CLIENT Relience Jio Infocomm Ltd.

CONSULTANT:
PROJECT: 24m Guyed Mast
TITLE: 24m Guyed Mast REV02
Date: 10/15/2018

CONTENTS:

1) Specifications
2) Load Calculations
3) Staad Pro Input and Output
CLIENT Relience Jio Infocomm Ltd. CONSULTANT:
PROJECT: 24m Guyed Mast
TITLE: 24m Guyed Mast REV02
Date: 10/15/2018

1) SPECIFICATIONS

Dimensions
Height of Guyed Mast = 24.00 m
Width of Guyd Mast = 300.00 mm
Outer diameter of pipe = 33.70 mm

Reference Standard
Wind load IS-875 (part-3):2015
Steel design Code IS 800:2007
Earthquake design code IS 1893(part-1): 2016

Member Specifications

Pipe Section NB25M


Outer dia = 33.70 mm
Thickness = 3.20 mm
Diagonal Member = 12.00 mm dia. rod
Horizontal Member = 12.00 mm dia. rod
Guyed Wire = 8.00 mm dia. Wire
Pre-tension in wire = 12.50 KN
Plan angle of guy wire = 120.00 deg.

guy wire height from bottom and angle in elevation

guy wire ht. from angle in


bottom elevation
11.50m 77 deg.
16.50m 74 deg.
21.50m 67 deg.

Antenna Specifications
U.B.R 0.400 X 0.600 m 2Nos.
M/W 1 0.600 m Dia 1No.

Weight of U.B.R = 10.00 Kg


Weight of M/W 1 = 28.00 Kg

Antenna mounting height


1) U.B.R 0.40 X 0.60 m at 0.30m from top
2) M/W 600mm dia at top level
CLIENT Relience Jio Infocomm Ltd. CONSULTANT:
PROJECT: 24m Guyed Mast
TITLE: 24m Guyed Mast REV02
Date: 10/15/2018

3) LOAD CALCULATIONS
Dead Load:
1) Self wt. of the mast and cables is generated through selfweight command in Staad-Pro V8i

2) self Weight of Antenna considered is a follows.


Due to U.B.R = 10.00 Kg = 0.10 KN
Due to M/W 1 = 28.00 Kg = 0.28 KN

Imposed Load:

Live Load (Weight of man + equipment) = 50.00 Kg


Load on each node = 0.50 KN

Wind Load:

as per clause 9 of IS 975 part 3 -2015


a) Height / minimum lateral dimension ratio
h = 24.00 m
d = 0.30 m
H/d = 80.00 > 5.000

b) Fundamental frequency calculation


Time period Ta = 0.085h^0.75 Ref I.S 1893 pt.1 Cl 7.6.1
where,
h = height of structure

Ta = 0.92 sec
fa = 1/Ta
fa = 1.085 Hz > 1.000 Hz
From condtion H/d ratio is greater than 5 dynamic effect of wind is to be considered

Dynamic wind analysis


Hourly Mean Wind Speed Calculation
VzH = Kz,i x Vb refer cl. 6.4 of IS 875-Part3
where,
Vz,h = Hourly wind speed at height Z
Kzi = hourly Mean Wind Speed factor for terrain category i
Vb = Basic wind speed
hourly Mean Wind Speed factor for terrain category 2
Kz,2 = 0.1423 x [ln(z/z0,2)] x (Z0,2)^0.0706
where
CLIENT Relience Jio Infocomm Ltd. CONSULTANT:
PROJECT: 24m Guyed Mast
TITLE: 24m Guyed Mast REV02
Date: 10/15/2018
Z0,i = Aerodynamic roughness height for I zone from pag6 IS 875 part 3 2015
Z0,2 = 0.02 m

Hourly mean wind speed and hourly design wind pressure at different height is as shown in table

Sr. No. HT Z0,2 (m) Kz,2 Vb (m/s) Vz,h (m/2) K1 K3 K4


1 9.00 0.02 0.66 50.00 32.98 0.90 1.00 1.00
2 12.00 0.02 0.69 50.00 34.53 0.90 1.00 1.00
3 15.00 0.02 0.71 50.00 35.73 0.90 1.00 1.00
4 18.00 0.02 0.73 50.00 36.72 0.90 1.00 1.00
5 21.00 0.02 0.75 50.00 37.55 0.90 1.00 1.00
6 24.00 0.02 0.77 50.00 38.27 0.90 1.00 1.00

