Вы находитесь на странице: 1из 4

Fifteenth National Power Systems Conference (NPSC), IIT Bombay, December 2008

A case study of Power quality improvement and


energy saving in textile industry using solid state
harmonic filter
M.K.Pradhan, Kamlesh Keharia, Rajesh Darapu, B. Mariappan
pradhan@emcoindia.com; krkeharia@emcoindia.com; rdarapu@emcoindia.com; bmariappan@emcoindia.com
R & D Department, EMCO Limited, Thane, India
x Demand reduction (kVA)
Abstract - This paper presents a case study of application of x Improved PF & voltage quality.
solid-state harmonic filter to improve electric power quality and x Reduction in I2R losses in conductor
reduce energy consumption in textile industries. Detailed studies x Reduction in equipment losses (motors, transformers,
were carried out in various textile firms in India and the effects
switchyard )
of poor power quality specially harmonics were analyzed on the
productivity and energy consumption. Harmonic current x Operating cost reduction
generated by nonlinear loads like motors driven by Variable x Reduction in taxes
Frequency Drives (VFD) cause power system heating and add to Soft savings include:
user power bills. The harmonic related losses are present in the x Reactive power savings (kVAR)
power cables, bus bars linking the loads with source, the power x Apparent power savings (kVA)
transformer itself. A more serious effect of harmonic loads
x Increased electrical equipment life.
served by transformer is due to an increase in winding eddy
current losses. The heat generated due to harmonics must be x Improved performance of equipment
removed in order to save electrical energy, thus leading to x Protection of sensitive electronic equipment.
savings in the utility bill. x Reduced maintenance, decrease consumption of
The paper is a case study where a 1.5 MVA transformer used spare parts
for powering the spinning section of a textile mill. The current x Space savings
harmonics is recorded with & without using the Active harmonic
x Better capacity utilization of transformer & generator
filter (AHF). The power parameters are recorded on both the
primary & secondary side of transformer to demonstrate how x Less Heating ventilation & Air conditioning (HVAC)
the active harmonic filter can reduce the effects of harmonics and system
save energy. The hard savings are the direct financial benefits to the
purchasing company. Each electrical parameter that
I. Introduction contributes to hard saving must be assessed, monitored &
Machineries which draw non sinusoidal currents when a measured accurately to claim the appropriate payback
sinusoidal voltage is applied create harmonics. These period.
harmonics are multiple of the fundamental frequency of an
electrical power system. Machineries used in a plant that draw II. Problems observed in textile industries
non sinusoidal currents are also known as non linear load.
Listed below are some of these devices. Power system apparatus overheating:
1) Adjustable speed drives It is normally observed that transformer gets overheated. Extra
2) DC Drives fans near transformers and at places water sprinkler are
3) Variable frequency drives installed to cool the transformers. LT distribution panel doors
4) 6 pulse converters are kept open and cooling fans and even air conditioning of
5) Power rectifiers panel room is carried out to cool the switchgears, busbars in
6) Uninterrupted Power Supplies the room. The bursting of PF capacitors due to excessive
7) Computers harmonics was reported. Over correction of PF leading to
If a facility has more than 15% non linear load, then a increase of LT voltage has damaged the sensitive components
harmonic study should be performed before applying the of VFD used in machineries.
Power Quality (PQ) solutions. Various methods are used in Detailed harmonic measurement study on presence of
order to promote the savings involved with applying PQ harmonics and their effects on more than 20 textile industries
solutions. The most important method followed in Textile have been carried out. Following table shows the %THD
mills is to claim significant benefits associated with the cost of content present at the PCC of various machineries.
solution equipment related to payback. Many are so called The heating of power transformer in the presence of
tangible or hard savings but many are intangible or related to harmonics is analyzed. The theoretical calculations of heat
payback. Many are so called tangible or hard savings but loss along with the measurement were carried out.
many are intangible or soft savings that are associated with or
a side benefit of the solution.
Hard savings include:
x Reduced energy (kWH) usage

