Вы находитесь на странице: 1из 31

User Manual

用户手册

Cabinet Air Conditioner


机柜空调器

Shenzhen Envicool Technology Co., Ltd.

深圳市英维克科技股份有限公司
Shenzhen Envicool Technology Co., Ltd.
CONTENTS
1 DESCRIPTION........................................................................................ 1
1.1 PREFACE......................................................................................................................................................... 1
1.2 OPERATION PRINCIPLE....................................................................................................................................1
1.3 APPLIED STANDARD........................................................................................................................................2

2 INSTALLATION AND OPERATION.................................................. 3


2.1 UNPACKING AND INSPECTION.........................................................................................................................3
2.2 PREPARATIONS................................................................................................................................................3
2.3 INSTALLATION.................................................................................................................................................3
2.4 ELECTRICAL CONNECTION.............................................................................................................................. 5
2.5 CHECKLIST......................................................................................................................................................6
2.6 START-UP........................................................................................................................................................ 7

3. FUNCTION..............................................................................................8
3.1 DESCRIPTION...................................................................................................................................................8
3.2 COOLING......................................................................................................................................................... 8
3.3 HEATING(OPTIONAL).......................................................................................................................................8
3.3 EXTERNAL FAN (OPTIONAL)............................................................................................................................8
3.3 TESTING.........................................................................................................................................................10
3.4 ALARM.......................................................................................................................................................... 10
3.5 MONITORING................................................................................................................................................. 11
3.6 CONTROLLER.................................................................................................................................................11

4 TECHNICAL PARAMETER............................................................... 13

5 MAINTENANCE................................................................................... 14
深圳市英维克科技股份有限公司

目 录

1 简介......................................................................................................... 15
1.1 前言............................................................................................................................................................. 15
1.2 空调器描述.................................................................................................................................................. 15
1.3 符合标准..................................................................................................................................................... 16

2 安装和操作............................................................................................. 17
2.1 拆除包装和检验......................................................................................................................................... 17
2.2 安装前准备.................................................................................................................................................. 17
2.3 空调器机械安装......................................................................................................................................... 17
2.4 电气安装..................................................................................................................................................... 18
2.5 安装查检表.................................................................................................................................................. 20
2.6 开机步骤..................................................................................................................................................... 20

3 系统功能介绍......................................................................................... 21
3.1 功能............................................................................................................................................................. 21
3.2 制冷............................................................................................................................................................. 21
3.3 加热(选配).................................................................................................................................................21
3.4 外部风扇(选配)..................................................................................................................................... 21
3.5 自测............................................................................................................................................................. 22
3.6 故障............................................................................................................................................................. 23
3.7 监控............................................................................................................................................................. 23
3.8 菜单结构..................................................................................................................................................... 24

4 技术参数................................................................................................. 26

5 日常维护................................................................................................. 27
Shenzhen Envicool Technology Co., Ltd.

1 Description

1.1 Preface

Note:Any operation should be performed by professionally qualified personnel.


The information contained in this manual is used for correct handling, installation,
management and day-to-day maintenances of the air conditioner.

1.2 Operation Principle

The EC series air conditioner for the outdoor cabinet is a kind of cooling product developed
for cabinets. It is applicable for the scenarios where internal equipment of the cabinet emits a
large quantity of heat and is sensitive to the environment temperature and where the indoor
environment needs to be isolated from the outdoor environment completely. This product has full
functions, integrating external fan control and external air conditioner interlocking functions. It
features high reliability and easy installation and can work immediately upon power on, avoiding
complex adjustment.

The internal cycle air path absorbs hot air from the upside, and discharges cold air from the
downside of the air conditioner. The external cycle air path absorbs external cold air from the
downside, and discharges hot air from the upside after heat exchange. As shown in Fig.1.1.

Note: It is prohibited to put the air conditioner upside down during handling, storage and running.

