Вы находитесь на странице: 1из 21

D

RT'
CE
Saudi Electricity Company ‫الشركـة السعوديـة للكـهرباء‬
Western Region Branch
APPR'D

CHK'D
MA
HVAC LOAD CALCULATION
HVAC SYSTEM SOW DESCRIPTION:
The construction of Al Adel 380/110/13.8kV BSP Substation is planned in order to meet the
growing power demand of the Area. The Scope of Work in term of “Mechanical (HVAC)”
Providing new and independent HVAC facilities along with all necessary ductwork and
control system for the following Buildings;
IISSUED FOR BASE DESIGN SUBMITTAL

N 1. 380kV GIS Building. 5. Pump Room


O
TI
P
2. 110kV GIS Building. 6. Gate House.
3. Control Building. 7. Cable Tunnels.
RI R.
C NE
OW
S
4. 13.8kV Switchgear Building
ITS
E OF
D T
EN
NS
Air conditioning system for the Al Adel 380/110/13.8kV BSP Substation will be totally CO
EN

independent with 100% Standby facilities. For the 380kV GIS Building, 110kV GIS Building, ITT
WR

Control Building & 13.8kV Switchgear Building packaged type Direct Expansion units (PACU) E
TH

shall be used, as per the Project’s Technical Specification (PTS-11WN355). Each PACU unit
T
OU

is selected at 100% of zone(s) load; therefore, each zone(s) had 100% standby capacity.
TH
WI

That means each unit of the pair runs independently of the other and can fulfill the
NT
ME

concerned zones requirements as per the load demand/variation.


CU
DO
S
THI
OM
For Gate House, 01 No. Ceiling Mounted mini Split Type A/C Unit with 100% capacity will be FR
D

BY C provided. NE
TAI
OB
Ventilation System will be provided for the following zones as per PTS-11WN355;
AJE
BE
ALL
SH
APRIL 2014

RT

DATE 1. Cable Tunnel (Under 380kV Bldg.). PA


IN
OR

2. Outgoing Outdoor Cable Tunnel from 110kV Bldg.). LL


FU
IN
00 NO.
3. Cable Tunnel (Control Bldg. / 380kV Bldg.).
N
TIO
REVISIONS UC

4. Cable Tunnel (Control Bldg. / 110kV Bldg.).


OD
DRAWN
PR
RE

5. Cable Tunnel (110kV Bldg/Power Transformer).


NO
BY: Md. Nayeemullah CO.
Y
DATE: APRIL 2014 CIT
6. Pump Room. TRI

CHECKED
EC
EL

BY: Muhammad Afzal 7. Toilet. UDI


SA
OF
DATE: APRIL 2014 8. Battery Room. TY
ER

OPRG. DEPT
OP

HVAC System design shall comply with the requirement of following Standards.
PR
LE
BY SO
E
DATE:- 1. Project scope of work/Technical specification (PTS-11WN355) TH
E

ENG'G. DEPT.
AR

2. SEC Engineering Standard (TES-K-100.01) N


REI
BY:- HE

DATE:-
3. SEC Construction Standard (TCS-K-100) ED
AIN
NT

CERTIFIED. 4. American Society of Heating, Refrigeration & Air conditioning Engineers (ASHRAE).
CO
N
TIO
BY:-
5. SMACNA for Design & Construction of Low Pressure Ducts.
MA
OR
DATE:-
INF
E

DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 1 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S

JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED

SEC-ERB CAD-E (2002/03)


WORD
D
RT'
CE
Saudi Electricity Company ‫الشركـة السعوديـة للكـهرباء‬
Western Region Branch
APPR'D

MA SYSTEM DESIGN DESCRIPTION:


CHK'D
System has been designed to provide constant volume application to maintain the required
inside temperature of 77o F (25o C) under all outdoor summer ambient conditions.

For each building, two pairs of Packaged Type A/C units are used. Each pair of two units runs
independently controlled by their concerned zones / areas.

The Packaged A/C units are located outdoor the Substation and zones description are
mentioned below;
IISSUED FOR BASE DESIGN SUBMITTAL

380kV GIS Building:


O
TI
P

 As per Tender Layout Drawing # WT - 908465, Due to large size of 380kV GIS
RI R.
C NE

Building 02 set of Air-Conditioning Units shall be provided for 380kV GIS Building.
OW
S
ITS
E OF
D T

 1st set of Air Conditioning unit (System # 01 consisting of PACU-1A & PACU-1B) and 2 nd
EN
NS
CO
set of Air Conditioning unit (System # 02 consisting of PACU-2A & PACU-2B) is used for EN
ITT
below mentioned zones; WR
E


TH
380kV GIS Room T
OU
TH
WI

• Store Room
NT
ME
CU
DO

 Hence the System # 01 & 02 has total 02 separate/independent Zones.


S
THI
OM
FR
D

BY C 110kV GIS Building: NE


TAI
AJE OB

 As per Tender Layout Drawing # WT - 908465, Due to large size of 110kV GIS
BE
ALL

Building 02 set of Air-Conditioning Units shall be provided for 110kV GIS Building.
SH
APRIL 2014

RT
PA
DATE IN

 1st set of Air Conditioning unit (System # 03 consisting of PACU-3A & PACU-3B) and 2 nd
OR
LL
FU

00 NO. set of Air Conditioning unit (System # 04 consisting of PACU-4A & PACU-4B) is used for IN
N

REVISIONS below mentioned zones; TIO


UC


OD
DRAWN 110kV GIS Room PR
RE
NO
BY: Md. Nayeemullah CO.


Y
DATE: APRIL 2014 Cable Basement CIT
TRI

CHECKED
EC
EL

• Store Room
UDI
BY: Muhammad Afzal SA
OF
DATE: APRIL 2014 TY

 Hence the System # 03 & 04 has total 03 separate/independent Zones.


ER

OPRG. DEPT
OP
PR

Control Building:
LE
BY SO
E
DATE:- TH

 As per Tender Layout Drawing # WT - 908465, Due to large size of Control Building
E

ENG'G. DEPT.
AR

02 set of Air-Conditioning Units shall be provided for Control Building.


N
REI
BY:- HE
ED
DATE:-
 1st set of Air Conditioning unit (System # 05 consisting of PACU-5A & PACU-5B) is used for
AIN
NT

CERTIFIED.
CO
below mentioned zones; N
TIO
BY:- MA
OR
DATE:-
INF
E

DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 2 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S

JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED

SEC-ERB CAD-E (2002/03)


WORD
D
RT'
CE
Saudi Electricity Company ‫الشركـة السعوديـة للكـهرباء‬
Western Region Branch
APPR'D

MA • Control & Relay Room & Raised Floor


CHK'D
 Hence the System #05 has total 02 separate/independent Zones.
 2nd set of Air Conditioning unit (System # 06 consisting of PACU-6A & PACU-6B) is used
for below mentioned zones;
• Associated rooms/ Cable Basement.

 Hence the System #06 has total 15 separate/independent Zones.


