Академический Документы
Профессиональный Документы
Культура Документы
Abstract
A theoretical model of an earth–air heat exchanger (EAHE) is developed for predicting the outlet air temperature and cooling
potential of these devices in a hot, arid climate. The model is validated against other published models and shows good agreement. A
sub-soil temperature model adapted for the specific conditions in Kuwait is presented and its output compared with measurements
in two locations. A building model representative of a typical Kuwaiti dwelling has been implemented and all the models have been
encoded within the TRNSYS-IISIBAT environment. A typical meteorological year for Kuwait was prepared and used to predict the
cooling loads of the air-conditioned dwelling with and without the assistance of the EAHE. Simulation results showed that the
EAHE could provide a reduction of 1700 W in the peak cooling load, with an indoor temperature reduction of 2.8 1C during summer
peak hours (middle of July). The EAHE is shown to have the potential for reducing cooling energy demand in a typical house by
30% over the peak summer season.
r 2005 Elsevier Ltd. All rights reserved.
0360-1323/$ - see front matter r 2005 Elsevier Ltd. All rights reserved.
doi:10.1016/j.buildenv.2005.01.027
ARTICLE IN PRESS
236 F. Al-Ajmi et al. / Building and Environment 41 (2006) 235–244
climates like that of Kuwait. The EAHE (or earth system to provide thermal comfort inside a building
cooling pipe) functions by transferring heat from the complex in two different regions in India. The two
sub-soil environment to air flowing in a buried pipe. In earth–air tunnel systems were shown to be an effective
summer this provides pre-cooling of the outdoor way to precondition ambient air during the summer.
ventilation air, which serves to reduce the cooling load From the tables provided, the daily average cooling
of the building. capacity produced by the earth cooling tunnel system
Several experimental and analytical studies on EAHE was about 512 kWh and the heating capacity of the same
have been conducted. Francis [3] presented measured system was about 269 kWh (Fig. 1). Sawhney’s data
data showing the performance of an earth cooling tube showed that the cooling potential of the system in May
system in the Midwest region of the USA. A similar reaches 341 kWh, with a monthly average value of about
study was carried out by Akridge et al. [4] and Shingari 180 kWh. The reported coefficient of performance
[5] in the Punjab Agricultural University in India. (COP), defined as the useful heat gain divided by the
Akridge [6] found that the passive cooling performance fan energy consumption of the system, was 3.35.
of an EAHE in a humid region was limited. The earth Mihalakakou et al. [12] produced a parametrical
can provide sufficient sensible cooling, but the latent model of an EAHE using the methodology of regression
cooling cannot be adequately achieved. Dhaliwal et al. analysis through a simulation program developed by the
[7] presented a theoretical model of the earth cooling authors. Parametrical analysis of an extensive set of
pipe; the results were compared with experimental data input parameter values was used to develop a model that
obtained in North Carolina, USA and showed good can be regarded as a ‘‘chart method’’ and is capable of
agreement. In Japan, Qingysuan et al. [8] and Ishihara predicting the air temperature at the pipe outlet. The
et al. [9] performed experimental studies using an model was validated against experimental data.
earth cooling pipe, which resulted in a reduction in the
indoor temperature of a test house in Kumamoto by 1.2. The desert climate of Kuwait
more than 1 1C.
Sodha et al. [10] and Sawhney et al. [11] built a Kuwait is typical of a dry desert climate with the
cooling system that included a large earth–air tunnel highest air temperature being recorded in July and
ARTICLE IN PRESS
F. Al-Ajmi et al. / Building and Environment 41 (2006) 235–244 237
Fig. 1. Cross-section of the earth tunnel and its connection to the buildings (After Sodha et al. [10]).