Cabinet Ambient
Inner cycle

External cycle

Figure 1.1 Functional diagram

Cabinet Air Conditioner User Manual


1
Shenzhen Envicool Technology Co., Ltd.

Applied arrange:
Voltage Input range:
AC Input:220VAC±15% 50Hz
Ambient temperature range:-40℃~55℃

1.3 Applied Standard

Form 1.1 Applied Standards


Standard Standard Description
IEC61000-4 Electromagnetic Compatibility
IEC335-1 Safety requirement
IEC68-2 Environment condition-storage

IEC68-2 Environment condition-transportation

IEC68-2 Environment condition-use

Cabinet Air Conditioner User Manual


2
Shenzhen Envicool Technology Co., Ltd.

2 Installation and Operation

2.1 Unpacking and Inspection

The product uses standard carton package. To remove the package, remove the external
straps first, and then open the top cover and put out the carton. Please check the packing list
and accessory bags in the carton.

Note:

1. When the package is removed, make sure the air conditioner is placed vertically. It
cannot be placed horizontally or upside down.
2. When the external package is removed, please check carefully whether the
appearance of the air conditioner is damaged or stained with oil. If any damage is
found, please report this together with the bar code number on the package to the
retailer.
3. If the product is not to be installed immediately or it is required to transport the
product to another area, please repack the air conditioner after the check.
4. To protect the environment, it is recommended to recycle the packing cartons.

2.2 Preparations

Please pay attention to the following before the installation:

 While placing the environmental equipment in the cabinet, make sure that there is no
obstruction in the internal cycle air inlet and outlet of the air conditioner.

2.3 Installation

Installation of the air conditioner includes two parts:


 Stick the sealing materials on the air conditioning
 Fix the air conditioner on the cabinet
Tool list: Screwdriver.
Installation must be accordance with the following steps:

Cabinet Air Conditioner User Manual


3
Shenzhen Envicool Technology Co., Ltd.
1. There is enough room for any easy installation and maintenance both inside and
outside of the cabinet (ensure there are at lease 600mm space between any of the
unit’s surface to any of other fixed surface).
2. Check the accessories (Power lines, communication lines, mounting bolts, sealing
materials, user manual) and prepare the installation tools.
3. Seal the installation surface of the cooling units and the cabinet with sealing tapes
according to the designed sealing surface.
4. Fix the air conditioner on the installation surface of the cabinet firmly. As shown
in Fig. 2.1 and Fig. 2.2.
Mounting screws M5x12 Adhesive gasket
Air Conditioner Door

Figure 2.1 Schematic diagram for mechanical installation

Cabinet Air Conditioner User Manual


4
Shenzhen Envicool Technology Co., Ltd.
Figure 2.2 Size diagram for mounting hole

2.4 Electrical Connection

Installation include following work:


 connect the power input line
 connect the signal line
Note: Electrical service must perform by qualified person and conform to national
and local electrical codes. Before any operation, shut off the power input.
Refer to unit nameplate and technical parameters for wire size and circuit protection
requirements.
Strictly following the steps bellowing:
1. Check the power is shut off.
2. Connect the power line to the power input connector.
3. Connect the power input connector to the unit and fix it.
4. Connect the other end of power line to the corresponding air switch.
5. Connect the signal line to the signal line connector following the figure 2.4.
6. Check if the power input line is broken or short circuit.
7. Check if the signal input line is broken or short circuit.

 3PIN AC power input connector:


Connector Definition
L AC power input: L

N AC power input: N

PE AC power input: PE

Figure 2.3 Power input connector definition

 Monitoring /Alarm connector:

Cabinet Air Conditioner User Manual


5
Shenzhen Envicool Technology Co., Ltd.

Form2.1 RJ13 connector definition


Corresponding
Type Signal definition
base pin
NC The NC contact of the first public alarm dry contact output
COM The COM contact of the first public alarm dry contact output
The NO contact of the first public alarm dry contact output
Alarm output NO
output(optional)
1 The COM contact of the second public alarm dry contact output (optional)
2 The NO contact of the second public alarm dry contact output (optional)
3 External exhaust fan control output(optional)
4 External exhaust fan feedback input(optional)
5 The NO contact of the external exhaust fan control output (optional)
Alarm input The COM contact of the external exhaust fan control output
6
(optional)
7
The contact of door open alarm input (optional)
8
First-way RS485 interface D+ (upstream equipment monitoring
+
interface, Modbus protocol)
Communication
First-way RS485 interface D- (upstream equipment monitoring
-
interface, Modbus protocol)

 The wiring diagram of alarm input ports:

RS485
COM
NO

Screen printing :
NC

- + 1 2 3 4 5 6 7 8
COM

PWM

NC

COM
FG
NO

Annotation:
The first public
C ommunication ports
Rs485 通讯端口

alarm dry contact

第一路公共告警干接点

alarm dry contact


The second public

Door open alarm input


dry contact
The external fan
第二路公共告警干接点

门禁
外部 风扇 干接点

Figure 2.4 The wiring diagram of alarm input ports

2.5 Checklist

Before starting the unit, follow the checklist:


1. No obstacles near the air conditioner’s inner and external cycles.

Cabinet Air Conditioner User Manual


6
Shenzhen Envicool Technology Co., Ltd.
2. The air conditioner is vertically mounted and all the screws are tightened.
3. The power line and signal line is reliable fixed.
4. The voltage is conforming to the requirement listed in 1.2.
5. Fan turns smooth with no abnormal noise.

2.6 Start-Up

Turn on the power, the internal fan will run after standby within 30 seconds .If the
cabinet temperature is lower than the set-point, the unit’s inner fan will cause air recirculation
in the cabinet. If the cabinet temperature is higher than the set-point, the compressor will
start., and the external fan is controlled by the condensing pressure.

Cabinet Air Conditioner User Manual


7
Shenzhen Envicool Technology Co., Ltd.

3. Function

3.1 Description

The air conditioner is controlled by the controller inside the unit. It will adjust the
temperature inside the cabinet according to the set-point.

3.2 Cooling

Cooling On temperature = Cooling Off temperature + Sensitivity. When the cabinet


temperature is higher than the cooling on temperature, the compressor starts, when the
cabinet temperature is lower than the cooling off temperature, the compressor stops.
Form3.1 Cooling Parameter Setting

Parameters Default Value Setting Range Unit Description


Cooling Off Point 23 15-50 ℃ Point when cooling stops

Cooling Sensitivity 3 1-10 ℃ Temperature control sensitivity

Note: The actual parameters have been set upon delivery according to the customer’s requirement.

3.3 Heating(optional)

Heating startup point = heating stop point - heating sensitivity. When the temperature
inside the cabinet is lower than the heating startup point, the heating will start; when the
temperature inside the cabinet is higher than the heating stop point, the heating will stop.
Form3.2 Heating Parameter Setting

Parameters Default Value Setting Range Unit Description


15 -15-15 The temperature point of the
Heating stop point ℃
heating stop
5 1-10 The sensitivity of the temperature
Heater Sensitivity ℃
control
Note: The actual parameters have been set upon delivery according to the customer’s requirement.

3.3 External Fan (optional)

3.4.1 Hydrogen discharging fan

according to the requirement for the environment inside the cabinet, the hydrogen

Cabinet Air Conditioner User Manual


8
Shenzhen Envicool Technology Co., Ltd.
discharging fan realizes automatic cycle hydrogen discharging . The interval time of each
automatic cycle hydrogen discharging is 24 hours and the discharging time is 5 minutes.

3.4.2 Emergency fan

when the compressor does not have cooling capacity (including compressor failure,
power failure), the temperature inside the cabinet is higher than the startup point of
Emergency fan and the temperature inside the cabinet is 4ºC higher than that outside the
cabinet, start the Emergency fan.

3.4.3 Energy saving fan

When the temperature inside the cabinet is higher than the startup point of Energy
saving fan and the temperature inside the cabinet is 4ºC higher than that outside the cabinet,
start the Energy saving fan.

3.4.4 The wiring diagram of hydrogen discharging / emergency/ energy saving fan

Note: The max capacity of the hydrogen discharging / emergency/ energy saving fan’s dry contact: AC fan:
8A/ 230V;DC fan: 2A /48V.

Figure 3.1 The wiring diagram of AC hydrogen discharging /


emergency/ energy saving fan

Figure 3.2 The wiring diagram of DC hydrogen discharging /


emergency/ energy saving fan

Cabinet Air Conditioner User Manual


9
Shenzhen Envicool Technology Co., Ltd.

Figure 3.3 The wiring diagram of DC hydrogen discharging /


emergency/ energy saving fan
Note: To prevent short circuit, GND can't connect to 0V.

