Вы находитесь на странице: 1из 12

R

TESTING

Lab Code: 201079-0

Report of Test
LLIA001029-001
Catalog Number: F-WP-100W/50K/BZ/HE
Wall mounted, cast aluminum housing, cast
aluminum heatsink, clear prismatic glass lens.
240 white LEDs with white plastic reflector tray over LEDs.
One Fahold FD-100H-042B LED driver.
120.0Vac, 60.00Hz, 0.7911A, 94.45W, 0.995PF, 4.5%THD(i)

Performance Summary
Total Light Output 11703 lm Power Factor 0.995
Luminaire Power 94.4 W THD(i) 4.5 %
Luminous Efficacy 124.0 lm/W Lateral Classification Type IV
Vertical Classification Short

% of Luminous Flux
BUG Rating B2-U4-G5 80°-90° Zone as
% of 0-90 lumens 10.2 %

PREPARED FOR : Topaz Lighting Corp, 925 Waverly Avenue, Holtsville, NY 11742, USA

(issuing laboratory) Page 1 of 12


11
R

TESTING

Lab Code: 201079-0

Test Report No. LLIA001029-001


Catalog Number: F-WP-100W/50K/BZ/HE
Wall mounted, cast aluminum housing, cast
aluminum heatsink, clear prismatic glass lens.
240 white LEDs with white plastic reflector tray over LEDs.
One Fahold FD-100H-042B LED driver.
120.0Vac, 60.00Hz, 0.7911A, 94.45W, 0.995PF, 4.5%THD(i)

(issuing laboratory) Page 2 of 12


R

TESTING

Lab Code: 201079-0

Test Report No. LLIA001029-001


Catalog Number: F-WP-100W/50K/BZ/HE
Wall mounted, cast aluminum housing, cast
aluminum heatsink, clear prismatic glass lens.
240 white LEDs with white plastic reflector tray over LEDs.
One Fahold FD-100H-042B LED driver.
120.0Vac, 60.00Hz, 0.7911A, 94.45W, 0.995PF, 4.5%THD(i)

Polar Light Distribution Curves

90 90

1500

60 60
3000

30 30
4500

House side / L270 L90 / 270 - Black, Plane of maximum - Red, L0 / 180 - Blue (cd) Street side / L90

Percentage Outputs
Upward Downward Total
Street Side 12.3 % 74.3 % 86.6 %
House Side 0.3 % 13.1 % 13.4 %
12.6 % 87.4 % 100.0 %

Report data based on absolute values as measured.

Signed:

Authorized Signatory Date of test 24-Sep-2018


Date of report 28-Sep-2018

(issuing laboratory) Page 3


2 of 12
11
R

TESTING

Lab Code: 201079-0

Test Report No. LLIA001029-001


Catalog Number: F-WP-100W/50K/BZ/HE
Wall mounted, cast aluminum housing, cast
aluminum heatsink, clear prismatic glass lens.
240 white LEDs with white plastic reflector tray over LEDs.
One Fahold FD-100H-042B LED driver.
120.0Vac, 60.00Hz, 0.7911A, 94.45W, 0.995PF, 4.5%THD(i)
Intensity in principal plane Principal Vertical Plane
(based on overall max intensity)
(L0.0)
Vertical Intensity
Angle (°) (cd)
0.0 2710.7
90
10.0 3301.0
20.0 4231.8
30.0 4136.5
35.0 2874.7
40.0 4466.6
45.0 3787.4
47.5 3890.3
50.0 5183.3
2000
52.5 5162.9
55.0 4021.5
57.5 3959.9
60
60.0 4810.7
62.5 4630.5
65.0 4286.0
67.5 3473.8
70.0 3928.7
72.5 3885.0 4000
75.0 3674.3
77.5 3502.8
80.0 3494.1
82.5 3258.2
85.0 2970.1
87.5 2908.0
90.0 2540.4 30
92.5 2339.8 6000
95.0 2164.6 Plane of maximum intensity (cd)
97.5 1650.5
100.0 1273.1 House side max intensity Street side max intensity
102.5 1070.4 2710.7 cd @ (90.0°, 0.0°) 5266.6 cd @ (0.0°, 50.5°)
105.0 936.9
120.0 488.4
135.0 336.8
150.0 233.6 Coordinates expressed in the C Type coordinate system
165.0 53.3 Data for the two symmetric halves of the luminaire has been averaged.
180.0 0.0

