COST ABSTRACT

Name of Work: Construction of Research Park at IITG Campus.


Sl. No. Particulars Amount (Rs.)

1 Part - A : Building works

2 Part - B : Internal Sanitary & Water Supply Installation

3 Part - C : Site Development Works

4 Part - D(i): Fire Fighting works

Part - D(ii) : Fire Detection & Alarm System

5 Part - E : Electrical Works including Lift

6 Part - F: HVAC works

Total

Rebate if any

Grand Total
NOTE :- Quoted Rate shall be exclusive of GST.
Bill of Quantity
Name of Work: Construction of Research Park at IITG Campus.
Part-A(Building works)
Item
Description Unit Quantity Rate in figure (Rs.) Rate in words Total Amount(Rs.)
no.

Boring, providing and installation bored cast-in-situ


reinforced cement concrete piles of grade M-30 of
specified diameter and length below the pile cap, to
carry a safe working load not less than specified,
excluding the cost of steel reinforcement but
including the cost of boring with bentonite solution
and temporary casing of appropriate length for
1 setting out and removal of same and the length of
the pile to be embedded in the pile cap etc. by
percussion drilling using Direct mud circulation
(DMC) or Bailer and chisel technique by tripod and
mechanical Winch Machine all complete, including
removal of excavated earth with all its lifts and leads
(length of pile for payment shall be measured up to
bottom of pile cap).

600 mm dia piles Rm 16100.00

Vertical load testing of piles in accordance with IS


2911 (Part IV) including installation of loading
platform by Kentledge/Anchor piles method and
2 preparation of pile head or construction of test cap
and dismantling of test cap after test etc. complete
as per specification & the direction of Engineer in-
charge.

Note: 1. Initial and Routine Load Test shall not be


carried out by Dynamic method of testing.
Note: 2. Testing agency shall submitt the design of
loading platform for the approval of Engineer-in-
charge.
Single pile above 50 tonne and upto 100 tonne
a Safe
capacity
Initial test (Test Load 2.5 times the Safe Load
capacity)

Single pile above 100 tonne and upto 150 tonne


Per test 4.00
capacity (As per Design required)

Cyclic vertical load testing of pile in accordance with


b IS Code of practice IS: 2911 (part IV) by Kentledge
method including preparation of pile head etc for.

Single pile

Above 50 tonne and upto 100 tonne Safe capacity


Per test 12.00
pile

Integrity testing of Pile using Low Strain/ Sonic


Integrity Test/ Sonic Echo Test method in
accordance with IS 14893 including surface
preparation of pile top by removing soil, mud, dust
c & chipping lean concrete lumps etc. and use of Per test 629.00
computerised equipment and high skill trained
personal for conducting the test & submission of
results, all complete as per direction of Engineer-in-
charge.

Earth work in excavation by mechanical means


(Hydraulic excavator) / manual means in foundation
trenches or drains (not exceeding 1.5 m in width or
10 sqm on plan), including dressing of sides and
3
ramming of bottoms, lift upto 1.5 m, including
getting out the excavated soil and disposal of
surplus excavated soil as directed, within the IITG
campus.

All kinds of soil. Cum. 3695.00


Filling available excavated earth (excluding rock)
in trenches, plinth, sides of foundations etc. in
4 layers not exceeding 20cm in depth, consolidating Cum 3374.00
each deposited layer by ramming and watering,
lead up to 50 m and lift upto 1.5 m.

Supplying and filling in plinth with sand under floors,


5 including watering, ramming, consolidating and Cum 2416.00
dressing complete.

Supplying and injecting chemical emulsion for pre-


constructional anti-termite treatment and creating a
chemical barrier under & all-round the column pits,
wall trenches, basement excavation, top surface of
plinth filling, junction of wall and floor, along the
external perimeter of building, expansion joints,
6 sqm 2757.00
surroundings of pipes and conduits etc. complete.
Stages shall be treated as per CPWD specification.
(Plinth area of the building at ground floor level only
shall be measured for payments).- With
Chlorpyriphos Emulsifiable concentrate 20%
with 1% concentration./ or

Providing and laying in position cement concrete of


7 specified grade excluding the cost of centering and
shuttering - All work up to plinth level :

1:2:4 (1 cement : 2 coarse sand (zone-III) : 4


a Cum 371.00
graded stone aggregate 20 mm nominal size).

1:3:6 (1 Cement : 3 coarse sand (zone-III): 6


b Cum 437.00
graded stone aggregate 40 mm nominal size).

Providing and laying damp-proof course 50mm thick


with cement concrete 1:2:4 (1 cement : 2 coarse
c Sqm 114.00
sand(zone-III) : 4 graded stone aggregate 20mm
nominal size).
Providing and laying of cement concrete of
proportion 1:5:10 (1cement : 5 sand : 10 AAC block
d cum 105.00
bats of size 40mm) in sunken floors at all floors,
heights and levels
Making plinth protection 50mm thick of cement
concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded
stone aggregate 20 mm nominal size) over 75mm
e thick bed of dry brick ballast 40 mm nominal size, Sqm 198.00
well rammed and consolidated and grouted with
fine sand, including necessary excavation, levelling
& dressing & finishing the top smooth.

Centering and shuttering including strutting,


8
propping etc. and removal of form for all heights :

a Foundations, footings, bases for columns Sqm 591.00

Walls (any thickness) including attached pilasters,


b Sqm 8651.00
butteresses, plinth and string courses etc.

Suspended floors, roofs, landings, balconies and


c Sqm 17774.00
access platform. with water proof ply 12 mm thick

Lintels, beams, plinth beams, girders, bressumers


d Sqm 18100.00
and cantilevers. with water proof ply 12 mm thick

Columns, Pillars, Piers, Abutments, Posts and


e Sqm 9804.00
Struts

f Stairs, (excluding landings) except spiral-staircases Sqm 1214.00

g Extra for shuttering in circular work. Sqm 1390.00


Extra for additional height in centering, shuttering
where ever required with adequate bracing,
propping etc., including cost of de-shuttering and
h
decentering at all levels, over a height of 3.5 m, for
every additional height of 1 metre or part thereof
(Plan area to be measured).

Suspended floors, roofs, landing, beams and


i Sqm 2179.00
balconies (Plan area to be measured)

Steel reinforcement for R.C.C. work including


straightening, cutting, bending, placing in position
9
and binding all complete upto plinth level &
above.

Thermo-Mechanically Treated bars of grade Fe-


a Kg 2655621.00
500D

Providing and laying in position machine batched


and machine mixed design mix M-25 grade
cement concrete for reinforced cement concrete
work, using cement content as per approved design
mix, including pumping of concrete to site of laying
10 but excluding the cost of centering, shuttering,
finishing and reinforcement, including admixtures in
recommended proportions as per IS: 9103 to
accelerate, retard setting of concrete, improve
workability without impairing strength and durability
as per direction of Engineer-in-charge.

a All works upto plinth level Cum 253.00

b All works from plinth level upto floor V level Cum 120.00
Providing and laying in position machine batched
and machine mixed design mix M-30 grade
cement concrete for reinforced cement concrete
work, using cement content as per approved design
mix, including pumping of concrete to site of laying
11 but excluding the cost of centering, shuttering,
finishing and reinforcement, including admixtures in
recommended proportions as per IS: 9103 to
accelerate, retard setting of concrete, improve
workability without impairing strength and durability
as per direction of Engineer-in-charge.

a All works upto plinth level Cum 3189.00

b All works from plinth level upto floor V level Cum 4758.00

Including extra for R.C.C./ B.M.C/ R.M.C. work


c above floor V level for each four floors or part
thereof.

d All works above V level upto floor IX level Cum 3441.00

Brick work with common burnt clay F.P.S. (non


modular) bricks of class designation 7.5 in
12 Cum 410.00
foundation and plinth in Cement mortar 1:6 (1
cement : 6 coarse sand)

Providing and laying autoclaved aerated cement


blocks masonry with 100 mm thick AAC blocks in
super structure above plinth level up to floor V level
13 in cement mortar 1:4 (1 cement : 4 coarse sand ). Cum 37.00
The rate includes providing and placing in position 2
Nos 6 mm dia M.S. bars at every third course of
masonry work.
Providing and laying autoclaved aerated cement
blocks masonry with 150mm/230mm/300 mm thick
AAC blocks in super structure above plinth level up
to floor V level with RCC band at sill level and lintel
14 Cum 1732.00
level with approved block laying polymer modified
adhesive mortar all complete as per direction of
Engineerin- Charge. (The payment of RCC band
and reinforcement shall be made for seperately).

Above V level up to floor IX level (Including extra for


15 each four floors or part thereof by mechanical Cum 700.00
means).

Half brick masonry with common burnt clay F.P.S.


17 (non modular) bricks of class designation 7.5 in
superstructure above plinth level up to floor V level

a Cement mortar 1:4 ( 1 cement :4 coarse sand) sqm 546.00

Extra for half brick masonry in superstructure,


b above floor V level for every four floors or part sqm 273.00
thereof by mechanical means.
Extra for Providing and placing in position two
numbers 6mm dia. M.S. bars or equivalent hoop
c sqm 546.00
iron at every third coarse of all half brick masonry
works at all floors, heights, levels.
Making circular opening for exhaust fan upto 600
mm dia in AAC masonry work by providing proper
d each 100.00
precast RCC ring of required diameter on edgeat all
floors, heights and levels.

Honey-comb brick work 10/11.4 cm thick with


common burnt clay bricks of class designation 7.5
e sqm 100.00
in super structure with cement mortar 1:4 (1
cement : 4 coarse sand)at all floors, heights, levels.

FLOORING
Providing flat brick soling under foundation, floor,
plinth beam including packing with coarse sand and
watering etc complete as directed with bricks class
18 sqm 500.00
designation-75 in cement mortar in proportion 1:4
including curing complete as specified and as
directed.

Providing and laying (double charged full body)


vitrified floor tiles of minimum 600mmx600mm sizes
(thickness as per manufacturer's specifications)
conforming to IS : 15622 of approved make in all
19 colours and shades, laid on 20mm thick cement
mortar 1:4 (1 cement : 4 coarse sand) including
grouting the joints with tile jointing compounds of
matching colours etc., complete at all floors, levels
and heights.(rooms,balcony,kitchen)

(i) in floors sqm 3661.50

(ii) in skirting sqm 350.00

Providing and laying rectified Glazed Ceramic floor


tiles of size 400x400 mm or more (thickness to be
specified by the manufacturer), of 1st quality
conforming to IS : 15622, of approved make, in all
colours, shades, except White, Ivory, Grey, Fume
20
Red Brown, laid on 20 mm thick Cement Mortar 1:4
(1 Cement : 4 Coarse sand), including pointing the
joints with white cement and matching pigments
etc., complete at all floors, levels and heights.(GF
Toilets)

a Floors Sqm 50.00


Providing and laying in floor heavy duty vitrified
antiskid matt finish tiles of minimum thickness 10
mm without warpage of approved design and
manufacturer laid on 20mm thick cement mortar 1:4
(1 cement:4 coarse sand) including filling the joints
b with pigmented tile joint filler Nitotile-GR or sqm 85.00
equivalent of matching shade and approved
manufacturer as per manufacturers specification
etc. and cleaning the surface with detergent and
water complete (size 300mm x 300mm) (Laundry
and Gym.)

Providing and fixing 18mm thick mirror polish


granite slab of approved colour etc. over 20mm
c
cement mortar 1:3 (1 cement : 3 coarse sand) all
complete at all floors, heights, levels.
In Floors, landings,lift lobby,podiumetc of all sizes
(i) etc in approved patterns.(Area of alab sqm 1019.25
upto0.50sqm)

In kitchen platform, wash basin counter,steps,


(ii) sqm 20.00
risers,skirting etc.(Area of slab over 0.50sqm).

(iii) In lift facade (Area of slab over 0.50sqm). sqm 30.00

Extra for providing edge moulding to 18mm thick


marble stone counters,Vanities etc. over Item No.
(iv) 10(g) including machine polishing to edge to give Metre 30.00
high gloss finish etc. complete as per design
approved by Engineer-in-Charge Granite work

Extra for providing opening of required size & shape


for wash basins/kitchen sink in kitchen platform,
vanity counters and similar location in marble/stone
(v) each 19.00
work including necessary holes for pillar taps etc
.including rubbing and polishing of cut edges to
bring to the original colour etc. complete.
Extra for fixing marble /granite stone over and
above corresponding basic item, in facia and drops
(vi) m 19.00
of width upto 150 mm with epoxy resin based
adhesive including cleaning etc. complete.

Providing and laying CC pavement of mix M25 with


ready mixed concrete from batching plant. The
ready mixed concrete shall be laid and finished with
d screed board vibrator, vacuum dewatering process cum 150.00
and finally finished by floating, brooming with wire
brush etc. complete as per specification and
directions of Engineer-incharge.(Parking area)

Providing and fixing markana Chak doongri marble


stone 18 mm thick, (average) over 20 mm thick
base mortar of proportion 1:4 (1 cement: 4 coarse
sand) laid and jointed with cement slurry including
e rubbing and polishing complete in all respects sqm 134.00
including cutting the stone to make noutch/ offset
on all corners vertical and horizontal and make as
per noutch details in drawing and directed (in
door/window sill) of required sizes in single piece.

Cement plaster skirting of all height with cement


mortar 1:3 ( 1 cement : 3 coarse sand) finished with
f sqm 1050.00
floating coat of neat cement including rounding of
junctions with floor where required. 18 mm thick

52 mm thick cement concrete flooring with


concrete hardener topping, under layer 40 mm
thick cement concrete 1:2:4 (1 cement : 2 coarse
sand : 4 graded stone aggregate 20 mm nominal
size) and top layer 12 mm thick cement hardener
consisting of mix 1:2 (1 cement hardener mix : 2
g Sqm 76.00
graded stone aggregate 6 mm nominal size) by
volume, hardening compound mixed @ 2 litre per
50 kg of cement or as per manufacturer's
specifications. This includes cost of cement slurry,
but excluding the cost of nosing of steps etc.
complete.(Electrical room & AHU)
25 mm thick Kota stone slab flooring over 20 mm
(average) thick base laid over and jointed with grey
cement slurry mixed with pigment to match the
21 Sqm 315.00
shade of the slab, including rubbing and polishing
complete with base of cement mortar 1 : 4 (1
cement : 4 coarse sand)

8 mm thick Laminated wooden flooring of National


finish with classic look of AC4 grade, LWF-
CLASSICA 832 OAK BRIONE PLANK laid over 40
mm thick leveling layer of cement concrete 1:2:4 (1
cement : 2 coarse sand : 4 graded stone aggregate
22 10 mm nominal size) to be paid separately, levelled Sqm 133.00
smooth and finished complete with tongue & groove
joint, end and T profile wherever required with
adhesive bonding quality conforming to IS : 2046
Type S, including cost of adhesive of approved
quality. (Seminar rooms )

8 mm thick Laminated wooden flooring of National


finish with classic look of AC4 grade, LWF-
CLASSICA 832 OAK BRIONE PLANK laid over 25
mm thick waterproof ply base over M. S. frame work
23 paid separately,levelled smooth and finished Sqm 40.00
complete with tongue & groove joint, end and T
profile wherever required with adhesive bonding
quality conforming to IS : 2046 Type S, including
cost of adhesive of approved quality.(Gymnasium)

12 mm thick Laminated wooden flooring of National


finish with classic look of AC4 grade, LWF-
CLASSICA 832 OAK BRIONE PLANK laid over 15
mm thick Cement Plaster 1:4 (1 cement : 4 coarse
sand ) to be paid separately, levelled smooth and
24 Rm 67.00
finished complete with tongue & groove joint, end
and T profile wherever required with adhesive
bonding quality conforming to IS : 2046 Type S,
including cost of adhesive of approved quality.
(Seminar rooms skirting)
Providing and laying Antiskid Vitrified floor tiles
in sizes (600 x 600) mm (thickness to be specified
by the manufacturer) with water absorption less
than 0.08% and conforming to IS: 15622, of
25 approved make, in all colours and shades, laid on Sqm 103.00
20mm thick cement mortar 1:4 (1 cement : 4 coarse
sand), jointing with grey cement slurry @ 3.3kg/sqm
including grouting the joints with white cement and
matching pigments etc., complete.(Toilets)
Providing and fixing PVC sheet flooring of thickness
of 2 mm with HOF-TORO SC/TARKETT the size of
2m x 20m . The product should be homogeneous
and single layered with PUR (Clean Sweep)range.
The wear surface shall consist of impregnated
polyurethane homogeneous mixture of PVC with
TRUESHIELD technology, Plasticizers without DOP,
Urethane, color pigments and filler calendared to
form a sheet. Color and pattern details shall be
dispersed throughout the thickness of the wear
layer. It should conform to group "T" wear
resistance as per EN 685, Flammability resistance
of class Bfl-s1 as per GB8624-2006, Dynamic
coefficient of friction of class DS as per EN 13893,
Thermal Resistance of 0.072m2K/W as per EN
12667, Thermal conductivity of 0.071W/mK as per
26 Sqm 227.00
EN12524, impact sound reduction of 3dB as per
ISO 10140, Slip Resistance of class R9 as per DIN
51130, Residual indentation of 0.03mm as per GB/T
4085-2005, Color fastness rating of ≥6 as per ISO
105-B02, total weight being 3.3kg/m2 as per
EN430. The product shall be suitable for
applications in class 23/34/43 areas as per EN685.
Product shall exhibit antistatic behavior, resistance
to bacteria, resistance to chemical, resistance to
staining, suitability to castor chair. The product shall
be Floor Score certified with no SVHC content
published by European Chemicals Agency
(REACH). Product shall contribute to LEED points
under Indoor environmental quality category.
Equivalent to Armstrong Medintech Plus.

Extra for joining of PVC sheets by Hot Weelding


27 Rm 150.00
Chord.

28 DADO
Providing and fixing 1st class degital ceramic tiles
of approved designs and makes of minimum
thickness 5.6 mm in dado in any pattern over 12
mm thick cement plaster 1:3 (1 cement : 3 coarse
sand) and jointed with tile jointing compound of
approved manufacturer complete as directed.

a 300mm x 450mm in kitchen,toilets,OHT. sqm 750.00

Kota stone slabs 20 mm thick in risers of steps,


skirting, dado and pillars laid on 12 mm (average)
thick cement mortar 1:3 (1 cement: 3 coarse sand)
b Sqm 25.00
and jointed with grey cement slurry mixed with
pigment to match the shade of the slabs, including
rubbing and polishing complete.

Extra for pre finished nosing in treads of steps


c Rm 10.00
of Kota stone/ sand stone slab.

Extra for Kota stone/ sand stone in treads of steps


d Sqm 25.00
and risers using single length up to 1.05 metre.

18 mm thick Cement plaster skirting up to 30 cm


e height, with cement mortar 1:3 (1 cement : 3 coarse Sqm 379.00
sand), finished with a floating coat of neat cement.

Extra for making chequers of approved pattern on


f cement concrete floors, steps, landing, pavements Sqm 105.00
etc.
DOORS AND WINDOWS
Providing and fixing pressed steel door frames
conforming to IS: 4351, manufactured from
commercial mild steel sheet of 1.60 mm thickness,
including hinges, jamb, lock jamb, bead and if
required angle threshold of mild steel angle of
section 50x25 mm, or base ties of 1.60 mm,
29 pressed mild steel welded or rigidly fixed together
by mechanical means, including M.S. pressed
butt hinges 2.5 mm thick with mortar guards, lock
strike plate and shock absorbers as specified and
applying a coat of approved steel primer after pre-
treatment of the surface as directed by Engineerin-
charge: [Profile E]

Fixing with adjustable lugs with split end tail to each


a Rm 50.00
jamb

Providing and fixing of WFC (Wood Fibre


Composite)Door frame of size 125 x 65mm solid
with special wooden hot stamping/pigmented of
similar colour of door shutterduly attached with
b Architrave of same colour of 64.2mm width and m 595.00
12mm thickness on all the borders of the door
frame. The Door Frame should be, insect
,pest,water,acid proof and it should also be certified
by IGBC.

