GENERAL NOTES:
LEGENDS
1. THE COMPLETE INSTALLATION OF FIRE ALARM SYSTEMS SHALL CONFIRM TO THE APPLICABLE SECTION
BREAK GLASS POINT OF NFPA-72 & OTHER NATIONAL COMPLYING ELECTRICAL CODES.
2. THE SYSTEM SHALL HAVE PROVISIONS FOR DISABLING AND ENABLING ALL CIRCUITS INDIVIDUALLY FOR
SMOKE DETECTOR MAINTENANCE -OR-TESTING PURPOSES.
3. EM IN PLANT ROOMS AND PARKING MUST BE IP-54.
SMOKE DETECTOR WITH BUILT IN SOUNDER 4. EXIT IN CAR PARKING AND PLANT ROOMS MUST BE IP-54.
4750
5. ELECTRICAL OPERATED DOORS MUST BE INTERLOCKED WITH FIRE ALARM SYSTEM AND MUST BE KEPT
HEAT DETECTOR OPEN INCASE OF FIRE.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FORTHE COORDINATION OF ALL SERVICES.
7. THE FAHU's SHALL BE INTERLOCKED WITH FIRE ALARM SYSTEM & SHALL AUTOMATICALLY SWITCH-OFF
1x5W LED SELF-CONTAINED NON-MAINTAINED TYPE WITH 3 WHENEVERA SIGNAL IS INITIATED IN THE PANEL.
HOURS BACK-UP BATTERY IP-54 RECESSED MOUNTED 8. SHORT CIRCUIT PROTECTION FOR EVERY15 DETECTORS TO BE PROVIDED IN GENERAL AREAS AND IN
CHANGE OF FLOORS /FIRE ZONES.
1x5W LED SELF-CONTAINED NON MAINTAINED TYPE 9. ALL EXIT DOORS MUST BE PROVIDED WITH EXIT LIGHTS.
EMERGENCY LIGHT WITH MONITORING MODULE & 3-HOUR 10. ALL EQUIPMENT SHALL BE TO THE APPROVAL OF CIVIL DEFENCE DEPARTMENT.
DURATION, IP-54 SURFACE MOUNTED, WITH 11. ALL GAPS & OPENINGS FOR THE CABLES TO BE FILLED WITH SMOKE /FLAME PROOF FIRE BARRIER.
RECHARGEABLE BATTERY & CHARGING MODULE 12. LIFTS TO BE INTERLOCKED WITH FIRE ALARM SYSTEM.
13. ANY DISCREPANCIES ARE TO BE BROUGHT TO THE ATTENTION OF ENGINEER AND RESOLVED BEFORE
1x5W LED SELF-CONTAINED NON-MAINTAINED WALL COMMENCEMENT OF ANY WORK.
MOUNTED TYPE EXIT LIGHT WITH 3-HOUR DURATION, IP-54 14. FIRE ALARM SYSTEM SHALL BE CONVENTIONAL TYPE.
15. MAIN FIRE PANEL MUST BE LINKED TO THE CIVIL DEFENCE CENTRAL MONITORING STATION THROUGH
2 WITH DIRECTIONS WITH ARROW , DCD APPROVED.
SPEAKER
A CIVIL DEFENCE APPROVED COMMUNICATION DEVICE WITH MODEM, DEDICATED TELEPHONE LINE
AND UNFUSED SPUR OUTLET.
16. ALL EXPOSED CONDUITS MUST BE GI.
17. ALL EMERGENCY LIGHTS MUST BE SELF CONTAINED & NON MAINTAINED TYPE.
1850
SOUNDER WITH FLASHER 18. ALL EXIT LIGHTS MUST BE NON-MAINTAINED.
19. FIRE PROOF CABLE TO BE USED FOR SPEAKER WIRING.
SOUNDER WITH FLASHER, W/P 20. FOR TYPE OF EMERGENCY / EXIT LUMINARIES REFER SPECIFICATIONS.
21. PULL BOX TO BE PROVIDED IN EVERY 15m RUN OF CONDUIT AND CHANGE IN DIRECTIONS AND SHALL
ALARM GONG BE INSTALLED NOT LESS THAN 42 INSH (1067mm) NOT MORE THAN 48 INSH (1219mm) ABOVE THE FINUSH
FLOOR.
23.
EXIT STICKERS MUST BE PROVIDED IN FIRE ESCAPE AND MUST BE PROVIDED IN FIRE ESCAPE DOORS,
IF EXIT LUMINAIRE IS NOT INSTALLED ABOVE THE DOOR.
THE SOUND LEVEL AT BED HEAD MUST BE 75 dB. SPECIALIST VENDORS TO PEOVIDE ADDITIONAL
SOUNDERS IF REQUIRED TO ACHIEVE THE REQUIREMENT.
24. ALL EQUIPMENT SHALL BE UL/FM LISTED AS PER THE CIVIL DEFENSE AND EHS REQUIREMENTS.
EMERGENCY LIGHT MONITORING PANEL
25. ACTUAL LOCATION FOR FIRE ALARM POINT TO BE COORDINATED WITH FALSE CEILING DRAWING.
26. MAXIMUM 20 NOS. FITTING PER CIRCUIT.
27. ALL FITTINGS ARE CONSIDER 8W.
28. ALL EQUIPMENT SHALL BE UL/FM LISTED AS PER THE CIVIL DEFENSE AND E.H.S.REQUIREMENT
29. DO NOT SCALE FROM THIS DRAWING.
SPACE 30. ALL DIMENSIONS ARE IN MM UNLESS NOTED OTHERWISE.
SHAFT
FOR MEP
WATER TANK
4987
4 SHAFT
AC
SHAFT
2360
AC
SHAFT
5
7000
41560
41210
G + 2 FLR. RESIDENTIAL
6
SHAFT
PLOT No.913-1403, UMM NAHAD 3RD, DUBAI, U.A.E.
2713
CLIENT/OWNER:
MAIN CONSULTANT:
8
KAIZEN
ARCHITECTS & ENGINEERS
4325
SHAFT
Info@kae.ae www.kae.ae
M.E.P. CONSULTANT:
9
475
10 INTERIOR DESIGNER:
1575
11
LANDSCAPE CONSULTANT:
4550
LIGHTING CONSULTANT:
SPA CONSULTANT:
4400
2770845.676 N
F&B CONSULTANT:
507786.906 E N 2770873.179
E 507794.969
13
CONTRACTOR :
28660
DRAWING TITLE:
FA-104