Вы находитесь на странице: 1из 5

DESIGN FOR AREA OF CROSS

MAXIMUM FAULT CURRENT (Ir) 25 KA

TYPE OF CONDUCTOR STEEL 1020

THERMAL CAPACITY FACTOR(TCAP) 3.28

DURATION OF FAULT CURRENT (tc) 1

THERMAL CO-EFFICENT OF RESISTIVITY AT 0.0016


REFERENCE TEMPARATURE (20o c) αr

RESISTIVITY OF GROUND CONDUCTOR AT


15.9
REFERENCE TEMPERATURE (20 oC) ƪr

RECIPROCAL OF THERMAL COEFFICENT OF 605


RESISTIVITY (KO)
MAXIMUM ALLOWABLE TEMPERATURE IN 0C 1510
AMBIENT TEMPERATURE IN oC 50
CROSS SECTION AREA OF THE CONDUCTOR 203.36

10% corossion 223.70

Flat Choosen 50 6

300
REA OF CROSSSECTION OF CONDUCTOR FOR EARTHING
˳
Material αr factor 20 C
S.NO Description K0 at 0o c
conductivity (%) (1/oC)

COPPER
1 ANNEALED 100 0.00393 234
SOFT DRAWN

COPPER,
2 COMMERCIAL 97 0.00381 242
HARD DRAWN

COPPER-CLAD
3 40 0.00378 245
STEEL WIRE

COPPER-CLAD
4 30 0.00378 245
STEEL WIRE

COPPER-CLAD
5 20 0.00378 245
STEEL WIRE b

ALUMINIUM EC
6 61 0.00403 228
GRADE
ALUMINIUM
7 53.5 0.00353 263
5005 ALLOY
ALUMINIUM
8 52.5 0.00347 268
6201 ALLOY
ALUMINIUM-
9 CLAD STEEL 20.3 0.0036 258
WIRE

10 STEEL 1020 10.8 0.0016 605

STAINLESS CLAD
11 9.8 0.0016 605
STEEL ROD

ZINC COATED
12 8.6 0.0032 293
STEEL ROD

STAINLESS
13 2.4 0.0013 749
STEEL 304

3.2290076336
1.1721748558 LOG
R EARTHING

Fusing a temparature (Tm). � TCAP thermal


� 20 o C ( μ Ω .cm)
o
C capacity (J/cm3 . oC)
r

1083 1.72 3.42

1084 1.78 3.42

1084 4.4 3.85

1084 5.86 3.85

1084 8.62 3.85

657 2.86 2.56

652 3.22 2.6

654 3.28 2.6

657 8.48 3.58

1510 15.9 3.28

1400 17.5 4.44

419 20.1 3.93

1400 72 4.03