A 125Vac with neutral abaissé) N L1 L2 L3
A 63 64 0,5A 230Vac
resistive
3P L1 L2 L3 L1 L2 L3 max 60W or 250VA
AUT
A 2A 30Vdc
3P L1 L2 L3 N L1 L2 L3 N 1A 125Vac
73 74 0,5A 230Vac
TEST resistive
A max 60W or 250VA
3P N L1 L2 L3 N L1 L2 L3
AUT / PRIORITY
OK
OK
A new product must have the neutral configuration pre-programmed as on the left or on the right at
the first start up using a real (not a recreated) 3 phase + neutral supply.
Load
L1 L2 L3
ATyS g M
2 4 6 8 2 4 6 8 Inputs
I II
Priority/test
retransfer
Common
Inhibition
Product Genset
Priority/
1 3 5 7 1 3 5 7
available start
N N
207 208 209 210 63 64 73 74
RM32 2P RM32 2P
2 A aM RM1 RM2 2 A aM
1 A aM 1 A aM
-T1 -T2
0 400
230 230
400 0
Load Step 1
It is first necessary to connect the ATyS g M in three-phase
+ neutral (4NBL) to allow configuration of the neutral position
5 A AC1
(neutral position is detected at the first power-up).
250 Vac
2 4 6 8 2 4 6 8 12 14 11
Step 2
Connect the autotransformers.
21 24 22
eutral must be connected as shown in the
N
1 3 5 7 1 3 5 7 01 04 02
drawing above in section «10.3.4.1. Auto-
OK START transformer connections», page 30
1P L1 N L1 N NOK STOP
B
207 208 209 210 63 64 73 74
1P L1
B
N L1 N 2A 30Vdc
1A 125Vac
A 63 64 0,5A 230Vac
resistive
3P L1 L2 L3 N L1 L2 L3 N max 60W or 250VA
AUT
A 2A 30Vdc
1A 125Vac
3P N L1 L2 L3 N L1 L2 L3 73 74 0,5A 230Vac
TEST resistive
max 60W or 250VA
AUT / PRIORITY
SI SII
OK
10.3.4.3. Reset
OK of neutral position
In case the network is not recognized by the ATyS g M (or in case you would like to change the neutral position),
proceed as follows:
Step 1
Ensure that the product is powered and within voltage limits.
Open the AUTO/MANU cover.
Step 2
Set DIP Switch 1 from 3P to 1P.
Step 3
Set DIP Switch 1 from 1P to 3P.
Step 4
Close the cover.
11 14 12 11 14 12
11 14 12 11 14 1112 14 12 1114 14
11 14 1112 12 12
11 14 12 11 14 12
01 04 02 01 04 02
01 04 0102 04 02 01 04 0102 04 02
1309 0001
1 3 5 7 01 04 02 1 3 5 7 1 3 5 7 1309 0001 01 04 02
1309 0011
1 3 5 7 01 04 02 1 3 5 7 1 3 5 7 01 04 02
O1 O2 O1 O2
O1 O2 O1 O2
207208 209 210 63 64 73 74 207208 209 210 63 64 73 74
207208 209 210 63 64 73 74 207208 209 210 63 64 73 74
/ /
/ /
SI SII
I1 I2 I3
I1 I2 I3
I1 I2 I3
I1 I2 I3
SI SII
Capacité de raccordement
Capacité de raccordement
0,5 to 2,5 mm 2 Slotted head 3 mm
0,5 to 2,5 #mm
0,5 to 2,5 mm²
2 Slotted head3,97
20 to # 14 AWG 3 mm
lb-in 0,5 Nm
# 20 to # 140,5 AWGto 1,5 mm3,97
2 lb-in 0,5 Nm
2
0,5 to 1,5 mm
0,5 to 1,5 mm²# 20 to # 16 AWG
# 20 to # 16 AWG
6 mm / 0,236 "
6 mm 6 mm / 0,236 "
2P
4P
Status Recommended
Output
Type Terminal no. Application of the Description connection
characteristics
contact cross-section
Inputs I1: 207 / 208 Network/ With priority
Network
Without priority Dry potential
Network- Automatic retransfer free contact
Genset.
