Академический Документы
Профессиональный Документы
Культура Документы
METAL FASTENINGS
PART 1 GENERAL
1.1 SECTION INCLUDES
1.3 REFERENCES
05090-1
G. International Standards Organization (ISO).
1.4 SUBMITTALS
C. Samples: For each product specified, two samples in sizes required for
construction.
PART 2 PRODUCTS
2.1 MANUFACTURERS
A. Acceptable Manufacturer: Kee Safety, Inc., which is located at: 100 Stradtman
St. ; Buffalo, NY 14206; Toll Free Tel: 800-851-5181; Tel: 716-896-4949; Email:
request info (info@keeklamp.com); Web: www.keesafety.com/us
05090-2
3. Finish: Hot Did Galvanized.
C. Size:
1. As required or indicated.
D. Components:
1. Grade 8.8 nut, bolt and washer.
2. Top Set of BeamClamp Fixings Type:
a. BA.
b. BB.
c. BE1.
d. BE2.
e. BK1.
f. BT.
g. BW.
3. Packing Pieces Type:
a. BH1.
b. BF1.
c. BG1.
d. BF2.
e. BG2.
4. Location plate.
5. Bottom Set Type:
a. BA.
b. BB.
c. BE1.
d. BE2.
e. BK1.
f. BT.
g. BW.
05090-3
2.5 EXPANSION BOLT
PART 3 EXECUTION
3.1 EXAMINATION
C. Verify that components are of the correct quantity, types, finishes, and sizes
specified for Work of this Section.
3.2 INSTALLATION
END OF SECTION
05090-4
SECTION 05155
PART 4 GENERAL
4.1 SECTION INCLUDES
4.3 REFERENCES
05090-5
B. American Society for Testing and Materials (ASTM) A572 / A572M - Standard
Specification for High-Strength Low-Alloy Columbium-Vanadium Structural Steel.
4.4 SUBMITTALS
B. Design Requirements:
1. Tension/compression rod and cabling systems shall perform as an
aesthetic element fulfilling the design intent as well as a structural component
of the building structural system or building element as indicated and
scheduled.
C. Service Requirements:
1. Tension/compression rod and cabling systems shall comply with safety
factors, anticipated loads imposed or induced as scheduled or required and
with local building code, requirements of authorities having jurisdiction.
2. Load carrying and resisting capacity shall comply with A58.l Minimum
Design Loads in Buildings and Other Structures.
D. Structural Requirements:
1. Assembly shall be analyzed and modeled using finite analysis.
2. Structural Performance: Tension/compression rod and cabling systems
shall withstand the effects of gravity loads and the following loads and
stresses within limits and under conditions scheduled.
3. Seismic Performance: Tension/compression rod and cabling
systems shall withstand the effects of earthquake motions determined
according to ASCE/SEI 7.
a. Component Importance Factor is 1.5.
05090-6
4.6 DELEGATED DESIGN
D. Design Approval. The design agent will submit a set of pre-final drawings and
project specifications to the respective AHJ representatives for review to ensure
compliance with applicable codes and regulations.
05090-7
jurisdiction.
PART 5 PRODUCTS
5.1 MANUFACTURERS
A. Acceptable Manufacturer: Decon® USA, which is located at: 103 E. Napa St.
Suite B P. O. Box 1486 ; Sonoma, CA 95476; Toll Free Tel: 866-DECON-US; Tel:
707-996-5954; Email: request info (sales@decon.ca); Web: www.deconusa.com
5.2 MATERIALS
05090-8
which combine the function of a lock nut and a blending thread cover.
3. Adjustment: The standard left hand- right hand tendon shall provide
adjustment to accommodate site and manufacturing tolerances:
a. Adjustment for rods M10, 3/8 inch (9.5 mm) to M56, 2-1/4 inches
(57 mm) plus or minus 1/2 inch (13 mm) thread diameter each end.
b. Adjustment for rods M64, 2-1/2 inches (63.5 mm) to M100, 4
inches (102 mm) plus or minus 1 inch (25 mm) each end.
c. Turnbuckles give additional adjustment of:
1) M10 3/8 inch (9.5 mm) - M24 1 inch (25 mm): plus or
minus 1 (25 mm).
2) M30 1-1/4 inch (32 mm) - M100 4 inch (102 mm): plus or
minus 2 inches (51 mm)
4. Fabrication Tolerance:
a. Cutting tolerance for rods: up to M76, 3 inches (76 mm) plus or
minus 1/4 inch (6 mm).
b. Cutting tolerance for rods: over M76, 3 inches (76 mm) plus or
minus 1 inch (25 mm).
c. Maximum lengths
1) M10 3/8 inch (9.5 mm) - M16 5/8 inch (16 mm): 19 feet 6
inches (6 meters).
2) M20 3/4 inch (19 mm) - 29 feet 6 inches (9.0 meters).
3) M24 1 inch (25 mm) - M100 4 inch (102 mm): 39 feet 2
inches (11.95 meters).
5. Coating: Galvanizing as scheduled.
6. Coating: Priming as scheduled.
7. Coating: Painting as scheduled.
8. Coating: Plating.
9. Connection: The connection to the structure shall be made by utilizing
a connection plate with the same thickness and edge distance as the
manufacturer's spade. Engineered fabricated building connections shall be
made using standard grade 50 material.
05090-9
permitted.
d. Couplers and Turnbuckles: As indicated or required.
e. Architectural fittings shall be furnished to provide a smooth
transition from the bar to the fork by the use of threaded lock covers,
which combine the function of a lock nut and a blending thread cover.
3. Adjustment: The standard left hand- right hand tendon will provide
adjustment to accommodate site tolerances:
a. Adjustment for rods M10, 3/8 inch (9.5 mm) to M56, 2-1/4 inches
(57 mm) plus or minus 1/2 inch (13 mm) thread diameter each end.
b. Adjustment for rods M64, 2-1/2 inches (63.5 mm) to M100, 4
inches (102 mm) plus or minus 1 inch (25 mm) each end.
c. Turnbuckles give additional adjustment of:
1) M10 3/8 inch (9.5 mm) - M24 1 inch (25 mm): plus or
minus 1 inch (25 mm).
