Академический Документы
Профессиональный Документы
Культура Документы
Contents
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB AB. ABB AB assumes
no responsibility for any errors that may appear in this document.
Trademarks
ABB and Relion are registered trademarks of ABB Group. All other brand or product names mentioned in this document may be trademarks or
registered trademarks of their respective holders.
2 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Customized Revision: B
ABB 3
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
2. Functionality two-winding
power
xx05000050.vsd transformer with
Differential protection
IEC05000050 V1 EN two circuit
Transformer differential protection breakers on one
T2WPDIF/T3WPDIF side
The functions Transformer differential two-winding
protection, two-winding (T2WPDIF) and power
Transformer differential protection, three- transformer with
winding (T3WPDIF) are provided with two circuit
internal CT ratio matching and vector group breakers and two
compensation and when required zero CT-sets on both
sequence current elimination is also made xx05000051.vsd sides
internally in the software. IEC05000051 V1 EN
4 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
ABB 5
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
independent zones. Individual settings for The heavy load transfer that is common in
each zone in resistive and reactive reach many transmission networks may make fault
gives flexibility for use as back-up protection resistance coverage difficult to achieve.
for transformer connected to overhead lines Therefore, FDPSPDIS has a built-in algorithm
and cables of different types and lengths. for load encroachment, which gives the
possibility to enlarge the resistive setting of
ZMQPDIS together with Phase selection with
both the phase selection and the measuring
load encroachment FDPSPDIS has
zones without interfering with the load.
functionality for load encroachment, which
increases the possibility to detect high The extensive output signals from the phase
resistive faults on heavily loaded lines. selection gives also important information
about faulty phase(s), which can be used for
The distance protection zones can operate
fault analysis.
independently of each other in directional
(forward or reverse) or non-directional mode. Full-scheme distance protection,
quadrilateral for earth faults ZMMPDIS,
Full-scheme distance measuring, Mho ZMMAPDIS
characteristic ZMHPDIS
The distance protection is a five zone
The numerical mho line distance protection is
protection with three fault loops for phase-to-
afive zone full scheme protection for back-up
earth fault for each of the independent zones.
detection of short circuit and earth faults. The
Individual settings for each zone resistive and
full scheme technique provides back-up
reactive reach give flexibility for use on
protection of power lines with high
overhead lines and cables of different types
sensitivity and low requirement on remote
and lengths.
end communication. The five zones have
fully independent measuring and settings, The Full-scheme distance protection,
which gives high flexibility for all types of quadrilateral for earth faults functions
lines. ZMMDPIS and ZMMAPDIS have functionality
for load encroachment, which increases the
possibility to detect high resistive faults on
The function can be used as under
heavily loaded lines .
impedance back-up protection for
transformers and generators. The independent measurement of impedance
for each fault loop together with a sensitive
Phase selection, quadrilateral and reliable built in phase selection makes
characteristic with fixed angle FDPSPDIS the function suitable in applications with
The operation of transmission networks single phase auto-reclosing.
today is in many cases close to the stability
The distance protection zones can operate,
limit. Due to environmental considerations,
independent of each other, in directional
the rate of expansion and reinforcement of
(forward or reverse) or non-directional mode.
the power system is reduced, for example,
This makes them suitable, together with
difficulties to get permission to build new
different communication schemes, for the
power lines. The ability to accurately and
protection of power lines and cables in
reliably classify the different types of fault, so
complex network configurations, such as
that single pole tripping and autoreclosing
parallel lines, multi-terminal lines.
can be used plays an important role in this
matter. Phase selection, quadrilateral Directional impedance element for Mho
characteristic with fixed angle FDPSPDIS is characteristic ZDMRDIR
designed to accurately select the proper fault
The phase-to-earth impedance elements can
loop in the distance function dependent on
be optionally supervised by a phase
the fault type.
unselective directional function (phase
6 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
The optional phase preference logic main The Instantaneous residual overcurrent
purpose is to provide a selective tripping for protection EFPIOC has a low transient
cross-country faults in isolated or high overreach and short tripping times to allow
impedance-earthed networks. use for instantaneous earth-fault protection,
with the reach limited to less than typical
Power swing detection ZMRPSB eighty percent of the transformer impedance
at minimum source impedance. EFPIOC can
Power swings may occur after disconnection
be configured to measure the residual current
of heavy loads or trip of big generation plants.
from the three-phase current inputs or the
Power swing detection function (ZMRPSB) is current from a separate current input.
used to detect power swings and initiate EFPIOC can be blocked by activating the
block of selected distance protection zones. input BLOCK.
Occurrence of earth-fault currents during a
power swing can block ZMRPSB function to
allow fault clearance.
