Specification sheet

Diesel
generator set
QSB7 series
engine
136 kVA–220 kVA 50 Hz
113 kW–200 kW 60 Hz

Description
This Cummins® Power Generation Cooling system – Standard integral set-
commercial generator set is a fully integrated mounted radiator system, designed and tested
power generation system, providing optimum for rated ambient temperatures, simplifies facility
performance, reliability, and versatility design requirements for rejected heat.
for stationary standby, prime power and
continuous duty applications. Control system – The PowerCommand®
electronic control is standard equipment and
provides total genset system integration,
Features including auto remote start/stop, alarm and
Cummins® heavy-duty engine – Rugged status message display.
4-cycle industrial diesel delivers reliable
power, low emissions and fast response to Enclosures – Optional weather-protective and
load changes. sound attenuated enclosures are available.

Optional permanet magnet generator Warranty – Backed by a comprehensive


(PMG) – Offers enhanced motor starting and warranty and Worldwide distributor network.
fault clearing short circuit capability.

Alternator – Low reactance 2/3 pitch


windings; low waveform distortion with
non-linear loads, fault clearing short-circuits
capability, and class H insulation.

Standby rating Prime rating Emissions compliance


50 Hz 60 Hz 50 Hz 60 Hz
Model kVA (kW) kW (kVA) kVA (kW) kW (kVA) EU stage Controller Data sheet
C150 D5e 150 (120) 136 (109) Stage IIIA 1.1 DS89-CPGK
C175 D5e 175 (140) 158 (126) Stage IIIA 1.1/1.2 DS329-CPGK
C200 D5e 200 (160) 182 (146) Stage IIIA 1.2 DS330-CPGK
C220 D5e 220 (176) 200 (160) Stage IIIA 1.2 DS331-CPGK
C125 D6e 125 (156) 113 (141) 1.1 DS90-CPGK
C150 D6e 150 (188) 135 (169) 1.1/1.2 DS332-CPGK
C175 D6e 175 (219) 160 (200) 1.2 DS333-CPGK
C200 D6e 200 (250) 180 (225) 1.2 DS334-CPGK

Our energy working for you. TM


cumminspower.com
© 2012 Cummins Power Generation Inc. | SS22-CPGK-RevA (05/12)
Generator set specifications
Governor regulation class ISO 8528 G3
Voltage regulation, no load to full load +/- 1%
Random voltage variation +/- 1%
Frequency regulation Isochronous
Random frequency variation +/- 0.25%
EMC compatibility In compliance with BS 800 and VDE levels G and N

Engine specifications
Design 4 cycle, in-line, turbo charged
Bore 107 mm
Stroke 124 mm
Displacement 6.69 liter (408.0 in3)
Cylinder block Cast iron, 6 cylinder
Battery capacity 100 AH
Battery charging alternator 70 amps
Starting voltage 12 volt, negative ground
Fuel system Direct injection
Fuel filter Spin on fuel filters with water separator
Air cleaner type Dry replaceable element with restriction indicator
Lube oil filter type(s) Spin on full flow filter
Standard cooling system 122 °F (50 °C) ambient radiator

Alternator specifications
Design Brushless, single bearing, revolving field
Stator 2/3 pitch
Rotor Single bearing, flexible disc
Insulation system Class H
Standard temperature rise Standby 125-163 °C
Exciter type Separately excited by PMG
Phase rotation A (U), B (V), C (W)
Alternator cooling Direct drive centrifugal blower fan
AC waveform total harmonic distortion (THDV) No load < 1.5%. Non distorting balanced linear load < 5%
Telephone influence factor (TIF) < 50 per NEMA MG1-22.43
Telephone harmonic factor (THF) < 2%

Available voltages
50 Hz Line–Neutral/Line–Line 60 Hz Line–Neutral/Line–Line
• 110/190 • 127/220 • 120/208 • 139/240 • 254/440
• 115/200 • 230/400 • 127/220 • 220/380* • 266/460
• 120/208 • 240/415 • 132/230 • 240/416 • 277/480
* Derate may be applicable at this voltage. Please consult the factory for details.