Sr. No. Vd,h (m/s) kd Pzd(KN/m2)


1 29.68 0.90 0.48
2 31.08 0.90 0.52
3 32.16 0.90 0.56
4 33.05 0.90 0.59
5 33.80 0.90 0.62
6 34.44 0.90 0.64

where
Z0,2 = aerodynamic roughness height for terrain category2, ref IS 875 pt3(2015) pg no : 6
Kz,2 = hourly Mean Wind Speed factor for terrain category2 ref IS 875 pt3(2015) cl. 6.4
Vb = basic wind speed
Vz,h = hourly Mean Wind Speed ref IS 875 pt3(2015) cl. 6.4
Vz,h = Vb x Kz,2
K1 = risck coefficeint ref IS 875 pt3(2015) cl. 6.3.1
K3 = topography factor ref IS 875 pt3(2015) cl. 6.3.3
K4 = Importance factor for cyclonic region ref IS 875 pt3(2015) cl. 6.3.4
Vh,d = design hourly mean wind speed ref IS 875 pt3(2015) cl. 6.4
Vd,h = Vz,h x K1 x Kz,2 x K3
kd = wind directionality factor ref IS 875 pt3(2015) cl. 7.2.1
Pz,d = design hourly wind pressure ref IS 875 pt3(2015) cl. 7.2
Pz,d = 0.6 x Kd x Vz,d^2
CLIENT Relience Jio Infocomm Ltd. CONSULTANT:
PROJECT: 24m Guyed Mast
TITLE: 24m Guyed Mast REV02
Date: 10/15/2018

Gust factor calculation

refer IS 875 part 3(2015) Cl. 10

G =
 H * g R2 * S * E 
(gust factor) 1 r  s  g v2 * Bs * (1   ) 2 
  

Given :
H = 24 m
d = 0.3 m
bsh = 0.3 m
β = 0.01 considering welded steel structure
ϕ = 0
gust factor for differnet Height
Sr No. Height(m) gR ϕ gv Ih,1 r=2*Iz,1 β Hs
1.00 9.00 4.28 0.00 3.00 0.16 0.32 0.01 1.14
2.00 12.00 4.28 0.00 3.00 0.16 0.32 0.01 1.25
3.00 15.00 4.28 0.00 3.00 0.16 0.32 0.01 1.39
4.00 18.00 4.28 0.00 3.00 0.16 0.32 0.01 1.56
5.00 21.00 4.28 0.00 3.00 0.16 0.32 0.01 1.77
6.00 24.00 4.28 0.00 3.00 0.16 0.32 0.01 2.00

Sr No. Height(m) Bs N E S G
1 9.00 0.93 8.10 0.02 0.12 2.20
2 12.00 0.95 8.10 0.02 0.12 2.23
3 15.00 0.96 8.10 0.02 0.12 2.27
4 18.00 0.97 8.10 0.02 0.12 2.31
5 21.00 0.99 8.10 0.02 0.12 2.35
6 24.00 1.00 8.10 0.02 0.12 2.3952

Sample Calcultion
d = maximum base dimension of building along wind direction
d = 0.3 m
h = 24 m
Frequency calculation Manually
T  0.085 * h 0.75 Ref I.S 1893 pt.1 Cl 7.6.1
CLIENT Relience Jio Infocomm Ltd. CONSULTANT:
PROJECT: 24m Guyed Mast
TITLE: 24m Guyed Mast REV02
Date: 10/15/2018
T = 0.922
fa = 1/T
fa = 1.0846 Hz

Religh Frequency from staad pro anlysis


fa = 2.6381 Hz from staad pro analysis

gR   2 * ln* (3600 * f a 
1. gR = 4.28

0.25
Lh =  h  For terrain category 1 to 3
85 *  
 10 
Lh = 105.80 m

N = fa*Lh
Vh,d
N = 8.10

E =  *N
1  70.8 * N  2 5/ 6

2. E = 0.023

bsh = 0.3 m

1
S =  3.5 * f a * h   4 * f a * b0 h 
1   * 1  
 Vh ,d   Vh,d 

3. S = 0.12

4. β = 0.01 considering welded steel structure

5. gv = 3 ref IS 875 pt3(2015) pg no : 47

Hs = 2
s
1  
h
CLIENT Relience Jio Infocomm Ltd. CONSULTANT:
PROJECT: 24m Guyed Mast
TITLE: 24m Guyed Mast REV02
Date: 10/15/2018
Hs = 1 +(24/24)^2
6. Hs = 2
1
Bs =
 0.26(h  s  2  0.46 * bsh2
1
Lh