ABB 7
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
8 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
stress on rotating machines and can cause outages or as long-time delayed back-up to
unwanted operation of zero sequence or primary protection.
negative sequence current functions.
UV2PTUV has two voltage steps, each with
Normally the own breaker is tripped to inverse or definite time delay.
correct such a situation. If the situation
persists the surrounding breaker should be Two step overvoltage protection OV2PTOV
tripped to clear the unsymmetrical load Overvoltages may occur in the power system
situation. during abnormal conditions, such as, sudden
The Polediscordance protection function power loss, tap changer regulating failures,
CCRPLD operates based on information from open line ends on long lines.
auxiliary contacts of the circuit breaker for Two step overvoltage protection OV2PTOV
the three phases with additional criteria from can be used as open line end detector,
unsymmetrical phase current when required. normally then combined with directional
reactive over-power function or as system
Directional over/underpower protection voltage supervision, normally then giving
GOPPDOP/GUPPDUP
alarm only or switching in reactors or switch
The directional over-/under-power protection out capacitor banks to control the voltage.
(GOPPDOP/GUPPDUP) can be used
OV2PTOV has two voltage steps, each of
wherever a high/low active, reactive or
them with inverse or definite time delayed.
apparent power protection or alarming is
required. The functions can alternatively be OV2PTOV has an extremely high reset ratio
used to check the direction of active or to allow setting close to system service voltage.
reactive power flow in the power system.
There are number of applications where such Two step residual overvoltage protection
functionality is needed. Some of them are: ROV2PTOV
Residual voltages may occur in the power
• detection of reversed active power flow
system during earth faults.
• detection of high reactive power flow
Two step residual overvoltage protection
Each function has two steps with definite ROV2PTOV calculates the residual voltage
time delay. Reset times for every step can be from the three-phase voltage input
set as well. transformers or from a single-phase voltage
input transformer fed from an open delta or
Broken conductor check BRCPTOC neutral point voltage transformer.
The main purpose of the function Broken
ROV2PTOV has two voltage steps, each with
conductor check (BRCPTOC) is the detection
inverse or definite time delayed.
of broken conductors on protected power
lines and cables (series faults). Detection can Overexcitation protection OEXPVPH
be used to give alarm only or trip the line
When the laminated core of a power
breaker.
transformer or generator is subjected to a
Voltage protection magnetic flux density beyond its design
limits, stray flux will flow into non-laminated
Two step undervoltage protection components not designed to carry flux and
UV2PTUV cause eddy currents to flow. The eddy
Undervoltages can occur in the power system currents can cause excessive heating and
during faults or abnormal conditions. Two severe damage to insulation and adjacent
step undervoltage protection (UV2PTUV) parts in a relatively short time. Overexcitation
function can be used to open circuit breakers protection OEXPVPH has settable inverse
to prepare for system restoration at power operating curve and independent alarm stage.
ABB 9
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
10 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
protection applications where positive, a non-directly earthed system and can detect
negative or zero sequence components of one or two phase fuse failures.
current and voltage quantities are typically
The method based on detection of du/dt-di/
required.
dt where a change of the voltage is compared
Secondary system supervision to a change in the current. Only voltage
changes means a voltage transformer fault.
Current circuit supervision CCSRDIF This principle can detect one, two or three
Open or short circuited current transformer phase fuse failures.
cores can cause unwanted operation of many Control
protection functions such as differential,
earth-fault current and negative-sequence Synchronizing, synchrocheck and
current functions. energizing check SESRSYN
It must be remembered that a blocking of The Synchronizing function allows closing of
protection functions at an occurrence of open asynchronous networks at the correct
CT circuit will mean that the situation will moment including the breaker closing time.
remain and extremely high voltages will The systems can thus be reconnected after an
stress the secondary circuit. autoreclose or manual closing, which
improves the network stability.
Current circuit supervision (CCSRDIF)
compares the residual current from a three Synchrocheck, energizing check (SESRSYN)
phase set of current transformer cores with function checks that the voltages on both
the neutral point current on a separate input sides of the circuit breaker are in
taken from another set of cores on the synchronism, or with at least one side dead
current transformer. to ensure that closing can be done safely.
ABB 11
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
12 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
VSGGIO can be controlled from the menu or residual overcurrent protection (ECRWPSCH)
from a symbol on the single line diagram function.
(SLD) on the local HMI.