Generator set options and accessories


Engine Alternator Motorised 3 or 4 pole circuit Silencer
Water jacket heater Alternator heater breaker 9 dB attenation critical
220/240 V High humidity isolation Base frame silencer
Cooling Exciter voltage regulator Double wall fuel tank 25 dB residential – delivered
(PMG) loose
Antifreeze 50/50 (ethylene Warranty
glycol) Control panel 5 years for standby
Enclosure PowerCommand 3.3 application
Silent power canopy 4 pole main circuit breaker 2 years for prime
application
Note: Some options may not be available on all models - consult factory for availability.

Our energy working for you. TM


cumminspower.com
© 2012 Cummins Power Generation Inc. | SS22-CPGK-RevA (05/12)
Control system Service adjustments – The HMI includes provisions for
adjustment of generator set control functions. Adjustments
PowerCommand© 1.2 – The PowerCommand® are protected by a password. Functions include:
control system is a microprocessor-based generator set • Engine speed governor adjustments.
monitoring, metering and control system designed to meet
• Voltage regulation adjustments.
the demands of today’s engine driven generator sets. The
integration of all control functions into a single control • Cycle cranking.
system provides enhanced reliability and performance • Configurable fault set up.
compared to conventional generator set control systems. • Configurable output set up.
These control systems have been designed and tested to
• Meter calibration.
meet the harsh environment in which gensets are typically
applied. • Units of measurement.

Description Protective functions


The PowerCommand® generator set control is suitable for Protective functions include:
use on a wide range of generator sets in non-paralleling • Battle short mode.
applications. The PowerCommand control is compatible • Configurable alarm and status inputs.
with shunt or PMG excitation style. It is suitable for use
• Emergency stop.
with connectable or non reconnectable generators, and it
can be configured for any frequency, voltage and power • Hydro mechanical fuel system engine protection.
connection from 120-600 VAC line-to-line. • Overspeed shutdown.
Power for this control system is derived from the generator • Low lube oil pressure warning.
set starting batteries. The control functions over a voltage • High lube oil temperature warning/shutdown.
range from 8 VDC to 30 VDC.
• High engine temperature warning/shutdown.
Major features • Low coolant temperature warning.
• Sensor failure indication.
• 128 x 128 pixels graphic LED backlight LCD.
• Full authority electronic engine protection.
• Digital voltage regulation. Single phase full wave SCR
type regulator compatible with either shunt or PMG • General engine protection.
systems. • Low and high battery voltage warning.
• Digital engine speed governing (where applicable). • Weak battery warning.
• Generator set monitoring and protection. • Fail to start (overcrank) shutdown.
• Advanced over-current protection. • Fail to crank.
• Modbus® interface for interconnecting to customer • Cranking lockout.
equipment.
• 12 and 24 VDC battery operation. Alternator protection
• Warranty and service. Backed by a comprehensive • High AC voltage shutdown (59).
warranty and worldwide distributor service network. • Low AC voltage shutdown (27).
• Certification. Suitable for use on generator sets that are • Overcurrent warning/shutdown.
designed, manufactured, tested and certified to relevant • Under frequency shutdown (81 u).
UL, NFPA, ISO, IEC Mil Std., CE and CSA standards.
• Over frequency shutdown/warning (81 o).
Base control functions • Loss of sensing voltage shutdown.
• Field overload shutdown.
HDMI capability.
Operator adjustments – The HMI includes provisions for Field control interface
many set up and adjustment functions.
Input signals to the base control include:
Data logs – Includes engine run time, controller on time,
number of start attempts. • Remote start.
Fault history – Provides a record of the most recent fault • Local and emergency stop.
conditions with control hours time stamp. Up to 10 events • Configurable inputs: Control includes (4) input signals
are stored in the control non-volatile memory. from customer.

