Академический Документы
Профессиональный Документы
Культура Документы
3 The ratio of the actual water vapor pressure of the air to the saturated
water vapor pressure of the air at the same temperature is known as relative
humidity.
37
Guidebook in Air Conditioning Design and Analysis
O When a thermometer with its bulb covered by a wetted wick is spun in the
air until the air surrounding the bulb becomes saturated, the equilibrium
temperature reached is termed as wet-bulb temperature. Wet-bulb
temperature is lower than the diy-bulb temperature because the energy
required to evaporate the water vapor into the air comes from the
surrounding air vapor mixture.
O The amount of water vapor that air can hold decreases as the air temperature
decreases. When an air vapor mixture is cooled at constant pressure until
the air becomes saturated, the temperature reached is known as the dew
point temperature. If cooling process continues at constant pressure, this
would result in the condensation of moisture from the air.
-
O An empirical equation known as Carrier equation is useful in
determining the partial pressure of water vapor in a moist air:
(p,-p.)(DB-WB)
Pv - Pw 2800-1 3(WB)
ÿ
wÿere
Pw = saturation pressure of water vapor
at a temperature equal to the wet-bulb temperature in psi, DB = dry-bulb
temperature in °F, WB = wet-bulb temperature in °F, and pt = barometric
pressure in psi.
3«
Psychrometry
For 0°C < DB < 60°C: -> h = 1.007 DB - 0.026 + W (2501 + 1.84 DB)
O Specific volume is the volume in m3 of one kg of dry air together with the
mass of water vapor associated with it. In the mixture, the water vapor
occupies the same volume as the dry air but each of these two components
is at its own partial pressure.
O An ideal gas law is used to determine the humid volume of air in three
ways:
a) making use of the mass and partial pressure of the dry air;
b) making use of the mass and partial pressure of the water vapor; and
c) making use of the mass and total pressure of the mixture.
39
Guidebook in Air Conditioning Design and Analysis
3 The following are the definitions of ASHRAE for U.S. Standard Atmosphere:
% Acceleration due to gravity is constant at 32.174 fps2 or 9.807 m/s2.
ÿ Temperature at sea level is 59°F, 15°C, or 288. 1°K.
ÿ Pressure at sea level is 29.921 inches of mercury or 101.039 kPa.
The atmosphere consists of dry air, which behaves as a perfect gas.
P = a + bH
IP means inch-pound
40
Psychrometry
O The enthalpy of a moist air is the sum of the enthalpy of dry air and the
enthalpy of water vapor. Enthalpy values are always based on some datum
line, and the zero value of the diy air is chosen as air at 0°C or 32°F and
the zero value of the water vapor is saturated liquid water at 0°C or 32°F.
41
—
ÿm V- "
- .
- "
'
•
ÿ
I
Psychrometry
PROBLEMS
2. How high a relative humidity must a 35°C air have in order to obtain
saturated air at 18°C by evaporative cooling?
43
Guidebook in Air Conditioning Design and Analysis
4. Using the humidity ratios from psychrometric chart, calculate the error in
considering the wet-bulb line to be the line of constant enthalpy at the
point 35°C DB and 50% RH.
44
Psychrometry
7. Given for an air water vapor mixture that DB = 60°C; Pt = 300 kPaa, and
RH = 50.1%. Find the dew-point temperature and the humidity ratio.
45
Guidebook in Air Conditioning Design and Analysis
10. Find the densities of humid air at 25°C DB, when it is at 20% saturation
and then when it is at 23°C WB.
11. Calculate the specific volume of humid air at 22°C DB; 17°C WB; and
vapor pressure 16 mb.
12. Find the dew-point temperature of humid air at 22°C DB; 17°C WB; and
vapor pressure 16 mb using the three methods described.
46
Psychrometry
13. Determine the degree or percent saturation of water vapor in an air at 2 1°C
DB and 10°C WB. What is the RH? Barometric pressure is 29" Hg.
