Вы находитесь на странице: 1из 20

2017 SEAOC CONVENTION PROCEEDINGS

An Economical Approach to Floor Vibration through


Appropriate Design Criteria and Analytical Methods
2017 SEAOC Convention

Jeffrey Keileh, PE, SE, LEED AP BD+C, Associate


Mark Sarkisian, PE, SE, LEED, Partner
Skidmore, Owings & Merrill LLP
San Francisco, California

Abstract equipment being used, as well as museums and residential


floors to not disturb the occupant’s experience.
Human response and acceptance criteria to footfall excitations
can be very complex. Each building function carries its own The employment of the appropriate acceptance criteria
set of parameters that influence the selected acceptance measures, analytical methodologies, and design criteria to
criteria, analysis methodologies and design solutions. The evaluate the acceptance of the floor system all play an equal
acceptance criteria metrics include accelerations, velocities, role in addressing floor vibration. Such criteria and design
and sometimes frequencies, whereas, the analytical methods methodologies can be applicable to various types of structures
range from simple hand calculations to complex time history on which people walk, including floors and bridges, as well as,
footfall analyses. The objective of this article is to provide to structures of various forms of construction material, e.g.
project specific examples that address various acceptance steel, composite, reinforced/pre-stressed concrete, timber,
criteria measures and employment of the appropriate analytical etc…
methodologies. The design examples shown herein will reflect
the full range of applicable acceptance criteria ranging from As it relates to Frequency Response Function (FRF) and Time
laboratories, museums and airports, to typical office and History Analyses (THA), these two analytical design methods
residential functions. can be applied to varying systems and material types despite
the complex and/or regular/irregular type structures.
In addition, recent projects have employed frequency as a
design constraint, however, it is more appropriate to employ The Basics
system responses to human activity in lieu of an arbitrary
restriction of the floor system’s frequency and therefore When walking excitations are applied to the supporting
stiffness. Employing such criteria only restricts the design structural floors, staircases or bridges, they apply dynamic
solutions and needlessly uses an excess of material to address forces that cause the structure to vibrate. The displacement
human comfort to floor vibration. The use of higher analytical amplitude associated to such excitations are typically small
procedures can provide an enhanced understanding of the and not perceptible visually and do not significantly affect the
system’s response, thereby assisting the designer to find more structural integrity. However, walking excitations can be felt
cost effective and sustainable solutions. through other measures such as accelerations and/or velocities.
If such responses are excessive to human perception, the
Introduction response of the structure can impair the function of the space.
However, if a walker or group of walkers’ excitation frequency
While footfall induced vibrations on buildings and/or bridges (step frequency) is aligned with the structural systems’
may not be significant in terms of structural integrity, footfall frequency (structural frequency), resonant build-up can be
vibration can be a critical serviceability condition to address. activated, thereby, yielding human perceivable displacement
As Hardy Cross once wrote, “Strength is essential but and potentially affect the structures’ integrity.
otherwise not important.” Therefore, in modern building
design, the assessment of human-induced vibration due to To evaluate the structures response to walking induced
occupant specific activities need to be addressed by the excitations, it is necessary to understand the following key
designers to ensure that the floor responses are not perceivable items:
to the typical occupant. This is particularly important for  walking excitation/s being applied,
hospitals/laboratory floors due to the sensitive tasks and  evaluation criteria,

1
2017 SEAOC CONVENTION PROCEEDINGS

 dynamic properties of the structure and


 design methods to obtain the structural response.

Walking Excitation / Footfall

The dynamic excitations applied to a structural systems due to


walking or running can be classified as harmonic, periodic,
transient or impulsive, shown in Figure 1. Harmonic and
periodic can be used in a time history analysis approach for
mechanical equipment if such loading functions are known.
Transient loading can also be used in a time history approach
for structures near trains, or any other variable load function if (a) AISC DG 11 – 2nd Edition 
such loading functions are known.

This article is focused on periodic and transient type dynamic


excitations as they are more representative of human walking
excitations.

(b) Obata and Miyamori, 2006


Figure 2: Walking heal drop excitations

Both functions are represented by plotting force verse time of


a footstep and have key differences which are visibly apparent.
The idealized footstep function defined in AISC DG 11 2nd
Edition starts with an increasing heel loading portion followed
Figure 1: Types of dynamic excitations by the constant load transferring from heal to toe, then
reduction in load as the toe left the ground.
To better understand periodic and transient applied loads let’s
start from an impulse load. An impulse load can be used to Whereas, Obata and Miyamori function further defines the
define a single footstep, otherwise known as a heal. A heal load transfer portion as seen by the valley in-between the heal
drop can be defined in an idealized function as seen in and toe. Similar to an idealized function, there is an increasing
American Institute of Steel Construction (AISC) Design Guide heel loading portion, however, as the heel transfers load to the
(DG) 11-2nd Edition or as defined in the publication by Obata toe verse time the load has a slight dip, then increases again as
and Miyamori, 2006, both are shown here-in. the toe takes full load. Then similarly to the idealized step, the
load reduces as the toe has left the ground. It should be noted
for the Obata Miyamori footstep function has a larger force at
the toe relative to the heel. This phenomenon occurs from the
double impact (heal then toe) and the slight flicking effect as
the toe leaves the ground.

