Академический Документы
Профессиональный Документы
Культура Документы
RT'
CE
Saudi Electricity Company الشركـة السعوديـة للكـهرباء
Western Region Branch
APPR'D
CHK'D
MA
HVAC LOAD CALCULATION
HVAC SYSTEM SOW DESCRIPTION:
The construction of Al Adel 380/110/13.8kV BSP Substation is planned in order to meet the
growing power demand of the Area. The Scope of Work in term of “Mechanical (HVAC)”
Providing new and independent HVAC facilities along with all necessary ductwork and
control system for the following Buildings;
IISSUED FOR BASE DESIGN SUBMITTAL
independent with 100% Standby facilities. For the 380kV GIS Building, 110kV GIS Building, ITT
WR
Control Building & 13.8kV Switchgear Building packaged type Direct Expansion units (PACU) E
TH
shall be used, as per the Project’s Technical Specification (PTS-11WN355). Each PACU unit
T
OU
is selected at 100% of zone(s) load; therefore, each zone(s) had 100% standby capacity.
TH
WI
That means each unit of the pair runs independently of the other and can fulfill the
NT
ME
BY C provided. NE
TAI
OB
Ventilation System will be provided for the following zones as per PTS-11WN355;
AJE
BE
ALL
SH
APRIL 2014
RT
CHECKED
EC
EL
OPRG. DEPT
OP
HVAC System design shall comply with the requirement of following Standards.
PR
LE
BY SO
E
DATE:- 1. Project scope of work/Technical specification (PTS-11WN355) TH
E
ENG'G. DEPT.
AR
DATE:-
3. SEC Construction Standard (TCS-K-100) ED
AIN
NT
CERTIFIED. 4. American Society of Heating, Refrigeration & Air conditioning Engineers (ASHRAE).
CO
N
TIO
BY:-
5. SMACNA for Design & Construction of Low Pressure Ducts.
MA
OR
DATE:-
INF
E
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 1 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S
JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED
For each building, two pairs of Packaged Type A/C units are used. Each pair of two units runs
independently controlled by their concerned zones / areas.
The Packaged A/C units are located outdoor the Substation and zones description are
mentioned below;
IISSUED FOR BASE DESIGN SUBMITTAL
As per Tender Layout Drawing # WT - 908465, Due to large size of 380kV GIS
RI R.
C NE
Building 02 set of Air-Conditioning Units shall be provided for 380kV GIS Building.
OW
S
ITS
E OF
D T
1st set of Air Conditioning unit (System # 01 consisting of PACU-1A & PACU-1B) and 2 nd
EN
NS
CO
set of Air Conditioning unit (System # 02 consisting of PACU-2A & PACU-2B) is used for EN
ITT
below mentioned zones; WR
E
•
TH
380kV GIS Room T
OU
TH
WI
• Store Room
NT
ME
CU
DO
As per Tender Layout Drawing # WT - 908465, Due to large size of 110kV GIS
BE
ALL
Building 02 set of Air-Conditioning Units shall be provided for 110kV GIS Building.
SH
APRIL 2014
RT
PA
DATE IN
1st set of Air Conditioning unit (System # 03 consisting of PACU-3A & PACU-3B) and 2 nd
OR
LL
FU
00 NO. set of Air Conditioning unit (System # 04 consisting of PACU-4A & PACU-4B) is used for IN
N
•
OD
DRAWN 110kV GIS Room PR
RE
NO
BY: Md. Nayeemullah CO.
•
Y
DATE: APRIL 2014 Cable Basement CIT
TRI
CHECKED
EC
EL
• Store Room
UDI
BY: Muhammad Afzal SA
OF
DATE: APRIL 2014 TY
OPRG. DEPT
OP
PR
Control Building:
LE
BY SO
E
DATE:- TH
As per Tender Layout Drawing # WT - 908465, Due to large size of Control Building
E
ENG'G. DEPT.
AR
CERTIFIED.
CO
below mentioned zones; N
TIO
BY:- MA
OR
DATE:-
INF
E
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 2 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S
JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED
1st set of Air Conditioning unit (System # 07 consisting of PACU-7A & PACU-7B) is used for
E OF
D T
•
CO
•
TH
Cable Basement
T
OU
TH
WI
Return/Re-circulated air (MVD) along with Outdoor air (VD) Damper. These Dampers control
ALL
SH
APRIL 2014
and regulate the airflow rates under different load conditions. Separate ducting from each
RT
PA
Unit of the pair combines into one common ducting (sized for 100% of Supply air from single
DATE IN
OR
Unit). The supply air is ducted while the return air is free. The volume damper for supply air
LL
FU
is motorized while the other volume dampers are manually operated. The duct smoke
IN
00 NO. N
BY: Md. Nayeemullah The Fresh Air or Outdoor Air is supplied through the Sand Trap Louver with Wire Mesh NO
CO.