IISSUED FOR BASE DESIGN SUBMITTAL

N 13.8kV Switchgear Building:


O

 As per Tender Layout Drawing # WT - 908465, 01 set of Air-Conditioning Units shall


TI
P
RI
C be provided for 13.8kV Switchgear Building. R.
NE
OW
S
ITS

 1st set of Air Conditioning unit (System # 07 consisting of PACU-7A & PACU-7B) is used for
E OF
D T

below mentioned zones;


EN
NS


CO

13.8kV Switchgear Building


EN
ITT
WR
E


TH

Cable Basement
T
OU
TH
WI

 Hence the System #07 has total 02 separate/independent Zones.


NT
ME
CU
DO
S
THI

SYSTEM OPERATION: (NORMAL MODE)


OM
FR
D
NE
BY C TAI
AJE
Each Packaged type air conditioning unit (PACU) is equipped with supply air (MVD), OB
BE

Return/Re-circulated air (MVD) along with Outdoor air (VD) Damper. These Dampers control
ALL
SH
APRIL 2014

and regulate the airflow rates under different load conditions. Separate ducting from each
RT
PA

Unit of the pair combines into one common ducting (sized for 100% of Supply air from single
DATE IN
OR

Unit). The supply air is ducted while the return air is free. The volume damper for supply air
LL
FU

is motorized while the other volume dampers are manually operated. The duct smoke
IN
00 NO. N

detector is mounted on the common supply & return air duct.


TIO
REVISIONS UC
OD
DRAWN
PR
RE

BY: Md. Nayeemullah The Fresh Air or Outdoor Air is supplied through the Sand Trap Louver with Wire Mesh NO
CO.

DATE: APRIL 2014 Screen & Aluminum filter. The Fresh Air intake from the Sand Trap Louver arrangement is Y
CIT

CHECKED
connected to the openings provided in PACU unit. TRI
EC
EL
UDI
BY: Muhammad Afzal
If the PACU Unit is not running i.e. in standby mode, then all the Motorized volume control
SA
OF
DATE: APRIL 2014
dampers (MVD) is in closed position. For the Duty Unit, the Supply Dampers (MVD) is fully
TY
ER

OPRG. DEPT opened; while Return Air damper (MVD) is also operating respectively and Outdoor Air
OP
PR

Damper (MVD) is set at minimum open position. The minimum open position for Outdoor Air
LE
BY SO
E
DATE:- Damper is that which provides the minimum Flow Rate of Outdoor Air required for ventilation TH
E

ENG'G. DEPT. and pressurization of zones and maintains a +ve pressure of 0.2” of W.G. AR
N
REI
BY:- HE

DATE:-
The Duty & standby units will operate on a shift basis. The changeover from duty to standby ED
AIN

unit or vice-versa can be either automatic or manual. NT

CERTIFIED.
CO
N
TIO
BY:- MA
OR
DATE:-
INF
E

DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 3 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S

JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED

SEC-ERB CAD-E (2002/03)


WORD
D
RT'
CE
Saudi Electricity Company ‫الشركـة السعوديـة للكـهرباء‬
Western Region Branch
APPR'D

MA In “Automatic” mode, the Changeover from duty to Standby unit is either on the Time Basis
CHK'D
or due to failure of running unit. The time Basis changeover can be set from one day to one
week, as required. The 7-day per week – 24 hour per day timer shall take care of scheduling
the operation of the two units in order to make sure that the two Units works equally. Also in
case of failure of the running PACU unit due to any reason, then the operation shall be
transferred automatically to the standby PACU unit. “Manually” the changeover can be
activated any time from the HVAC Control Panel.

The temperature controller (or Thermostat) will decide whether cooling or heating is required
or not, by comparing the set-point with actual space temperature, If cooling is required then
IISSUED FOR BASE DESIGN SUBMITTAL

N DX cooling stages have to be activated/deactivated based on the cooling demand to meet


O
TI the set-point, which is adjustable from the controller display. If heating is required then the
P
RI
duct mounted electric heater is activated. R.
C NE

The Temperature controls shall be provided as part of the AC unit by the Control Panel
OW
S
ITS
E OF
D
Supplier/Installer. The Thermostat shall be cooling and heating type with a minimum of 2 T
EN
stages of Mechanical Cooling / Heating. The Thermostat shall be mounted on the return air NS
CO
stream @ 1.5M above F.F.L. The Thermostat shall be provided with lockable transparent EN
ITT

cover. WR
E
TH
T
OU
TH

SMOKE PURGE MODE:


WI
NT
ME
CU
DO

In case the Smoke Detector installed at the common Supply and Return air Ducts detects
S
THI

smoke or the FACP sends a signal indicating smoke presence, then the Duty Packaged unit
OM
FR

shall be automatically de-energized and all temperature control function shall stop. At such
D
NE

condition, an indication shall be sent to the HVAC control Panel also.


BY C TAI
AJE OB
BE
ALL

During the Smoke purge operation all PACU’s (Duty and standby) dampers (Supply and
SH
APRIL 2014

RT
PA
DATE
Return air) will be closed and smoke purge / exhaust damper and Return Opening MF/SD IN
OR
will be opened fully to clear the smoke and product of combustion from the concerned zone. LL
FU

00 NO. Smoke Purge Fan operates during smoke purging operation i.e. to exhaust smoke from the IN
N

REVISIONS zones in the event of fire or heavy smoke conditions. It should be possible to manually run TIO
UC

the Smoke Purge Fan either from the HVAC Control Panel or from Smoke Purge Fan
OD
DRAWN
PR

isolating switch or from Remote Selector Switch located outside near the main door of
RE
NO
BY: Md. Nayeemullah
Control Room.
CO.
Y
DATE: APRIL 2014 CIT
TRI

CHECKED
After the smoke purging operation ends, it would only be possible to re-start the Air
EC
EL
UDI
BY: Muhammad Afzal Conditioning units by re-setting the HVAC Control Panel. SA
OF
DATE: APRIL 2014 TY
ER

OPRG. DEPT
OP
PR

SYSTEM DESIGN CRITERIA:


LE
BY SO
E
DATE:- TH
E

ENG'G. DEPT. For calculating air-conditioning load of Al Adel 380/110/13.8kV BSP Substation, reference is AR
N

BY:- taken from Project Technical Specification (PTS-11WN355) and other inputs / data are REI
HE

DATE:-
adopted from ASHRAE standards or SEC Engineering Standards. ED
AIN
NT

CERTIFIED.
CO
N
TIO
BY:- MA
OR
DATE:-
INF
E

DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 4 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S

JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED

SEC-ERB CAD-E (2002/03)


WORD
D
RT'
CE
Saudi Electricity Company ‫الشركـة السعوديـة للكـهرباء‬
Western Region Branch
APPR'D

MA

CHK'D

DESIGN PSYCHROMETRIC CONDITIONS:

SEASON OUTDOOR CONDITION INDOOR CONDITION

48 C or 118 F Dry bulb


IISSUED FOR BASE DESIGN SUBMITTAL

Summer Electrical Equipments Rooms


O
TI temperature & 27C or 81F Wet
P
RI
C bulb temperature. 25 C or 77.0 F Dry bulb R.
NE
OW
S
temperature & 50 % RH for all
ITS
E
14 C or 57 F Dry bulb
OF
D T