It is the opinion of the author when using Time History


Analysis approach, both footstep functions should be used and
apply a minimum of five consecutive steps to evaluate
susceptibility of resonant build-up. These footstep functions

2
2017 SEAOC CONVENTION PROCEEDINGS

are defined as a periodic or transient loading function Evaluation Criteria


depending on the selected walking frequencies.
There are many possible ways in which the magnitude of
A typical walker frequency ranges from 1.6 to 2.2 Hz which vibration responses can be evaluated relative to human
translates to an approximate 96 to 132 steps per minute. An perception, which range from acceleration, velocity and
average step length is approximately 2.5 feet (762 mm). Table displacement. As displacements are typically too small to be
1 below is a helpful guide of when to employ which walking perceivable due to walking excitations, accelerations and
speed and step frequency as it relates to Frequency Response velocities are seen to be more prudent for design. Hence past
Function and Time History Analysis methodologies. and current design standards defining acceleration and velocity
criteria values for varying occupancies as it relates to human
Application of Walking Speeds perception.
Speed Frequency Applications for Time History
(Step/Min) fstep (Hz) Analysis1 However in a few projects, it seems that frequency has been
Generally a slow walking speed creeping into the mix as an evaluation acceptance criterion for
should not be used unless it is walking excitation floor vibration. When using frequency as
known that the space is small, an acceptance criterion shows a limited understanding of
congested and space has limited acceleration and velocity based methodologies as frequency
paths of direct travel. A inherently plays a dominant role in the structures response to
potential example is an MRI human induced floor excitations. Also by using frequency as
Very Slow an acceptance criterion ignores contributions of all other
0.83-1.25 room where the equipment
50-75 variables, such as damping or effective weight, associated to a
takes up the majority of the
space and the technician is structures response to human induced excitation, thereby
working in another section of limiting the designers’ capacity to solve the project specific
the small room, thereby needs in a more cost effective manner.
limiting movement at the MRI
unit itself. It is not the intention to ignore the frequency value of a given
Moderate walking speeds can floor system, rather, to state that frequency limits should be
be used for mid-sized rooms used as rules of thumb to evaluate if further investigation is
Slow with some obstructions limiting needed to address the project specific needs, thereby allowing
1.6 the designer to use the various factors that affect the structures
96 the paths of direct movement
such as typical offices, response to employ more cost effective solutions.
laboratories, etc.
Moderate walking speeds are Peak Acceleration Evaluation Criteria
recommended for initial design
Moderate unless room sizes with layouts It is more common to see the evaluation limit criterion defined
1.85 in terms of peak acceleration for typical structural responses to
111 are known. Moderate walking
speeds can be used for larger walking excitation, see Figure 3 below, which provides the
rooms with few obstructions. AISC DG 11 2nd Edition peak acceleration limits versus
Fast walking speeds are structural frequency. Additionally, the figure shows the
typically reserved for author’s recommendations for typical airport and museum
verification of rooms adjacent peak accelerations criteria. Judgement of peak acceleration
to corridors. However, for very criteria should be evaluated and defined on a case by case
Fast large rooms with repetitive basis, as well as, be coordinated with the project expectations
2.08-2.2 and needs. If more stringent criteria is required, then one shall
125-132 modules that provide a central
spine/s about the space with employ such evaluation parameters.
limited obstructions can
warrant using fast walking It should be noted that the peak acceleration of 0.5%g is the
speeds for evaluation. most stringent criteria defined and applicable to such spaces as
1
Judgement should be used when selecting the walking office, residence, and church type occupancies where the
speed/s for evaluated. In addition, such criteria should be human sensitivity to floor vibrations can be at its’ highest.
defined and coordinated with the design team early in the Also by applying the stringent peak acceleration one can
design process. provide a performance level equaling an essentially vibration
Table 1: Application of walking speeds free floor system where only highly sensitive human can
perceive such an acceleration due to walking excitations.

3
2017 SEAOC CONVENTION PROCEEDINGS

The expression  = 0.83e-0.35fn is a recommended dynamic


coefficient from Rainer et al. (1988) and Allen and Murray
(1993). This expression provides a simplified relationship of
the step function and the dynamic coefficient,  with the
structures natural frequency, fn. Therefore, the acceleration
inequality only looks at the dominant harmonic, but is still
appropriate for repetitive and regular structures. When it
comes to non-repetitive and irregular structures, Frequency
Response Functions and/or Time History Analysis should be
used in evaluating the structural response, which are described
later in this article.

Figure 3 Human comfort limits


Figure 4: Dynamic coefficient versus frequency
In order to calculate the peak acceleration we lean on design
standards and research that has been conducted to define such With a better understanding of how the equations were
standards. In AISC DG 11 2nd Edition, the derivation of the derived, the equations can be tuned to each specific condition,
peak acceleration formula used to compare to the peak if required, and provide an understanding of when further
acceleration acceptance criteria in evaluating if the structural analysis and design methodologies need to be used.
system is deemed acceptable is shown to yield the following
acceleration inequality: Peak Velocity Evaluation Criteria