(issuing laboratory) Page 4


3 of 12
11
R

TESTING

Lab Code: 201079-0

Test Report No. LLIA001029-001


Catalog Number: F-WP-100W/50K/BZ/HE
Wall mounted, cast aluminum housing, cast
aluminum heatsink, clear prismatic glass lens.
240 white LEDs with white plastic reflector tray over LEDs.
One Fahold FD-100H-042B LED driver.
120.0Vac, 60.00Hz, 0.7911A, 94.45W, 0.995PF, 4.5%THD(i)
Intensity in principal cone Principal Conical Surface
(based on overall max intensity)

Lateral (V50.5) 60 30
Plane (°) (cd)
0 5266.6
15 4578.5
30 3307.2
40 3699.2
45 3425.5
50 2554.3
55 2321.9
60 2423.4
65 2385.0
70 2331.2 0
75 2100.2
80 1886.5
85 1673.0
90 1433.7
95 1180.6
100 844.5
105 684.6
110 557.2 2500
115 486.9
120 425.1
125 386.6 330
130 352.1
135 325.2
140 290.4
150 237.3 300
165 168.3 5000
180 156.3 House side Cone of maximum intensity (cd) Street side

House side max intensity Street side max intensity


2710.7 cd @ (90.0°, 0.0°) 5266.6 cd @ (0.0°, 50.5°)

Coordinates expressed in the C Type coordinate system


Data for the two symmetric halves of the luminaire has been averaged.

(issuing laboratory) Page 5


4 of 12
11
R

TESTING

Lab Code: 201079-0

Test Report No. LLIA001029-001


Catalog Number: F-WP-100W/50K/BZ/HE
Wall mounted, cast aluminum housing, cast
aluminum heatsink, clear prismatic glass lens.
240 white LEDs with white plastic reflector tray over LEDs.
One Fahold FD-100H-042B LED driver.
120.0Vac, 60.00Hz, 0.7911A, 94.45W, 0.995PF, 4.5%THD(i)

Polar curve through L90 / L270 Polar curve through L0 / L180

90 90 90

60 60
1000 2000

60

2000 4000

30 30

30
3000 6000

(L90) (cd) (L270) House side (L180) (cd) Street side (L0)

(issuing laboratory) Page 6


5 of 12
11
R

TESTING

Lab Code: 201079-0

Test Number: LLIA001029‐001
Catalog Number: F‐WP‐100W/50K/BZ/HE
Wall mounted, cast aluminum housing,  cast
aluminum heatsink, clear prismatic glass lens.
240 white LEDs with white plastic reflector tray over LEDs.
One Fahold FD‐100H‐042B LED driver.
120.0Vac, 60.00Hz, 0.7911A, 94.45W, 0.995PF, 4.5%THD(i)
Coefficients Of Utilization ‐ Zonal Cavity Method
Effective Floor Cavity Reflectance 0.20
RC 80 70 50 30 10 0
RW 70 50 30 10 70 50 30 10 50 30 10 50 30 10 50 30 10 0
0 116 116 116 116 112 112 112 112 104 104 104 97 97 97 91 91 91 88
1 102 96 90 85 98 92 87 83 86 82 78 80 76 73 74 72 69 66
2 92 82 73 67 88 79 71 65 73 67 61 68 63 58 63 59 55 52
3 83 71 61 54 79 68 59 52 63 56 50 59 53 48 55 50 45 42
4 75 62 52 45 72 60 51 44 56 48 42 52 45 40 48 43 38 35
5 69 55 45 38 66 53 44 37 49 42 36 46 39 34 43 37 33 30
6 63 49 40 33 61 48 39 32 44 37 31 42 35 30 39 33 28 26
7 59 44 35 29 56 43 34 28 40 33 27 38 31 26 35 30 25 23
8 55 40 31 25 52 39 31 25 37 29 24 35 28 23 33 27 22 20
9 51 37 28 23 49 36 28 22 34 27 22 32 25 21 30 24 20 18
10 48 34 26 20 46 33 25 20 31 24 19 30 23 19 28 22 18 16
For absolute test reports, CUs are expressed as a percentage of total lumen output. Calculations were based on published IES procedures, and are based on the zonal cavity method.  Basic 
assumptions: 1) Room surfaces are lambertian reflectors. 2) Incident flux on each surface is uniformly distributed. 3) The room is spectrally neutral. When luminaires are not evenly distributed 
throughout the room, or do not exhibit lateral symmetry, CU values may differ from actual performance.

