TAC I/A Series 1

MN 800 Series Controllers


TAC I/A Series Micronet MN 800
The TAC I/A Series MicroNet MN 800 Series
Controllers are programmable, interoperable,
LonWorks™ based control devices.
The MN 800 series controller features eight universal
inputs, four analog outputs, eight digital outputs, a
5.1 volt reference, LED indication, and support for
TAC MicroNet
MN-Sx Sensor Link (S-Link) sensors. Additionally,
network capability is provided through the use
of a FTT-10 transceiver allowing the controller
to communicate to other devices as part of a
LonWorks Free Topology Communications network.
A direct connection to a WPA-LON WorkPlace
Communication adapter and a PC with WorkPlace
SPECIFICATIONS Tech Tool software is necessary to download and
modify applications.
Hardware Designed for new or existing systems, the MN 800
Dimensions series controller may be used in large TAC I/A Series
ENCL-MZ800-WAL MicroNet systems, as well as with stand alone
applications. When programmed using WorkPlace
8.5 in. W x 10.875 in. H x 4.25 in. D
Tech Tool or loaded with a previously designed
(216 mm x 266 mm x 104 mm) application, it provides control strategies for a wide
ENCL-MZ800-PAN variety of mechanical equipment. Typical applications
8.5 in. W x 10.675 in. H x 4.125 in. D include central station air handlers, VAV air handlers,
fan coil units, unit ventilators, and cooling towers.
(216 mm x 262 mm x 101 mm)
MNL-800-101 The WorkPlace Tech Tool software is used to
Not applicable; circuit board only. program the controllers or to download applications.
The MN 800 series controller offers the advantages
Mounting of standalone or networked control. Using a TAC
ENCL-MZ800-WAL I/A Series MicroNet sensor (MN-Sx Series), the
NEMA 1 location. operator can monitor controller performance and edit
ENCL-MZ800-PAN operational values.
Control compartment of controlled equipment.
Microprocessor
Environment
SAF-C161, 10 MHz clock speed, 16-bit word size.
Operating Temperature
Memory
-40 to 140 °F (-40 to 60 °C)
EPROM 512 kbytes
RAM 128 kbytes Shipping and Storage Temperature
-40 to 160 °F (-40 to 71 °C)
EEPROM 32 kbytes
Humidity
Wiring Terminals 5 to 95% RH, non-condensing
Screw terminals. Each terminal accepts one AWG
#14 to 22 (2.08 to 0.326 mm2) wire or up to two Backup Clock/RAM
AWG #18 to 22 (0.823 to 0.326 mm2) wires. 3 days (rechargeable) at 77 °F (25 °C).
Backed-up Time Clock
Electrical
Accuracy +/-150 sec/mo at 77 °F (25 °C).
Power Supply Input Specifications continued on next page.
20.4 to 30 Vac, 50/60 Hz.
Maximum Power Consumption
20 VA at 24 Vac, 50/60 Hz.
Surge Immunity Compliance
IEEE C62.41 (IEEE-587, Category A & B).
TAC I/A Series MN 800 Series Controllers 2