598
Fifteenth National Power Systems Conference (NPSC), IIT Bombay, December 2008

Table 1 Current THD for textile mill machineries K-factor is the ratio of eddy current losses due to distorted
Sr. % Current current compared to the losses for the same rms fundamental
No Section THD frequency current.
1 Ring-Frames 40% The K factor is represented by,
h f
2 Winding/Autoconer 83% K ¦ I pu * h
2 2
h (3)
3 Loom Unit 38% h 1
4 Speed Frame 48% The K–factor determines the capability of a transformer to
5 Sizing 57% handle harmonics loads. By providing additional capacity (
large-size or multiple winding conductors), K- factor rated
6 Warping 61% transformers are capable of safely withstanding additional
7 Compressor 32% winding eddy current losses equal to K times the rated eddy
8 TFO 28% current loss.
Per unit losses:
9 Carding 13%
Since the greatest concern under harmonic load conditions
will be for over-heating of the windings, it is convenient to
III. Harmonic related (kWH) losses in transformer consider loss density in the windings on a per unit basis. (Base
Two main component areas to get maximum reduction in current is rated current & base loss density is the I2R loss
energy in a plant are density at rated current in watts per kg of conductor). Now the
A. The power transformer supporting transformer loss which is
harmonic loads
B. The cables carrying power to the
harmonic load PLL I 2 R  PEC  POSL can be written as,

A) Power Transformer:- PLL R pu =1+ PEC  R pu + POSL R pu (4)


The transformer loss is divided in to two components:-
a. No Load loss where POSL is the stray loss in the components other than the
b. Load related loss windings.
Given the eddy current loss under rated conditions for
The load losses are further divided in to two parts that are I2R transformer winding or portion of a winding,( PEC-R),the eddy
losses (PR), the ohmic losses & stray losses. The stray losses current loss due to any defined non sinusoidal load current can
are caused by eddy currents that produce stray electromagnetic be expressed as
h max 2
flux in the windings, core, core clamps, magnetic shields, tank Ih
PEC PECR * ¦ §¨ · * h 2 watts
I R ¸¹
walls & other structural parts. For a transformer feeding (5 )
h 1 ©
harmonic producing loads, the eddy current loss in the
windings may be the most dominant loss component in the The above equation can also be written in per unit form,
h max
transformer.
PEC pu PECR pu * ¦ I pu h
2
*h 2 (6)
For non sinusoidal load currents, the I2R Power loss (PR) can
h 1
be obtained by the sum of the squares of the fundamental and
The I2R loss at rated load is one per unit (by definition), but it
harmonic currents as shown in below equation.
will change for non sinusoidal load currents. The rms value of
hmax
the load current is given by,
PR
2
¦I h R h (1) 1
h 1 ªh max 2 º 2

where Rh is the winding resistance for the hth harmonic. I « ¦ I h » amps (7)
The winding eddy current loss in transformer increases «¬ h 1 »¼
proportional to the square of the product of harmonic current In per unit form this equation will be,
and its corresponding frequency. Given the winding eddy 1
2 2
current loss at the fundamental frequency PEC-1,the total eddy ªh max º
current losses including harmonic frequency component can I ( pu) « ¦ I h pu » amps (8)
be calculated by, «¬ h 1 »¼
hmax
The per unit loss density in the region of highest eddy-current
PEC PEC 1 ¦ I pu h
h 1
h
2 2
(2) loss can be calculated for the measured harmonic load current
by combining Equations 4, 6,and 8.
Where PEC-1 is the fundamental eddy current loss and Ih (pu) h max 2 h max

is the per unit harmonic current of hth order.


PLL (pu)= ¦Ih pu  PECR pu ¦Ih ( pu)2 h2
h 1 h 1
(9)

One of the factors called K factor is ideal to establish the where the first term on the RHS is the winding loss and the
increase in eddy current losses in a power transformer second term is eddy current loss.
supporting non-linear loads.

599
Fifteenth National Power Systems Conference (NPSC), IIT Bombay, December 2008

IV.Case study- 1.5MVA Transformer in the textile mill.