Winter zones.
EN
NS
temperature CO
EN
ITT
WR
E

Refer Attachment: “1” for the “Cooling Design Conditions” for Jeddah. We had taken the
TH
T

ambient dry bulb condition & ambient wet bulb condition as per PTS-11WN355.
OU
TH
WI
NT
ME
CU
DO
SITE INFORMATION: S
THI
OM
FR

The site conditions adopted for Load calculation are given below;
D
NE
BY C TAI
AJE OB
BE
ALL

SITE DATA VALUE


SH
APRIL 2014

RT
PA
DATE IN

Location Jeddah
OR
LL
FU

21.51 (North)
IN
00 NO.
Latitude N
TIO
REVISIONS UC
Longitude 39.13 (East) OD
DRAWN
PR
RE

BY: Md. Nayeemullah Altitude 7m (26ft)


NO
CO.
Y
DATE: APRIL 2014
Mean daily range 27F
CIT
TRI

CHECKED
EC

Max wind velocity 22 kph (14 mph)


EL
UDI
BY: Muhammad Afzal SA

Wind Direction
OF
DATE: APRIL 2014 North TY
ER

OPRG. DEPT
Required building pressurization
OP

+ve Pressurization of 50 Pa (0.2” W.G) in all PR


LE
BY SO

DATE:-
zone except Battery Room, which is to be E
TH
E

ENG'G. DEPT. Neutrally pressurized.


AR
N
REI
BY:- HE
ED
DATE:- Refer Attachment: “1” for the “Site Conditions” for Jeddah. We had taken the site data from AIN
NT

CERTIFIED. Geological Survey from Internet. CO


N
TIO
BY:- MA
OR
DATE:-
INF
E

DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 5 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S

JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED

SEC-ERB CAD-E (2002/03)


WORD
D
RT'
CE
Saudi Electricity Company ‫الشركـة السعوديـة للكـهرباء‬
Western Region Branch
APPR'D

MA

CHK'D

ZONE WISE LOAD DATA:

The HVAC load is calculated on the “zone basis” .The variable load inputs for each zone is
described below:
IISSUED FOR BASE DESIGN SUBMITTAL

N BUILDING WALL & FLOOR AREAS:


O
TI
P The zone’s areas are calculated using the Substation building plan. Refer Civil &
Architectural drawings for S/S building plan showing the room’s dimensions / area and their
RI R.
C NE

orientation.
OW
S
ITS
E OF
D T

BUILDING MATERIAL’S U-VALUES:


EN
NS
CO
EN
ITT
The U-Value is calculated based on the actual material used. All values for “R” (Resistance) WR
E

are extracted from ASHRAE GRP 158, cooling and heating load calculation manual, Table TH
T

3.1A unless otherwise noted. For detail U-value calculation, refer Attachment: “A” (Co- OU
TH
WI

Overall “U” Values ASHRAE NT

Building Element ME

(Btu / Hr. (Ft²) (ºF) Reference CU


DO
S
THI

Exposed Roof (Double T Slab w/ False Ceiling) 0.043 12 #


OM
FR
D

Pre-cast Wall 0.08 B


NE
BY C TAI
AJE OB

Internal Concrete Wall 0.31 B


BE
ALL
SH
APRIL 2014

RT

DATE Metal Door 0.14 G PA


IN
OR
LL

efficient of Heat Transmission Calculation: 7 pages). The U-Values adopted for different FU
IN
00 NO.
Architectural elements of Al Adel 380/110/13.8kV BSP Substation is summarized below.
N
TIO
REVISIONS UC
OD
DRAWN
PR
RE
NO
BY: Md. Nayeemullah CO.
Y
DATE: APRIL 2014 CIT
TRI

CHECKED
EC
EL
UDI
BY: Muhammad Afzal SA
OF
DATE: APRIL 2014 TY
ER

OPRG. DEPT
OP
PR
LE
BY SO
E
DATE:- TH
E

ENG'G. DEPT. (Based on the actual Insulation U-Value and SEC Approved R-Value data)
AR
N
REI
BY:- HE

Please note that only Control Room, Communication Room, Conference Room, Relay Test
ED
DATE:-
AIN
NT

CERTIFIED. Room, Office, Fire Fighting Room, Corridor & Toilet are provided with False Ceiling while CO
N
TIO
BY:- MA
OR
DATE:-
INF
E

DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 6 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S

JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED

SEC-ERB CAD-E (2002/03)


WORD
D
RT'
CE
Saudi Electricity Company ‫الشركـة السعوديـة للكـهرباء‬
Western Region Branch
APPR'D

MA 380kV GIS Room, 110kV GIS Room, 13.8kV Switchgear Room, Auxiliary Room, Store
CHK'D
Room’s, Cable Basement & Battery Room are without False Ceiling.

AIR CONDITIONED ZONES:

Keeping with the Technical specification and SEC requirements the complete building is to
be Air-conditioned, under this SOW.

For determining the HVAC load, the Building is divided into 02 separate zones, keeping in
IISSUED FOR BASE DESIGN SUBMITTAL

N
O
view its orientation, purpose, and load profile.
TI

The operation hours for the A/C zones are 24 Hours. Therefore, equipment is to be run
P
RI R.

continuously.
C NE
OW
S
ITS
E OF
D
OCCUPANCY LOAD:
T
EN
NS
CO
EN

The Substation is of unmanned type; but occupancy is considered in Control Room. This can ITT
WR

be considered as “office space”. As per ASHRAE’s Table for “Rates of Heat gain from E
TH

occupants of conditioned spaces”, for standing; light work, walking, rate of heat gain are;
T
OU
TH
WI

Adjusted Sensible heat gain = 73 Watts = 250 Btu / Hr


NT
ME
CU

Adjusted Latent heat gain = 59 Watts = 200 Btu / Hr


DO
S
THI
OM
(Refer Attachment: “B”) FR
D
NE
BY C TAI
AJE
Hence, for determining the occupant heat load, we will use following equation; OB
BE
ALL
SH
APRIL 2014

QPS = NP x 250
RT
PA
DATE IN

QPL = NP x 200
OR
LL
FU

Where
IN
00 NO. N

QPS = Occupant’s Sensible Heat Gain


TIO
REVISIONS UC
OD
DRAWN
PR
QPL = Occupant’s Latent Heat Gain RE
NO
BY: Md. Nayeemullah CO.