55 Kuwait Weather
50 Data
40
35
30 Underground
25 environment
Ambient air Temperature (Type 263)
20
15
Fig. 3. The building model, buried tube (EAHE), soil environment
1
122
243
364
485
606
727
848
969
1090
1211
1332
1453
1574
1695
1816
1937
2058
2179
2300
2421
2542
2663
2784
2905
3026
3147
3268
3389
3510
2. The earth–air heat exchanger concept 1. The soil surrounding the pipe is isotropic, with
homogenous thermal conductivity in all ground
The concept of the EAHE or earth cooling pipe is that strata.
of a pipe or several pipes buried in the ground. One end 2. The thermal resistance of the pipe material is
of the pipe system (the inlet) acts as the entrance for negligible (thickness of the pipe is very small).
outdoor ambient air, whilst the other end of the pipe 3. The surface temperature of the ground can be
system (the outlet) releases air to the interior of a approximated to the ambient air temperature, which
building. Ambient air is drawn into the pipe inlet, the air equals the inlet air temperature.
travelling through the pipe exchanging heat with the 4. The pipe is of uniform circular cross-section.
pipe walls which are in contact with the surrounding 5. The thermal effect of soil surrounding the pipe is
underground environment. In this way, heat is trans- negligible after a distance ‘r’ from the pipe outer
ferred to or from the surrounding soil by conduction surface, where ‘r’ is the pipe radius.
ARTICLE IN PRESS
238 F. Al-Ajmi et al. / Building and Environment 41 (2006) 235–244
23.8
of soil temperature exhibit a sinusoidal pattern due to 23.1
23.5 Measured
22.0
the annual temperature fluctuation above. The predic-
tion accuracy of the undisturbed soil temperature is very 20.0
Jan Feb Mar Apr May Jun Jul Auq Sep Oct Nov Dec
sensitive to the values of the input parameters in the months
following equation:
Fig. 4. Predicted and measured soil temperature at 4 m depth with
0:5
T ðz;tÞ ¼ T m As eðzðp=8760aÞ Þ thermal diffusivity equal to 0.0038 m2/h [17].
" !#
2p z 8760 0:5
cos t t0 . ð1Þ
8760 2 pa
Ta = Tinlet Toutlet
However, when the variables are determined from field Soil Cylinder
measurements, the model generally yields errors of no 2r
more than 1:1 C [16]. L
Rc
r Air
3.1.1. Prediction of the Kuwaiti sub-soil temperature
The sub-surface soil temperature in Kuwait was
predicted using Eq. (1) with input parameters measured
at two Kuwaiti sites (a desert region and a coastal Fig. 5. Earth–air heat exchanger (EAHE) system with the layers is
shown in cross-section.
region) at depths of 1, 2 and 3 m in both regions. Values
found for the annual mean ground temperature (T m ),
annual surface temperature amplitude (As ), soil thermal
diffusivity (a), and phase constant (t0 ) were 27 1C,
13.3 1C, 0.0038 m2/h and 552 h, respectively (Al-Ajmi et A steady-state analysis gives the thermal resistance
al. [17]). Substituting these values into Eq. (1), the (Rs ) of the ‘‘soil annulus’’ as
Kuwaiti sub-surface soil temperature can be predicted lnðr1 =rÞ
using the following modified equation: Rs ¼ . (3)
2pLk
T ðz;tÞ ¼ 27 13:3eð0:31zÞ The thermal resistance (Rc ) due to convection heat
transfer between air in the pipe and the pipe inner
2p
cos ðt 552 428:31zÞ . ð2Þ surface may be expressed as
8760
1
This equation has been validated against measured soil Rc ¼ , (4)
temperature values (Kuwait International Airport [1] 2prLh
and Allison, [18]). Good agreement between measured where
and predicted values to an accuracy of 1 C has been Nukair
found (see Fig. 4) [17]. Eq. (2) has therefore been used in h¼ . (5)
d
this analysis.
Here, thermal conductivity of the air (kair ) in Eq. (5) is
calculated [22] using Eq. (6):
3.2. EAHE model development
The Nusselt number for flow inside a pipe is given by where DPt is the fan total pressure difference, q is
Incropera et al. [23] as volumetric flow rate and Zfan is fan total efficiency which
Nu ¼ 4:36 if Reo2300. may be expressed as the ratio of total air power to the
shaft power input.