47
Guidebook in Air Conditioning Design and Analysis
'
"
Psychrometry
3. Calculate the moisture content of moist air at 20°C DB, 15°C WB, and
95 kPa barometric pressure. Let the saturation pressure of water at 15°C
equals to 1.7057 kPaa and at 20°C is 2.339 kPaa.
a) 0.00923 kg/kg d.a. b) 0.00293 kg/kg d.a.
c) 0.00392 kg/kg d.a. d) 0.00239 kg/kg d.a.
49
Guidebook in Air Conditioning Design and Analysis
10. A certain volume of moist air is at 34°C and 65% RH when the barometric
pressure is 101 kPa. If the vapor pressure at 34°C is 5.318 kPaa, determine
the humidity ratio.
a) 0.02204 kg/kg d.a. b) 0.00224 kg/kg d.a.
c) 0.04202 kg/kg d.a. d) 0.02402 kg/kg d.a.
13. Determine the moisture content of a moist air in kg vapor per kg diy air at
20°C DB, 15°C WB, and 95 Kpaa barometric pressure if Psa[ at
15°C = 1.7051 Kpaa.
a) 0.009228 b) 0.004354
c) 0.008622 d) 0.0235
14. Calculate the humidity ratio of moist air at 65% relative humidity and
34°C DB when barometric pressure is 101.3 Kpaa. P . @34°C = 5.324
Kpaa.
a) 0.033 - b) 0.022
c) 0.012 d) 0.018
50
Psychrometry
16. The mixing ratio of humid air is 0.034 at a dry-bulb temperature of 27°C.
Determine the enthalpy of the given air: hÿ@27°C = 2550.8 KJ/kg
a) 67.25 kJ/kg b) 80.62 KJ/kg
c) 87.73 KJ/kg d) 55.68 KJ/kg
18. In problem # 17, what is the density of the given air in kg/m3?
a) 1.64 b) 1.32
c) 1.25 d) 1.10
20. In problem #19, what is the enthalpy of room air in Btu/lb d.a.?
a) 22.51 b) 16.70
c) 12.3 d) 14.28'
21. Determine the saturation ratio of water vapor in an air at 21°C DB and
10°C WB. Barometric pressure is 29 in Hg absolute and P t fa 21°C is
s
22. The dry-bulb temperature of humid air is 35°C. What is the wet-bulb
depression in °F if the wet-bulb temperature is 18°C?
a) 17.6 -b) 30.6
c) 18.0 d) None of these
23. Determine the dew-point depression of the room air when the diy-bulb
and dew-point temperature is 69.8°F and 15°C, respectively.
a) 6°C b) 8°C
c) 5.8°C d) 7°F
51
Guidebook in Air Conditioning Design and Analysis
24. Determine the capacity of the heater which heats 1.5 m,/s of moist air at
a state of 21°C DB and 15°C WB by 20°C if the enthalpy of entering air is
62.26 KJ/kg and the enthalpy of the leaving air is 4 1.94 KJ/kg. The specific
volume of entering air is 845 liters per kg.
a) 28.05 KW b) 54.25 KW
c) 36.075 KW d) 10.525 KW
25. Calculate the load on the cooler coil that cools 1.8 kg/s of moist air at a
state of 21°C DB, 15°C WB and 1 atm pressure by 5°C. The enthalpy of air
entering is 41.84 KJ/kg and air leaving is 36.845 KJ/kg.
a) 12.05 hp b) 13.05 hp
c) 10.05 hp d) 8.05 hp
27. 2.5 m3/s of humid air at a state of 28°C DB, 21 WB and 101.325 Kpaa flow
across a cooler coil and leaves at 12.5°C DB and 0.0083 kg vapor per kg
dry air. If the apparatus dew-point (ADP) is 8.5, compute for the contact
factor (CF).
a) 0.835 b) 0.795
c) 0.579 d) 0.306
28. In problem # 27, what is the by-pass factor (BPF) of the cooler coil?
a) 0.502 b) 0.603
c) 0.205 d) 0.306
29. 1.4 kg/sec of air at 33°C DB and 19°C WB is cooled and .humidified by
passing through an air washer in which water is continuously circulated.