3.3 Testing

The Unit Offers testing function, following the steps:

1. Select the “Diagnosis” function in the “Set Up” menu, the unit will start the self testing
procedure automatically.
2. The indoor fan run for 30 seconds.
3. The compressor and the outdoor fan run for 3 minutes.
4. The compressor and outdoor fan stop and heater work for 2 minutes (optional).
5. The external fan (hydrogen discharging fan and so on) run for 2minutes (optional)
6. The external fan stop, and then the unit works according to the normal logic.

3.4 Alarm

The air conditioner offers following alarm output.


The set-point is listed in following forms

Form3.2 Alarm Parameter Setting


Parameter Default Setting Range Unit Description
HTemp.Alarm 40 25-80 ℃ Internal temperature is too high
LTemp.Alarm 0 -20-15 ℃ Internal temperature is too low
In.Ts.Fault -- -- -- The indoor sensor fails
Out.Ts.Fault -- -- -- The outdoor sensor fails
Pi.Ts.Fault -- -- -- The evaporator sensor fails
Con.Ts.Fault The condenser sensor fails

Cabinet Air Conditioner User Manual


10
Shenzhen Envicool Technology Co., Ltd.
HP.Alarm -- -- -- The condenser pressure is too high
The condenser pressure is too high
HP.Alm.Lock -- -- --
frequently
Door.Open -- -- -- Cabinet door is opened (optional)
The evaporation temperature is too
Evap Frost 0 -- ℃
low
VAC.Over 253 -- V The ac voltage is too high(optional)
VAC.Under 187 -- V The ac voltage is too low(optional)
Note: The actual parameters have been set upon delivery according to the customer’s requirement.

3.5 Monitoring

The air conditioner can be monitored through RS485 interface. Connecting the
computer’s serial port to the RS485 interface, you can get the wiring through the
factory(optional); the port should follow the form below.
Form3.3 PIN-TO-PIN
air conditioner(RJ13) RS485 Port
+ RS485+
- RS485-
Note: Make sure only qualified person can reset the set-point.

3.6 Controller

The controller offers a 96×32 LCD displayer. 7 keys are used for setting.
As shown in the following figure.

ON/OFF:Turn On/Off to the unit


: Up, add the setting value or move the menu upright
: Down, decrease the setting value or move the menu downward
: Left, select the forward value
: Right, select the backward value
ENTER: make the change of the setting

Cabinet Air Conditioner User Manual


11
Shenzhen Envicool Technology Co., Ltd.
ESC: Abort the change.
If the air conditioner is turned on, when there is no keyboard operation for 60 seconds,
the display will go back to normal display.
If the air conditioner is powered on, pressing any key will light the backlight of the
display. The backlight turned off when there is no keyboard operation for 60 seconds.
The default code is “0001”. Press “Enter” to the code input menu, press ”Left” or
“Right” to set every code. After all the numbers is inputted, press “Enter”. If the code is
wrong, then display “Wrong Code” and all the parameter cannot be changed. If the code is
right, shows the main menu and the parameter cann be changed.

ShutDown Menu LanguageMenu Normal Interface


Password Input
关机 中文 InTS :20.0℃
Psw: ****
ShutDown English Flow

Error
Password
MainMenu

Set Point
Alarm Menu
Status Menu
System Func

Set Point
Alarm Menu System Func
Status Menu
CoolSP:25℃
Active Alarm Para Set
Band: 5℃ Sensor Value
AlarmHistory Diagnosis
HeatSPd: 10℃ Run Status
Band: 5℃ VersionInfo
HT: 40℃ Restore
LT: 0℃
HH: 90%
InFan: 25℃

Run Status
Sensor Value
InFan: Run
AlarmHistory InT: 20.0℃ OutFan: Stop
Active Alarm Diagnosis
OutT: 20.0℃ Comp: Stop Para Set VersionInfo
Alrm: 01/100 Hum: 50% Heater: Stop
Alarm: 00/00 SelfTest
No Alarm Coil: 20.0℃ EmgFan: Stop Addr: 1 VER : 1.00
No Alarm
Air: 20.0℃ Dly : 00s Name: EC
Cond: 20.0℃ MNTR: 1.0
Amp: 0.0A
Vac: 220V

Note: The actual parameters in the menu have been set upon delivery according to the customer’s requirement.