The Nusselt number for fully developed laminar and The power supplied by the fan is regarded as being
turbulent flow in a circular pipe for the ranges converted to heat and to causing an increase in the
0:5pPrp2000 and 2300oReo5 106 is proposed by temperature of the air as it flows through the pipe,
Gnielinski, [24] as [25,26] hence
ðf =8ÞðRe 1000ÞPr DPt
Nu ¼ . (9) DT f ¼ . (18)
1 þ 12:7ðf =8Þ1=2 ðPr2=3 1Þ Zfan rC p
Here, f is the friction coefficient for smooth pipes and is Therefore the EAHE outlet air temperature may be
determined using Petukhov’s relationship [23], which is given by
expressed as
T outlet ¼ T 2 þ DT f . (19)
f ¼ ð0:79 ln Re 1:64Þ2 . (10)
Hence, total heat transferred along the pipe inclusive of
The total thermal resistance Rtot between pipe air and the fan-raised temperature inside the buried pipe may be
surrounding soil of the EAHE system may then be given by
determined from _ p ðT a T outlet Þ.
Q2 ¼ mC (20)
Rtot ¼ Rs þ Rc . (11)
_ p ðT a T 2 Þ.
Q1 ¼ mC (16) 20 Mihalakakou
15 EAHE
The fan energy consumed in blowing air through a pipe 10
2880 3380 3880 4380 4880 5380 5880 6380
is additional energy expenditure in the EAHE system. Time (hours)
The fan air power is given by
DPt q Fig. 6. EAHE model vs. Mihalakakou et al. [12] model predictions of
Pf ¼ , (17) outlet temperatures at depth 2 m using Kuwait TMY hourly weather
Zfan data [13].
ARTICLE IN PRESS
240 F. Al-Ajmi et al. / Building and Environment 41 (2006) 235–244
Table 1
Input parameters for three systems: Mihalakakou et al. [12], Shingari [5] and Dhaliwal et al. [7]
Table 2
EAHE model predictions vs. Dhaliwal et al. [7] experimental measurements
Time Air temperature Distance from the inlet of buried pipe to the outlet
At first hour 25.56 1C (Dhaliwal et al., 1984) 25.00 1C 24.40 1C 25.00 1C 24.40 1C 23.80 1C 23.80 1C
EAHE outlet temperature 24.94 1C 24.43 1C 23.97 1C 23.54 1C 23.15 1C 22.16 1C
After 17.5 h 20.55 1C (Dhaliwal et al., 1984) 20.55 1C 20.00 1C 20.00 1C 20.00 1C 20.00 1C 20.00 1C
EAHE outlet temperature 20.40 1C 20.27 1C 20.16 1C 20.05 1C 19.95 1C 19.71 1C
10cm Concrete
Block
2cm Cement
Plastering
Fig. 7. Building materials and construction for typical classical Kuwaiti walls and roof.
Table 4
Details of building space components and their thermophysical properties
No Name Material Thickness (mm) Thermal conductivity (W/mK) Density (kg/m3) Thermal capacity (KJ/kgK)
The simulations were conducted with the TRNSYS- and EAHE assistance was 2670 W. The peak cooling load
IISIBAT program using the EAHE model (Type264) reduction due to the operation of the EAHE was thus
and the Kuwaiti sub-soil model (Type263), as developed 1700 W (mid-July). The indoor temperature of the
in the paper, to investigate the thermal characteristics building for the ‘‘free running’’ condition (that is, without
and energy savings of a typical domestic Kuwaiti air conditioning) showed a reduction of 2.8 1C in the peak
building if assisted by an EAHE system. The example hours through use of the EAHE system (Fig. 10). The
building, modelled using TRNSYS-PREBID (which monthly total cooling energy consumptions for the
creates a file that has all building descriptions and period May–September are given in Table 5. It is evident
information) has the capability to let the user define the from Table 5 that the total cooling demand of the air
ventilation air as either ‘‘outside ambient air’’ or conditioning system can be decreased if the EAHE
‘‘other’’ in (each zone of) the building model. The outlet system is employed. The highest cooling capacity saving
air from the EAHE (Type264) is discharged into the is achieved in the months of July and August, with values
building and thus is taken as ‘‘other’’ for the ventilation of 411 and 420 kWh, respectively.