DATE: APRIL 2014 NP = No. of person / occupant in the zone Y


CIT
TRI

CHECKED
EC
EL

For occupancy in different zones, following estimates are used;


UDI
BY: Muhammad Afzal SA
OF
DATE: APRIL 2014 TY
ER

OPRG. DEPT
OP
PR

BY
Sr. No. Zone / Room Occupancy LE
SO
E
DATE:- TH
E

ENG'G. DEPT. 1 Control & Relay Room 06


AR
N
REI
BY:-
2 Control & Relay Room (Raised Floor)
HE
01 ED
DATE:-
AIN

3 ENT lobby (Staircase # 02)


NT

CERTIFIED. Nil CO
N
TIO
BY:- MA
OR
DATE:-
INF
E

DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 7 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S

JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED

SEC-ERB CAD-E (2002/03)


WORD
D
RT'
CE
Saudi Electricity Company ‫الشركـة السعوديـة للكـهرباء‬
Western Region Branch
APPR'D

MA

CHK'D LIGHTING LOAD:

The Lightings load in each air-conditioned room is taken from actual Lighting Calculation, as
adopted in the Detail Electrical Design.
The following equation will be used to calculate the heat dissipation from Light Fixtures in
individual rooms / zones;

QLIG. = 3.41 X W X FU X FS
(Refer ASHRAE Fundamental 1997)
IISSUED FOR BASE DESIGN SUBMITTAL

N Where;
QLIG. = Sensible Heat Gain from Light Fixtures (Btu/Hr)
O
TI
P
RI
C W = Total Wattage of Light Fixtures R.
NE
OW
S
FU = Light Fixtures Usage Factor = 1.0
ITS
E OF
D T

FS = Ballast Factor Allowance


EN
NS
CO

We have;
EN
ITT
WR

Ballast Factor for Fluorescent Lamps = 1.20


E
TH
T
OU
Ballast Factor for Incandescent Lamps = 1.00 TH
WI
NT
ME
CU

The heat dissipation due to the lighting load is summarized below; DO


S
THI
OM
FR

Lighting Heat D
NE

Sr. No. Zone / Room Dissipation


BY C TAI
AJE OB

(Watts)
BE
ALL
SH
APRIL 2014

1 Control & Relay Room


RT

DATE 12,715 PA
IN

2 Control & Relay Room (Raised Floor)


OR

Nil
LL
FU
IN
00 NO.
3 ENT lobby (Staircase # 02) 500
N
TIO
REVISIONS UC
OD
DRAWN For lighting load in each room, refer Table: “Heat Dissipation Detail” (Refer Attachment: “C”). PR
RE
NO
BY: Md. Nayeemullah CO.

EQUIPMENT LOAD:
Y
DATE: APRIL 2014 CIT
TRI

CHECKED
EC

For Equipment Heat Dissipation, the reference is taken from “Equipment Layout”. Equipment
EL
UDI
BY: Muhammad Afzal SA

DATE: APRIL 2014


heat dissipation is based on either data provided by the Manufacturer or Supplier or else OF
TY
data is adopted for similar type of panels, distribution board etc from other similar size ER

OPRG. DEPT
OP

projects. In either case the reference is provided for the data adopted for Equipment’s heat PR
LE
BY
dissipation. Refer Attachment: “D“, for Heat dissipation data adopted with panel details. SO
E
DATE:- TH
E

ENG'G. DEPT. Following values are taken for equipment heat dissipation in different rooms. AR
N
REI
BY:- HE
ED
DATE:- Equipment Heat AIN

Sr. No. Zone / Room NT

CERTIFIED. Dissipation (Watts)


CO
N
TIO
BY:-
1 Control & Relay Room
MA

51,512
OR
DATE:-
INF

2 Control & Relay Room (Raised Floor)


E

DRAWING TITLE INDEX PLANT 10,000


DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING
3 ENT lobby (Staircase # 02)
CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756
Nil Page 8 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S

JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED

SEC-ERB CAD-E (2002/03)


WORD
D
RT'
CE
Saudi Electricity Company ‫الشركـة السعوديـة للكـهرباء‬
Western Region Branch
APPR'D

MA

CHK'D

“Heat Dissipation Data” (Refer Attachment: “D”)

OUTDOOR AIR LOAD:


IISSUED FOR BASE DESIGN SUBMITTAL

N
O
TI As per SEC Standard, it is necessary to provide a slight positive internal pressure for
keeping the outdoor dust borne air out and also for proper zone pressurization. For
P
RI R.

calculating the Outdoor or Fresh air quantity, we need to calculate the Exhaust,
C NE
OW
S
Pressurization and Ex-filtration air quantity respectively and then we will calculate the total
ITS
E OF
D
outdoor air quantity based on the criteria set by SEC Standards.
T
EN
NS
For calculating the Building pressurization / ex-filtration air quantity, we have; CO
EN
Site max outdoor temperature = 49ºC = 120ºF ITT
WR
Outdoor wind velocity = 37 kph = 23 mph E
TH

(Refer Attachment: “1” sht. 1 of 2) T


OU

Prevailing wind direction = North of East


TH
WI

Building Pressurization = 0.2 inch of W.G. = 50 Pa


NT
ME

(As per TES-P-119)


CU
DO
S
THI
OM
FR

A.) Wind Pressurization:


D
NE
BY C TAI
AJE OB
BE
The Wind Pressure (or velocity head), caused by the moving air is given by; ALL
SH
APRIL 2014

RT
PA

Pw = C 1 C p  V2
DATE IN
OR

2
LL
FU

(Refer ASHRAE Fundamentals 1997, Chap: 25 – Equ. #25)


IN
00 NO. N

Where;
TIO
REVISIONS UC

Pw = Wind surface pressure relative to Static pr. in


OD
DRAWN
PR
RE

BY: Md. Nayeemullah undisturbed flow (inch of W.G.) NO


CO.

DATE: APRIL 2014 C1 = Unit conversion factor = 0.0129 Y


CIT
Cp = Wind surface pr. coefficient. (Dimensionless) TRI

CHECKED
EC

 = Air density (lbm / ft3) = 0.06 lbm / ft3


EL
UDI
BY: Muhammad Afzal
V = Wind speed (mph) = 23 mph (Specification)
SA
OF
DATE: APRIL 2014 TY
ER

OPRG. DEPT Cp is a function of location on building envelope and wind direction. For undisturbed surface
OP
PR

its value is taken as unity. Putting the values;


LE
BY SO
E
DATE:- TH
E

ENG'G. DEPT.
AR
N

BY:- Pw = 0.0129 x 1.0 x 0.06 x (23)2 REI


HE

DATE:-
2 ED
AIN
NT

CERTIFIED. = 0.2 inches of W.G.


CO
N
TIO
BY:- MA
OR
DATE:-
INF
E

DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 9 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S

JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED

SEC-ERB CAD-E (2002/03)


WORD
D
RT'
CE
Saudi Electricity Company ‫الشركـة السعوديـة للكـهرباء‬
Western Region Branch
APPR'D

MA B.) Make-up (Outside) Air Required to Pressurized the conditioned Space:


CHK'D
Using;

QP = Qexh + P0 Qexh + P0 Q x + Qx (B)


PI PI
Where;
QP = Amount of Ventilation (outdoor) air for required space
Pressurization to the design static pressure (Cfm)
Qexh = Exhaust air (Cfm) from conditioned Zone
IISSUED FOR BASE DESIGN SUBMITTAL

N Qx = Ex-filtration air (Cfm) from conditioned zone


O
TI PO = Outside static pressure on building wall (inches of W.G.)
P
RI
PI = Inside static pressure on building space (inches of W.G.) R.
C NE
S
E
Now, OW
ITS
OF
D T

PI = PS PO
EN
+ NS

Where;
CO
EN
ITT
WR

Ps = Required space pressurization (inches of W.G.)