DATE: APRIL 2014 Screen & Aluminum filter. The Fresh Air intake from the Sand Trap Louver arrangement is Y
CIT
CHECKED
connected to the openings provided in PACU unit. TRI
EC
EL
UDI
BY: Muhammad Afzal
If the PACU Unit is not running i.e. in standby mode, then all the Motorized volume control
SA
OF
DATE: APRIL 2014
dampers (MVD) is in closed position. For the Duty Unit, the Supply Dampers (MVD) is fully
TY
ER
OPRG. DEPT opened; while Return Air damper (MVD) is also operating respectively and Outdoor Air
OP
PR
Damper (MVD) is set at minimum open position. The minimum open position for Outdoor Air
LE
BY SO
E
DATE:- Damper is that which provides the minimum Flow Rate of Outdoor Air required for ventilation TH
E
ENG'G. DEPT. and pressurization of zones and maintains a +ve pressure of 0.2” of W.G. AR
N
REI
BY:- HE
DATE:-
The Duty & standby units will operate on a shift basis. The changeover from duty to standby ED
AIN
CERTIFIED.
CO
N
TIO
BY:- MA
OR
DATE:-
INF
E
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 3 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S
JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED
MA In “Automatic” mode, the Changeover from duty to Standby unit is either on the Time Basis
CHK'D
or due to failure of running unit. The time Basis changeover can be set from one day to one
week, as required. The 7-day per week – 24 hour per day timer shall take care of scheduling
the operation of the two units in order to make sure that the two Units works equally. Also in
case of failure of the running PACU unit due to any reason, then the operation shall be
transferred automatically to the standby PACU unit. “Manually” the changeover can be
activated any time from the HVAC Control Panel.
The temperature controller (or Thermostat) will decide whether cooling or heating is required
or not, by comparing the set-point with actual space temperature, If cooling is required then
IISSUED FOR BASE DESIGN SUBMITTAL
The Temperature controls shall be provided as part of the AC unit by the Control Panel
OW
S
ITS
E OF
D
Supplier/Installer. The Thermostat shall be cooling and heating type with a minimum of 2 T
EN
stages of Mechanical Cooling / Heating. The Thermostat shall be mounted on the return air NS
CO
stream @ 1.5M above F.F.L. The Thermostat shall be provided with lockable transparent EN
ITT
cover. WR
E
TH
T
OU
TH
In case the Smoke Detector installed at the common Supply and Return air Ducts detects
S
THI
smoke or the FACP sends a signal indicating smoke presence, then the Duty Packaged unit
OM
FR
shall be automatically de-energized and all temperature control function shall stop. At such
D
NE
During the Smoke purge operation all PACU’s (Duty and standby) dampers (Supply and
SH
APRIL 2014
RT
PA
DATE
Return air) will be closed and smoke purge / exhaust damper and Return Opening MF/SD IN
OR
will be opened fully to clear the smoke and product of combustion from the concerned zone. LL
FU
00 NO. Smoke Purge Fan operates during smoke purging operation i.e. to exhaust smoke from the IN
N
REVISIONS zones in the event of fire or heavy smoke conditions. It should be possible to manually run TIO
UC
the Smoke Purge Fan either from the HVAC Control Panel or from Smoke Purge Fan
OD
DRAWN
PR
isolating switch or from Remote Selector Switch located outside near the main door of
RE
NO
BY: Md. Nayeemullah
Control Room.
CO.
Y
DATE: APRIL 2014 CIT
TRI
CHECKED
After the smoke purging operation ends, it would only be possible to re-start the Air
EC
EL
UDI
BY: Muhammad Afzal Conditioning units by re-setting the HVAC Control Panel. SA
OF
DATE: APRIL 2014 TY
ER
OPRG. DEPT
OP
PR
ENG'G. DEPT. For calculating air-conditioning load of Al Adel 380/110/13.8kV BSP Substation, reference is AR
N
BY:- taken from Project Technical Specification (PTS-11WN355) and other inputs / data are REI
HE
DATE:-
adopted from ASHRAE standards or SEC Engineering Standards. ED
AIN
NT
CERTIFIED.
