Protection Relay-VMR (Digital) Product Code: PRX/02/VMR/DIN/07

Protection of 3 Phase devices against Over voltage,Under voltage,Single Phasing,


Reverse Phasing & Unbalance supply are one of the major issue in electrical systems.
For safe running of 3-phase devices, special protections that keep a continuous
watch on supply conditions are very essential. The major cause of maximum
load burn-out is overloading which occurs due to unbalance supply,
Single Phasing & Reverse Phasing conditions.
This product detects such Conditions & protect the load from burn out.

'PROTON's Protection Relay' offers above protections along with 3 digit display showing
R-Y,Y-B,B-R voltages in scanning mode with precise accuracy.

LOW/HIGH voltage tripping to ensure trouble free running of 3-phase Loads.

Protection Relay-VMR (Digital) Product Code: PRX/02/VMR/DIN/07


SALIENT FEATURES
- Microcontroller based technology.
- Voltage protection along with digital voltage readout.
- Wide range of supply variation.
- Unit will also work if any one phase is present.
- Protection against Under voltage.
- Protection against Over voltage.
- Single Phasing & Reverse Phasing protection.
- All the set points settable by keys.
- Phase unbalance protection.
- Trip Delay for Under voltage & Unbalance is settable
VMR 3P (BSL) Model
PROTON PR-07
ELECTRONICS
- Reverse Phasing Protection can be able
UV to bypass through settings.
OV
- Indications for Low voltage , High Voltage,
SPP & Relay ON .
TIME
SPP
- Message Display for SPP, Reverse Phasing
RLY
& Unbalance Faults.
FUN
SET
PROTON - No separate auxiliary supply required.
- Hold feature:- Press Upward Arrow key in Running
condition to hold the scrolling of Phase to Phase
supply voltages.
- Neutral Protection feature i.e. If one of the phase get
connected to neutral then there will be no
damage to the unit.

PROTON

PROTON POWER CONTROL PVT. LTD


Survey no. 28, Jagtap Dairy,
Pimple Nilakh, Pune - 411027
TEL/FAX : 020-7270100, 7270800,
7276777
Email : proelec@vsnl.net
Technical Specifications
Supply voltage : 3 Phase 415 VAC,50 Hz (R,Y,B &N) (No auxiliary supply)
Supply voltage Range : 200 V to 500 V
Output Contacts : Two SPDT ( C-N/O-N/C) Relay,Rating 5A at 250V AC

Under Volatge Setting : Default 360 V , UV Set Range :- 350 V to 380 V Hysterisis-10 V
Over Volatge Setting : Default 450 V , OV Set Range :- 430 V to 460 V Hysterisis-10 V
Unbalance Setting : Default 40 V , UB Set Range :- 1 V to 100 V Hysterisis-10 V
Trip Time delay for UV & UB: : Default 5 sec. Range- 1 to 60 seconds.
Trip Time delay for OV, SPP& REVP : Fixed < 100 msec.
Relay ON/RESET Delay : Default 60 sec. Relay ON/RESET Delay Range - 1 to 60 sec.
Fault Reset : Auto reset.
: UNDER VOLTAGE FAULT : RED LED
Indications OVER VOLTAGE FAULT : RED LED
SPP/UB/REV PHASING : RED LED
RELAY ON : GREEN LED
Keys SET : SET key, Press to enter into SET Mode

: Upward Arrow key, Press to increment the set point.

: Downward Arrow key, To Decrement the set point.

Operating Temperature range : -5 C to 60 C. 0 0

Relative Humidity : 10 to 95% RH


Mounting : Din rail.
Dimensions : 70 (L) x 62 (W) x 111 (D) mm.

WORKING
- After Power ON, display shows Phase to Phase Voltages for the duration of 10 sec. each following
the messages r-y, y-b,b-r respectively in a scrolling manner.
-If the Input supply is within the range of the fault limits then On Timer starts decrementing
on display & after Set On Time over Relay will be ON with RLY indication glowing.
-If Over voltage,Under voltage, Spp/Reverse phasing/Unbalance occurs in the supply then Relay
will be OFF after the trip delay of that particular fault & corresponding fault LED starts blinking.
-Hysterisis between Cut off & cut in for Under Voltage,Over Voltage& Unbalance faults is 10V
-If any Phase to Phase Voltage reduces below UV set point,Relay will trip after set trip delay
over. If that paticular phase to phase voltage increases above ( UV set point + 10 V),
Relay will be ON after the set reset delay over.
-If any Phase to Phase Voltage increases above OV set point,Relay will trip after trip delay
(<100 ms)over. If that paticular phase to phase voltage reduces below ( OV set point - 10 V),
Relay will be ON after the set reset delay over.
- If any Phase to Phase Voltage increases/reduces above/below the UB set point compared to other
two Phase to Phase voltages,Relay will trip after set trip delay over.If that paticular phase to phase
voltage reduces/increases below/above (UB set point -/+ 10 V),Relay will be ON after the
set reset delay over.
- If any of the Phase fails,Relay will trip after trip delay (<100 ms) over. If all phases are
present,Relay will be ON after the set reset delay over.
- If Phase sequence is changed to R-B-Y/Y-R-B/B-R-Y,Relay will trip after trip delay (<100 ms)
over. If phase sequence is corrected to R-Y-B,Relay will be ON after the set reset delay over.
- As there is common indication for UB/SPP/REVP,Display will show the messages
'ub FLt','SPP FLt' & 'rP FLt' for the respective faults following the P-P Voltages in scrolling manner.
- Hold feature:- Press & release Upward Arrow key to hold the display to view particular
Phase-Phase Voltage. By pressing the Upward Arrow key UV,OV&SPP indications flash
to indicate the Display HOLD.After hold the display will hold the last displayed
Phase to Phase Voltage along with its message (r-y/y-b/b-r) alternately .
PROCEDURE TO VIEW/CHANGE SETTINGS
SET POINTS:

- To change the settings press & release SET key,Display will show the message 'pas'
and then '000'. Now by operating upward arrow keys, user can enter the password
(default 11) and press SET key to accept. If correct key is entered, YES message will
be displayed, else for wrong entry the display will show NO message and then '000'.
- To change the Under Voltage settings press & release SET key,Display will show
the message 'uV'.Now again press & release the SET key.Now display will show
the Under Voltage Set point.Now by operating Upward/Downward Arrow keys, user can
increment/decrement the Under Voltage set point.
Press & release SET key or Wait for 10 seconds to save the settings.
- To change the Over Voltage settings press & release SET key again & again till
Display will show the message 'oV'.Now again press & release the SET key.Now display
will show the Over Voltage Set point.Now by operating Upward/Downward Arrow keys,
user can increment/decrement the Over Voltage set point.
Press & release the SET key or Wait for 10 seconds to save the settings
- To change the On Delay/Reset Delay settings for Relay press & release SET key again &
again till Display will show the message 'dLY'.Now again press & release the SET key.
Now display will show the On Delay/Reset Delay Set point.Now by operating
Upward/Downward Arrow keys,user can increment/decrement
the On Delay/Reset Delay set point.
Press & release the SET key or Wait for 10 seconds to save the settings.
- To change the Unbalance settings press & release SET key again & again till
Display will show the message 'ub'.Now again press & release the SET key.Now display
will show the Unbalance Set point.Now by operating Upward/Downward
Arrow keys,user can increment/decrement the Unbalance set point.
Press & release SET key or Wait for 10 seconds to save the settings.
- To change the Trip Delay settings for UV & UB press & release SET key again & again till
Display will show the message 'trp'.Now again press & release the SET key.Now display
will show the Trip Delay Set point.Now by operating Upward/Downward
Arrow keys,user can increment/decrement the Trip Delay set point.
Press & release SET key or Wait for 10 seconds to save the settings.
- To change the Reverse Phase Trip Enable/Disable settings press & release SET key
again & again till Display will show the message 'rp'.Now again press & release
the SET key.Now display will show the message 'YES' i.e. Reverse Phase protection
is enabled. Now by operating Upward/Downward Arrow key,user can enable/disable the
Reverse Phase protection by saving the message 'YES'/ 'no'.
Press & release SET key or Wait for 10 seconds to save the settings.
- NOTE :- After entering into the settings if user do not operate any keys then Display will
come out of the settings after 5 seconds. While viewing/changing the settings,
the period between the key strokes should not be more than 10 seconds.
Otherwise Display will come out of the settings.
CONNECTION DIAGRAM

Terminals:
1. Input Supply R-Phase
2. Input Supply Y-Phase
3. Input Supply B-Phase
4. Input Supply Neutral
5. Dummy
6. Dummy
7. Contact1 N/C
8. Contact1 C
9. Contact1 N/O
10. Contact2 N/C
11. Contact2 C
12. Contact2 N/O

12 11 10 9 8 7
VMR 3P Model
PROTON PR-07
ELECTRONICS VMR 3P

R Y B N UV

OV
TIME
SPP
RLY
FUN
SET
PROTON
1 2 3 4 5 6

N/V
ON
OFF

MOTOR
NOTE
INTERCHANGE 1 & 2
IN CASE STARTER DOSE
NOT HOLD. LED INDICATES
RELAY CONDITION.

Document No.:- CAT-DESG-123 Rev. 1


TERMINAL CONNECTIONS
Terminal No.1,2,3 & 4 - R,Y,B & N are
3 phase supply i/p terminals.
Supply is taken from all three phases.
Unit will work even if any one phase
is ON.Terminal No. 5 & 6 are Dummy
contacts.Terminal No.7,8,9 are Output
Relay1 contacts N/C,C,N/O resp. &
Terminal No. 10,11,12 are Output
Relay2 contacts N/C,C,N/O resp.
INDICATIONS:
1.UV - Starts flashing when voltage
decreases below set limit.
2.OV - Starts flashing when voltage
increases above set limit.
3.SPP - Starts flashing when SPP,UB,
REVP fault occurs.
4.RLY - Indicates that O/P Relays are ON.
SETTING:
uV - Default 330 V. Range-240 to 400V
oV - Default 460 V. Range- 430 to 500V
dLY - Default 10 sec. Range-1 to 60 sec.
uB- Default 70 V. Range- 1 to 100V
trP- Default 5 sec. Range- 1 to 60 sec.
rP- Default YES. Enable-YES,Disable-no

PROTON ELECTRONICS ,PUNE- 27

1 2 3 4 5 6
R Y B N Dummy

PRX/02/VMR/DIN/07
UV
OV
SPP
RLY SET

SET SET key

To increment set point


To decrement set point

PROTON POWER CONTROLPVT. LTD


PUNE - 411 027