Providing and fixing of WFC ( Wood Fibre


Composite)Door Panel/shutter made of extruded
multicavity one piece having over all thickness of
30mm with side thickness portion of 15mm, with
high pressure laminate of desired colour duly
30 compressed with closing of bottom and upper side
and suitable reinforced at hinges side to hold
screws. The door panel should be insect
,pest,water,acid proof and it should also be certified
by IGBC. The product should be paintable and
polishable.
30 mm thick sqm 285.00

Providing and fixing Hollow metal fire rated doors


as per IS 3614 part-1 & part-2 for stability and
integrity. Pressed Galvanized steel confirming to IS
277 with the following specification. Recommended
fire door shall have doors tested at CBRI for
maximum rating of 2hrs tested . Individual Test
certificates should also be available for glass used
in vision lites confirming the required fire ratings
/panels being a part of the fire door assembly.
Doors should be finished in Thermosetting Powder
Coating desired RAL Shades. Manufacturer test
31
certificate shall cover doors both single & double
leaf doors and Hardwares should pass European
certificate "CE" of conformity / UL with required fire
ratings. Any deviation in specification and sheet
thickness other than what is mentioned in the test
certificates are not allowed. Proper label confirming
the type of door and the hourly rating is mandatory.
Approved manufacturer Navair International Ltd or
equivalent subject to approval. And should be ISO
Certified company. The approved manufacturer are
Navair,AGNI suraksha, Godrej or equivalent .
Door frame shall be double rebate profile of
minimum size 154mm X 77 mm made out of
1.60mm (16gauge) minimum thick galvanized steel
sheet. NDRF 154x77 Frames shall be Butt jointed
and field assembled with self bolted. The frames
should be finished with Thermosetting Powder
Coating in desired RAL Shade. All provision should
be mortised, drilled and tapped for receiving
appropriate hardware. Frames should be provided
with back plate bracket and anchor fasteners for
installation on a finished plastered masonry wall
opening.

Door leaf shall be minimum 49mm thick fully flush


double skin door with or without vision lite. Door leaf
shall be manufactured from 1.20mm minimum thick
galvanised steel sheet. The internal construction of
the door should be rigid reinforcement pads for
receiving appropriate hardware. The infill material
shall be Rockwool treated with Viper FRS 881 LH.
All doors NSD 12049 shall be factory prepped for
receiving appropriate hardware and provided with
necessary reinforcement for hinges, locks, and door
closers. The edges should be interlocked with a
bending radius of 1.4mm. For pair of doors
astragals has to be provided on the meeting stile for
both active and inactive leaf. Vision lite shall be as
per direction of engineer in charge with a beeding
and screws from inside.The glass should be
contraflam Door Lite 11 mm of minimum size
350mm x 500mm clear 120 min fire rated and
partially insulated (EW120), Clear Toughened,
interlatered glass having a sound reduction of
>37dB, LT of 86% and compliant to class 2(B)2
category of Impact Resistance as per EN 12600
standard from Saint Gobain. ( Vision panel
All doors and frames shall be finished with Powder
coating in desired Shades. Rate should include
supply and installation of door and hardware as per
application

The rate includes the cost of all the materials, labor


& T & P required for proper completion of the item
decribed above. (For payment purpose the area of
opening including door frame shall only be
measured). The agency shall provide one number
additional door alongwith all frame and fittings for sqm 94.00
getting it tested from CBRI Roorkee and in case
sample fails, additional sets after improvement shall
be provided for testing till the item passes in tests,
which shall not be included in measurements for
payment. (Main entry Door)

Providing and fixing glazing in fire resistant door


shutters, fixed panels, ventilators and partitions
etc., with G.I. beading of appropriate size, made out
of 20 SWG G.I.sheet (zinc coating not less than 120
32
gm/m2), fire resistant sealant, including applying a
coat of approved fire resistant primer on G.I.
beading etc., complete all as per direction of
Engineer-incharge.

With clear fire resistant glass panes 6mm thick of


33 approved brand, having minimum 60 minutes fire Sqm 71.00
resistance

Providing and fixing ISI marked flush door shutters


conforming to IS : 2202 (Part I) non-decorative type,
core of block board construction with frame of 1st
34
class hard wood and well matched commercial 3 ply
veneering with vertical grains or cross bands and
face veneers on both faces of shutters:

35 mm thick including ISI marked Stainless Steel


Sqm 112.00
butt hinges with necessary screws.
Providing & Fixing decorative high pressure
laminated sheet of plain / wood grain in gloss / matt/
suede finish with high density protective surface
35
layer and reverse side of adhesive bonding quality
conforming to IS : 2046 Type S, including cost of
adhesive of approved quality.

1.5 mm thick Sqm 225.50

Providing and fixing Pre-laminated flat pressed 3


layer (medium density) particle board or graded
wood particle board IS : 3087 marked, with one side
decorative and other side balancing lamination
36
Grade I, Type II exterior grade IS : 12823 marked,
in shelves with screws and fittings wherever
required, edges to be painted with polyurethane
primer (fittings to be paid separately).

25 mm thick Sqm 127.00

Providing and fixing cup board shutters 25 mm


thick, with Pre-laminated flat pressed three layer
particle board or graded wood particle board IS:
12823 marked, exterior grade (Grade l Type ll),
having one side decorative lamination and other
37 Sqm 130.00
side balancing lamination, including IInd class teak
wood lipping of 25 mm wide x12 mm thick with
necessary screws and bright finished stainless steel
piano hinges, complete as per direction of the
Engineer-in-Charge

Extra for providing lipping with 2nd class teak


wood battens 25 mm minimum depth on all edges
38 Sqm 208.00
of flush door shutters (over all area of door shutter
to be measured).
Providing, fitting and fixing transparent P.V.C. sheet
of 1 mm thickness to be fixed to door shutter of
39 sqm 216.00
toilet as per drawings and directions of Engineer-
in–charge. (In toilet doors).
Extra for providing vision panel of Rectangular
or square not exceeding 0.1 sqm in all type of flush
40 Sqm 112.00
doors (cost of glass excluded) (overall area of door
shutter to be measured):

Providing and fixing bright /matt finished Stainless


41 Steel handles of approved quality & make with Each 232.00
necessary screws etc all complete with 125 mm.

Providing and fixing bright /matt finished Stainless


42 Steel handles of approved quality & make with Each 224.00
necessary screws etc all complete with 200 mm.

Providing and fixing IS : 12817 marked stainless


43 steel butt hinges (heavy weight) with stainless
steel screws etc. complete :

a 125x64x2.50 mm Each 344.00

b 100x60x2.50 mm Each 168.00

c 75x50x2.50 mm Each 204.00

Providing and fixing Stainless steel tower bolts


44
with necessary screw etc. complete.

(i) 300x10 mm long(Make Model code 8577 of Godrej) each 266.00

(ii) 150x10 mm long(Make Model code 8576 of Godrej) each 126.00


Providing and fixing special quality bright finished
brass cupboard or ward robe locks with four levers
45 Each 52.00
of approved quality including necessary screws etc.
complete. 65mm

Providing and fixing bright finished brass hanging


46 type floor door stopper with necessary screws, Each 196.00
etc. complete.

Providing and fixing aluminium extruded section


body tubular type universal hydraulic door closer
(having brand logo embossed on the body, door
47 Each 48.00
weight upto 80 kg to 120 kg with double speed
adjustment with necessary accessories and screws
etc. complete.

Providing and fixing chromium plated brass 100


mm mortice latch and lock with 6 levers and a
48 Each 66.00
pair of lever handles of approved quality with
necessary screws etc. complete.

Providing and fixing chromium plated brass 50 mm


49 Each 104.00
cupboard or wardrobe knobs with nuts complete.

Supply of Pad locks ( Make: Model Ultra Sherlock


50 each 70.00
code 3293 of Godrej)

Providing and fixing stainless steel sliding bolt with


nuts and screws etc. in entrance door shutters
51 including necessary arrangement for fixing in door
shutters with additional hook for providing lock in
open position of the door complete 250x16mm.

a 300x16mm (Make: Model code 8541 of Godrej) each 87.00

b 200x16mm (Make: Model code 8539 of Godrej) each 30.00


Providing and fixing stainless steel rubber hanging
c floor door stopper with necessary screws etc. Each
complete.(Make Model code 8830 of Godrej)
Providing and fixing magnetic catcher of approved
quality in cupboard / ward robe shutters, including
52 Each 200.00
fixing with necessary screws etc. complete. Triple
strip vertical type

Providing and fixing PVC 32mm dia Door buffer in


53 doors including necessary screws etc complete. each 62.00
(Make : Model code 8618 of Godrej)

Providing and fixing stainless steel curtain rod


54 including finial,bracket,rings etc. complete.(make m 245.00
Vista,MAC or equivalent)

Structural steel work in single section, fixed with or


without connecting plate, including cutting, hoisting,
55 Kg 1410.00
fixing in position and applying a priming coat of
approved steel primer all complete.

Supplying and fixing rolling shutters of approved


make, made of required size M.S. laths, interlocked
together through their entire length and jointed
together at the end by end locks, mounted on
specially designed pipe shaft with brackets, side
guides and arrangements for inside and
56
outside locking with push and pull operation
complete, including the cost of providing and fixing
necessary 27.5 cm long wire springs manufactured
from high tensile steel wire of adequate strength
conforming to IS: 4454 - part 1 and M.S. top cover
of required thickness for rolling shutters.

80x1.25 mm M.S. laths with 1.25 mm thick top


Sqm 18.00
cover

57 Providing and fixing ball bearing for rolling shutters. Each 6.00
Extra for providing grilled rolling shutters
manufactured out of 8 mm dia M.S. bar instead of
58 Sqm 4.00
laths as per design approved by Engineer-in-
charge, (area of grill to be measured).

Providing and fixing circular/ Hexagonal cast iron


or M.S. sheet box for ceiling fan clamp, of
internal dia 140 mm, 73 mm height, top lid of 1.5
mm thick M.S. sheet with its top surface hacked for
59 proper bonding, top lid shall be screwed into the Each 75.00
cast iron/ M.S. sheet box by means of 3.3 mm dia
round headed screws, one lock at the corners.
Clamp shall be made of 12 mm dia M.S. bar bent to
shape as per standard drawing.

Steel work in built up tubular ( round, square or


rectangular hollow tubes etc.) trusses etc., including
cutting, hoisting, fixing in position and applying a
60 Kg 7648.00
priming coat of approved steel primer, including
welding and bolted with special shaped washers
etc. complete.

Providing and fixing mild steel round holding down


61 Kg 450.00
bolts with nuts and washer plates complete.

Steel work welded in built up sections/ framed work,


including cutting, hoisting, fixing in position and
62
applying a priming coat of approved steel primer
using structural steel etc. as required.

In gratings, frames, guard bar, ladder, railings,


Kg 27721.00
brackets, gates, grill and similar works
Providing and fixing stainless steel ( Grade 304)
railing made of Hollow tubes, channels, plates etc.,
including welding, grinding, buffing, polishing and
making curvature (wherever required) and fitting the
same with necessary stainless steel nuts and bolts
63 Kg 9151.00
complete, i/c fixing the railing with necessary
accessories & stainless steel dash fasteners ,
stainless steel bolts etc., of required size, on the top
of the floor or the side of waist slab with suitable
arrangement as per approval of Engineer-incharge,

Providing and fixing carbon steel galvanised


( minimum coating 5 micron) dash fastener of 10
mm dia double threaded 6.8 grade (yield strength
64 480 N/mm2), counter sunk head, comprising of 10
m dia polyamide PA 6 grade sleeve, including
drilling of hole in frame , concrete/ masonry, etc. as
per direction of Engineer-in-charge.

a 10 x 60 mm Each 2400.00

b 10 x 140 mm Each 1196.00

Providing and fixing thermal insulation of ceiling


(under deck insulation) with Resin Bonded Fibre
glass wool conforming to IS : 8183, density 24kg /
65 m3, 50mm thick, wrapped in 200 G Virgin Polythene Sqm 99.00
bags, fixed to ceiling with metallic cleats (50x50x3
mm) @ 60 cm and wire mesh of 12.5 mm x 24
gauge wire mesh, for top most ceiling of building.

FINISHING

15 mm cement plaster on rough side of single or


66 Sqm 12912.00
half brick wall of mix 1:6 (1 cement: 6 coarse sand)
20 mm cement plaster of mix 1:4 (1 cement: 4
67
coarse sand)
Note :- Rates for external plaster are for height upto
10m from ground level in less otherwise stated. Ie. Sqm 5075.00
Upto 3rd floor Lv
Including extra for plastering exterior walls of height
68 more than 10 m from ground level for every
additional height of 3 m or part thereof.

a 3rd. FLOOR Lv. Sqm 1353.21

b 4th. FLOOR Sqm 1293.65

c 5th. FLOOR Sqm 1293.65

d 6th. FLOOR Sqm 1293.65

e 7th. FLOOR Sqm 1293.65

f 8th. FLOOR Sqm 1231.21

g 9th. FLOOR Sqm 735.21

6 mm cement plaster of mix 1:3 (1 cement : 3 fine


69 Sqm 6748.00
sand)
Providing and fixing 150mm wide 12 guage
25mmx25mm wire mesh over joints between RCC
70 columns, beams, lintels facias and brick wall with U m 5080.00
type MS nails and spread cement mortar 1:3 (1
cement : 3 coarse sand) to fix in position.

Making of 12mmx25mm groove in exterior plastered


surface or RCC projection at all heights, floors and
levels. Grooves shall be made by fixing of
71 m 500.00
alluminum channels of required sizes in the
required paterns to the walls before plastering and
shall be removed after plastering.

Providing and applying white cement based water


proof putty of approved brand and manufacturer,
72 Sqm 28296.00
over the exterior plastered wall surface to prepare
the surface even and smooth complete.

Finishing walls with fungus and algae resistant


superior grade water proof acrylic paint of approved
brands and manufacturers and of required shades
73 after surface preparation to give an even shade to Sqm 13294.00
all external surfaces of exterior walls (minimum two
or more coats) including application of one coat of
exterior primer at all heights, floors and levels.

74 Neat cement punning. Sqm 272.00

Extra for plastering on circular work not exceeding 6


75
m in radius:

76 In one coat Sqm 317.00

Wall painting with acrylic emulsion paint of


77 approved brand and manufacture to give an even Sqm 15349.00
shade with Two or more coats on new work

Applying one coat of water thinnable cement primer


78 of approved brand and manufacture on wall Sqm 15349.00
surface.
Finishing walls with textured exterior paint of
79
required shade
New work (Two or more coats applied @ 3.28 ltr/10
a sqm) over and including priming coat of exterior Sqm 647.00
primer applied @ 2.20kg/10 sqm

Applying priming coat with ready mixed red oxide


b zinc chromate primer of approved brand and Sqm 111.00
manufacture on steel galvanised iron/ steel works

Wall painting with acrylic emulsion paint of


c approved brand and manufacture to give an even Sqm 300.00
shade with Two or more coats on new work

Painting with synthetic enamel paint of approved


d brand and manufacture to give an even shade with Sqm 155.00
Two or more coats on new work

Finishing walls with water proofing cement paint of


e approved brand and manufacture and of required sqm 661.00
shade to give an even shade -Three or more coats

Extra for plastering exterior walls of height more


f than 10 m from ground level for every additional sqm 24221.72
height of 3 m or part thereof.
Roofing Work
Providing gola 75mmx75mm in cement concrete
1:2:4 ( 1 cement : 2 coarse sand : 4 stone
aggregate 10mm and down gauge) including
80 metre 400.00
finishing with cement mortar 1:3 ( 1 cement : 3 fine
sand) as per standard design 75x75mm deep
chase.

Making Khurras 45cmx45cm with average min.


thickness of 5cm cement concrete 1:2:4 ( 1
cement : 2 coarse sand : 4 graded stone aggregate
of 20mm nominal size) over PVC sheet 1mx1mx400
81 each 50.00
micron, finished with 12mm cement plaster 1:3 ( 1
cement : 3 coarse sand ) and a coat of neat cement
rounding the edges and making and finishing the
outlet complete.

82 WATER PROOFING
Providing water proofing treatment with best quality
acrylic polymer modified cementitious composite
slurry coating and fibre glass cloth of approved
brand over sunken floors & terraces as per
manufacturer’s specifications and as approved by
Engineer-in-charge. The waterproofing membrane
applied shall be subjected to water ponding test by
a Sqm 1152.00
filling minimum 50 mm water for 2-3 days or as
specified by Engineer - In charge. Areas to be
observed from bottom and all wet spots & water
leakage area should be marked for treatment. If the
wet areas are observed, they should be treated by
reapplication of waterproofing membrane.(sunken
floor of toilet & kitchen, tiolet walls, )

Providing 12mm thick plaster to protect


b waterproofing treatment in cement mortar 1:4 sqm 1152.00
( 1cement : 4 coarse sand) .

Grading roof for water proofing treatment with;


c Cement concrete 1:2:4 ( 1cement:2 coarse sand: 4 cum 234.00
graded stone aggregate 20mm nominal size)

Providing and mixing water proofing material in


d cement concrete/cement mortar in proportion as bag 1872.00
recommended by the manufacturer.
83 Water proofing Treatment at Roof surface.

Labour for cleaning of concrete surface to remove


dust, oil, grease including removal of existing loose
paint / coating, and cement laitance by cleaning
with compressed air, including all materials, labour,
tools and tackles complete Repairing surface
a irregularities, damaged concrete in base slab, if any, Sqm 2614.00
with a styrene butadiene polymer, Sika Latex or
equivalent modified repair mortar including a coat of
bonding agent of the same with cement slurry
including all material, labour, tools and tackles
complete
Providing and applying 2 coats of Sikatop seal
109hi - 2 or approved equivalent, componant
polymer modified coating after application of
b Sikatop seal 109hi primer over the roof after proper Sqm 2614.00
surface preparation.A glass fibre cloth shall be put
in between two coats including labour tools and
tackles etc all complete.

Supply and application of 1:3 cement-sand mortar,


mixed with Sika-Top 77 or approved equivalent the
polymer modified high quality emultion,as a coving
c Sqm 2614.00
the corners of floors and the vertical surface in the
sunken area, and between floor and walls in the
remaining area.
84 uPVC Windows

Providing, supplying & fixing of Fixed Window


made out of multi chambered uPVC sections with
TPV gaskets having isolated drainage and
reinforced with Galvanized Iron of 120 GSM
profiles through out the window. The outer frame
having a overall size of 60 x 55 mm with
reinforcement of 1 mm thickness and Mullion with
overall size of 74 x 60 mm with reinforcement of
a 1mm thickness. Composition of profile shall Sqm 136.00
consists a minimum of 6 PHR of TiO₂ for every 100
parts of PVC resin.Window panels shall be provided
with 20mm DG Glass . Wall thickness of frame &
Mullion shall be 2.2 - 2.4 mm. Cost is inclusive of all
taxes, materials, labour, hire charges of
manchineries all lead and lifts etc.,complete as per
the directions of the Engineer-in charge of work.
Providing, supplying & fixing of Openable Door
made out of multi chambered uPVC sections with
TPV gaskets having isolated drainage and
reinforced with Galvanized Iron of 120 GSM
profiles through out the window. The outer frame
having a overall size of 60 x 55 mm with
reinforcement of 1 mm thickness and sash with
overall size of 60 x 102 mm with reinforcement of 2
mm thickness. Glazing bead for fixing of glass shall
b be of size 20 x 18mm and coextruded with gasket. Sqm 60.80
Composition of profile shall consists a minimum of 6
PHR of TiO₂ for every 100 parts of PVC resin.
Doors shall be provided with 20mm DG Glass ,
standard hardware & Multi point locking system of
Espag type adn 3D hinges. Wall thickness of frame
& sash shall be 2.2 - 2.4 mm. Cost is inclusive of all
taxes, materials, labour, hire charges of
manchineries all lead and lifts etc., complete as per
the directions of the Engineer-in charge of work.
Providing, supplying & fixing of 2Track - 2Panel
Sliding Window With Bottom Fixed made out of
multi chambered uPVC sections with TPV gaskets
having isolated drainage and reinforced with
Galvanized Iron of 120 GSM profiles through out
the window. The top/bottom outer frame shall be
provided with 60 x 55 mm profile and reinforced
with 1.0 mm thickness. The outer frame having a
overall size of 60 x 45 mm with reinforcement of 1
mm thickness and sash with overall size of 39 x 58
c mm with reinforcement of 1.5 mm thickness. Sqm 25.60
Glazing bead for fixing of glass shall be of size 20 x
18mm and coextruded with gasket. Composition of
profile shall consists a minimum of 6 PHR of TiO₂
for every 100 parts of PVC resin. Windows shall be
provided with 20mm DG glass, standard hardware
& Flush locking system. Wall thickness of frame &
sash shall be 2.2 - 2.4 mm.Cost is inclusive of all
taxes, materials, labour, hire charges of
manchineries all lead and lifts etc.,complete as per
the directions of the Engineer-in charge of work.
Providing, supplying & fixing of 3 Track - 3 Panel
Sliding Window with Top Fixed made out of multi
chambered uPVC sections with TPV gaskets having
isolated drainage and reinforced with Galvanized
Iron of 120 GSM profiles through out the window.
The fixed window having a overall size of 60 x 55
mm with reinforcement of 1 mm thickness and
sliding frame with outer frame of 108 x 45mm with
sash of size 39 x 58mm with reinforcement of
1.5mm .Glazing bead for fixing of glass shall be of
d Sqm 63.20
size 20 x 18mm and coextruded with gasket.
Composition of profile shall consists a minimum of 6
PHR of TiO₂ for every 100 parts of PVC resin.
Windows shall be provided with 20mm DG glass,
standard hardware & Flush locking system. Wall
thickness of frame & sash shall be 2.2 - 2.4
mm.Cost is inclusive of all taxes, materials, labour,
hire charges of manchineries all lead and lifts
etc.,complete as per the directions of the Engineer-
in charge of work.