Current reversal and weak-end infeed logic
Single point generic control 8 signals for residual overcurrent protection
SPC8GGIO ECRWPSCH
The Single point generic control 8 signals The Current reversal and weak-end infeed
(SPC8GGIO) function block is a collection of logic for residual overcurrent protection
8 single point commands, designed to bring ECRWPSCH is a supplement to Scheme
in commands from REMOTE (SCADA) to communication logic for residual overcurrent
those parts of the logic configuration that do protection ECPSCH.
not need complicated function blocks that To achieve fast fault clearing for all earth
have the capability to receive commands (for faults on the line, the directional earth-fault
example, SCSWI). In this way, simple protection function can be supported with
commands can be sent directly to the IED logic that uses communication channels.
outputs, without confirmation. Confirmation
(status) of the result of the commands is The 670 series IEDs have for this reason
supposed to be achieved by other means, available additions to scheme communication
such as binary inputs and SPGGIO function logic.
blocks. If parallel lines are connected to common
busbars at both terminals, overreaching
Scheme communication permissive communication schemes can trip
Scheme communication logic for residual unselectively due to fault current reversal.
overcurrent protection ECPSCH This unwanted tripping affects the healthy
line when a fault is cleared on the other line.
To achieve fast fault clearance of earth faults
This lack of security can result in a total loss
on the part of the line not covered by the
of interconnection between the two buses. To
instantaneous step of the residual overcurrent
avoid this type of disturbance, a fault current
protection, the directional residual
reversal logic (transient blocking logic) can
overcurrent protection can be supported with
be used.
a logic that uses communication channels.
Permissive communication schemes for
In the directional scheme, information of the
residual overcurrent protection, can basically
fault current direction must be transmitted to
operate only when the protection in the
the other line end. With directional
remote terminal can detect the fault. The
comparison, a short operates time of the
detection requires a sufficient minimum
protection including a channel transmission
residual fault current, out from this terminal.
time, can be achieved. This short operate
The fault current can be too low due to an
time enables rapid autoreclosing function
opened breaker or high positive and/or zero
after the fault clearance.
sequence source impedance behind this
The communication logic module for terminal. To overcome these conditions,
directional residual current protection weak end infeed (WEI) echo logic is used.
enables blocking as well as permissive under/
overreaching schemes. The logic can also be Logic
supported by additional logic for weak-end
Tripping logic SMPPTRC
infeed and current reversal, included in
Current reversal and weak-end infeed logic A function block for protection tripping is
for residual overcurrent protection Current provided for each circuit breaker involved in
reversal and weak-end infeed logic for the tripping of the fault. It provides the pulse
prolongation to ensure a trip pulse of
ABB 13
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
sufficient length, as well as all functionality outputs where one is inverted. The memory
necessary for correct co-operation with setting controls if the block after a power
autoreclosing functions. interruption should return to the state
before the interruption, or be reset. Set
The trip function block includes functionality
input has priority.
for evolving faults and breaker lock-out.
14 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
ABB 15
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
The event recorder logs all selected binary operation of protection functions. It can
input signals connected to the Disturbance record disturbances not detected by
report function. Each recording can contain protection functions.
up to 150 time-tagged events.
The disturbance recorder information for the
The event recorder information is available last 100 disturbances are saved in the IED
for the disturbances locally in the IED. and the local HMI is used to view the list of
recordings.
The event recording information is an
integrated part of the disturbance record Event function
(Comtrade file).
When using a Substation Automation system
Trip value recorder DRPRDRE with LON or SPA communication, time-
tagged events can be sent at change or
Information about the pre-fault and fault
cyclically from the IED to the station level.
values for currents and voltages are vital for
These events are created from any available
the disturbance evaluation.
signal in the IED that is connected to the
The Trip value recorder calculates the values Event function (EVENT). The event function
of all selected analog input signals connected block is used for LON and SPA
to the Disturbance report function. The result communication.
is magnitude and phase angle before and
Analog and double indication values are also
during the fault for each analog input signal.
transferred through EVENT function.
The trip value recorder information is
available for the disturbances locally in the Measured value expander block RANGE_XP
IED. The current and voltage measurements
The trip value recorder information is an functions (CVMMXU, CMMXU, VMMXU and
integrated part of the disturbance record VNMMXU), current and voltage sequence
(Comtrade file). measurement functions (CMSQI and VMSQI)
and IEC 61850 generic communication I/O
Disturbance recorder DRPRDRE functions (MVGGIO) are provided with
The Disturbance recorder function supplies measurement supervision functionality. All
fast, complete and reliable information about measured values can be supervised with four
disturbances in the power system. It settable limits that is low-low limit, low limit,
facilitates understanding system behavior and high limit and high-high limit. The measure
related primary and secondary equipment value expander block (RANGE_XP) has been
during and after a disturbance. Recorded introduced to be able to translate the integer
information is used for different purposes in output signal from the measuring functions to
the short perspective (for example corrective 5 binary signals that is below low-low limit,
actions) and long perspective (for example below low limit, normal, above high-high
Functional Analysis). limit or above high limit. The output signals
can be used as conditions in the configurable
The Disturbance recorder acquires sampled logic.
