Академический Документы
Профессиональный Документы
Культура Документы
1
2017 SEAOC CONVENTION PROCEEDINGS
2
2017 SEAOC CONVENTION PROCEEDINGS
3
2017 SEAOC CONVENTION PROCEEDINGS
4
2017 SEAOC CONVENTION PROCEEDINGS
Vibration
Walking
Area of Use (Primary Velocity
Speed
Factor)1,2,3 Maximum
(steps/min)
(inch/sec)
100 to
Corridors 8,000
1251
Lab Offices / Patient Rooms 4,000 100
Surgical Suites (Human) 4,000 75
Laboratories and Laboratory
2,000 100
Support Rooms
Surgical Suites
1,250 75
(40X Surgical Microscope)
Imaging (MRI) / Surgical
Suites 500 50 to 75
(100X Surgical Microscope)
Electron Microscope 250 50 to 75
1
Spacing adjacent to corridors shall be evaluated to consider
vibration excitation from the corridors.
Figure 5: Generic vibration criteria (VC) curves 2
Use local isolation systems for mechanical equipment to limit
structure bone vibration to adjacent occupied areas.
3
Provide additional floating reinforced concrete slab on
isolation pads or mechanical isolation systems at sensitive
equipment where required.
Table 3: Recommended laboratory velocity limits with
respective walking excitation speeds
5
2017 SEAOC CONVENTION PROCEEDINGS
In structural engineering, frequency can also be defined as a Therefore when using a peak acceleration based approach,
displacement through its relationship with mass and stiffness. each variable and their appropriate contributions are
Looking at a simply supported beam with a uniformly incorporated in the acceleration inequality expression, thus,
distributed load, one can derive the first natural frequency: allowing a thorough investigation of all parameters when
looking to solve the needs of the project rather than looking at
a singular deflection criteria. That being said, frequency
should be used in the early design phases as rules of thumb in
2 the absence of acceleration and velocity calculations.
By rearranging the expression and substituting the maximum For example keeping the vertical frequencies at about 3 to 5
deflection equation in the first natural frequency formula, it Hz can be a starting point for typical office spaces, 5 to 6 Hz
can be seen that frequency can be distilled down to a for typical lab spaces, and 6 to 8 Hz for lab spaces with
displacement based criteria. sensitive equipment excluding VC-D and VC-E type
equipment. Whereas 2 Hz may be deemed appropriate for
extremely long one-way span type structures where there is a
5 5 5 significant amount of mass that needs to be excited and/or
∆ → →
384 384∆ 2 384∆ dampers are implemented.
6
2017 SEAOC CONVENTION PROCEEDINGS
would yield that the floor framing system shall not deflect
more than about 1/8 of an inch no matter what spans are used.
As one can see, this frequency limit will have a dramatic effect
not only on the space, as additional vertical elements will be
required, but also the amount of material needed for the floor
framing to meet the frequency/deflection criteria.
7
2017 SEAOC CONVENTION PROCEEDINGS
8
2017 SEAOC CONVENTION PROCEEDINGS
Live Loads
Range 6-11
Live Loads
Range 0-5
1
Loads are to be taken on a case-by-case basis and evaluated
Figure 11: Simple span with mid-span impulse for each space.
2
Exterior wall loads should be included as line loads, where
Stiffness – the stiffness can be calculated for any structural applicable, as dead loads.
3
system. It is important to include all contributions where Be sure to include ceiling, mechanical, electrical and
applicable such as composite behavior, appropriate damping plumbing weights as part of the superimposed dead loads.
ratios, post-tensioned behavior, cracked properties under Table 6: Recommended live loads
vibration loading, etc... Also, note that the correct boundary
support conditions should be used and are important for Damping – damping is variable and difficult to determine.
smaller models representing larger floor plates as they have a The damping can largely vary due to the structural system and
large effect on the structural response. how the designated space is being used. The recommended
values from reference (Allen, D.E. and Murray, T.M., 1993)
Mass – the mass attributed to the floor system response is vary from 2-3% for bare concrete floors to 5-8% with full
typical defined as total dead load of the structure, portions of height partitions where steel composite floors vary from 1%
the superimposed dead loads and expected service level live for bare structure up to 5% with full height partitions.
loads. Here are some recommendations for expected service
level live loads for varying floor occupancies. It is recommended to use the bare structure damping for open
spaces similar to malls, airports, museum, etc… However, as
larger groups use such spaces, larger live loads and damping
will be present as humans themselves will load the space and
act as great dampers, therefore, group effects should be
considered with the appropriate adjustments to the design
parameters.