supply. This ventilation supply is in terms of ‘‘energy There are many factors that could be varied so as to
rate control’’ and is defined in TRNSYS-Type 56 as an increase the performance of the EAHE and improve the
energy gain/loss input where its additional energy is thermal comfort in the building. Some of these include
added to or subtracted from the zone. TRNSYS-Type the length of pipe, the number of pipes used, the
56 will then adjust the loads accordingly to the entire diameter of the pipe, velocity of air in the pipe, ground
load (TRNSYS/PREBID 3.0) [27]. moisture content and ground reflectivity. In practice, the
last two can be influenced by shading the ground surface
and by vegetation cover; these effects can in turn be
7. Building simulation with the EAHE model accounted for in the model by varying soil thermal
diffusivity and thermal conductivity (since soil moisture
The simulation was carried out for the period from content can vary—see, for example, Al-Ajmi et al. [17]).
May to September, which is the most arid and the hottest Whilst the indoor temperature cannot be maintained in
time of the year in Kuwait. The hourly cooling load the thermal comfort range by the use of the EAHE
simulation from hour 3650 (May) to 6420 (September) is system alone, such a system could usefully enhance the
shown in Fig. 9 for the example building. The simulation cooling capacity of an air conditioning system, and
was conducted for the case of the building being cooled thereby reduce energy consumption.
by air-conditioning both with and without assistance It can be seen that over the summer period
from the EAHE (Fig. 9). The peak heat removal rate considered, the incorporation of an EAHE system can
from the building with air-conditioning alone was reduce the cooling load on the building by some
calculated to be 4370 W while that with air-conditioning 1693 kWh, a saving of 30%.
4000
.cool of building without EAHE
.Cool of building with EAHE
3500
3000
2500
Cooling Loads
2000
1500
1000
500
0
3646 3796 3946 4096 4246 4396 4546 4696 4846 4996 5146 5296 5446 5596 5746 5896 6046 6196 6346 6496
Hours [3646-6572]
Fig. 9. Heat removed from the building by air conditioning during May–September with and without EAHE assistance (EAHE pipe length 60 m,
pipe diameter 0.25 m at depth 4 m below ground surface, air flow rate 100 kg/h).
ARTICLE IN PRESS
F. Al-Ajmi et al. / Building and Environment 41 (2006) 235–244 243
40
35
30
Indoor Temperature (C)
25
20
Indoor Temp.(C) with out EAHE
Indoor Temp.(C) with EAHE
15
10
0
3650
3720
3800
3870
3940
4020
4090
4170
4240
4310
4390
4460
4540
4610
4680
4760
4830
4910
4980
5050
5130
5200
5280
5350
5420
5500
5570
5650
5720
5790
5870
5940
6020
6090
6160
6240
6310
6390
Hours [3650-6410]
Fig. 10. Indoor air temperature of the building during the period May–September for the ‘‘free-running’’ situation, with and without EAHE
assistance.
It is concluded that there is potential for EAHE systems [13] Kuwait Institute for Scientific Research (KISR). Typical Meteor-
to make a useful contribution to energy saving in ological Year (TMY). Engineering Division, Weather Station
Department, Kuwait, 1995.
Kuwait, and in similar desert climate locations.
[14] Kusuda TO, Bean W. Annual variation of temperature field and
heat transfer under heated ground surface, slab-on grade floor
heat loss calculation. Building Science Services 156, Gaithersburg,
References MD: National Bureau of Standards; 1983.
[15] Moreland FL, Higgs F, Shih J, (editors.) Earth-covered buildings.