data from all selected analog input and
binary signals connected to the Disturbance Metering
report function (maximum 40 analog and 96
binary signals). The binary signals are the Pulse counter logic PCGGIO
same signals as available under the event Pulse counter (PCGGIO) function counts
recorder function. externally generated binary pulses, for
The function is characterized by great instance pulses coming from an external
flexibility and is not dependent on the energy meter, for calculation of energy
consumption values. The pulses are captured
16 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
by the binary input module and then read by selection between local and remote
the pulse counter function. A scaled service control and reset.
value is available over the station bus. The • Isolated RJ45 communication port.
special Binary input module with enhanced
pulse counting capabilities must be ordered
to achieve this functionality.
system. This makes comparison of events and Figure 3. Small, alpha numeric HMI
disturbance data between all IEDs in a station
automation system possible.
ABB 17
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
18 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Galvanic interface G.703 resp G.703E1 The binary input/output module is used
when only a few input and output channels
The external galvanic data communication are needed. The ten standard output channels
converter G.703/G.703E1 makes an optical-to- are used for trip output or any signalling
galvanic conversion for connection to a purpose. The two high speed signal output
multiplexer. These units are designed for 64 channels are used for applications where
kbit/s resp 2Mbit/s operation. The converter short operating time is essential. Eight
is delivered with 19” rack mounting optically isolated binary inputs cater for
accessories. required binary input information.
ABB 19
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
20 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
B C
D
xx05000003.vsd
IEC05000003 V1 EN
xx05000004.vsd
IEC05000004 V1 EN
Case size A B C D E F
6U, 1/2 x 19” 265.9 223.7 201.1 242.1 252.9 205.7
6U, 3/4 x 19” 265.9 336.0 201.1 242.1 252.9 318.0
6U, 1/1 x 19” 265.9 448.1 201.1 242.1 252.9 430.3
(mm)
ABB 21
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
▪ 1/2 case size (h) 254.3 mm (w) 210.1 • Wall mounting kit
mm
▪ 3/4 case size (h) 254.3 mm (w) 322.4 See ordering for details about available
mm mounting alternatives.
▪ 1/1 case size (h) 254.3 mm (w) 434.7
mm
22 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
4. Connection diagrams
Table 1. Designations for 1/2 x 19” casing with 1 TRM slot
ABB 23
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
24 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
ABB 25
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
OEM 2) X311:A, B, C, D
Note!
1) 2 LDCM can be included. First LDCM always
in position X313, second LDCM always in
position X303.
2) OEM X311:A, B (IEC 61850-8-1). OEM
X311:C, D (IEC 61850-8-1)
26 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
ABB 27
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
IEC08000479 BG V1 EN
AI01 AI02 AI03 AI04 AI05 AI06 AI07 AI08 AI09 AI10 AI11 AI12
configuration
(50/60 Hz)
12I, 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A
12I, 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A
9I+3U, 1A 1A 1A 1A 1A 1A 1A 1A 1A 110-220V 110-220V 110-220V
1A
9I+3U, 5A 5A 5A 5A 5A 5A 5A 5A 5A 110-220V 110-220V 110-220V
5A
5I, 1A 1A 1A 1A 1A 1A 5A 5A 5A 5A 110-220V 110-220V 110-220V
+4I, 5A
+3U
7I+5U, 1A 1A 1A 1A 1A 1A 1A 110-220V 110-220V 110-220V 110-220V 110-220V
1A
7I+5U, 5A 5A 5A 5A 5A 5A 5A 110-220V 110-220V 110-220V 110-220V 110-220V
5A
6I, 5A 5A 5A 5A 5A 5A 5A 1A 110-220V 110-220V 110-220V 110-220V 110-220V
+1I, 1A
+5U
3I, 5A 5A 5A 5A 1A 1A 1A 1A 110-220V 110-220V 110-220V 110-220V 110-220V
+4I, 1A
+5U
6I+6U, 1A 1A 1A 1A 1A 1A 110-220V 110-220V 110-220V 110-220V 110-220V 110-220V
1A
6I+6U, 5A 5A 5A 5A 5A 5A 110-220V 110-220V 110-220V 110-220V 110-220V 110-220V
5A
3I, 5A 5A 5A 5A 1A 1A 1A 110-220V 110-220V 110-220V 110-220V 110-220V 110-220V
+3I, 1A
+6U
28 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
6I, 1A 1A 1A 1A 1A 1A 1A - - - - - -
6I, 5A 5A 5A 5A 5A 5A 5A - - - - - -
Note that internal polarity can be adjusted by setting of analog input CT neutral direction and/or on SMAI pre-
processing function blocks.