2) M30 1-1/4 inch (32 mm) - M100 4 inch (102 mm): plus or
minus 2 inch (51 mm).
4. Fabrication Tolerance:
a. Cutting tolerance for rods up to M56, 2-1/4 inches (57 mm) plus
or minus 1/4 inch (6 mm).
b. Adjustment for rods up to M10, 3/8 inch (9.5 mm) plus or minus
1/2 inch (12 mm) each end.
c. Maximum lengths:
1) M10 3/8 inch (9.5 mm) - M56 2 1/4 inch (57 mm): 24 feet
7 inches (7.5 meters).
2) M64 2 1/2 inch (63.5 mm) - M100 4 inch (102 mm): 19
feet 6 inches (6.0 meters).
5. Coating: Rods shall be finished with a light satin finish approximately
equal to an N3 finish.
6. Connection: The connection to the structure shall be made by utilizing
a connection plate with the same thickness and edge distance as the
manufacturer's spade. Engineered fabricated building connections shall be
made using standard grade 50 material or stainless equivalent.
a. If connecting stainless steel to carbon steel, measures shall be
taken to prevent bimetallic corrosion. Isolation bushings and washers
shall be provided to minimize bimetallic corrosion.
05090-10
connection which has yield strength equal to the minimum tendon yield
strength.
b. Spades shall be designed to be connected to forks or between
grade 50 plates simulating a fork/spade connection.
c. Pins connect the fork or spade to the host structure and may be
held in place with either safety rings or architectural caps indicated or
required.
d. Lock covers shall lock the components in place and hide the
remainder of the rod thread form and provide an aesthetic and smooth
transition from component to rod. Provide at either side of the
turnbuckle or coupler and at the back end of a fork or spade indicated
or required.
e. Couplers and Turnbuckles: As indicated or required.
f. Architectural fittings shall be furnished to provide a smooth
transition from the bar to the fork by the use of threaded lock covers,
which combine the function of a lock nut and a blending thread cover.
4. Adjustment: The standard left hand- right hand tendon shall provide
adjustment to accommodate site and manufacturing tolerances:
a. Adjustment for rods M10, 3/8 inch (9.5 mm) to M56, 2-1/4 inches
(57 mm) plus or minus 1/2 inch (13 mm) thread diameter each end.
b. Adjustment for rods M64, 2-1/2 inches (63.5) to M100, 4 inches
plus or minus 1 inch (25 mm) each end.
c. Turnbuckles give additional adjustment of:
1) M10 3/8 inch (9.5 mm) - M24 1 inch: plus or minus 1 inch
(25 mm).
2) M30 1 1/4 inch (32 mm) - M100 4 inch: plus or minus 2
inches (51 mm)
5. Fabrication Tolerance:
a. Cutting tolerance for rods: up to M76, 3 inches (76 mm) plus or
minus 1/4 inch (6 mm).
b. Cutting tolerance for rods: over M76, 3 inches (76 mm) plus or
minus 1 inch (25 mm).
c. Maximum lengths
1) M10 3/8 inch (9.5 mm) - M16 5/8 inch: 19 feet 6 inches (6
meters).
2) M20 3/4 inch (19 mm) - 29 feet 6 inches (9.0 meters).
3) M24 1 inch (25 mm) - M100 4 inch (102 mm): 39 feet 2
inches (11.95 meters).
6. Coating: Galvanizing as scheduled.
7. Coating: Priming as scheduled.
8. Coating: Painting as scheduled.
9. Coating: Plating.
10. Connection: The connection to the structure shall be made by utilizing
a connection plate with the same thickness and edge distance as the
manufacturer's spade. Engineered fabricated building connections shall be
made using standard grade 50 material.
05090-11
b. Hollow Sections: Circular Hollow Sections (CHS) shall be
stainless material.
c. Size: Diameters from M12 1/2 inch to M100 4 inches in carbon
or galvanized steel components.
d. Macalloy Compression Struts utilize Macalloy 520 fork and pin
sets. These are connected to the CHS (circular hollow section) by a
taper cone and threaded stud. This is welded onto each end of a CHS.
e. Fabrication Tolerance:
1) Cutting tolerance for a CHS is: plus or minus 1/8 inch (3
mm).
f. Adjustment: The standard left hand- right hand tendon shall
provide adjustment to accommodate site and manufacturing tolerances:
1) Adjustment for rods M12, 1/2 inch (13 mm) to M56, 2-1/4
inches plus or minus 1/2 inch (13 mm)thread diameter each end.
2) Adjustment for rods M64, 2-1/2 (63.5 mm) inches to
M100, 4 inches (102 mm) plus or minus 1 inch (25 mm) each
end.
PART 6 EXECUTION
6.1 EXAMINATION
6.2 PREPARATION
05090-12
achieving the best result for the substrate under the project conditions.
6.3 INSTALLATION
6.4 PROTECTION
END OF SECTION
05090-13
SECTION 05400
PART 7 GENERAL
7.1 SECTION INCLUDES
05090-14
I. Section 09255 - Exterior Sheathing Board.
7.3 REFERENCES
C. ASTM A90 - Standard Test Method for Weight (Mass) of Coating on Iron and
Steel Articles with Zinc or Zinc-Alloy Coatings.
D. ASTM A370 - Standard Test Methods and Definitions for Mechanical Testing
of Steel Products.
F. ASTM A780 - Standard Practice for Repair of Damaged and Uncoated Areas
of Hot-Dip Galvanized Coatings.
H. ASTM A1003 - Standard Specification for Steel Sheet, Carbon, Metallic- and
Nonmetallic-Coated for Cold-Formed Framing Members.
J. ASTM A1011 - Standard Specification for Steel, Sheet and Strip, Hot-Rolled,
Carbon, Structural, High-Strength Low-Alloy and High-Strength Low-Alloy with
Improved Formability.
N. ASTM C1513 - Standard Specification for Steel Tapping Screws for Cold-
Formed Steel Framing Connections.
05090-15
B. Performance Requirements:
1. Design system components per AISI reference. Provide for movement
of components due to thermal variations without damage, failure, or excessive
stress on components.
