Вы находитесь на странице: 1из 16

इंटरनेट मानक

Disclosure to Promote the Right To Information


Whereas the Parliament of India has set out to provide a practical regime of right to
information for citizens to secure access to information under the control of public authorities,
in order to promote transparency and accountability in the working of every public authority,
and whereas the attached publication of the Bureau of Indian Standards is of particular interest
to the public, particularly disadvantaged communities and those engaged in the pursuit of
education and knowledge, the attached public safety standard is made available to promote the
timely dissemination of this information in an accurate manner to the public.

“जान1 का अ+धकार, जी1 का अ+धकार” “प0रा1 को छोड न' 5 तरफ”


Mazdoor Kisan Shakti Sangathan Jawaharlal Nehru
“The Right to Information, The Right to Live” “Step Out From the Old to the New”

IS 15549 (2005): Satationary Regulated Lead Acid Batteries


[ETD 11: Secondary Cells and Batteries]

“!ान $ एक न' भारत का +नम-ण”


Satyanarayan Gangaram Pitroda
“Invent a New India Using Knowledge”

“!ान एक ऐसा खजाना > जो कभी च0राया नहB जा सकता ह”


है”

Bhartṛhari—Nītiśatakam
“Knowledge is such a treasure which cannot be stolen”
IS 15549:2005

W’@)vmm

R??mmaqf?wa d?di-mlik

Indian Standard
STATIONARY VALVE REGULATED LEAD ACID
BATTERIES — SPECIFICATION

lCS 29.220.20

0 BIS 2005

BUREAU OF INDIAN STANDARDS


MANAK BHAVAN, 9 BAHADUR SHAH ZAFAR MARG
NEW DELHI 110002

June 2005 Price Group 5


Secondary Cells and Batteries Sectional Committee, ET 11

FOREWORD

This Indian Standard was adopted by the Bureau of Indian Standards, after the draft finalized by the Secondary
Cells and Batteries Sectional Committee had been approved by the Electrotechnical Division Council.
In the preparation of this standard, assistance has been derived frolm the following International Standards: ,
i
a) IEC 60896-2 ( 1995 ) Stationary lead acid batteries — General requirements and test methods — Part 2: ,’
,1

Valve regulated types

b) BS 6290-1:1982 Specification for general requirements

c) 6290-4: 1997 Specification for classifying valve regulated types

d) DIN 43539 Part 5:1986 Accumulators; tests; sealed lead storage batteries with grid-type plates and immobilized
electrolyte, maintenance free test methods
For the purpose of deciding whether a particular requirement of this standard is complied with the final
value, observed or calculated, expressing the result of a test or analysis, shall be rounded off in accordance with -{

IS 2: 1960 ‘Rules for rounding off numerical values ( revised )’. The number of significant places retained in the
rounded off value should be the same as that of the specified value in this standard.
AMENDMENT NO. 1 FEBRUARY 2012
TO
IS 15549 : 2005 STATIONARY VALVE REGULATED LEAD
ACID BATTERIES — SPECIFICATION

(Page 4, clause 12.1, line 26 from top, formula) – Substitute

[Ct  R (27 t )]’ ‘Ct [Ct  R (27 t )]’


‘C t  for
100 100

(ET 11)
Reprography Unit, BIS, New Delhi, India
IS 15549:2005

Indian Standard
STATIONARY VALVE REGULATED LEAD ACID
BATTERIES — SPECIFICATION
1 SCOPE within + 1 psi variation and manufacturer shall
declare the closing and opening pressure values.
This standard specifies capacities and performance
requirements and corresponding test methods for 3.3 Type Tests
all types of high integrity series stationary valve
Tests carried out to prove the conformity with the
regulated lead acid ( VRLA ) batteries. These batteries
requirements of this standard. These are intended
works on oxygen recombination principle and do not
to prove the general quality and design of a given
require any topping up with distilled water during its
life time. battery.

2 REFERENCES 3.4 Acceptance Tests

Tests carried out on samples selected from a lot for


The Indian Standards listed in Annex A contain
the purpose of verifying the acceptability of the lot.
provisions which through reference in this text,
constitute provisions of this standard. At the time 3.4.1 Lot
of publication, the editions indicated were valid. Al I
standards are subject to revision and parties to All batteries of the same type, design and rating
agreements based on this standard are encouraged manufactured by the same factory during the same
to investigate the possibility of applying the most recent period, using the same process and materials, offered
editions of the standards indicated in Annex A, for inspection at a time shall constitute a lot.