. Velocity based design methodologies are typically used for


designing spaces with sensitive equipment, such as
laboratories or hospitals. In such cases where the floor system
supporting sensitive equipment and where criteria are not
Po = amplitude of the driving force, 0.83RQ, lb known, the designer needs to rely on generic criteria. These
R = 0.5 for two-way mode shapes industry standard velocity based generic design criteria are
R = 0.7 for one-way mode shapes expressed in terms of the greatest vibration velocity to which
= 0.83(0.5*157 lb) ~ 65 lb for typical floors various classes of equipment may be exposed. And providing
= 0.83(0.7*157 lb) ~ 92 lb for bridges and staircases such criteria in terms of velocity is convenient because the
criterion for a given class of equipment corresponds to a
Q = bodyweight, lb, 157 lb constant value of velocity over most frequency range of
fn = fundamental natural frequency, Hz interest, as shown in Figure 5.
 = damping ratio
W = effective weight of the floor, lb

= acceleration tolerance limits, see Figure 3

= ratio of peak floor acceleration to gravity

4
2017 SEAOC CONVENTION PROCEEDINGS

Vibration
Walking
Area of Use (Primary Velocity
Speed
Factor)1,2,3 Maximum
(steps/min)
(inch/sec)
100 to
Corridors 8,000
1251
Lab Offices / Patient Rooms 4,000 100
Surgical Suites (Human) 4,000 75
Laboratories and Laboratory
2,000 100
Support Rooms
Surgical Suites
1,250 75
(40X Surgical Microscope)
Imaging (MRI) / Surgical
Suites 500 50 to 75
(100X Surgical Microscope)
Electron Microscope 250 50 to 75
1
Spacing adjacent to corridors shall be evaluated to consider
vibration excitation from the corridors.
Figure 5: Generic vibration criteria (VC) curves 2
Use local isolation systems for mechanical equipment to limit
structure bone vibration to adjacent occupied areas.
3
Provide additional floating reinforced concrete slab on
isolation pads or mechanical isolation systems at sensitive
equipment where required.
Table 3: Recommended laboratory velocity limits with
respective walking excitation speeds

Frequency Evaluation Criteria

What is frequency? A simple way to understand frequency is


when looking at a sine wave, the frequency is the number of
cycles per unit of time or cycles per second, otherwise known
as Hertz. The higher the frequency the tighter the spacing of
the sine wave peaks, see Figure 6.

Table 2: Generic vibration criteria tolerance limits

Numerous scientific laboratories have been designed by SOM


and many of them required the floor systems to satisfy
stringent floor vibration limits in order to house sensitive
equipment and the needs of the space. Table 3 is a
recommendation on the velocity based criteria with its
respective walking excitation speeds used for design of the
floor systems supporting laboratory and hospital type spaces.

The question can be asked, how do designers appropriately


assess the system for vibration behavior to meet such criteria
with their respective walking speeds? The answer is,
Frequency Response Functions and Time History Analysis
approaches were used on the past projects and described later
in the paper.

Figure 6: Frequency comparison

5
2017 SEAOC CONVENTION PROCEEDINGS

In structural engineering, frequency can also be defined as a Therefore when using a peak acceleration based approach,
displacement through its relationship with mass and stiffness. each variable and their appropriate contributions are
Looking at a simply supported beam with a uniformly incorporated in the acceleration inequality expression, thus,
distributed load, one can derive the first natural frequency: allowing a thorough investigation of all parameters when
looking to solve the needs of the project rather than looking at
a singular deflection criteria. That being said, frequency
should be used in the early design phases as rules of thumb in
2 the absence of acceleration and velocity calculations.

By rearranging the expression and substituting the maximum For example keeping the vertical frequencies at about 3 to 5
deflection equation in the first natural frequency formula, it Hz can be a starting point for typical office spaces, 5 to 6 Hz
can be seen that frequency can be distilled down to a for typical lab spaces, and 6 to 8 Hz for lab spaces with
displacement based criteria. sensitive equipment excluding VC-D and VC-E type
equipment. Whereas 2 Hz may be deemed appropriate for
extremely long one-way span type structures where there is a
5 5 5 significant amount of mass that needs to be excited and/or
∆ → →
384 384∆ 2 384∆ dampers are implemented.

0.18 It should be noted for long one-way span type structures, a 3


0.18 → ∆ Hz horizontal frequency rule of thumb is recommended in the

initial phases of design to address potential “lock-in effects.”
It has been experimentally observed that people change their
Therefore, it can be seen that when a frequency limit is used as
walking frequency and step width to adapt to clearly
an acceptance criteria for design, it is essentially providing a
perceptible lateral vibrations of the supporting structure, which
deflection limit that has no relationship to span, location of
may unify the group of walkers as observed on the Millennium
supports/grid system, amount of damping, resonance potential,
Bridge during its opening day in 2000.
harmonic separation, nor amount of mass that needs to be
excited, see table below. Therefore, such limits should be used
Using frequency limits as the acceptance criteria only hinders
as rules of thumb for initial design phases, and not used as a
the ability to attain the more cost effective solution for the
criteria defining if a system is adequate. Adequacy of a floor
project needs. Two quick examples can be seen when applying
system due to walking excitations are defined through the use
frequency as an acceptance criteria for long span structures
of acceleration and/or velocity based approaches.
and/or retrofitting existing structures.
Frequency, Equivalent
For long span type structures, an initial study can be conducted
(Hz) Displacement,
comparing a damped structural system designed for strength
 (in) and deflection where the added damping achieves the
5 0.50 acceptable acceleration criteria, which can then be compared
6 0.35 to a similar system with no dampers, thereby, informing the
7 0.26 designer of the more cost effect solution for the project needs.
8 0.20 Another fault can be seen in retrofitting existing structures, as
9 0.15 using frequency limits would yield adding more
10 0.13 structure/stiffness rather than using dampers or employing
11 0.10 isolation systems for the sensitive equipment. Therefore, by
12 0.09 providing frequency limits prevents the use of such solutions
Table 4: Frequency and displacement in seeking the more cost effective approach for the project
needs.
When looking at the peak acceleration design inequality, one
can see that the frequency plays a dominate role as it takes on For an airport project example, it was stated in the Project
an exponential relationship relative to the peak acceleration Design Document (PDD) that “New designs should strive to
whereas damping and/or effective weight has a linear design floors which will exceed 9Hz.” With such an
relationship. excessively stringent criteria that also doesn’t follow standard
practice criteria for walking excitations, it was brought to the
. reviewers having jurisdiction’s attention early in the design
phase. As shown earlier this article, this 9Hz frequency criteria