The transformer in the case study is loaded at 70 % of its 1500
kVA rating. Each phase is loaded at 350 KW and Irms is 1487
Amp. At this point the load is compensated, (that is, unity
power factor & no harmonics). The objective here is to
calculate the additional losses caused by harmonics in the load
current after finding out the K- factor.
Fig.1-A, Fig.1-B and Fig.1-C show the secondary current
waveform, the current harmonic Table & the Power & energy
data.

Fig.1-C Power and energy


Table -2 shows the secondary harmonic current and Ih is the
rms current of hth harmonic current, and I1 is the rms value of
the fundamental current. Total Current THD of 13.3% is taken
into calculation. K-factor is calculated using Equation -3 & it
is 1.483 (summation of last row in Table-2).
The eddy current losses will increase by 1.483 times due to
harmonic current in the transformer.
For the transformer used in case study the PEC-R is taken from
the transformer test record. It is 1221 watts.
All of the stray loss is assumed to be winding eddy current
Fig.1-A. Current Waveform loss. The division of eddy current loss between the windings is
assumed to be as 70% in the inner winding and 30% in the
outer winding of the transformer. Since the transformer turns
ratio exceeds 4:1 & the secondary current exceeds 1000 amps,
the secondary winding eddy current loss is 0.7 times PEC-R
[ref-1]. Eddy current loss distribution within each winding is
assumed to be nonuniform. The maximum eddy current loss
density is assumed to be in the region of the winding hottest
spot and is assumed to be 400% of the average eddy current
loss density for that winding. Taking the assumptions in to
account,
Max PEC-R= 2.8 PEC-R watts / 1.5( I2-R )2 R2 watts. (10)
where I2-R is the secondary (L.V.) rms sine wave line current
under rated frequency and load conditions (amperes) and R2 is
the dc resistance measured between two L.V. terminals
(ohms).
Fig. 1-B Current Harmonics Table

Table-2.Calculation for K Factor


Harmonic
1 3 5 7 9 11 13 15
Ih
Current (Ih) 1487 13.38 191.81 57.9 4.46 10.408 1.486 1.486
Ih (pu ) 1.0 0.0089 0.1278 0.0386 0.00297 0.0069 0.00099 0.00099
Ih (pu)2 1.0 0.00007 0.0163 0.0014 0.000008 0.000047 0.0000009 0.0000009
h2 1.0 9 25 49 81 121 169 225
Ih(pu)2h2 1.0 0.0007 0.408 0.073 0.0007 0.0005 0.0001 0.0001

Using equation (10), one can calculate max PEC-R PLL (pu )= 1.017+ 0.352 X 1.4831=1.539 pu

Max PEC-R= 2.8x 1221 / 1.5x6467 =0.352 pu, The transformer losses due to harmonic current will increase
by 54% approximately of the tested transformer load losses.
where 6467 watts is the L.V. copper loss as per manufacturers The no load loss increase due to harmonic load current is
test report on transformer. assumed less in comparison to the increase in load loss. Hence
The loss density produced by the harmonic current in the it is not taken in to consideration.
region of highest eddy-current loss using Equation (9) is,