[1] Kuwait International Airport. Climatological summaries year Proceeding of conference in Fort Worth, Texas, U.S., May 1978,
1962–1982. Meteorological Department climatological division; Washington, DC: D.O.E., 1980.
(1st ed.). State of Kuwait, 1983. [16] Labs K. In: Cook J, editor. Passive cooling. Cambridge
[2] Ministry of Electricity and Water (MEW). Statistical yearbook Massachusetts, London, England: MIT Press; 1989.
2000, Electrical energy, (25th ed.) State of Kuwait, 2000. [17] Al-Ajmi F, Hanby VI, Loveday DL. Thermal performance of the
[3] Francis CE. Earth cooling tubes—case studies of three Midwest sub-soil environment in dry desert climate. ASHRAE Transac-
installations. Proceedings of the international passive cooling tion, 2002; 108, Pt. 2.
conference, Miami, Florida, 1981. p. 171–5. [18] Allison TR. Heat gains in Kuwait buildings, a simplified code,
[4] Akridge TM, Benton CC. Performance studies of a thermal Kuwait Institute for Scientific Research (KISR) -PPI/110 ENG-
envelope house. Phase II—cooling performance. Atlanta, Geor- PT-G-7931, 1979.
gia: Southern Solar Energy Center; 1981. [19] Elmer D, Gail S. A preliminary examination of the dehumidifica-
[5] Shingari BK. Earth tube heat exchanger. Poultry International tion potential of earth–air heat exchangers. Proceedings of the
1995;34(PT 14):92–7. international passive cooling conference, Miami, Florida, 1981. p.
[6] Akridge JM. Investigation of passive cooling techniques for hot- 161–5.
humid climates. Research report, College of Architecture, [20] Scot NR. Analysis and performance of an earth–air heat
Georgia Institute of Technology, Atlanta, Georgia, 1982. exchanger. Presented at the 1965 Winter meeting, American
[7] Dhaliwal AS, Goswami DY. Heat transfer analysis environment Society of Agricultural Engineer, Chicago, Illinois, 1965.
control using an underground air tunnel. ASME Solar Energy [21] Zoellick B. Predicted and observed performance of a buried
Div., Las Vegas, 1984. p. 505–10. earth–air heat exchanger cooling system. Proceedings of the 6th
[8] Qingysuan Zhang, Osamu Ishihara, Tetsuo Hayashi. Develop- national passive solar conference (6th 1 sponsors, Passive system
ment of residence with solar heating earth cooling, and air division); 1981. p. 822–6.
circulation. ASHRAE Transactions, 1994. p. 333–41. [22] Hanby V. Combustion and pollution control in heating systems.
[9] Ishihara O, Zhang Q. Cooling effects of earth tubes on dwellings. London, UK: Springer; 1994.
Proceedings of the 1992 ASME/JSES/KSES international solar [23] Incropera F, David De W. Introduction to heat transfer. 2nd ed.
energy conference, 1992. New York, NY: Wiley; 1996.
[10] Sodha MS, Sharma AK, Singh SP, Bansal Kumar A. Evaluation [24] Gnielinski V. New equation for heat and mass transfer
of an earth–air tunnel system for cooling/heating of a hospital in turbulent pipe and channel flow. Int. Chem. Eng. 1976;16:
complex. Building and Environment 1985;20(2):115–22. 359–68.
[11] Sawhney RL, Buddhi D, Thanu NM. An experimental study of [25] Jones WP. Air conditioning engineering, 4th ed. London: Edward
summer performance of a recirculation type underground airpipe air Arnold; 1994.
conditioning system. Building and Environment 1999;34:189–96. [26] Kreider J, Rabi A. Heating and cooling of buildings. Design for
[12] Mihalakakou G, Santamouris M, Asimakopoulos D. Tselepidaki. efficiency. New York: McGraw-Hill; 1994.
Parametric prediction of the buried pipes cooling potential [27] Solar Energy Laboratory. TRNSYS user manual. University of
for passive cooling applications. Solar Energy 1995;55(3):163–73. Wisconsin-Madison, 1996.