The Doble Lemke PD-Smart is a versatile, multi-application
®

partial discharge (PD) analyzer especially designed for day to


day field use. With its easy-to-use software interface and
capability to conduct both on-line and off-line measurements,
there really is very few places you can’t use a PD-Smart.
It is well established that partial discharge activity is one of
the leading indications of insulation health and should be
measured as part of an asset management program.

Features
• Smart grafical User Interface
• Enhanced Digital Filtering
• Fully included Gating Features
• Rugged and Reliable

Multiple Applications

Transformers Rotating Machines Cables Switch Gears


Features
FFT of the background noise Rugged and Reliable Interference Rejection
The FFT of the background noise gives The unit is self-contained in a rugged Nothing is more problematic than the
you excellent information about the noise polyurethane case. Complete electrical interference caused by on-site noise. The
situation during your measurements isolation between the PD-Smart and PC PD-Smart has a variety of interference
and will support you in finding the right provides superior safety in high voltage rejection techniques to include windowing,
frequency slot. test setups. gating and frequency band shifting.
Synchronous Measurement Adjustable internal digital filter improve the
Gating
The system can easily extended for truly rejection of interference and broadcasting
Advanced Doble Lemke Noise-Gating-
synchronous multichannel measurements. frequencies.
Technology: The PD-Smart comes with
an integrated separate noise-gating The Star-Diagram helps to differentiate State of the Art
channel for noise-suppression via external various PD sources and Noise from each With advanced noise rejection, pulse
antenna. other. While measuring three phases sequence recording and frequency
simultaneously, the combined results are domain signal conditioning, the unit can
Digital Filtering
displayed in the Star-Diagram. be used to make critical decisions with
With the digital filtering it is quite easy to
True Phase Resolved Analysis data you can trust.
get rid of the noise, which occurs mainly
during onsite measurements. You have The PD-Smart measures both the PD Multiple Applications
full control over the high and the low and the actual applied voltage under The PD-Smart has a wide variety of
pass values without any limitations to the test. This way, users can ascertain the application to include cable, transformer,
bandwidth. effect of the voltage applied as well rotating machine and switchgear testing.
as the PD produced. Phase resolved It’s also possible to use the PD-Smart for
Smart User Interface
analysis provides keen insight into the both off-line and on-line testing.
The new smart user interface represents
characteristic and source of the PD. Specialized Cable Fault Location
over 40 years of Lemke`s knowledge in
design of measurement equipment. Each Analysis Tools Using time domain reflectometry, the PD-
user can now customize the layout of the Using internationally recognized Smart can locate cable faults.
dashboard to the user's needs. PD testing algorithms approved IEEE and IEC, the
will therefore be easier, faster and a great best possible diagnosis for fault conditions
experience. can be realized. These tools include Phi-
Q-N, Phi-Q and Phi-n displays.

Technical Specifications
Voltage supply: Input voltage: PD input protection:
• 8.4 V DC with battery • Voltage: 50 V rms (max) • Input protection against over-voltage
• External power supply • PD signal: 70 V rms (max) and short-circuit
(100 – 240 V, 50 – 60 Hz) Input impedance: PD input coupling:
Outputs: • Voltage: 1 MOhm • DC, AC
• 1 x FOL-Output with • PD signal: 50 Ohm Single pulse detection: < 4 ns
E/O converter as Ethernet Input frequency range:
• 1 x FOL-Output Downlink Max. double pulse
• Voltage: DC to 10 kHz
• 1 x FOL-Output Uplinl resolution: < 32 ns
• PD signal: DC to 20 MHz
• 1 x TNC Trigger output (time range, super position error < 1 %)
• 1 x FOL Trigger output Integration in time and frequency range
Max. pulse frequency: > 2,1 MPulses/sec
• Time Range: 140 ns … 8 μs
Inputs: • Frequency range: 35 kHz … 20 MHz Synchronizations
• 1 x TNC HF PD signal • Filter bandwiths free adjustable between units: < 800ps
• 1 x TNC LF voltage signal
• 1 x TNC HF Gating signal Dynamic range: Temperature range:
• Voltage: 16 bit, 80 dB • 0 °C to 40 °C (operation)
• PD signal: 16 bit, 100 dB • 0 °C to 60 °C (storage)
knowle
TOGETHER WE POWER THE WORLD®

ke
d
m

ge
Le

For more information, contact


Doble Engineering Company
PDinfo@doble.com
Corporate Headquarters
inSide
85 Walnut Street
Watertown, MA 02472 USA
Doble is ISO Certified
tel +1 617 926 4900
Doble is an ESCO Technologies Company
fax +1 617 926 0528
MKT-SL-Doble Lemke_PD-Smart -06/11

Вам также может понравиться