TECHNICAL MANUAL
(TM – SMR 50N – 01E)
11/26/2009_Rev.aa Page 1 of 16
Contents
1. Introduction p.3
2. Rectifier description p.4
3. Operating characteristics p.6
3.1. Input p.6
3.2. Output p.6
3.3. Remote control p.7
3.4. Alarms and monitoring p.8
3.5. Compliances p.10
3.6. Environmental characteristics p.11
3.7. Mechanical characteristics p.12
3.8. Connections p.13
4. Dimensions p.13
5. Fig.1: Block diagram p.14
6. Fig. 2: Power block diagram p.15
7. Fig. 3: Boards position and internal connections p.16
1. Introduction.
11/26/2009_Rev.aa Page 2 of 16
The rectifier MOD. OM1S50N is a battery charger designed to provide an
output current up to 58A in a 48V nominal voltage system. This rectifier has
designed to be used together with a battery like a DC UPS.
Output DC voltage has the proprieties:
• Is very stable,
• Has a very small noise,
• Is limited at current increasing,
• Has nominal values: 48 V
• Can be connected with polarity + or – at GND.
The rectifier OM1S50N is a switching mode rectifier which realizes the
conversion AC/DC in pulse width modulation (PWM).
The rectifier has some remarkable performances:
• Parallel operating with equal current sharing and automatic disabling
of faulty unit,
• softstart – the input current is increasing in 8 sec at power up,
• the rectifier can be hot plugged up,
• operating control with a microprocessor,
• very good efficiency,
• very high power density.
The rectifier is designed to work with forced air cooling using 2 fans.
All the connections (AC, ground, DC, communications) are on the rear
connector. When a rectifier is put in its position in the rack, connectors
mating (rectifier – backplane) is automatically made. In a standard rack of
19” rectifiers can be put horizontal – 2 in line or vertical – up to 6. This
mechanical arrangement does replacement and installation to be very easy
and can be done by one person. Racks can be stacked connected allowing
operation of up to 225 rectifiers in parallel. The rectifiers are controlled by a
control and supervising unit (MiniCSU). The system can be monitorised and
controlled from distance using the software WinCSU and a modem. The
rectifiers are hot-pluggable. The rectifiers are put in the rack from left to
right and from top to bottom. In this order are the currents read in the
RECTIFIER Menu in MCSU.
2. Rectifier description.
11/26/2009_Rev.aa Page 3 of 16
In the figures 1, 2, and 3 are shown the functional block diagram, the power
block diagram, the board connections and the internal wiring.
The rectifier has 5 circuit printed boards:
• PMB (power mother board),
• DSCC (digital secondary control card),
• DCCB (dc/dc converter card),
• PFCB (power factor correction board)
• AUXPSU2 (auxiliary power supply).
The rectifier is working in PWM mode.
PMB
• Transient overvoltage protection
• Eliminating input electromagnetic interferences
• Inrush current limiting
• Rectifying AC
• Power factor correction
11/26/2009_Rev.aa Page 4 of 16
• Measuring input current
• Measuring output current
• DC voltage conversion in AC voltage (high frequency)
• Rectifying and filtering AC high frequency voltage
• Providing the supply voltage for auxiliary circuits
• Eliminating output electromagnetic interferences
• Providing isolation between power and signal circuits
• Driving power transistors
PFCB
• Generating gate drive pulses for transistors of boost stage
• Control of power factor correction
DCCB
• Generating gate drive pulses for transistors of DC/DC converter
• Monitoring AC input voltage
• Control of the relay limiting inrush current
• Transistors blocking at over voltage and over currents
DSCC
• Output voltage control
• Output current control
• MiniCSU communications
• Memorizing working program
• Memorizing working parameters
• Watching heatsink temperature
• Sensing rectifier number
• Generating signal control for output voltage and current
• Limiting output current
• Indicating rectifier status (with a three-color LED)
Green = rectifier OK;
Yellow = rectifier alarm (e.g: no load);
Red = rectifier failed.
AUXPSU2
• Generating power supplies for controlling boards.
11/26/2009_Rev.aa Page 5 of 16
3. Operating characteristics of the SMR 50N 25°C ambient, 230VAC
3.1. Input
3.2. Output
11/26/2009_Rev.aa Page 6 of 16
70
60
50
40
(V)
30
20
10
0
0 10 20 30 40 50 60
(A)
Static Regulation:
Line: better than ± 0.02%;
Load: terminal voltage drops by 0.45V ± 0.03V from zero to full load
(for passive current sharing) for stand alone units, or regulates
to better than ±0.05% for MiniCSU controlled units;
Dynamic Regulation: ± 5% for 10% to 90% to 10% step load change;
± 1% of final value within 1ms of step change;
± 0.1% for a 25% step change in AC input voltage;
Noise: < 2mV RMS Psophometrically weighted;
< 40mV RMS (10kHz - 100MHz);
< 200mV peak to peak (10kHz - 100MHz);
Load Sharing: Better than ± 5% of full scale with active current sharing from
MiniCSU;
Protection: Hotplug – no surge when connection is made to a live DC bus;
Overvoltage - only faulty unit shuts down;
Overcurrent - can sustain short circuit at output terminals
indefinitely. Output current folds back when output voltage
drops below 10V;
Over-temperature - gradual reduction of power limit if heatsink
temperature exceeds pre-set limit;
Voltage Withstand Test: 1000VAC output to chassis for 1 minute;
Acoustic Noise: < 55dB (A Weighted), fan connected
3.3. Remote Controls (from MiniCSU)
11/26/2009_Rev.aa Page 7 of 16
• Float Voltage
• Equalise Voltage
Programmable parameters - SMR menu:
• Current Limit
• High Voltage Alarm level
• Low Voltage Alarm level
• High Voltage Shut-Down level (HVSD)
• HVSD Reset
Equalise mode:
The SMR will automatically enter and exit equalise mode at user specified
conditions, or can be manually initiated. Under any fault condition the SMR
will default to the float value.
