Вы находитесь на странице: 1из 6

WOPMP-GEN-450010117375-V-DS-0166 PAGE: 1 of 6

DESCON ENGINEERING LIMITED 
DOCUMENT REVIEW/APPROVAL 
Permission to proceed does not constitute acceptance or approval 
of design details, calculations, analysis, test methods or materials 
developed or selected by vendor and does not relieve vendor 
from full compliance with contractual obligations.  

 Category – 1 
Approved  
Work May Proceed  
Review Not Required 
  Category – 2 
Work may proceed 
Revise and Resubmit 
  Category – 3  Work may proceed subject to 
incorporation of changes indicated 
Revise and Resubmit 
  Category – 4 
Work must not proceed 
 

2 18-July-18 Issued For Approval FK TS

1 23-May-18 Issued For Approval FK TS

0 05-May-18 Issued For Approval FK TS

Initial Signature Initial Signature Initial Signature


Rev Date Description
Prepared by Checked by Approved by

PAK-ARAB PIPELINE COMPANY LIMITED CLIENT


Pak-Arab Refinery Limited
CLIENT PROJECT N0.
Corporate Headquarters Korangi Creek Road. Karachi-75190 Pakistan
Tel: (+92-21)35090100-113, 35122112, 35090154
Fax: (+92-21) 35090799 10-0167
DESCON ENGINEERING LIMITED
18-Km Ferozepur Road, Lahore 54760, Pakistan DESCON
EPCC Tel: +92 42 35990034, 35805134 UAN: +92-42 111-DES-CON PROJECT NO
CONTRACTOR Fax: +92 42 35811005, 35811135
Email: descon@descon.com; Website www.descon.com PP.33001

S M JAFFER & COMPANY SMJ


WOPMP-GEN-450010117375-V-DS-0166

SUB Q-29/C Gulberg-II, Lahore 54760, Pakistan PROJECT NO


CONTRACTOR UAN: +92-42 111-SMJ-SMJ Fax: +92 42 35715021
Email: info@smjaffer.com; Website www.smjaffer.com G016049-AA

PROJECT WHITE OIL PIPELINE MOGAS PROJECT

TITLE GENSETS DATA SHEET

DOC.
PREPARED CHECKED APPROVED DATE DOCUMENT NO. REV.
SIZE

FK TS 18-May-18 WOPMP-GEN-450010117375-V-DS-0166 2 A4
DOC. NO. MKT-E-ELA-6514 PAGE: 1 OF 5

NOTE: This document has been developed from FEED document


number MKT-E-ELA-6514 Rev. 0 dated 26-Oct-15 after incorporating
B&V comments and / or latest design updations

0 6-Sep-17 Issued For Approval FAA RAB AHE

Initial Signature Initial Signature Initial Signature


Rev Date Description
Prepared by Checked by Approved By
PAK-ARAB PIPELINE COMPANY LIMITED
Pak-Arab Refinery Limited CLIENT
Corporate Headquarters Korangi Creek Road. Karachi-75190 Pakistan PROJECT NO.
CLIENT
Tel: (+92-21)35090100-113, 35122112, 35090154
Fax: (+92-21) 35090799
10-0167

DESCON ENGINEERING LIMITED


DESCON
18-Km Ferozepur Road, Lahore-54760, Pakistan
PROJECT NO.
EPCC
DESCON DOC. NO. 6614-30-304-S1381-003

Tel: +92 42 35990034, 3585134 UAN: +92-42 111-DES-CON


CONTRACTOR
Fax: +92 42 35811005, 35811135
PP.33001
Email: descon@descon.com: Website www.descon.com

PROJECT WHITE OIL PIPE LINE MOGAS PROJECT

TITLE
DATA SHEET FOR EMERGENCY DIESEL GENERATOR AT WOTS-
III
REV. DOC. SIZE
PREPARED CHECKED APPROVED DATE DOCUMENT NO.

FAA RAB AHE 6-Sep-17 MKT-E-ELA-6514 0 A4


PROJECT NO. 10-0167. PAGE NO. 2 OF 5

PROJECT WHITE OIL PIPE LINE MOGAS PROJECT DOCUMENT NO. MKT-E-ELA-6514

DOCUMENT DATA SHEET FOR EMERGENCY DIESEL GENERATOR AT WOTS-III

Sr. DESCRIPTION REQUESTED VALUE Rev.


