Вы находитесь на странице: 1из 3

Project: Rating Program: XEngine 1.0.

7053
Unit Tag: Software Version: YW 19.02
Engineer: Date: 05/06/2019 18:28:25
Customer:

SALES REPORT

Unit Specifications
Model YMC2-S1934AB Refrigerant R-134a
Specified Net Capacity (Tons) 550.0 Refrigerant Charge (lb) 1470
Rated Net Capacity (Tons) 550.0 Variable Orifice V2
Heat Rejection Capacity (MBtu/h) 7.660
Full Load (kW/Ton.R) 0.5469 Isolation Valve Y
NPLV.IP (kW/Ton.R) 0.3107 OptiSound Control Y
Input Power (kW) 300.8 Voltage / Hz 415 / 50.0
Starter Type HYP0730XHC***-68A FLA (Amps) 441
Compressor M2C-246FAC A-Weighted SPL (dBA) 76
Evaporator EB3314-321-CS*-2*** Min Circuit Ampacity 552
Condenser CB3314-260-BS*-2*** Max Circuit Breaker Amps 800
Sales Model YMC3314C3314B246M2B

Evaporator Condenser
Fluid Water* Water*
Tube MTI No. 321 260 / 260
Passes 2* 2*
Fouling Factor (hr-ft²-°F/Btu) 0.000100* 0.000250*
Entering Fluid Temp (°F) 54.00* 85.00*
Leaving Fluid Temp (°F) 44.00* 94.34
Fluid Flow (gpm) 1316 1650*
Fluid Pressure Drop (ft H2O) 15.5 20.6
(*) Designates User Specified Input
NPLV.IP CALCULATION:
1
1
NPLV.IP = 0.01 0.42 0.45 0.12 NPLV.IP = 0.3107
+ + + 3.219
A B C D
A = kW/Ton.R AT 100% NET CAPACITY C = kW/Ton.R AT 50% NET CAPACITY
B = kW/Ton.R AT 75% NET CAPACITY D = kW/Ton.R AT 25% NET CAPACITY

Certified in accordance with the AHRI Water-Cooled Water Chilling and Heat Pump Water-Heating Packages Using
Vapor Compressor Cycle Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI 551/591
(SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org. Auxiliary components included in
total kW: Chiller Controls.
Compliant with ASHRAE 90.1-2004.
Compliant with ASHRAE 90.1-2007.
Compliant with ASHRAE 90.1-2010.
Compliant with ASHRAE 90.1-2013.
Compliant with ASHRAE 90.1-2016.
Compliant with the requirements of the LEED Energy and Atmosphere Enhanced Refrigerant Management Credit
(EAc4).
Materials and construction per mechanical specifications - Form 160.84-EG1.
Auxiliary components included in total kW - Chiller controls.

Page 1 of 3
Project: Rating Program: XEngine 1.0.7053
Unit Tag: Software Version: YW 19.02
Engineer: Date: 05/06/2019 18:28:25
Customer:

Partload Data (Full Load with IPLV/NPLV per Std. Condition Set)
Net Capacity Input Power EEFT ELFT CEFT CLFT
% Load % Power kW/Ton.R
(Tons) (kW) (°F) (°F) (°F) (°F)
100 550.0 100 300.8 54.00 44.00 85.00 94.34 0.5469
75 412.5 54 160.9 51.50 44.00 75.00 81.72 0.3902
50 275.0 24 72.52 49.00 44.00 65.00 69.33 0.2637
25 137.5 13 39.55 46.50 44.00 65.00 67.18 0.2877

Certified in accordance with the AHRI Water-Cooled Water Chilling and Heat Pump Water-Heating Packages Using
Vapor Compressor Cycle Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI 551/591
(SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org. Auxiliary components included in
total kW: Chiller Controls.
Compliant with ASHRAE 90.1-2004.
Compliant with ASHRAE 90.1-2007.
Compliant with ASHRAE 90.1-2010.
Compliant with ASHRAE 90.1-2013.
Compliant with ASHRAE 90.1-2016.
Compliant with the requirements of the LEED Energy and Atmosphere Enhanced Refrigerant Management Credit
(EAc4).
Materials and construction per mechanical specifications - Form 160.84-EG1.
Auxiliary components included in total kW - Chiller controls.

Page 2 of 3
Project: Rating Program: XEngine 1.0.7053
Unit Tag: Software Version: YW 19.02
Engineer: Date: 05/06/2019 18:28:25
Customer:

Certified in accordance with the AHRI Water-Cooled Water Chilling and Heat Pump Water-Heating Packages Using
Vapor Compressor Cycle Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI 551/591
(SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org. Auxiliary components included in
total kW: Chiller Controls.
Compliant with ASHRAE 90.1-2004.
Compliant with ASHRAE 90.1-2007.
Compliant with ASHRAE 90.1-2010.
Compliant with ASHRAE 90.1-2013.
Compliant with ASHRAE 90.1-2016.
Compliant with the requirements of the LEED Energy and Atmosphere Enhanced Refrigerant Management Credit
(EAc4).
Materials and construction per mechanical specifications - Form 160.84-EG1.
Auxiliary components included in total kW - Chiller controls.

Page 3 of 3

Вам также может понравиться