3 TERMINOLOGY 4 MATERIAL AND CONSTRUCTION

3.0 For the purpose of this standard, the definitions 4.1 General
given in IS 1885 ( Part 8 ) in addition to the following
All the materials used in the manufacture of stationary
shall apply.
valve regulated lead acid batteries shall be the best
3.1 Battery Supply Condition of their respective kind, free from flaws and defects
and shall conform to the relevant Indian Standard, if
Valve regulated lead acid batteries are supplied in any. There shall be no impurities that be harmful to
factory charged condition. The user of this battery the performance or life of a cell or battery.
shall follow the recommendations of supplier for
handling and storage instructions as per manufacturers 4.2 Containers
instructions. The cells shall be free standing type
The container shall be made of polypropylene co-
on a wooden support or assembled in metallic
polymer ( PPCP ), acrylonitrile butadiene styrene
trays/racks painted with acid resistant paint.
( ABS ), styrene — acrylonitrile ( SAN ) or any other
3.2 Venting Device — Pressure Regulating Valve acid resistant plastic mat&ial and shall have chemical
and electrochemical compatibility. The container shall
The venting device shall be designed to relieve the be fire retardant grade and shall comply with provisions
excessive pressure from the cell. Seating of valve either of UL 94 — V2/VO. The other requirement for plastic
shall be integral part of the cell lid or a provision in container shall be as per IS 1146.
lid for separate venting device. Each cell shall be
provided with venting device such that it cannot be 4.3 Cell Lids
opened without a proper tool. The valve shall be
The cell lids shall be made of same plastic material
capable to withstand the internal pressure specified
as that of container material and suitable either for
by the manufacturer.
resin bonding type or permanently sealing type
Each valve regulated venting device shall be provided based on the cell sealing design adopted by the
with flame arrestor capable of preventing the ingress manufacturer.
of moisture/flame into the cell interior when the valve
4.4 Plates
release the gas mixture.
The plates shal I be of pasted construction and of
The opening and closing pressure shall be
good workmanship. These shall be free from cracks,
1
IS 15549:2005

white patches and other imperfections, which may 7 RATING AND DESIGNATION
affect the life and performance of the battery.
7.1 Rating
4.5 Separators
The rating assigned to the cell or battery shall be
The separators used shall be of glass mat having the capacity expressed in ampere hours ( Ah )
high acid absorption capability, resistance to ( After correction to 27°C ) stated by the manufacturer
sulphuric acid and good insulating properties. The to the obtainable when the cell or battery is discharged
separator shall meet the test requirements as given at the 10-hour rate to an end voltage of 1.75 V. This
in this standard. rating is known as 10-hour rating of the cell or battery
and shall be designated as C 10.
4.6 Terminal Posts
7.2 Designation of Cells
Positive and negative terminals posts shall have built
in lead plated copper or brass inserts. Terminals of Cells shall be suitably designated in order to identifi
the type, capacity and rating, etc. f
cells shall be clearly and unmistakably identifiable and
marking shall be of permanent nature. Terminal posts 7.3 Standard Cell Capacities
shall be suitably sealed at the lid to prevent leakage
of any gas. Any gas escape shall be only through The individual cell capacities are 20, 40, 60, 80,
the venting device provided. 100, 120, 150,200,300,400,500, 600,800, 1000 and 1:

1500 Ah.
4.7 Fasteners
-{
For the cell capacities above 1500 Ah, paralleling of
Nuts and bolts for connecting the cells shall be made smaller capacities shal I be done.
of copper, brass or stainless steel. Copper or brass
nuts and bolts shall be effectively lead coated to prevent 7.4 Information to be Furnished by Purchaser with
corrosion. Stainless steel bolts and nuts shall be Enquiry/Order
passivated to prevent corrosion with acid.
7.4.1 Application of the battery: Float/ SPV,
4.8 Electrolyte 7.4.2 Number of identical batteries required in parallel.
The sulphuric and water used for the preparation of 7.4.3 Number of cells per battery.
electrolyte shall conform to IS 266 and IS 1069
respectively. 7.4.4 The rate of charge and discharge at which the
batteries are to work. ‘
4.9 Connectors
7.4.5 Capacity of the battery in Ampere hours at C 10.
When it is not possible to bolt the cell terminals
directly to assemble the battery, a separate lead coated 7.4.6 Type of stacking arrangement required depending
copper connectors or flexible copper cable connectors on floor loading and space available number of tiers/
of suitable cross-section shall be provided to join the stack.
cells. The lead plating on copper connectors shall
7.4.7 Type of specific stand required, if any.
not be less than 25 micron.
7.4.8 Proposed location of installation and ultimate
5 FLAME ARRESTOR consignee.
Valve regulated venting device of each cell shall be 7.4.9 Probable date of commissioning the battery.
provided with flame arrestors to prevent any sparking
flame from entering the cell. 7.4.10 Accessories and spares required, if any.