2. Compute structural properties per AISI - Specifications for the Design
of Cold-Formed Steel Structural Members.
3. Design exterior wall system for environmental loads as outlined in the
ASCE 7 latest edition to provide for movement of components without
damage, failure of joint seals, undue stress on fasteners, or other detrimental
effects when subject to seasonal or cyclic day/night temperature ranges.
4. Design system to accommodate construction tolerances, deflection of
building structural members, and clearances of intended openings.
5. Maximum Allowable Deflection:
a. Gypsum Board: L/360 of span under total design loads.
b. Exterior Insulation Finish System: L/360 of span under total
design loads.
c. Plaster or Stucco: L/360 of span under total design loads.
d. Brick Veneer: L/600 of span under total design loads.
6. Horizontal Assemblies:
a. Maximum Allowable Deflection: L/360 of span under total
design loads.
7.5 SUBMITTALS
05090-16
and locations, and other fastener requirements.
3. Where prefabricated or prefinished panels are to be provided, provided
drawings depicting panel configurations, dimensions and locations.
F. Selection Samples: For each finish product specified, two complete sets of
color chips representing manufacturer's full range of available colors and patterns.
PART 8 PRODUCTS
05090-17
8.1 MANUFACTURERS
8.2 MATERIALS
05090-18
25. Web Depth: 11 1/2 inch (292 mm) 1150 depth.
26. Web Depth: 12 inch (305 mm) 1200 depth.
27. Web Depth: 13-1/2 inch (342.9 mm) 1350 depth.
28. Web Depth: 14 inch (355.6 mm) 1400 depth.
29. Web Depth: 16 inch (406.4 mm) 1600 depth.
30. Web Depth: As indicated on drawings.
31. Section Properties: Refer to Drawings.
05090-19
8. Minimum Base-Metal Thickness: 10 gauge, 0.1180 inch (3.0 mm).
9. Flange Width: 1-3/8 inches (35 mm).
10. Flange Width: 1-5/8 inches (41 mm).
11. Flange Width: 2 inches (51 mm).
12. Flange Width: 2-1/2 inches (63 mm).
13. Flange Width: 3 inches (76 mm).
14. Flange Width: 3-1/2 inches (89 mm).
15. Web Depth: 2 1/2 inch (64 mm) 250 depth.
16. Web Depth: 3 1/2 inch (89 mm) 350 depth.
17. Web Depth: 3 5/8 inch (92 mm) 362 depth.
18. Web Depth: 4 inch (102 mm) 400 depth.
19. Web Depth: 5 1/2 inch (140 mm) 550 depth.
20. Web Depth: 6 inch (152.4 mm) 600 depth.
21. Web Depth: 7 1/4 inch (184 mm) 725 depth.
22. Web Depth: 8 inch (203 mm) 800 depth.
23. Web Depth: 9 1/4 inch (235 mm) 925 depth.
24. Web Depth: 10 inch (254 mm) 1000 depth.
25. Web Depth: 11 1/2 inch (292 mm) 1150 depth.
26. Web Depth: 12 inch (305 mm) 1200 depth.
27. Web Depth: 13-1/2 inch (342.9 mm) 1350 depth.
28. Web Depth: 14 inch (355.6 mm) 1400 depth.
29. Web Depth: 16 inch (406.4 mm) 1600 depth.
30. Web Depth: As Indicated on drawings.
31. Section Properties: Refer to Structural Drawings.
05090-20
21. Web: 11 1/2 inch (292 mm) 1150 depth.
22. Web: 12 inch (305 mm) 1200 depth.
23. Web: 13-1/2 inch (342.9 mm) 1350 depth.
24. Web: 14 inch (355.6 mm) 1400 depth.
25. Web: 16 inch (406.4 mm) 1600 depth.
26. Web: Track Web Size to match stud web size.
05090-21
a. Minimum Base-Metal Thickness: 18 gauge, 0.0428 inch (1.09
mm).
b. Minimum Base-Metal Thickness: 16 gauge, 0.0538 inch (1.37
mm).
c. Minimum Base-Metal Thickness: 14 gauge, 0.0677 inch (1.72
mm).
d. Minimum Base-Metal Thickness: 12 gauge, 0.0966 inch (2.45
mm).
e. Minimum Base-Metal Thickness: 10 gauge, 0.1180 inch (2.00
mm).
f. Flange Width: Width equal to sum of outer deflection track
flange width plus 1 inch (25 mm).
F. Slotted Slip Track: Manufactured by CEMCO. U-shaped track with 1-1/2 inch
vertical slots spaced 1 inch along the legs to allow vertical deflection as follows:
1. Standard leg of 2-1/2 inches in leg.
2. Standard vertical slot of 1 1/2 inches in leg.
3. Minimum Base-Metal Thickness: 16 gauge, 0.0538 inch (1.37 mm).
4. Minimum Base-Metal Thickness: 18 gauge, 0.0428 inch (1.09 mm).
5. Minimum Base-Metal Thickness: 20 gauge, 0.0329 inch (0.84 mm).
6. Web Depth: 2 1/2 inch (64 mm) 250 depth.
7. Web Depth: 3 5/8 inch (92 mm) 362 depth.
8. Web Depth: 4 inch (102 mm) 400 depth.
9. Web Depth: 6 inch (152.4 mm) 600 depth.
10. Web Depth: 8 inch (203 mm) 800 depth.
G. Drift Clips: Manufacturer's standard bypass or head clips, capable of isolating
wall stud from upward and downward vertical displacement and lateral drift of
primary structure.