The air leaves the air washer at 23°C DB. Determine the air moisture added
in kg/ sec if the specific humidity of air leaving and air entering the washer
is 0.0122 and 0.0081, respectively.
a) 0.005*4 b) 0.00385
c) 0.00853 d) 0.00835
30. Determine the bypass factor of air heating coils if the mean coil temperature
is 110°F and it heats air from 60°F to 90°F.
a) 0.30 b) 0.50
c) 0.40 d) 0.60
52
*1
0 037
0 031 ,
SI METRIC UNITS
Barometric Pressure 101 325 kPa
SEA LEVEL
-10
* Dry Bulb ltmprratjic C
on o 0.05
8»to~ 0"C Pioptibn and Entlutpf Devutiow Lum An f oi let Volume mÿ/kf Or* An Copyfijht Ctrner Corpont.tn 1975
Cti No 794 00? Punted m U.S.A.
REFERENCES:
ASHRAE, Inc. 1999 ASHRAE Handbook HVAC Systems and Equipment, SI Edition.
ASHRAE, Inc., Atlanta, G.A.., 1999.
ASHRAE, Inc. 1996 ASHRAE Handbook HVAC Systems and Equipment, SI Edition.
ASHRAE, Atlanta, G.A., 1996.
Jones, W. P. Air Conditioning Engineering, 3rd Ed. London: Edward Arnold, 1985.
Jordan, Richard C. and Priester, Gayle B. Refrigeration and Air Conditioning, 2nd Ed.
Englewood Cliffs, N.J.: Prentice-Hall, Inc., 1956.
Keenan, Joseph H., Keyes, Fredereck G., Hill, Philip G., and Moore, Joan G. Steam
Tables, SI Units. New York: John Wiley 8s Sons Publication, 1978.
Stoecker, Wilbert F. and Jones, Jerold W. Refrigeration and Air Conditioning, 2nd Ed.
New York: McGraw-Hill Company, 1982.
54
h.
PSVCHROMETRV
OF RIR CONDITIONING
PROCESSES
INTRODUCTION
This lesson deals with the basic air conditioning processes such as sensible
heating, sensible cooling, humidifying, dehumidifying, heating and humidifying,
cooling and dehumidifying, cooling and humidifying, heating and dehumidifying or
chemical dehumidifying, and the air mixing processes. Each process is discussed
with the corresponding schematic and psychrometric diagrams. Sample or illustrative
problems are discussed for application of the topics.
At the end of the lesson, additional problems are provided for the students to
further enhance their learning process in solving problems in air conditioning
processes. .
LESSON OBJECTIVES
55
-*
Guidebook in Air Conditioning Design and Analysis
5. determine and calculate the capacity of air washer, cooling coil, and heater
battery using psychrometric chart and formulas;
6. plot and illustrate each process in the psychrometric chart; and
7. solve the problems provided at the end of the lesson.
3 As shown in Figure 3.1 below, the basic air conditioning processes are
sensible cooling; sensible heating; humidifying; dehumidifying; heating and
humidifying; cooling and dehumidifying; cooling and humidifying; and
heating and dehumidifying or chemical dehumidifying.
56
Psyclirometry of Air Conditioning Process
Heater Coil
Air Entering Air Leaving
Heating
Medium In
w. = w
57
Guidebook in Air Conditioning Design and Analysis
Heater Capacity:
q = m (h2 - hj
<ÿ> Application: Air in a duct passing through a cooling coil or air washer.
The surface temperature of a cooling coil is above the dew-point
temperature of the air.
Cooling
Medium Out
Cooler Coil
Air Entering Air Leaving
Cooling
Medium In
w = w,
db2 db,
Figure 3. 5. Psychrometric Diagram, Sensible Cooling
5«
Psychrometry of Air Conditioning Process
q= mfh, - h2) in kW or TR
1TR = 3.517 kW
y.