CO
N
TIO
BY:- MA
OR
DATE:-
INF
E
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 4 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S
JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED
MA
CHK'D
Winter zones.
EN
NS
temperature CO
EN
ITT
WR
E
Refer Attachment: “1” for the “Cooling Design Conditions” for Jeddah. We had taken the
TH
T
ambient dry bulb condition & ambient wet bulb condition as per PTS-11WN355.
OU
TH
WI
NT
ME
CU
DO
SITE INFORMATION: S
THI
OM
FR
The site conditions adopted for Load calculation are given below;
D
NE
BY C TAI
AJE OB
BE
ALL
RT
PA
DATE IN
Location Jeddah
OR
LL
FU
21.51 (North)
IN
00 NO.
Latitude N
TIO
REVISIONS UC
Longitude 39.13 (East) OD
DRAWN
PR
RE
CHECKED
EC
Wind Direction
OF
DATE: APRIL 2014 North TY
ER
OPRG. DEPT
Required building pressurization
OP
DATE:-
zone except Battery Room, which is to be E
TH
E
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 5 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S
JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED
MA
CHK'D
The HVAC load is calculated on the “zone basis” .The variable load inputs for each zone is
described below:
IISSUED FOR BASE DESIGN SUBMITTAL
orientation.
OW
S
ITS
E OF
D T
are extracted from ASHRAE GRP 158, cooling and heating load calculation manual, Table TH
T
3.1A unless otherwise noted. For detail U-value calculation, refer Attachment: “A” (Co- OU
TH
WI
Building Element ME
RT
efficient of Heat Transmission Calculation: 7 pages). The U-Values adopted for different FU
IN
00 NO.
Architectural elements of Al Adel 380/110/13.8kV BSP Substation is summarized below.
N
TIO
REVISIONS UC
OD
DRAWN
PR
RE
NO
BY: Md. Nayeemullah CO.
Y
DATE: APRIL 2014 CIT
TRI
CHECKED
EC
EL
UDI
BY: Muhammad Afzal SA
OF
DATE: APRIL 2014 TY
ER
OPRG. DEPT
OP
PR
LE
BY SO
E
DATE:- TH
E
ENG'G. DEPT. (Based on the actual Insulation U-Value and SEC Approved R-Value data)
AR
N
REI
BY:- HE
Please note that only Control Room, Communication Room, Conference Room, Relay Test
ED
DATE:-
AIN
NT
CERTIFIED. Room, Office, Fire Fighting Room, Corridor & Toilet are provided with False Ceiling while CO
N
TIO
BY:- MA
OR
DATE:-
INF
E
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 6 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S
JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED
MA 380kV GIS Room, 110kV GIS Room, 13.8kV Switchgear Room, Auxiliary Room, Store
CHK'D
Room’s, Cable Basement & Battery Room are without False Ceiling.
Keeping with the Technical specification and SEC requirements the complete building is to
be Air-conditioned, under this SOW.
For determining the HVAC load, the Building is divided into 02 separate zones, keeping in
IISSUED FOR BASE DESIGN SUBMITTAL
N
O
view its orientation, purpose, and load profile.
TI
The operation hours for the A/C zones are 24 Hours. Therefore, equipment is to be run
P
RI R.
continuously.
C NE
OW
S
ITS
E OF
D
OCCUPANCY LOAD:
T
EN
NS
CO
EN
The Substation is of unmanned type; but occupancy is considered in Control Room. This can ITT
WR
be considered as “office space”. As per ASHRAE’s Table for “Rates of Heat gain from E
TH
occupants of conditioned spaces”, for standing; light work, walking, rate of heat gain are;
T
OU
TH
WI
QPS = NP x 250
RT
PA
DATE IN
QPL = NP x 200
OR
LL
FU
Where
IN
00 NO. N
CHECKED
EC
EL
OPRG. DEPT
OP
PR
BY
Sr. No. Zone / Room Occupancy LE
SO
E
DATE:- TH
E
CERTIFIED. Nil CO
N
TIO
BY:- MA
OR
DATE:-
INF
E
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 7 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S
JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED
MA
The Lightings load in each air-conditioned room is taken from actual Lighting Calculation, as
adopted in the Detail Electrical Design.