Manual Retransfer
I1: 207 / 209 Network/ Source priority 1
Network
Source priority 2 Dry potential
Network- Stop the test on load free contact
Genset.
Test on load
I3: 207 / 210 Network- AUTO mode
Network or Dry potential 0.5 to 2.5 mm²
Network- Automatic mode inhibition
free contact (rigid)
Generating set
Outputs O1: 63 / 64 Network- Product not available : Resistive load 0.5 to 1.5 mm²
Network or - Manual mode 2A 30 Vdc (stranded)
Network- - Command default
Generating set - Electronic default 0.5A 230Vac
- No source Pmax : 60W or
Product available 125VA
Umax : 30Vdc
or 230Vac
O2: 73 / 74 Network- No start command genset Resistive load
Genset. Generating set starting 2A 30 Vdc
0.5A 230Vac
Pmax : 60W or
125VA
Umax : 30Vdc
or 230Vac
Recommended
Terminal no. Status of Output
Type the contact Description connection
characteristics cross-section
Auxiliary 250V AC 5A AC1
contact 11/12/14 11
14
12 Changeover switch in position I 24VDC 2A
block
AC13 - 250VAC - 2A
1309 0001
250V AC 5A AC1
24
21/22/24 21 22 Changeover switch in position II 24VDC 2A
AC13 - 250VAC - 2A
01/02/04 01
04
02
250V AC 5A AC1
Changeover switch in position 0 24VDC 2A 0.5 to 2.5 mm²
AC13 - 250VAC - 2A (rigid)
Auxiliary 250V AC 5A AC1 0.5 to 1.5 mm²
contact 11/12/14 Changeover switch in position I 24VDC 2A
block (stranded)
AC13 - 250VAC - 2A
1309 0011 11
14
12
250V AC 5A AC1
24
21/22/24 21 22 Changeover switch in position II 24VDC 2A
04 AC13 - 250VAC - 2A
01 02
01/02/04 250V AC 5A AC1
Changeover switch in position 0 24VDC 2A
AC13 - 250VAC - 2A
Position
Position I I
Position
Position 0 0
Position
Position II II
C.A. Position
C.A. Position I I 11-14 Closed
11-12 Open
C.A. Position
C.A. Position 0 0 01-04 Closed
01-02 Open
C.A. Position
C.A. Position II II 21-24 Closed
21-22 Open
5 4 3
4 3
5 5 6 6
1 2
1. Locking
• Option to padlock using a 1 x 8 mm max. padlock.
2. AUT/MAN cover
• Open the cover to switch to manual mode.
• Close the cover to return to automatic (remote control) mode.
• Open and close the cover to clear faults.
5. Manual switching
• Insert the Allen key (5.0 mm) provided and turn to switch
manually.
• Manual operation is not possible when padlocked.
4 3
As soon as manual mode is activated, remote orders are inhibited (except the Genset start order in case
of a mains loss
Manual mode
The commissioning must always result in having at least 1 LED source available lit..
Therefore, the voltage and frequency must be within the defined thresholds.
Any action on the potentiometers changes the settings, even if the cover is closed.
A Dip switch settings B Hysteresis settings C Timer settings D Source supply voltage
and frequency
Auto-Configuration
Loss of priority source timer
u/f
Ensure that the supply
[hySt] voltage is available and
within the following limits:
Un: 176-288VAC
Fn: 45-65Hz
[hySt]
FT
Stop in 0 position: E-F FT: 0-60 sec.
• E: No stop in O position
• F: 2s stop in O position
Return of priority source timer
Type of application: G-H HYST: 20 %DU/F Press PROG for ≥ 2s
• G: Network - Genset DU: 5-20% u/f
• H: Network - Network DF: 3-10%
E LED info
Fault reset
The LED signalling and operation is only active when the product supply is available.
To set the dip switches, it is necessary to open the Auto/Manual cover.
Commissioning must always result in having at least 1 LED source available on.