Providing, supplying & fixing of Fixed Window


made out of multi chambered uPVC sections with
TPV gaskets having isolated drainage and
reinforced with Galvanized Iron of 120 GSM
profiles through out the window. The outer frame
having a overall size of 60 x 55 mm with
reinforcement of 1 mm thickness and Mullion with
overall size of 74 x 60 mm with reinforcement of
e 1mm thickness. Composition of profile shall Sqm 100.80
consists a minimum of 6 PHR of TiO₂ for every 100
parts of PVC resin.Window panels shall be provided
with 20mm DG Glass . Wall thickness of frame &
Mullion shall be 2.2 - 2.4 mm. Cost is inclusive of all
taxes, materials, labour, hire charges of
manchineries all lead and lifts etc.,complete as per
the directions of the Engineer-in charge of work.
Providing, supplying & fixing of 2Track - 2Panel
Sliding Window made out of multi chambered
uPVC sections with TPV gaskets having isolated
drainage and reinforced with Galvanized Iron of 120
GSM profiles through out the window.The outer
frame having a overall size of 60 x 45 mm with
reinforcement of 1 mm thickness and sash with
overall size of 39 x 58 mm with reinforcement of 1.5
mm thickness. Glazing bead for fixing of glass shall
f be of size 20 x 18mm and coextruded with gasket. Sqm 141.00
Composition of profile shall consists a minimum of 6
PHR of TiO₂ for every 100 parts of PVC resin.
Windows shall be provided with 20mm DG glass,
standard hardware & Flush locking system. Wall
thickness of frame & sash shall be 2.2 - 2.4
mm.Cost is inclusive of all taxes, materials, labour,
hire charges of manchineries all lead and lifts
etc.,complete as per the directions of the Engineer-
in charge of work.

Providing, supplying & fixing of 2Track - 2Panel


Sliding Window made out of multi chambered
uPVC sections with TPV gaskets having isolated
drainage and reinforced with Galvanized Iron of 120
GSM profiles through out the window.The outer
frame having a overall size of 60 x 45 mm with
reinforcement of 1 mm thickness and sash with
overall size of 39 x 58 mm with reinforcement of 1.5
mm thickness. Glazing bead for fixing of glass shall
g be of size 20 x 18mm and coextruded with gasket. Sqm 122.00
Composition of profile shall consists a minimum of 6
PHR of TiO₂ for every 100 parts of PVC resin.
Windows shall be provided with 20mm DG glass,
standard hardware & Flush locking system. Wall
thickness of frame & sash shall be 2.2 - 2.4
mm.Cost is inclusive of all taxes, materials, labour,
hire charges of manchineries all lead and lifts
etc.,complete as per the directions of the Engineer-
in charge of work.
Providing, supplying & fixing of 2Track - 2Panel
Sliding Window made out of multi chambered
uPVC sections with TPV gaskets having isolated
drainage and reinforced with Galvanized Iron of 120
GSM profiles through out the window.The outer
frame having a overall size of 60 x 45 mm with
reinforcement of 1 mm thickness and sash with
overall size of 39 x 58 mm with reinforcement of 1.5
mm thickness. Glazing bead for fixing of glass shall
h be of size 20 x 18mm and coextruded with gasket. Sqm 26.00
Composition of profile shall consists a minimum of 6
PHR of TiO₂ for every 100 parts of PVC resin.
Windows shall be provided with 20mm DG glass,
standard hardware & Flush locking system. Wall
thickness of frame & sash shall be 2.2 - 2.4
mm.Cost is inclusive of all taxes, materials, labour,
hire charges of manchineries all lead and lifts
etc.,complete as per the directions of the Engineer-
in charge of work.
Providing, supplying & fixing of 2Track - 2Panel
Sliding Window With Top & Bottom Fixed made
out of multi chambered uPVC sections with TPV
gaskets having isolated drainage and reinforced
with Galvanized Iron of 120 GSM profiles through
out the window. The top/bottom outer frame shall be
provided with 60 x 55 mm profile and reinforced
with 1.0 mm thickness. The outer frame having a
overall size of 60 x 45 mm with reinforcement of 1
mm thickness and sash with overall size of 39 x 58
i mm with reinforcement of 1.5 mm thickness. Sqm 208.80
Glazing bead for fixing of glass shall be of size 20 x
18mm and coextruded with gasket. Composition of
profile shall consists a minimum of 6 PHR of TiO₂
for every 100 parts of PVC resin. Windows shall be
provided with 20mm DG glass, standard hardware
& Flush locking system. Wall thickness of frame &
sash shall be 2 - 2.2 mm.Cost is inclusive of all
taxes, materials, labour, hire charges of
manchineries all lead and lifts etc.,complete as per
the directions of the Engineer-in charge of work.
Providing, supplying & fixing of Top Hung Window
made out of multi chambered uPVC sections with
TPV gaskets having isolated drainage and
reinforced with Galvanized Iron of 120 GSM
profiles through out the window. The outer frame
having a overall size of 60 x 55 mm with
reinforcement of 1 mm thickness and sash with
overall size of 60 x 75 mm with reinforcement of 1.5
mm thickness. Glazing bead for fixing of glass shall
j be of size 20 x 18mm and coextruded with gasket. Sqm 42.40
Composition of profile shall consists a minimum of 6
PHR of TiO₂ for every 100 parts of PVC resin. They
shall be provided with 5mm Clear glass, standard
hardware & Multi point locking system of Espag
type/ Wall thickness of frame & sash shall be 2 - 2.2
mm.Cost is inclusive of all taxes, materials, labour,
hire charges of manchineries all lead and lifts
etc.,complete as per the directions of the Engineer-
in charge of work.
Providing, supplying & fixing of Top Hung Window
made out of multi chambered uPVC sections with
TPV gaskets having isolated drainage and
reinforced with Galvanized Iron of 120 GSM
profiles through out the window. The outer frame
having a overall size of 60 x 55 mm with
reinforcement of 1 mm thickness and sash with
overall size of 60 x 75 mm with reinforcement of 1.5
mm thickness. Glazing bead for fixing of glass shall
k be of size 20 x 18mm and coextruded with gasket. Sqm 8.00
Composition of profile shall consists a minimum of 6
PHR of TiO₂ for every 100 parts of PVC resin. They
shall be provided with 5mm Clear glass, standard
hardware & Multi point locking system of Espag
type/ Wall thickness of frame & sash shall be 2 - 2.2
mm.Cost is inclusive of all taxes, materials, labour,
hire charges of manchineries all lead and lifts
etc.,complete as per the directions of the Engineer-
in charge of work.

MISCELLANEOUS ITEMS
Providing and fixing 40mm dia G.I. pipe for spout
85 including cutting holes in walls and making good the
same.

600mm long each 80.00


Providing and fixing false ceiling tiles of
Dexune/Armstrong/Nittobo make of size 595x595
mm in true horizontal level suspended in inter
locking metal grid of hot dipped galvanised steel
sections (galvanised @170gsm/sqm) consisting of
main "T" runner suitably spaced at joints to get
required length and size of 15x32mm made from
0.30 mm thk (minimum) sheet spaced at 1200 mm
c/c and cross tee of size 15x27mm made of 0.3mm
thk (minimum) sheet, 1200 mm long spaced
between main Tat 600 mm c/c to form a grid of
1200x600mm and secondary cross T of length
86
600mm and size 15x27 mm made of 0.30 mm thk
(minimum) sheet to be interlocked at middle of the
1200x600 mm panel to form grids of 600x600mm
and laying false ceiling tiles of approved texture in
the grid including, wherever, required,
cutting/making,opeings for services like
diffusers,grills,light fittings, fixtures, smoke detectors
etc. Main T runners to be suspended from ceiling
using GI slotted cleats fixed to the ceiling with 6mm
dia and 50mm long dash fastners,4mm GI
adjustable rods with galvanised level clips spaced
at 1200 mm

c/c along main T , bottom exposed width of 15 mm


of all the T sections shall be prepainted with
polyester paint, all complete t all heights as per
specifications drawings & as directed by engineer sqm 2610.00
incharge. the rate is including cost of mineral fibre
600mmx600mm Armstrong/Dexune/Nittobo ceiling
tiles dune 15mm thk micro look white colour
Supply and fixing of approved brand 150F Plain
Aluminum Panel Facade Cladding of approved
manufacturer manufactured of approved colour
consisting of panels150mm wide x17mm deep x
87 0.7mm thick panel length up to 6 mtrs, Coil Coated
on a Continuous Paint Line, Double-baked and roll
farmed from enameled Corrosion Resistance
Aluminium Alloy AA3005 (Al.Mn) for higher Strength
and good Roll Forming characteristics.

Panel shall be clipped to Baked enamel!ed


Aluminium Panel Carrier of 34.5 mm wide x 48mm
deep x0.95mm thick in Standard lengths of 5metrs
made of double baked enameled Aluminum Alloy
AA'5050(Al..Mg).The panel Carrier Shall be
mounted by Means of suitableSub-Structure (shall
be charged as extra as separate item).

Paint Finish: Aluminium panels :shall be


chromatised for Maximum bond between metal and
paint enameled twice under high temperature one
Sqm 457.60
side with full primer and Luxacote finish the other
side (innerside)with a primer coat and skin coat on
a Continuous Paint Line

Drilling with core cutting machine in RCC


beams,slabs,floorsetc.,for laying pipes and
rendering the same in RCC 1:2:4 finishing the same
to the satisifaction of the owner or his authorised
representative etc.,including nominal reinforcement
88
wherever required,complete,at all levels The quote
shall also include for providing EPOXY based water
proofing compound for sealing the joints around the
pipes upto 250mm max depth at all heights & levels

Above 75mm dia and upto 100mm dia. (depth of


a Nos 37.00
hole 100 mm to 200 mm)
Above 101mm dia. and up to 200mm dia (depth of
b Nos 66.00
hole 100 mm to 200 mm)

ALUMINIUM WORKS

Providing and fixing aluminium work for doors,


windows, ventilators and partitions with extruded
built up standard tubular sections/ appropriate Z
sections and other sections of approved make
conforming to IS: 733 and IS: 1285, fixing with dash
fasteners of required dia and size, including
necessary filling up the gaps at junctions, i.e. at top,
bottom and sides with required EPDM rubber/
89
neoprene gasket etc. Aluminium sections shall be
smooth, rust free, straight, mitred and jointed
mechanically wherever required including cleat
angle, Aluminium snap beading for glazing /
paneling, C.P. brass / stainless steel screws, all
complete as per architectural drawings and the
directions of Engineer-in-charge. (Glazing, paneling
and dash fasteners to be paid for separately) :

a For fixed portion


Polyester powder coated aluminium
(minimum thickness of polyester powder Kg 404.00
coating 50 micron)

For shutters of doors, windows & ventilators


including providing and fixing hinges/ pivots and
making provision for fixing of fittings wherever
b
required including the cost of EPDM rubber /
neoprene gasket required (Fittings shall be paid for
separately)

Polyester powder coated aluminium


(minimum thickness of polyester powder Kg 880.00
coating 50 micron)
Providing and fixing glazing in aluminium door,
window, ventilator shutters and partitions etc. with
PVC/ neoprene gasket etc. complete as per the
c
Architectural drawings and the direction of Engineer
- in - Charge (Coast of aluminium snap beading
shall be paid in basic item) :

(i) With frosted glass panes of 4.0 mm thickness sqm 43.00

(ii) With float glass panes of 5.0 mm thickness sqm 162.00

(iii) Extra for providing toughening of glass sqm 162.00

Filling the gap in between aluminium frame &


adjacent RCC/ Brick/ Stone work by providing
d weather silicon sealant over backer rod of
approved quality as per architectural drawings and
direction of Engineer-in-charge complete.

Upto 5mm depth and 5 mm width Rm 1713.00

Providing and fixing 12 mm thick prelaminated


particle board flat pressed three layer or graded
wood particle board conforming to IS: 12823 Grade
l Type ll, in panelling fixed in aluminum doors,
e
windows shutters and partition frames with C.P.
brass / stainless steel screws etc. complete as per
architectural drawings and directions of Engineer-in-
charge.

Pre-laminated particle board with decorative


f Sqm 114.00
lamination on both sides
Providing & fixing double action hydraulic floor
spring of approved brand and manufacturer
(conforming IS:6315) for aluminium doors including
cost of cutting floors as required, embedding in
90
floors and cover plates etc. as per direction of
Engineer-in-Charge.(With stainless steel cover plate
minimum 1.25 mm thickness of D60 Floor spring
(60 kg) LKYGDF0FS 7477 Godrej Make)

With SS cover plate minimum 1.25 mm thickness Each 128.00

91 EXPANSION JOINT
Expansion Joints Treatment with Sikadur Combiflex
a
System

Step-1. Removal of extra topping between the


expansion joint area: Preparation of Expansion
Joint edge by grinding and removal of all loose
particles, dirt, dust etc to make the surface clean
including scaffolding , tools tackles etc all complete

Step-2. Providing and Mixing of epoxy adhesive


sikadur 31 C (2:1) by mechanical mixture and apply
on the 50 mm surface of both sides as per the
manufacturer specification including tools, labour,
machines etc all complete

Step-3. Providing and Fixing of Hypalon based


Sikadur Combiflex SG strip (200 mm width x 2mm
thickness on the expansion joint as per the
manufacturer specification including tools, labour,
machines scaffoldings etc all complete

Step-4. Finally Providing and Mixing of epoxy


adhesive sikadur 31 C (2:1) by mechanical mixture
and apply on the 50 mm surface of both sides as
Rm 450.00
per the manufacturer specification including tools,
labour, machines etc all complete as a protective
coating
Preparing the surface by cleaning and chipping the
surface for removing loose, laitance etc. All the
construction joints should be cut in a groove and
wash the entire surface thoroughly by water making
b the surface saturated dry condition and filling the Rm 450.00
gaps with polymer modified mortar with Asian MPP.
Applying polysulphide Sealant primer on both the
edges. Finally application of polysulphide Sealant in
the gap of 6 mmx 40 mm depth.

Providing and fixing machine moulded aluminium


covering of approved pattern & design, made out of
machine cut aluminium sheet and machine holed
for receiving dash fastener, over expansion joints
on vertical surfaces/ceiling floors, the fixing on plate
in one row on one side of joint only shall be done
c with stainless steel dash fasteners of 8 mm dia and
75 mm long bolt including providing aluminium
washers 2 mm thick & 15 mm dia , at a staggered
pitch of 200mm centre to centre including drilling
holes in the receiving surface and providing
expandable plastic sleeves in holes etc. complete
as per direction of Engineer-in-charge.

Powder coated aluminium sheet 2.5mm thick


(minimum thickness of powder coating 50 micron), [ Kg 496.00
7.00 kg/ sqm ]
STRUCTURAL GLAZING
Providing and supplying aluminium extruded tubular
and other aluminium sections as per the
architectural drawings and approved shop drawings
, the aluminium quality as per grade 6063 T5 or T6
as per BS 1474,including super durable powder
coating of 60-80 microns conforming to AAMA 2604
92 Kg 617.00
of required colour and shade as approved by the
Engineer-in-Charge. (The item includes cost of
material such as cleats, sleeves, screws etc.
necessary for fabrication of extruded aluminium
frame work. Nothing extra shall
be paid on this account).

Providing, assembling and supplying vision glass


panels (IGUs) comprising of hermetically-sealed 6-
12- 6 mm insulated glass (double glazed) vision
panel units of size and shape as required and
specified, comprising of an outer heat strengthened
float glass 6mm thick, of approved colour and
shade with reflective soft coating on surface # 2 of
approved colour and shade, an inner Heat
strengthned clear float glass 6mm thick, spacer
tube 12mm wide, dessicants, including primary seal
and secondary seal (structural silicone sealant) etc.
93 all complete for the required performances, as per
the Architectural drawings, as per the approved
shop drawings, as specified and as directed by the
Engineer-in-Charge. The IGUs shall be assembled
in the factory/ workshop of the glass
processor.“(Payment for fixing of IGU Panels in the
curtain glazing is included in cost of item
No.26.2)“For payment, only the actual area of glass
on face # 1 of the glass panels (excluding the areas
of the grooves and weather silicone sealant)
provided and fixed in position, shall be measuredin
sqm.“
Coloured tinted float glass 6mm thick substrate
with reflective soft coating on face # 2, + 12mm
Airgap + 6mm Heat Strengthened clear Glass of
approved make having properties as visible Light
transmittance (VLT) of 25 to 35 %, Light reflection
a Sqm 190.00
internal 10 to 15%, light reflection external 10 to 20
%, shading coefficient (0.25- 0.28) and U value of
3.0 to 3.3 W/m2 degree K etc. The properties of
performance glass shall be decided by technical
sanctioning authority as per the site requirement.

Extra for openable side / top hung vision glass


panels (IGUs) including providing and supplying at
site all accessories and hardwares for the openable
panels as specified and of the approved make such
as heavy duty stainless steel friction hinges, min 4
-point cremone locking sets with stainless steel
b Sqm 61.00
plates, handles, buffers etc. including necessary
stainless steel screws/ fasteners, nuts, bolts,
washers etc. all complete as per the Architectural
drawings, as per the approved shop drawings, as
specified and as directed by the Engineer- in-
Charge.

Total of Part-A
Bill of Quantity
Name of Work: Construction of Research Park at IITG Campus.
Part-B(Sanitary and water supply works)
Item
Description Unit Quantity Rate in figure (Rs.) Rate in words Total Amount(Rs.)
no.

Providing and fixing white vitreous china three pieces


water closet (European type W.C. pan) with dual flush
fitting, of flushing capacity 2 litre/ 4 litre including flush
pipe,cistern with lid, conforming to IS : 7231, with all
1 Each 69.00
fittings and fixtures complete, including cutting and
making good the walls and floors wherever
required( Make Model No.Hindware cornice wall
mounted 92055, cist : 92121 of Hindware or equivalent)

Providing and fixing water closet squatting pan (Indian


type W.C. pan ) with 100 mm sand cast Iron P or S trap,
10 litre low level white P.V.C. flushing cistern, including
2 flush pipe, with manually controlled device (handle lever)
conforming to IS : 7231, with all fittings and fixtures
complete, including cutting and making good the walls
and floors wherever required:

(a) White Vitreous china Orissa pattern W.C. pan of size


Each 2.00
580x440 mm with integral type foot rests

Providing and fixing white vitreous china oval wash


basin of size 560 x 450 mm, for under counter
mounting, specially fabricated brackets,C.P.brass 32 mm
3 CP brass waste coupling including cutting and making each 74.00
good the walls, wherever required.( Make Hindware
Cat No. 10049, C.P.brass 32 mm CP, brass waste
coupling ,Model No. 709 / 705 , jaquar or equivalent )
Providing and fixing glazed vitreous china flat back
urinals approx. size 375X315X620 mm with
infrared /ultra violet electric operated concealed
auto flush sensor 15mm dia. complete including
making connection with CP brass pipe to CP
4 each 35.00
spreaders, 32mm domical waste with 32mm brass
bottle trap and pipe to wall, wall flanges comp.
including cutting and making good the walls and
floors complete wherever required. (Make: Model
URS-WHT-132530 of Jaquar or equivalent )

Providing and fixing CP brass urinal valve auto


closing system with built in control cock & wall
5 flange of approved quality with wall flanges each 35.00
complete.-15mmNB,98mm long weighing not less
than 75gm.
Providing and fixing urinal partition with frosted
safety glass of 8mm thick of size 900mm(height) x
450 mm(width) corner chamfered fixed in brick wall
6 sqm 31.00
with stainless steel clips of grade 304 all complete.
(Model 1810-US or 1810-UC of Jaquar or
equivalant)
Providing & fixing 32 mm dia CP brass bottle trap
7 including fisher union for wash basins complete Cal no each 109.00
ALD 769 of Jaquar or equivalent)

Providing & fixing 1mm thick Stainless steel kitchen sink


of grade-304 as per IS: 13983 with 32 mm C.P. brass
waste coupling complete including the fittings, cutting
8 No. 24.00
and making good the wall wherever required, 1000 x 500
x 178 bowl size with drain board.(Make: Nirali Elegance
unique or equivalent)
Providing and fixing PVC waste pipe of standard pattern
9
for wash basins, sinks etc. of approved make.