The following equation will be used to calculate the heat dissipation from Light Fixtures in
individual rooms / zones;
QLIG. = 3.41 X W X FU X FS
(Refer ASHRAE Fundamental 1997)
IISSUED FOR BASE DESIGN SUBMITTAL
N Where;
QLIG. = Sensible Heat Gain from Light Fixtures (Btu/Hr)
O
TI
P
RI
C W = Total Wattage of Light Fixtures R.
NE
OW
S
FU = Light Fixtures Usage Factor = 1.0
ITS
E OF
D T
We have;
EN
ITT
WR
Lighting Heat D
NE
(Watts)
BE
ALL
SH
APRIL 2014
DATE 12,715 PA
IN
Nil
LL
FU
IN
00 NO.
3 ENT lobby (Staircase # 02) 500
N
TIO
REVISIONS UC
OD
DRAWN For lighting load in each room, refer Table: “Heat Dissipation Detail” (Refer Attachment: “C”). PR
RE
NO
BY: Md. Nayeemullah CO.
EQUIPMENT LOAD:
Y
DATE: APRIL 2014 CIT
TRI
CHECKED
EC
For Equipment Heat Dissipation, the reference is taken from “Equipment Layout”. Equipment
EL
UDI
BY: Muhammad Afzal SA
OPRG. DEPT
OP
projects. In either case the reference is provided for the data adopted for Equipment’s heat PR
LE
BY
dissipation. Refer Attachment: “D“, for Heat dissipation data adopted with panel details. SO
E
DATE:- TH
E
ENG'G. DEPT. Following values are taken for equipment heat dissipation in different rooms. AR
N
REI
BY:- HE
ED
DATE:- Equipment Heat AIN
51,512
OR
DATE:-
INF
JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED
MA
CHK'D
N
O
TI As per SEC Standard, it is necessary to provide a slight positive internal pressure for
keeping the outdoor dust borne air out and also for proper zone pressurization. For
P
RI R.
calculating the Outdoor or Fresh air quantity, we need to calculate the Exhaust,
C NE
OW
S
Pressurization and Ex-filtration air quantity respectively and then we will calculate the total
ITS
E OF
D
outdoor air quantity based on the criteria set by SEC Standards.
T
EN
NS
For calculating the Building pressurization / ex-filtration air quantity, we have; CO
EN
Site max outdoor temperature = 49ºC = 120ºF ITT
WR
Outdoor wind velocity = 37 kph = 23 mph E
TH
RT
PA
Pw = C 1 C p V2
DATE IN
OR
2
LL
FU
Where;
TIO
REVISIONS UC
CHECKED
EC
OPRG. DEPT Cp is a function of location on building envelope and wind direction. For undisturbed surface
OP
PR
ENG'G. DEPT.
AR
N
DATE:-
2 ED
AIN
NT
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 9 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S
JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED
PI = PS PO
EN
+ NS
Where;
CO
EN
ITT
WR
Therefore; DO
S
THI
OM
PI = 0.2// + 0.2//
FR
D
= 0.4// of W.G
NE
BY C TAI
AJE OB
BE
Hence inside required pressure on the building is 0.4// of W.G ALL
SH
APRIL 2014
RT
PA
DATE IN
CHECKED
EC
EL
AL
ER
OPRG. DEPT
= (Ref: ASHRAE
0.0150 Cfm2Fundamental;
/ in4.0F Chap: 25) OP
PR
LE
BY (Refer ASHRAE Fundamentals 2009, Ch. 16, Table: 4) SO
E
DATE:- Cw = Wind Co-efficient (Cfm2 / in4. Mph2)
TH
E
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 10 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S
JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED
MA = 77.0 – 120 = - 43 0F
CHK'D V = Average wind velocity = 23 mph
Putting the values;
N
O
Qx = 2.377 X AL (Cfm)
TI
P
RI R.
Where;
C NE
OW
S
ITS
AL = Effective Air leakage area, (in2 / ft 2)
E OF
D T
Air leakage can take place through doors, windows, crawl space etc; for the Control & Relay EN
NS
Building air leakage can only take place through the doors opening outside the building. CO
EN
ITT
WR
Using;
E
TH
Where;
NT
ME
CU
AL = Effective Air leakage area. DO
S
AD = Area of door opening outside. THI
OM
DL = Air leakage through door FR
D
RT
For the zones / rooms in the HVAC system, the outdoors is located in the Control & Relay
PA
DATE IN
Room.