Cabinet Air Conditioner User Manual


12
Shenzhen Envicool Technology Co., Ltd.

4 Technical Parameter

320
30

20 10
315

352
155 17 0 3 3 8 .4
96 67 7 7 .6 40 1 95

34
52
96.5

67
165

202
250
583

545

550

480
569
94

42

4 2 .5 25 0
154
232.5

62

1 0 -7 x1 0 154 4 9 .5

Figure 4.1 Dimension

Cabinet Air Conditioner User Manual


13
Shenzhen Envicool Technology Co., Ltd.

5 Maintenance
The enclosure air conditioner is working under rigorous environment, following form
5.1 for schedule preventative maintenance.
Warning: All the maintenance work must be performed by qualified person. Cut
off the power supply and signal line before starting maintenance job and reconnect
after that.

Check Item Description period


wiring Inspect if any wiring are loose 12 months
Make fan turns to inspect if there are abnormal noise or fan
Fan 12 months
moves fluent
Drain pipe Inspect if the pipe is twisted or bogged 12 months
Condenser coil Inspect the condenser coil, using brush, compressed air to clean it 6 months

Cabinet Air Conditioner User Manual


14
深圳市英维克科技股份有限公司

1 简介

1.1 前言

注意:任何针对本产品的操作必须由专业的工程技术人员进行。
本手册只能用于指导机柜空调器的安装和操作。手册内容包含机组的功能描述和定
期维护。

1.2 空调器描述

机柜用空调器产品是针对机柜等应用环境而开发的一款制冷产品。适用于机柜内部
设备发热量较大,内部设备对于环境温度敏感,且内外需要完全隔离的应用场合。本产
品功能齐备,有外部风机控制功能,可靠性高,安装简单便捷,通电后即可工作,无需
复杂调试。
空调器内循环的风路从上部吸入热空气,冷空气从下部排出空调器。外部循环从下
部吸入外界冷空气,经过热交换后热空气从上部排出空调器。见图 1.1
注意:空调严禁倾倒搬运、储存和运行。

机柜外环境

机柜
柜内循环风路

柜外循环风路

图 1.1 功能示意图

机柜空调 用户手册
15
深圳市英维克科技股份有限公司

应用范围:
电网适用范围:
交流电源:220V±15% 50Hz
外循环温度范围:-40℃~55℃

1.3 符合标准

表 1.1 产品适用的标准

标准 标准描述
GB/T 17626.7-1998 电磁兼容性

GB4706.1 家用和类似用途电器的安全

GB4798.1 电工电子产品应用环境条件-储存

GB4798.2 电工电子产品应用环境条件-运输

GB4798.3 电工电子产品应用环境条件-使用

机柜空调 用户手册
16
深圳市英维克科技股份有限公司

2 安装和操作
2.1 拆除包装和检验
本产品标准采用纸箱包装,拆除包装时,先将包装外部的打包带拆除,打开纸箱上
盖并将纸箱抽出。注意清点包装内的装箱清单和附件包。

注意:
1. 拆除包装后,请确保空调竖立放置,不能平放或者倒置。
2. 拆除外部的包装后,请仔细检查空调器外观是否有损伤或者油污。如果发现了任何损伤,请在
一周内连同包装外的条形码编号报告销售商。
3. 如果产品不是立即安装或者需要转运到其它地区,请在检查完后重新对空调器进行包装。
4. 为了保护环境,我们建议对包装纸箱进行回收利用。

2.2 安装前准备
安装前注意:
 机柜内部环境设备的摆放,如与空调器内循环进出风口有阻隔,尽量避免。

2.3 空调器机械安装
空调器机械安装包括如下工作:
 空调器贴密封海绵。
 在机柜上固定空调器。
安装工具:十字螺丝刀。
安装时必须严格按照下述的步骤进行安装:
1. 确保有足够的空间安装空调,且便于空调内部和外部的维护(空调的表面最少要离阻挡物
600mm 远)
2. 清点附件(附件包括:电源线、通信线、螺钉、用户手册)并准备安装工具。
3. 用密封海绵按照设计的密封面对机组和机柜的安装面进行密封。
4. 用安装螺钉将空调可靠固定在机柜安装面上。(见图 2.1 和图 2.2)