6 CHARGERS 7.4.11 Any other special condition/requirement, if


any.
This shall be constant potential type with current
and voltage limit ing faci lity. The charger shall have: 7.5 Information to be Furnished by the Battery
Supplier
a) Higher voltage cut off at 2.35 VPC
7.5.1 Capacity of the battery at C 10 rate.
b) Lower voltage cut off at 1.75 VPC
c) Voltage and current ripple <2 percent and 7.5.2 Manufacturer’s name.
5 percent respectively 7.5.3 Method of connections between cells, whether
d) Voltage regulation:+ 1 percent bolted or burnt.
The user shall follow the above recommendations. 7.5.4 Type and material of the container.
2
IS 15549:2005

7.5.5 Material of the separator. ( 12.9), and

7.5.6 Overall dimensions and weight of each complete m) Endurance life cycle test ( 12.10).
cell. NOTE — The capacity of other discharge rates like
C3, C5 shall be conducted by agreement between the
7.5.7 Space and floor loading in the desired purchaser and the supplier. Capacities atvariousdischarge
configuration. rates are given in Table 2.

7.5.8 Specific order, if any, in which the cells are to 10.1.2 Type tests shall be carried out on seven cells.
be arranged. Refer to sequence of type testing given in Table 3.

7.5.9 Procedure for monitoring the health of battery 10.1.3 If the different capacities of cells are made
during maintenance and preventive measures using, capacity same size of standard plate, any
required. one of the capacity cell shall be subjected for life test.
The test to be waived off after ascertaining the plate
7.5.10 Measures required to be taken at the site of size.
installation. Showing the state of discharge and
procedure for recoupment thereof. 10.1.4 [f any of the samples fails in the relevant type
test, the testing or inspecting authority may call for
8 MARKINGS ON CELL fresh samples not exceeding twice the original
The following information shall be durably number and subject them again to all the tests or
marked on the outside of the cell or battery or battery test in which the failure has occurred as agreed to
module between the lmanufacturer and the buyer. If there is
any failure in any of the retests, the type shall be
a) Manufacturers’ name, considered as not having passed the requirement of
b) Cell designation, this standard.
c) Cell Ah capacity, 10.1.5 During tests, if required, additional cells for
d) Month and year of manufacture, voltages matching requirement of the test
equipment shall be permitted.
e) Date on which charge given before dispatch,
and 11 ACCEPTANCE TESTS
o Next due date for freshening charge.
Visual exalnination ( 4.1 to 4.9 and 8,1). Checking of
9 TEMPERATURE FOR TESTS dimensions as per manufacturers drawing ( Refer to
Annex 11). Test for capacity and test for voltage during
The temperature range during the tests shall be discharge.
within 20 to 35°C.
A recommended sampling plan and criteria for
10 CLASSIFICATION OF TESTS
acceptance of a lot are given in Table 4.
10.1 Type Tests
12 TESTS PROCEDURES
10.1.1 The following shall constitute type tests:
12.1 Test for C 10 Capficity
a) Visual examination ( 4.1 to 4.9 and 8.1 ),
After standing on open circuit not less than 2 hours
b) Checking of dimension as per manufacturer’s and not more than 24 houfs from the completion of
drawing, a full charge, the cell shall be discharged through
c) Test for C 10 capacity and voltage during a suitable variable resistance at a constant current
discharge ( 12.1 ), of I = 0.1 x C 10 amperes. The discharge shall be
d) stopped when the close circuit voltage falls to
Test for C 1 capacity and voltage during
discharge ( 12.2), 1.75 V per cell.