OR
LL
FU
IN
00 NO. N
REVISIONS
For Substation building different sizes of outward doors used the detail of which are as TIO
UC
follows; OD
DRAWN
PR
RE
NO
BY: Md. Nayeemullah
Since there is no door directly exposed to ambient for Control & Relay Room, the Ex- CO.
Y
DATE: APRIL 2014
Filtration Air for this zone will be considered as nil.
CIT
TRI
CHECKED
EC
EL
UDI
BY: Muhammad Afzal
Qx = 0 Cfm SA
OF
DATE: APRIL 2014 TY
ER
OPRG. DEPT
OP
PR
From Air conditioned spaces Al Adel Control & Relay Room have no any exhaust air.
E
ENG'G. DEPT.
AR
N
REI
BY:-
HE
Qexh = 0 Cfm ED
DATE:-
AIN
NT
CERTIFIED.
CO
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 11 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S
JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED
MA Now
CHK'D (B) QP = 0 + (0.1/0.3)0+ (0.1/0.3) 0 + 0
= 0+0+0+0
Taking;
QP = 0 Cfm
IISSUED FOR BASE DESIGN SUBMITTAL
N
O
TI
P
RI R.
C NE
OW
S
ITS
E OF
D T
EN
NS
G.) Estimating Outdoor Air Quantity Air : CO
EN
ITT
WR
and other duct sensitive facility, it is mandatory to provide 10% of supply air
T
OU
fresh air make up. Therefore 10% of the supply air for the fresh air make up
TH
WI
is 1,643 CFM (For supply air quantity Refer cooling Load (CHVAC) Output
NT
ME
sheets; section: C)
CU
DO
S
THI
BY C air shall equal the greater of 5% of supply air in excess of all exhaust air. NE
TAI
AJE Therefore 5% of total supply air is 822 CFM plus exhaust and ex-filtration air, OB
BE
RT
PA
Comparing the values, the higher value of 1,643 CFM is considered as per Section10.2
DATE IN
OR
LL
FU
Hence;
IN
00 NO. N
TIO
REVISIONS UC
CHECKED
EC
EL
UDI
BY: Muhammad Afzal SA
OF
DATE: APRIL 2014 TY
ER
OPRG. DEPT
OP
PR
LE
BY SO
E
DATE:- TH
E
ENG'G. DEPT.
AR
N
REI
BY:- HE
ED
DATE:-
AIN
NT
CERTIFIED.
CO
N
TIO
BY:- MA
OR
DATE:-
INF
E
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 12 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S
JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED
MA
CHK'D
IISSUED FOR BASE DESIGN SUBMITTAL
N
O
TI
P
RI R.
C NE
OW
S
ITS
E OF
D T
H.) SUMMARY: EN
NS
CO
EN
Total ITT
(Cfm) (Cfm)
WI
(Cfm) (Cfm)
NT
ME
CU
DO
Using;
BE
ALL
RT
Supply air
PA
DATE IN
OR
And; LL
FU
DRAWN
Or OD
PR
CHECKED
EC
EL
The load calculations is performed using HVAC software (Elite CHVAC SOFTWARE Ver.
UDI
BY: Muhammad Afzal SA
6.03.6 (window based) commercial HVAC Program) which employees ASHRAE CLTD / CLF
OF
DATE: APRIL 2014 TY
calculation’s method / guidelines. For calculating the Sub station’s cooling and heating load,
ER
OPRG. DEPT
OP
the building is divided into separate zone, keeping in view its orientation, purpose and load
PR
LE
BY SO
profiles. The load inputs (i.e. area, orientation, occupancy, equipment and light load etc.) are E
DATE:- TH
described in the “Zone Wise Data Sheets”. E
ENG'G. DEPT.
AR
N
BY:- The Calculation was performed using the above data on proportion supply Cfm basis. The REI
HE
DATE:-
load summary is given below. Detailed computer load output is attached. ED
AIN
NT
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 13 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S
JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED
MA No. of Zones : 03
Safety factor : 10% (for both Latent & Sensible and Heating)
CHK'D
N
O
TI
Total Sensible Load : 424,077 BTUH or 35.34 Tons
Total Heating Load : 58,087 BTUH or 17.02 kW
P
RI R.