E
TH
T
PS = 0.2 in of W.G (as req. by specification) OU
TH
PO= Pw = 0.2 in of W.G (as calculated previously) WI
NT
ME
CU

Therefore; DO
S
THI
OM

PI = 0.2// + 0.2//
FR
D

= 0.4// of W.G
NE
BY C TAI
AJE OB
BE
Hence inside required pressure on the building is 0.4// of W.G ALL
SH
APRIL 2014

RT
PA
DATE IN

C.) Ex-filtration Air from Conditioned Space


OR
LL
FU
IN
00 NO.
Using;
N
TIO
REVISIONS UC
OD
DRAWN
PR
RE
NO
BY: Md. Nayeemullah CO.
Y
DATE: APRIL 2014
=
CIT

Qx (Cs x t) + (Cw x V2)


TRI

CHECKED
EC
EL

BY: Muhammad Afzal Where; UDI


SA
OF
DATE: APRIL 2014
Cs = Stack Co-efficient (Cfm2 / in4.0F)
TY

AL
ER

OPRG. DEPT
= (Ref: ASHRAE
0.0150 Cfm2Fundamental;
/ in4.0F Chap: 25) OP
PR
LE
BY (Refer ASHRAE Fundamentals 2009, Ch. 16, Table: 4) SO
E
DATE:- Cw = Wind Co-efficient (Cfm2 / in4. Mph2)
TH
E

ENG'G. DEPT. Cw = 0.0119 Cfm2 / in4. Mph2


AR
N
REI
BY:- (Refer ASHRAE Fundamentals 2009*, Ch. 16, Table: 5) HE
ED
DATE:- t = Average temperature difference between
AIN
NT

CERTIFIED. Indoor – outdoor space. (0F)


CO
N
TIO
BY:-
 t = Tspace – Toutdoor
MA
OR
DATE:-
INF
E

DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 10 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S

JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED

SEC-ERB CAD-E (2002/03)


WORD
D
RT'
CE
Saudi Electricity Company ‫الشركـة السعوديـة للكـهرباء‬
Western Region Branch
APPR'D

MA = 77.0 – 120 = - 43 0F
CHK'D V = Average wind velocity = 23 mph
Putting the values;

 Qx = [0.0150 x (-43)] + [0.0119 x (23)2]


AL

Qx = 2.377 Cfm / in2


AL
Or
IISSUED FOR BASE DESIGN SUBMITTAL

N
O
Qx = 2.377 X AL (Cfm)
TI
P
RI R.

Where;
C NE
OW
S
ITS
AL = Effective Air leakage area, (in2 / ft 2)
E OF
D T

Air leakage can take place through doors, windows, crawl space etc; for the Control & Relay EN
NS

Building air leakage can only take place through the doors opening outside the building. CO
EN
ITT
WR

Using;
E
TH

AL = AD1 x DL1 + AD2 x DL2 + ..........+ ADN x DLN


T
OU
TH
WI

Where;
NT
ME
CU
AL = Effective Air leakage area. DO
S
AD = Area of door opening outside. THI
OM
DL = Air leakage through door FR
D

BY C N = No: of Doors of each type NE


TAI
AJE OB
BE

D.) Zone Ex-filtration Air :


ALL
SH
APRIL 2014

RT

For the zones / rooms in the HVAC system, the outdoors is located in the Control & Relay
PA
DATE IN

Room.
OR
LL
FU
IN
00 NO. N

REVISIONS
For Substation building different sizes of outward doors used the detail of which are as TIO
UC
follows; OD
DRAWN
PR
RE
NO
BY: Md. Nayeemullah
Since there is no door directly exposed to ambient for Control & Relay Room, the Ex- CO.
Y
DATE: APRIL 2014
Filtration Air for this zone will be considered as nil.
CIT
TRI

CHECKED
EC
EL
UDI
BY: Muhammad Afzal
Qx = 0 Cfm SA
OF
DATE: APRIL 2014 TY
ER

OPRG. DEPT
OP
PR

E.) Zone Exhaust Air :


LE
BY SO
E
DATE:- TH

From Air conditioned spaces Al Adel Control & Relay Room have no any exhaust air.
E

ENG'G. DEPT.
AR
N
REI
BY:-

HE
Qexh = 0 Cfm ED
DATE:-
AIN
NT

CERTIFIED.
CO

F.) Zone Pressurization Air : N


TIO
BY:- MA
OR
DATE:-
INF
E

DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 11 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S

JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED

SEC-ERB CAD-E (2002/03)


WORD
D
RT'
CE
Saudi Electricity Company ‫الشركـة السعوديـة للكـهرباء‬
Western Region Branch
APPR'D

MA Now
CHK'D (B) QP = 0 + (0.1/0.3)0+ (0.1/0.3) 0 + 0

= 0+0+0+0

Taking;
QP = 0 Cfm
IISSUED FOR BASE DESIGN SUBMITTAL

N
O
TI
P
RI R.
C NE
OW
S
ITS
E OF
D T
EN
NS
G.) Estimating Outdoor Air Quantity Air : CO
EN
ITT
WR

1. As per TES-K-100.01 P-51 of 89 (sec. 10-1-b) in substations, control room E


TH

and other duct sensitive facility, it is mandatory to provide 10% of supply air
T
OU

fresh air make up. Therefore 10% of the supply air for the fresh air make up
TH
WI

is 1,643 CFM (For supply air quantity Refer cooling Load (CHVAC) Output
NT
ME

sheets; section: C)
CU
DO
S
THI

2. As per TES-K-100.00 P-51 of 89 (sec. 10.2) the maximum amount of outside


OM
FR
D

BY C air shall equal the greater of 5% of supply air in excess of all exhaust air. NE
TAI
AJE Therefore 5% of total supply air is 822 CFM plus exhaust and ex-filtration air, OB
BE

i.e. 822 + 0 + 0 CFM. Total makeup air is 822 CFM. ALL


SH
APRIL 2014

RT
PA

Comparing the values, the higher value of 1,643 CFM is considered as per Section10.2
DATE IN
OR
LL
FU

Hence;
IN
00 NO. N
TIO
REVISIONS UC

Outdoor Air Quantity = 1,643 CFM


OD
DRAWN
PR
RE
NO
BY: Md. Nayeemullah CO.
Y
DATE: APRIL 2014 CIT
TRI

CHECKED
EC
EL
UDI
BY: Muhammad Afzal SA
OF
DATE: APRIL 2014 TY
ER

OPRG. DEPT
OP
PR
LE
BY SO
E
DATE:- TH
E

ENG'G. DEPT.
AR
N
REI
BY:- HE
ED
DATE:-
AIN
NT

CERTIFIED.
CO
N
TIO
BY:- MA
OR
DATE:-
INF
E

DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 12 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S

JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED

SEC-ERB CAD-E (2002/03)


WORD
D
RT'
CE
Saudi Electricity Company ‫الشركـة السعوديـة للكـهرباء‬
Western Region Branch
APPR'D