1 PROJECT/EQUIPMENT INFORMATION
2 PROJECT NAME WHITE OIL PIPE LINE MOGAS PROJECT
3 EQUIPMENT DESCRIPTION Emergency Diesel Generator
4 EQUIPMENT TAG TBA
5 MANUFACTURER INFORMATION
6 MANUFACTURER NAME VTA FG WILSON
7 PLACE OF MANUFACTURE VTA EUROPE
8 MODEL NO. VTA P400-3
9 APPLICABLE DOCUMENTS
10 SPECIFICATION FOR EMERGENCY DIESEL GENERATOR 0167-E-ELA-6518 COMPLY
11 ELECTRICAL SYSTEM DESIGN BASIS 0167-E-GA-8001 COMPLY
13 APPLICABLE CODE AND STANDARDS
14 IEC 61869 INSTRUMENT TRANSFORMERS COMPLY
15 IEC 60034-1 ROTATING ELECTRICAL MACHINES – PART 1: RATING AND PERFORMANCE COMPLY
GENERAL

16 IEC 60050 INTERNATIONAL ELECTRO TECHNICAL VOCABULARY COMPLY


17 IEC 60038 IEC STANDARD VOLTAGES COMPLY
18 IEC 60051 DIRECT ACTING INDICATING ANALOGUE ELECTRICAL MEASURING INSTRUMENTS AND THEIR ACCESSORIES COMPLY
19 IEC 60072 DIMENSIONS AND OUTPUT SERIES FOR ROTATING ELECTRICAL MACHINES -
20 IEC 60079 ELECTRICAL APPARATUS FOR EXPLOSIVE GAS AREAS -
21 IEC 60085 ELECTRICAL INSULATION – THERMAL EVALUATION AND DESIGNATION -
22 IEC 60317 SPECIFICATIONS FOR PARTICULAR TYPE OF WINDING WIRES -
23 IEC 61000 ELECTROMAGNETIC COMPATIBILITY (EMC) COMPLY
24 ISO 3046-4 RECIPROCATING INTERNAL COMBUSTION ENGINES: PERFORMANCE - PART 4: SPEED GOVERNING COMPLY
25 ISO 8528 RECIPROCATING INTERNAL COMBUSTION ENGINE DRIVEN ALTERNATING CURRENT GENERATING SETS COMPLY
26 ISO 9000 QUALITY MANAGEMENT SYSTEMS – FUNDAMENTALS AND VOCABULARY COMPLY
27 ISO 9001 QUALITY MANAGEMENT SYSTEMS – REQUIREMENTS COMPLY
28 ISO 14001 ENVIRONMENTAL MANAGEMENT SYSTEMS COMPLY
29 OHSAS 18001 OCCUPATIONAL HEALTH AND SAFETY MANAGEMENT SYSTEMS COMPLY
30 IEC 60529 DEGREES OF PROTECTION PROVIDED BY ENCLOSURES (IP CODE) COMPLY
31 NEQS NATIONAL ENVIRONMENTAL QUALITY STANDARDS (REVISED) - PAKISTAN
32 MAX. / MIN. AMBIENT TEMP. 50 / 0 °C COMPLY
SITE CONDITIONS

33 ALTITUDE Less than 1000m AMSL COMPLY


34 ENVIRONMENT Dusty / Sandy COMPLY
35 HUMIDITY 90% (MAX) COMPLY
36 ATMOSPHERE Tropical COMPLY
37 AREA CLASSIFICATION Safe (Unclassified) COMPLY
39 GENERATOR RATED OUTPUT 350kVA COMPLY
40 MANUFACTURER VTA FG WILSON
41 NOMINAL OUTPUT 350kVA @0.8 pf COMPLY
42 MODEL NUMBER VTA P400-3
43 NOMINAL OUTPUT CURRENT VTA 504 AMP
DATA FOR GENERATOR SET

44 FRAME SIZE VTA LL6114B


45 NEUTRAL GROUNDING Solidly Earthed COMPLY
46 RATED CONTINUOUS OUTPUT 350kVA COMPLY
47 DUTY Standby COMPLY
48 RATED OUTPUT VOLTAGE 400 V COMPLY
49 TYPE OF EXCITATION Self Excited/ PMG COMPLY
50 RATED OUTPUT FREQUENCY 50 Hz COMPLY
51 COOLING MEDIUM Water Cooled COMPLY
52 RATED SPEED 1500 COMPLY
53 PAINTING SPECIFICATION As per Painting Specification (Doc. No. 10-0167-GS-9502) COMPLY
54 COLOUR SHADE FOR GENERATOR RAL6011
55 COLOUR SHADE FOR REMOTE CONTROL PANEL RAL6021
56 RATED EXCITATION VTA -
NOTES:

REVISION 0
DATE 6-Sep-17
BY FAA
CHECKED RAB
PROJECT NO. 10-0167. PAGE NO. 3 OF 5

PROJECT WHITE OIL PIPE LINE MOGAS PROJECT DOCUMENT NO. MKT-E-ELA-6514

DOCUMENT DATA SHEET FOR EMERGENCY DIESEL GENERATOR AT WOTS-III

Sr. DESCRIPTION REQUESTED VALUE Rev.