7. Bs = 0.98

r = roughness factor which is twice of


Longitudinal turbulence intensity, Izi

Iz,2 = Iz,1 + 1/7 (Iz4 - iz1) ref IS 875 pt3(2015) cl. 6.5
Iz,1 = 0.3507 - 0.0535 x log10 (Z/Z0,1) ref IS 875 pt3(2015) cl. 6.5
Iz,4 = 0.466 - 0.1358 x log10(Z/Z0,4) ref IS 875 pt3(2015) cl. 6.5

where
Z0,1 = 0.002 m ref IS 875 pt3(2015) pg no : 6
Z0,4 = 2.00 m ref IS 875 pt3(2015) pg no : 8
Iz,1 = 0.13
Iz,4 = 0.32
Iz,2 = 0.16
r = 2 * Ih,i
8. r = 0.32

9. ϕ = 0 Ref IS 875 pt3 (1987),


since there is no condition specified in IS 875pt3(2015)

G =
 H s * g R2 * S * E 
(gust factor) 1 r   g v2 * Bs * (1   ) 2 
  

G = 2.40

Calculation of Force co-efficient and antenna wind load


Height of pannel = 3.000 m
width of tower = 0.300 m
diagonal length = 0.424 m

dia. Of vertical = 33.70 mm = 0.034 m


dia. Of horizontal = 12.00 mm = 0.012 m
dia. Of diagonal = 12.00 mm = 0.012 m
CLIENT Relience Jio Infocomm Ltd. CONSULTANT:
PROJECT: 24m Guyed Mast
TITLE: 24m Guyed Mast REV02
Date: 10/15/2018
gross area = 0.90 m2
area of vertical = 0.20 m2
area of horizontal = 0.03 m2
area of diagonal = 0.05 m2
net area = 0.28 m2
solidity ratio = 0.31
D*Vz,d = 1.16 <6 m2/s
Cf of round = 1.50 (From Table-35)

Antenna Loading:
1)U.B.R 0.4 X 0.6m = 0.4 x 0.6
Cf = Cf x Pz,d x A
For UBR 400x 600 x200mm
h = 600 mm
b = 400 mm
a = 200 mm
h/b = 600/400 = 1.5
a/b = 200/400 = 0.5
Cf = 1.27 from fig. 4
= 0.195 KN

6) M/W1, 600mm = 0.6 m


Cf = 1.2 from Table 27
= Cf x Pz,d x A
= 0.217 KN

Estimation of Levelwise Wind Pressure Values on Cables

Vb = 50 m/s
Class of Structure = 2
K1 Factor = 0.9
Terrain Category : = 2
zo,i = 0.02
K2,i = Refer IS 875 part 3-2015 pg no. 9
K3 = 1.0 For Slope upto 30o
Kd = 0.9 Wind directionality factor
Sr. No. HT Z0,2 (m) Kz,2 Vb (m/s) Vz,h (m/2) K1 K3 K4
1.00 9.00 0.02 0.66 50.00 32.98 0.90 1.00 1.00
2.00 12.00 0.02 0.69 50.00 34.53 0.90 1.00 1.00
3.00 15.00 0.02 0.71 50.00 35.73 0.90 1.00 1.00
4.00 18.00 0.02 0.73 50.00 36.72 0.90 1.00 1.00
5.00 21.00 0.02 0.75 50.00 37.55 0.90 1.00 1.00
CLIENT Relience Jio Infocomm Ltd. CONSULTANT:
PROJECT: 24m Guyed Mast
TITLE: 24m Guyed Mast REV02
Date: 10/15/2018
6.00 24.00 0.02 0.77 50.00 38.27 0.90 1.00 1.00

Sr. No. Vd,h (m/s) kd Pzd(KN/m2)


1.00 29.68 0.90 0.48
2.00 31.08 0.90 0.52
3.00 32.16 0.90 0.56
4.00 33.05 0.90 0.59
5.00 33.80 0.90 0.62
6.00 34.44 0.90 0.64