MA

CHK'D
IISSUED FOR BASE DESIGN SUBMITTAL

N
O
TI
P
RI R.
C NE
OW
S
ITS
E OF
D T
H.) SUMMARY: EN
NS
CO
EN
Total ITT

Total Total Ex- WR


Outside Exhaust Pressure E

supply Return filtration % % TH

Area Air Air Air T

Airflow Airflow Air O.A Press. OU

Req. (Cfm) (Cfm) TH

(Cfm) (Cfm)
WI
(Cfm) (Cfm)
NT
ME
CU
DO

Control & Relay


S

16,433 14,790 1,643 ----- 1,643 --- 10 10


THI
OM
Room FR
D
NE
BY C TAI
AJE OB

Using;
BE
ALL

% O.A = Outside Air x 100


SH
APRIL 2014

RT

Supply air
PA
DATE IN
OR
And; LL
FU

00 NO. % Press = Outside Air – Exhaust Air x 100 IN


N

REVISIONS Supply Air TIO


UC

DRAWN
Or OD
PR

% Press = Ex-filtration Air + Pressure Air x 100


RE
NO
BY: Md. Nayeemullah
Supply Air
CO.
Y
DATE: APRIL 2014
HVAC LOAD CALCULATION:
CIT
TRI

CHECKED
EC
EL

The load calculations is performed using HVAC software (Elite CHVAC SOFTWARE Ver.
UDI
BY: Muhammad Afzal SA

6.03.6 (window based) commercial HVAC Program) which employees ASHRAE CLTD / CLF
OF
DATE: APRIL 2014 TY

calculation’s method / guidelines. For calculating the Sub station’s cooling and heating load,
ER

OPRG. DEPT
OP

the building is divided into separate zone, keeping in view its orientation, purpose and load
PR
LE
BY SO
profiles. The load inputs (i.e. area, orientation, occupancy, equipment and light load etc.) are E
DATE:- TH
described in the “Zone Wise Data Sheets”. E

ENG'G. DEPT.
AR
N

BY:- The Calculation was performed using the above data on proportion supply Cfm basis. The REI
HE

DATE:-
load summary is given below. Detailed computer load output is attached. ED
AIN
NT

CERTIFIED. HVAC LOAD SUMMARY:


CO
N
TIO
BY:-
As per the load calculation, (Refer HVAC Load output sheets; Section: C)
MA
OR
DATE:-
INF
E

DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 13 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S

JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED

SEC-ERB CAD-E (2002/03)


WORD
D
RT'
CE
Saudi Electricity Company ‫الشركـة السعوديـة للكـهرباء‬
Western Region Branch
APPR'D

MA No. of Zones : 03
Safety factor : 10% (for both Latent & Sensible and Heating)
CHK'D

System type : Constant Volume


Load Peak Time : June @ 5PM
Supply Air Qty. : 16,433 Cfm
Outdoor Air Qty. : 1,643 Cfm
Total Cooling Load : 471,119 BTUH or 39.26 Tons
IISSUED FOR BASE DESIGN SUBMITTAL

N
O
TI
Total Sensible Load : 424,077 BTUH or 35.34 Tons
Total Heating Load : 58,087 BTUH or 17.02 kW
P
RI R.
C NE

Detailed computer load output is attached.


OW
S
ITS
E OF
D
HVAC EQUIPMENT SCHEDULE: T
EN
NS
CO

As per latest project Specification, each A/C’s Equipment should be selected 100% for the
EN
ITT
WR
maximum required capacity. One A/C unit shall be duty and other standby. E
TH
T
OU

Therefore each equipments Configuration is detailed below; (Refer HVAC Load output TH
WI

sheets; Section: C) NT
ME
CU
DO

For System No.1 (PACU-5A & PACU-5B)


S
THI
OM
FR

No. of Unit = 02 (01 Duty & 01 Standby)


D
NE
BY C TAI

Type of Unit = Packaged Type


AJE OB
BE
ALL
SH
Supply Air Qty. = 16,433 Cfm
APRIL 2014

RT
PA
DATE IN

Outdoor Air Qty. = 1,643 Cfm OR


LL
FU

00 NO. Entering D.B. = 80.72 °F IN


N
TIO
REVISIONS
Entering W.B. = 66.25 °F
UC
OD
DRAWN
PR

Leaving D.B. = 57.00 °F


RE
NO
BY: Md. Nayeemullah CO.

Leaving W.B. = 56.94 °F


Y
DATE: APRIL 2014 CIT
TRI

CHECKED
EC
Cooling Load = 39.36 Tr. (471,119 Btuh) EL
UDI
BY: Muhammad Afzal SA

DATE: APRIL 2014


Sensible Load = 35.34 Tr. (424,077 Btuh) OF
TY
ER

OPRG. DEPT Heating Load = 17.02 kW (58,087 Btuh) OP


PR
LE
BY SO
E
DATE:- TH

ENG'G. DEPT.
AIR BALANCING: E
AR
N
REI
BY:- HE
ED
DATE:-
AIN
NT

CERTIFIED.
CO
N
TIO
BY:- MA
OR
DATE:-
INF
E

DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 14 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S

JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED

SEC-ERB CAD-E (2002/03)


WORD
D
RT'
CE
Saudi Electricity Company ‫الشركـة السعوديـة للكـهرباء‬
Western Region Branch
APPR'D

MA
Sr. Supply Return Exhaust Press. Air Ex-filtration Room
Zone Description
CHK'D
No. Air Cfm Air Cfm Air Cfm Cfm Air Cfm Press.

1 Control & Relay Room 14,318 12,886 -- 1,432 -- +ve

Control & Relay Room


2 1,894 1,705 -- 189 -- +ve
(raised floor)
IISSUED FOR BASE DESIGN SUBMITTAL

N
O
TI ENT Lobby
3 220 198 -- 22 -- +ve
(Staircase # 02)
P
RI R.
C NE
OW
S
ITS
E OF
D
Total 16,433 14970 -- 1,643 --
T
EN
NS
CO
EN
ITT
WR
E
TH

Result Verification:
T
OU
TH
WI
NT

We have;
ME
CU
DO

Supply Air = 16,433 CFM


S
THI
OM
FR
Return Air = 14,970 CFM D
NE
BY C TAI
AJE
Exhaust Air = 0 CFM OB
BE
ALL

Pressure Air = 1,643 CFM


SH
APRIL 2014

RT
PA

Ex-filtration = 0 CFM
DATE IN
OR
LL

Now,
FU
IN
00 NO. N

Outdoor Air = Exhaust Air + Pressure Air + Ex-filtration


TIO
REVISIONS UC
OD
DRAWN
PR
RE
NO
BY: Md. Nayeemullah CO.