Circle of Light Plot
Beam Width
(across 50% Nadir Illum)
Height(ft) Illuminance at Nadir (fc) 0‐180 90‐270

6.0 75.3 7.54 7.22

8.0 42.4 10.05 9.63

10.0 27.1 12.56 12.04

12.0 18.8 15.07 14.45

14.0 13.8 17.58 16.86

16.0 10.6 20.09 19.27

(issuing laboratory) Page 7


6 of 12
11
R

TESTING

Lab Code: 201079-0

Test Report No. LLIA001029-001


Catalog Number: F-WP-100W/50K/BZ/HE
Wall mounted, cast aluminum housing, cast
aluminum heatsink, clear prismatic glass lens.
240 white LEDs with white plastic reflector tray over LEDs.
One Fahold FD-100H-042B LED driver.
120.0Vac, 60.00Hz, 0.7911A, 94.45W, 0.995PF, 4.5%THD(i)

(issuing laboratory) Page 8


7 of 12
11
R

TESTING

Lab Code: 201079-0

Test Report No. LLIA001029-001


Catalog Number: F-WP-100W/50K/BZ/HE
Wall mounted, cast aluminum housing, cast
aluminum heatsink, clear prismatic glass lens.
240 white LEDs with white plastic reflector tray over LEDs.
One Fahold FD-100H-042B LED driver.
120.0Vac, 60.00Hz, 0.7911A, 94.45W, 0.995PF, 4.5%THD(i)

Intensity data (cd)


L-Plane
Vertical L0 L15 L30 L40 L45 L50 L55 L60 L65
0.0 2711 2711 2711 2711 2711 2711 2711 2711 2711
10.0 3301 3268 3092 2838 2774 2796 2855 2871 2776
20.0 4232 4066 3756 3878 3873 3632 3275 3034 2943
30.0 4137 3994 3538 3407 3725 3992 3396 3289 3271
35.0 2875 2845 3239 4025 3277 3199 3483 3225 2955
40.0 4467 3600 2707 2756 3095 3881 2972 3017 2918
45.0 3787 4037 4150 2748 2555 2571 3123 2731 2649
47.5 3890 3655 3791 3238 2662 2469 2491 3013 2440
50.0 5183 4313 3277 4069 3138 2523 2333 2505 2391
52.5 5163 5079 3607 3019 3594 2896 2323 2202 2461
55.0 4022 4161 4681 3083 2840 3329 2564 2141 2246
57.5 3960 3860 3940 3565 2897 2660 2977 2259 2029
60.0 4811 4341 3600 3711 3637 2672 2488 2442 2024
62.5 4631 4931 3770 3170 3145 3267 2488 2354 2053
65.0 4286 3902 4598 3210 2911 2782 2756 2282 2128
67.5 3474 3568 3474 3652 3109 2628 2483 2365 2083
70.0 3929 3692 3400 3009 2895 2845 2429 2199 2008
72.5 3885 3472 3271 2912 2658 2498 2367 2207 1928
75.0 3674 3582 3197 2759 2582 2347 2190 2025 1839
77.5 3503 3619 3217 2722 2437 2266 2060 1896 1697
80.0 3494 3209 3124 2619 2347 2121 1965 1764 1552
82.5 3258 3269 2771 2419 2212 1985 1796 1624 1391
85.0 2970 2870 2707 2202 1966 1759 1582 1418 1215
87.5 2908 2694 2350 2002 1728 1529 1328 1145 976
90.0 2540 2721 2153 1761 1552 1301 1094 910 740
92.5 2340 2162 2109 1571 1339 1152 944 765 607
95.0 2165 1903 1718 1511 1234 1012 856 681 531
97.5 1651 1964 1541 1261 1154 948 764 627 481
100.0 1273 1161 1403 1139 984 864 715 569 438
102.5 1070 1101 943 1010 896 759 650 524 391
105.0 937 911 839 718 707 686 577 469 347
120.0 488 476 428 364 325 290 260 233 203
135.0 337 329 296 269 254 233 209 179 141
150.0 234 229 201 170 149 126 100 71 41
165.0 53 47 27 6 1 0 0 0 0
180.0 0 0 0 0 0 0 0 0 0