A. Steel Joists: Cold-formed steel joists, of web depths indicated, with punched
enlarged service holes with stiffened flanges, and as follows:
1. Type: Marino\Ware JoistRITE steel joists.
2. Type: Marino\WARE standard steel joists.
3. Minimum Base-Metal Thickness: 20 gauge, 0.0329 inch (0.84 mm).
4. Minimum Base-Metal Thickness: 18 gauge, 0.0428 inch (1.09 mm).
5. Minimum Base-Metal Thickness: 16 gauge, 0.0538 inch (1.37 mm).
6. Minimum Base-Metal Thickness: 14 gauge, 0.0677 inch (1.72 mm).
7. Minimum Base-Metal Thickness: 12 gauge, 0.0966 inch (2.45 mm).
8. Minimum Base-Metal Thickness: 10 gauge, 0.1180 inch (3.00 mm).
9. Minimum Flange Width: 1-5/8 inches (41 mm).
10. Minimum Flange Width: 2 inches (51 mm).
11. Minimum Flange Width: 2-1/2 inches (63 mm).
12. Minimum Flange Width: 3 inches (76 mm).
13. Minimum Flange Width: 3-1/2 inches (89 mm).
14. Minimum Joist Depth: 9 inches (203 mm).
15. Minimum Joist Depth: 9-1/4 inches (235 mm).
05090-22
16. Minimum Joist Depth: 10 inches (254 mm).
17. Minimum Joist Depth: 11-1/4 inches (286 mm).
18. Minimum Joist Depth: 12 inches (305 mm).
19. Minimum Joist Depth: 14 inches (356 mm).
20. Section Properties: Refer to Structural Drawings.
B. Steel Joist Track: Cold-formed steel joist track, of web depths indicated,
unpunched, with unstiffened flanges, and as follows:
1. Type: Marino\Ware JoistRITE steel joist track.
2. Type: Marino\WARE standard steel joist track.
3. Minimum Base-Metal Thickness: 20 gauge, 0.0329 inch (0.84 mm).
4. Minimum Base-Metal Thickness: 18 gauge, 0.0428 inch (1.09 mm).
5. Minimum Base-Metal Thickness: 16 gauge, 0.0538 inch (1.37 mm).
6. Minimum Base-Metal Thickness: 14 gauge, 0.0677 inch (1.72 mm).
7. Minimum Base-Metal Thickness: 12 gauge, 0.0966 inch (2.45 mm).
8. Minimum Base-Metal Thickness: 10 gauge, 0.1180 inch (3.0 mm).
9. Minimum Base-Metal Thickness: Matching steel joists.
10. Flange Width: 1-1/4 inches (32 mm), minimum.
8.6 ROOF-RAFTER FRAMING
05090-23
6. Minimum Base-Metal Thickness: 14 gauge, 0.0677 inch (1.72 mm).
7. Minimum Base-Metal Thickness: 12 gauge, 0.0966 inch (2.45 mm).
8. Minimum Base-Metal Thickness: 10 gauge, 0.1180 inch (3.0 mm).
9. Minimum Base-Metal Thickness: Matching steel joists.
10. Minimum Flange Width: 1-5/8 inches (41 mm).
11. Minimum Flange Width: 2 inches (51 mm).
12. Minimum Flange Width: 2-1/2 inches (63 mm).
13. Minimum Flange Width: 3 inches (76 mm).
14. Minimum Flange Width: 3-1/2 inches (89 mm).
15. Section Properties: Refer to Structural Drawings.
A. Steel Shapes and Clips: ASTM A36/A36M, zinc coated by hot-dip process
according to ASTM A123/A123M.
05090-24
8.10 MISCELLANEOUS MATERIALS
A. Galvanizing Repair Paint: SSPC-Paint 20 or DOD-P-21035.
B. Cement Grout: Portland cement, ASTM C150, Type I; and clean, natural
sand, ASTM C404. Mix at ratio of 1 part cement to 2-1/2 parts sand, by volume, with
minimum water required for placement and hydration. Refer to Structural Drawings.
E. Sealer Gaskets: Closed-cell neoprene foam, 1/4 inch (6.4 mm) thick,
selected from manufacturer's standard widths to match width of bottom track or rim
track members.
8.11 FABRICATION
A. Fabricate cold-formed metal framing and accessories plumb, square, and true
to line, and with connections securely fastened, according to referenced AISI's
specifications and standards, manufacturer's written instructions, and requirements
in this Section.
1. Fabricate framing assemblies using jigs or templates.
2. Cut framing members by sawing or shearing; do not torch cut.
3. Fasten cold-formed metal framing members by welds, screw fasteners,
clinch fasteners, or rivets as standard with fabricator. Wire tying of framing
members is not permitted.
a. Comply with AWS D1.3 requirements and procedures for
welding, appearance and quality of welds, and methods used in
correcting welding work.
b. Locate mechanical fasteners and install according to Shop
Drawings, with screw penetrating joined members by not less than
three exposed screw threads.
4. Fasten other materials to cold-formed metal framing by welding,
bolting, or screw fastening, according to Shop Drawings.
PART 9 EXECUTION
9.1 EXAMINATION
05090-25
B. If substrate preparation is the responsibility of another installer, notify
Architect of unsatisfactory preparation before proceeding.
9.2 FASTENING
9.3 ERECTION
B. Wall Systems:
1. Handle and lift prefabricated panels in a manner so as not to cause
distortion in any member.
2. Anchor runner track securely to the supporting structure as shown on
the erection drawings. Install concrete anchors only after full compressive
strength has been achieved. Provide a sill sealer or gasket barrier between
all concrete and steel connections.
3. Butt all track joints. Securely anchor abutting pieces of track to a
common structural element, or butt-weld or splice together.
4. Align and plumb studs, and securely attach to the flanges or webs of
both upper and lower tracks except when vertical movement is specified.
5. Install jack studs or cripples below window sills, above window and
door heads, at freestanding stair rails and elsewhere to furnish support,
securely attached to supporting members.
6. Attach wall stud bridging in a manner to prevent stud rotation. Space
bridging rows according to manufacturer's recommendations.
7. Frame wall openings to include headers and supporting studs as
shown in the drawings.
8. Place studs at maximum 16 inches on center; not more than 2 inches
from abutting walls, and at each side of openings. Connect studs to tracks
using mechanical fastener method.
9. Construct corners using minimum 3 studs. Double studs at wall
openings, doors, and window jambs, 1 of which is full length unless indicated
otherwise.
05090-26
10. Coordinate placement of insulation in multiple stud spaces made
inaccessible after erection.
11. Attach cross studs or furring channels to studs for attachment of
fixtures anchored to walls.