机柜空调 用户手册
17
深圳市英维克科技股份有限公司

安装螺钉 M5x12
空调 防水胶条 安装门

图 2.1 机械安装示意图

图 2.2 门开孔尺寸

2.4 电气安装
空调器电气安装包括如下工作:
 连接电源线
 通信线缆
注意:所有电气连接都必须符合国家和当地电气规范要求,安装前断开所有的空调电源。

机柜空调 用户手册
18
深圳市英维克科技股份有限公司
根据空调铭牌和技术参数选择合适的线径以及电路保护装置。请根据铭牌的指示
和机组上的说明进行线缆的连接。
按照以下步骤进行电气连接:
1. 确认空调电源断开。
2. 按照电源端子定义将电源线与输入端子连接。
3. 将输入端子可靠连接在机组的电源插头处,并将固定螺钉紧固。
4. 将电源线另一端按照定义接入到相应的配电空开上。
5. 将信号线缆按照定义接入到信号输入端子上。
6. 用万用表测试交流电源输入线是否有短路,断路的现象。
7. 用万用表测试信号输入线是否有短路,断路现象。

 3PIN 交流输入接口:
端子 定义
电源 L 空调电源火线
电源 N 空调电源零线
PE 空调电源地线

图 2.4 交流输入接口

 通信及告警输出端口:
表 2.1 RJ13 位端子信号定义
类型 对应管脚 信号定义
NC 第 1 路公共告警继电器干接点输出 NC 触点
告警输出

COM 第 1 路公共告警继电器干接点输出 COM 触点


NO 第 1 路公共告警继电器干接点输出 NO 触点(选配)
1 第 2 路公共告警继电器干接点输出 COM 触点(选配)
2 第 2 路公共告警继电器干接点输出 NO 触点(选配)
3 外部风扇控制输出(选配)
信号输入

4 外部风扇反馈输入(选配)
5 外部风扇控制继电器干接点输出NO(选配)
6 外部风扇控制继电器干接点输出COM(选配)
7
门禁告警输入(选配)
8
通信

+ 第 1 路 RS485 接口 D+ (上位机监控接口,Modbus 协议)


- 第 1 路 RS485 接口 D- (上位机监控接口,Modbus 协议)

机柜空调 用户手册
19
深圳市英维克科技股份有限公司
 告警输入端口接线示意:
RS485

CO M
丝印:

NO
NC
- + 1 2 3 4 5 6 7 8

C OM

PW M

NC

C OM
FG
NO
注释:

The firs t pub lic


C om munic at ion p ort s
R s 485 通讯端口

alarm dry c ont ac t

第一路公共告警干接点

alar m dr y c ont ac t
The se co nd p ublic

D oo r op en alarm in put
dry c ont ac t
The external f an
第二路公共告警干接点

门禁
外部风扇干接点
图 2.5 告警输入端口接线示意

2.5 安装查检表
在电气和空调器安装完毕后,请核对下列查检表。
1. 空调器的内外循环的进/出风口附近无明显的阻挡物。
2. 空调器竖直安装,且所有安装螺钉已经紧固。
3. 交流输入电源线已经可靠接驳。
4. 交流输入电压符合 1.2 节中内容。
5. 风机可以自由顺畅转动,无异声。

2.6 开机步骤
闭合交流输入电源空开,待机 30S 后空调器内循环风机运行。如果内循环温度达到
运行的条件,制冷系统或加热系统运行。制冷系统运行时,外循环风机的开启由冷凝压
力控制,因此会滞后于压机。

机柜空调 用户手册
20
深圳市英维克科技股份有限公司

3 系统功能介绍
3.1 功能

空调器运行完全根据机柜内部的温度自动控制,控制器通过内循环温度传感器检测机
柜回风温度,和设定点比较进行判断,控制压缩机或风机的工作。

3.2 制冷

制冷开启点=制冷停止点+回差,当机柜内部温度超过制冷开启点,开始制冷运行,
当柜内温度低于制冷停止点,制冷运行停止。
表 3.1 制冷参数设置点
参数 缺省值 设置范围 单位 设置点描述