C NE
As per latest project Specification, each A/C’s Equipment should be selected 100% for the
EN
ITT
WR
maximum required capacity. One A/C unit shall be duty and other standby. E
TH
T
OU
Therefore each equipments Configuration is detailed below; (Refer HVAC Load output TH
WI
sheets; Section: C) NT
ME
CU
DO
RT
PA
DATE IN
CHECKED
EC
Cooling Load = 39.36 Tr. (471,119 Btuh) EL
UDI
BY: Muhammad Afzal SA
ENG'G. DEPT.
AIR BALANCING: E
AR
N
REI
BY:- HE
ED
DATE:-
AIN
NT
CERTIFIED.
CO
N
TIO
BY:- MA
OR
DATE:-
INF
E
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 14 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S
JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED
MA
Sr. Supply Return Exhaust Press. Air Ex-filtration Room
Zone Description
CHK'D
No. Air Cfm Air Cfm Air Cfm Cfm Air Cfm Press.
N
O
TI ENT Lobby
3 220 198 -- 22 -- +ve
(Staircase # 02)
P
RI R.
C NE
OW
S
ITS
E OF
D
Total 16,433 14970 -- 1,643 --
T
EN
NS
CO
EN
ITT
WR
E
TH
Result Verification:
T
OU
TH
WI
NT
We have;
ME
CU
DO
RT
PA
Ex-filtration = 0 CFM
DATE IN
OR
LL
Now,
FU
IN
00 NO. N
CHECKED
EC
EL
UDI
BY: Muhammad Afzal
Return Air = Supply Air – Outdoor Air
SA
OF
DATE: APRIL 2014 TY
ER
OPRG. DEPT
OP
PR
ENG'G. DEPT.
AR
N
REI
BY:-
FRESH AIR INTAKE (SAND TRAP LOUVER) SIZE:
HE
ED
DATE:-
AIN
NT
CERTIFIED.
CO
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 15 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S
JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED
A = Q
V
= 1,643
IISSUED FOR BASE DESIGN SUBMITTAL
N
300
O
= 5.48 ft²
TI
P
RI R.
C NE
From the manufacturer’s catalogue, the sand trap louver of size 48” in height by 54” wide
OW
S
ITS
EN
5.54ft²
WI
NT
ME
= 297 ft/m
CU
DO
S
BY C Sand Trap Louver Pressure Drop = 0.7” of W.G. (Refer Attachment “E”) NE
TAI
AJE OB
BE
Note: Selection of S.T.L is tentative based on the projects PTS, however final selection of ALL
SH
APRIL 2014
CHECKED
EC
OPRG. DEPT
(From HVAC Load Calculation)
OP
PR
LE
BY SO
E
DATE:- Hence the Heating Capacity in kW shall be; TH
E
= 58,087
NT
CERTIFIED.
CO
3413
N
TIO
BY:- MA
OR
DATE:-
INF
E
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 16 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S
JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED
MA
CHK'D
= 17.02 kW
Duct Size; on location of E.D.H. is 1400mm X 650mm; hence the net free area available for
heater installation is;
N
O Hence;
TI
P
kW / ft Ratio of EDH = 17.02 / 10.11
= 1.68 kW / ft
RI R.
C NE
OW
S
Therefore the recommended Duct Mounted Electric Heater rating shall be;
ITS
E OF
D T
EN
NS
CO
= 24.60 Amps
BE
ALL
SH
APRIL 2014
DRAWN
EDH Criteria for Control & Relay Room Shall be; OD
PR
RE
NO
BY: Md. Nayeemullah
Total Wattage of E.D.H = 17.02 kW CO.
Y
DATE: APRIL 2014
No. of Steps = 02
CIT
TRI
CHECKED
No. Ampere/Step = 12.30 Amps
EC
EL
UDI
BY: Muhammad Afzal SA
OF
DATE: APRIL 2014 TY
ER
ENG'G. DEPT.
AR
N
REI
BY:- 1) For BMO-1; HE
ED
DATE:-
AIN
NT
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 17 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S
JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED
MA
CHK'D
As per TES-K-100.01 the minimum velocity for main duct is 900 FPM.
Therefore;
A = Q
V
= 14,790
900
= 16.43 ft²
IISSUED FOR BASE DESIGN SUBMITTAL
N
The required size of Bell Mouth Opening the area is 16.43 ft².
O
TI
P
The provided size of BMO is 1900 X 800mm (76” X 32”).
RI
A = LxH
R.