9
2017 SEAOC CONVENTION PROCEEDINGS
Natural Frequency – refer to frequency evaluation criteria bit stringent, but due to the high profile project and vibration
section above. concerns, such criteria was employed.
Hand calculations are easily programmable in varying However, when it comes to multiple walkers, the input
software packages and examples for regular and repeating variables are adjusted and are as follows.
structures can be found in many design guides and standards
which are not covered in this article. However, to address First vertical frequency = 3.9 Hz
multiple walkers, simplified hand calculations can be useful Weight = 505 kips (conservatively did not included the
when used with FEA analysis models to attain the structure’s added weight of the occupants)
vertical frequencies. Damping ratio = 5%
o Humans work well as dampers, therefore, it can be
For the given project example, a one story vierendeel steel seen that damping for multiple walkers can range
truss was used on each face of the walk way to span the 150 from 4 to 8%. The appropriate values should be used
foot gap between two steel braced frame core buildings. As a to take into consideration all aspects of the structural
starting point for floor vibration, the system was first designed and non-structural components.
for gravity, seismic and deflection based design criteria.
The agreed upon floor vibration criteria for this specific case
was defined as 0.5%g for a single walker and 1.5%g for a
group of walkers. These acceleration limits may be seen as a
10
2017 SEAOC CONVENTION PROCEEDINGS
Number of walkers
o Full length = 150 feet utilized the middle half for
active walkers = 75 feet.
o Width = 10’-6” clear allows for about three rows of
passengers, side by side walkers.
o Walking stride = 3 feet.
11
2017 SEAOC CONVENTION PROCEEDINGS
12
2017 SEAOC CONVENTION PROCEEDINGS
iii. Calculate the resonant build-up factor . peak-to-peak velocity or acceleration, narrowband spectral
1 velocity or acceleration, or one-third octave spectral velocity
or acceleration.
iv. Then calculate the fifth peak acceleration which is the
product of the fifth peak steady-state acceleration Floor evaluations and designs should be based on specific
from SAP, the harmonic amplitude factor, the limits for the equipment to be used in the space when possible.
average body weight (168 lb Willford et al. 2007) and However, if the equipment items or their tolerances are not
the fifth peak resonant build-up factor. known, it has become typical practice to rely on generic
tolerance limits, which can be seen in AISC DG 11 2nd Edition.
13
2017 SEAOC CONVENTION PROCEEDINGS
14
2017 SEAOC CONVENTION PROCEEDINGS
d. Apply appropriate floor system loading as well as the f. Define and verify the damping. It is recommend to
footfall loading. It is recommend to conduct both AISC conduct the analysis with pure structural damping and
DG 11 2nd Edition and Obata Miyamori footfall functions with assumed additional damping from non-structural
to bound the analysis and attain a better understanding of components, thereby providing a bounded analysis. It is
the floor responses. up to the design team to define the appropriate damping to
take in consideration the planned and potential future use
i. Define both footfall functions of the space.
Design Guide 11
The damping can be verified by using simple dynamics.
Plot the acceleration and measure the peaks and time
between peaks after the footfall function has stopped.
Obata Miyamori
15
2017 SEAOC CONVENTION PROCEEDINGS
The use of walking paths are a special case used and should
only be used to supplement the scenario approach. Also, this
effect can be used in studying large long-span structures for
group effects where such verification is warranted.
Additional Considerations
16
2017 SEAOC CONVENTION PROCEEDINGS
Testing
As it relates to non-structural components and mass, testing
was conducted for a project in Los Angeles, California. We
also attained Professor Thomas Murray and Brad Davis to
predict and measure the performance of the structural system.
Figure 19: Mullion comparison A summary of key points are shared herein.
The modeling process is simple enough, by adding the steel
The floor vibrations due to walking at the northeast
mullion column element with a moment, shear, and torsional
cantilevered corner were measured during construction. Floor
release at the top and bottom in a staged construction manner,
acceleration measurements were made for the bare slab
after all the appropriate loads are applied to the floor system,
condition, and then with 10.2 psf superimposed dead load,
one can capture the behavior of the component. As the loading
partitions, and simulated curtain wall weight added
from a walking excitation, the friction of the bolted type
incrementally. Also, a finite element model of the structural
connection can be seen an active axial support similarly to steel
framing was developed and tuned using initial measurement
shear tab connections acting as a moment connection. If a more
data. The model was then used to predict floor vibration
refined analysis is needed, a spring can be added instead of this
response of the occupied areas. Architectural and structural
simplified approach to account for the friction of the snug tight
plans of the corner are shown below.
bolted connection.