57 INSULATION CLASS
58 a) ROTOR H COMPLY
59 b) STATOR H COMPLY
60 c) EXCITOR H COMPLY
61 TEPMERATURE CLASS
62 a) ROTOR B H-CLASS
63 b) STATOR B H-CLASS
64 c) EXCITOR B H-CLASS
65 SHORT TERM OVERLOAD 1 hr. per 24 hrs. COMPLY
DATA FOR GENERATOR SET

66 HARMONIC DISTORTION VTA 4.0%


67 WINDING CONNECTIONS 4 Wire Star COMPLY
68 NOISE ATTENUATION 85 dB COMPLY
69 STATOR WINDING LEADS Six COMPLY
70 NUMBER OF POLES VTA 4 POLES
71 PARALLEL OPERATION REQD YES COMPLY
72 ENCLOSURE CONSTRUCTION VTA COMPLY
73 NUMBER OF GENERATOR SETS 1 COMPLY
74 ENCLOSURE IP RATINGS IP 55 NOT REQUIRED IN CASE OF POWERHOUSE
75 DIMENSIONS VTA 3800x1131x2156
76 ENCLOSURE COOLING TYPE VTA AIR COOLED
77 OVERALL WEIGHT VTA 3241 kg
78 GENERATOR PROTECTION CLASS IP23 COMPLY
79 FIRE MONITORING & EXTINGUISHING SYSTEM Required, As per Specification COMPLY
80 LOUVERS Motorized, As per Specification NOT REQUIRED IN CASE OF POWERHOUSE
81 ENCLOSURE COOLING TYPE Forced, As per Specification NOT REQUIRED IN CASE OF POWERHOUSE
82
83 LOCATION Manufacturer Standard AS PER MANUFACTURER RECOMMENDATION
COMPLY
CONSTRUCTION
TERMINAL BOX

84 CABLE TYPE 0.6/1 KV 4 Core XLPE


85 CABLE SIZE TBA -
86 TERMINAL / CONNECTION TYPE IEC Thread COMPLY
87 STRESS RELIEVING No COMPLY
88 SPACE FOR FUTURE CTS No COMPLY
89 AUXILIARIES Yes YES
90 CONDUIT / CABLE ENTRY SIZE VTA AS PER GA DRAWING
91
92 TYPE 2 Bearing Type Required 1 BEARING
93 BEARING MANUFACTURER VTA as per manufacturer
94 SPECIAL BEARING LIFE YES COMPLY
BEARINGS

95 DRIVE END VTA -


96 BEARING TEMP DETECTION YES Not available at principl end so cannot be provided
97 NON DRIVE END (SINGLE BEARING) VTA single bearing
98 VIBRATION DETECTION YES
as per manufacturer
99 LUBRICATION TYPE VTA API CH4 SAE15W-40
100 MAX VIBRATION ALLOWANCE VTA as per manufacturer
101 LUBRICATION QUANTITY VTA 0.1 % fuel cons.
102
103 TYPE VTA PMG
104 MODEL NO. VTA N/A
105 MANUFACTURER VTA N/A
EXCITER

106 MODEL NO. VTA N/A


107 OUTPUT VTA N/A
108 RATED CURRENT VTA
N/A
109 RATED VOLTAGE VTA N/A
110 INPUT CURRENT VTA
N/A
111 INPUT VOLTAGE VTA N/A
AUTOMATIC VOLTAGE

112
113 TYPE Microprocessor based N/A
REGULATOR

114 MODEL NO. VTA R450


115 MANUFACTURER VTA N/A
116 MODEL NO. VTA N/A
117 OUTPUT VTA N/A
118
NOTES:

REVISION 0
DATE 6-Sep-17
BY FAA
CHECKED RAB
PROJECT NO. 10-0167. PAGE NO. 4 OF 5

PROJECT WHITE OIL PIPE LINE MOGAS PROJECT DOCUMENT NO. MKT-E-ELA-6514

DOCUMENT DATA SHEET FOR EMERGENCY DIESEL GENERATOR AT WOTS-III

Sr. DESCRIPTION REQUESTED VALUE Rev.


119
120 RATED CURRENT VTA 504 Amp
121 RATED VOLTAGE VTA 400 V
122 INPUT CURRENT VTA 504 Amp
123 INPUT VOLTAGE VTA 400 V
124 MAKE VTA LEROY SOMER
125 MODEL NO. VTA LL6114B
126 EFFICIENCY AT 100%, 75%,50% AND 25% VTA REFER ALTERNATOR DATASHEET
127 PROTECTION Yes YES
128 VOLTAGE 400 V COMPLY
129 VOLTAGE TOLERANCE + 10% COMPLY
130 PHASE & CONNECTIONS 3Phase + N COMPLY
131 SYNCHRONOUS SPEED VTA 1500
132 POLES VTA 4 POLES
DATA FOR ALTERNATOR