C NE
OW
S
ITS
E
D = 76” x 32” OF
T
= 2,432 inch²
EN
NS
CO
EN
= 16.88 ft² [
ITT
WR
Comparing the value of BMO size, the provided size is bigger than to required size. It means the
E
TH
Supply Air Qty. for System # 01 in Control & Relay Room = 1,894 CFM OM
FR
(Raised Floor)
D
NE
BY C TAI
AJE OB
As per TES-K-100.01 the minimum velocity for Branch duct is 600 FPM.
BE
ALL
SH
Therefore;
APRIL 2014
RT
PA
A = Q
DATE IN
OR
V LL
FU
IN
00 NO. N
600 OD
DRAWN
PR
RE
NO
BY: Md. Nayeemullah
= 3.15 ft² CO.
Y
DATE: APRIL 2014
The required size of Bell Mouth Opening the area is 3.15 ft². CIT
TRI
CHECKED
EC
OPRG. DEPT
OP
= 18 x 34” PR
LE
BY SO
= 612 inch² E
DATE:- TH
E
CERTIFIED.
CO
N
TIO
BY:- MA
OR
DATE:-
INF
E
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 18 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S
JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED
MA
CHK'D
IISSUED FOR BASE DESIGN SUBMITTAL
N
O
TI
P
RI R.
C NE
OW
S
ITS
E OF
D T
EN
NS
CO
EN
ITT
WR
E
TH
T
OU
TH
WI
For sizing of Smoke Purge Fan, we take the building air change to be 6 so that smoke laden air
DO
S
without any draught can be exhausted. For each packaged unit, separate smoke purge fans are
THI
OM
provided.
FR
D
NE
BY C TAI
RT
CHECKED
= 4,371 m³ = 154,360 ft³
EC
EL
UDI
BY: Muhammad Afzal
No. of Air changes required = 6 Air change / Hr
SA
OF
DATE: APRIL 2014 TY
ER
BY:-
60 REI
HE
= 154,360 x 6 ED
DATE:-
AIN
60 NT
CERTIFIED.
CO
N
TIO
BY:- = 15,436 CFM MA
OR
DATE:-
INF
E
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 19 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S
JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED
MA
CHK'D
2) Control Relay (raised floor):
Length = l = 50.85 m
Width = b = 23.23 m
Height = h = 0.9 m
Therefore;
IISSUED FOR BASE DESIGN SUBMITTAL
Hence using; EN
ITT
WR
E
60 OU
TH
= 37,539 x 6 WI
NT
60 ME
CU
DO
S
RT
PA
Length = l = 10.77 m
DATE IN
OR
Width = b = 4.20 m
LL
FU
IN
00 NO.
Height = h = 3.70 m N
TIO
REVISIONS Therefore; UC
OD
DRAWN
PR
RE
CHECKED
EC
BY:- 60 REI
HE
ED
DATE:-
AIN
= 5,910 x 6 NT
CERTIFIED.
CO
60 N
TIO
BY:- MA
OR
DATE:-
INF
E
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 20 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S
JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED
MA = 591 CFM
CHK'D
= 19,601 CFM
Taking;
O
TI
P
RI R.
C NE
S Smoke Purge Exhaust Air = 19,601 CFM OW
ITS
E OF
RT
PA
DATE IN
OR
LL
FU
IN
00 NO. N
TIO
REVISIONS UC
OD
DRAWN
PR
RE
NO
BY: Md. Nayeemullah CO.
Y
DATE: APRIL 2014 CIT
TRI
CHECKED
EC
EL
UDI
BY: Muhammad Afzal SA
OF
DATE: APRIL 2014 TY
ER
OPRG. DEPT
OP
PR
LE
BY SO
E
DATE:- TH
E
ENG'G. DEPT.
AR
N
REI
BY:- HE
ED
DATE:-
AIN
NT
CERTIFIED.
CO
N
TIO
BY:- MA
OR
DATE:-
INF
E
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TH
THIS DRAWING IS NOT D
TO BE USED FOR
HVAC SYSTEM DESIGN CALCULATION AN
CONSTRUCTION OF
FOR ORDERING CONTROL BUILDING @SYSTEM # 01 A JD526 WE - 254756 Page 21 of 21 00
ING
AW
MATERIALS UNTIL
DR
CERTIFIED AND
AL ADEL 380/110/13.8kV BSP S
JEDDAH SAUDI ARABIA JOB ORDER NO. 4400001340 DWG. CONT. SHT. WE - 254702
THI
DATED