SM6-NOVELTIES

Easergy
Remote control
&
Autochange over
What ’s new?
 SM6 range takes advantage of Easergy technology
• SM6 catalog offer is enriched with remote control facilities
• Change over offers (NSM) are improved
– Network and generator change over function
– Current solution is old and components becomes obsolete
– Need of 3 phases / unbalanced voltage detection
– Productivity

 Catalog : 3 versions
• NSM switchgear : emergency generator change over
• NSM switchgear : Network line change over
– Without Remote control
– With Remote control
• Remote control
– One unit allows Remote control of 1 or 2 IM switchgears

2
Joseph MARZOCCA - 17/10/02 - EN
2
Easergy T200 S

 Principle
• T200S is based on the standard components of Easergy T200
remote control devices.
– Advantage of Easergy function catalog
– Advantage of Easergy accessories catalog
– Advantage of Easergy skill and support
• T200 S is a kit of components ready to be mounted into a
375mm LV compartment of an SM6 switchgear.
– Rack including all electronic cards
– Fault Passage Indicators
– Miscellaneous cables and accessories for wiring
– Current transforer for FPI and current measurement (split
core type)

3
Joseph MARZOCCA - 17/10/02 - EN
3
NSM change over switchgears
 Emergency generator change over automation
• Instead of RNS11 relay based solution
 Emergency generator change over automation
• Line voltage loss detection
T200 S – VPIS-PH/VPIS-PL
Voltage – VD3H
detector
NSM IM • Time setting before change over : 1s to 15s
• Generator start control output
Fault
VD3H
• Change over when generator is running (input)
Passage
Indicator • Time setting for return to normal : 60s to 120s
• generator stop control order (delay 6s)
 Other
• Lockout on Fault Detection on live line
• Parallel mode allowed

4
Joseph MARZOCCA - 17/10/02 - EN
4
NSM change over switchgears
 Network change over
• Instead of RCV420 relay based solution
 Normal / backup auto change over automation
T200 S
• Line voltage loss detection
Voltage – VPIS-PH/VPIS-PL
detector – VD3H
NSM IM
• Time setting before change over : 0,1s to 2s
• Time setting for return to normal : 5s to 120s
VD3H VD3H  Other
• Lockout on Fault Detection on live line
Fault • Parallel mode allowed
Passage
Indicator • Telecontrol feature available in option

5
Joseph MARZOCCA - 17/10/02 - EN
5
IM switchgear

 Telecontrol of 2 IM switchgears
• New functionnality for SM6 range
T200 S
 Protocols - Transmission system
IM
• Modbus [ RS232,RS485,PSTN,GSM, Radio]
• IEC 870-5-101 [ RS232,RS485,PSTN,GSM, Radio]
• DNP3.0 [ RS232,RS485]
 Monitoring
• Switch and earth switch position
Fault
passage • Overcurrent and earth fault detectors
indicator
• Load current for 1 or 2 switches
 Control order
• 1 or 2 IM switch motor control

6
Joseph MARZOCCA - 17/10/02 - EN
6
Characteristics

 Main supply 230Vca

 Operating temperature : -15°C to 55°C

 Local control panel

 Configuration by lap top PC

 Uninterrupted power supply

 Embedded Fault Passage Indicators

7
Joseph MARZOCCA - 17/10/02 - EN
7
Presentation Power supply

T200S Telecontrol

Local Control
terminals
Configuration
by PC
VD3H
Area for
transmission devices

8
Joseph MARZOCCA - 17/10/02 - EN
8