6
2017 SEAOC CONVENTION PROCEEDINGS

would yield that the floor framing system shall not deflect
more than about 1/8 of an inch no matter what spans are used.
As one can see, this frequency limit will have a dramatic effect
not only on the space, as additional vertical elements will be
required, but also the amount of material needed for the floor
framing to meet the frequency/deflection criteria.

This criteria triggered many discussions as there were long


span conditions to limit foundation touchdown points, budget
constraints and needs for large open spaces for functionality
purposes. The frequency criteria governing the design and
limited the designers’ ability to achieve a cost effective system
that met the requirements of the PDD.

It was later understood that the intent of the statement in the


PDD was to provide an essentially vibration free space.
Therefore, comparison studies were conducted to evaluate the
appropriate floor vibration criteria and was presented to the Figure 8: Initial floor vibration methods used
reviewers having jurisdiction.
Study Two:
Each study started with strength and deflection checks as this Then as an apples to apples comparison, the stringent 9Hz
defined the member’s minimum size prior to evaluating the frequency criteria was applied instead of the 0.5%g
floor as it relates to vibration. The floor system was comprised acceleration criteria.
of a typical 30 foot by 30 foot repeating grid of steel framing
with composite metal deck slab. These results yielded in a significant uptick in steel quantities
relative to the starting point of meeting strength and deflection
Study One: checks. The methods used for the initial studies were Finite
To respond to the floor vibration project needs, the most Element Analysis tools and hand calculations to verify that the
stringent acceleration criteria of 0.5%g, which is reserved for floor systems met the 9Hz frequency criteria.
offices, residences, and churches, was recommend. These
results yielded in a slight uptick in steel quantities relative to Below is a comparison of steel quantities when employing the
the starting point of meeting strength and deflection checks. stringent, essentially vibration free structure, criteria of 0.5%g
acceleration limit versus the 9 Hz frequency criteria. One can
A computer analysis model was built using the SAP Finite see that the steel savings can be significant due to the large area
Element Analysis (FEA) package to conduct an elastic of the repeating structure.
Frequency Response Function (FRF) and Time History
Analysis (THA) with Fourier Series Transform Walking Approximate Budge
Floor Vibration Steel
Functions. Savings Relative to 9
Criteria Quantities
Hz Criteria
0.5%g
12 psf ~ $3.1M
Acceleration
9 Hz Frequency 18 psf $0
Table 5: Summary result comparison

Figure 7: 3D SAP analysis model

7
2017 SEAOC CONVENTION PROCEEDINGS

Figure 9: 0.5%g limit Figure 10: Frequency 9Hz criteria

Therefore, it is recommended that the frequency evaluation


criteria only be used in the initial design phase as rules of
thumb and additional evaluations with stand practice
acceleration and velocity based approaches be used to verify
acceptance of a floor structure in its response to walking
excitations.

Structural Dynamic Properties

All structures have dynamic properties and natural modes of


vibration. Each of these modes has a spatial distribution of
displacement otherwise known as mode shapes. The natural
modes are a structure’s “preferred” displaced shape if it were
to be excited by a sudden impact. Consider a one-way
spanning floor system in Figure 11, idealized as a uniformly
loaded simply supported beam. Some of the beams lowest

8
2017 SEAOC CONVENTION PROCEEDINGS

mode shapes could be excited by someone walking at mid- Recommendations for


Area of Use
span. This would cause the floor to vibrate as shown. Live Loads (psf)1,2,3
Laboratories
As depicted in the figure below, the natural frequency of the
structure depends on the beams, stiffness, supporting weight,
damping, and for concrete, the amount of cracking at service
Live Loads
level loading. The structures response to an impulse load
Range 8-15
generates vibration displacement, velocity and acceleration
amplitudes that all vary in a sinusoidal shape when plotted
against time. The structures amplitude of vibration decaying
with time at its specific rate, which is depended on the amount
of damping that the system has from both structural and non- Office Spaces
structural components.

Live Loads
Range 6-11

Museums, Malls, Airports, and


similar spaces.