IEC08000484 BG V1 EN
IEC08000480 BG V1 EN
ABB 29
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
IEC08000477 BG V1 EN
IEC08000476 BG V1 EN
30 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
IEC08000478 BG V1 EN
IEC08000481 BG V1 EN
Figure 13. Binary output module (BOM). Output contacts named XA corresponds to rear
position X31, X41, and so on, and output contacts named XB to rear position
X32, X42, and so on.
ABB 31
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
IEC08000482 BG V1 EN
IEC08000483 BG V1 EN
Figure 15. Binary in/out module (IOM). Input contacts named XA corresponds to rear position
X31, X41, and so on, and output contacts named XB to rear position X32, X42,
and so on.
32 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
5. Technical data
General
Definitions
Reference The specified value of an influencing factor to which are referred the
value characteristics of the equipment
Nominal The range of values of an influencing quantity (factor) within which, under
range specified conditions, the equipment meets the specified requirements
Operative The range of values of a given energizing quantity for which the equipment,
range under specified conditions, is able to perform its intended functions
according to the specified requirements
Analog inputs
ABB 33
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Auxiliary DC voltage
34 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Table 11. BIM - Binary input module with enhanced pulse counting capabilities
ABB 35
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Table 13. IOM - Binary input/output module contact data (reference standard: IEC
61810-2)
Breaking capacity for AC, cos φ > 0.4 250 V/8.0 A 250 V/8.0 A
36 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Table 14. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary
outputs
ABB 37
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Table 15. SOM - Static Output module data (reference standard: IEC 61810-2):
Electromechanical relay outputs
Table 16. BOM - Binary output module contact data (reference standard: IEC 61810-2)
38 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Influencing factors
ABB 39
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
40 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Test According to
Immunity EN 50263
Emissivity EN 50263
Low voltage directive EN 50178
ABB 41
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Differential protection
Table 25. Transformer differential protection T2WPDIF, T3WPDIF
42 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
ABB 43
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Impedance protection
Table 28. Distance measuring zone, Quad ZMQPDIS
44 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
ABB 45
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Table 30. Full-scheme distance protection, quadrilateral for earth faults ZMMPDIS
46 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
ABB 47
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
48 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Current protection
Table 35. Instantaneous phase overcurrent protection PHPIOC
ABB 49
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
50 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
ABB 51
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
52 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Table 39. Sensitive directional residual overcurrent and power protection SDEPSDE
ABB 53
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Table 39. Sensitive directional residual overcurrent and power protection SDEPSDE ,
continued
Function Range or value Accuracy
Operate time, non 60 ms typically at 0 to 2 x Iset -
directional residual over
current
Reset time, non 60 ms typically at 2 to 0 x Iset -
directional residual over
current
Operate time, start 150 ms typically at 0 to 2 x Iset -
function
Reset time, start function 50 ms typically at 2 to 0 x Iset -
I = Imeasured
Alarm level 1 and 2 (50–99)% of heat content ± 2.0% of heat content trip
trip value
Operate current (50–250)% of IBase ± 1.0% of Ir
Reset level temperature (10–95)% of heat content ± 2.0% of heat content trip
trip
54 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
ABB 55
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Voltage protection
Table 46. Two step undervoltage protection UV2PTUV
56 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
ABB 57
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
(0.18 × k )
IEEE : t =
( M - 1) 2
EQUATION1319 V1 EN (Equation 2)
58 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Frequency protection
Table 52. Underfrequency protection SAPTUF
ABB 59
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Multipurpose protection
Table 55. General current and voltage protection (GAPC)
See table 93 and table 94 Parameter ranges for customer See table 93 and table 94
defined characteristic no 17:
k: 0.05 - 999.00
A: 0.0000 - 999.0000
B: 0.0000 - 99.0000
C: 0.0000 - 1.0000
P: 0.0001 - 10.0000
PR: 0.005 - 3.000
TR: 0.005 - 600.000
CR: 0.1 - 10.0
60 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
High and low voltage limit, (1.0 - 200.0)% of Ubase ± 1.0% of Ur for U<Ur
voltage dependent operation ± 1.0% of U for U>Ur
ABB 61
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
62 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Control
Table 58. Synchronizing, synchrocheck and energizing check SESRSYN
ABB 63
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