12. Install framing between studs for attachment of mechanical and
electrical items, and to prevent stud rotation.
13. Touch-up field welds and damaged galvanized and primed surfaces
with primer.
14. Provide bridging (horizontal stiffeners) at 4 feet 0 inches on center
maximum vertical spacing for exterior and load bearing metal stud walls.
C. Steel Joists:
1. Locate joist end bearing directly over load bearing studs or provide
load-distributing member to top of stud track.
2. Provide web stiffeners at reaction points where indicated in drawings.
3. Provide joist bridging as shown in drawings.
4. Provide end blocking where joist ends are not otherwise restrained
from rotation.
5. Place joists at maximum 12 inches on center and not more than 2
inches from abutting walls. Connect joists to supports using mechanical
fastener method.
6. Touch-up field welds and damaged galvanized surfaces with primer.
C. If tests indicate Work does not meet specified requirements, remove Work,
replace with new material, and retest at no cost to Owner.
D. Visually inspect 100 percent of welds for specified length, size, and continuity
per AWS D1.3 for metal less than 1/8 inch thickness. For Work designed as a
structural element. Provide testing and inspection for field welds previously
specified per Section 05120.
9.5 PROTECTION
END OF SECTION
05090-27
SECTION 05510
PART 10 GENERAL
10.1 SECTION INCLUDES
05090-28
A. Automatic electric disappearing stairways.
10.3 REFERENCES
A. ANSI A14.3: Ladders - Fixed - Safety Requirements.
10.4 SUBMITTALS
A. Submit under provisions of Section 01300.
05090-29
A. Store products in manufacturer's unopened packaging until ready for
installation.
B. Store stairway until installation inside under cover. If stored outside, under a
tarp or suitable cover.
10.6 WARRANTY
A. Limited Warranty: One year against defective material and workmanship,
covering parts only, no labor or freight. Defective parts, if deemed so by the
manufacturer, will be replaced at no charge, freight excluded, upon inspection at
manufacturer's plant which warrants same.
PART 11 PRODUCTS
11.1 MANUFACTURERS
A. Acceptable Manufacturer: Precision Ladders, LLC, which is located at: P. O.
Box 2279 ; Morristown, TN 37816-2279; Toll Free Tel: 800-225-7814; Tel: 423-586-
2265; Email: request info (info@PrecisionLadders.com); Web:
www.PrecisionLadders.com
B. Accessories:
1. Standard toggle wall mounted switch.
2. Key operated dead-man type wall switch.
3. Emergency manual operation to lower (only) from above if power fails.
4. Emergency manual operation to lower (only) from below if power fails.
5. Emergency manual operation to lower (only) from above or below if
power fails.
6. Warning buzzer.
C. Components:
1. Stairway Stringer: 7 inches by 0.230 inch (178 mm by 5.8 mm)
extruded aluminum channel. Steel rollers at base of each stringer. Pitch: 52
degree.
2. Stairway Tread: Aluminum channel 6 inches by 20-3/16 inches by
0.225 inch (152 mm by 513 mm by 5.7 mm). Nonskid safety material at
walking surface.
05090-30
3. Riser Height: 9-1/2 inches (241 mm) maximum.
4. Railing: Hand/guide rail 1-1/16 inches (27 mm) OD both sides,
galvanized.
5. Frame: 1/8 inch (3 mm) steel formed channel. Height to suit total
ceiling thickness.
6. Door: 1/8 inch (3 mm) aluminum panel. Steel piano hinge.
7. Door: 1-3/4 (44.5 mm) inches wood with mineral core. Steel piano
hinge.
8. Drive Unit: 1/3 horsepower 246 W), 115 volt instantly reversible motor
direct-connected to a reduction gear drive, complete with contactors. Pre-
wired control switches. Sealed ball bearing guides. Double 1/8 inch (3 mm)
aircraft cable drive.
9. Finishes: Mill finish on aluminum stairway components. Prime coat on
frame. Galvanized handrails.
B. Accessories:
1. Steel pole to aid opening and closing stairways.
2. Keyed lock for non-fire rated door.
3. Roof hatch, factory sized and mounted to top of stairway frame.
C. Components:
1. Ceiling Opening: 30 inches by 54 inches (762 mm by 1372 mm).
2. Ceiling Opening: __ inches by 54 inches (__ mm by 1372 mm).
3. Ceiling Opening: 30 inches by 64 inches (762 mm by 1626 mm).
4. Ceiling Opening: __ inches by 64 inches (__ mm by 1626 mm).
5. Stairway Stringer: 6005-T5 Extruded aluminum channel 5 inches by 1
inch by 1/8 inch (127 mm by 25 mm by 3 mm). Tri-fold design. Steel blade
type hinges. Adjustable feet with plastic Mar-guard. Pitch 63 degrees.
6. Stairway Tread: 6005-T5 extruded aluminum channel 5 3/16 inches by
1 1/4 inches by 1/8 inch (132 mm by 32 mm by 3 mm). Depth is 5 3/16 inches
(132 mm). Deeply serrated top surface. Riser Height: 9-1/2 inches (241 mm).
a. Clear Tread Width for Standard Width: 19-1/2 inches (495 mm).
b. Clear Tread Width for Non-Standard (Custom) Width: _____
inches (___ mm).
05090-31
7. Railing: Aluminum bar handrail riveted to stringers, upper section only.
8. Frame: 1/8 inch (3 mm) steel formed channel. 6 inches (152 mm) deep.
9. Frame: 1/8 inch (3 mm) steel formed channel. 5 inches (127 mm) deep.
10. Aluminum Door: 1/8 inch (3 mm) aluminum panel. Steel piano hinge.
Door overlaps bottom flange of frame. Eye bolt accommodates pole for
opening and closing door.
11. Fire Rated Steel Door: 20 gauge (0.912 mm) steel door with 2 hour
fire-rated Warnock Hersey label meeting ASTM E-119 and UBC 43-7
requirements, passing 250 degree F (121 degree C) temperature rise in the
first 30 minutes. Steel piano hinge. Door is flush with bottom of frame. Hole in
paddle-latch accommodates pole for opening and closing door.
