GUARANTEE : The equipment carries a Engine Cranking time : Adjustable from1 to 15

warranty of 12 months from the date of purchase. seconds. A U T O S TA RT


The equipment will be replaced free of cost for any 1 3
manufacturing defect during its warranty period. Interval Between each start attempt : 10 seconds Start Reset
The equipment has to be sent to our factory for G EN
any replacement. The warranty is void and null for Engine Stop solenoid activation: Adjustable from 1 2 4
Stop
any of the following conditions: to 30 seconds.

1. The equipment should not be tampered Dimension : 96 mm x 96 mm x 110 mm depth 5


with or opened by any unauthorised
person/s.  Mode
Auto Manual

2. The equipment is wrongly connected,


misused or used in application other than Low Oil High Start Engine
Pressure Temp. Failure Overspeed
that for which it is recommended by the
manufacturer. Manufactured by : M IC R O L O G IC S Y S
3. The equipment is used in conditions of S.R.ELECTRO CONTROLS
voltage or current other than that Autostart is a state of the art Micro controller
recommended by the manufacturer. based AMF logic module used for Automatic
Bangalore Starting and stopping of Diesel Engine Pumps
on Pressure switch activation in a Fire control
Panel. The front fascia of the Autostart AMF
TECHNICAL SPECIFICATIONS logic module is shown above. There are 5
pushbuttons in the Autostart AMF logic
Operating voltage: 8 to 16 V DC for 12 V battery module. These are: Start (1), Stop (2), Reset
and 15 to 30 V DC for 24 V battery. (3), Acknowledge (4) and Mode (5), Visual
indications are provided by LEDs for the
Relays contact rating: 5 Amps Resistive at 12 V following: Power on (DC supply on), Pump on,
DC. Engine Start, Engine Stop Manual mode, Auto
mode, Low oil pressure, High engine
Battery Reverse polarity protection is built into temperature, Start failure and Engine Over-
AUTOSTART. speed. The functions of each of the above
pushbuttons are explained below :
Maximum input current at 12 V DC: 150 ma DC.
Idle current : 30 ma DC Start (1): To start the engine in manual mode.
0
Operating Temperature: 0 to + 55 C. Stop (2) : To stop the engine in manual mode

Engine starting delay after mains failure: Reset (3) : To reset the system after any fault
Adjustable from 0 to 4 minutes. SALIENT FEATURES OF conditions occurs.
AUTOSTART
Hooter Acknowledge (4) : Hooter silence Autostart can be operated in two modes of monitored whenever the Generator is running
pushbutton to switch off hooter after any fault operation : and in case of any fault the alarm / Hooter is
occurs. activated.
AUTO-MODE
Mode (5) : To select the manual and auto TERMINAL DETAILS:
mode of operation. On power up condition the Autostart will scan 1. BATTERY +VE
all the leds individually and then come to the 2. BATTERY –VE
Autostart performs the complete control Manual mode as indicated by the MANUAL 3.
functions in an AMF panel for a Fire Fighting led. When the MODE pushbutton is pressed 4. LOW LUBE OIL PRESSURE NO
Engine control panel : Automatic starting of the unit comes to the Auto mode. In the 5. LOW LUBE OIL PRESSURE NC
Engine Pump on activation of a Pressure Automode, Autostart will monitor pressure 6. HIGH ENGINE/WATER TEMP
switch, monitoring failure conditions of the switch status connected to #7. Whenever the 7. PRESSURE SWITCH
Engine like High Engine temperature, Low pressure switch is activated then the 10 . STOP RELAY OUTPUT
lube oil pressure and Engine Over-speed. Engine/Pump is automatically started after a 11. START RELAY OUTPUT
delay adjustable by T1. The cranking time of 12 OVERSPEED SWITCH
The terminal diagram of the Autostart is as the engine is adjustable by T2. If the Engine 13. HOOTER RELAY
shown below. does not start in the first attempt then two
more attempts are made to start the
Engine/Pump. If the Engine does not start
after the third attempt the system is locked
and Start fail Led comes on and the hooter is
switched on.

If the Engine starts successfully then the


system will automatically go to Manual Mode.
The enginer fault conditions are now
monitored continueously and an alarm/Hooter
There are 3 adjustable timers T1 to T3 located is activated whenever any fault occurs. The
at the rear side of the Autostart. These timers
engine does not stop for any failure conditions.
are: The Hooter/ Alarmcan be silenced by pressing
the hooter pushbutton and the system can be
T1 : Start delay timer adjustable from 0 to 4 reset by pressing the RESET key.
minutes. Default setting : 0 seconds
MANUAL MODE
T2: Engine cranking timer adjustable from 1
to 15 seconds. Default setting : 5 seconds Autostart can work in the manual mode by
selecting Manual mode through the MODE
T3 : Stop solenoid activation timer adjustable pushbutton. This is indicated by the manual
from 1 to 30 seconds. Default setting is 20 LED coming on. In the Manual mode all the
seconds operations can be done manually. Starting of
the generator, Stopping of the Generator, by
pressing the relevant pushbuttons in the
Autostart. Generator failure conditions will be