(a) 40 mm dia each 24.00

Supply and fixing 15mm CP brass Sink Cock with


swinging casted spout wall flange and suitable length CP
10 each 24.00
brass extension pipe all of approved make (CP fittings
CAT No. FLR5347ND of Jaquar or equvalent).
Providing and fixing 600x120x5mm glass shelf with
edges rounded off fixed with necessary screws, raw
11 each 74.00
plugs etc. all complete. (Make: Model ACN1171N of
Jaquar continental)
Providing and fixing 600x450 mm beveled edge mirror of
superior glass (of approved quality) complete with 6 mm
12 each 74.00
thick hard board ground fixed to wooden cleats with C.P.
brass screws and washers complete.
Providing and fixing of 600mm long towel rail Jaquar Cat
No. AKP-35711P or equivalent make all complete with
13 each 24.00
required acceessories as directed by the Engineer-in-
Charge.

Providing & fixing CP towel ring of size 150mm dia of


14 approved make ( Make : Model AKP35721P of Jaquaer each 48.00
Queen's)

Providing & fixing stainless steel soap tray of approved


15 make and design with necessary screws for wash basin each 122.00
(Make : Model AKP-35731P of Jaquar)

Providing and fixing CP brass toilet paper holder as


16 directed by Engineer in Charge (Make: Model- Each 69.00
AKP35753P of Jaquar or Equivalent).

Providing & fixing stainless steel Shower basket of


approved make and design with necessary screws for
17 each 24.00
toilets (Make : Model ACN 1177N of Jaquar OR
equivalent)

Providing and fixing C.P. brass wall mixer 3-in-1 system


with provision for both hand shower and overhead
shower complete with 115mm long bend pipe ,
18 each 24.00
connecting legs & wall flange ( without hand and
overhead shower) etc complete.( Jquar Cat No
FLR5281N or equivalent)

Providing and fixing C.P bib cock with wall flange


including cutting and making good the walls wherever
19
required all complete as directed by the Engineer-in-
Charge.Charge.

(a) 2- way bib cock Jaquar Cat No.FLR-5041N or


each 76.00
equivalent
(b) Standard Bib cock (Make Model FLR 5047N of
each 48.00
Jaquar or equivalent)

Providing and fixing C.P. angular stop cock of 15mm


nominal bore complete with flange and C.P. copper
20 each 199.00
connection (Make Model FLR 5053 N of Jaquar
Florentine)

Providing and fixing C.P. brass overhead shower 100 mm


round shape multi flow (ABS Body chrome plated with
21 each 24.00
gray face plate ) with rubit cleaning system with wall
flange etc ( Jquar Cat No OHS-1999 or equivalent)

Providing and fixing C.P. brass pillar cock of approved


22 quality conforming to I.S. standards - 15mm nominal each 74.00
bore.(Make Model FLR 5015 N of Jaquar or equivalent)

Providing and fixing C.P. brass close hole basin mixer


pillar tap of approved quality and make, weighting not
23 each 24.00
less 1-970kg - 15mm nominal bore of standard back type
.(Make Model FLR 5001B of Jaquar Florentine).
Providing and fixing health faucet with 8mm dia,1m long
flexible tube & wall hook with NRV (back flow preventer)
24 each 76.00
of approved quality and make,(Make Model ALD 577 of
Jaquar or equivalent).
Supply and fixing 450 mm long braided connection
pipe with two15mm nuts & rubber washers etc. of
25 each 145.00
approved make ( CAT No.ALD 803AB of Jaquar or
Equivalent )

Providing, fitting and fixing of foldable horizontal Grab


26 Bar of stainless ateel (Make Jaquar or equivalent) for Each 4.00
person with disabilities (for WC)

Providing, fitting and fixing of vertical Grab Bar long satin


27 692 mm of Jaquar or Equivalent for person with Each 12.00
disabilities. (for wash basin & WC)
Providing and fixing Hot water GEYSER of approved
28 Make- Havells including with two nos connection pipe
450 mm long.

(a) 10 Ltrs capacity Each 24.00


Providing, fixing, testing & commissioning of Bathroom
Drain (Make-Viega model no.-4935.1) Article Code-
557119 with Sealing flange,with removable trap,(Storage
Water Height 50 mm-Water Seal),without top,with
protection plug, with rotable supply DN40, with horizontal
drain socket,with outlet 100 mm. Drain capacity 1.7-
1.1L/s WITH height adjustable and rotratable TOP
29 FRAME Model-4922.4 Article Code-534523(Height each 24.00
adjustment piece) 150x 150 (suitable for 143x143
GRATE) WITH BACK PRESSURE SEAL.WITH
STAINLESS STEEL GRATE(143x143)Model- 4933.4
Article Code- 554040. LOADING CAPACITY CLASS
K=300KG Quality controlled in accordance with DIN EN
-1253(Body and Top Frame made of environmentall
friendly PP (poly propylene)

Providing & fixing in position uPVC P"or S" trap/elbow of


self cleaning design of following sizes for the
embedded areas. Making proper connection with drip-
30 seal joints, cutting chase / hole in floors /slabs and
bringing the same in proper condition in cement concrete
1:2:4 mix complete as required. including cost of cutting
and making good the walls and floors where required.

(a) 110 mm inlet and 110 mm outlet each 210.00

(b) 110 mm inlet and 63 mm outlet (Floor Drains only) each 40.00

Providing and fixing 100 mm dia S.S grating (with or


31 each 250.00
without hole) for floor or Nahani trap.

Providing and fixing on wall face un-plasticised - Rigid


PVC sewer pipes conforming to IS:13592 Type-B
including jointing with seal ring conforming to IS:5382
32
leaving 10mm gap for thermal expansion single socketed
pipes with all accessories as bend, door bend, horn
bend etc., complete as directed.
(a) 110 mm nominal bore m 750.00

(b) 150 mm nominal bore m 692.00

Providing & fixing in position un-plasticised-Rigid PVC


33 waste pipes with necessary fittings, cutting & chasing
walls/floors etc. and making good the same.

(a) 40 mm dia metre 75.00

Providing, fitting and fixing of three layered white


outside ,black middle and blue inside PVC storage water
per litre
34 tank of approved make as per IS:12701 of all capacity 15000.00
capacity
with cover and locking arrangement complete as
directed.

Providing and fixing Chlorinated Polyvinyl Chloride


(CPVC) pipes, having thermal stability for hot & cold
water supply, including all CPVC plain & brass threaded
fittings, i/c fixing the pipe with clamps at 1.00 m spacing.
This includes jointing of pipes & fittings with one step
35
CPVC solvent cement and the cost of cutting chases and
making good the same including testing of joints
complete as per direction of Engineer in Charge.
Concealed work, including cutting chases and making
good the walls etc.

(a) 15 mm nominal outer dia Pipes m 150.00

(b) 20 mm nominal outer dia Pipes m 650.00


Providing and fixing Chlorinated Polyvinyl Chloride
(CPVC) pipes, having thermal stability for hot & cold
water supply including all CPVC plain & brass threaded
36 fittings This includes jointing of pipes & fittings with one
step CPVC solvent cement, trenching, refilling & testing
of joints complete as per direction of Engineer in Charge.
Internal work – Exposed on wall.

(a) 25 mm OD meter 54.00

(b) 32 mm OD meter 750.00

(c) 40 mm OD meter 900.00

(d) 50 mm OD meter 130.00

(e) 75 mm nominal inner dia Pipes meter 110.00

Providing and fixing G.I. pipes complete with G.I. fittings


37 and clamps, including cutting and making good the walls
etc. (rising main)

(a) 65 mm dia. nominal bore meter 90.00

(b) 80 mm dia. nominal bore meter 150.00

Providing, fixing, testing and commissioning etc. of G.I.


Pipes of all diametres complete with G.I. fittings and
38 clamps including painting with anti corrosive bitumastic
paint etc., including trenching and refilling etc. (external
work)
(a) 80 mm nominal bore Heavy Duty metre 750.00

(b) 100 mm nominal bore Heavy Duty metre 135.00

Making connection of G.I. distribution branch with G.I.


main 50 mm to 80 mm nominal bore by providing and
39 each 1.00
fixing tee, including cutting and threading the pipe etc.
complete

Providing and fixing ball valves (Brass) of approved


40 quality with high pressure plastic floats,25mm nominal each 3.00
diameter

Providing and fixing brass full way valve with hard


chrome plated ball inside PTFE (Teflon) seat & ring with
41
chrome plated centre handle with female BSP threads
complete in all respects.( Make Zoloto or equivalent)

(a) 25 mm dia. nominal bore each 12.00

(b) 32 mm dia. nominal bore each 45.00

(c) 40 mm dia. nominal bore each 70.00

(d) 50 mm dia. nominal bore each 25.00

(e) 65 mm dia. nominal bore each 4.00

(f) 80 mm dia. nominal bore each 8.00


Providing and fixing square mouth SW gully traps
grade-A complete with C.I. grating brick masonry
chamber with bricks of class designation 75 and water
42 tight C.I. cover with frame of size 300 x 300 (inside) the each 16.00
weight of cover to be not less than 4.50kg and frame to
be not less than 2.70kg as per standard design 180 x
150 mm size P and S type with FPS bricks

Providing and fixing un-plasticised -hollow core PVC


structured wall pipes conforming to IS:16098:Part1 SN-8
43 designation including jointing with all accessories etc.,
complete as directed. Eco drain pipe of Suprenme or
equivalent. (Sewer Pipe)

(a) 150 mm nominal bore m 190.00

(b) 200 mm nominal bore m 730.00

(c) 250 mm nominal bore m 30.00

(d) 315 mm nominal bore m 20.00

Providing an laying cement concrete 1:5:10 ( 1 cement :


5 coarse sand : 10 stone aggregate 40mm nominal size)
44
upto hunches of hollow core PVC pipe including bed
concrete as per standard design.

(a) 150 mm nominal bore m 190.00

(b) 200 mm nominal bore m 730.00

(c) 250 mm nominal bore m 30.00


(d) 315 mm nominal bore m 20.00

Constructing brick masonry manhole with 75 class


designation bricks in cement mortar 1 : 5 ( 1 cement : 5
coarse sand) R.C.C. top slab with 125mm thick RCC in
proportion 1 : 2 : 4 ( 1 cement : 2 coarse sand : 4 graded
stone aggregate 20 mm nominal size), 125mm thick RCC
bed concrete 1:2:4 mix ( 1 cement : 2 coarse sand: 4
graded stone aggregate 20 mm nominal size) with
45 reinforcement, inside plastering 12 mm thick with
cement mortar 1: 3 (1 cement : 3 coarse sand ) finished
with a floating coat of neat cement and making channels
in cement concrete 1 : 2 : 4 mix ( 1 cement : 2 coarse
sand : 4 graded stone aggregate 20 mm nominal size)
neatly finished complete as per design but excluding the
cost of reinforcement but including the cost of centering
and shuttering.

(a) Inside size 90 cm x 80 cm and 60 cm deep including


circular FRP composite manhole cover with frame (heavy each 23.00
duty) 530 mm dia With F.P.S. bricks.

(b) Inside size 120 cm x 90 cm and 90 cm deep including


circular FRP composite manhole cover with frame (heavy each 30.00
duty) 530 mmdia With F.P.S. bricks.

(c) Extra depth for manhole of size 120cmX90cmX90cm m 25.00

Making connection of drain or sewer line with existing


manhole including breaking into and making good the
walls floors with cement concrete 1:2:4 ( 1 cement : 2
coarse sand : 4 grade stone aggregate 20mm nominal
46 each 2.00
size),cement plastered on both sides with cement mortar
1:3 (1 cement: 3 coarse sand) finished with a floating
coat of neat cement and making necessary channels for
drain etc.250-300mm dia

Constructing brick masonry gully chamber 50 x 45 x 60


cm with bricks of class designation 75 with 500 x 450 mm
47 each 16.00
C.I. horizontal gratings with frame complete as per
standard design with F.P.S. brick
BORE WELL

Boring/drilling bore well of required dia for casing/


strainer pipe, by suitable method prescribed in IS: 2800
(part I), including collecting samples from different strata,
preparing and submitting strata chart/ bore log, including
48
hire & running charges of all equipments, tools, plants &
machineries required for the job, all complete as per
direction of Engineer-in-charge, upto 90 metre depth
below ground level.

(a) 300 mm dia Metre 180.00

Boring/drilling bore well of required dia for casing/


strainer pipe, by suitable method prescribed in IS: 2800
(part I), including collecting samples from different strata,
preparing and submitting strata chart/ bore log, including
49
hire & running charges of all equipments, tools, plants &
machineries required for the job, all complete as per
direction of Engineer -in-charge, beyond 90 metre & upto
150 metre depth below ground level.

(a) 300 mm dia Metre 80.00

Gravel packing in tubewell construction in accordance


with IS: 4097, including providing gravel fine/ medium/
50 coarse, in required grading & sizes as per actual Cum 36.80
requirement, all complete as per direction of Engineer-in-
charge.
Development of tube well in accordance with IS : 2800
(part I) and IS: 11189, to establish maximum rate of
usable water yield without sand content (beyond
permissible limit), with required capacity air compressor,
running the compressor for required time till well is fully
developed, measuring yield of well by "V" notch method
51 or any other approved method, measuring static level & Hour 144.00
draw down etc. by step draw down method, collecting
water samples & getting tested in approved laboratory, i/c
disinfection of tubewell, all complete, including hire &
labour charges of air compressor, tools & accessories
etc., all as per requirement and direction of Engineer-in-
charge.

Providing and fixing Bail plug/ Bottom plug of required


52 dia to the bottom of pipe assembly of tubewell as per
IS:2800 (part I).

(a) 200 mm dta Each 2.00

Providing and fixing M.S. clamp of required dia to the top


of casing/ housing pipe of tubewell as per IS: 2800 (part
53
I), including necessary bolts & nuts of required size
complete.

(a) 200 mm clamp Each 2.00

Supplying, assembling, lowering and fixing in vertical


position in bore well, unplasticized PVC medium well
casing (CM) pipe of required dia, conforming to IS:
54
12818, including required hire and labour charges,
fittings & accessories etc. all complete, for all depths, as
per direction of Engineer -in-charge.

(a) 150 mm nominal size dia Rm 120.00

(b) 200 mm nominal size dia Rm 80.00


Total Amount of Part -B =
Bill of Quantity
Name of Work: Construction of Research Park at IITG Campus.
PART - C Site Development
Item
Description Unit Quantity Rate in figure (Rs.) Rate in words Total Amount(Rs.)
no.
Earth work in excavation by mechanical means (Hydraulic
excavator) / manual means over areas (exceeding 30cm in
1 depth. 1.5m in width as well as 10 sqm on plan) including
disposal of excavated earth, lead upto 50m and lift upto
1.5m, disposed earth to be levelled and neatly dressed.

All types of soil cum 500

Earth work in filling for site preparation with approved quality


of earth including filling the portion within plinth area upto the
formation level, peripheral apron & drains etc. complete upto
formation level. in layers not exceeding 20 cm in depth
including watering, ramming, consolidating to the acceptable
density and dressing complete as directed including
2
obtaining earth and removal of top vegetation, dressing the
surface upto proper grade and slope. (The rate shall be
inclusive of providing earth including all leads and lifts,
payment of land compensation for obtaining earth, payment
of royalty and taxes etc. The payment will be made in profile
measurement)

a) With the earth from outside the campus cum 50000

Providing & laying grass turf with earth 50mm to 60mm


thickness of existing ground prepared with proper level and
ramming with tools wooden and than rolling the surface with
2 light roller make the surface smoothen and light watering the sqm 5000
same, with sprinkler and maintenance for 30 days or more till
the grass established properly as per direction of officer in
charge.
Providing and laying cement concrete in footings and bases
for column in string or lacing courses, parapets, copings, bed
blocks, anchor blocks, plain window sills & the like upto floor
3
two level excluding the cost of centering, shuttering but
including finishing the exposed surface with cement mortar
1:3 (1 cement : 3 fine sand ) with

with mix 1:3:6 ( 1, cement : 3, coarse sand : 6, graded stone


a Cum 100
aggregate 20mm nominal size )

with mix 1:2:4 ( 1, cement : 2, coarse sand : 4, graded stone


b Cum 180
aggregate 20mm nominal size )

Centering and shuttering including strutting, propping etc., &


4 removal of form at all heights for : Foundations, footings, sqm 600
bases of columns, mass concrete , precast shelves etc.

Random rubble masonry with hard stone in foundation and


plinth including leveling up with cement concrete 1:6:12 (1
cement : 6 coarse sand : 12 graded stone aggregate 20 mm
5 cum 500
nominal size) at plinth level with cement mortar 1:6 (1
cement : 6 coarse sand) including providing weep holes with
50mm PVC pipes and making good the same as directed.

Random rubble masonry with hard stone in super structure


above plinth level and upto floor two level, including leveling
up with cement concrete 1:6:12 (1 cement : 6 coarse sand :
6 cum 750
12 graded stone aggregate 20 mm nominal size) including
providing weep holes with 50mm PVC pipes and making
good the same as directed.
Approach Road
Preparation and consolidation of sub grade with power road
roller of 8 to 12 tonne capacity after excavating earth to an
average of 22.5 cm depth, dressing to camber and
7 Sqm. 4550
consolidating with road roller including making good the
undulations etc. and re-rolling the sub grade and disposal of
surplus earth with lead upto 50 metres.
Construction of granular sub-base by providing close graded
Material conforming to specifications, mixing in a mechanical
mix plant at OMC, carriage of mixed material by tippers to
work site, for all leads & lifts, spreading in uniform layers of
specified thickness with motor grader on prepared surface
and compacting with vibratory power roller to achieve the
desired density, complete as per specifications and directions
of Engineer-in-Charge.

With material conforming to Grade-II (size range 53 mm to


Cum 180
0.075 mm ) having CBR Value-25

Providing, laying, spreading and compacting stone


aggregates of specific sizes to water bound macadam
specification including spreading in uniform thickness, hand
packing, rolling with 3 wheels steel/ vibratory roller 8-10
8 tonnes in stages to proper grade and camber, applying and
brooming requisite type of screening/ binding materials to fill-
up the interstices of coarse aggregate, watering and
compacting to the required density. (boulder will be issued
free of cost inside the campus)

By mechanical means : Hand broken metal from blasted


a boulder grading-I 90mm to 45mm using screening Type-A cum 360
(13.2mm aggregate)

By mechanical means : Hand broken metal from blasted


b boulder grading II 63mm to 45mm using screening Type-B cum 240
(11.2mm aggregate)

By mechanical means : Hand broken metal from blasted


c boulder grading III 53mm to 22.4mm using screening Type-B cum 180
(11.2mm aggregate)

Providing and applying tack coat with bitumen emulsion at


9 the rate of 0.50 kg per sqm on the prepared bituminous/ sqm 2392
granular surface cleaned with broom
Providing, laying and rolling of close-graded premix surfacing
material of 20mm thickness composed of 11.2 mm to
0.09mm aggregates using penetration grade bitumen to the
10 required line, grade and level to serv as wearing course on a sqm 2392
previoulsy prepared base, including mixing in a suitable hot
mix plant laying and rolling with a smooth wheeled roller 8-10
tonne capacity, and finishing to required level and grad.