DATE: APRIL 2014 = 0 + 1,643 + 0 = 1,643 CFM Y


CIT
TRI

CHECKED
EC
EL
UDI
BY: Muhammad Afzal
Return Air = Supply Air – Outdoor Air
SA
OF
DATE: APRIL 2014 TY
ER

OPRG. DEPT
OP
PR

= 16,433 - 1,643 = 14,790 CFM


LE
BY SO
E
DATE:-
 O.K
TH
E

ENG'G. DEPT.
AR
N
REI
BY:-
FRESH AIR INTAKE (SAND TRAP LOUVER) SIZE:
HE
ED
DATE:-
AIN
NT

CERTIFIED.
CO

As per project HVAC Load calculation:


N
TIO
BY:- MA
OR
DATE:-
INF
E

DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 15 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S

JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED

SEC-ERB CAD-E (2002/03)


WORD
D
RT'
CE
Saudi Electricity Company ‫الشركـة السعوديـة للكـهرباء‬
Western Region Branch
APPR'D

MA Total Outside Air Quantity (Q) = 1,643 Cfm


CHK'D Qty of Sand trap louver = 01 No.

As per SEC Standard, the recommended velocity is 300 FPM

 A = Q
V

= 1,643
IISSUED FOR BASE DESIGN SUBMITTAL

N
300
O

= 5.48 ft²
TI
P
RI R.
C NE

From the manufacturer’s catalogue, the sand trap louver of size 48” in height by 54” wide
OW
S
ITS

gives a net free area of 5.54 ft². [Refer Attachment “E’]


E OF
D T


EN

Sand trap Louver Size = 48 inch x 54 inch (H x W)


NS
CO
EN
ITT
Qty of S.T.L = 01 No. per System WR
E
TH
T

Actual Sand Trap Louver Velocity = 1,643ft³/m


OU
TH

5.54ft²
WI
NT
ME

= 297 ft/m
CU
DO
S

Sand Trap Louver Efficiency = 38% (Refer Attachment “E”)


THI
OM
FR
D

BY C Sand Trap Louver Pressure Drop = 0.7” of W.G. (Refer Attachment “E”) NE
TAI
AJE OB
BE

Note: Selection of S.T.L is tentative based on the projects PTS, however final selection of ALL
SH
APRIL 2014

S.T.L shall be made by Equipment Manufacturer/Supplier and shall be included with RT


PA

the packaged unit material submittal.


DATE IN
OR
LL
FU
IN
00 NO. N

ELECTRIC DUCT HEATER SIZE:


TIO
REVISIONS UC
OD
DRAWN
PR
RE

BY: Md. Nayeemullah As per project HVAC Load calculation: NO


CO.
Y
DATE: APRIL 2014 CIT

Total Supply Air Quantity = 16,433 Cfm


TRI

CHECKED
EC

(From HVAC Load Calculation)


EL
UDI
BY: Muhammad Afzal SA
OF
DATE: APRIL 2014
Total Heating Calculated = 58,087 Btuh
TY
ER

OPRG. DEPT
(From HVAC Load Calculation)
OP
PR
LE
BY SO
E
DATE:- Hence the Heating Capacity in kW shall be; TH
E

ENG'G. DEPT.  = Total Heating Req. in Btuh AR


N

3413 Btu/ Hr. /kW


REI
BY:- HE
ED
DATE:-
AIN

= 58,087
NT

CERTIFIED.
CO

3413
N
TIO
BY:- MA
OR
DATE:-
INF
E

DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 16 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S

JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED

SEC-ERB CAD-E (2002/03)


WORD
D
RT'
CE
Saudi Electricity Company ‫الشركـة السعوديـة للكـهرباء‬
Western Region Branch
APPR'D

MA

CHK'D
= 17.02 kW

Duct Size; on location of E.D.H. is 1400mm X 650mm; hence the net free area available for
heater installation is;

Supply Duct Area = 1400mm X 650mm


= 56” X 26”
= 10.11 ft
IISSUED FOR BASE DESIGN SUBMITTAL

N
O Hence;
TI
P
kW / ft Ratio of EDH = 17.02 / 10.11
= 1.68 kW / ft
RI R.
C NE
OW
S
Therefore the recommended Duct Mounted Electric Heater rating shall be;
ITS
E OF
D T
EN
NS
CO

E.D.H. Recommended Size = 17.02 kW


EN
ITT
WR

Qty. of E.D.H = 01 No.


E
TH
T
OU
TH

ELECTRIC DATA OF DUCT MOUNTED HEATER: WI


NT
ME
CU

From the manufacturer’s catalogue DO


S
THI

The required line current for 3 phase = Wattage/ (Voltage x 1.73)


OM
FR
D

= 17,020/ (400 x 1.73)


NE
BY C TAI
AJE OB

= 24.60 Amps
BE
ALL
SH
APRIL 2014

Considered number of step control = 02 Nos.


RT
PA
DATE IN
OR
The ampere per step = 12.30 Amps LL
FU
IN
00 NO.
Hence, N
TIO
REVISIONS UC

DRAWN
EDH Criteria for Control & Relay Room Shall be; OD
PR
RE
NO
BY: Md. Nayeemullah
Total Wattage of E.D.H = 17.02 kW CO.
Y
DATE: APRIL 2014
No. of Steps = 02
CIT
TRI

CHECKED
No. Ampere/Step = 12.30 Amps
EC
EL
UDI
BY: Muhammad Afzal SA
OF
DATE: APRIL 2014 TY
ER

OPRG. DEPT BELL MOUTH OPENING SIZING: OP


PR
LE
BY
For sizing of Bell Mouth Opening, we take the maximum & minimum duct velocities as
SO
E
DATE:-
mentioned in Table-5.0 TES-K-100.01.
TH
E

ENG'G. DEPT.
AR
N
REI
BY:- 1) For BMO-1; HE
ED
DATE:-
AIN
NT

CERTIFIED. As per HVAC Load Calculation: CO


N
TIO
BY:-
Return Air Qty. for System # 01 in Control & Relay Room = 14,790 CFM
MA
OR
DATE:-
INF
E

DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 17 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S

JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED

SEC-ERB CAD-E (2002/03)


WORD
D
RT'
CE
Saudi Electricity Company ‫الشركـة السعوديـة للكـهرباء‬
Western Region Branch
APPR'D

MA

CHK'D
As per TES-K-100.01 the minimum velocity for main duct is 900 FPM.
Therefore;
 A = Q
V

= 14,790
900

= 16.43 ft²
IISSUED FOR BASE DESIGN SUBMITTAL

N
The required size of Bell Mouth Opening the area is 16.43 ft².
O
TI
P
The provided size of BMO is 1900 X 800mm (76” X 32”).
RI
A = LxH
R.
C NE
OW
S
ITS
E
D = 76” x 32” OF
T

= 2,432 inch²
EN
NS
CO
EN
= 16.88 ft² [
ITT
WR

Comparing the value of BMO size, the provided size is bigger than to required size. It means the
E
TH

size of BMO provided is suitable.


T
OU
TH
2) For BMO-2; WI
NT
ME
CU
As per HVAC Load Calculation: DO
S
THI

Supply Air Qty. for System # 01 in Control & Relay Room = 1,894 CFM OM
FR

(Raised Floor)
D
NE
BY C TAI
AJE OB

As per TES-K-100.01 the minimum velocity for Branch duct is 600 FPM.
BE
ALL
SH
Therefore;
APRIL 2014

RT
PA
 A = Q
DATE IN
OR

V LL
FU
IN
00 NO. N

REVISIONS = 1,894 TIO


UC

600 OD
DRAWN
PR
RE
NO
BY: Md. Nayeemullah
= 3.15 ft² CO.
Y
DATE: APRIL 2014
The required size of Bell Mouth Opening the area is 3.15 ft². CIT
TRI

CHECKED
EC

The provided size of BMO is 450 X 850mm (18 X 34”).