133 FREQUENCY 50 Hz COMPLY


134 CONTINUOUS OUTPUT 350kVA COMPLY
135 STANDBY OUTPUT VTA 400 KVA
136 REGULATION VTA ± 0.5 %
137 THERMAL SENSORS VTA -
138 UNDER FREQUENCY PROTECTION COMPLY
139 MAX. VOLTAGE DROP VTA REFER MOTOR STARTING VD CURVE IN DOC.01
140 ROTOR'S MOMENT OF INERTIA INPUT VTA 4.6331 kgm2
141 SHORT CIRCUIT CURRENT VTA 0.3968
142 BEARING TEMP. SENSOR TYPE VTA PT100
143 EXCITER TYPE Self Excited/PMG Brushless PMG Brushless
144 OVERLOAD CAPACITY / TIME 1 Hour COMPLY
145 PROTECTION CLASS _ H CLASS
146 INSULATION CLASS
147 a) ROTOR H COMPLY
148 b) STATOR H COMPLY
149 MAKE Note : 5 PERKINS
150 MODEL NO. VTA* 2206A-E13TAG2
151 CONFIGURATION DIESEL ENGINE
152 ASPIRATION(SELECTION SYSTEM) Natural Air Turbocharged A-A
153 ENGINE GROSS KW VTA 324 kw
154 ENGINE NET KW VTA 324
155 RADIATOR RATED FOR (°C) VTA REFER DATASHEET ATTACHED IN DOC 02
DATA FOR DIESEL ENGINE

156 WATER CAPACITY OF RADIATOR VTA REFER DATASHEET ATTACHED IN DOC 02


157 NO OF CYLINDERS VTA 6 INLINE
158 COOLING METHOD Water Cooled COMPLY
159 SWEPT VOLUME VTA -
160 BASE LOAD CONTINUOUS OUTPUT (10% OVER LOAD) VTA COMPLY
161 STANDBY DUTY - MAX. OUTPUT (WITHOUT OVER LOAD) VTA COMPLY
162 GOVERNING (SPEED) 1500 COMPLY
163 STARTER BATTERY VTA 24 V
164 STARTER BATTERY TYPE Nickel Cadmium (Maintenance free) COMPLY
165 STARTER BATTERY V VTA 24 V
166 LUBE OIL CAPACITY VTA 40 L
167 LUBE OIL CONSUMPTION DAY TANK CAPACITY VTA 40 L
168 FUEL CONSUMPTION VTA 69.6 L/HR
169 (CONTINUOUS OPERATION AT 100% LOAD) 12 HOURS COMPLY
170 GRADE OF DIESEL OIL REQUIRED Conform to BS2896 COMPLY
171 MAX SIZE OF PARTICULATE MATTER VTA -
172 MAX WATER CONTENT VTA -
ENGINE FUEL SYSTEM

173 DIESEL TANK Yes at basement of DG Set NOT REQUIRED


174 DIESEL TANK CAPACITY For 12 Hours Continuous Operation NOT REQUIRED
175 PRIMING / BLEEDING PROVISION VTA -
176 GOVERNOR TYPE VTA ELECTRONIC
177 GOVERNOR MAKE VTA N/A
178 GOVERNOR MODEL VTA N/A
179 NEMA CLASS VTA NEMA MG-1.22.
180 REGULATION VTA -
NOTES:

REVISION 0
DATE 6-Sep-17
BY FAA
CHECKED RAB
PROJECT NO. 10-0167. PAGE NO. 5 OF 5

PROJECT WHITE OIL PIPE LINE MOGAS PROJECT DOCUMENT NO. MKT-E-ELA-6514

DOCUMENT DATA SHEET FOR EMERGENCY DIESEL GENERATOR AT WOTS-III

Sr. DESCRIPTION REQUESTED VALUE Rev.

181
ENGINE STARTING SYSTEM

182 PRIMARY STARTING SYSTEM VTA SELF IGNITION


183 CRANKING DURATION 4 to 25 sec COMPLY
184 CHARGE ALTERNATOR VTA -
185 NUMBER OF BATTERIES VTA 2
186 BATTERY CAPACITY VTA 24 v
187 BATTERY RECHARGE TIME VTA 1 Hr.
188 NOMINAL BATTERY VOLTAGE VTA 24 V

NOTES:
(1) Vendor to comply / verify all details as mentioned.
(2) Emergency Diesel Generator shall be sized on Prime Power Rating.
(3) Vendor to supply Sound Attenuated Container for Outdoor Installation (Minimum degree of Protection IP55) Engine Securities required.
(4) Indication Lights for: Generator in Operative, Overload Condition, Low Oil Shutdown
(5) Microprocessor based Control Panel for DG set shall be skid mounted having minimum all the required metering, protections & Auto/Manual/Stop/Test mode options.

REVISION 0
DATE 6-Sep-17
BY FAA
CHECKED RAB