Providing and laying seal coat sealing the voids in a


11 bituminous surface laid to the specified levels, grade and sqm 2392
cross fall using type A seal coats (11.2mm to 0.09mm).
Providing and fixing following pipes in ground for cable
12 crossing in road/ paved areas including excavation, back
fillilng, jointing with sockets etc. as required.

a 100 mm. GI Pipe (medium) M 100

b 50 mm G.I.pipe (medium) M 100

Internal Foot path


Providing and laying interlocking precast cement concrete
paver of approved design and compressive strength of
13 sqm 3000
300kg/sqcm laid on a bed of 40mm thick coarse sand
including filling the joints with local sand complete 80mm

Providing and laying factory made chamfered edge Cement


Concrete paver blocks In foot path, park & lawns driveway or
light & traffic parking etc. of required strength, thickness &
size/ shape, made by table vibratory method using PU
mould, laid in required colour & pattern over 50mm thick
compacted bed of course sand, compacting and proper
14 embedding/laying of inter locking paver blocks into the sand
bedding layer through vibratory compaction by using plate
vibrator, filling the joints with sand and cutting of paver blocks
as per required size and pattern, finishing and sweeping
extra sand, all complete as per manufacturer's specifications
& direction of Engineerin-
Charge.
80mm thick Cement concrete paver block of M-30 grade with
a Sqm 2098
approved colour, design & pattern.

80mm thick Cement concrete paver block of M-40 grade with


b non colour, design & pattern for provition of Grass growth Sqm 1178
into the holes.
STORM WATER DISPOSAL
Providing and laying non-pressure NP3 class RCC pipes and
collar jointed with stiff mixure of cement morter in the
15
proportion of 1:2 (1 cement : 2 fine sand) inccluding testing
of joints etc., complete.

a 450mm dia metre 50

b 600mm dia metre 50

c 900mm dia metre 30

d 1200mm dia metre 30

Brick work with bricks of class designation 75 in foundation &


16 plinth in cement mortar 1:6 (1 cement : 6 coarse sand) cum 320
including curing.

12mm thick, cement plaster finished with a floating coat of


17 Sqm 1800
neat cement of 1:4(1 cement: 4 coarse sand).

Providing and fixing G.I. chain link fabric fencing of required


width in mesh size 50x50 mm including strengthening with 2
18
mm dia wire or nuts, bolts and washers as required complete
as per the direction of Engineer-in-charge.
Made of G.I. wire of dia. 4 mm Sqm 31

Providing and laying non-pressure NP2 class (light duty)


R.C.C. pipeswith collars jointed with stidd mixture of cement
19
mortar in the proportionof 1:2 (1 cement : 2 dine sand)
including testing of joints etc. complete :

a 150 mm dia. R.C.C. pipe m 50

b 250 mm dia. R.C.C. pipe m 150

Total of Part-C
Bill of Quantity
Name of Work: Construction of Research Park at IITG Campus.
PART - D(i) : Fire Fighting works
Item
Description Unit Quantity Rate in figure (Rs.) Rate in words
no.
Sub-head -I Hydrants & Spinklers
Supplying and Fixing Single Headed Internal Hydrant Valve
oblique pattern with intantanneous S S coupling of 63 mm dia
with cast iron wheel ISI marked, conforming to IS: 5290 (Type A),
1 each 8
with 80 mm dia flanged inlet,with ABS cap and chain complete
with all accessroies etc. as required.
Make : GETECH/NEWAGE/SAFEX

Providing RRL Hose with ISI Marked (IS:636) 63 mm dia X15 M long
complete with instantaneous type Gun Metal 3 mm dia ISI Marked
2 male & female couplings (IS:903) bound & riveted to hose pipes with each 16
copper rivets and copper wire complete as reqd.
( MAKE: NIRMAL RUBBER/NEWAGE/BRG)

Supplying and fixing 63mm dia, S S Branch Pipe with


16/20mm dia copper nozzle confirming to IS : 903 suitable for
3 each 8
instantaneous connection, interconnect hose pipe, coupling as
required. (Type A) as required. MAKE:GETECH/NEWAGE/SAFEX

Supplying and Fixing First Aid Hose Reel, wall mounting swinging
type complete with drum & bracket of MS construction, spray
painted in Post office Red, confirming to IS 884/1995 with upto date
amendments, complete with the following as required. 36 Meter long
4 20 mm dia water hose Thermoplastic (Textile reinforced) Type - 2 each 16
as per IS : 12585 20 mm dia gun metal globe valve & nozzle. Drum
and brackets for fixing the quimpments on wall. Connection from riser
with stop valve (gun metal) & M.S. Pipe
MAKE : GETECH/NEWAGE/SAFEX
Supplying and Fixing of Weather Proof Hose Cabinet suitable for
external yard hydrant / FBIC fabricated out of 2 mm thick M.S.
sheet with 4 mm thick glazed glass door in front having locking
arrangements, suitable to accommodate external hydrant with
valve, hose reels, branch pipe / FBIC with all the necessary
5 pipes, accessories, fittings etc., mounted on wall or raised brick each 16
platform and duly painted with PO Red externally and white
internally with synthetic enamel paint, sign writing etc. complete in
all respects as required at site and having minimum following
dimensions. 900 mm x 600 mm x 450 mm deep
MAKE:GETECH OR SELF FEBRICATED

Providing, Fixing, Testing and Commissioning of Sprinkler Installation


Control Valve of Cast iron body and brass / bronze working
parts comprising of water motor, alarm, bronze seat clapper and
clapper arm, hydraulically driven mechanical gong bell to sound
continuous alarm when the Sprinkler system activates, pressure
6 each 4
gauges, emergency releases, strainer, pressure switch, cock valve
complete with drain valve and bypass, test control box, ball valves,
MS pipe of required size, flanges, orifice plate, gasket etc. of size 150
mm dia, as required.
MAKE:GETECH/NEWAGE/SAFEX

Providing and Fixing 15 mm dia gunmetal / brass quartzoid type


Sprinkler Head with quartz bulb and set to operate at specified
7
temperature.
MAKE:GETECH/NEWAGE/SAFEX

a Pendent / Upright type, 68 C, Chrome plated each 320

b Side wall 68 C, Chrome plated each 75

Sub Head - II Piping, Valves and Accessories


Providing, Laying, Testing and Commissioning of 'B' class ( Medium )
MS pipe on surface confirming to IS 3589 and 1239 including
cutting and welding with fittings like elbows, reducer, hanger, tees,
flanges, tapers, nuts bolts, gaskets etc., fixing the pipe on the wall
8 / ceiling with suitable clamps and painting with two coats of
synthetic enamel paint after primer coat of required shade,
cutting hole and chase in brick wall / RCC slab and making good
the same etc. complete as required.
MAKE: TATA,JINDAL,NEZONE

a 200 mm dia mtr. 15

b 150 mm dia mtr. 415

c 80 mm dia mtr. 75

d 65 mm dia mtr. 230

e 50 mm dia mtr. 122

f 40 mm dia mtr. 10

g 32 mm dia mtr. 152

h 25mm dia mtr. 450

j 20mm dia mtr. 60


Supplying, Installation, Testing and Commissioning of cast
iron sluice valves of PN 1.6 rating flanged at both ends of following
9 sizes complete with rubber insertion, nuts, bolts and washers etc.
as required.
MAKE: KARTAR,AUDCO,SANT

a 200 mm dia each 4

b 150 mm dia each 4

c 100 mm dia each 8

d 80 mm dia each 8

Supplying, Installation, Testing and Commissioning of


butterfly valves of PN 1.6 rating of following sizes with nitrile
seat and stainless steel stem with lever/gear operation and cast iron
10
body in powder coated finish for fire fighting application complete
in all respects as required.
MAKE: KARTAR,AUDCO,SANT

a 150 mm dia nos. 4

b 100 mm dia nos. 4

c 80mm dia nos. 8

d 65 mm dia nos. 8
e 50 mm dia nos. 4

Providing, Installation, Testing and Commissioning of


double flanged cast iron Non-Return Valve, PN 1.6 of following
11 sizes confirming to IS : 5312 complete with rubber gasket, Gl
bolts, nuts, washers etc. as required.
MAKE: KARTAR,AUDCO,SANT

a 200 mm dia each 2

b 150 mm dia each 4

c 80 mm dia each 4

Providing, Installation, Testing and Commissioning of


forged brass / Gun Metal Ball Valves with brass body chrome
12
plated of following sizes as required.
MAKE: KARTAR,AUDCO,SANT

a 50mm dia each 6

b 25mm dia each 16

Supply, Installation, Testing and Commissioning of 100 mm dia


Bourden type, Stainless Steel dial type Pressure Gauge including
13 brass isolation valve and siphon pipe having caliberation of 0 -16 Kg / each 8
cm2
MAKE:H.GURU/FEBEC

Supplying and Fixing of Fire Man's axe with heavy insulated


14 rubber as per standard conforming to IS 926 each 16
MAKE:GETECH/NEWAGE/SAFEX
Constructing masonary chamber for external sluice valve of 90 x
90 x 100 cm, inside finish with II class designation brick work in
cement mortar 1:5 (1 cement : 5 fine sand) for sluice valve, with
C.I. main hole cover & frame of 600 mm dia. and RCC top slab ( 1:2:4
mix, 1 cement: 2 coarse sand : 4 graded stone aggregate 20 mm
15 each 8
nominal size) necessary excavation foundation concrete 1:5:10
(1 cement : 5 fine sand : 10 graded stone aggregate 40 mm
nominal size) inside plastering with cement mortar 1:3 (1
cement : 3 coarse sand) 12 mm thick finished with a floating coat
of neat cementcomplete as required.

B EXTERNAL FIRE FIGHTING SYSTEM (MAIN PUMP).

Supply, Erection, Testing & commissioning of Electrical Motor


Driven Pump centrifugal end section type pump complete
with bronze impeller, mechanical seal capable of delivering 2280
liters/minute against a total head of 70 metres, induction motor
suitable for 415V, 50 Hz, AC supply min. 60 HP with speed of 2900
16 set 1
RPM , TEFC type conforming to IP: 55, flexible coupling, coupling
guard. Common bedplate fabricated from mild steel channel,
vibration pads, isolation arrangement & RCC foundation. MAKE
:KIRLOSKAR OR EQUIV.

17 DIESEL ENGINE DRIVEN FIRE PUMP:

Supply, Erection, Testing & commissioning of Diesel Engine


Driven Pump Horizontal end section, centrifugal type pump
complete with bronze impeller, mechanical seal capable of
delivering 2280 liters/minute against a total head of 70 metres,
Diesel Engine Min.Cap. of 93 BHP with speed of 1800 RPM ,
flexible coupling, coupling guard. Common bed plate fabricated
set 1
from mild steel channel, starter motor, batteries, battery charger &
cabling, fuel piping, instrumental panel, exhaust piping with
residential type silencer, cooling arrangements including 200
Litres Diesel Tank Complete, vibration pads, isolation
arrangement, heat exchanger & RCC foundation.
MAKE: KIRLOSKAR OR EQUIV.

18 JOCKEY PUMPS:
Supply, Erection, Testing & commissioning of Jockey Pump
Horizontal end section single stage centrifugal type pump
complete with bronze impeller, mechanical seal capable of
delivering 180 liters/minute against a total head of 70 metres,
induction motor suitable for 415V, 50 Hz, Min 15 HP with 2900 RPM, set 1
TEFC type conforming to IP: 55, flexible coupling, coupling guard.
Common bedplate fabricated from mild steel channel, vibration
pads, isolation arrangement & RCC foundation.
MAKE:KIRLORKAR OR EQUIV.

19 TERRACE PUMPS:

Supply, Erection, Testing & commissioning of Terrace Pump


Horizontal end section single stage centrifugal type pump
complete with bronze impeller, mechanical seal capable of
delivering 27 (M3/Hr) against a total head of 30 metres, induction
motor suitable for 415V, Min 5.5KW with 2900 RPM, TEFC type
2
conforming to IP: 55, flexible coupling, coupling guard. Common
bedplate fabricated from mild steel channel, vibration pads,
isolation
arrangement & RCC foundation.
MAKE:KIRLORKAR OR EQUIV.

SITC of industrial type pressure switch having 1/4" BSP(F)


connection IP:32 enclosure protection, phosphor bronze bellows
as sensing element, SDPT contact system, switch rating 6A
Inductive/10A resistive 380 V AC, 0.2A Inductive/10A
20 resistive 250V DC suitable for maximum pressure range of nos. 4
230 PSI with isolation cock and interconnecting cables using
copper conductor between pressure switch and panels completed as
required.
MAKE:INDFOS OR DANFOSS

Supply, Erection, Testing & commissioning of Air Vessel made of 10


mm M.S. Sheet size 450 x 2000 mm including supply & fixing of
Gun metal 32 mm dia Air release Valve, 32 mm dia Gun Metal
21 gate valve, 40 mm dia gun metal gate valve including 2Mts of nos. 5
M.S 40 mm dia G. I (Heavy pipe for drainage and 1 no. 65 mm
dia Butterfly valve with all necessary accessories as per IS 2825
MAKE:GETECH / SELF FEBRICATED.

22 PIPING ABOVE GROUND FOR EASY MAINTENANCE


Supply, Erection, Testing & commissioning of M.S pipe (Medium)
ISI marked 1239-part-1 and ISI : 3589 including cutting,
welding/threading with accessories like tees, elbows, flanged joints,
reducers, rubber gaskets, nuts & bolts including fixing the pipe
with suitable clamps/bracket, complete as required including
painting of one coat of red oxide & 2 coats of P.O. red paint
MAKE: TATA,JINDAL,NEZONE.

a 80 mm dia mtr. 40

b 150 mm dia mtr. 300

Supply, Erection, Testing & commissioning of Single headed


hydrant S S valves conforming to ISI: 5290 with flanged inlet with 63
23 mm female instantaneous of gun metal coupling with blank cap & nos. 26
chain, nuts, bolts, washers & 5mm thick rubber gasket etc.
MAKE:GETECH/NEWAGE/SAFEX

Supply, Erection, Testing & commissioning of 63 mm dia, 15 M long


RRLhose pipe conforming to ISI-636 type A Mark fire hose pipe
24 nos. 26
conforming to IS 901 mark with S S male & female coupling wire
wound with the pipe MAKE:GETECH/NEWAGE/SAFEX

Supply, Erection, Testing & commissioning of S Sshort branch


25 pipes conforming to ISI spec 903 with 16 mm dia nozzle. nos. 8
MAKE:GETECH/NEWAGE/SAFEX

Supply & Erection of M.S.Fire Hose Box of size 900 x 600x 450 mm
approx.) fabricated from 16 SWG. M.S. Sheet of fully welded
construction with hinge front door with locking arrangement & partially
glazed with 5 mm thick glass powder coated fire red
26 nos. 8
finish paint with Fire Hose Box written on the front side of the glass
for internal hydrants to house 2 nos. hose pipes, 1 no. Branch pipe,
1 no. Hose reel & Landing valve 1 No.
MAKE:GETECH/NEWAGE/SAFEX
Supply, Erection, Testing & commissioning of Drawl of connection
with CI foot valve 150 mm dia (for fire tank)and 3 Meter G.I. 100 mm
27 nos. 1
dia (H) pipe, nuts, bolts, washers & 5mm thick rubber gasket etc.
MAKE:GETECH/NEWAGE/SAFEX

Fire brigade Two Way Inlet Valve with 2 nos. G.M 63 mm dia Male
instantaneous coupling with 100 mm flanged out let connection and
28 nos. 4
built in check valves
MAKE:GETECH/NEWAGE/SAFEX
Main Fire Pump Panel

Fabricating, supplying, erection, testing and commissioning of


cubicle type floor mounted panel made from 14 CRCA Sheet
complete with contactors,Auxillary contacts ,indicating
lamps,Ammeters with selector switches, voltmeters with
selector switches,fuses, automatic delta type motor starter
including connections complete as required for 1 No Fire hydrant
and sprinkler pump, 1 No. Jockey pump, 1 No Battery charger
and 1 Set of Battery complete in all respect including
neccessary control wiring as per the details given below:
Incoming
29 1) 500 Amps MCB - 1 No.
2) Voltmeter (0-500) V (size 96mm x 96mm) - 1No.
3) Voltmeter Selector Switch - 1 No.
4) Indication Lamps (LED type) -1 sets (1 set of 03 Nos.RYB)
5) Ammeters(0-200A) - 1 No.
6)Ammeter selector switch -1 No
7)Current transformer (300/5A) -3Nos
8)Bus bar chamber with 900 Amps Aluminim bus bar ,suitable
for 3 phase and neutral system - 01set.
9)Required number of Auxillary contacts

set 1
Outgoing
1)200 Amps MCB , -2 Nos
2) 100 Amps MCB - 1 No
3) Fully Automatic delta starter (60 hp ) with LED illuminated
set 1
ON-OFF push button -2Nos.
4) Fully Automatic delta starter (15hp ) with LED illuminated
ON-OFF push button - 1 No.
5)Auxillary contactors for main, sprinkler and jockey pumps
6) Auto/ manual selector switch with control wiring for main,
sprinkler and jockey pump
7) Annunciator with hooter, accept/ reset push button with
control wiring
8) Currect Transformer (200/5A) --6 Nos
9) Currect Transformer (100/5A) --3 Nos
10) Ammeter 0-150 --3 Nos
11) Volt Meter 0-500--3 Nos
12) Single phase preventer--3 Nos
13) 3 Set Phase indication Lamps with Phuses

Control Panel Engine


a) 15 Amp Battery charges with trickle and boost facility
b) 0-32 volts/ meter--1 No
c) 0-15 Amps ammeter--1 No
d) Auto Starting contractor with relay
e) Auto/ Manual selector switch with push button for manual
start--1 No
f) 63 MCB - 1No
g) Buzzer--1 N0
h) Indication Lamp--3 No
I) Push Button--2 No

30 TERRACE PUMP PANEL to start the Terrace Pump Automaic Nos 2

Supply of fire buckets Set of four nos. with MS stand with sand etc. as
31 Nos. 20
required.
Supply, Installation, Fixing of ABC stored Pressure Fire Extinguisher
with built – In Pressure Gauge to know the Ready ness of the
32 Extinguisher Squeeze Grip Handle as per IS:15683 with ISI mark. Nos 46
(6 kg capacity)
BRAND : GETECH / MINIMAX/ SAFEX

Supply, Installation, Fixing of CARBON DIOXIDE Fire Extinguisher


33 confirming to IS: 15683 with ISI Mark.(4.5 LITERS) Nos 16
BRAND: GETECH /MINIMAX / SAFEX

34 Manual Call Point & Hooter each floor area. Make:Agni Suraksha Nos 16

35 12 Zone Panel for Manual Call Box & Hooter to identify the Nos 4

Location/ floor area Zone wise.Make :Agni Suraksha

36 Exit Board Auto Glow type for easy evcuation floor wise. Nos 24

Providing & fixing angle iron (40mm x 40mm x 5mm) door frame and
M.S sheet (2mm thick) sum glass shutter of size 2.1 mtr. X 1.2 mtr.
(N.S) with 25 mm x 3 mm angleframe all around & stiffenced in
37 between i/c hinges, handle, locking arrangement, painting with each 44
approved synthetic enamle paint i/c sign writing on glass at internal
hydrant including providing & fixing M.S. Sheet 2 mm thick on remaing
portion above door to close opening i/c painting etc. as required.

Total of Part -D(i)


Total Amount(Rs.)
Bill of Quantity
Name of work: Construction of Research Park Building at IITG campus
PART-D(ii) (FIRE DETECTION, ALARM SYSTEM)
Item no. Description Unit Quantity Rate in figure (Rs.) Rate in words Total Amount(Rs.)
Research Block : FIRE DETECTION, ALARM & P.A. SYSTEM
Supply, installation, testing & commissioning of short -
1
circuit - Isolators.

Nos 49

Supply, installation, testing & commissioning of Control


2 Modules (CMX) for controlling Hooters/ speakers, Strobe
(Flasher) Lamps, Manual Call Points (MCP), etc.

Research Block Each 12

Supply, installation, testing & commissioning of 'Rise'


type Heat Detectors, approved make, with Operating
3
Temperature of ( - ) 10OC to ( + ) 70OC and OPERATING
VOLTAGE OF 18 TO 28 V D.C.

Research Block Each 18

Supply, installation, testing & commissioning of 'Rise'


type Multicriteria Detectors, approved make, with
4
Operating Temperature of ( - ) 10OC to ( + ) 70OC and
OPERATING VOLTAGE OF 18 TO 28 V D.C.

Each 670

Supplying, fitting & fixing Base of Dectector,Model no-


5
B501

Each 694
6 Supplying, fitting & fixing Duck Dectector.

Research Block Each 24

7 Supplying, fitting & fixing Beam Dectector.

Research Block Each 4

Supply, installation, testing & commissioning of manual


push button station break glass type - Manual call points
8 (MCP) with MS / ABS body, with chain & hammer, and
also with Blinking facility, completely compatible with the
main Fire Alarm Panel.