Specifications continued from first page. 10K ohm Thermistor w/ 11K ohm Shunt Resistor
-40 to 250 °F (-40 to 121 °C) range. TSMN-57011-
AGENCY listings 850, TS-5700-850 Series or equivalent.
US 1k Resistance 0 to 1.5k ohms.
FCC Part 15, Class A 10k Resistance 0 to 10.5k ohms.
UL 916, File #E71385 Category PAZX Potentiometers 1K to 15K ohm resistance, using
5.1 V reference.
Canadian
UL Listed to Canadian Safety Standards Voltage 0 to 5 Vdc.
(CAN/CSA 22.2) Current 0 to 20 mA requires an external 250 ohm
shunt resistor.
Australian
Digital Input Dry Contact. Detection of closed
Meets requirements to bear the C-Tick Mark
switch requires less than 300 ohms. Detection of
European Community- EMC Directive open switch requires more than 1.5K ohms.
EN55022 (Emissions, Class A)
EN50081-1 (EMC, Immunity)
EN50082-1 (AC Mains Power Line Voltage) Communications
Inputs and outputs LonWorks Networks
Pulse Count A LonWorks communications network uses a
IN1 Only TP/FT-10 Free Topology configuration. Controllers
Minimum pulse count rate of 1 per 4 min. on a LonWorks network can communicate with each
other in a peer-to-peer fashion. A LonWorks network
Maximum pluse count rate of 10 per sec (50 msec
has a communications speed of 78 kbps, using
minimum On or Off time per pulse).
unshielded, twisted-pair cabling, with connections
IN2-IN8 that are not polarity sensitive.
Minimum pulse count rate of 1 per 4 min.
S-Link
Maximum pluse count rate of 1 per sec (0.5 sec The Sensor Link (S-Link) communications wiring
minimum On or Off time per pulse). provides power and a communication interface for an
Analog Outputs MN-Sx MicroNet sensor. The various MN-Sx sensors
Quantity 4 can provide room temperature, room humidity,
Type 0-20 mA range programmable source into 80 to setpoint adjustment, and occupancy override. This
550 ohm load, momentary short circuit protection. connection uses two-wire, unshielded cable and is
not polarity sensitive. Maximum wire length allowed
Digital to Analog Conversion Resolution 8 bit.
between a controller and a MicroNet Sensor is 200 ft
Digital Outputs (61 m).
Quantity 8
Contact Ratings 30 VA at 24 Vac, pilot duty. 120 VA
at 120 Vac, pilot duty.
Contact Type Form C (SPDT) isolated.
Status Indication Light emitting diode.
Voltage Reference 5.1 Vdc, 20 mA maximum.
Analog to Digital Conversion Resolution
12 bit.
Universal Inputs
Quantity 8
1K ohm Balco Input -40 to 250 °F (-40 to 121°C)
© 2009 Schneider Electric. All rights reserved.

range. TSMN-81011, TS-8000 Series or equivalent.


1K ohm Platinum Input -40 to 240 °F (-40 to
116 °C) range. TSMN-58011, TS-5800 Series or
equivalent.
1K ohm Copper Input -31 to 240 °F (-35 to 116 °C)
range. TS-5600 Series or equivalent.

Schneider Electric 1354 Clifford Avenue, P.O. Box 2940, Loves Park, IL 61132-2940, USA 1-888-444-1311 www.schneider-electric.com/buildings

F-26627-5 November 2009 pm


TAC I/A Series MN 800 Series Controllers 3

INPUTS FROM MN-SX I/A SERIES MICRONET SENSORS


Inputs Description MN-Sx Sensor

Space Temperature 32 to 122 °F (0 to 50 °C) MN-S1, MN-S1HT, MN-S2, MN-S2HT, MN-S3, MN-S3HT,
MN‑S4, MN-S4HT, MN-S4-FCS, MN-S4HT-FCS, MN-S5
and MN-S5HT
Space Humidity 5 to 95% RH, Non-condensing MN-S1HT, MN-S2HT, MN-S3HT, MN-S4HT, MN-S4HT-
FCS, and MN-S5HT
Adjustable Setpoint 40 to 95 °F (4 to 35°C) MN-S3, MN-S3HT, MN-S4, MN-S4HT, MN-S4-FCS,
MN‑S4HT‑FCS, MN-S5, and MN-S5HT
Override Pushbutton For standalone occupancy control or MN-S2, MN-S2HT, MN-S3, MN-S3HT, MN-S4, MN-S4HT,
remote status monitoring of local status MN‑S5, and MN-S5HT
condition.
Fan Operation and Speed Fan mode selection: On, Speed (Low/ MN-S4, MN-S4HT, MN-S4-FCS, MN-S4HT-FCS, MN-S5,
Medium/High), or Auto. and MN-S5HT
System Mode System mode selection: Heat, Cool, Off, MN-S4, MN-S4HT, MN-S5, and MN-S5HT
or Auto.
Emergency Heat Emergency heat mode selection: Enable MN-S5 and MN-S5HT
or Disable