Alternator data Output signals from the PowerCommand control


• Voltage (single or three phase line-to-line and line-to include:
neutral). • Configurable relay outputs: Control includes (2) relay
• Current (single or three phase). output contacts rated at 2 A.
• KVA (three phase and total).
• Frequency.

Engine data
• Starting battery voltage.
• Engine speed.
• Engine temperature. PowerCommand© 1.2
• Engine oil pressure. control operator/
• Partial Full Authority Engine (FAE) data (where applicable). display panel

Our energy working for you. TM


cumminspower.com
© 2012 Cummins Power Generation Inc. | SS22-CPGK-RevA (05/12)
Ratings definitions OPEN

Emergency standby power (ESP):


Applicable for supplying power to varying electrical

C
load for the duration of power interruption of a reliable
utility source. Emergency standby power (ESP) is
in accordance with ISO 8528. Fuel stop power in
accordance with ISO 3046, AS 2789, DIN 6271 and
BS 5514. A B

Limited-time running power (LTP):


ENCLOSED
Applicable for supplying power to a constant electrical
load for limited hours. Limited time running power
(LTP) is in accordance with ISO 8528.

C
Prime power (PRP):
Applicable for supplying power to varying electrical
load for unlimited hours. Prime power (PRP) is in
A B
accordance with ISO 8528. Ten percent overload
capability is available in accordance with ISO 3046,
AS 2789, DIN 6271 and BS 5514. This outline drawing is to provide representative configuration
details for Model series only.
Base load (continuous) power (COP):
See respective model data sheet for specific model outline
Applicable for supplying power continuously to
drawing number.
a constant electrical load for unlimited hours.
Continuous power (COP) in accordance with
ISO 8528, ISO 3046, AS 2789, DIN 6271 and BS 5514. Do not use for installation design

Weight and dimensions


Open Enclosed
A B C Dry wt. Wet wt. A B C Dry wt. Wet wt.
Model mm mm mm (kg) (kg) mm mm mm (kg) (kg)
C150 D5e 2656 1100 1658 1467 1506 3980 1100 2062 2343 2947
C175 D5e 2656 1100 1658 1546 1572 3900 1100 2246 2557 3160
C200 D5e 2656 1100 1658 1544 1670 3900 1100 2246 2698 3301
C220 D5e 2656 1100 1658 1544 1670 3900 1100 2246 2698 3301
C125 D6e 2656 1100 1658 1467 1506 3980 1100 2062 2343 2947
C150 D6e 2656 1100 1658 1546 1572 3900 1100 2246 2387 2991
C175 D6e 2656 1100 1658 1544 1670 3900 1100 2246 2557 3160
C200 D6e 2656 1100 1658 1544 1670 3900 1100 2246 2698 3301
*Note: Weights represent a set with standard features. See outline drawings for weights of other configurations.

Certifications
This generator set is designed in facilities
This generator set is available with
certified to ISO 9001 and manufactured in
CE certification.
facilities certified to ISO 9001 or ISO 9002.

The Prototype Test Support (PTS) program All low voltage models are
verifies the performance integrity of the CSA certified to product
generator set design. Cummins Power class 4215-01.
Generation products bearing the PTS
symbol meet the prototype test requirements
of NFPA 110 for Level 1 systems.

Cummins Power Generation

Americas Asia Pacific Europe, CIS, Middle East and Africa


1400 73rd Avenue N.E. 10 Toh Guan Road #07-01 Manston Park Columbus Ave
Minneapolis, MN 55432 USA TT International Tradepark Manston Ramsgate
Phone 763 574 5000 Singapore 608838 Kent CT12 5BF United Kingdom
Fax 763 574 5298 Phone 65 6417 2388 Phone 44 1843 255000
Fax 65 6417 2399 Fax 44 1843 255902

Our energy working for you. TM

© 2012 Cummins Power Generation Inc. All rights reserved.


Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand, AmpSentry, InPower
and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names
may be trademarks or service marks of others. Specifications are subject to change without notice. cumminspower.com
SS22-CPGK-RevA (05/12)