Live Loads
Range 0-5

1
Loads are to be taken on a case-by-case basis and evaluated
Figure 11: Simple span with mid-span impulse for each space.
2
Exterior wall loads should be included as line loads, where
Stiffness – the stiffness can be calculated for any structural applicable, as dead loads.
3
system. It is important to include all contributions where Be sure to include ceiling, mechanical, electrical and
applicable such as composite behavior, appropriate damping plumbing weights as part of the superimposed dead loads.
ratios, post-tensioned behavior, cracked properties under Table 6: Recommended live loads
vibration loading, etc... Also, note that the correct boundary
support conditions should be used and are important for Damping – damping is variable and difficult to determine.
smaller models representing larger floor plates as they have a The damping can largely vary due to the structural system and
large effect on the structural response. how the designated space is being used. The recommended
values from reference (Allen, D.E. and Murray, T.M., 1993)
Mass – the mass attributed to the floor system response is vary from 2-3% for bare concrete floors to 5-8% with full
typical defined as total dead load of the structure, portions of height partitions where steel composite floors vary from 1%
the superimposed dead loads and expected service level live for bare structure up to 5% with full height partitions.
loads. Here are some recommendations for expected service
level live loads for varying floor occupancies. It is recommended to use the bare structure damping for open
spaces similar to malls, airports, museum, etc… However, as
larger groups use such spaces, larger live loads and damping
will be present as humans themselves will load the space and
act as great dampers, therefore, group effects should be
considered with the appropriate adjustments to the design
parameters.

Similarly for laboratories with high flexibility, varying


damping studies should be used to provide the designer with a
deeper understanding of the floor systems’ response.

9
2017 SEAOC CONVENTION PROCEEDINGS

Natural Frequency – refer to frequency evaluation criteria bit stringent, but due to the high profile project and vibration
section above. concerns, such criteria was employed.

After generating the analysis model with the appropriate


member sizes for gravity, seismic, and deflection criteria, the
first natural mode for both vertical and horizontal frequencies
were obtained and shown below. As stated before, the
horizontal frequency is important to help reduce the “lock-in”
effect from multiple walkers. Further evaluation can be
conducted if the frequency cannot be met.

Figure 13: 150 foot long span truss framing


Figure 12: Steady-state response of mass-spring-damper
system to sinusoidal force By using the following values attained from the analysis model
Resonant Build-Up – resonant build-up is the phenomenon of
 First vertical frequency = 3.9 Hz
having a step frequency aligned with the system’s natural
 Weight = 505 kips
frequency, thereby increasing the response of the structure due
to the step excitation. For a retrofit type remedy, reducing mass  Damping ratio = 2%
while maintain the stiffness can help shift the frequency further  Constant Force Po = 92 lbs for footbridge
away from the step frequency by minimizing finishes and/or  Acceleration limit = 0.5%g
removing segments of the beam about the web region. Also,
the use of dampers or a floating floor on an isolation plane may
.
prove to be more cost effective in retrofit cases.

Design Methods and Procedures


. ∗ .
92 ∗
∗ 100 0.23% 0.5%
Hand Calculations – Single versus Multiple Walkers 0.02 ∗ 505,000

Hand calculations are easily programmable in varying However, when it comes to multiple walkers, the input
software packages and examples for regular and repeating variables are adjusted and are as follows.
structures can be found in many design guides and standards
which are not covered in this article. However, to address  First vertical frequency = 3.9 Hz
multiple walkers, simplified hand calculations can be useful  Weight = 505 kips (conservatively did not included the
when used with FEA analysis models to attain the structure’s added weight of the occupants)
vertical frequencies.  Damping ratio = 5%
o Humans work well as dampers, therefore, it can be
For the given project example, a one story vierendeel steel seen that damping for multiple walkers can range
truss was used on each face of the walk way to span the 150 from 4 to 8%. The appropriate values should be used
foot gap between two steel braced frame core buildings. As a to take into consideration all aspects of the structural
starting point for floor vibration, the system was first designed and non-structural components.
for gravity, seismic and deflection based design criteria.

The agreed upon floor vibration criteria for this specific case
was defined as 0.5%g for a single walker and 1.5%g for a
group of walkers. These acceleration limits may be seen as a

10
2017 SEAOC CONVENTION PROCEEDINGS

 Number of walkers
o Full length = 150 feet  utilized the middle half for
active walkers = 75 feet.
o Width = 10’-6” clear allows for about three rows of
passengers, side by side walkers.
o Walking stride = 3 feet.

o Therefore, the number (No) of passengers are 75 feet


* 3 people per row / 3 foot stride = 75 active walkers

Figure 14: FRF flow chart


. ∗ .
92 ∗
√75 ∗ 100 1.3% 1.5% Before embarking on a project specific example a key topic to
0.03 ∗ 505,000
understand is harmonic and sub-harmonic frequencies.
Harmonic and sub-harmonic frequencies are integer
As shown above, hand calculations are still viable for both
representations of the step frequency. For example, the
simple evaluations in the design phase as well as verifying the
harmonic frequency of a 2 Hz step frequency are 4 Hz, 6 Hz,
analysis results from more refined and elaborate analysis
8 Hz, etc… A sub-harmonic frequency is an integer
procedures.
subdivision of a system frequency. For example the fourth
sub-harmonic frequency of an 8 Hz natural system frequency
Frequency Response Functions (FRF)
is 2 Hz (8 Hz / 4th sub-harmonic = 2 Hz). Therefore, the 2 Hz
step frequency is the fourth sub-harmonic of the system
Frequency Response Function (FRF) is a plot of sinusoidal
frequency.
response verse frequency which indicates the dominant natural
frequencies for the floor system. The reason for such analysis
The following project examples are used to elaborate on the
is that FRF procedures can be used to evaluate structural
provided flow chart in evaluating a structural system with the
systems that are not regular, have non-uniform loading, have
FRF method. The project example is from a 20 story
flexible supports, and/or contain cantilevers/balconies. This
residential tower to be located in San Francisco, California.
section presents the methodology and tips when conducting
The superstructure consists of a reinforced concrete shear wall
FRF to evaluate a structures response.
core and perimeter gravity columns with two-way flat plate
post-tensioned slab framing. The slab clear spans from the
core to the perimeter columns then typically cantilevers 8’-0”
beyond the perimeter columns.