12. Hardware:
a. Steel blade type hinge connecting stringer sections. Zinc plated
and chromate sealed.
b. Steel operating arms, both sides. Zinc plated and chromate
sealed.
c. Double acting steel springs and V-hooks, both sides.
d. Rivets rated at 1100 lb (499 kg) shear strength each.
e. Steel section alignment clips at stringer section joints.
f. Molded rubber guards at corners of aluminum door panel.
13. Finishes: Mill finish on aluminum stairway components. Prime coat on
frame.
D. Components:
1. Ceiling Opening: 30 inches by 54 inches (762 mm by 1372 mm).
2. Ceiling Opening: __ inches by 54 inches (___ mm by 1372 mm).
3. Ceiling Opening: 30 inches by 64 inches (762 mm by 1626 mm).
4. Ceiling Opening: __ inches by 64 inches (__ mm by 1626 mm).
5. Stairway Stringer: 6005-T5 Extruded aluminum channel 5 inches by 1
inch by 1/8 inch (127 mm by 25 mm by 3 mm). Tri-fold design. Steel blade
type hinges. Adjustable feet with plastic Mar-guard. Pitch 63 degrees.
6. Stairway Tread: 6005-T5 extruded aluminum channel 5 3/16 inches by
1 1/4 inches by 1/8 inch (132 mm by 32 mm by 3 mm). Width is 5 3/16 inches
(132 mm). Deeply serrated top surface. Riser Height: 9-1/2 inches (241 mm).
a. Clear Tread Width: 19-1/2 inches (495 mm).
b. Clear Tread Width: ___.
7. Railing: Aluminum bar handrail riveted to stringers, upper section only.
8. Frame: Custom fabricated from 1/8 inch (3 mm) steel with factory-
installed tread to cover the distance from finished ceiling to finished floor
above. Frame shall be on a 63 degree angle on the hinge end in order to
continue the climb from ceiling and beyond on the same incline as the folding
portion of the unit. The frame shall have pre-drilled and mounted brackets to
allow for hanging from and fastening to the floor above.
9. Standard Door: 1/8 inch (3 mm) aluminum panel. Steel piano hinge.
Door overlaps bottom flange of frame. Eye bolt accommodates pole for
opening and closing door.
10. Door: 20 gauge (.912 mm) steel door with 2 hour fire-rated Warnock
Hersey label meeting ASTM E-119 and UBC 43-7 requirements, passing 250
degree F (121 degree C) temperature rise in the first 30 minutes. Steel piano
hinge. Door is flush with bottom of frame. Hole in paddle-latch accommodates
pole for opening and closing door.
05090-32
11. Hardware:
a. Steel blade type hinge connecting stringer sections. Zinc plated
and chromate sealed.
b. Steel operating arms, both sides. Zinc plated and chromate
sealed.
c. Double acting steel springs and V-hooks, both sides.
d. Rivets rating at 1100 lb (500 kg) shear.
e. Steel section alignment clips at stringer section joints.
f. Molded rubber guards at corners of aluminum door panel.
12. Finishes: Mill finish on aluminum stairway components. Prime coat on
frame.
B. Components:
1. Ladder Stringer: 2-1/2 inch by 1-1/16 inch by 1/8 inch (64 mm by 27
mm by 3 mm) extruded 6005-T5 aluminum channel. Pitch: 90 degrees.
2. Ladder Tread: 2-1/4 inch by 3/4 inch by 1/4 inch (57 mm by 19 mm by
6 mm) extruded 6005-T5 aluminum with deeply serrated top surface.
3. Ladder Mounting Bracket: 8-1/2 inch by 2 inch by 3 inch by 1/4 inch
thick (216 mm by 51 mm by 76 mm by 6 mm) aluminum angle.
4. Walk-Thru:
a. Frame: 1-1/4 inch (32 mm) aluminum square tube.
b. Mounting Brackets: 4 inch by 4 inch by 1/4 inch (102 mm by 102
mm by 6 mm) aluminum.
c. Side Rails: 42 inch (1067 mm) side rail extension for through
ladder exits.
5. Safety Cage:
a. Bar Hoops: 1/4 inch by 2 inch (6 mm by 51 mm) 6005-T5
aluminum.
b. Vertical Bars: 1/4 inch by 2 inch (6 mm by 51 mm) 6005-T5
aluminum.
6. Rest Platform:
a. 1/8 inch (3 mm) aluminum tread plate.
b. Platform Size: 37-1/2 inches by 63 inches (953 mm by 1600
mm) standard.
c. Toe Boards. 6005 T-5 aluminum.
d. Handrails: 1-2/4 inch (32 mm) aluminum square tube 42 inches
(1067 mm) high.
7. Security Door: 0.125 inch (3 mm) 3003-H14 aluminum panel 84 inches
(2134 mm) tall with padlock provision.
8. Security Gate: Hinged gate at bottom of cage with padlock provision.
05090-33
9. Fall Prevention System: Complete system with rail, sleeves, and
harness to limit any fall to 6 inches (152 mm) or less.
10. Floor Brackets: Floor bracket at foot of each stringer, 3 by 2 by 1/4
inch (76 by 51 by 6 mm).
11. Finishes:
a. Mill finish on aluminum ladder components.
b. Anodized.
c. Painted.
d. Powder Coat.
11.6 FABRICATION
A. Completely fabricate ladder ready for installation before shipment to the site.
PART 12 EXECUTION
05090-34
12.1 EXAMINATION
A. Do not begin installation until rough opening and structural support have been
properly prepared.
C. Examine materials upon arrival at site. Notify the carrier and manufacturer of
any damage.
12.2 INSTALLATION
A. Install in accordance with manufacturer's instructions.
12.3 PROTECTION
A. Protect installed products until completion of project.
END OF SECTION
SECTION 05520
PART 13 GENERAL
13.1 SECTION INCLUDES
A. Roof edge protection.
05090-35
F. Grab bars.
L. Pipe fittings.
13.3 REFERENCES
A. British Standard BS 970 - Specification for wrought steels for mechanical and
allied engineering purposes. General inspection and testing procedures and specific
requirements for carbon, carbon manganese, alloy and stainless steels.