(Therefore, the voltage and frequency must be within the defined thresholds).
Any action on the potentiometers will change the settings, even when the cover is closed.
127/230 Vac version 230/400 Vac version Loss of priority source timer Source availability LED
Fault reset
Type of application: G-H RT
• G: Network - Genset HYST: 20 %DU/F
• H: Network - Network DU: 5-20% RT: 0-30 min.
DF: 3-10%
AUTOMATIC MODE
Mode settings
G
MODE 1 MODE 2
AUT
AUT
MODE 3 MODE 4
Priority
Priority
H
207 209
TEST 5 sec.
FT 5 sec.
4 min.
5 sec. TEST
FT
5 sec.
207 209
Transfer from
Commutation Product
Produit in
en Source
Source Source
SourcemissingÉcoulement
Timer d’une
is Genset
Groupe Genset missing NORMAL
Groupe NORMAL PRIORITYII II
PRIORITY TEST
TEST
deI Ito II II
vers position
position II available
présente absente counting down
temporisation available
présent absent
Loss of
source 1
No
Return of
source 1 End of FT ?
Yes
Genset start
order
Genset
available
End of 5s No
timer + genset
still available?
Yes
Transfert
I -> II
Return of
source 1
No
Loss of End Loss of End of
source 1 RT? genset 5s?
Yes
Yes
Transfert End Genset
I I -> I CDT? stop
No
207 209
TEST 5 sec.
FT 5 sec.
207 208
4 min.
5 sec. TEST
5 sec.
207 208 RT
207 209
Transferfrom
Transfer Productinin
Product Source
Source SourcemissingTimer Timer
Source is counting
is Genset
Genset missing NORMAL
Genset
Genset NORMAL PRIORITY
PRIORITYII II TEST
TEST
from
I toI to
II II positionII
position available
available missing down
counting down available
available missing
Loss of
source 1
No Return of
End of FT ? source 1
Genset
start
No End of No
5 s timer ?
Genset always
on
Yes
Transfert
I -> II
Return of
source 1
No
Loss of End of
source 1 RT?
Yes
Loss of
genset
Opening of
contact 207/208
No
End of
5 s timer ?
Yes
Closing of contact
207/209
No
End of
5s timer ?
Yes
Genset start
order
Genset No
available
End of
5s timer + genset
still available ?
Yes
Transfert
I -> II
Yes Yes
Yes
Transfert End of Genset
I I -> I CDT? stop
No
207 209
TEST 5 sec.
FT
PRIORITY RT
5 sec. TEST
RT
FT PRIORITY
207 209
Transfer
Transfer Product
from I to II Product in
in position Source
Source available Source missing
Source Timer is counting
Timer is counting NORMAL
NORMAL PRIORITY IIII
PRIORITY TEST
TEST
from I to II position
I I available missing down down
Loss of
source 1
Return of No
End of
source 1 FT ?
Yes
Transfert
I -> II
Return of
source 1
No
Loss of End of Loss of End of
source 1 RT? source 2 5 s timer ?
Yes
Transfert
I I -> I
Closing of
contact 207/209
Priority source 2
End of No
Loss of
source 2 5 s timer ?
Yes
Return of
source 2
End of Transfert
RT? I -> II
Opening of
Loss of contact 207/209
source 2
No End of
Loss of
5 s timer ?
End of source 1
FT
Yes
Return of
source 1
Transfert
I I -> I
Transfert End of
I I -> I RT?
207 209
TEST 5 sec.
ou
FT
5 sec. TEST
ou
FT
207 209
Loss of
source 1
Return No
End of
source 1 FT?
Transfert
I -> II
Return of
source 1
Loss of
source 2
No
Return of End of
source 2 RT?
Yes
Transfert
I I -> I
Impulsion of
contact 207/209
Loss of End of No
source 2 5 s timer ?
Yes
Transfert
I -> II
Return of
source 1
Impulsion of
contact 207/209
No
Loss of End of
source 1 5 s timer ?