11
2017 SEAOC CONVENTION PROCEEDINGS

d. Define the damping, see sections above for further


discussion.

Define the number of modes.


a. At a minimum take the first frequency and multiply by 2.
b. It is also recommended to have enough mode shapes to
reach about 8 Hz.

Figure 15: Typical floor plan


Generating the Frequency Response Function
Summary Methodology a. Define the frequency band lower limit as 1Hz below the
fundamental frequency.
Define the analysis model b. Define the frequency band upper limit as 1Hz above the
a. Define the geometry, boundary conditions and mesh the maximum computed modal frequency.
model. c. Compute and plot the sinusoidal steady-state response at
i. The mesh should be sufficient if further refinements locations of interested relative to the unit amplitude
do not result in natural frequency changes larger than sinusoidal load at the point of application.
0.05 to 0.1 Hz.
ii. Meshes typically at 1/10 the bay size are usually
adequate.

b. Define material properties, reference design guide 11 2nd


Peak acceleration and compare to acceleration criteria.
edition.
a. Define the respective system frequency and steady-state
i. Include 1.35 factor for concrete modulus of elasticity.
acceleration at all peaks, in this case there were 5.
ii. Include 2.5 stiffness factor about the perimeter beam.
b. Define the harmonic at each peak steady-state
iii. If steel framing is used, all simple shear connections
acceleration.
can be assumed to be fixed.
i. In the example given above, the fifth peak systems
iv. Include cracked properties under service level loads.
frequency and associated peak steady-state
acceleration are 7.2 Hz and 0.03%g respectively.
c. Apply appropriate loading
ii. The typical walker (1.6 Hz to 2.2 Hz) step frequency
i. Include the exterior wall loads, reduced
is the 4th harmonic of the fifth system frequency peak
superimposed dead and live loads to represent
(7.2 Hz / 4 = 1.8 Hz), therefore, the harmonic
realistic day to day loading conditions.
amplitude factor can be obtained (Willford et al.
2007).

12
2017 SEAOC CONVENTION PROCEEDINGS

iii. Calculate the resonant build-up factor . peak-to-peak velocity or acceleration, narrowband spectral
1 velocity or acceleration, or one-third octave spectral velocity
or acceleration.
iv. Then calculate the fifth peak acceleration which is the
product of the fifth peak steady-state acceleration Floor evaluations and designs should be based on specific
from SAP, the harmonic amplitude factor, the limits for the equipment to be used in the space when possible.
average body weight (168 lb Willford et al. 2007) and However, if the equipment items or their tolerances are not
the fifth peak resonant build-up factor. known, it has become typical practice to rely on generic
tolerance limits, which can be seen in AISC DG 11 2nd Edition.

Similarly to the FRF methodology, the THA methods are


based on the fundamental mode/s of the floor system,
therefore, for a given floor system, one needs an estimate of
the natural frequency, effective weight, mode shapes, walking
excitation functions and estimated damping. Also similar to
FRF methodologies, this approach can be used to evaluate
structural systems that are not regular, have non-uniform
loading, have flexible supports, and/or contain
v. Then compare the peak acceleration to the cantilevers/balconies. This section presents the methodology
acceleration criteria. and tips when conducting THA to evaluate a structures
response.
The summary of all five peaks and their respective peak
acceleration are shown below. It should be noted that the
largest frequency with the largest separation between a typical
walker (4th harmonic in this case) generated the largest peak
acceleration, therefore, such results further supports that
frequency based design criteria are not appropriate in design
for floor vibration due to walking excitations.

Table 7: Summary acceleration results

Time History Analysis (THA)

The use of Time History Analysis (THA) is more applicable to


evaluating vibration of floors supporting sensitive equipment,
such as precision imaging, measurement, manufacturing
instruments, and floors supporting sensitive occupancies such
as laboratories, hospital patient rooms, and operating rooms.

The tolerance limits relating to human comfort typically are


stated in terms of sinusoidal acceleration or velocities at a Figure 16: THA flow chart
single frequency. In contrast, the suppliers of sensitive
equipment often provide specific tolerance limits in terms of

13
2017 SEAOC CONVENTION PROCEEDINGS

The following project examples are used to elaborate on the


provided flow chart in evaluating a structural system with the
THA method. The project example is for a five story
laboratory structure to be located in Merced, California. The
superstructure consists of reinforced concrete shear walls and
gravity columns with two-way flat plate conventionally
reinforced concrete slab framing. The slab spans the typical
31’-6” by 21’-0” grid.

c. Define governing walking scenarios to evaluate the floor


system, examples given below.
Figure 17: Typical floor plan Scenario 1 - Excitation = 100 steps/min in corridor
Measured responses in adjacent lab area
Summary Methodology – Refer to FRF information above Scenario 2 - Excitation = 75 steps/min to lab area
Measured response in lab at 3 feet away
Define the analysis model from point of excitation
a. Define the geometry, boundary conditions and mesh the Scenario 3 - Excitation = 100 steps/min in corridor
model. Measured responses in adjacent to office
area
Scenario 4 - Excitation = 75 steps/min in office area
Measured response in office area at same
location of excitation
Scenario 5 - Excitation = 75 steps/min in lab space
within 5 feet of column lines
Measured response in lab at same
location of excitation to verify response
for more stringent 500 in/sec criteria.

b. Define material properties, reference AISC DG 11 2nd Ed.


i. Include cracked properties under service level loads.