Force (kN/m) = G x Cf x Pzd x d


where Cf is the Force coefficient, taken from Table 30, Pg no. 42 of IS 875

d is the diameter of the cable = 0.008 m


K2,i Pzd Cf Force
Sr No. Height(m) Vd,h (m/s) (KN/m2) G kN/m
1.00 0.00 0.66 29.68 0.48 2.20 1.20 0.010
2.00 0.00 0.69 31.08 0.52 2.23 1.20 0.011
3.00 0.00 0.71 32.16 0.56 2.27 1.20 0.012
4.00 0.00 0.73 33.05 0.59 2.31 1.20 0.013
5.00 0.00 0.75 33.80 0.62 2.35 1.20 0.014
6.00 0.00 0.77 34.44 0.64 2.40 1.20 0.015

Seismic Load:

seismic loads in generated for the given parameters in Staad-Pro V8i

Seismic Zone Factor (Z) = 0.36 ref IS 1893 pt1(2016) table 3


Response Reduction Factor ( R) = 4.00 ref IS 1893 pt1(2016) table 9
Importance Factor ( I ) = 1.00 ref IS 1893 pt1(2016) table 8
CLIENT Relience Jio Infocomm Ltd. CONSULTANT:
PROJECT: 24m Guyed Mast
TITLE: Preliminary Design Report For 24m Guyed Mast
Date: 10/8/2018

CONTENTS:

1) Specifications
2) Load Calculations
3) Staad Pro Input and Output
1) SPECIFICATIONS

Dimensions
Height of Guyed Mast = 24.000 m
Width of Guyd Mast = 300.000 mm
Outer diameter of pipe = 33.700 mm

Reference Standard
Wind load IS-875 (part-3):2015
Steel design Code IS 800:2007
Earthquake design code IS 1893(part-1)

Member Specifications

Pipe Section NB25M


Outer dia = 33.700 mm
Thickness = 3.200 mm
Diagonal Member = 12.000 mm dia. rod
Horizontal Member = 12.000 mm dia. rod
Guyed Wire = 10.000 mm dia. Wire

guyed Wire are at 11.50m , 16.50m and 21.50m from bottom respectievely

Antenna Specifications
U.B.R 0.400 X 0.600 m 2Nos.
M/W 1 0.600 m Dia 1No.

Weight of U.B.R = 10.00 Kg


Weight of M/W 1 = 28.00 Kg

Antenna mounting height


1) U.B.R 0.40 X 0.60 m at 0.30m from top
2) M/W 600mm dia at top level
3) LOAD CALCULATIONS
Dead Load:
1) Self wt. of the mast and cables is generated through selfweight command in Staad-Pro V8i

2) self Weight of Antenna considered is a follows.


Due to U.B.R = 10.00 Kg = 0.10 KN
Due to M/W 1 = 28.00 Kg = 0.28 KN

Imposed Load:

Live Load (Weight of man + equipment) = 50.00 Kg


Load on each node = 0.50 KN

Wind Load:

as per clause 9 of IS 975 part 3 -2015


a) Height / minimum lateral dimension ratio
h = 24.00 m
d = 0.30 m
H/d = 80.00 > 5.000

b) Fundamental frequency calculation


Time period Ta = 0.085h^0.75 Ref I.S 1893 pt.1 Cl 7.6.1
where,
h = height of structure

Ta = 0.92 sec
fa = 1/Ta
fa = 1.085 Hz > 1.000 Hz
From condtion H/d ratio is greater than 5 dynamic effect of wind is to be considered

Dynamic wind analysis

Hourly Mean Wind Speed Calculation


VzH = Kz,i x Vb refer cl. 6.4 of IS 875-Part3
where,
Vz,h = Hourly wind speed at height Z
Kzi = hourly Mean Wind Speed factor for terrain category i
Vb = Basic wind speed
hourly Mean Wind Speed factor for terrain category 2
Kz,2 = 0.1423 x [ln(z/z0,2)] x (Z0,2)^0.0706
where
Z0,i = Aerodynamic roughness height for I zone from pag6 IS 875 part 3 2015
Z0,2 = 0.02 m

Hourly mean wind speed and hourly design wind pressure at different height is as shown in table
Sr. No. HT Z0,2 (m) Kz,2 Vb (m/s) Vz,h (m/2) K1 K3 K4
1 9.00 0.02 0.66 50.00 32.98 0.90 1.00 1.00
2 12.00 0.02 0.69 50.00 34.53 0.90 1.00 1.00
3 15.00 0.02 0.71 50.00 35.73 0.90 1.00 1.00
4 18.00 0.02 0.73 50.00 36.72 0.90 1.00 1.00
5 21.00 0.02 0.75 50.00 37.55 0.90 1.00 1.00
6 24.00 0.02 0.77 50.00 38.27 0.90 1.00 1.00