(issuing laboratory) Page 9


8 of 12
11
R

TESTING

Lab Code: 201079-0

Test Report No. LLIA001029-001


Catalog Number: F-WP-100W/50K/BZ/HE
Wall mounted, cast aluminum housing, cast
aluminum heatsink, clear prismatic glass lens.
240 white LEDs with white plastic reflector tray over LEDs.
One Fahold FD-100H-042B LED driver.
120.0Vac, 60.00Hz, 0.7911A, 94.45W, 0.995PF, 4.5%THD(i)

Intensity data (cd)


L-Plane
Vertical L70 L75 L80 L85 L90 L95 L100 L105 L110
0.0 2711 2711 2711 2711 2711 2711 2711 2711 2711
10.0 2606 2522 2603 2700 2663 2546 2482 2499 2500
20.0 2728 2607 2562 2393 2399 2377 2264 2177 1962
30.0 2741 2524 2426 2270 2165 2085 1933 1605 1460
35.0 2833 2421 2249 2148 2015 1889 1674 1354 1244
40.0 2604 2319 2104 1977 1830 1661 1394 1096 996
45.0 2477 2368 1976 1830 1641 1421 1098 884 776
47.5 2495 2196 1904 1719 1523 1310 970 790 674
50.0 2377 2109 1894 1680 1455 1205 865 700 574
52.5 2160 2004 1820 1602 1346 1077 768 618 496
55.0 2038 1928 1766 1553 1264 965 675 535 431
57.5 1983 1824 1674 1480 1184 855 594 460 376
60.0 1972 1750 1575 1386 1078 734 512 397 334
62.5 1878 1669 1485 1274 944 600 428 345 301
65.0 1829 1586 1392 1150 796 485 357 305 267
67.5 1786 1506 1291 1006 645 397 311 271 237
70.0 1754 1411 1169 844 516 335 275 242 210
72.5 1640 1321 1045 712 414 289 246 215 187
75.0 1567 1230 928 590 339 253 220 190 166
77.5 1443 1134 802 470 288 225 195 168 150
80.0 1302 987 669 380 246 202 174 151 136
82.5 1124 817 537 312 214 179 153 136 119
85.0 950 663 416 262 184 155 136 122 105
87.5 750 520 329 218 161 135 121 108 91
90.0 576 399 264 184 138 119 107 94 79
92.5 462 324 222 159 121 106 96 83 70
95.0 389 275 195 143 107 95 85 71 61
97.5 343 239 174 126 96 86 74 63 54
100.0 305 215 158 116 90 79 67 57 48
102.5 272 194 146 107 85 74 61 53 44
105.0 244 179 137 101 82 69 58 50 39
120.0 172 140 99 72 62 51 38 28 22
135.0 104 65 39 32 27 22 18 16 14
150.0 14 12 10 8 7 4 3 3 0
165.0 0 0 0 0 0 0 0 0 0
180.0 0 0 0 0 0 0 0 0 0

(issuing laboratory) Page


Page10
9 of 12
11
R

TESTING

Lab Code: 201079-0

Test Report No. LLIA001029-001


Catalog Number: F-WP-100W/50K/BZ/HE
Wall mounted, cast aluminum housing, cast
aluminum heatsink, clear prismatic glass lens.
240 white LEDs with white plastic reflector tray over LEDs.
One Fahold FD-100H-042B LED driver.
120.0Vac, 60.00Hz, 0.7911A, 94.45W, 0.995PF, 4.5%THD(i)