14
2017 SEAOC CONVENTION PROCEEDINGS

d. Apply appropriate floor system loading as well as the f. Define and verify the damping. It is recommend to
footfall loading. It is recommend to conduct both AISC conduct the analysis with pure structural damping and
DG 11 2nd Edition and Obata Miyamori footfall functions with assumed additional damping from non-structural
to bound the analysis and attain a better understanding of components, thereby providing a bounded analysis. It is
the floor responses. up to the design team to define the appropriate damping to
take in consideration the planned and potential future use
i. Define both footfall functions of the space.
Design Guide 11
The damping can be verified by using simple dynamics.
Plot the acceleration and measure the peaks and time
between peaks after the footfall function has stopped.

Obata Miyamori

Define the number of modes.


a. At a minimum take the first frequency and multiply by 2.
b. It is also recommended to have enough mode shapes to
reach about 8 Hz.
e. Define the Vibration Criteria

15
2017 SEAOC CONVENTION PROCEEDINGS

Generating Velocity Responses Plots and Compare to Criteria

Figure 18: THA walking path

The use of walking paths are a special case used and should
only be used to supplement the scenario approach. Also, this
effect can be used in studying large long-span structures for
group effects where such verification is warranted.

Additional Considerations

When evaluating floor vibrations, non-structural components


For the case study shown above, five steps were applied at a play a large role in the floor response, either by providing a
particular point and the floor response was either measured stiffening effect and/or increasing the systems’ damping.
conservatively at the same location or about 3 feet away Therefore, for floor systems that are governed by floor
mimicking the plan dimension of a human. Five steps were vibration, additional refinement may need to be incorporated
used to verify that the walking frequency didn’t generate in the analysis and response. Also the use of field testing is
resonant build-up, therefore the floor response before and after not an unreasonable request for highly sensitive areas so
the stop time of the walking excitation responses are equally appropriate action can be employed if needed.
important to the designer.
Exterior Wall Effects
As it relates to the THA methodology, further refinement can
be used in special cases. The use of walking paths with THA Modeling
can be used and allows the designer to model the walker along As previously stated and defined in AISC DG 11 2nd Edition,
a walking path/s to then verify if the response of the floor the edge of slab is stiffened to about 2.5 times due to the
system meets the human perceptive criteria of acceleration exterior wall. Additionally, it should be noted that the
and/or velocity, see Figure 18. It is important to mesh the slab mullions of an exterior wall system may also be used to help
to the approximate stride dimension of 2.5 feet. reduce the perceivable accelerations generated from walking
by sharing such load distribution between levels, thereby
achieving the acceleration criteria.

16
2017 SEAOC CONVENTION PROCEEDINGS

An example below is from the same 20 story residential tower


case study defined above. Here you will see a comparison of
floor vibration with and without the vertical exterior wall steel
mullions.

Table 8: Summary acceleration responses

As shown in the tables above, the acceleration effects when


including the mullion contributions are significant. Non-
structural components do play a large role in the structural
performance, and the designer should include such
contributions when warranted.

Testing
As it relates to non-structural components and mass, testing
was conducted for a project in Los Angeles, California. We
also attained Professor Thomas Murray and Brad Davis to
predict and measure the performance of the structural system.
Figure 19: Mullion comparison A summary of key points are shared herein.
The modeling process is simple enough, by adding the steel
The floor vibrations due to walking at the northeast
mullion column element with a moment, shear, and torsional
cantilevered corner were measured during construction. Floor
release at the top and bottom in a staged construction manner,
acceleration measurements were made for the bare slab
after all the appropriate loads are applied to the floor system,
condition, and then with 10.2 psf superimposed dead load,
one can capture the behavior of the component. As the loading
partitions, and simulated curtain wall weight added
from a walking excitation, the friction of the bolted type
incrementally. Also, a finite element model of the structural
connection can be seen an active axial support similarly to steel
framing was developed and tuned using initial measurement
shear tab connections acting as a moment connection. If a more
data. The model was then used to predict floor vibration
refined analysis is needed, a spring can be added instead of this
response of the occupied areas. Architectural and structural
simplified approach to account for the friction of the snug tight
plans of the corner are shown below.
bolted connection.

17
2017 SEAOC CONVENTION PROCEEDINGS

1. bare structure

Figure 20: Northeast floor plan


2. Item 1 plus 10.2 psf superimposed dead load (CMU
The primary concern was the vibration of the judicial chamber blocks were used)
at the corner. Therefore the most stringent limit for human
perceptibility and comfort of 0.5%g was incorporated (AISC
DG 11 2nd Edition).

The level 2 structural system consisted of 3 inch metal deck +


4.5 inch normal weight concrete fill supported by wide flange
steel beams and girders. All other levels, the structural system
consisted of 3 inch metal deck + 3.25 inch light weight
concrete fill supported by wide flange steel beams and girders.
Additionally at the corner, a telescoping mullion connection
for the building’s curtain wall was also present.