64 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Table 59. Voltage control TR1ATCC, TR8ATCC, TCMYLTC and TLCYLTC, continued
Function Range or value Accuracy
Alarm level of active power in (-9999.99–9999.99) MW ± 1.0% of Sr
forward and reverse direction
Alarm level of reactive power in (-9999.99–9999.99) MVAr ± 1.0% of Sr
forward and reverse direction
Time delay for alarms from power (1–6000) s ± 0.5% ± 10 ms
supervision
Tap position for lowest and highest (1–63) -
voltage
mA for lowest and highest voltage (0.000–25.000) mA -
tap position
Type of code conversion BIN, BCD, GRAY, SINGLE, mA -
Time after position change before (1–60) s ± 0.5% ± 10 ms
the value is accepted
Tap changer constant time-out (1–120) s ± 0.5% ± 10 ms
Raise/lower command output pulse (0.5–10.0) s ± 0.5% ± 10 ms
duration
Scheme communication
Table 60. Scheme communication logic for residual overcurrent protection ECPSCH
ABB 65
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Table 61. Current reversal and weak-end infeed logic for residual overcurrent protection
ECRWPSCH
Logic
Table 62. Tripping logic SMPPTRC
66 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
LogicOR 60 60 160 - -
LogicXOR 10 10 20 - -
LogicInverter 30 30 80 - -
LogicSRMemory 10 10 20 - -
LogicGate 10 10 20 - -
LogicTimer 10 10 20 (0.000–90000.000) s ± 0.5% ± 10 ms
LogicPulseTimer 10 10 20 (0.000–90000.000) s ± 0.5% ± 10 ms
LogicTimerSet 10 10 20 (0.000–90000.000) s ± 0.5% ± 10 ms
LogicLoopDelay 10 10 20 (0.000–90000.000) s ± 0.5% ± 10 ms
Monitoring
Table 64. Measurements CVMMXN
ABB 67
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
68 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Function Value
Buffer capacity Maximum number of events in 1000
the list
Resolution 1 ms
Accuracy Depending on time
synchronizing
ABB 69
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Function Value
Buffer capacity Maximum number of indications presented 96
for single disturbance
Maximum number of recorded disturbances 100
Function Value
Buffer capacity Maximum number of events in disturbance report 150
Maximum number of disturbance reports 100
Resolution 1 ms
Accuracy Depending on
time
synchronizing
Function Value
Buffer capacity Maximum number of analog inputs 30
Maximum number of disturbance reports 100
Function Value
Buffer capacity Maximum number of analog inputs 40
Maximum number of binary inputs 96
Maximum number of disturbance reports 100
Maximum total recording time (3.4 s recording time and 340 seconds (100 recordings)
maximum number of channels, typical value) at 50 Hz
280 seconds (80 recordings) at
60 Hz
Metering
Table 73. Pulse counter PCGGIO
70 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Station communication
Table 75. IEC 61850-8-1 communication protocol
Function Value
Protocol IEC 61850-8-1
Communication speed for the IEDs 100BASE-FX
Function Value
Protocol LON
Communication speed 1.25 Mbit/s
Function Value
Protocol SPA
Communication speed 300, 1200, 2400, 4800, 9600, 19200 or 38400 Bd
Slave number 1 to 899
Function Value
Protocol IEC 60870-5-103
Communication speed 9600, 19200 Bd
ABB 71
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Remote communication
72 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Hardware
ABB 73
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
IED
Table 84. Water and dust protection level according to IEC 60529
Connection system
74 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Data Value
Recording manner Continuous, event controlled
List size 1000 events, first in-first out
Function Value
Time tagging resolution, events and sampled measurement values 1 ms
Time tagging error with synchronization once/min (minute pulse ± 1.0 ms typically
synchronization), events and sampled measurement values
Time tagging error with SNTP synchronization, sampled ± 1.0 ms typically
measurement values
Function Value
Max antenna cable attenuation 26 db @ 1.6 GHz
Antenna cable impedance 50 ohm
Lightning protection Must be provided externally
Antenna cable connector SMA in receiver end
TNC in antenna end
ABB 75
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Inverse characteristic
Table 93. ANSI Inverse time characteristics
Reset characteristic:
tr
t = ×k
(I 2
)
-1
EQUATION1250-SMALL V1 EN
I = Imeasured/Iset
76 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
æ A ö
t = ç P ÷×k
ç ( I - 1) ÷
è ø
EQUATION1251-SMALL V1 EN
I = Imeasured/Iset
TR
t = ×k
(I PR
- CR )
EQUATION1253-SMALL V1 EN
I = Imeasured/Iset
ABB 77
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
I = Imeasured/Iset
æ I ö
t = 5.8 - ç 1.35 × In ÷
è k ø
EQUATION1138-SMALL V1 EN
I = Imeasured/Iset
78 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Table 96. Inverse time characteristics for Two step undervoltage protection (PUVM, 27)
U< = Uset
U = UVmeasured
U< = Uset
U = Umeasured
ABB 79
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Table 97. Inverse time characteristics for Two step overvoltage protection (POVM, 59)
U> = Uset
U = Umeasured
80 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Table 98. Inverse time characteristics for Two step residual overvoltage protection
(POVM, 59N)
U> = Uset
U = Umeasured
ABB 81
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
6. Ordering
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management. Be aware that certain
functions can only be ordered in combination with other functions and that some functions require specific
hardware selections.