EL
UDI
BY: Muhammad Afzal SA
OF
DATE: APRIL 2014 A = LxH TY
ER

OPRG. DEPT
OP
= 18 x 34” PR
LE
BY SO
= 612 inch² E
DATE:- TH
E

ENG'G. DEPT. = 4.25 ft² [


AR
N
REI
BY:- Comparing the value of BMO size, the provided size is bigger than to required size. It means the HE
ED
DATE:- size of BMO provided is suitable. AIN
NT

CERTIFIED.
CO
N
TIO
BY:- MA
OR
DATE:-
INF
E

DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 18 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S

JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED

SEC-ERB CAD-E (2002/03)


WORD
D
RT'
CE
Saudi Electricity Company ‫الشركـة السعوديـة للكـهرباء‬
Western Region Branch
APPR'D

MA

CHK'D
IISSUED FOR BASE DESIGN SUBMITTAL

N
O
TI
P
RI R.
C NE
OW
S
ITS
E OF
D T
EN
NS
CO
EN
ITT
WR
E
TH
T
OU
TH
WI

SMOKE PURGE FAN SIZING: NT


ME
CU

For sizing of Smoke Purge Fan, we take the building air change to be 6 so that smoke laden air
DO
S

without any draught can be exhausted. For each packaged unit, separate smoke purge fans are
THI
OM

provided.
FR
D
NE
BY C TAI

1) Control & Relay Room:


AJE OB
BE
ALL
SH
APRIL 2014

RT

DATE Room dimensions are as follows; PA


IN
OR
LL
Length = l = 50.85 m FU
IN
00 NO.
Width = b = 23.23 m N
TIO
REVISIONS
Height = h = 3.70 m
UC
OD
DRAWN
Therefore;
PR
RE
NO
BY: Md. Nayeemullah CO.

Volume of conditioned space = 50.85 m x 23.23 m x 3.70 m


Y
DATE: APRIL 2014 CIT
TRI

CHECKED
= 4,371 m³ = 154,360 ft³
EC
EL
UDI
BY: Muhammad Afzal
No. of Air changes required = 6 Air change / Hr
SA
OF
DATE: APRIL 2014 TY
ER

OPRG. DEPT As per PTS Page no.62 (Refer Attachment: “F”) OP


PR
LE
BY Hence using; SO
E
DATE:- TH
E

ENG'G. DEPT. Exhaust Air = Volume of Space x Air Change / Hr AR


N

BY:-
60 REI
HE
= 154,360 x 6 ED
DATE:-
AIN
60 NT

CERTIFIED.
CO
N
TIO
BY:- = 15,436 CFM MA
OR
DATE:-
INF
E

DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 19 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S

JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED

SEC-ERB CAD-E (2002/03)


WORD
D
RT'
CE
Saudi Electricity Company ‫الشركـة السعوديـة للكـهرباء‬
Western Region Branch
APPR'D

MA

CHK'D
2) Control Relay (raised floor):

Room dimensions are as follows;

Length = l = 50.85 m
Width = b = 23.23 m
Height = h = 0.9 m
Therefore;
IISSUED FOR BASE DESIGN SUBMITTAL

N Volume of conditioned space = 50.85 m x 23.23 m x 0.9 m


O
TI = 1063 m³ = 37,539 ft³
P
RI
C No. of Air changes required = 6 Air change / Hr R.
NE
OW
S
ITS
E OF
D T

As per PTS Page no.62 (Refer Attachment: “F”) EN


NS
CO

Hence using; EN
ITT
WR
E

Exhaust Air = Volume of Space x Air Change / Hr TH


T

60 OU
TH

= 37,539 x 6 WI
NT

60 ME
CU
DO
S

= 3,754 CFM THI


OM
FR
D

3) ENT Lobby (Staircase # 02):


NE
BY C TAI
AJE OB
BE

Room dimensions are as follows;


ALL
SH
APRIL 2014

RT
PA

Length = l = 10.77 m
DATE IN
OR

Width = b = 4.20 m
LL
FU
IN
00 NO.
Height = h = 3.70 m N
TIO
REVISIONS Therefore; UC
OD
DRAWN
PR
RE

BY: Md. Nayeemullah Volume of conditioned space = 10.77 m x 4.20 m x 3.70 m NO


CO.
Y
DATE: APRIL 2014
= 167.36 m³ = 5,910 ft³ CIT
TRI

CHECKED
EC

No. of Air changes required = 6 Air change / Hr EL


UDI
BY: Muhammad Afzal SA
OF
DATE: APRIL 2014 TY
ER

OPRG. DEPT As per PTS Page no.62 (Refer Attachment: “F”) OP


PR
LE
BY
Hence using; SO
E
DATE:- TH
E

ENG'G. DEPT. Exhaust Air = Volume of Space x Air Change / Hr AR


N

BY:- 60 REI
HE
ED
DATE:-
AIN

= 5,910 x 6 NT

CERTIFIED.
CO

60 N
TIO
BY:- MA
OR
DATE:-
INF
E

DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 20 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S

JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED

SEC-ERB CAD-E (2002/03)


WORD
D
RT'
CE
Saudi Electricity Company ‫الشركـة السعوديـة للكـهرباء‬
Western Region Branch
APPR'D

MA = 591 CFM
CHK'D

Total Exhaust Air CFM = 15,436 + 3,574 + 591

= 19,601 CFM

As per Smoke Purge Fan calculation:


IISSUED FOR BASE DESIGN SUBMITTAL

Taking;
O
TI
P
RI R.
C NE
S Smoke Purge Exhaust Air = 19,601 CFM OW
ITS
E OF

Qty. of Smoke Purge Fan = 01 No.


D T
EN
NS
CO
EN
ITT
WR
E
TH
T
OU
TH
WI
NT
ME
CU
DO
S
THI
OM
FR
D
NE
BY C TAI
AJE OB
BE
ALL
SH
APRIL 2014

RT
PA
DATE IN
OR
LL
FU
IN
00 NO. N
TIO
REVISIONS UC
OD
DRAWN
PR
RE
NO
BY: Md. Nayeemullah CO.
Y
DATE: APRIL 2014 CIT
TRI

CHECKED
EC
EL
UDI
BY: Muhammad Afzal SA
OF
DATE: APRIL 2014 TY
ER

OPRG. DEPT
OP
PR
LE
BY SO
E
DATE:- TH
E

ENG'G. DEPT.
AR
N
REI
BY:- HE
ED
DATE:-
AIN
NT

CERTIFIED.
CO
N
TIO
BY:- MA
OR
DATE:-
INF
E

DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 21 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S

JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED

SEC-ERB CAD-E (2002/03)


WORD

Вам также может понравиться