VENTICON -C

CO2 Monitor / Controller

FEATURES:
VENTICON is an easy to use CO2 Monitor/ Controller and has many features …

 NDIR ( Non-Dispersive-Infrared) technology used to measure CO2 concentration

 Reliable Sensor provides long-term calibration stability.

 Three different LED display show the current Indoor Air Quality

 Relay output for Ventilation control

 The visual and audible alarm function can be adjustable by user.

 Temperature display

 For High Altitude operation, much needed correction is incorporated

 Wall Mount rugged enclosure with terminal block provided for quick / easy installation

 230Vac power supply option


This product is developed to detect presence of CO2 in the ambient air and control the Indoor Air Quality.
The compact device is designed for use in demand controlled ventilation in variety of applications. By
using the CO2 in ppm as the parameter, it adjusts the ventilation to the comfort condition as set in control.
This avoids over-ventilation of the building resulting in substantial energy saving.
VENTICON-C can be widely used in the office building, green houses, schools, exhibitions, shopping
malls. Applications include - Demand controlled ventilation, food processing and food storage ,
mushrooms cultivation, flower growers and nurseries ,CO2 level control in dairy ventilation
requirements ,agricultural animal confinement , breweries and restaurants/pubs etc.

Product offers unique feature of Calibration correction for High Altitude ( low ambient pressure )

Specifications:
Measurement Range of Range options: 0 to 3000 ppm std
CO2 concentration 0 to 10,000 ppm, 0 to 50,000 ppm
Accuracy +/-75ppm or 5% of reading ( better accuracy on demand)
Zone Display (LED) 3 LEDs Green : <800ppm Yellow : 800~1200ppm Red :
>1200ppm the level is adjustable
Buzzer Alarm yes
Temp.Display standard
Display CO2 in ppm
Sample Method Diffusion or flow through (0.05 ~0.2l/min)
Storage Range -20~60C,96%RH
Update Period 7 seconds
Temperature +/-0.1% of Reading per degC or +/-2ppm per degC,whichever is
Dependence greater ,refered to 25degC
Repeatability 20ppm or 1% of reading

Press. Effect 0.13% of reading per mm Hg ;


Response Time <2min #R1 (63% RiseTime)
Warm up time <60s
Analog Output 4~20mA(Rlmax=500 Ohms); 0~10VDC(100 Ohms output
impedance)
Relay Output 30VDC or 250VAC, max 2A ., SPST .Normal Open
Alarm Level for 3 LEDs Green : <800ppm Yellow : 800~1200ppm Red :
Relay/LED >1200ppm the level is adjustable
Operating Temp Range 33 to 122° F (0-50°C ,-5-50°C on request )
0-95% RH, non-condensing
Analog Output 0 to 10 Vdc
Comm.Output RS485 with Modbus protocol ( Optional extra)
AC/DC Supply Option 1. 24VAC+/-20% ; 18~40VDC , Option2 : 90 Vac to 230 Vac 50Hz
Dimension 210x150x35 mm
Sensor Life >5year

ACORN CONTROLS Marketed by:


4-Mayuresh Apts.,
104-Mayur Colony,
Kothrud, Pune 411 038
e-mail : acorn@eth.net
T/F : +91 20 2542 2057

Specifications subject to change due to continuous development .Please confirm before ordering.