Thermal Relief Valve Data Sheet

DATA SHEET OF ORIFICE PLATE


Units Units
V12-RV-
1 Item no. 70 GENERAL
0001,0002,0003,0004,0006
2 Service 71 Plant / Unit Tank Farm Piping Replacement-Amal
Refer attached Process
3 Line No. 72 Location Field
Document No 235564IN01-
4 Line Size /Schedule 73 Classified Area Zone Class 1 Divison 2 as per NEC
PRO-012
5 P&ID Drg No. 74 Protection concept Flame Proof
6 Quantity 5 Nos. 75 Gas Group C&D
7 76 Temperature Class T2
8 77 Ingress protection class
9 78
10 79
11 Process Data 80 SPECIAL REQUIREMENTS
12 Fluid 81 NACE Requirements Body,Bonnet And for all part
13 Required Capacity 82 Competent Authority
14 Fluid State 83 Environmental Requirements
15 Operating Pressure Refer attached Process 84 Material Certificate Required
16 Set Pressure Document No 235564IN01- 85
17 Back Pressure PRO-012 86
18 Temperature (deg C) 87
19 Specific Gravity 88
20 Viscosity 89
21 Compression Factor - 90
22 Specific Heat Ratio (Cp/Cv) - 91
23 Molecular Weight - 92
24 93
25 94
26 95
27 Valve 96
28 Safety,Relief or safety relief Thermal Relief 97
29 Conv / Bellows /Pilot Op Conventional 98
30 Bonnet Type Closed 99
31 100
32 Connection 101
33 Size Inlet X Outlet (MM x MM) 19.05 X 25.4 102
34 Flange Rating 150 # ANSI B 16.5 103
35 Type of Facing RF 104
36 105
37 106
38 Material 107
39 Body and Bonnet A2116 WCB 108
40 Seat and Disc SS316 109
41 Nozzel , Spindle & Guide SS316 110
42 Spring Spring Steel 111
43 Bellows NA 112
44 113
45 Option 114
46 Cap : Screwed or Bolted NR 115
47 Lever : Plain or Bolted Plain 116
48 Test Gauge NR 117 REMARKS
49 118 1) VTA = Vendor to Advise/ Confirm
50 119 2) NR= Not Required
51 Basic 120 3) Manufacturing to start only after approval of Vendor drawing.
52 Code ASME Section-8 Division 1 121 4) For Pressure Relieving valve GES J.10.Various Specifications, Codes &
53 Fire 122 Standards refeered to in GES J.10 Shall also be referred to. Any deviationsfrom the
54 123 specification and data sheet shall be clearly indicated with reference to clause no. and
55 Other 124 reasons for the deviation.
56 Calculated area in Sq mm 125
57 Selected area sq in 0.11 -VTA 126
58 Orifice Designation D- VTA 127
59 128
60 129
61 130
62 131
63 132
64 PURCHASE DATA 133
65 Manufacturer VTA 134
66 Model Number VTA 135
67 Serial Number 136
68 Purchase Order No 137
69 138
INSTRUMENT DATA SHEET

B Issued For Tender 15.03.10 APG SGB VPR


Thermal Relief Valve
A Issued For Comments 11.11.08 JHS/APG SGB RM MMCI Project No.235564 IN01 Sheet 3

Rev Description Date Prepared By Checked By Approved By Doc No.235564IN01-INS-012 Rev B

G:\HOO - Tank Farm -Final Documentation\7 Instrumentation Deliverables\1 - Inst. Docs\Thermal Relief Valve INS 012\Thermal Relief Valve