17
2017 SEAOC CONVENTION PROCEEDINGS
1. bare structure
18
2017 SEAOC CONVENTION PROCEEDINGS
4. Item 3 plus curtain wall weight (bundled reinforcement were then completed to provide a predicted in-service
were used to mimic floor line loading) responses.
For each floor condition on each level, ambient and heal drop
measurements were first recoded from which the natural
frequency or frequencies were determined. Then controlled
and natural walking measurements were made along two
paths to determine maximum walking responses.
Conclusion
(a) North-South Walking Path
The objective of this article was to provide project specific
examples to show how to define the appropriate design criteria,
parameters, and conduct varying design methodologies to
achieve a more cost effective solution.
19
2017 SEAOC CONVENTION PROCEEDINGS
Acknowledgements References
The authors gratefully acknowledge the forward thinking Applied Technology Council (ATC). 1999. ATC Design
leading experts of floor vibration Professor Thomas Murray Guide 1 – Minimizing Floor Vibration. ATC. Redwood City,
Ph.D., P.E. and Brad Davis, Ph.D, S.E. for the joint efforts CA.
conducted on numerous projects here at SOM. The common
pursuit of obtaining a deeper understanding of the appropriate Chopra, A.K. (2001). Dynamics of Structures: Theory and
structural methods of evaluation, design criteria and structural Applications of Earthquake Engineering, 2nd Edition, Prentice
responses to obtain more cost effective solutions are Hall, Upper Saddle River, New Jersey.
paramount. This support is critical in achieving enhanced
designs while meeting the Clients expectations and project’s Murray, T.M., Allen, D.E., and Ungar, E.E. (1997). Steel
needs. Design Guide Series 11: Floor Vibrations Due to Human
Activity, American Institute of Steel Construction (AISC),
Abbreviations Chicago, Illinois
AISC - American Institute of Steel Construction Murray, T.M., Allen, D.E., and Ungar, E.E. (2016). Steel
a0 - Peak acceleration tolerance limit Design Guide Series 11: Floor Vibrations Due to Human
- Acceleration tolerance limits, see Figure 3 Activity Second Edition, American Institute of Steel
Construction (AISC), Chicago, Illinois
ap - Peak acceleration
- Ratio of peak floor acceleration to gravity Murray, T. M., Allen, D. E., and Ungar, E. E., “Floor
ASCE - American Society of Civil Engineers Vibrations Due to Human Activity,” AISC, 2003.
DG - Design Guide
E - Elastic modulus Murray, T. M., Ungar, E. E., Davis B.D., “Facts for Steel
FEA - Finite element analysis Buildings No 5 – Vibration Steel-Framed Structural Systems
fn - Fundamental natural frequency, Hz Due to Human Activity.” AISC 2017.
FRF - Frequency Response Function
g - Acceleration of gravity Obta, T. and Miyamori, Y. (2006). “Identification of a Human
H - Harmonic Walking Force Model Based on Dynamic Monitoring Data
Hz - Hertz from Pedestrian Bridges.” Computers and Structures.
I - Flexural moment of inertia
in - Inches Willford, M., Field, C., and Young, P. (2006). “Improved
kips - kips = 1000 lbs Methodologies for the Prediction of Footfall-Induced
L - Length Vibration.” Proceedings of the 2006 Architectural
lb - Pounds Engineering National Conference, ASCE, Reston, Virginia.
N - Number of steps
No - Number of walkers Willford, M., Young, P., and Field, C. (2007). “Predicting
Po - Amplitude of the driving force Footfall-Induced Vibration: Part I.” Structures and Buildings,
psf - Pounds per square foot 160(SB2).
Q - Bodyweight, lb, 157 lb
SAP - Structural Analysis Program Willford M., Young P., (2006). “A Design Guide for Footfall
SEAOC - Structural Engineers Association of California Induced Vibration of Structures.” The Concrete Centre.
SOM - Skidmore, Owings & Merrill LLP
THA - Time History Analysis
VC - Vibration Control
w - Distributed load
W - Effective weight of the floor, lb
- Dynamic coefficient
- Damping ratio
- Deflection
inch - Microinches
- Resonant build-up factor
20