Sr. No. Vd,h (m/s) kd Pzd(KN/m2)


1 29.68 0.90 0.48
2 31.08 0.90 0.52
3 32.16 0.90 0.56
4 33.05 0.90 0.59
5 33.80 0.90 0.62
6 34.44 0.90 0.64

where
Z0,2 = aerodynamic roughness height for terrain category2, ref IS 875 pt3(2015) pg no : 6
Kz,2 = hourly Mean Wind Speed factor for terrain category2 ref IS 875 pt3(2015) cl. 6.4
Vb = basic wind speed
Vz,h = hourly Mean Wind Speed ref IS 875 pt3(2015) cl. 6.4
Vz,h = Vb x Kz,2
K1 = risck coefficeint ref IS 875 pt3(2015) cl. 6.3.1
K3 = topography factor ref IS 875 pt3(2015) cl. 6.3.3
Vh,d = design hourly mean wind speed ref IS 875 pt3(2015) cl. 6.4
Vd,h = Vz,h x K1 x Kz,2 x K3
kd = wind directionality factor ref IS 875 pt3(2015) cl. 7.2.1
Pz,d = design hourly wind pressure ref IS 875 pt3(2015) cl. 7.2
Pz,d = 0.6 x Kd x Vz,d^2

Gust factor calculation

refer IS 875 part 3(2015) Cl. 10


G =
 H * g R2 * S * E 
(gust factor) 1 r  s  g v2 * Bs * (1   ) 2 
  

Given :
H = 24 m
d = 0.3 m
bsh = 0.3 m
β = 0.01 considering welded steel structure
ϕ = 0

gust factor for differnet Height

Sr No. Height(m) gR ϕ gv Ih,1 r=2*Iz,1 β Hs


1.00 9.00 4.26 0.00 3.00 0.16 0.32 0.01 1.14
2.00 12.00 4.26 0.00 3.00 0.16 0.32 0.01 1.25
3.00 15.00 4.26 0.00 3.00 0.16 0.32 0.01 1.39
4.00 18.00 4.26 0.00 3.00 0.16 0.32 0.01 1.56
5.00 21.00 4.26 0.00 3.00 0.16 0.32 0.01 1.77
6.00 24.00 4.26 0.00 3.00 0.16 0.32 0.01 2.00

Sr No. Height(m) Bs N E S G
1 9.00 0.93 7.52 0.02 0.13 2.23
2 12.00 0.95 7.52 0.02 0.13 2.26
3 15.00 0.96 7.52 0.02 0.13 2.30
4 18.00 0.97 7.52 0.02 0.13 2.34
5 21.00 0.99 7.52 0.02 0.13 2.39
6 24.00 1.00 7.52 0.02 0.13 2.4363

Sample Calcultion
d = maximum base dimension of building along wind direction
d = 0.3 m
h = 24 m
Frequency calculation Manually
Ref I.S 1893 pt.1 Cl 7.6.1
T  0.085 * h 0.75

T = 0.922
fa = 1/T
fa = 1.0846

Religh Frequency from staad pro anlysis


fa = 2.4473 from staad pro analysis

gR   2 * ln* (3600 * f a 
1. gR = 4.26

0.25
Lh =  h  For terrain category 1 to 3
85 *  
 10 
Lh = 105.80 m

N = fa*Lh
Vh,d
N = 7.52

E =  *N
1  70.8 * N  2 5/6

2. E = 0.024

bsh = 0.3 m

1
S =  3.5 * f a * h   4 * f a * b0 h 
1   * 1  
 Vh ,d   Vh ,d 

3. S = 0.13

4. β = 0.01 considering welded steel structure

5. gv = 3 ref IS 875 pt3(2015) pg no : 47

Hs = 2
s
1  
h

Hs = 1 +(24/24)^2
6. Hs = 2
1
Bs =
 0.26(h  s  2  0.46 * bsh2
1
Lh

7. Bs = 0.98

r = roughness factor which is twice of


Longitudinal turbulence intensity, Izi

Iz,2 = Iz,1 + 1/7 (Iz4 - iz1) ref IS 875 pt3(2015) cl. 6.5
Iz,1 = 0.3507 - 0.0535 x log10 (Z/Z0,1) ref IS 875 pt3(2015) cl. 6.5
Iz,4 = 0.466 - 0.1358 x log10(Z/Z0,4) ref IS 875 pt3(2015) cl. 6.5

where
Z0,1 = 0.002 m ref IS 875 pt3(2015) pg no : 6
Z0,4 = 2.00 m ref IS 875 pt3(2015) pg no : 8
Iz,1 = 0.13
Iz,4 = 0.32
Iz,2 = 0.16
r = 2 * Ih,i
8. r = 0.32