Basic IED 670 platform and common functions housed in selected casing
Manuals on CD
82 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Current protection
Voltage protection
Control
Logic Rotating Switch for function selection and LHMI presentation (SLGGIO)
Selector mini switch (VSGGIO)
IEC 618850 generic communication I/O functions (DPGGIO)
Single point generic control 8 signals
Single command, 16 signals
Horizontal communication via GOOSE for VCTR
ABB 83
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Logic
Monitoring
Metering
Station communication
84 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Remote communication
Hardware
Product specification
RET670 Quantity:
Default:
The IED connect CD contains configuration alternative. Use the PCM600 to create or modify the configuration. The
PCM600 can also be used for adaptation of an included example configuration.
Option:
Customer specific configuration On request
Rule: Same connection type for Power supply modules and I/O modules must be ordered
Compression terminals 1MRK 002 960-AA
ABB 85
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Differential protection
Qty:
Transformer differential protection, three winding (PDIF, 87T)
1 2 1MRK 002 901-CB
Optional functions
Differential protection
1 2 3 4 5 6
1Ph High impedance differential protection (PDIF, 87) Qty: 1MRK 002 901-HA
1 2 3
Restricted earth fault protection, low impedance (PDIF, 87N) Qty: 1MRK 002 901-EA
Impedance protection
Rule: One and only one of the alternatives (Alt. 1-3) can be ordered
Alternative 1: 1 2 3 4 5
Rule: Distance protection and Directional impedance Qty: 1MRK 002 904-XA
must be ordered together
Distance protection zones, quadrilateral characteristic
(PDIS, 21)
Directional impedance quadrilateral (RDIR, 21) 1 2
Qty: 1MRK 002 904-YA
Alternative 2: 1 2 3 4 5
Rule: All functions within the alternative must be ordered Qty: 1MRK 002 925-EA
Full scheme distance protection, mho characteristic
(PDIS, 21)
Full scheme distance protection, quadrilateral for earth 1 2 3 4 5
faults(PDIS, 21) Qty: 1MRK 002 925-GA
Additional distance protection directional function for Qty: 1MRK 002 908-VA
earth faults(RDIR)
Mho impedance supervision logic (GAPC) Qty: 1MRK 002 908-UA
86 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Current protection
Voltage protection
ABB 87
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Frequency protection
Multipurpose protection
7 8 9 10 11 12
Control
Tap changer control and supervision, 6 binary inputs, 1 2 3 4 1MRK 002 925-PA
coded binary (Binary, BCD, Gray)(TCMYLTC, 84) Qty:
88 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Scheme communication
Scheme communication logic for residual overcurrent protection (ECPSCH, 85) 1MRK 002 906-GA
Current reversal and weak end infeed logic for residual overcurrent protection 1MRK 002 906-HA
(ECRWPSCH, 85)
Logic
Optional hardware
ABB 89
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Rule: One must be ordered. “Medium size - graphic display” HMI is required in
order to be able to give Raise/Lower commands, in the manual operating mode, to
the OLTC from IED 670 via Voltage control (VCTR) function.
Small size – text only, IEC symbols, 1/2 19” 1MRK 000 008-HB
Small size – text, IEC symbols, 3/4 19” 1MRK 000 008-PB
Small size – text, IEC symbols, 1/1 19” 1MRK 000 008-KB
Medium size – graphic display, IEC symbols, 1/2 19” 1MRK 000 008-LB
Medium size – graphic display, IEC symbols, 3/4 19” 1MRK 000 008-NB
Medium size – graphic display, IEC symbols, 1/1 19” 1MRK 000 008-MB
Medium size – graphic display, ANSI symbols, 1/2 19” 1MRK 000 008-LC
Medium size – graphic display, ANSI symbols, 3/4 19” 1MRK 000 008-NC
Medium size – graphic display, ANSI symbols, 1/1 19” 1MRK 000 008-MC
90 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Analog system
ABB 91
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Note: One Analog digital conversion module, with time synchronization is always delivered with each Transformer
input module.
Case size
When ordering I/O modules, observe the maximum quantities according to tables below.
Note: Standard order of location for I/O modules is BIM-BOM-SOM-IOM-MIM-GSM from left to right as seen from
the rear side of the IED, but can also be freely placed. Only the GSM (GPS time synchronization module) has a
specific slot designation, depending on case size.
Note: Maximum quantity of I/O modules depends on the type of connection terminals.