Each 24

Supply , installation, testing & commissioning of Monitor


9
Modules for Manual call points - (MMX)
Research Block

Each 6

Supply , installation, testing & commissioning of M.S.


10 NOS 23
Junction Boxes.

Supplying & laying 2 core x 1.5 sq.mm copper conductor


11 PVC insulated, sheathed armoured cable - ISI marked.

Rm 5347

Supplying & laying Telephone wire


12

Research Block Rm 900

Supply, installation, Testing, Commissioning of Field


13
Handset for Both way Communication system.
Research Block Set 12

Supply, installation, Testing, Commissioning of Fire


14
Fighter Telephone Jack.

Research Block Each 12

Supply, installation, Testing, Commissioning of


15
Telephone Module.

Research Block Each 12

Supply, installation, Testing & Commissioning of Digital


16
Voice Evacuaition.

Research Block Set 12

Supply, installation, Testing & Commissioning of 50 Wat


17
Amplifer.

Research Block Each 1

Providing, Installing, Testing & Commissioning Horn with


18
Strobe, complete.

Research Block Each 12

Providing, Installing, Testing & Commissioning Relay


19
Moudle, all complete.

Research Block Each 12


Sprinklers - Supply, installation, testing & commissioning
of open type spray nozzles ( sprinkler jets)) - pendent
type - with 1/2" inch inlet connection (male threaded)
20 with deflector and quartzoid bulb of (MAKE :- "Tyco" /
"Viking"/ "Central" - Model :ELO-16 / "Crawlie & Ray" /
"Omex"), Conventional "Pendent" - "UL" Listed
Sprinklers. (For Sprinkler system)

("Pendent" only - in all Floors below False Ceiling / True


(a) Each 399
ceiling)

("Up-Right" only - in respective Floors, above False


(b) Each 335
Ceiling only).

Gross Total (Research Block)

Apartment block (FIRE DETECTION, ALARM SYSTEM)


FIRE DETECTION, ALARM & P.A. SYSTEM
Supply, installation, testing & commissioning of short -
1
circuit - Isolators.

Nos 23

Supply, installation, testing & commissioning of Control


2 Modules (CMX) for controlling Hooters/ speakers,
Strobe (Flasher) Lamps, Manual Call Points (MCP), etc.

Each 8

Supply, installation, testing & commissioning of 'Rise'


type Heat Detectors, approved make, with Operating
3
Temperature of ( - ) 10OC to ( + ) 70OC and OPERATING
VOLTAGE OF 18 TO 28 V D.C.
Kitchen Each 6

Supply, installation, testing & commissioning of 'Rise'


type Multicriteria Detectors, approved make, with
4
Operating Temperature of ( - ) 10OC to ( + ) 70OC and
OPERATING VOLTAGE OF 18 TO 28 V D.C.

Nos 330

Supplying, fitting & fixing Base of Dectector,Model no-


5
B501

Nos 342

6 Supplying, fitting & fixing Duck Dectector.


Apartment Block

Kitchen Nos 6

Supply, installation, testing & commissioning of manual


push button station break glass type - Manual call
7 points (MCP) with MS / ABS body, with chain &
hammer, and also with Blinking facility, completely
compatible with the main Fire Alarm Panel.
Apartment Block

Each 20

Supply , installation, testing & commissioning of Monitor


8
Modules for Manual call points - (MMX)
Apartment Block

Each 8
Supply , installation, testing & commissioning of M.S.
9 NOS 20
Junction Boxes.

Supplying & laying 2 core x 1.5 sq.mm copper conductor


10 PVC insulated, sheathed armoured cable - ISI marked.

Rm 3581.3

Supplying & laying Telephone wire


11

Apartment Block Rm 400

Supply, installation, Testing, Commissioning of Field


12
Handset for Both way Communication system.

Apartment Block Set 8

Supply, installation, Testing, Commissioning of Fire


13
Fighter Telephone Jack.

Apartment Block Each 8

Supply, installation, Testing, Commissioning of


14
Telephone Module.

Apartment Block Each 8

Supply, installation, Testing & Commissioning of Digital


15
Voice Evacuaition.

Apartment Block Set 8

Supply, installation, Testing & Commissioning of 50 Wat


16
Amplifer.
Apartment Block Set 1

Providing, Installing, Testing & Commissioning Horn with


17
Strobe, complete.

Apartment Block Each 8

Providing, Installing, Testing & Commissioning Relay


18
Moudle, all complete.

Apartment Block Each 8

Sprinklers - Supply, installation, testing & commissioning


of open type spray nozzles ( sprinkler jets)) - pendent
type - with 1/2" inch inlet connection (male threaded)
19 with deflector and quartzoid bulb of (MAKE :- "Tyco" /
"Viking"/ "Central" - Model :ELO-16 / "Crawlie & Ray" /
"Omex"), Conventional "Pendent" - "UL" Listed
Sprinklers. (For Sprinkler system)

("Pendent" only - in all Floors below False Ceiling / True


(a)
ceiling)

Each 222

("Up-Right" only - in respective Floors, above False


(b)
Ceiling only).

Each 136

Providing, Installing, Testing & Commissioning of cyling /


20
wall mounted Baffle Speaker of 6 watts each, complete.

Apartment Block Each 40


Total of Part -D(ii)
Bill of Quantity
Name of Work: Construction of Research Park at IITG Campus.
Part-E (Electrical works)
Item Total
Description Unit Quantity Rate in figure (Rs.) Rate in words
no. Amount(Rs.)
Basic Infra Part-A
WIRING IN STEEL & PVC CONDUIT

Wiring for light point/ fan point/ exhaust fan point/ call bell point
with 1.5 sq.mm FRLS PVC insulated copper conductor single core
cable in surface / recessed medium class PVC conduit, with
1 modular switch, modular plate, suitable GI box and earthing the
point with 1.5 sq.mm FRLS PVC insulated copper conductor single
core cable etc. as required.

1.1 Group B Point 3.00

1.2 Group C Point 20.00

Wiring for circuit/ submain wiring alongwith earth wire with the
2 following sizes of FRLS PVC insulated copper conductor, single core -
cable in surface/ recessed medium class PVC conduit as required.

2.1 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire meter 80.00

2.2 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire meter 190.00

Supplying and fixing following modular switch/ socket on the


4 existing modular plate & switch box including connections but -
excluding modular plate etc. as required.

4.1 5/6 A switch Each 1.00


4.2 15/16 A switch Each 6.00

4.3 3 pin 5/6 A socket outlet Each 1.00

4.4 6 pin 15/16 A socket outlet Each 6.00

Supplying and fixing following size/ modules, GI box alongwith


7 modular base & cover plate for modular switches in recess etc. as
required.

7.2 3 Module (100 mmX75 mm) Each 1.00

7.3 4 Module (125 mmX75 mm) Each 6.00

Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction Each
8 3.00
box/ wooden block including connections etc. as required.

CHAPTER-2-MCCB, MCB & DB’S -

Supplying and fixing following way, single pole and neutral, sheet
steel, MCB distribution board, 240 V, on surface/ recess, complete
10 with tinned copper bus bar, neutral bus bar, earth bar, din bar, -
interconnections, powder painted including earthing etc. as
required. (But without MCB/RCCB/Isolator)

10.1 6 way, Double door Each 1.00


Supplying and fixing following way, horizontal type three pole and
neutral, sheet steel, MCB distribution board, 415 V, on surface/
11 recess, complete with tinned copper bus bar, neutral bus bar, -
earth bar, din bar, interconnections, powder painted including
earthing etc. as required. (But without MCB/RCCB/Isolator)

11.1 4 way (4 + 12), Double door Each 1.00

Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C”


curve, miniature circuit breaker suitable for inductive load of
13 -
following poles in the existing MCB DB complete with connections,
testing and commissioning etc. as required.

13.1 Single pole Each 18.00

13.2 Double pole Each 1.00

13.3 Triple pole and neutral Each 1.00

13.3 Supplying and fixing single pole blanking plate in the existing Each 4.00
MCB DB complete etc. as required.

WIRING IN STEEL & PVC CONDUIT -


CHAPTER -5- EARTHING -
Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including
accessories, and providing masonry enclosure with cover plate Each
19.1 41.00
having locking arrangement and watering pipe etc. with
charcoal/coke and salt as required.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick
including accessories, and providing masonry enclosure with cover
19.2 Set 10.00
plate having locking arrangement and watering pipe of 2.7 meter
long etc. with charcoal/ coke and salt as required.

Supplying and laying 25 mm X 5 mm copper strip at 0.50 meter


below ground as strip earth electrode, including
19.3 connection/terminating with nut, bolt, spring, washer etc. as meter 150.00
required.(Jointing shall be done by overlapping and with 2 sets of
brass nut bolt & spring washer spaced at 50 mm)

Supplying and laying 25 mm X 5 mm G.I strip at 0.50 meter below


ground as strip earth electrode, including connection/terminating
19.4 with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be meter 660.00
done by overlapping and with 2 sets of G.I. nut bolt & spring
washer spaced at 50 mm)

Providing and fixing 25 mm X 5 mm copper strip on surface or in meter


19.5 72.00
recess for connections etc. as required.

Providing and fixing 25 mm X 5 mm G.I. strip on surface or in meter


19.6 304.00
recess for connections etc. as required.

Providing and fixing 6 SWG dia G.I. wire on surface or in recess for meter
19.7 1,060.00
loop earthing as required.

CHAPTER 6-LIGHTNING CONDUCTOR -


Providing and fixing of lightning conductor finial, made of 25 mm
dia 300 mm long, G.I. tube, having single prong at top, with 85
20.1 mm dia 6 mm thick G.I. base plate including holes etc. complete as Each 7.00
required.

Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or


20.2 on surface of wall for lightning conductor complete as required. meter 410.00
(For horizontal run)

Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or


20.3 on surface of wall for lightning conductor complete as required. meter 235.00
(For vertical run)
Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I.
20.4 strip, 125 mm long, with 4 Nos. of G.I. bolts, nuts, chuck nuts and Each 107.50
spring washers etc. complete as required
CHAPTER 7-MV CABLE LAYING -
Laying of one number PVC insulated and PVC sheathed / XLPE
power cable of 1.1 kV grade of following size direct in ground
21 -
including excavation, sand cushioning, protective covering and
refilling the trench etc. as required.

21.1 Upto 35 sq. mm meter 400.00

21.2 Above 95 sq. mm and upto 185 sq. mm meter 966.00

21.3 Above 185 sq. mm and upto 400 sq. mm meter 1,796.00

Laying of one number PVC insulated and PVC sheathed / XLPE


22 power cable of 1.1 kV grade of following size in the existing RCC/ -
HUME/ METAL pipe as required.

22.1 Upto 35 sq. mm meter 66.00

22.2 Above 95 sq. mm and upto 185 sq. mm meter 76.00

22.3 Above 185 sq. mm and upto 400 sq. mm meter 40.00

Laying and fixing of one number PVC insulated and PVC


23 sheathed / XLPE power cable of 1.1 kV grade of following size on -
wall surface as required.
23.1 Upto 35 sq. mm (clamped with 1mm thick saddle) meter 1,504.00

Laying and fixing of one number PVC insulated and PVC


24 sheathed / XLPE power cable of 1.1 kV grade of following size on -
cable tray as required.

24.1 Upto 35 sq. mm (clamped with 1mm thick saddle) meter 2,238.00

Above 95 sq. mm and upto 185 sq. mm (clamped with 25/


24.2 meter 128.00
40x3mm MS flat clamp)

Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm meter
24.3 600.00
MS flat clamp)

CHAPTER 9-MV CABLE JOINTING & END TERMINATION -


Supplying and making end termination with brass compression
gland and aluminium lugs for following size of PVC insulated and
25 -
PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade
as required.

25.1 3½ X 35 sq. mm (32mm) each 48.00

25.2 3½ X 120 sq. mm (45 mm) each 8.00

25.3 3½ X 185 sq. mm (57mm) each 16.00

25.4 3½ X 300 sq. mm (70 mm) each 56.00


25.5 4 X 10 sq. mm (25 mm) each 230.00

25.6 4 X 16 sq. mm (28mm) each 4.00

-
CHAPTER 14- MISC. CIVIL ITEMS -
Providing, laying and fixing following dia G.I. pipe (medium class)
26 in ground complete with G.I. fittings including trenching (75 cm -
deep) and re-filling etc. as required

26.1 50 mm dia meter 100.00

Providing, laying and fixing following dia RCC pipe NP2 class (light
duty) in ground complete with RCC collars, jointing with cement
27 -
mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm
deep) and refilling etc. as required.

27.1 300 mm dia meter 300.00

Basic Infra Part-B


1.00 MV SWITCHGEAR / POWER PANEL / DISTRIBUTION BOARDS.

1.10 POWER PANEL:


Supply, installation, testing and commissioning of cubicle type
panels as specified and shown on drawing no. WTE2233/STAGE
2/901 SHEET 1 TO 6 with :
i) Main Aluminium busbars with bar type feeder connections & all
internal wiring and connections.
ii) Earthing all components, frame etc. to a common internal earth
bar.
iii) Powder Coat painting of all sheet metal works.
iv) All accessories & supporting structure.
v) Brass glands and crimping lugs for sending and receiving ends.

vi) All ammeters with C.T's and voltmeter and energy meters with
necessary fuses.
vii) Panel components as specified.
viii) MS base frame.
ix) All switch gear to have short circuit levels as specified.

1.1 MAIN LT PANEL each 1.00

1.2 APFC PANEL(700KVAR) each 2.00

1.3 LAB BLOCK MAIN PANEL each 1.00

1.4 APARTMENT BLOCK MAIN PANEL each 1.00

1.5 FEEDER PILLAR PANEL each 1.00

1.6 UPS PANEL each 1.00

1.14 UTILITY PANEL each 1.00

2.00 MV CABLE
Supply of heavy duty 1100V grade LT XLPE insulated sheathed &
2.1 armoured cables with aluminium / copper conductors as specified
and required.
2.1.1 4C X 10sq.mm. Al. Ar. XLPE Cable rm 2,324.00

2.1.2 4C X 16sq.mm. Al. Ar. XLPE Cable rm 66.00

2.1.3 3.5C X 35sq.mm. Al. Ar. XLPE Cable rm 1,770.00

2.1.4 3.5C X 120sq.mm. Al. Ar. XLPE Cable rm 276.00

2.1.5 3.5C X 185sq.mm. Al. Ar. XLPE Cable rm 894.00

2.1.6 3.5C X 300sq.mm. Al. Ar. XLPE Cable rm 2,436.00

2.1.7 4C X 4sq.mm. CU. Ar. XLPE Cable rm 50.00

2.1.8 12C X 1.5sq.mm. CU.pvc control Cable rm 30.00

2.1.9 3C X 1.5sq.mm. CU. AR. XLPE Cable rm 48.00

3 INTERNAL LIGHT, CEILING AND EXHAUST FAN FITTINGS


Surface mounted 1200mm high effiecency 20W integrated LED
batten, with minimum 100 Lumens/Watt efficacy. CCT 6500K,
CRI> 80. Luminaire driver should be Isolated and multistage
3.1.5 constant current type. Driver Input voltage range of 150V to each 12.00
270V ( nominal rated voltage – 240V) with minimum 2.5KV surge
protection, PF >0.90, THD <20%, Similar to Wipro Make LL20-
221-XXX-65NE1 or equivalent.

Supply of Bulkhead LED enclosed in die cast Aluminium housing


for superior heat management and Polycarbinate opul diffuser.
The maximum system wattage should be 10W. CCT 5700K, CRI>
80. Luminaire driver should be Isolated and multistage constant
3.1.9 current type. Driver Input voltage range of 150V to 270V each 8.00
( nominal rated voltage – 240V) with minimum 2.5KV surge
protection, PF >0.9, THD <20%,. Luminaire should be IP65
Protected. Similar to Wipro Make LW07-141-XXX-57-XX or
equivalent.

3.1.11 450mm sweep exhaust fan heavy duty each 3.00

5 SUBSTATION AUXILIARIES INSTALLATION -


Supply and fixing of MS chequered plate 6mm thick of different
size for covering trench inside substation area including MS angle
5.1 of section 35 x 35 x 5mm for support of plate and necessary civil SqM 60.00
work and painting

Supply and fixing of shock treatment chart with glass and each
5.2 2.00
aluminium frame on wall in Bengali, Hindi and English

5.3 Supply of First Aid box with all necessary materials and medicines each 1.00

Supply,installation of 4.5kg CO2 fire extinguisher complete with each


5.4 2.00
intial charges discharge hose, horn and bracket
5.5 Supply and fixing of fire bucket filled with sand each 8.00

Supply and erection of fire bucket stand 1500mm wide and


1000mm height, made of 50mm x 50mm x 6mm angle iron with
5.6 cross bracing and 4nos. Hook for hanging the bucket as completed each 2.00
with painting (2 coats of Red paint over one coat of red oxide
primer)

6 EXTERNAL LIGHTING -

Supply & fixing of Top Maintainable LED Street Light luminaire


enclosed in pure polyester powder coated Pressure Die Cast
aluminium housing suitable to mounted on 55 mm OD bracket
arm. The maximum wattage of luminaire shall be 70W with
minimum system efficacy 110lm/W. Luminaire shall have two
separate compartments for LEDs and driver and both
compartments should be hermitically sealed to achieve IP 66
ingress protection. Optical compartment shall be provided with
6.1 heat resistant clear toughened glass to withstand IK 07 impact 40.00
rating, while control gear shall be provided with die cast
aluminium cover for safety. Potted LED Driver shall be SELV,
Isolated type, multistage Constant Current Constant Voltage
topology driver with proper heat sink for heat dissipation suitable
to operate in input voltage range of 100V to 300V (nominal rated
voltage – 240V) with 4 KV internal surge protection in both CM
and DM mode. Similar to Wipro make LR02-781-XXX-57-G2 or
Equivalent.

Supply & fixing of 45W top maintanable LED Post-top housed in


die cast aluminium housing and HET diffuser. Luminaire is suitable
6.2 for pole diameter of 4.00
65-75 mm. Protected with IP65 protection. CCT 5700K, CRI >70.
Similar to wipro make LP02-501-XXX-57-XX and Equivalent
Supply, installation , testing & commisioning of Steel 9 Mtr GI
Octagonal Pole -Top dia -70 mm, Bottom Dia-155 mm, Section-1
(Section Length - 7000 mm) Thick-3mm. Base Plate - 260mm x
260mm x 16mm. hole in pole at a height of 300mm above the
planting depth with Single Arm Bracket 1 Mtr long with 33.7mm
6.3 OD GI Pipe and coated with two coats of black bituminous paint -
through out internally and externally upto the planting depth and
the remaining portion above ground shall be painted with two
coat of aluminium painting over one coat of red oxide primer and
individual spike earthing with 8 SWG wire inclusive of civil
foundation work. Foundation Bolt- M24 x 750 mm (4Nos)

6.3.1 Single arm (9 MTR) no. 44.00

Supply & fixing of Junction box with clamp on street light pole /
recessed in gate pillars, comprising of 6A SP MCB with elmex
terminals suitable for terminating incoming and out going cables
6.4 no. 44.00
of upto 3 core 10 sq.mm 1.1 kV grade armoured PVC insulated and
covered cables including bolt,nut & screws, D - clamp etc. as
complete and as directed by Engineer - in - charge.

Wiring with 3 X 1.5sqmm 600 V grade FRLS insulated flexible Cu


conductor wire from looping junction boxes at the base of the
6.5 pole to the light fittings through prelaid rigid PVC conduit, as rm 360.00
required to be completed in all respect and as directed by
Engineer - in - Charge.

Supply and fixing of integral LED AVIATION Light with double lamp
6.6 nos 1.00
including all necessary accessories as required.

Providing and fixing following capacity 4 pole automatic on load


ON/OFF -Load changeover switches with side handle operation, in
7.0 -
sheet enclosure in metal board including drilling holes in metal
board, making connection , earthing the body etc. as required.