Intensity data (cd)


L-Plane
Vertical L115 L120 L125 L130 L135 L140 L150 L165 L180
0.0 2711 2711 2711 2711 2711 2711 2711 2711 2711
10.0 2452 2391 2342 2288 2189 2074 1915 1780 1742
20.0 1836 1651 1524 1442 1422 1408 1290 1162 1147
30.0 1298 1182 1148 1062 964 923 874 792 763
35.0 1103 1013 944 833 776 739 661 570 546
40.0 890 798 722 642 601 558 478 398 376
45.0 672 598 537 481 450 412 347 273 252
47.5 581 512 461 417 389 354 292 218 202
50.0 503 438 398 362 335 301 247 176 163
52.5 434 380 345 315 285 255 203 144 136
55.0 377 335 301 272 242 215 167 124 118
57.5 333 296 265 237 205 182 140 108 105
60.0 297 263 236 205 175 155 119 98 108
62.5 266 236 211 178 151 132 102 104 103
65.0 236 213 186 156 130 111 92 84 72
67.5 209 190 164 135 110 91 83 58 54
70.0 188 170 142 114 92 75 56 40 39
72.5 169 150 120 93 72 61 33 20 15
75.0 151 129 103 75 57 38 11 0 0
77.5 134 109 83 60 38 19 3 0 0
80.0 116 90 65 44 28 15 2 0 0
82.5 98 76 54 36 22 12 2 0 0
85.0 85 65 45 29 18 9 1 0 0
87.5 74 55 38 25 15 8 1 0 0
90.0 64 48 32 20 12 7 0 0 0
92.5 56 41 27 17 10 6 0 0 0
95.0 48 34 23 14 9 5 0 0 0
97.5 42 29 19 12 8 4 0 0 0
100.0 36 25 17 11 7 4 0 0 0
102.5 31 22 15 10 6 4 0 0 0
105.0 28 20 14 9 6 4 0 0 0
120.0 17 13 10 0 0 0 0 0 0
135.0 12 10 0 0 0 0 0 0 0
150.0 0 0 0 0 0 0 0 0 0
165.0 0 0 0 0 0 0 0 0 0
180.0 0 0 0 0 0 0 0 0 0

(issuing laboratory) Page 11


10 of 12
11
R

TESTING

Lab Code: 201079-0

Test Report No. LLIA001029-001


Catalog Number: F-WP-100W/50K/BZ/HE
Wall mounted, cast aluminum housing, cast
aluminum heatsink, clear prismatic glass lens.
240 white LEDs with white plastic reflector tray over LEDs.
One Fahold FD-100H-042B LED driver.
120.0Vac, 60.00Hz, 0.7911A, 94.45W, 0.995PF, 4.5%THD(i)

Test Distance 9.5 m


Test Temperature 24.7 °C

Notes The laboratory has not participated in the selection of samples to be tested. All testing
is performed on the understanding that the significance of the report is limited to the
extent that the test sample is representative of production units.

Tested in accordance with the applicable sections of publications: IES LM-79-08


(Sec. 12), IES LM-16-93, IES LM-58-13, CIE 13.3:1995, CIE 15:2004, ANSI
C78.377:2015, ANSI C82.77-10:2014.
The luminous intensity values, and other derived quantities, contained in this report
are based on the absolute data, as measured.

Prorating the performance of the sample for the use of other component
combinations (such as lamp / LED / Ballast / driver), or for use in different
environmental conditions than that tested, may produce erroneous results.

This report is free of erasures and corrections.

Photometric intensity values are reported using the IESNA Type C coordinate system
(L, V) as defined in IESNA publication LM-75.

This report may contain data that are not covered by the NVLAP accreditation.
Quantities marked with * are not covered.

This report must not be used by the customer to claim product certification, approval
or endorsement by NVLAP, NIST, or any agency of the Federal Government.

28-Sep-18 11:41:15 REPORT program version: 3.820a

(issuing laboratory) Page 12


11 of 12
11