e) Ampere hour ( 12.4) and watt hour efficiency ● During the discharge at 10-hour rate, the
test ( 12.5 ), voltmeter and ammeter readings shall be
Test for retention of charge ( 12.6), recorded every 5 minutes for first 15 minutes,
t)
thereafter up to the end voltage.
g) Acid retention capability test on separators
( 12.7). ● The discharge current shall be maintained
within + 1 percent of the specified rate of
h) Wicking test on separators ( 12.7), discharge.
j) Test on vent seal operation ( 12.8), ● The time in hours elapsing between ~he
k) Test for oxygen recombination efficiency beginning and end of discharge shall be t&en
3
IS 15549:2005

as period of discharge. Requirement


● The average temperature of the electrolyte Actual capacity corrected to 27°C shall not be less
during discharge shall be the average of the than 85 percent of the rated capacity in first cycle.
temperature readings noted at hourly The rated capacity shall be met within 5 cycles. The
intervals, for discharge rates between C5 and capacity shal I not exceed 120 percent of the rated
C 10. This shall be done by measuring the capacity.
temperature of the battery terminal as it will
be almost the same as that of electrolyte. 12.1.1 Voltages During C 10 Discharge Test
However, for discharge rates higher than C5 The cell voltage shall not be less than the following
( C 1 to C4 ), the average temperature values:
measurement shall be made from the cell
container surface. a) After six minutes from the start
of discharge : 1.98V
● Unless or otherwise agreed capacity test at
b) After six hours of discharge : 1.92V
10-hour rate as described above is normally
to be treated as the test discharge for the c) At ten hours of discharge : 1.75V
purpose of the acceptance of the cell. 12.2 Test for Cl Capacity
● On the first discharge, the cell shall give not
After standing on open circuit not less than 2 hours
less than 90 percent of the rated capacity.
and not more than 24 hours from the completion of
● The cell/battery shall give 100 percent rated a full charge and after satisfactory completion of
capacity within 5 discharges. C 10 capacity test, the cell shall be discharged through
● Once the rated capacity has been met on any a suitable variable resistance at a constant current of
discharge, further discharge cycles for I =0.5x C 10 amperes. The discharge shall be stopped
capacity need not be continued. when the close circuit voltage falls to 1.70 V per cell.

The capacity shall be corrected at 27°C by the following ● During the discharge at hour rate, the volt-
formula: meter and ammeter readings shall be
recorded every 5 minutes up to the end
C,+[C, xR(27-f)] voltage.
Capacity at 27°C = ● The discharge current shall be maintained
100
within +1 percent of the specified rate of
Where discharge.

Ct = observed capacity at t°C, ● The time in hours elapsing between the


beginningand end of discharge shall be
R = variation factor as per Table 1, and taken as period of discharge.
‘t’= average cell temperature measured at ● The average temperature of the electrolyte
terminals in “C. during discharge shall be the average of
the temperatures of the electrolyte noted at
Example for calculation of capacity at different
hourly intervals. This can be done by
temperature:
measuring the temperature of the battery
Capacity ‘C’ measured at 24?;= 1000 Ah terminal as it will be almost the same as that
of electrolyte.
IOOO+[1OOOXO.43X
● On the first discharge the cell shall give not
(27-24)]
Capacity at 27°C = less than 90 percent of the C 1 capacity.
100
● The cell/battery shall give 100 percent rated
= 1012,9Ah capacity within 3 discharges.

Table 1 ‘R’ Temperature Correction Factor Versus Rate of Discharge


( Clause 12.1)

Discharge C1O and C9 C8 C7 C6 C5 C4 C3 C2 cl


Rate above
Value of ‘R’ 0.43 0.45 0.47 0,50 0.54 0.58 0.62 0.68 0.76 0.90

NOTE — Capacity-temperature correction is not a true linear relationship.

4
-. , “..,
.,,.-=4—

IS 15549:2005

NOTE — In between of Cl discharge, test may be 12.5 Watt Hour Efficiency


conducted at low discharge rate ( for example: in between
two Cl discharge, C 10test maybe conducted). ● Watt hour efficiency shall be calculated by
multiplying the Ah efficiency by the ratio of
12.3 Capacity Test at Other Discharge Rates
average discharge and recharge voltage.
The capacity tests at discharge rates other than ● The value of discharge and recharge voltage
C 10, if required shall be conducted as per the shal I be calculated from the log sheets of Ah
agreement between the customer and the supplier. efficiency test.
The percentage of capacity at different discharge
rates are given in Table 2. Average voltage
during discharge
Table 2 Percentage of Capacity at Different Wh efficiency = x Ah efficiency
Average voltage
Discharge Rates .,
(v.)