600
Fifteenth National Power Systems Conference (NPSC), IIT Bombay, December 2008

The tested load loss given by the transformer manufacturer is 13.265 kW.
. the advent of new technology for improving the eddy current
Therefore the additional losses calculated due to harmonic losses for the transformer.
current flowing through transformer is (13.265 x 0.54) =7.16
kW. Acknowledgement
This additional loss can easily be mitigated by using a PQ The Authors are grateful to the EMCO Management for
solution gadget such as ACTIVE HARMONIC FILTER. Here granting permission to publish this paper.
the loss of 7.16 kW is less than 0.5% of the full load capability
of the transformer. References
Hence a high accuracy (below 0.5% class accuracy) revenue [1] American National Standard- Recommended practice for establishing
grade meter, CT s and PTs are required to measure the decrease transformer capability when supplying non sinusoidal load currents.
in losses in transformer with Active harmonic filters in ANSI/IEEE C57.110-1986. Volume, Issue, 1 Apr 1988 Page(s): -
operation.
[2] Thomas Key and jih-Sheng Lai Industry Applications Conference, 1995.
V. Experimental details of field test Thirtieth IAS Annual Meeting, IAS apos;95., Conference Record of the 1995
200 Amp (2x100) EMCOSINE Active Harmonic filter was IEEEVolume 2, Issue , 8-12 Oct 1995 Page(s):1101 - 1108 vol.2
installed in power distribution board, PDB 2 feeder of spinning
unit supplied by 1.5 MVA transformer- TX1. This transformer [3] Robert E. Fuhr “Save Energy and Improve Power Quality. A case study-
75 kVA Transformer.”, P.E. Power Systems Engineering,
also supports other linear loads in addition to the VFD loads
connected to PDB 2.
About The Authors
We could measure high current harmonics giving more than
30% of THD in PDB2.The readings were recorded to see the Mr. M. K. Pradhan, born in July 1954,completed his graduation in
improvement achieved by eliminating the harmonics in the Electronics and Communication Engineering from NIT, Kurukshetra in
feeder line leading 1976,followed by post graduation in 1978 in Microwave and Radar engineering
from Indian Institute of Technology at Kharagpur . He started his career in
Avionics Design Bureau, Hindustan Aeronautics Limited-Hyderabad and was
PDB 1
involved in design and development of Power amplifiers in Radar systems.
Since1990, Mr. Pradhan has been associated in R&D department of various
private sectors like Elcot Power Controls Ltd, TVS Electronics Ltd,& Numeric
PDB 3
IL Power System Ltd. Mr. Pradhan is presently the General Manager, EMCO’s
R&D unit and is responsible for research & technology development in the area
of Power quality
PDB4
Mr.Kamlesh Keharia obtained Master of Engineering in Electrical from M.S.
University Vadodara in November 2001 & B.E. in Power Electronics from L.E.

LT
IS ILh college, Morvi in May 2000. He has 6 years of experience in R&D of Power
Electronics & instrumentation. His area of interest is power electronic &
PDB 2 (NONLINEAR LOAD)
PANEL
Ih instrumentation. He has more than eight papers in
Mr. Rajesh Darapu: has done his B.Tech. In Electrical & Electronics from
EMCOSINE JNTU, Hyderabad in 2002. Also has done his M.Tech. In Electronics Design &
Utility 1.5 MVA AHF
x'mer TX1 Technology from CEDT (Centre for Electronics Design and Technology),
2 x 100 amps Dr.B.A.M.University, Aurangabad in 2006.He is with EMCO Ltd since
November ’06. He is working as Executive in Corporate R&D.
Figure 5.1 Experimental set-up Mr.B.Mariappan has graduated as Electrical Engineer from BIT Sathy, and
Table-3: Test results received M.Tech (Electrical) with second rank, from NIE Mysore in 2005.
Avg. Avg. Avg. Losses in Since 2006 he was a research Fellow of CSIO unit of CSIR Labs. Currently he
is working as Design Engineer (R&D), at EMCO LTD, Thane. His research
Losses Losses Losses percentage interests in include Power Quality, Power Electronics application to improve
(Before) (After) saved w r t rated Power Quality, Digital Signal processing etc.
in kW In kW (kW) capacity
12. 7 * 7.5 * 5.2 0.5 %

*Data taken from 12 Hr trend record of PDB with AHF ON


and AHF OFF.
VI. Conclusion
The maximum savings due to cancellation of harmonics from
the power transformer comes from the eddy current loss
component of the total load loss of the transformer. This eddy
current loss increases with the increase in current THD in the
load. Though current distortion of 30% and more are measured
near the harmonic load feeders, the current THD came down to
15% at the secondary of the transformer due to other feeders
supporting linear loads powered by the same transformer. The
saving in energy can be up to 1% of the rated load capacity in
textile mills where variable frequency drives with 6 –pulse
rectifiers are used. The savings may further come down with

601

Вам также может понравиться