92 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
3/4 x 19”, one (1) TRM 4 P3, P5, P7, P9 Note: No ringlugs in 1MRK 000 151-NB
P9 if GSM is ordered
3/4 x 19”, two (2) TRM 2 P3, P5 1MRK 000 151-NE
ABB 93
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
8 9 10 11 12 13 14
8 9 10 11 12 13 14
8 9 10 11 12 13 14
8 9 10 11 12 13 14
8 9 10 11 12 13 14
8 9 10 11 12 13 14
8 9 10 11 12 13 14
8 9 10 11 12 13 14
94 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Binary output module 24 output relays (BOM) Qty: 1 2 3 4 1MRK 000 614-AB
ABB 95
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Note: Optical ethernet module, 2 glass interfaces is not allowed together with SLM.
Optical ethernet module, 1 channel glass 1MRK 002 266-AA
Serial and LON communication module, supports SPA/IEC 60870-5-103, LON and DNP
3.0
Serial/LON plastic interface 1MRK 001 608-AA
Galvanic RS485 communication module for DNP 3.0 1MRK 002 309-AA
Rule: Max two LDCM can be ordered, only one LDCM in 1/2 x 19" case
Optical short range line data communication module 1 2
(Multi mode 850 nm) (SR LDCM) Qty: 1MRK 002 122-AB
Time synchronization
Engineering facilities
19” rack mounting kit for 1/2 x 19” IED or 2 x RHGS6 or RHGS12 Quantity: 1MRK 002 420-BB
19” rack mounting kit for 3/4 x 19” IED or 3 x RHGS6 Quantity: 1MRK 002 420-BA
19” rack mounting kit for 1/1 x 19” IED Quantity: 1MRK 002 420-CA
Wall mounting kit for all IED sizes Quantity: 1MRK 002 420-DA
96 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Flush mounting kit for all IED sizes Quantity: 1MRK 000 020-Y
Flush mounting kit + IP54 sealing (factory mounted). Cannot be Quantity: 1MRK 002 420-EA
ordered separately thus must be specified when ordering an IED.
Accessories
GPS antenna and mounting details
External interface converter from C37.94 to G703 including Quantity: 1 2 1MRK 002 245-AA
1U 19” rack mounting accessories
External interface converter from C37.94 to G703.E1 Quantity: 1 2 1MRK 002 245-BA
ABB 97
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Test switches type RTXP 24 are ordered are ordered separately. Please refer to Section
separately. Please refer to Section "Related "Related documents"for reference to
documents" for reference to corresponding corresponding documents.
documents.
RHGS 6 Case or RHGS 12 Case with mounted
RTXP 24 and the on/off switch for dc-supply
Protection cover
Protective cover for rear side of RHGS6, 6U, 1/4 x 19” Quantity: 1MRK 002 420-AE
Protective cover for rear side of IED, 6U, 1/2 x 19” Quantity: 1MRK 002 420-AC
Protective cover for rear side of IED, 6U, 3/4 x 19” Quantity: 1MRK 002 420-AB
Protective cover for rear side of IED, 6U, 1/1 x 19” Quantity: 1MRK 002 420-AA
High impedance resistor unit 1-ph with resistor 1.8 kOhms and Quantity: 1 2 3 RK795101-MA
voltage dependent resistor for 20-100V operating voltage
High impedance resistor unit 3-ph with resistor 1.8 kOhms and Quantity: RK795101-MB
voltage dependent resistor for 20-100V operating voltage
High impedance resistor unit 1-ph with resistor 6.8 kOhms and Quantity: 1 2 3 RK795101-CB
voltage dependent resistor for 100-400V operating voltage
High impedance resistor unit 3-ph with resistor 6.8 kOhms and Quantity: RK795101-DC
voltage dependent resistor for 100-400V operating voltage
Combiflex
Key switch for lock-out of settings via LCD-HMI Quantity: 1MRK 000 611-A
Note: To connect the key switch, leads with 10 A Combiflex socket on one end must be used.
Front connection cable between LCD-HMI and PC Quantity: 1MRK 001 665-CA
98 ABB
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Manuals
Note: One (1) IED Connect CD containing user documentation (Operator’s manual, Technical reference
manual, Installation and commissioning manual, Application manual and Getting started guide),
Connectivity packages and LED label template is always included for each IED.
Rule: Specify additional quantity of IED Connect CD requested. Quantity: 1MRK 002 290-AB
User documentation
Rule: Specify the number of printed manuals requested IEC Quantity: 1MRK 504 087-UEN
Operator’s manual
ABB 99
Transformer protection RET670 1MRK 504 090-BEN B
Customized
Product version: 1.1 Issued: June 2010
Reference information
For our reference and statistics we would be pleased to be provided with the following application data:
Related documents
100 ABB
101
Contact us
www.abb.com/substationautomation