7.1 100 A , 4 POLE nos -


7.2 630 A , 4 POLE nos -
18.0 TELEPHONE, CCTV, ACCES CONTROL -

Supply testing commessioning of IP DIGITAL Indoor/Outdoor Type


MEGAPIXEL CAMERA-(IR Camera , 4.9 MEGAPIXEL SONY CHIPSET
LOW ILLUMINATION HIGH COLOR RESOLUTION AUDIO MIC
18.1 SUPPORT,POE SUPPORT , /MM lens, 50 mts (works in zero Light)- nos 65.00
video output• ONVIF technology• True day / night • DNR, Smart
IR• Up to 25m IR distance H.265 With Smart Analytics &
embedded Intelligence)

Supply testing commessioning of HD NVR : Recording Unit For


Cameras 36 Channel 4K NVR - with support for 4 SATA Hard Disk
And Audio Mic Support in 36 Channels H.265 With Smart Analytics
& embedded Intelligence (1) 4K NVR WIith Preview / Recording
Resolution upto 12MP 2) Recording frame rate: 3) SATA port:
18.2 nos 2.00
H.265 With Smart Analytics & embedded Intelligence , 4 SATA HDD
support 4)USB 2.0 Ports, VGA output, HDMI port . 5) Support
Onvif; Third-party IP cameras Supports 3G, 6) Support 15 x digital
zoom in preview/ playback channel Support IE, mobile phone
remote monitoring)

Supply testing commessioning of INTERCOM SYSTEM P&T Ports :


18.3 08 ; Digital Extension : 08 ; Extension Ports : 184 nos 1.00

Supply testing commessioning of INTERCOM SYSTEM P&T Ports :


18.4 nos 1.00
08 ; Extension Ports : 136

Supply testing commessioning of ACCESS CONTROL SYSTEM


ACCESS CONTROL WITH SINGLE LEAF LOCK ALONG WITH
18.5 ACCESSORIES , 4PC CARD PER DEVICE ,EXIT SWITCHFINGER+CARD nos 24.00
BASED STAND ALONE ACCESS CONTROL WITH LOCK AND
ACCESSORIES of Toshiba/Western Digital / Seagate make

Supply testing commessioning of Hard Disk Internal Surveillance


18.6 Hard Disk For Recording unit- 4TB of Toshiba/Western Digital / pcs 4.00
Seagate make
Supply testing commessioning of Power Supply LOCAL POWER port
18.7 100.00
POINT TO BE PROVIDED NEAR EACH CAMERA of GPTRON make

Supply testing commessioning of 8 Port Network Switch of


18.8 pcs 280.00
DLINK/REPUTED make

Supply testing commessioning of 16 Port Network Switch of


18.9 pcs 2.00
DLINK/REPUTED make

18.10 Supply testing commessioning of telephone reciever of REPUTED pcs 136.00


make

18.11 Supply testing commessioning of KTS reception phone of REPUTED pcs 2.00
make

Supply testing commessioning of krone module for intercom of


18.12 REPUTED make pcs 7.00

18.13 Supply testing commessioning of Desktop Computer For Viewing pcs 2.00
Cameras from the reception for intercom of REPUTED make

18.14 Supply testing commessioning of Camera Connectors lot 1.00

18.15 Supply & laying of Camera Network Cable rm 2,500.00

18.16 Supply & laying of Power Cable rm 1,000.00

18.17 Supply & laying Telephone cable rm 5,200.00


18.18 Supply & laying Conduit Pipe rm 8,700.00

18.19 Supply testing commessioning of Rack 6u nos 2.00

18.20 Supply testing commessioning of LED 42 INCH LED nos 2.00

18.21 Accessories for keeping camera /network switch accessories at the pcs 80.00
place of installation

18.22 Laying Charges with accessories rm 8,700.00

18.23 Training /Installation Charges job 1.00

DIESEL GENERATOR
4.00 DIESEL GENERATOR SET

Supply, installation, testing, commissioning of DG set with


accoustic enclosure including supply and installation of exhaust
pipe with 48kg/cum density fibreglass white wool along with all
MS support structure (The insulation shall be held in position with
4.1 galvanised steel wire mesh 0.63dia and finished neatly with
26SWG aluminium cladding) as required from engine to residential
silencer and thereafter upto termination point 3 M above the roof
level or as per lattest PCB norms and as specified in equipment
data sheet.

4.1,1 160 KVA (with Auto mains failure Panel) each 1.00
4.1.2 1250 KVA each 1.00

1250 KVA Auto mains failure, Auto load sharing & Auto
4.1.2.1 synchronization Panel

4.1.3 500 KVA (with Auto mains failure Panel) each 1.00

7.00 LIFT

Supply, installation testing and commissioning of lifts of maximum


rated load 15 passenger, speed 1.75mps of triplex system
travelleing for G +10 floors of travel height. Hair line stainlesssteel
venyle floor finish, centre opening automatic door of fire retardent
capacity not less than 2hours without machine room, gear less
system inclusive of all accessories, gadgets, emergency light car EACH
7.1 2.00
operating panel indicator door close and open button alarms,
colour LCD display, emergency phone, handicapped COP, braille
push buttons, star light ceiling finish inside the car, PVC floor
finish, and all other devices complying to fire escape, emergency
evacuation control, NBC etc. complete in all respect inclusive of
taxes duties etc.

Supply, installation testing and commissioning of lifts of maximum


rated load 544Kg, speed 1.00mps, travelleing for G + 7 floors of
travel height hair line stainlesssteel venyle floor finish, centre
opening automatic door of fire retardent capacity not less than
2hours with machine room, gear less system inclusive of all
7.4 accessories, gadgets, emergency light car operating panel indicator EACH 1.00
door close and open button alarms, colour LCD display, emergency
phone, handicapped COP, braille push buttons, star light ceiling
finish inside the car, PVC floor finish, and all other devices
complying to fire escape, emergency evacuation control, NBC etc.
complete in all respect inclusive of taxes duties etc.
1.7 LAB BLOCK LIFT PANEL each 1.00

1.8 APARTMENT BLOCK LIFT PANEL each 1.00

Internal Electrification (Part-A)


Wiring for light point/ fan point/ exhaust fan point/ call bell point
with 1.5 sq.mm FRLS PVC insulated copper conductor single core
cable in surface / recessed medium class PVC conduit, with
1 modular switch, modular plate, suitable GI box and earthing the
point with 1.5 sq.mm FRLS PVC insulated copper conductor single
core cable etc. as required.

1.1 Group B Point 169.00

1.2 Group C Point 749.00

Wiring for circuit/ submain wiring alongwith earth wire with the
2 following sizes of FRLS PVC insulated copper conductor, single core
cable in surface/ recessed medium class PVC conduit as required.

2.1 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire meter 6,050.00

2.2 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire meter 10,265.00

2.3 2 X 4 sq. mm + 1 X 4 sq. mm earth wire meter 6,819.00


2.4 4 X 4 sq. mm + 2 X 4 sq. mm earth wire meter 250.00

Supplying and fixing of following sizes of medium class PVC


conduit along with accessories in surface/recess including cutting
3 the wall and making good the same in case of recessed conduit as
required.

3.1 25 mm meter 850.00

3.2 32 mm meter 550.00

Supplying and fixing following modular switch/ socket on the


4 existing modular plate & switch box including connections but
excluding modular plate etc. as required.

4.1 5/6 A switch Each 134.00

4.2 15/16 A switch Each 568.00

4.3 3 pin 5/6 A socket outlet Each 1,430.00

4.4 6 pin 15/16 A socket outlet Each 136.00

4.5 Bell push Each 24.00

Supplying and fixing two module stepped type electronic fan


5 regulator on the existing modular plate switch box including Each 78.00
connections but excluding modular plate etc. as required.
Supplying and fixing modular blanking plate on the existing Each
6 432.00
modular plate & switch box excluding modular plate as required.

Supplying and fixing following size/ modules, GI box alongwith


7 modular base & cover plate for modular switches in recess etc. as
required.

7.2 3 Module (100 mmX75 mm) Each 134.00

7.3 4 Module (125 mmX75 mm) Each 136.00

7.4 8 Module (125 mmX125 mm) Each 432.00

Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction


8 box/ wooden block including connections etc. as required. Each 44.00

Wiring for group controlled (looped) light point/fan point/exhaust


fan point/ call bell point (without independent switch etc.) with
1.5 sq. mm FRLS PVC insulated copper conductor single core cable
9 in surface/ recessed PVC conduit, and earthing the point with 1.5
sq. mm FRLS PVC insulated copper conductor single
core cable etc. as required.

9.1 Group C Point 422.00

MCCB, MCB & DB’S


Supplying and fixing following way, single pole and neutral, sheet
steel, MCB distribution board, 240 V, on surface/ recess, complete
10 with tinned copper bus bar, neutral bus bar, earth bar, din bar,
interconnections, powder painted including earthing etc. as
required. (But without MCB/RCCB/Isolator)

10.1 6 way, Double door Each 32.00

Supplying and fixing following way, horizontal type three pole and
neutral, sheet steel, MCB distribution board, 415 V, on surface/
11 recess, complete with tinned copper bus bar, neutral bus bar,
earth bar, din bar, interconnections, powder painted including
earthing etc. as required. (But without MCB/RCCB/Isolator)

11.1 4 way (4 + 12), Double door Each 32.00

11.2 6 way (4 + 18), Double door Each 17.00

Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C”


curve, miniature circuit breaker suitable for inductive load of
13 following poles in the existing MCB DB complete with connections,
testing and commissioning etc. as required.

13.1 Single pole Each 816.00

13.2 Double pole Each 41.00

13.3 Triple pole and neutral Each 44.00


13.3 Supplying and fixing single pole blanking plate in the existing Each 112.00
MCB DB complete etc. as required.

Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet,


with 4 pole and earth, metal enclosed plug top alongwith 30 A,
“C” curve, TPMCB, in sheet steel enclosure, on surface or in Each
15 16.00
recess, with chained metal cover for the socket out let and
complete with connections, testing and commissioning etc. as
required.

Supplying and installing following size of perforated Hot Dipped


Galvanised Iron cable tray (galvanisation thickness not less than 50
16 microns) with perforation not more than 17.5%, in convenient
sections, joined with connectors, suspended from the ceiling with
G.I. suspenders including G.I. bolts & nuts, etc. as required.

16.1 150 mm width X 50 mm depth X 1.6 mm thickness Each 115.00

16.2 300 mm width X 50 mm depth X 1.6 mm thickness Each 640.00

Supplying and installing following size of perforated Hot Dipped


Galvanised Iron cable tray “bends” (galvanisation not less than 50
17 microns) with perforation not more than 17.5%, in convenient
sections, joined with connectors, suspended from the ceiling with
G.I. suspenders including G.I. bolts & nuts, etc. as required.

17.1 150 mm width X 50 mm depth X 1.6 mm thickness Each 13.00

17.2 300 mm width X 50 mm depth X 1.6 mm thickness Each 36.00


Supplying and installing following size of perforated Hot Dipped
Galvanised Iron cable tray “Tee” (galvanisation not less than 50
18 microns) with perforation not more than 17.5%, in convenient
sections, joined with connectors, suspended from the ceiling with
G.I. suspenders including G.I. bolts & nuts, etc. as required.

18.1 150 mm width X 50 mm depth X 1.6 mm thickness Each 4.00

18.1 300 mm width X 50 mm depth X 1.6 mm thickness Each 8.00

Internal Electrification (Part-B)


1.00 MV SWITCHGEAR / POWER PANEL / DISTRIBUTION BOARDS.

1.10 POWER PANEL:


Supply, installation, testing and commissioning of cubicle type
panels as specified and shown on drawing no. WTE2291/STAGE
2/7.001 SHEET 1
i) Main Aluminium busbars with bar type feeder connections & all
internal wiring and connections.
ii) Earthing all components, frame etc. to a common internal earth
bar.
iii) Powder Coat painting of all sheet metal works.
iv) All accessories & supporting structure.

v) Brass glands and crimping lugs for sending and receiving ends.

vi) All ammeters with C.T's and voltmeter and energy meters with
necessary fuses.
vii) Panel components as specified.
viii) MS base frame.
ix) All switch gear to have short circuit levels as specified.
1.9 LAB BLOCK LIGHTING & POWR FLOOR PANEL (L1, L2, L3) each 2.00

1.10 APARTMENT BLOCK LIGHTING & POWR FLOOR PANEL A1 each 1.00

1.11 APARTMENT BLOCK LIGHTING & POWR FLOOR PANEL A2, A3 each 1.00

1.12 KITCHEN & DINNING DB each 1.00

1.13 LAB DB (1 TO 8) each 16.00

3.1 Supply & fixing of light fixtures complete with:


a) Lamps and Ballasts
b) all necessary accessories as required
C) all necessary Down rods & fixing accessories for suspending
type light fittings

600 x 600 mm recess mounting decorative direct/indirect


LED luminaire enclosed in powder coated CRCA deep drawn
housing with unique floating spherical direct diffuser and
surrounding indirect light chamber. The luminaire comprised
with two optical compertment and it should be controlled
3.1.1 seperately. The maximum system wattage should be 34W each 96.00
with minimum system efficacy 100lm/w, CCT 5700K, CRI>
80. . Luminaire driver should be Isolated and multistage
constant current constant voltage type. input voltage range
of 150V to 270V ( nominal rated voltage – 240V) with
minimum 3KV surge protection, PF >0.95, THD <10%,
Similar to Wipro Make LM38-461-XXX-57-XX or Equivalent.
Supply of recess mounted LED Downlight enclosed in
preseure die cast aluminum housing for superior heat
management and HET diffuser for better light output and
uniform light distribution without glare. The maximum system
3.1.2 wattage should be 11W with minimum system efficacy each 130.00
95lm/w, CCT 6500K, CRI> 80. Luminaire driver should be
Isolated and multistage constant current type. Driver Input
voltage range of 150V to 270V ( nominal rated voltage –
240V) with minimum 2.5KV surge protection, PF >0.95, THD
<20%, Similar to Wipro Make LD91-141-XXX-65-XX or equivalent.

Supply of recess mounted LED Downlight enclosed in


preseure die cast aluminum housing for superior heat
management and HET diffuser for better light output and
uniform light distribution without glare. The maximum system
3.1.3 wattage should be 15W with minimum system efficacy each 422.00
95lm/w, CCT 6500K, CRI> 80. Luminaire driver should be
Isolated and multistage constant current type. Driver Input
voltage range of 150V to 270V ( nominal rated voltage –
240V) with minimum 2.5KV surge protection, PF >0.95, THD
<20%, Similar to Wipro Make LD91-201-XXX-65-XX or equivalent.

Surface mounted 600mm high effiecency 10W integrated LED


batten, with minimum 100 Lumens/Watt efficacy. CCT 6500K, CRI>
80. Luminaire driver should be Isolated and multistage constant
3.1.4 current type. Driver Input voltage range of 150V to 270V ( nominal each 75.00
rated voltage – 240V) with minimum 2.5KV surge protection, PF
>0.90, THD <20%, Similar to Wipro Make LL20-111-XXX-65-NE or
equivalent.

Surface mounted 1200mm high effiecency 20W integrated


LED batten, with minimum 100 Lumens/Watt efficacy. CCT
6500K, CRI> 80. Luminaire driver should be Isolated and
3.1.5 multistage constant current type. Driver Input voltage range each 161.00
of 150V to 270V ( nominal rated voltage – 240V) with
minimum 2.5KV surge protection, PF >0.90, THD <20%,
Similar to Wipro Make LL20-221-XXX-65NE1 or equivalent.
Surface/Suspended integrated LED Channel enclosed in
CRCA housing for superior heat management and highly
effective extruded Polycarbonate diffuser for maximum
effective illumination. The maximum system wattage should
3.1.6 be 39W with minimum system efficacy 100lm/w, CCT 5700K, each 176.00
CRI> 80. Luminaire driver should be Isolated and multistage
constant current type. Driver Input voltage range of 150V to
270V ( nominal rated voltage – 240V) with minimum 3KV
surge protection, PF >0.95, THD <10%, Similar to Wipro
Make LE10-491-XXX-57-XX or equivalent.

Suspended circular decorative LED Luminaire enclosed in


CRCA housing for superior heat management and highly
effective PMMA diffuser for maximum effective illumination.
The maximum system wattage should be 26W, CCT 5700K,
3.1.7 CRI> 80. Luminaire driver should be Isolated and multistage each 23.00
constant current type. Driver Input voltage range of 150V to
270V ( nominal rated voltage – 240V) with minimum 3KV
surge protection, PF >0.95, THD <10%, Similar to Wipro
Make LM71-341-XXX-57-XX or equivalent.

Surface mounted LED Downlight enclosed in CRCA housing


for superior heat management and HET diffuser for better
light output and uniform light distribution. The maximum
system wattage should be 9W. CCT 5700K, CRI> 80.
3.1.8 Luminaire driver should be Isolated and multistage constant each 39.00
current type. Driver Input voltage range of 150V to 270V
( nominal rated voltage – 240V) with minimum 2.5KV surge
protection, PF >0.9, THD <20%, Similar to Wipro Make LW01-
101-XXX-57-XX or equivalent.

Supply of Bulkhead LED enclosed in die cast Aluminium


housing for superior heat management and Polycarbinate
opul diffuser. The maximum system wattage should be 10W.
CCT 5700K, CRI> 80. Luminaire driver should be Isolated
3.1.9 and multistage constant current type. Driver Input voltage each 43.00
range of 150V to 270V ( nominal rated voltage – 240V) with
minimum 2.5KV surge protection, PF >0.9, THD <20%,.
Luminaire should be IP65 Protected. Similar to Wipro Make
LW07-141-XXX-57-XX or equivalent.
Supply of 2W recessed mounted LED Footlamp with all
3.1.10 mounting accsessories. Similar To Wipro Make FL921or each 24.00
equivalent.

3.1.12 300mm sweep exhaust fan each 46.00

3.1.13 BUZZER each 24.00

3.1.14 1200 mm sweep ceiling Fan each 64.00

3.1.15 600 mm sweep hi- speed ceiling Fan each 14.00

3.1.16 KEY card switch 3 PHASE each 8.00

3.1.17 KEY card switch single PHASE each 16.00

8 LAN SYSTEM
LAN NETWORK SYSTEM
PoE+ 24 Port Switch
The switch should have 24 x 10/100/1000Base t ports plus 4x
1000x SFP ports .Min 370 Watt PoE power budget and support for
IEEE 802.3af and IEEE 802.3at, Switch should have 16K MAC
entries table.Should have 8 Hardware QOS Queues per port ,OS
should support individual process (eg ssh , snmp, telnet, dhcp etc)
restart to prevent reboot in case of Software Process Crash by
running processes on top of Kernel.Switch should have switching NOS
8.1 21.00
fabric performance of minimum 56Gbps switch fabric. Layer 2, IP
v4 & IP v6 - Switch should be upgradeable to Open Shortest Path
First (OSPF) and VRRP.Should support less than 50 Millisecond
convergance for ring based architecture based on RFC
3619/REP/ERPS/G.8032 etc, Switch should have Port, vlan, IPv4,
IPv6, and time based Access Control Lists for both directions.
Switch should have Operating temperature: 32 to 122°F (0°C
to 45°C). Preffered Make : CISCO/Extreme /Juniper /Avaya

Core Switch
Switch should support stacking up to 8 switches or more with
stacking bandwidth of 40Gbps . The switch should have24x
10/100/1000Base t ports with 8x 1000x SFP ports .Min 4 10 G
based SFP+ port , Scalable to min 2 QSFP+ port , The switch should
be upgraded to 4 x SFP+ ports in future without changing the
base hardware . Should have min 2x Stacking port with min 40 NOS
8.2 1.00
Gbps stacking bandwidth from day 1 .Stacking should be ready
from day 1 with accessorries /cables.Stacking mechanism could be
achieved over a diversified location as minimum 800 Meters .
Switch should have dedicated 1 x 10/100/1000 BaseT port for Out
of band Management port. Switch should have Operating
temperature: 32 to 122°F (0°C to 50°C). Preffered Make :
CISCO/Extreme /Juniper /Avaya
CAT6 UTP cable - 4 pairs PVC - 23 AWG - 305 mtr Box
4 Pair CAT6 Unshielded, Twisted Pair (U/UTP) Cable 305
mtr per Box. Blue/Orange/White/Green in colour conforming
8.3 to the following standards like 23AWG, ANSI EIA/TIA 568 Box 46.00
C.2, EN50173, IEC 11801 3rd ED, frequency tested upto
700Mhz with Third Party Certificate etc. Cable Dia 6.1 ± 0.3,
Cross-member (+) fluted Spine/isolator for uniform
separation for all pairs. (Make : Legrand /Systemax/Hubbel)

CAT6 RJ45 socket - User End


Cat 6 UTP RJ 45 Sockets Tool Less Crimping, as per -
ISO/IEC 11801 Edition 2; ANSI/EIA/TIA 568-C.2; IEC series
60603-7, should have transparent shutter for protection
against dust, Contacts :gold/nickel, minimum thickness of
8.4 gold > 0.8 μm , Body should PBT Polycarbonate plastic Nos 325.00
material, IEEE 802.3af standard and PoE+, Endurance
2500 movements (plug insertion/withdrawal). IK03.
Operating Temp -40 Deg C to +70 Deg C, Maximum no of
Connections/ Re connections 5 without refreshing the
wiring. (Make : Legrand /Systemax/Hubbel)