05090-36
Floor Openings, Floor Holes and Roofs.
13.4 SUBMITTALS
A. Submit under provisions of Section 01300.
D. Selection Samples: For each finish product specified, two complete sets of
color chips representing manufacturer's full range of available colors and patterns.
05090-37
B. Inspect rail sections for damage before signing the receipt from the trucking
company. Truck driver must note damaged goods on the bill of lading if damaged
product is found.
13.7 WARRANTY
A. Warranty: Provide manufacture's two (2) year warranty.
PART 14 PRODUCTS
14.1 MANUFACTURERS
A. Acceptable Manufacturer: BlueWater Mfg., Inc., which is located at: 4064
Peavey Rd. ; Chaska, MN 55318; Toll Free Tel: 866-933-2935; Tel: 952-448-2935;
Email: request info (info@bluewater-mfg.com); Web: www.bluewater-mfg.com
14.2 SYSTEMS
A. Roof Edge Protection: Provide freestanding pedestrian egress barrier system
on roof, including pipe railings, uprights, bases, and fittings.
1. Approved Product: SafetyRail 2000.
2. Standards: System shall have top and mid rail in accordance with
OSHA Standards - 29 CFR 1910.23 (a)(2).
3. Structural Load: 200 lb (90.7 kg), minimum, in any direction to all
components in accordance with OSHA Regulation 29 CFR 1926.502.
4. Height: 42 inches (1067 mm), minimum.
5. Railings: 1-5/8 inch (41 mm) O.D. hot rolled pickled electric weld
tubing, free of sharp edges and snag points.
6. Mounting Bases: Class 30 gray iron material cast with four receiver
posts. Provide rubber pads on bottom of bases.
7. Receiver Posts: Shall have a positive locking system into slots that
allow rails to be mounted in any direction. Friction locking systems are not
allowed. Receiver posts shall have drain holes.
8. Accessories:
a. Toe Board Brackets: Provide brackets and friction knobs as
manufactured by BlueWater Mfg. Inc.
b. Step-Rail: Variable height railing enables a continuous run of
SafetyRail 2000 when the roof steps up or down.
c. Raised Mid-Rail: Railing to fit over duct work for continuous run
05090-38
of SafetyRail2000.
d. LP Outrigger: Supports placed under ducting or conduit to
continue run of SafetyRail 2000 when rail section cannot be used.
e. SG2000: Sliding gate.
f. Finishing Rail: D-shaped railing extension for ladder landings,
length of rail section and D-loop as indicated on the Drawings.
9. Hardware: Securing pins shall be 1010 carbon steel, zinc plated and
yellow chromate dipped. Pins shall consist of collared pin and lanyard that
connects to lynch pin.
B. Collapsible Guard Rails: Provide collapsible portable guard rail section with
one-way pivot assembly that allows guardrail to fold down to horizontal surface for
clean sightlines; requires no penetrations in substrates for installation. Rails shall be
compatible with SafetyRail 2000 Guardrail System.
1. Approved Product: Stealth Rail.
2. Standards: Guard rail system shall meet or exceed OSHA (Standards -
29 CFR) 1926.501 and 1926.502.
3. Hardware: Detent pin on each pivot assembly shall lock rail in upright
position.
05090-39
8. Mounting Bases: Class 30 gray iron material cast with four receiver
posts. Provide rubber pads on bottom of bases.
9. Receiver Posts: Shall have a positive locking system into slots that
allow rails to be mounted in any direction. Friction locking systems are not
allowed. Receiver posts shall have drain holes.
10. Railing Hardware: Securing pins shall be 1010 carbon steel, zinc plated
and yellow chromate dipped. Pins shall consist of collared pin and lanyard
that connects to a lynch pin.
11. Gate Hardware: Bolts and washers shall be 3/8 inch by 3-1/2 inch (9.5
mm by 89 mm) and 3/8 inch by 3 inch (9.5 mm by 76 mm) grade 5, zinc
plated.
12. Gate Opener: Latch pole.
13. Gate Opener: Latch.
14. Installation: Locate within 6 inches of open roof hatch or roof opening.
F. Grab Bar: Mounts to an open receiver on the SafetyRail 2000 base. Width of
bars shall adjust to ladder width inside hatch.
1. Approved Product: Grab Bar.
2. Mount Pad: Adjustable; shall enable bars to be used with curbs or on
uneven surfaces.
3. Hardware: Bars lock into place with securing pin and friction collar.
05090-40
e. Kit: 6 Foot 90 Degree Extension; Part No. 500140.XX.
2. Standards: System shall have top and mid rail in accordance with
OSHA Standards - 29 CFR 1910.23 (a)(2).
3. Height: 42 inches (1067 mm), minimum.
4. Railings: 1-1/2 inch pipe (1.90 inch (48 mm) OD).
5. Railings: 1-1/4 inch pipe (1.66 inch (42 mm) OD).
6. Gate: Custom, as indicated on Drawings.
7. Hardware: Anchor bolts.
8. Material: Mild steel, powder coated.
9. Material: Mild steel, hot-dip galvanized.
10. Material: Mild steel, hot-dip galvanized with powder-coated finish.
11. Material: Aluminum.
I. Non-Penetrating Railing System for Roof Edge Fall Protection: Provide metal
handrail system consisting of a top rail, mid rail and base. Stanchions shall be
capable of mounting in any direction.
1. Approved Product: SafetyRail 2000 Architectural Series Guardrail
System.
2. Standards: System shall meet and exceed OSHA Standards - 29 CFR
1926.502 (b) and 1910.23 (e).
3. Height: 42 inches (1067 mm), minimum.
4. Railings and Stanchions: 1-1/4 inch pipe (1.66 inch (42 mm) OD).
a. Curved upright.
b. Inclined upright.
c. Straight upright.
5. Free Standing Base: Class 30 gray cast iron.
6. Hardware: 1010 carbon steel securing pins, zinc plated and yellow
chromate dipped.
