Abstract – As power generation plants which use wind generating system is to use the induction generator connected
energy are increasingly integrated into existing electric power directly to the grid system.
systems, it becomes important to evaluate the power quality The induction generator has inherent advantages of cost
problem due to installation of wind turbine with the grid. The effectiveness and robustness. However; induction generators
influence of the wind turbine in the grid system concerning the
power quality measurements are-the active power, reactive
require reactive power for magnetization. When the generated
power, variation of voltage, flicker, harmonics, and electrical active power of an induction generator is varied due to wind,
behavior of switching operation and these are measured absorbed reactive power and terminal voltage of an induction
according to national/international guidelines.This paper generator can be significantly affected. A proper control
demonstrates new control scheme for STATIC COMPENSATOR scheme in wind energy generation system is required under
(STATCOM) which is connected at a point of common coupling normal operating condition to allow the proper control over
with a battery energy storage system (BESS) to mitigate the the active power production. In the event of increasing grid
power quality issues. The STATCOM control scheme for power disturbance, a battery energy storage system for wind energy
quality improvement is simulated using MATLAB/SIMULINK generating system is generally required to compensate the
in power system block set.
fluctuation generated by wind turbine [4].
Index Terms – Static Compensator (STATCOM), Battery A STATCOM based control technology has been
Energy Storage System (BESS), Power Quality proposed and implemented at point of common
coupling(PCC) for improving the power quality which can
I. INTRODUCTION technically manages the power level associates with the
commercial wind turbines.
Renewable energy resources are receiving considerable
attention in the continued growth and development of electric TABLE I
power systems, being the wind power production the fastest SYSTEM PARAMETERS
S.NO PARAMETERS RATINGS
growing type of renewable energy [1]. The need to integrate 1 GRID VOLTAGE 3-PHASE, 415V, 50HZ
the renewable energy like wind energy into power system is to 2 INDUCTION 3.35KVA, 415V, 50HZ, P=4,
make it possible to minimize the environmental impact on GENERATOR SPEED=440RPM
conventional plant[2][3] . The integration of wind energy into 3 LINE SERIES 0.07mH
INDUCTANCE
existing power system presents a technical challenges and that
4 INVERTER RATING DC LINK VOLTAGE=800V. DC
requires consideration of voltage regulation, stability,power LINK CAPACITANCE=100µF
quality problems. The power quality is an essential customer 5 IGBT RATING COLLECTOR
focused measure and is greatly affected by the operation of a VOLTAGE=1200V,FORWARD
distribution and transmission network. The issue of power CURRENT=50A,GATE
VOLTAGE=20V
quality is of great importance to the wind turbine. There has
6 LOAD NON-LINEAR LOAD=25KW
been an extensive growth and quick development in the PARAMETER
exploitation of wind energy in recent years.
The STATCOM is shunt connected at the bus where
During the normal operation, wind turbine produces a the wind turbine is connected to the power network to provide
continuous variable output power. These power variations are voltage regulation and improve the short-term transient
mainly caused by the effect of turbulence, wind shear, and voltage stability. The STATCOM control schemes are suitably
tower-shadow and of control system in the power system. designed and coordinated. The system is implemented in
Thus, the network needs to manage for such fluctuations. The SIMULINK/MATLAB simulation.
power quality issues can be viewed with respect to the wind II. POWER NETWORK MODEL
generation, transmission and distribution network, such as Power network model of the proposed grid connected
voltage sag, swells, flickers, harmonics etc. However the wind system is shown in Fig.1.The system consists of wind energy
generator introduces disturbances into the distribution generation system and battery energy storage system with
network. One of the simple methods of running a wind STATCOM. The battery energy storage system (BESS) is
used as an energy storage element for the purpose of voltage
regulation. The BESS will naturally maintain DC capacitor PCC in the grid system. The STATCOM compensator output
voltage constant and is best suited in STATCOM since it is varied according to the controlled strategy, so as to maintain
rapidly injects or absorbed reactive power to stabilize the grid the power quality norms in the grid system. The current
system. BESS can be used to level the power fluctuation by control strategy is included in the control scheme that defines
charging and discharging operation. The battery is connected the functional operation of the STATCOM compensator in the
in parallel to the dc capacitor of STATCOM [6]-[10] power system. A single STATCOM using insulated gate
bipolar transistor is proposed to have a reactive power support,
to the induction generator and to the nonlinear load in the grid
system.
The instantaneous values of reference three phase grid These current errors are given to hysteresis current
currents are computed as controller. The hysteresis controller then generates the
Fig .3 Simulation diagram for wind farm with STATCOM with Non linear load.
It is observed that the source current on the grid is The performance of the system is measured by switching
affected due to the effects of nonlinear load and wind the STATCOM at time t=0.7s in the system. When
generator, thus purity of waveform may be lost on both sides STATCOM controller is made ON, without change in any
in the system. The inverter output voltage under STATCOM other load condition parameters, it starts to mitigate for
operation with load variation is shown. The dynamic load does reactive demand as well as harmonic current. the result of
affect the inverter output voltage. The source current with and source voltage, source current and load current are shown in
without STATCOM operation is shown. This shows that the Fig4,Fig.5 and Fig.7.While the result of injected current from
unity power factor is maintained for the source power when STATCOM are shown in Fig.6.Supply voltage and current at
the STATCOM is in operation. PCC is shown in Fig.8
Fig. 4 Source voltage Fig .8 Supply voltage and current at PCC