\ /\ /\
j J
1
:;V 1
Spray of Water
'' 1 1 1
' 1 1 1
' '
1
i
1
2
db, = db2
Figure 3. 7. Psychrometric Diagram, Humidifying
59
Guidebook in Air Conditioning Design and Analysis
Cooling Water In
Air Washer
mv= mfWj-WJ
6o
Psychrometry of Air Conditioning Process
Hot Water In
-— *
• , , Spray
1 i of hot or ,
warm water , , , , '
1
1 1 1 1 1 1 1
1 1 1
DB.2
q= m(h2- h,)
61
Guidebook in Air Conditioning Design and Analysis
Y
Air Entering Air Leaving
ir Washer
Cooling
Water Out
Cooling
Medium Out
Cooler Coil
Air Entering Air Leaving
Cooling
Medium In
mv = m(W, - W2)
q = m(h, - h2)
ÿ This is the action that takes place in an ordinaiy air washer in which
the same water is continuously recirculated, but is neither heated
nor cooled.
63
Guidebook in Air Conditioning Design and Analysis
Cooling Water In
>=ÿ
~ . . :' . .• J
i i i
N Air Washer
/ Cooling Water Out
ÿ Air can be dehumidified by passing the air over a chemical that has
an affinity for moisture. Usually, in so doing, the moisture is condensed
and gives up its latent heat, raising the DB temperature of the air.
The air leaves drier but warmer. The WB temperature may increase or
64
Psychrometry of Air Conditioning Process
i L
DB.1 DB2
ÿ When air at one condition is mixed with air at another condition, the
condition of the final mixture can be indicated on the psychrometric
chart by a point on the line joining the points indicating the original
conditions, as shown in the figure below. The exact location of the
final point will depend upon the relative weights of dry air in the
original air quantities.
Return Air
Mixture
Outdoor Air
65
Guidebook in Air Conditioning Design and Analysis
m3 = mi + m2
m,W, + m2W2
W3 = m, + m2
ÿ
_ mÿj + m2h2
ny + m2
66
Psychrometry of Air Conditioning Process
niiDB, + m2DB2
DB =
m, + m2
™PP 3
= m,DP, + mPP,
mjDP, + m2DP,
dp3 =
m, + m2
B. ILLUSTRATIVE PROBLEMS
Ex. 3.1] Calculate the load on a heater battery which heats 1.5 m3/s of moist
air, initially at a state of 2 1°C DB, 15°C WB and 10 1.325 kPa barometric pressure,
by 20 degrees. If low pressure hot water at 85"C return, is used to achieve this,
calculate the flow necessary, in kg/s of water.
Pt = 101.325 kPa
DB, = 21°C
Heater Coi
WB, = 15°C Air Entering Air Leaving
ADB = 20°C
V, = 1.5 m3/s
t . = 85 °C
DB2 = 21 + 20
41°C=
wl
= temperature of hot water entering the heater battery
w2
= temperature of hot water leaving the heater battery
Required:
67
Guidebook in Air Conditioning Design and Analysis
21 °C 41 °C
Figure 3. a.
Solution:
q = m(h2 - hj
m= Vl =
J_15_ = i 775 k
/s
Vj 0.845
68
Psychrometry ofAir Conditioning Process
Let q =q
"
= mc (t-tj
'w w pw* wl w2'
Therefore,
36.068
m.„ = = 0.861 kg/s
Cpw(t„,-tw2) 4.187(85-75)
Ex. 3.2] Determine the heat required to raise 0.50 m3/s of air at 10°C and 80%
RH to 32°C. What is the final relative humidity?
DB, = 10°C
Heater Coi
RH, = 80% Air Entering Air Leaving
DB2 = 32°C
V. = 0.50 m3/s Hot Water In
Required:
w, = w2
10 °C 32 °C
Figure 3.b.
6t)
Guidebook in Air Conditioning Design and Analysis
Solution:
at point 2: h,
2
= 48.2 - 0.44 = 47.76 kJ/kg d.a.
w, W.
RH2 = 21%
Ex. 3.3] (Sensible Cooling) Calculate the load on a cooler coil which cools the
moist air mentioned in exercise 3.1. by 5 degrees. What is the flow rate of
chilled water necessaiy to this cooling if flow and return temperatures of 10°C
and 15nC are satisfactory?
Water Out
DB, = 21°C tb=15°C
ta = 10°C 1 2
15°C Heater Coil
WB, =
Air Entering Air Leaving
tb = 15°C
Water
DB2 = 21-5= 16°C t = 10°C
V, = 1.5 m3/s
70