DC Power System -48VDC, up to 20.3kW

ACTURA Durus 48350

Benefits
ACTURA Durus 48350/25 system is optimized for common base station power
applications and balances performance, features and cost. This system offers
advanced features including, intelligent battery monitoring, remote monitoring
and low voltage battery disconnect. The cabinet comes fully equipped with
integrated AC and DC distribution.

This is the system of choice for installations in regions with poor AC regulation
and operates with ultra-wide input voltage and frequency ranges. In addition,
integrated surge protection is provided in the AC distribution unit.

Features
Provides up to 20.3kW in one cabinet
Operates with global AC voltages
Designed to operate in poor power quality environments
Front access and top cabling design for installation and maintenance
Optional Priority load function to support critical load functions
Cabinets equipped with AC surge protection and DC distribution
LCD display for alarm and component status
Low voltage battery disconnect to protect batteries
Utilizes CE approved 25A rectifier HD 4825-3
Optional remote monitoring and control
Integrated battery cabinet in PS48350-1B/25

ACTURA Durus 48350-1B/25

ACTURA Durus 48350


System Electrical Specifications
Nominal Output Voltage -48 Vdc
Operating Voltage Range -42 Vdc to -58 Vdc
Output Power(max) 20.3kW
Input Voltage 156 Vac to 500 Vac,3phase
Frequency 45HZ to 65HZ
Regulation < 0.5%
AC Ripple <100mVrms
Output Noise <200mV(pk-pk)

System Physical Specifications


Width x Depth 600mm(w) x 600mm(D)
Height, Weight 1200mm,120Kg
Height, Weight with integrated battery rack 1800mm,140Kg
Bettery Rack Dimension 456mm x 312mm x 520mm(W x H x D), 2 Subracks
Operating Temperature Range -5 to 55 (Full power to +45 )
ACTURA Durus 48350-1A/25
Operating Relative Humidity Range 95%RH
Withstand lighting surge AC side 10/700 us 5kV, 8/20 us 20kA
DC side 8/20 us 10kA

DC- distribution unit Fuse size Fuse type


Battery fuse 2 x 400 A NT1
Distribution fuses(Standard configuration) 8 x 63A MCB
5 x 32 A MCB
2 x 10 A MCB
PSM-A10 Monitoring module
Features
Menu operated and user friendly
Intelligent battery monitoring
Control of rectifier and batteries
Visual and audible alarms
Alarm history log
RS232, RS 422/428 and dry contacts
Optional web access through Power Star softwere,NMS. Web Browser

PSM-A10 Monitoring module

HD4825-3 Rectifier module


General Environment conditions
Safety CE, UL EN60950:1992, UL1950 Operation temperature -5 to + 45 (full power)
EMC EN 55022 Class A Storage temperature -40 to + 85
Dimensions 132 x 86 x 330 mm(H x W x D) Relative humidity 95% RH
Weight 3 kg Elevation 3000 m

Production: Marketing.The Emerson logo is a trademark and service mark of Emerson Electric Co. Subject to change without notice. Print: Icicle Production Co.,Ltd.,HongKong
Enclosure IP 20

Input characteristics Range Unit Comments Protection characteristics


Input voltage 90 - 290 VAC Single phase Short circuit protection, fallback current <1/3 rated current
Line frequency 45 - 65 HZ Output over-voltage protection, voltage set point selectable
Power Factor 0.99 Input over-voltage protection, automatically recoverable
Efficiency 90% Input under-voltage protection, automatically recoverable
Over-temperature protection , Theatsink > 85 power limiting, > 90 protection,
automatically recoverable

Output characteristics
Output voltage -42 to -58 VDC
Power 1450 W 25A@58V
Current 0 -27.5 A
Load regulation 0.4 %
Line regulation 0.1 %
Load share +/- 3 %
Temperature co-efficienct 0.02 % per 1 deg C
Peak to peak noise 150 mV pk-pk (0-20MHz)
Psophometric weighted noise 1 mV pk

Output power Output current(A)


HD4825-3 Rectifier module
100% 27.5

50% 25

0 90 176 290 Input voltage(V) 40 53.5 58 Output voltage(V)


Output Power and Input Voltage Relationship Output Current and Output Voltage Relationship