MODELS
Part Number Description Backed-up Time Clock

ENCL-MZ800-WAL TAC I/A Series MicroNet 800 Series No


Controller with Wall-Mount Enclosure
ENCL-MZ800-PAN TAC I/A Series MicroNet 800 Series No
Controller with Panel-Mount
Enclosure
MNL-800-101 TAC I/A Series MicroNet 800 Series Yes
Controller Card

FEATURES
• Complete user creation of custom control • Capability to function in standalone mode or
strategies through TAC I/A Series WorkPlace as part of a LonWorks TP/FT-10 Free Topology
Tech Tool software adapts the MN 800 Series communications network.
Controller to virtually any HVAC control sequence • Multiple controllers on a LonWorks FTT network
or mechanical system. create a complex network of controllers for
• LonWorks compatible applications are completely virtually any building control need.
programmable. • Provides basic trend of up to 24 points within
• WorkPlace Tech Tool can be used to reconfigure the application. Trend maintains last 48 analog
and edit application configuration data to fit a samples or digital changes of state with time
© 2009 Schneider Electric. All rights reserved.

wide range of control requirements. stamp. Analog sampling adjustable time rates.
• Interoperability achieved using LonWorks
Standard Network Variable Types (SNVTs).
• Backed-up time clock provides true stand-alone
direct digital control with optimum start stop,
scheduling functions, and backed-up RAM.

Schneider Electric 1354 Clifford Avenue, P.O. Box 2940, Loves Park, IL 61132-2940, USA 1-888-444-1311 www.schneider-electric.com/buildings

F-26627-5 November 2009 pm


TAC I/A Series MN 800 Series Controllers 4

Architecture
PDA
MicroNet Sensor Universal
Desktop PC or (MN-S5 Shown) 5
Notebook PC with Network
WorkPlace Tech Controller
4 MNL-V3RVx
Tool Software 1 MN 100, MN 150, or
2 or MN 50
MN 200 Controller
Controller

SW
24H
SW 3

MNL-CIM
24H
SW 2
24H
24H 1
24G
GN AO
D

UI
S-L
K/C DI

MicroNet Controller
OM
S-L
K
LO
N
LO
N

Interface Module

LONWORKS Router 6
Cet appareil numerique de la classe B respecte toutes les exigences du Reglement sur le material brouilleur du Canada
This Class B digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations.
interference that may cause undesired operation.
device may not cause harmful interference, and (2) This device must accept any interference received, including
This device conforms with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This

D E C O N N E C T E R AVA N T E N T R E T E N .
D I S C O N N E C T P O W E R B E F O R E S E RV I C I N G .
I N T E R C O N N E C T S E PA R AT E C L A S S 2 C I R C U I T S .
R I S K O F E L E C T R I C A L S H O C K O R F I R E . D O N OT

C5
DO5

Network
DO5: 250VAC, 3A Max, COS f = 0.4.

(if required)
DO1-DO4: 24VAC, 0.4A Max Total Load.
S-LK: 16VDC Max, Class 2.
CAUTION

UI: 5VDC Max, Class 2.


Ambient Temp: -40°C to +60°C

Power: 24VAC, 50/60Hz, Class 2,


Regulating Equipment
N2223

Temperature indicating and

DO4
8.5VA + DO1-DO4 loads.