Yes
Transfert
I I -> I
I - O - II - O - I
Note: Maintenance should be planned carefully and carried out by qualified and authorised personnel. Consideration
of the critical level and application where the product is installed should form an essential and integral part of the
maintenance plan. Good engineering practice is imperative whilst all necessary precautions must be taken to ensure
that the intervention (whether directly or indirectly) remains safe in all aspects.
The use of any Megohmmeter is prohibited on this product as the connection terminals are intrinsically
connected to the sensing circuit.
In case of transformer / Genset, check that FT timer (Main Failure Timer) The Genset works and the
has finished counting down. LED «Emergency Source
• Use a stopwatch. Disponibility» is lit
• Start the stopwatch when the product has lost its Priority SOURCE.
- Contact 73 - 74 must be closed after 60s max (M-G application )
- GENSET run command = Contact 73-74 Closed
- GENSET stop = Contact 73-74 Open
The product does Check that the product is not in manual mode: The "AUT" LED is lit
not switch over after - Automatic mode = Cover closed
the Priority SOURCE
- Manual mode = Cover open
is lost
Check that automatic operation has not been inhibited by external control
commands (terminals 207-210)
Check the status of led « Emergency SOURCE availability ».If it is off, refer The "AUT" and "Emergency
to the symptom concerned (higher in the list) SOURCE Availability" LEDs
are lit
In case of tansformer / Transformer, check the setting of FT timer (Main At the end of the time delay,
Failure Timer). The duration of this time delay is between 0 and 60s. If the product switches to
necessary, use a stopwatch to check switching to SOURCE after FT mechanical position 0, and to
countdown. emergency SOURCE.
The product does Check that the product is not in manual mode: The "AUT" LED is lit
not switch over when - Automatic mode = Cover closed
the Priority SOURCE
- Manual mode = Cover open
is restored
Check that automatic operation has not been inhibited by external control
commands (terminals 207-210)
Check the state of the "Priority Source Availability" LED. If it is off, refer to The "AUT" and "Emergency
the symptom concerned (higher in the list) SOURCE Availability" LEDs
are lit
Check the setting of RT timer (Main Return Timer).The duration of this At the end of the time delay,
delay is between 0 and 30 min. Use a stopwatch to check the switch to the product switches to
Priority SOURCE after the RT timer. mechanical position 0, and to
priority SOURCE.
Check that the "manual retransfer" function is not active* Contact 207-208 must be
• Retransfer mode activated = Contact 207-208 closed open to enable switching to
priority SOURCE
• Retransfer mode desactivated = Contact 207-208 open
* if this function is not required.
Return to Priority Check CDT timer (Cool Down Timer) has finished counting down - Fixed The GenSet switches off and
SOURCE has been time delay:4 min led « Emergency SOURCE
executed, but the • Use a stopwatch. availability » is OFF
Emergency Source
- Start the stopwatch when the product has switched over to the Priority
(for a Generator)
SOURCE.
continues to operate
- Contact 73-74 must be open after time delay CDT has finished counting
down
Check that the product is not in Automatic mode: The "AUT" LED is lit
- Automatic mode = Cover closed
- Manual mode = Cover open
Check that automatic operation has not been inhibited by external control
commands (terminals 207-210)
Use the handle extension on the ALLEN key to check that the appropriate
adjustment torque is applied.
When using a single AC, check that the length of the screws used is not
greater than 20 mm
AUTOMATIC mode Check that the plastic pin is in place on the bottom of the cover.This pin The "AUT" LED is lit
is not activated even activates the sensor which indicates the position of the cover (open or
though the cover is closed).
closed Check that automatic operation has not been inhibited by external control
commands (terminals 207-210)
The product cannot Check the mechanical position of the changeover switch: Locking is possible
be locked • Locking is only possible in position 0 as standard
• Locking in positions 1-0-2 is possible by modifying the product in
accordance with the instructions
The product is faulty Check status of contact 63-64 (Product available): FAULT LED is OFF
• Product available: 63-64 = closed
Product non available :
63-64 = open
Product available = A product which is within voltage and frequency limits
without any internal failure.
Open and close the cover to reset the fault;