制冷停止点 23 15-50 ℃ 制冷运行停止的温度点


回差 3 1-10 ℃ 温度控制的回差

注:实际参数已按客户要求在出厂进行设置

3.3 加热(选配)

加热开启点=加热停止点 - 回差,当机柜内部温度低于加热开启点,开始加热运行,
当机柜内部温度高于加热停止点停止加热。
表 3.2 加热参数设置点
参数 缺省值 设置范围 单位 设置点描述

加热停止点 15 -15-15 ℃ 加热开启温度点

回差 5 1-10 ℃ 温度控制的回差

注:实际参数已按客户要求在出厂进行设置

3.4 外部风扇(选配)

3.4.1 排氢风扇运行
按照柜内环境需求,排氢风机实现自动循环排氢功能,自动循环排氢每次排氢间隔时
间为 24 小时,排氢运行时间为 5 分钟。
3.4.2 应急/节能风扇运行
在柜内温度过高或者出现系统故障时,同时外部温度较低时,开启应急/节能风机,实

机柜空调 用户手册
21
深圳市英维克科技股份有限公司
现强制通风功能。
3.4.3 节能风扇运行
当柜内温度高于节能风机开启温度,且柜内温度比柜外温度高 4 度时,开启节能风扇。
3.4.4 排氢/应急/节能风扇接线示意图
注意:排氢/应急/节能风扇干接点最大容量为:交流风机:8A/ 230V;直流风机:2A /48V。

图 3.1 交流排氢/应急/节能风机输入端口接线示意图

图 3.2 直流排氢/应急/节能风机输入端口接线示意图

图 3.3 直流排氢/应急/节能风机输入接口接线示意图
注:两线及三线制直流风机(开停控制,不可调速),GND 不能同 0V 接到一起会短路。

3.5 自测
机组提供自测供现场检测使用。自测过程如下:
1. 通过系统功能菜单中,系统诊断按钮,机组自动进入自测程序。

机柜空调 用户手册
22
深圳市英维克科技股份有限公司
2. 室内风机运行 30 秒。
3. 压缩机及室外风机运行 3 分钟。
4. 若选配了电加热,电加热运行 2 分钟。
5. 若选配了排氢/应急/节能风机,开启外部风机 2 分钟。
6. 外部风机停止,然后按照正常逻辑工作。

3.6 故障
机柜空调器提供如下告警信息。设定点参照表 3.3。

表 3.3 告警内容及参数设置点

告警内容中文 缺省值 设置范围 单位 告警条件


内高温告警 40 25-80 ℃ 内循环温度高于高温告警点
内低温告警 0 -20-15 ℃ 内循环温度低于低温告警点
内温感失效 -- -- -- 内循环温度传感器失效
外温感失效 -- -- -- 外循环温度传感器失效
盘管温感失效 -- -- -- 盘管温感故障
冷凝温感失效 -- -- -- 冷凝温感故障
系统高压告警 -- -- -- 系统高压(或外风机故障)
系统频繁高压 -- -- -- 系统频繁触发高压告警
门禁告警 -- -- -- 柜内被打开(选配)
盘管防冻保护 0 -- ℃ 盘管温度过低
交流电压过高 253 -- V 交流电压过高(选配)

交流电压过低 187 -- V 交流电压过低(选配)


注:实际参数已按客户要求在出厂进行设置

3.7 监控
空调器利用 RS485 通讯口和电脑进行通讯。可以使用厂家提供的线缆(选配)来连接
RS485 通讯口与电脑串口。RS485 通讯线缆引脚对应关系如表 3.3。
表 3.3 串口连接对应表
空调(RJ13) RS485 口
+ 第 1 路 RS485 接口 D+
- 第 1 路 RS485 接口 D-
为使机组运行可靠和发挥最大能效, 请用户勿随意更改温度设定点。