9. ϕ = 0 Ref IS 875 pt3 (1987),


since there is no condition specified in IS 875pt3(2015)

G =
 H * g R2 * S * E 
(gust factor) 1 r  s  g v2 * Bs * (1   ) 2 
  

G = 2.44

Calculation of Force co-efficient and antenna wind load


Height of pannel = 3.000 m
width of tower = 0.300 m
diagonal length = 0.424 m

dia. Of vertical = 33.70 mm = 0.034 m


dia. Of horizontal = 12.00 mm = 0.012 m
dia. Of diagonal = 12.00 mm = 0.012 m
gross area = 0.90 m2
area of vertical = 0.20 m2
area of horizontal = 0.03 m2
area of diagonal = 0.05 m2
net area = 0.28 m2
solidity ratio = 0.31
D*Vz,d = 0.00 <6 m2/s
Cf of round = 1.50 (From Table-35)

Antenna Loading:
1)U.B.R 0.4 X 0.6m = 0.4 x 0.6
Cf = Cf x Pz,d x A
For UBR 400x 600 x200mm
h = 600 mm
b = 400 mm
a = 200 mm
h/b = 600/400 = 1.5
a/b = 200/400 = 0.5
Cf = 1.27 from fig. 4
= 0.195 KN

6) M/W1, 600mm = 0.6 m


Cf = 1.2 from Table 27
= Cf x Pz,d x A
= 0.217 KN

Estimation of Levelwise Wind Pressure Values on Cables

Vb = 50 m/s
Class of Structure = 2
K1 Factor = 0.9
Terrain Category : = 2
zo,i = 0.02
K2,i = Refer IS 875 part 3-2015 pg no. 9
K3 = 1.0 For Slope upto 30o
Kd = 0.9 Wind directionality factor

Sr. No. HT Z0,2 (m) Kz,2 Vb (m/s) Vz,h (m/2) K1 K3 K4


1.00 9.00 0.02 0.66 50.00 32.98 0.90 1.00 1.00
2.00 12.00 0.02 0.69 50.00 34.53 0.90 1.00 1.00
3.00 15.00 0.02 0.71 50.00 35.73 0.90 1.00 1.00
4.00 18.00 0.02 0.73 50.00 36.72 0.90 1.00 1.00
5.00 21.00 0.02 0.75 50.00 37.55 0.90 1.00 1.00
6.00 24.00 0.02 0.77 50.00 38.27 0.90 1.00 1.00

Sr. No. Vd,h (m/s) kd Pzd(KN/m2)


1.00 29.68 0.90 0.48
2.00 31.08 0.90 0.52
3.00 32.16 0.90 0.56
4.00 33.05 0.90 0.59
5.00 33.80 0.90 0.62
6.00 34.44 0.90 0.64

Force (kN/m) = G x Cf x Pzd x d


where Cf is the Force coefficient, taken from Table 30, Pg no. 42 of IS 875

d is the diameter of the cable = 0.008 m


K2,i Vz,d pd Cf Force
Sr No. Height(m) G kN/m
1.00 0.00 0.66 29.68 0.48 2.23 1.20 0.010
2.00 0.00 0.69 31.08 0.52 2.26 1.20 0.011
3.00 0.00 0.71 32.16 0.56 2.30 1.20 0.012
4.00 0.00 0.73 33.05 0.59 2.34 1.20 0.013
5.00 0.00 0.75 33.80 0.62 2.39 1.20 0.014
6.00 0.00 0.77 34.44 0.64 2.44 1.20 0.015
Seismic Load:

seismic loads in generated for the given parameters in Staad-Pro V8i

Seismic Zone Factor (Z) = 0.36 ref IS 1893 pt1(2016) table 3


Response Reduction Factor ( R) = 4.00 ref IS 1893 pt1(2016) table 9
Importance Factor ( I ) = 1.00 ref IS 1893 pt1(2016) table 8