News
OLTC Scan on
Power Transformers
New dynamic resistance measurement function
for the CPC 100
OLTCs are an important component of a power transformer. As its Reasons for transformer failures in %
name suggests an OLTC permits tap changing and hence volt-
age regulation without interrupting the load current. This can Coil 34
versified tap changer designs. The two most common ones Tank 21
are the so called inductive and resistive type tap changers.
Bushing 20
Others 19.5
Studies show that about 26 % of all reported outages
Core 5
are related to the aging effects on OLTCs. Due to this
high failure rate, it is very important to monitor the
0 10 20 30 40
condition of the power transformer’s OLTC closely.
Transformer failure statistics (Viereck, Hillinger, Transform 2011)
Unlike other more static components in a transformer, the OLTC
consists of numerous moving parts. Manufacturers typically
recommend a maintenance cycle that mostly depends on the total
number of switching operations. Operating times below 100 ms
Current
Winding Resistance per Tap
1
0.33 Ohm
0.28 Ohm
3
0.23 Ohm
2
4
0.18 Ohm
1 2
0.13 Ohm
Taps 1 3 5 7 9 11 13 15 17 19 21 23 25
R R R R
A B A B
Static winding resistance measurement of a transformer including all
tap positions and the switching process in detail by using DRM.
www.omicronenergy.com/cpc100
Time
3 4
R R R R
A B A B
The Primary Test Manager™ (PTM) shows the switching
process of the individual taps in a single diagram.