Dimensioning of Sandwich Anchors

Project Data:
No.: Element Description:
Construction Windzone, Height [m]: WZ I, <= 10
Project:
Designer: Facing Layer Thickness: 7 cm
Street: Insulation Layer Thickness: 6 cm
Location: Dimensions [cm]: L =599 / H =268
Person in charge: Pos. of Center of Gravity: x = 355 / y = 121
Date: 17.07.2015 QEd Facing Layer: 24,4 kN
Element: Position 1 Concrete Quality: min. C30/37 up to max. C45/55
Quantity: 1 Turn Item: No
Note: formwork's surface flatly

Openings: local Thickenings:


1) x = 70 / y = 48

Result of dimensioning:
Load bearing Anchor: 2 x FLA-160-1,5-175 Reinforcement (per Anchor)
Positioning: x = 23 / y = 134 2 x 6 Ø 6 mm, L = 400 mm
Positioning: x = 470 / y = 134
Design Resistance: 19,8 kN
Design Impact: 18,1 kN

Torsion Anchor: 1 x FLA-80-1,5-175 Reinforcement (per Anchor)


Positioning: x = 355 / y = 246 2 x 4 Ø 6 mm, L = 400 mm
Design Resistance: 3,7 kN
Design Impact: 2,4 kN

Pins: 19 x Connector Pins VN - 4-180


Edge Distance: x-Direction 15 cm / y-Direction 15 cm
No. of Grids in x-Direction: 5 x 114 cm
No. of Grids in y-Direction: 2 x 119 cm

Notes
- All additional reinforcement has to be provided by the panel manufacturer!
- The anchor- and pin sizes are based on minimum technical requirements. If required higher anchors
and pins can be choosen. If anchor- or pin sizes have been changed, the installation has to be
checked by the engineer in charge!
- Deformations should be expected for any panel with a size above 5m.
- The insulation layer thickness has to be increased in the area of the marked Flat Anchors ( ) .
- If the thickness of the insulation layer has been changed, the installation has to be checked by the
engineer in charge!
- In addtion to this installation advice please observe the general installation instructions in our
brochure "PFEIFER-Sandwich Anchor System".
- The calculation's basis is a quality control during production with regard to the connection devices'
exact installation which renders the calculation of an accidental load eccentricity due to the connetion
devices' inexactness during installation unnecessary.

PFEIFER - Sandwich Anchor System Dimensioning Software Version 3.0.1 Page: 1/2
Drawing:

Position: Position 1
Load bearing Anchor: 2 x FLA-160-1,5-175 Edge Distance: x-Direction 15 cm / y-Direction 15 cm
Torsion Anchor: 1 x FLA-80-1,5-175 No. of Grids in x-Direction: 5 x 114 cm
Pins: 19 x VN-4-180 No. of Grids in y-Direction: 2 x 119 cm

268

134

134

220
599

470

260

x
23

Checked: _______________ __________________________


Date/Location Designer/Planner

PFEIFER - Sandwich Anchor System Dimensioning Software Version 3.0.1 Page: 2/2