Вы находитесь на странице: 1из 3

To produce ultra filtration water we need 3000m3 River water /day

Quantity
Component Description unit of measure
Caustic Soda NaOH (48%)
30
kg/day

Sodium Hypochlorite (NaOCl)


1
Kg/day

Hydrochloric acid (HCl) 60 Kg/day

To produce service water from UF water we need below chemicals required

Quantity
Component Description unit of measure
Sodium Hypochlorite (NaOCl)
4.23
Kg/day

To produce Ro water from service water we required below chemicals

Component Description Quantity unit of measure


1.Hypesperse MDC714/ Genesys LF Membrane
1
antiscalant Kg/day

2.Hydrochloric acid (HCl) 32-33% 22 Kg/day

3. Caustic Soda NaOH (48%) 28 Kg/day

4. Sudscav S Bisulphite 3 Kg/day

To produce electricity from Ro we required below chemicals and demin water


Component Description Quantity unit of measure
Oxygen scavenger (Carbohydrazide) CORTROL
0.04
OS5601 Kg/day

Demin water from RO 200 M3 /day

Ammonia STEAMATE NA 1320 / SUDAMINE N1000 0.138 Kg/day

PHOSPHATE OPTISPERSE; HP 3100 & HP 5493 0.00014 Kg/day

Cooling tower we need blow chemicals

Component Description Quantity unit of measure


Sodium Hypochlorite Solution 83 Kg/day

Sulphuric Acid (H2SO4) 98% 108 Kg/day

Non oxidant Biocide;SPECTRUS NX100; 210L 120 Kg/day

Antiscalant (*) DEPOSITROL BL 6510 5.83 Kg/day

Corrosion Inhibitor Corrshield MD 4103 5.5l Kg/day

Sludge treatment area/recovery system from backwash basin. Recovered water is sent back to raw
water tank and used in the Ultrafiltration. Roughly 500M3

Component Description Quantity unit of measure


ZE TAG 7557 FLOCCULENT 1 Kg/day

Coagulant Ferric Chloride 40% (SUDFLOC 300) 75 Kg/day

Potable water from service water tank. It is used for safety showers, sanitation.

Component Description Quantity unit of measure


Sodium Hypochlorite (NaOCl) 12-16% 4.05 Kg/day