during charge
Rate of Capacity Expressed End Cell
Requirement: Watt hour efficiency when calculated
Discharge as Percentage ( 0/0 ) Voltage ( V )
of Capacity at as above shall not be less than 80 percent.
Rate C 10
12.6 Test for Retention of Charge
cl 50.0 1.70
C2 63.3 1.70 ● Capacity shall be verified by performing C1O
C3 71.7 1.74 capacity test twice for average capacity and
the capacity shall be recorded as ‘C’.
C4 78.2 1.74
C5 83.3 1.75 ● The cell shall be fully recharged as per
1
manufacturers instructions.
I C8 I 95 I 1.75 I
1

Clo 100 1.75 ● After complete recharge, clean and wipe the
t

cell/battery surface dry. The cell shall be left


NOTES on open circuit for a period of 28 days without
1 The capacity at different discharge rates specified disturbance at 27 + 3“C.
above to be reached witbin 3 cycles ( other than C 10, ● After the storage period of 28 days, the cell
for which requirement are specified in 10.1 ) a~d these
shal I be discharged in accordance with
tests shall be conducted after the cell reaches the rated
capacity at C IO. capacity tests. The value of capacity
measured after storage is denoted by ‘C 1‘.
2 In between the higher rate of discharge, test shall be
conducted at low discharge rate ( Excample: in between
The loss of capacity ‘Y expressed as a percentage is
two C 3 discharge, C 10 test to be conducted ).
calculated as :
12.4 Ampere Hour Efficiency (c-c, ) ~loo
s=
● Fully charge the cell/battery as per c
manufacturers instructions.
Requirement: The loss in capacity as calculated above
● Discharge the cell/battery at I = 0.1 x C 10 shall not be more than 5 percent.
Amperes to an end voltage of 1.75 V.
12.7 Test on Separators ( Ref to Fig. 1 and Annex B
● Calculate the exact number of Ampere hours
for Test Set Up and Pr6cedure )
delivered.
● Recharge the battery for the same number ● The uncompressed water absorption of the
of Ampere hour at the same current. separator shall be at least 5 g of water per
● A second dischwge shall be made to the same gram of separator material.
cut ,off voltage as before. ● WICKING TEST: The total wicking height
● The efficiency of the cell/battery is then in separator shall not be less than 630 mm in
calculated as: 24 hours.

Ah delivered during ● ACID RETENTION TEST: lleminhnum acid


the second discharge retention capacity of the separator shall be
Ah efficiency ( ‘%o ) = x 100 6.5 g per gram of separator material.
Ah input given
during recharge 12.8 Test for Vent Seal Operation

Requirement: The Ah efficiency when calculated as ● Five regulating valves shall be selected for
above shall not be less than 90 percent. the test.
.5
IS 15549:2005

● The venting shall only occur through the Requirement: The gas recombination efficiency shall
valves. not be less than 90 percent.

Requirement : Opening and closing pressure of the 12.10 Endurance Life Cycle Test
valve shall he as per manufacturers specification and
shall be within +1 psi. To ascertain float service life as well as ageing, the
accelerated test as under shall be performed:
12.9 Test for Oxygen Recombination Efficiency
( Ref to Fig. 2 and Annex C for Test Set Up ) Part 1

