Specifications continued from first page. 10K ohm Thermistor w/ 11K ohm Shunt Resistor
-40 to 250 °F (-40 to 121 °C) range. TSMN-57011-
AGENCY listings 850, TS-5700-850 Series or equivalent.
US 1k Resistance 0 to 1.5k ohms.
FCC Part 15, Class A 10k Resistance 0 to 10.5k ohms.
UL 916, File #E71385 Category PAZX Potentiometers 1K to 15K ohm resistance, using
5.1 V reference.
Canadian
UL Listed to Canadian Safety Standards Voltage 0 to 5 Vdc.
(CAN/CSA 22.2) Current 0 to 20 mA requires an external 250 ohm
shunt resistor.
Australian
Digital Input Dry Contact. Detection of closed
Meets requirements to bear the C-Tick Mark
switch requires less than 300 ohms. Detection of
European Community- EMC Directive open switch requires more than 1.5K ohms.
EN55022 (Emissions, Class A)
EN50081-1 (EMC, Immunity)
EN50082-1 (AC Mains Power Line Voltage) Communications
Inputs and outputs LonWorks Networks
Pulse Count A LonWorks communications network uses a
IN1 Only TP/FT-10 Free Topology configuration. Controllers
Minimum pulse count rate of 1 per 4 min. on a LonWorks network can communicate with each
other in a peer-to-peer fashion. A LonWorks network
Maximum pluse count rate of 10 per sec (50 msec
has a communications speed of 78 kbps, using
minimum On or Off time per pulse).
unshielded, twisted-pair cabling, with connections
IN2-IN8 that are not polarity sensitive.
Minimum pulse count rate of 1 per 4 min.
S-Link
Maximum pluse count rate of 1 per sec (0.5 sec The Sensor Link (S-Link) communications wiring
minimum On or Off time per pulse). provides power and a communication interface for an
Analog Outputs MN-Sx MicroNet sensor. The various MN-Sx sensors
Quantity 4 can provide room temperature, room humidity,
Type 0-20 mA range programmable source into 80 to setpoint adjustment, and occupancy override. This
550 ohm load, momentary short circuit protection. connection uses two-wire, unshielded cable and is
not polarity sensitive. Maximum wire length allowed
Digital to Analog Conversion Resolution 8 bit.
between a controller and a MicroNet Sensor is 200 ft
Digital Outputs (61 m).
Quantity 8
Contact Ratings 30 VA at 24 Vac, pilot duty. 120 VA
at 120 Vac, pilot duty.
Contact Type Form C (SPDT) isolated.
Status Indication Light emitting diode.
Voltage Reference 5.1 Vdc, 20 mA maximum.
Analog to Digital Conversion Resolution
12 bit.
Universal Inputs
Quantity 8
1K ohm Balco Input -40 to 250 °F (-40 to 121°C)
© 2009 Schneider Electric. All rights reserved.
Schneider Electric 1354 Clifford Avenue, P.O. Box 2940, Loves Park, IL 61132-2940, USA 1-888-444-1311 www.schneider-electric.com/buildings
Space Temperature 32 to 122 °F (0 to 50 °C) MN-S1, MN-S1HT, MN-S2, MN-S2HT, MN-S3, MN-S3HT,
MN‑S4, MN-S4HT, MN-S4-FCS, MN-S4HT-FCS, MN-S5
and MN-S5HT
Space Humidity 5 to 95% RH, Non-condensing MN-S1HT, MN-S2HT, MN-S3HT, MN-S4HT, MN-S4HT-
FCS, and MN-S5HT
Adjustable Setpoint 40 to 95 °F (4 to 35°C) MN-S3, MN-S3HT, MN-S4, MN-S4HT, MN-S4-FCS,
MN‑S4HT‑FCS, MN-S5, and MN-S5HT
Override Pushbutton For standalone occupancy control or MN-S2, MN-S2HT, MN-S3, MN-S3HT, MN-S4, MN-S4HT,
remote status monitoring of local status MN‑S5, and MN-S5HT
condition.
Fan Operation and Speed Fan mode selection: On, Speed (Low/ MN-S4, MN-S4HT, MN-S4-FCS, MN-S4HT-FCS, MN-S5,
Medium/High), or Auto. and MN-S5HT
System Mode System mode selection: Heat, Cool, Off, MN-S4, MN-S4HT, MN-S5, and MN-S5HT
or Auto.
Emergency Heat Emergency heat mode selection: Enable MN-S5 and MN-S5HT
or Disable
MODELS
Part Number Description Backed-up Time Clock
FEATURES
• Complete user creation of custom control • Capability to function in standalone mode or
strategies through TAC I/A Series WorkPlace as part of a LonWorks TP/FT-10 Free Topology
Tech Tool software adapts the MN 800 Series communications network.