24VAC
DO3

I/A
DO2
24VAC
DO1

Se
E9429
934G

MN rie
80 s®
T
I
M
X

0
V
C
E
R
C
V

SRVC
R
S

LON
J1

LON
S-LK
S-LK

COM 0V

COM 0V
UI1

MNL-11RF2
I/A Series
UI2

24VAC
UI3

GND
0V

3 MNL-V1RVx or 4
MN 110 or MN 130 MNL-V2RVx MN 800 MicroNet Sensor
Controller Controller Controller (MN-S3 Shown)

1 A PC can be connected to the LONWORKS TP/FT-10 Network, either directly or through the LONWORKS network jack of a
LONWORKS controller or MN-Sxxx Wall Sensor. The PC must have an Echelon™ LONTALK™ adapter card.
2 Programming any of the TAC I/A Series controllers, including the MN 800 Series, requires WorkPlace Tech Tool.
3 This controller is not suitable for exposed mounting on a wall or panel, or in any other easily accessible place due to the
possibility of personal contact with the high-voltage terminals. It must be mounted inside a suitable grounded metal enclosure.
4 MicroNet Sensors can be connected to any MN controller.
5 A PDA running the Pocket I/A interface software may be used to communicate with TAC I/A Series MicroNet controllers.
6 When routers are used, WP Tech is able to communicate through them to any of the TAC I/A Series devices on the network.

MicroNet Sensor MN 100, MN 150, or MN 110 or MN 130 MN 800


(MN-S5 Shown) MN 200 Controller Controller
3 Controller
4
I/A
Se
MN rie
80
0

Cet appareil numerique de la classe B respecte toutes les exigences du Reglement sur le material brouilleur du Canada
This Class B digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations.
interference that may cause undesired operation.
device may not cause harmful interference, and (2) This device must accept any interference received, including
This device conforms with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This

D E C O N N E C T E R AVA N T E N T R E T E N .
D I S C O N N E C T P O W E R B E F O R E S E RV I C I N G .
I N T E R C O N N E C T S E PA R AT E C L A S S 2 C I R C U I T S.
R I S K O F E L E C T R I C A L S H O C K O R F I R E . D O N OT

C5
DO5

DO5: 250VAC, 3A Max, COS f = 0.4.


DO1-DO4: 24VAC, 0.4A Max Total Load.
S-LK: 16VDC Max, Class 2.
CAUTION

UI: 5VDC Max, Class 2.

Desktop PC with TAC I/A Series


Ambient Temp: -40°C to +60°C

Power: 24VAC, 50/60Hz, Class 2,


Regulating Equipment
N2223

Temperature indicating and

DO4
8.5VA + DO1-DO4 loads.

24VAC
DO3
DO2
24VAC
DO1
E9429
934G
T
I
M

Enterprise Server
X
V
C
E
R
C
V

SRVC
R
S

LON
J1

LON
S-LK
S-LK

COM 0V

COM 0V
UI1

MNL-11RF2
I/A Series
UI2

LONWORKS
24VAC
UI3

GND
0V

Network

6 Router
Ethernet (if required)
CLO
SE
OP 24G
EN
SW 24G
24H
SW 3
24H
SW 2
24H
24H 1
24G
GN AO
D CO
M
UI
S-L
K/C DI
OM
S-L
K
LO
N

Universal
LO
N

4
Network MNL-V1RVx or MNL-V3RVx MicroNet Sensor
© 2009 Schneider Electric. All rights reserved.

Controller MNL-V2RVx or MN 50 (MN-S3 Shown)


Controller Controller

Distributed, manufactured, and sold by Schneider Electric. I/A


Series trademarks are owned by Invensys Systems, Inc. and are
used on this product under master license from Invensys. Invensys
does not manufacture this product or provide any product warranty
or support. For service, support, and warranty information, contact
Schneider Electric.

On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric, however there
remain references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate corporate brand changes.

All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.

Schneider Electric 1354 Clifford Avenue, P.O. Box 2940, Loves Park, IL 61132-2940, USA 1-888-444-1311 www.schneider-electric.com/buildings

F-26627-5 November 2009 pm

Вам также может понравиться