1. The fully charged battery shall be overcharged ● Fully charge the cell/battery as per
at a current of C 10/100 for 96 consecutive manufacturers instructions.
hours. ● Discharge the cell/battery at I = 2.4 x C 10
2. Install the discharge gas collector. Amperes to an end voltage of 1.74 V
3. Within one hour of completion of ( 1 ) , the ( Equivalent to C 3 capacity ). This shall be
batteries shall be continuously charged at a treated as original test capacity.
current of C 10/200 for further 24 hours. Part 2
a) Immediately after completion of
24 hours, collection of gases emitted shall ● The cell/battery shall be charged as per the
be started. manufacturers instruction.
b) Collect the emitted gases for one hour. ● The cell/battery shall be immersed in hot water
bath maintained at a temperature of 55 +3°C
c) During the collection time, the ambient
till it has attained the bath temperature.
temperature of the batteries shall be
27+ 10°C and the outlet of the pipe for ● The cell/battery shall be discharged for 3 hours
the gas collector leading from the at the rate of I = 1.92x C 10 Amperes followed
batteries shall not be more than 50 mm by a charge at constant voltage of 2.33
below the water. V/cell and with current limit of40 percent of
its rated capacity for duration of 9 hours.
Then, the volume of gases emitted ( expressed at
● The above charge and discharge cycle shall
atmospheric pressure of 101.3 kPa at 27°C ) shall be
be repeated 30 times.
determined from the formula:
● This shall be treated as 1 life unit.
P 298 v 1
Jf.
—x Part 3
101.3 (t+273) x Q x ;
where ● After bringing the cell/battery to ambient
v. volume of gases emitted expressed at an temperature conditions, capacity test as per
atmospheric pressure 101.3 kPa at 27°C per Part I to be conducted as test discharge to
1 Ah of electricity discharge ( ml /Ah ), verify the capacity after each unit of life test.
p. atmospheric pressure during measurement, The above tests to be repeated till the capacity
1= ambient temperature of the collector falls below 80 percent of its original test capacity.
(“c ),
Requirement : Minimum five such life units shall be
v= amount of emitted gas collected ( ml ), Isuccessfully completed before the capacity falls below
Q= ampere hour input at the time of gas 80 percent of its original test capacity.
collection ( Current x Time ), and
The life of the battery may be arrived at by plotting
n . number of cells. the test results on Arrhennius graph and extrapolating
The gas recombination efficiency shall be calculated them.
by the formula. NOTES

(1- V)X1OO 1 This test shall be conducted on a cell. For a battery


Gas recombination efficiency ( % ) = module formed by paralleling the cells to enhance
684 capacity, this test need not to be repeated.

where 2 If the different capacities of cells are made using same


size plates and if higher capacity cel Is have undergone
684 is theoretical volume of gases emitted per Ah life test with same size plate, this test need not to be
at atmospheric pressure 101.3 kPa at 27”C. repeated.

6
-.. . I .-, .“- . .. ..-—”.

IS 15549:2005

13 SEQUENCE OF TYPE TESTING In order to ensure the randomness for selection, random
number tables shall be used ( see IS 4905 ).
The sequence of type testing shall be in accordance
with Table 3. The cells selected as above shall be subjected to the
acceptance test in the order specified.
Table 3 Sequence of Type Testing Cell Numbers

S1 Test Description 123456 Each of the batteries selected in the first stage in
No. accordance with COI2 of Table 4 above shall be tested
I. Visual examination Xxx xxx for acceptance. A battery shall be declared defective
if it fails in one or more of the acceptance tests.
2. Physical verification Xxx xxx
3. Test for C 10 capacity Xxx xxx
i) If the number of defective is less than or
4. Test for C 1 capacity xx———— equal to S1, the lot shall be considered as
5. Ampere hour and watt — — xx—— confirming to the requirements of the standard.
$

hour efficiency test


ii) If the number of defective is equal to or
6. Test for retention of xx————
greater than S2, the lot shall be considered
charge
as not conforming to the requirements of the
7. Test for oxygen — — xx——
standard.
recombination
efficiency iii) If the number of defective in the first stage
8. Endurance life cycIe — —— — xx is less than S2 and greater than S 1, a further
test sample of same size as taken in the first stage
shall be taken and tested.
14 SAMPLING SCHEME AND CRITERIA FOR iv) If the number of defective in the two samples
ACCEPTANCE combined is less than S3, the lot shall be
The number of cell to be selected at random considered as conforming to the requirements
from the lot shall be in accordance with co] 1 and of the standard. Otherwise, the lot shall be
CO12of Table 4. considered as not conforming to the
requirements of the standard.
Table 4 Sampling Scheme and Criteria for
Acceptance

Lot Size First Second 2N S1 S2 S3


Stage Stage
(1 ) (2) (3) (4) (5) (6) (7)
up to 50 2 2 4011
51 to 300 3 3 6011
301 to 500 5 5 10 0 2 2
501 to 1000 8 8 16 0 2 2
I 001 and above 13 13 26 0 3 4

7
IS 15549:2005

ANNEX A
( Clause 2 )

LIST OF REFERRED INDIAN STANDARDS

IS No Title IS No. Title

266:1993 Specification for sulphuric acid container for lead acid storage
( third revision) batteries ( second revision )

1069:1993 Specification for quality tolerances 1885 Electrotechnical vocabulary: Part 8


for water for storage batteries (Part 8): 1986 Secondary cells and batteries (first
( second revision) revi9ion )

1146:1981 Specification for rubber and plastics 4905:1968 Methods for random sampling

ANNEX B
(Clause 12.7)
PROCEDURE FOR WICKING TEST ON AGM SEPARATORS

B-1 Cut the separator of Size: 750 mm x 50 mm width from stand.