Controller to virtually any HVAC control sequence • Multiple controllers on a LonWorks FTT network
or mechanical system. create a complex network of controllers for
• LonWorks compatible applications are completely virtually any building control need.
programmable. • Provides basic trend of up to 24 points within
• WorkPlace Tech Tool can be used to reconfigure the application. Trend maintains last 48 analog
and edit application configuration data to fit a samples or digital changes of state with time
© 2009 Schneider Electric. All rights reserved.
wide range of control requirements. stamp. Analog sampling adjustable time rates.
• Interoperability achieved using LonWorks
Standard Network Variable Types (SNVTs).
• Backed-up time clock provides true stand-alone
direct digital control with optimum start stop,
scheduling functions, and backed-up RAM.
Schneider Electric 1354 Clifford Avenue, P.O. Box 2940, Loves Park, IL 61132-2940, USA 1-888-444-1311 www.schneider-electric.com/buildings
Architecture
PDA
MicroNet Sensor Universal
Desktop PC or (MN-S5 Shown) 5
Notebook PC with Network
WorkPlace Tech Controller
4 MNL-V3RVx
Tool Software 1 MN 100, MN 150, or
2 or MN 50
MN 200 Controller
Controller
SW
24H
SW 3
MNL-CIM
24H
SW 2
24H
24H 1
24G
GN AO
D
UI
S-L
K/C DI
MicroNet Controller
OM
S-L
K
LO
N
LO
N
Interface Module
LONWORKS Router 6
Cet appareil numerique de la classe B respecte toutes les exigences du Reglement sur le material brouilleur du Canada
This Class B digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations.
interference that may cause undesired operation.
device may not cause harmful interference, and (2) This device must accept any interference received, including
This device conforms with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This
D E C O N N E C T E R AVA N T E N T R E T E N .
D I S C O N N E C T P O W E R B E F O R E S E RV I C I N G .
I N T E R C O N N E C T S E PA R AT E C L A S S 2 C I R C U I T S .
R I S K O F E L E C T R I C A L S H O C K O R F I R E . D O N OT
C5
DO5
Network
DO5: 250VAC, 3A Max, COS f = 0.4.
(if required)
DO1-DO4: 24VAC, 0.4A Max Total Load.
S-LK: 16VDC Max, Class 2.
CAUTION
DO4
8.5VA + DO1-DO4 loads.
24VAC
DO3
I/A
DO2
24VAC
DO1
Se
E9429
934G
MN rie
80 s®
T
I
M
X
0
V
C
E
R
C
V
SRVC
R
S
LON
J1
LON
S-LK
S-LK
COM 0V
COM 0V
UI1
MNL-11RF2
I/A Series
UI2
24VAC
UI3
GND
0V
3 MNL-V1RVx or 4
MN 110 or MN 130 MNL-V2RVx MN 800 MicroNet Sensor
Controller Controller Controller (MN-S3 Shown)
1 A PC can be connected to the LONWORKS TP/FT-10 Network, either directly or through the LONWORKS network jack of a
LONWORKS controller or MN-Sxxx Wall Sensor. The PC must have an Echelon™ LONTALK™ adapter card.
2 Programming any of the TAC I/A Series controllers, including the MN 800 Series, requires WorkPlace Tech Tool.
3 This controller is not suitable for exposed mounting on a wall or panel, or in any other easily accessible place due to the
possibility of personal contact with the high-voltage terminals. It must be mounted inside a suitable grounded metal enclosure.
4 MicroNet Sensors can be connected to any MN controller.
5 A PDA running the Pocket I/A interface software may be used to communicate with TAC I/A Series MicroNet controllers.
6 When routers are used, WP Tech is able to communicate through them to any of the TAC I/A Series devices on the network.
D E C O N N E C T E R AVA N T E N T R E T E N .
D I S C O N N E C T P O W E R B E F O R E S E RV I C I N G .
I N T E R C O N N E C T S E PA R AT E C L A S S 2 C I R C U I T S.
R I S K O F E L E C T R I C A L S H O C K O R F I R E . D O N OT
C5
DO5
DO4
8.5VA + DO1-DO4 loads.
24VAC
DO3
DO2
24VAC
DO1
E9429
934G
T
I
M
Enterprise Server
X
V
C
E
R
C
V
SRVC
R
S
LON
J1
LON
S-LK
S-LK
COM 0V
COM 0V
UI1
MNL-11RF2
I/A Series
UI2
LONWORKS
24VAC
UI3
GND
0V
Network
6 Router
Ethernet (if required)
CLO
SE
OP 24G
EN
SW 24G
24H
SW 3
24H
SW 2
24H
24H 1
24G
GN AO
D CO
M
UI
S-L
K/C DI
OM
S-L
K
LO
N
Universal
LO
N
4
Network MNL-V1RVx or MNL-V3RVx MicroNet Sensor
© 2009 Schneider Electric. All rights reserved.
On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric, however there
remain references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate corporate brand changes.
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
Schneider Electric 1354 Clifford Avenue, P.O. Box 2940, Loves Park, IL 61132-2940, USA 1-888-444-1311 www.schneider-electric.com/buildings