11/26/2009_Rev.aa Page 8 of 16
Normal: Status is normal;
Alarm: See Alarm table;
Equalise: SMR is in equalise mode;
Shutdown: SMR is shut down by remote control, or there is an internal
fault in the SMR, such as control loop out of limit or temperature sensor
faulty;
µP fault: Internal micro-controller is faulty.
Alarm table:
Vh * Output voltage too high
Vl * Output voltage too low
Il * Unit is in current limit
Po * Unit is in power limit
Th * Heatsink temperature high and thermal limit is active
Nd * No demand (output terminal voltage higher than internal regulation value)
Lo * Load current low (less than 0.9A)
Ma * Operating parameters out of allowable range (or eeprom fault)
Sd Unit is shut down by remote command - user shutdown
Mr Internal voltage reference faulty
11/26/2009_Rev.aa Page 9 of 16
Mc SMR communication fault. (Generated within MiniCSU)
Vs High voltage shut down (output), latched alarm. User setting or fault
Unit Unit is shut down due to AC out of range or SMR primary circuit fault.
Off (normal operation or fault)
Ts Temperature sensor fault
Dc DC-DC feedback fault, latched alarm
Ff Fan failure (only if fan is connected)
Note: * indicates flashing of alarm led on SMR.
3.5. Compliances
Safety: IEC60950:1999; EN60950
EMC Generic Emissions: EN50081-2
EMC Generic Immunity: EN50082-1
Immunity:
Category: Tested to comply with:
Electrostatic IEC 61000-4-2; EN61000-4-2
Discharge (Level 4: Air 15kV, Contact 8kV) Criterion A
(ESD)
Radiated RF IEC 61000-4-3; EN61000-4-3
(Level 4: 10V/m, 1kHz 80% AM) Criterion A
Electrical Fast IEC 61000-4-4; EN61000-4-4 Criterion A
Transient (Level 4: 4kV on AC lines) Criterion A
(EFT) (Level 3: 1kV on load lines)
Surge ANSI C62.41-1991 category B3 - AC lines
Protection (Combination Wave 6kV/3kA; Ring Wave 6kV/500A)
IEC 61000-4-5; EN61000-4-5 (Impulse)
(Level X: 6kV/3kA Common Mode [CM] on AC lines) Criterion B
(Level X: 6kV/3kA Differential Mode [DM] on AC lines) Criterion B
11/26/2009_Rev.aa Page 10 of 16
IEC 61000-4-12; EN61000-4-12 (Ring Wave)
(Level X: 6kV/500A, 100kHz CM & DM on AC lines) Criterion A
Conducted RF IEC 61000-4-6; EN61000-4-6
(Level 3: 10V on AC, load and comms lines) Criterion A
Voltage Dip, IEC 61000-4-11; EN61000-4-11
Interruptions (Level: 30% dip for 10ms) Criterion A
(Level: 60% dip for 100ms) Criterion B
(Level: 100% dropout for 5s) Criterion B
3.6. Environmental
Temperature:
Vibration:
Operational: 1.5mm displacement 2-9Hz – all major axes,
0.5g acceleration 9-200Hz – all major axes,
Transportation: 0.01g/Hz2 acceleration 5-20Hz,
(packaged) -3dB/oct 20-200Hz – all major axes.
Shocks:
Transportation: 6ms, 18g half sine (packaged)
11/26/2009_Rev.aa Page 11 of 16
Drop test: 1m drop all faces (packaged)
Cooling:
Cooling is performed through forced convection using 2 x 60mm fans with
variable speed control, finger guard. On rectifier startup, if a fan is
disconnected it will be detected and the fan alarm software routines
activated. Fans stop if AC power fails or rectifier inhibited remotely. The
fans are mounted internally into the rectifier.
3.7. Mechanical
Size:
Width: 218mm
Height: 72 mm (1.62U)
Depth: 300 mm
Mass: < 5.2kg
3.8. Connections
11/26/2009_Rev.aa Page 12 of 16
4. Dimensions - rectifier
11/26/2009_Rev.aa Page 13 of 16
11/26/2009_Rev.aa Page 14 of 16
11/26/2009_Rev.aa Page 15 of 16
11/26/2009_Rev.aa Page 16 of 16