Вы находитесь на странице: 1из 1

Differential Relay Sensitivity Adjuster

L. HEADLEY
M E M B E R AIEE

M A G N E T I Z I N G I N R U S H C U R R E N T experienced
when energizing a transformer has always presented
a problem in the application of differential relays. T h e
inrush current appears to the differential relay as a fault
within the transformer and will cause the relay to operate
and trip the transformer circuit breakers incorrectly. This
problem is increased with the use of large transformers.
T o overcome this difficulty, a device has been developed
which automatically desensitizes the differential relay
during the inrush period. This device is referred to as a
sensitivity adjuster and consists of a small iron-core reactor
connected across the restraint winding terminals of the
differential relay. A center tap on the reactor winding is
connected to the operating winding terminal of the differen­ Figure 1. Percentage differential relay equipped with sensi­
tial relay by a circuit which includes the contacts of a time- tivity adjuster
delay relay and may also include an adjustable resistor.
T h e sensitivity adjuster is a simple device and can be relay setting is desensitized to prevent operation on magne­
applied to almost any type of percentage restraint differen­ tizing inrush. When the transformer is energized, relay
tial relay. T h e adjuster does not change the sensitivity C is energized which after a time delay opens contact
of the differential relay or interfere in any way with the C restoring the differential relay to a normal sensitive
relay operation during normal conditions. setting. If a fault of sufficient magnitude occurs in the
O n e adjuster is required for each phase element of the transformer during the inrush period, it will be detected
differential relay and can be easily applied, even on relays by the differential relay which will operate to clear the
that are already in service. T h e application of this device transformer from the system.
does not require making any changes in the differential Tests were made to determine the effect of magnetizing
relay or its adjustment. T h e setting required for the inrush current on a differential relay equipped with a
differential relay during the inrush period is determined sensitivity adjuster. These tests were made on a 40,000-
primarily by the number of turns on the reactor. A low- kva 33/110-kv 3-phase transformer by energizing the
ohmage adjustable resistor in series with the center tap of transformer through a 33-kv oil circuit breaker. T h e
the reactor can be used if further accuracy is required. transformer was equipped with percentage restraint
Figure 1 shows a sensitivity adjuster applied to one differential relays set for sensitive operation to give maxi­
phase element of a differential relay. When the trans­ m u m protection.
former is de-energized, relay C is de-energized and contact T h e first series of tests was made by energizing the
C is closed. So long as contact C" is closed, the differential transformer several times with the sensitivity adjuster
disconnected from the differential relay. Each time the
Table I. Tests Without Sensitivity Adjuster transformer was energized the inrush current was sufficient
to cause the differential relay to operate. T h e second
Magnetizing I n r u s h , 3 3 Kilovolt-Amperes,
rms series of tests was made with the sensitivity adjuster con­
Test
Number Phase Β Phase C Relay R e s p o n s e
nected to the differential relay. No change was made
in the normal setting of the relay. T h e transformer was
1 700 1,160 360 Phase Β again energized several times, and each time the inrush
2 1,200 500 500 Phase A
3 1,200 1,200 700 Phase A and Phase Β current was equally severe as on the previous tests. How­
ever, the differential relay did not respond to trip the
transformer circuit breakers. T h e results of these tests
Table II. Tests With Sensitivity Adjuster Connected
are shown in Tables I and I I .
M a g n e t i z i n g I n r u s h 3 3 Kilovolt-Amperes,
T h e use of sensitivity adjusters on transformer differential
rms relays prevents the relays from tripping on magnetizing in­
Test
Number Relay Response rush and permits extremely sensitive relay settings.
Digest of paper 50-190, "Differential Relay Sensitivity Adjuster," recommended by
4 350 340 860 None the A I E E Committee on Relays and approved by the A I E E Technical Program C o m ­
5 400 1,140 620 None mittee for presentation at the A I E E Middle Eastern District Meeting, Baltimore, M d . ,
6 1,200 540 1,200 None October 3-5, 1950. Scheduled for publication in A I E E Transactions, volume 69, 1950.
7 700 1,160 400 None
8 1,150 500 400 None C. L. H e a d l e y is with the Consolidated Gas, Electric Light, and Power C o m p a n y of
Baltimore, Baltimore, M d .

NOVEMBER 1950 Headley—Differential Relay Sensitivity Adjuster 967

Вам также может понравиться