3. Item 2 plus selected interior dry wall partitions (partitions


were constructed for testing purposes)
(a) Female Connection (b) Male Connection
Figure 21: Typical curtain wall unit

The floor vibration measurements were made on Levels 02 and


04 during construction. Measurements were made for each of
the flour floor conditions:

18
2017 SEAOC CONVENTION PROCEEDINGS

4. Item 3 plus curtain wall weight (bundled reinforcement were then completed to provide a predicted in-service
were used to mimic floor line loading) responses.

(a) Level 02 Comparisons

For each floor condition on each level, ambient and heal drop
measurements were first recoded from which the natural
frequency or frequencies were determined. Then controlled
and natural walking measurements were made along two
paths to determine maximum walking responses.

(b) Level 04 Comparisons


Table 9: Summary comparisons

Conclusion
(a) North-South Walking Path
The objective of this article was to provide project specific
examples to show how to define the appropriate design criteria,
parameters, and conduct varying design methodologies to
achieve a more cost effective solution.

An additional objective of this article was to expose the


limitations generated when using frequency as an acceptance
criteria. Frequency based design limits ignores other
important factors such as damping and the significant impact
that frequency holds in evaluating a floor system with standard
practice acceleration and velocity based methods. Frequencies
should not be ignored, however, they should be used as rules
(b) Corner Walking Path of thumb in initial design phases, thus, allowing the designer
Figure 22: Walking paths to use appropriate methods to meet the Client’s expectations
and project needs in a more cost effective manner. Therefore,
The comparison between the actual and the initial predicted using industry standards of acceleration and velocity based
models were seen to be close. With the information obtained approaches should be the primary method in evaluating if a
through measurement, tuning of the finite element modeling floor system is adequate when subjected to walking
excitations.

19
2017 SEAOC CONVENTION PROCEEDINGS

Acknowledgements References

The authors gratefully acknowledge the forward thinking Applied Technology Council (ATC). 1999. ATC Design
leading experts of floor vibration Professor Thomas Murray Guide 1 – Minimizing Floor Vibration. ATC. Redwood City,
Ph.D., P.E. and Brad Davis, Ph.D, S.E. for the joint efforts CA.
conducted on numerous projects here at SOM. The common
pursuit of obtaining a deeper understanding of the appropriate Chopra, A.K. (2001). Dynamics of Structures: Theory and
structural methods of evaluation, design criteria and structural Applications of Earthquake Engineering, 2nd Edition, Prentice
responses to obtain more cost effective solutions are Hall, Upper Saddle River, New Jersey.
paramount. This support is critical in achieving enhanced
designs while meeting the Clients expectations and project’s Murray, T.M., Allen, D.E., and Ungar, E.E. (1997). Steel
needs. Design Guide Series 11: Floor Vibrations Due to Human
Activity, American Institute of Steel Construction (AISC),
Abbreviations Chicago, Illinois

AISC - American Institute of Steel Construction Murray, T.M., Allen, D.E., and Ungar, E.E. (2016). Steel
a0 - Peak acceleration tolerance limit Design Guide Series 11: Floor Vibrations Due to Human
- Acceleration tolerance limits, see Figure 3 Activity Second Edition, American Institute of Steel
Construction (AISC), Chicago, Illinois
ap - Peak acceleration
- Ratio of peak floor acceleration to gravity Murray, T. M., Allen, D. E., and Ungar, E. E., “Floor
ASCE - American Society of Civil Engineers Vibrations Due to Human Activity,” AISC, 2003.
DG - Design Guide
E - Elastic modulus Murray, T. M., Ungar, E. E., Davis B.D., “Facts for Steel
FEA - Finite element analysis Buildings No 5 – Vibration Steel-Framed Structural Systems
fn - Fundamental natural frequency, Hz Due to Human Activity.” AISC 2017.
FRF - Frequency Response Function
g - Acceleration of gravity Obta, T. and Miyamori, Y. (2006). “Identification of a Human
H - Harmonic Walking Force Model Based on Dynamic Monitoring Data
Hz - Hertz from Pedestrian Bridges.” Computers and Structures.
I - Flexural moment of inertia
in - Inches Willford, M., Field, C., and Young, P. (2006). “Improved
kips - kips = 1000 lbs Methodologies for the Prediction of Footfall-Induced
L - Length Vibration.” Proceedings of the 2006 Architectural
lb - Pounds Engineering National Conference, ASCE, Reston, Virginia.
N - Number of steps
No - Number of walkers Willford, M., Young, P., and Field, C. (2007). “Predicting
Po - Amplitude of the driving force Footfall-Induced Vibration: Part I.” Structures and Buildings,
psf - Pounds per square foot 160(SB2).
Q - Bodyweight, lb, 157 lb
SAP - Structural Analysis Program Willford M., Young P., (2006). “A Design Guide for Footfall
SEAOC - Structural Engineers Association of California Induced Vibration of Structures.” The Concrete Centre.
SOM - Skidmore, Owings & Merrill LLP
THA - Time History Analysis
VC - Vibration Control
w - Distributed load
W - Effective weight of the floor, lb
 - Dynamic coefficient
 - Damping ratio
 - Deflection
inch - Microinches
 - Resonant build-up factor

20

Вам также может понравиться