机柜空调 用户手册
23
深圳市英维克科技股份有限公司
3.8 菜单结构

机组控制器采用 96×32 液晶显示,共 7 个按键来对控制器进行设置,操作界面如下


控制器操作界面
ON/OFF:开/关机键,操作此键对机组进行开/关机;
↑:上移键,选择上一条记录/菜单或者对设置值(仅限密码)进行增加;
↓:下移键,选择下一条记录/菜单或者对设置值(仅限密码)进行降低;
←:左移键,对设置值进行增加或者在进行密码操作时选择前一位数据;
→:右移键,对设置值进行降低或者在进行密码操作时选择后一位数据;
ENTER:回车键,确认输入;
ESC:退出键,返回上一屏菜单;
开机后,在任何界面下,如果持续 60 秒无键盘操作,自动返回正常显示界面。
系统上电后,按任意键,背光灯亮,如果持续 60 秒无键盘操作,背光灯灭。
机组出厂的操作密码为“0001”。在正常显示界面按回车进入密码输入界面,按左移
键,右移键选择需要输入的位,按上下键修改,输入完毕按回车键确认。如果密码不正
确,界面显示错误信息,不能修改机组设定。如果密码正确,进入主菜单,可以对机组
设定进行编辑。

机柜空调 用户手册
24
深圳市英维克科技股份有限公司

关机界面 语言界面 正常界面 密码输入界面

关机 中文 内 温 :20.0℃ 密 码 : ****
ShutDown English 送风

密码错误
不能修改参数
主菜单

运行设定
告警菜单
系统状态
系统功能

运行设定 告警菜单
系统状态 系统功能
制 冷 点 : 25℃ 当前告警
回 差 : 5℃ 环境状态 系统参数
告警历史 系统诊断
加 热 点 : 15℃ 输出状态
回 差 : 5℃ 系统版本
高 温 点 : 40℃ 恢复出厂
低 温 点 : 0℃
高 湿 点 : 90%
内 风 机 : 25℃

输出状态
环境状态
内风机:运行
告警历史 内 温 : 20.0℃
当前告警 外风机:停止 系统诊断
外 温 : 20.0℃ 系统参数 系统版本
压缩机:停止
告 警 : 1 / 100 湿 度 : 50.0%
告 警 : 00 / 00 电加热:停止 系统自测
无告警 盘 管 : 20.0℃ 地 址 : 01 软 件 : 1.00
无告警 应急 :停止
排 气 : 20.0℃ 延 时 : 0s 机 型 : EC
冷 凝 : 20.0℃ 监 控 : 1.0
电 流 : 1.0A
Vac : 220.0V

注:此图仅为菜单结构图,不代表出厂参数配置。

机柜空调 用户手册
25
深圳市英维克科技股份有限公司

4 技术参数

320
30

20 10
315

352
155 17 0 3 3 8 .4
96 67 7 7 .6 40 1 95

34
52
96.5

67
165

202 250
583

545

550

480
569
94

42

4 2 .5 25 0
154
232.5

62

1 0 -7 x1 0 154 4 9 .5

图 4.1 空调尺寸

机柜空调 用户手册
26
深圳市英维克科技股份有限公司

5 日常维护
为了保障空调器的正常运行,请参考表 5.1 对空调器进行定期维护
警告:所有的维护工作必须由合格的专业人员进行维护,在进行任何维护前,请事先
断开空调器电源和信号线,维护工作结束后接通空调器电源和信号线。
表 5.1 日常维护表
检查项目 步骤内容描述 维护周期
接线 目视检查是否有松脱 12 个月
风机异常 拨动风机,转动是否顺畅,有无异响 12 个月
排水管 目视检查排水管是否有变形,脏堵 12 个月
冷凝器 检查冷凝器清洁状况,用压缩空气清洁冷凝器 6 个月

机柜空调 用户手册
27
Declaration:
This manual shall not be reproduced without the written approval of Envicool.
Envicool reserves the right to update the product without notice.
声明:
版权所有,禁止任何未经授权的拷贝和抄袭。
厂家对产品持续升级进行的资料更改,恕不另行通知

Shenzhen Envicool Technology Co., Ltd.


Building 9 , Hongxin Industrial Park , Guanlan , Bao’an
District,Shenzhen
Tel: 86-755-29588896
Fax: 86-755-29588895
Website: http://www.envicool.com
深圳市英维克科技股份有限公司
深圳市宝安区观澜街道鸿信工业园 9 栋
电话:0755-29588896
传真:0755-29588895
网址: http://www.envicool.com
L50010078

Вам также может понравиться