7. Finish for Rails: Hot dipped galvanized.
8. Finish for Rails: Powder coat paint.
9. Finish for Bases: Hot dipped galvanized.
10. Finish for Bases: Powder coat paint.
J. Portable Warning/Barrier System: Provide self-contained, hand carried visual
warning system with spindle mount and handle for transporting and hoisting.
1. Approved Product: Kwik-Stand
2. Standards: System shall meet or exceed the requirements in OSHA
Standards - 29 CFR 1926.502 (f).
3. Height: 39 inches (991 mm) tall.
4. Area, Foot Print: 39 inches by 32 inches (991 mm by 813 mm) in use.
5. Weight: 34 lbs. (15.4 kg), each stand.
6. Support Bars: Hole at each end for accessories.
7. Accessories:
a. Extender Feet: For metal roofs.
b. Stakes: For gravel or asphalt roofs.
c. Rubber Pads: For feet of stands.
8. Flags: Bright yellow; OSHA rated.
9. Hardware: Securing pin attached to stanchion with lanyard.
05090-41
K. Portable Guard Rail System: Provide C-clamp locking guard rail system with
off-set compression plates and compression rods.
1. Approved Product: Versa-Clamp.
2. Height: Adjustable, to comply with OSHA guardrail heights.
3. Clamps: Expand from 1 inch (25 mm) to 12 inches (305 mm).
4. Accessories:
a. Toe Board Brackets: Provide brackets and friction knobs as
manufactured by BlueWater Mfg. Inc. for deck applications.
b. Adaptors: As manufactured by BlueWater Mfg. Inc., for
permanent placement of Versa-Clamp.
14.3 FITTINGS
A. Pipe Fittings:
1. Approved Product: Kwik-Fit.
2. Type: Provide fittings required for a complete operational system that
meets OSHA requirements.
3. Type: Provide the following:
a. Series 1047 - 90 Degree Elbow.
b. Series 1048 - Short Tee.
c. Series 1049 - Long Tee.
d. Series 1050 - Railing Base Flange.
e. Series 1051 - 3-Way Blind Corner.
f. Series 1052 - 3 Way Open Corner
g. Series 1053 - Short Cross.
h. Series 1054 - Straight Sleeve.
i. Series 1055 - Expanding Connector.
j. Series 1056 - Internal Swivel Tee.
k. Series 1057 - Swivel Base.
l. Series 1058 - Base Flange.
m. Series 1060 - Wall Flange.
n. Series 1061 - Rail Bracket.
o. Series 1062 - Side Outlet Tee.
p. Series 1063 - 4 Way with Center Pipe.
q. Series 1064 - Short Tee Swivel.
r. Series 1065 - Adjustable 2 Socket Cross.
s. Series 1067 - Variable Angle Tee.
t. Series 1068 - Collar.
u. Series 1069 - Gate Eye.
v. Series 1070 - Gate Hinge.
w. Series 1071 - Hook.
x. Series 1072 - Fixing Pad.
y. Series 1073 - Single Male Swivel.
z. Series 1074 - Single Female Swivel.
aa. Series 1075 - Alternate Male Swivel.
bb. Series 1076 - Double Male Swivel.
cc. Series 1077 - 90 Degree Corner Male Swivel.
dd. Series 1078 - Cross Over.
05090-42
ee. Series 1079 - Clamp On Tee.
ff. Series 1080 - Single Swivel Kit.
gg. Series 1081 - Base Swivel Kit.
hh. Series 1082 - Double Swivel Kit.
ii. Series 1083 - 90 Degree Corner.
jj. Series 1084 - Spare Screws.
kk. Series 1085 - End Cap.
ll. Series 1086 - Extended Straight Sleeve.
4. Material, Structural Pipe Fittings: Malleable iron, in accordance with BS
EN 1562.
5. Material, Fitting Types 26, 27 and 90: Weldable cast steel, in
accordance with BS 3100.
6. Finish: Pipe fittings shall be galvanized in accordance with BS EN ISO
1461.
7. Fitting, Inside Diameter:
a. 1.38 inch (35 mm).
b. 1.73 inch (44 mm).
c. 1.97 inch (50mm).
8. Hardware: Stainless steel set screws, in accordance with BS 970
Grade 420. Each set screw shall support axial load of 900 kg when tightened
to torque of 40Nm.
14.4 ACCESSORIES
A. Safety/Caution Signage: Cushioned foam strip with self adhesive backing;
UL- rated for indoor/outdoor use.
1. Approved Product: Safety Strip.
2. Thickness: 3/8 inch (9.5 mm).
3. Length: 36 inches (914 mm).
4. Width: 2 inches (51 mm).
5. Width: 4 inches (102 mm).
6. Color: Safety yellow.
7. Color: Safety yellow with black stripes.
B. Roof Pads: Provide the following pad under each base to protect roof
membrane.
1. Approved Product: BUR Pad.
2. Approved Product: EPDM Roof Pad.
C. Rolling Storage Cart: Provide four-wheeled cart for storage and movement of
SafetyRail 2000 components.
1. Approved Product: HYPERLINK "http://www.arcat.com/clickthru.pl?
coid=41461&prodid=121647&loc=www.bluewater-mfg.com/RTC-2000.htm"
RTC-2000.
2. Capacity: 120 lineal feet (36.6 m) of various size railings (70 feet (21
m) usable); 12 individual rail sections.
3. Lockable Storage Box: For storage of toe board brackets and securing
pins.
4. Lifting Rings: For hoisting to elevated areas.
05090-43
D. Base Mover: Provide two-wheeled steel cart to transport one base unit.
1. Approved Product: EZ Mover.
14.5 FINISHES
A. Finish: Factory finished powder coat paint.
14.6 FABRICATION
A. Assemble components with joints tightly fitted and secured. Accurately form
components to suit installation.
PART 15 EXECUTION
15.1 EXAMINATION
A. Do not begin installation until substrates have been properly prepared.
15.2 PREPARATION
A. Prepare surfaces using the methods recommended by the manufacturer for
achieving the best result for the substrate under the project conditions.
15.3 INSTALLATION
A. Install in accordance with manufacturer's instructions.
15.4 PROTECTION
A. Protect installed products until completion of project.
END OF SECTION
05090-44