Submission Date: Tuesday, November 12, 2019

Marks: 70
Please read the instructions carefully prior to start this assignment.
1. Use this page as a title page of your assignment
2. Solve your assignment on A4 size paper. Otherwise your marks will be deducted.
3. Copying of assignment will be considered as a serious crime.
4. Please follow deadline strictly; no assignment will be entertained after the due date and time.

Name: ___________________________________

Registration #: ___________________________________

Question No.1

(a) Draw the power transmission system that includes generation, transmission and distribution and
also clearly label the connection configuration (𝑦𝑦, 𝑦∆, ∆𝑦 𝑎𝑛𝑑 ∆∆) at each block.
(b) Write down at least three applications for each 𝑦𝑦, 𝑦∆, ∆𝑦 𝑎𝑛𝑑 ∆∆ configurations.

Question No.2

The magnitude of the phase voltage of an ideal balanced three-phase Y-connected source is 125 V. The
source is connected to a balanced Y-connected load by a distribution line that has an impedance of 0.1
+ j0.8 . The load impedance is 19.9 + j14.2 . The phase sequence is acb (i.e. negative phase sequence).
Use the a-phase as reference and figure out the three line currents, the three phase voltages at the load
and the three line voltages at the load.

Ans. IaA = 5<-36.87 , IbB = 5<83.12, IcC = 5<-156.87, VAN = 122.3 <-1.36, VBN = 122.3 <118.64,
VCN = 122.3 <-121.36, VAB = 211.71<-31.36 , VBC = 211.71<88.69, VCA = 211.71<-151.36.

Question No.3

A balanced delta-connected load has an impedance of 60 + j45. The load is fed through a line having an
impedance of 0.8 + j0.6. The phase voltage at the terminals of the load is 480 V. The phase sequence is
positive. Use VAB as reference

a. Calculate the three phase currents of the load.


b. Calculate the three line currents.
c. Calculate the three line voltages at the load.
Ans. IAB = 6.4<-36.87, IBC = 6.4<-156.87, ICA = 6.3<83.13. IaA = 11.09<-66.87 , IbB =
11.09<173.13, IcC = 11.09<53.13. 480<0, 480<-120, 480<120.

Question No.4

The c-phase voltage of a balanced three-phase Y-connected system is 450<-25 V. If the phase sequence
is negative , what is the value of VAB.

Ans. 779.42<65

Page 1 of 2
Question No.5

The line voltage VAB at the terminals of a balanced three-phase delta-connected load is 4160<0 V. The
line current IaA is 69.28<-10 A.

a. Calculate the per-phase impedance of the load if the phase sequence is positive.
b. Repeat (a) for negative phase sequence.
Ans. 104<-20, 104<40.

Question No.6

A factory has an electrical load of 1600 kW at a lagging power factor of 0.8. An additional variable
power factor load is to be added to the factory. The new load will add 320kW to the real power load of
the factory. The power factor of the added load is to be adjusted so that the overall power factor of the
factory is 0.96 lagging.
a. Specify the reactive power associated with the added load.
b. Does the added load absorbs or delivers magnetizing vars?
c. What is the power factor of the additional load?
d. Assume that the voltage at the input to the factory is 2400 V(rms). What is the rms magnitude
of the current into the factory before the variable power factor load is added?
e. What is the rms magnitude of the current into the factory after the variable power factor load has
been added.
Ans. -640KVAR, delivers, S(added load) =320-640j, pf = 0.4472 leading, 833.33<-36.87, 833.33<-
16.26

Question No.7

The three loads shown in the figure are S1 = 4 +1 j KVA, S2 = 5 + 2j KVA and S3 = 10 +0j KVA
a. Calculate the complex power associated with each voltage source, Vg1 and Vg2.
b. Verify that the total real and reactive power delivered by the sources equals the total real and
reactive power absorbed by the network.
Ans. Sg1 = 9166.4 + j1076.8 VA, Sg2 = 10448 + j1923.2 VA. P(dissipated) = P(supplied) =
19614.4Watts , Q(dissipated) = Q(supplied) = 3000VAR.

Page 2 of 2