B-2 Take a stand and hold the separator vertically B-6 MeasuR the wicking height in separator from
as shown in Fig. 1. bottom ( Excluding the height of separator
B-3 Take D. M. Water in a jar and add small clamped ).
quantity of potassium permanganate for colour NOTES
identification.
1 Water level in jar shall be maintained throughout
B-4 Keep the jar on a stand and dip the separator the test.
bottom portion of 25 mm in solution ( Water + 2 The test to be conducted in closed environment.
Potassium permanganate ) for 24 h.
Figure 1 given below shows the wicking test set up:
B-5 After 24 h remove the separator from jar and

I 1
1

SEPARATOR

STAND

.-, .-. . . .
-------- --
. -.--m----
. . . ..-. . . . ,fARWITHD.M.WAT~+
\ / PERMANGANAT13
I

FIG. 1 WICKINGTESTSETUP

8
IS 15549:2005

ANNEX C
( Clause 12.9)
TEST FOR OXYGEN RECOMBINATION EFFICIENCY

+
11
..- M-uring
---- cylinder

----
H -..

---
H /
Wakr
BATTERY
..-

---
--- 4 r
t ------- 5- ------- “---------”-”-:----1
------- ------

NOTE — Test should be carried out on a minimum of 2 samples and both should meet the requirements.

FIG. 2 ARRANGEMENT
FORGAS COLLECTION
ANI)MEASUREMENT

,.

9
Bureau of Indian Standards

BIS is a statutory institution established under the Bureau of Indian Standards Act, 1986 to promote
harmonious development of the activities of standardization, marking and quality certification of goods and
attending to connected matters in the country.

Copyright

!31Shas the copyright of all its publications. No part of these publications may be reproduced in any form
without the prior permission in writing of BIS. This does not preclude the free use, in the course of implementing
the standard, of necessary details, such as symbols and sizes, type or grade designations. Enquiries relating
to copyright be addressed to the Director (Publications), BIS.

Review of Indian Standards

Amendments are issued to standards as the need arises on the basis of comments. Standards are also reviewed
periodically; a standard along with amendments is reaffirmed when such review indicates that no changes are
needed; if the review indicates that changes are needed, it is taken up for revision. Users of Indian Standards
should ascertain that they are in possession of the latest amendments or edition by referring to the latest issue
of ‘BIS Catalogue’ and ‘Standards : Monthly Additions’.

This Indian Standard has been developed from Doc : No. ET 11 ( 5388 ).

Amendments Issued Since Publication

Amend No. Date of Issue Text Affected

BUREAU OF INDIAN STANDARDS


Headquarters:

Manak Bhavan, 9 Bahadur Shah Zafar Marg, New Delhi 110002


Telephones: 23230131,2323337’5,2323 9402 Website: www.bis.org.in

Regional Offices: Telephones


I

Central : Manak Bhavan, 9 Bahadur Shah Zafar Marg 23237617


NEW DELHI 110002 { 23233841

Eastern : l/14C. 1.T. Scheme VII M,V. 1.P. Road, Kankurgachi 23378499,23378561
KOLKATA 700054 { 23378626,23379120
Northern : SCO 335-336, Sector 34-A, CHAN131GARH160022 2603843
{ 2609285
Southern: C. I. T. Campus, IV Cross Road, CHENNAI 600113 22541216,22541442
{ 22542519,22542315
Western : Manakalaya, E9 MIDC, Marol, Andheri (East) 28329295,28327858
MUMBAI 400093 { 28327891,28327892

Branches : AHMEDABAD. BANGALORE. BHOPAL. BHUBANESHWAR. COIMBATORE.


FARIDABAD. GHAZIABAD. GUWAHATI. HYDERABAD. JAIPUR. KANPUR.
LUCKNOW. NAGPUR. NALAGARH. PATNA. PUNE. RAJKOT. THIRUVANANTHAPURAM.
VISAKHAPATNAM.
Printed at New India Printing Press, Khurja, India

Вам также может понравиться