CAT6 UTP patch panel - 24 port loaded - Toolless


CAT6 UTP RJ45 Loaded patch panel & connector - 24 port loaded
19" panel - 1 U, Panel: DC01 galvanised sheet steel, Compliant
with standards: ISO/IEC 11801 Edition 3.0 CENELEC EN 50173-1
2007 ANSI/EIA/TIA 568 C2-1 IEC series 60603-7, NFC 20730,
Standard 8877 – 603.7, Contacts: gold/nickel, thickness of gold >
0.8 μm minimum, Equipped with rear cable guide to hold cable
8.5 Nos 15.00
during maintenance,The connectors are connected from the front
without a special tool. Equipped with 4 cassettes of 6 RJ45 Cat. 6
connectors with toolless fast connection, marked 568 A/B, Max.
number of connections and disconnections: 5 without replacing
the wire, Endurance: 2500 operations (plug-in/pull-out) IK03,
Operating temperature: -40°C to +70°C (Make : Legrand
/Systemax/Hubbel)
CAT6 UTP patch cord - 1 mtr - Rack End
1 Meter Cat 6 U/ UTP Patch Cord, PVC,Performance at 250MHz
8.6 Should be as per Standards - IEC 61935-2 - Ed. 3.0 ISO/IEC 11801, Nos 325.00
Usage Temp – 20 to + 60°C, No of Twists 500, No of insertions
750, 24 AWG (Make : Legrand /Systemax/Hubbel)

CAT6 UTP patch cord - 2 mtr - User End


2 Meter Cat 6 U/ UTP Patch Cord, PVC ,Performance at 250MHz
8.7 Should be as per Standards - IEC 61935-2 - Ed. 3.0 ISO/IEC 11801, Nos 325.00
Usage Temp – 20 to + 60°C, No of Twists 500, No of insertions
750, 24 AWG (Make : Legrand /Systemax/Hubbel)

Single port face plate


8.8 Single Port Face Plate 1 Module in white colour. (Make : Legrand Nos 325.00
/Systemax/Hubbel)

Plastic surface box - 1/2 module


8.9 Plastic Flush Mounting Box 1/2 Module. (Make : Legrand Mtr 325.00
/Systemax/Hubbel)

6 Core OM3 Unarmoured LSZH OFC


6 Core - Optic fiber cable OM3 - Unitube Single Jacket Unarmor
Lite, Jelly Filled Loose Tube Optical Fiber Cable 50 μm /125 μm ,
Glass Roving Yarn provide tensile strength and antibuckling
properties. LSZH Aqua RAL-6027, IEC 60793-2-10 category A1a.2;
EN 60793-2-10: type A1a.2, TIA/EIA-492 AAAB, ITU
Recommendation G.651, EN 50 173:2002 category OM3,ISO/IEC
9.0 Nos 400.00
11801:2002 category OM3, IEEE 802.3-2002 incl. amendment
802.3ae - 2002. Maximum installation tensile strength - E1 1000 N,
- Short term tensilestrength - E1 650 N, - Permanent
tensilestrength - E1 350 N , Compressive strength(crush) - E3 1500
N, Min. Bending radius,unloaded - E11 10 D, Min. Bending
radius,loaded 20 D, Operating temp : - 30°C to +70°C (Make :
Legrand /Systemax/Hubbel)
19" Modular optic drawer
6 to 96 Port Rack mount Sliding Fibre optic drawer (LIU) with
trasperent cover, Metal 19” fibre optic drawers, 4 cable entries,
9.1 supplied with screw fixing kit, 2 cable glands (Ø 13.5 and 16 mm), Nos 3.00
coiling system, Sliding: end stop at a 30° angle for easier wiring
with lock with lock. Depth: 220 mm, height 1 U (Make : Legrand
/Systemax/Hubbel)

SC pigtails - OM3 - 1 mtr


SC pigtails - OM3 - 1 mtr, ITU-G651, standards TIA / EIA 492AAAD ,
9.2 Nos 54.00
900 μm tight structure, Crush Resistance 500N Operating temp : -
20°C to +60°C (Make : Legrand /Systemax/Hubbel)

Unit of 3 duplex SC adapters loaded with adapter plate - MM


6 port Adapter plate, loaded with 3 nos. of duplex SC unit for
9.3 multi mode fiber adapters to be compatible to fit in 19" U/UTP 24 Nos 9.00
port modular patch panel or 24 port LIU. (Make : Legrand
/Systemax/Hubbel)

Splice Tray - 24 fibre capacity


9.4 Stackable Splice Tray - 24 fibre capacity, Stack upto 2 Splice Tray In Nos 3.00
Single LIU (Make : Legrand /Systemax/Hubbel)

Blanking plate for LIU


Blanking plate for LIU and Modular Patch Panel (6XRJ45 Blanking
9.5 Nos 4.00
plate for 19" panel - Black in colour). (Make : Legrand
/Systemax/Hubbel)

SC/LC duplex fibre patch cord - OM3 - 3 mtr


3 Meter SC/LC Optic Fiber Patch Cords – Multimode (OM3)
9.6 Operating temp : - 20°C to +60°C. Insertion loss: 0.15dB, 500 Nos 9.00
matings. Conform to IEC, EIA-TIA, and Telecordia performances
requirements. (Make : Legrand /Systemax/Hubbel)
Racks : 42U 800x800 Free standing cabinet with all standard
accessories
Width (mm) 800, Depth (mm) 800, Approx.Net Wt (kg) 150,
CRCA 'D' Grade thickness (mm) 1.2, RAL 9017 (Matt Black),
Glass: 4mm Toughened Tinted Glass Door, Injected one
piece polyurethane gasket on frame, Accessories: Cooling
Fan (230V A/C 90 CFM) - 4 Nos, Cable Manager Metal- 4
Nos, PDU 230VAC - 1 No (12 nos. 6A/16A sockets with
9.7 plugs 6A/16A - 1/1pc & MCB 16A/32A - 0/1 Pc), Cable Nos 1.00
Channel 100mm wide 42U- 2 Nos, Heavy Duty Stationary
Shelf 600W x 475D - 1 No., Mounting Hardware (20 sets of
M6 screws,washer,cage nuts (nickel coated)) - 3 Nos.,
Earthing Strips 150mm H - 1 No, Door Lock - 1 No, Castor
Wheels (with Brake) - 2 Nos, Castor Wheels (without Brake)
- 2 Nos, Front Metal Band - 1 No. Packing: 5 ply cardboard &
Inside 28 ply EP foam. In the rack there must be maintained
1 U = 1.75 inches space. ( Make :Legrand/ Rittal / Valrack)

27U 800x800 Free standing cabinet with all standard


accessories
Width (mm)-800, Depth (mm) - 800, Approx.Net Wt (kg) -
100, CRCA 'D' Grade thickness (mm) - 1.2, RAL 9017 (Matt
Black), Glass - 4mm Toughened Tinted Glass Door,
Accessories:, Cooling Fan (230V A/C 90 CFM) - 4 Nos, PDU
230V AC - 1, Cable Channel 100mm wide 22U - 2 No, Cable
9.8 Manager Metal - 2 Nos, Heavy Duty Stationary Shelf 600W Nos 2.00
x 475D - 1 No., Earthing Strips 150mm H - 1 No, Mounting
Hardware (20 sets of M6 screws,washer,cage nuts (nickel
coated)) - 3 No, Door Lock - 1 No, Front Metal Band -1 No.,
Castor Wheels (with Brake) - 2 Nos., Castor Wheels (without
Brake) - 2 Nos. Packing: 5 ply cardboard & Inside 28 ply EP
foam. In the rack there must be maintained1 U = 1.75 inches
space.

11.0 RISING MAIN


Supplying, installing on wall, testing and commissioning of
following capacity 1000 volt grade, 3phase 4 wire ( 100% N), IP-55
Sandwich Type Rising mains made of 1.5 mm thick Hot-galvanized
sheet Steel confirming IK-10 impact strength duly painted with
RAL 7035 Resin , wall straps, fully insulated by Class F ( 155 deg )
PET Film 4 Nos aluminium bus bars ( Cu+ Tin Plating) in convenient
11.1 sections and suitable for 415 volts, 3 phase, 4 wire, 50 Hz, A.C.
supply with factory fitted joint monobloc, expansion joints ( if
length more than 40 mtrs), joint cover, End Cover, Spring brackets
and earthing with 2 runs of Aluminium Earth strips etc. and
provision for 2 nos. tap-off box in each floor as required. (Rising
mains confirming to IS 8623, IEC 61439- 6, DIN VDE 0660 PART 500
AND 502)

11.1.1 1600 amps (S.C. rating for 1 sec - 50 KA) meter 22.50

11.1.2 630 amps (S.C. rating for 1 sec - 50 KA) meter 13.50

11.1.3 Elbow ( fabrication Cost) for 1600A NOS 4.00

11.1.4 Elbow ( fabrication Cost) for 630A NOS 4.00

11.1.5 Flanged End (fabrication Cost) for 1600A NOS 2.00

11.1.6 Flanged End (fabrication Cost) for 630A NOS 1.00

11.1.7 1600A Braided Cu Flexible ( electro-tinned with silver coated SETS 2.00
Socket) TPN
11.1.8 630A Braided Cu Flexible ( electro-tinned with silver coated SETS 1.00
Socket) TPN

11.1.9 Adopter Box for 1600A/ 630A NOS 3.00

Supplying, installing, testing and commissioning of following


capacity 4P tap off box / plug-in box made of 1.5mm thick sheet
12.0 steel enclosure duly painted with powder coating on existing bus
bar system complete with 4P MCCB, 36KA T/M release ,
connection, earthing etc. as follows.

12.1 Tap-off-Box with 250A, FP, ( I cs = Icu = 36kA ) , incomer MCCB each 4.00

12.2 Tap-off-Box with 100A, FP, ( I cs = Icu = 36kA ) , incomer MCCB each 2.00

Supplying and fixing following modular switch / socket on the


13.0 modular plate & switch box including connections modular plate
etc. as required.

13.1 20 amps switch WITH 6 pin 20 amp socket outlet each 32.00

Supply, installation, testing & commissioning of 20 kva true online


double conversion UPS system with 30 mins & with inbuilt each
14.0 2.00
isolation Transformer, SMF battery backup, MS rack Links and
accessories as required

Providing and fixing following capacity 4 pole automatic on load


ON/OFF -Load changeover switches with side handle operation, in
16.0 sheet enclosure in metal board including drilling holes in metal
board, making connection , earthing the body etc. as required.
16.1 100 A , 4 POLE nos 1.00

supply, laying, testing, commissioning, of under floor GI race


17.0 ways with all accsesaries of following dimention DLP TRUNKING

17.1 PLASTIC TRUNKING 105MMX50MMX 2MTR EACH 175.00

17.2 FLEXIBLE COVER 85MM WIDTH EACH 118.00

17.3 4 MOSAIC MOD.FRA FOR 85MM COVE EACH 128.00

17.4 JOINT FOR 85MM WIDTH COVER EACH 352.00

17.5 BASE JOINT EACH 352.00

17.6 END CAP EACH 64.00

17.7 INTERNAL ANGLES-ADJ FRM 80 DEG EACH 448.00

17.8 EXTERNAL ANGLES-ADJ FRM 60 DEG EACH 448.00

17.9 FLAT ANGLES EACH 224.00


17.10 SOCKET SHUTTERED 6/16 3 PIN INDIAN 3 MODULE EACH 128.00

17.11 SWITCH 20 A SP 1 WAY 1 MODULE EACH 128.00

supply, laying, testing, commissioning, of under floor GI race


18.0 ways with all accsesaries of following dimention

18.1 225mmx38 mm 3 compartments race way (2.44 mtr) EACH 200.00

18.2 GI FIXING BRACKET 225X25 MM (1 No. for 2mtr) EACH 208.00

18.3 COUPLING 38 (For joining 2 pieces of raceway) EACH 100.00

18.4 225x225 mm height adjustable junction box 50-70mm EACH 160.00

Total of Part-E
Bill of Quantity
Name of Work: Construction of Research Park at IITG Campus.
Part-F(HVAC works)
Item Rate in figure
Description Unit Quantity Rate in words Amount (Rs.)
no. (Rs.)
Sub Head-A
VRF Airconditioning system
VRF/ VRV -IVth generation Outdoor units

Supply Installation Testing & commissioning of IVth Generation air


cooled Full Inverter VRF System with Modular type outdoor units,
all scroll DC Inverter compressors for cooling & Heating applications
along with different types of indoors compitable with VRF ODUs. All
inverter capacity controlling compressors shall be suitable for 3
Phase, 50 Hz.. The outdoor should be with 'Ocean Black Fin' heat
exchanger with a black coating to shield it from Salt, Sand & other
1.0 elements brought in by the air. The manufacturer must be having its
own make compressor fitted in outdoor. All proposed outdoor unit
should have minimum COP of 4.0 & 6.1 at 100% & 50% load
condition respectively for Cooling .conditions ((Outside DBT-35 Deg
C & Inside DBT 27 Deg C &19 WBT) .COP should be based on
nominal capacity as mentioned in BOQ and power input at this
condition i/c first charge of refrigenet .Refrigerent shall be used
410a.

1.1 8 HP (22.4 KW) Top discharge Nos 6

1.2 10 HP (28 KW) Top discharge Nos 1

1.3 12 HP (33.6 KW) Top discharge Nos 10


1.4 20 HP (56 KW) Top discharge Nos 16

2.0 VRF/ VRV -Indoor units.

Supply, Instalaltion, testing and commissioning of( histatcic


ductable Type/Casseette Type/Hiwall Type) Indoor units equipped
with pre-filter, fan section with suitable static fan, multispeed
motor, coil section with DX coil, outer cabinet, insulation, pipe
connections etc. of various capacities as per specifications and
drawings. The minimum TR/CFM has to be adhere while selecting
the equipment.Diversity beetwen ODU and IDU should not exceed
108 %. Vendor has to select IDU or ODU of nearby higher capacity
to maintain the diversity as specified.

2.1 Hi Static Type

2.1.1 8 TR/2650 CFM Nos 2

2.2 Cassette Type indoors

2.2.1 4 TR/1200 CFM Nos 2

2.2.2 2.5 TR/940 CFM Nos 33

2.2.3 3.5 TR /1164 CFM Nos 54

2.3 Hiwall Type

2.3.1 1.28 TR /470 CFM Nos 48

3.00 Fresh Air System


Supply , Installation , Testing & commissioining of Fresh Air unit with
3.10 low noise BLDC motor .It can supply the fresh air in conditioned
space and create positive presure inside which can reduce
contaminated air from outside.

3.1.1 6.3 TR/835 CFM Nos 6

4.00 SITC of Refnet joints for proper distribution of refrigernt through the
complete circuit for indoor and Outdoor

4.1 Refnet Nos 139

4.2 SITC of Corded remote controller-For Cassette & Hi Static Nos 8

4.3 SITC of Cordless Remote Controller- For Hi wall Nos 137

Supply , Installation , Testing & commissioining of interconnecting


5.00 refrigerant piping along with closed cell elastomeric insulation and
supports, between indoor & outdoor units duly insulated as per
specifications. Make-Rajco/Mandev

5.1 41.3 mm O.D. ( insulation : 19 mm ) RM 180

5.2 34.9 mm O.D. ( insulation : 19 mm ) RM 240

5.3 28.6 mm O.D. ( insulation : 19 mm ) RM 380


5.4 25.4 mm O.D. ( insulation : 19 mm ) RM 210

5.5 22.2 mm O.D. ( insulation : 19 mm ) RM 280

5.6 19.1 mm O.D. ( insulation : 13 mm ) RM 450

5.7 15.9 mm O.D. ( insulation : 13 mm ) RM 740

5.8 12.7 mm O.D. ( insulation : 13 mm ) RM 380

5.9 9.5 mm O.D. ( insulation : 13 mm ) RM 690

5.10 6.4 mm O.D. ( insulation : 13 mm ) RM 210

6.00 SITC of 1.5 sq x 2c mm shielded cu cable for communication RM 2530

Supply, installation, testing and balancing of powder coated


7.00 Extruded Aluminium supply air Grilles with volume control dampers
in accordance with the approved shop drawings and Sq Mt 14
specifications.Make-Dynacraft/Sysytem Air

Supply, installation, testing and balancing of Air Grilles without


8.00 volume control dampers in accordance with the approved shop Sq Mt 10
drawings and specifications.Make-Dynacraft/Sysytem Air
Supply, installation, testing and balancing of powder coated
9.00 Extruded Aluminium supply air Diffuse with volume control
dampers in accordance with the approved shop drawings and Sq Mt 12
specifications.Make-Dynacraft/Sysytem Air/

Supply, installation, testing and balancing of Air Diffuse without


10.00 volume control dampers in accordance with the approved shop Sq Mt 12
drawings and specifications.Make-Dynacraft/Sysytem Air/

Supply, installation and testing of Factory fabricated GI sheet metal


11.00 ducts as per approved shop drawings and as required by the
specifications with 6 mm nitrile insulation . Make-Jindal/Tata

11.1 22 G Sq Mt 170

11.2 24 G Sq Mt 410

Supply, fabrication, installation and testing the flexible connections


12.00 constructed of fire resistance flexible double canvas sleeve as per Nos 2
the approved shop drawings.

DRAIN PIPING : Supply, Installation and Testing of UPVC heavy class


drain piping insulated out of 13 mm thick Class O closed cell
13.00 elastomeric nitrile rubber material of approved make as per
specification complete with supports, consumables, fittings, pipe
sleeves, U trap & leak arresting of following sizes.

13.1 25 mm RMT 530

13.2 32 mm RMT 430


13.3 40 mm RMT 260

14.0 POWER PANEL:


Supply, installation, testing and commissioning of cubicle type
panels as specified and shown on drawing no.
WTE2291/STAGE 2/7.001 SHEET 1
i) Main Aluminium busbars with bar type feeder connections &
all internal wiring and connections.
ii) Earthing all components, frame etc. to a common internal
earth bar.
iii) Powder Coat painting of all sheet metal works.
iv) All accessories & supporting structure.
v) Brass glands and crimping lugs for sending and receiving
ends.
vi) All ammeters with C.T's and voltmeter and energy meters
with necessary fuses.
vii) Panel components as specified.
viii) MS base frame.
ix) All switch gear to have short circuit levels as specified.

14.1 LAB BLOCK MAIN AC PANEL NOS 1

i) 1 Nos.1000A, 4P, EDO, microprocessor based ACB


complete with Over current & S/C protection as incomer
ii) 2 Nos. 200A TPN MCCB complete with Over current & S/C
protection as OUTGOING
iii) 6 Nos. 160A TPN MCCB complete with Over current & S/C
protection as OUTGOING
iv) 3 Nos. 63A TPN MCB complete with Over current & S/C
protection as OUTGOING
v) 96 mm² Voltmeter 0 - 600V with Voltmeter selector switch -
3Nos
vi) 96 mm² Ampmeter 0-1000A with Ampmeter selector switch
- 3Nos.
vii) 3 Nos. CT's 1000/5A 10VA Class-I accuracy
viii) 3 Nos. indicating lamps (LED Type)
ix) TPN Aluminium busbar mounted on non-hygroscopic
insulator supports - 5x150x10 mm electrical grade bar for
phase 3x150x10 mm electrical grade bar for neutral
x) Two Nos. 10 mm stud type earth terminals G.I. earth bus
bar arrangement

14.2 APPARTMENT BLOCK MAIN AC PANEL NOS 1

i) 1 No.250A 4P MCCB complete with Over current & S/C


protection as incomer
ii) 2Nos. 63A TPN MCB as outgoing
iii) 16Nos. 32A TPN MCB as outgoing
iv) 96 mm² Voltmeter 0 - 600V with Voltmeter selector switch -
1 No
v) 96 mm² Ampmeter 0-250A with Ampmeter selector switch -
1No
vi) 3 Nos. CT's 250/5A 10VA Class-I accuracy
vii) 3 Nos. indicating lamps (LED Type)
viii) TPN Aluminium busbar mounted on non-hygroscopic
insulator supports - 1x100x6 mm electrical grade bar for phase
1x80x6 mm electrical grade bar for neutral
ix) Two Nos. 10 mm stud type earth terminals G.I. earth bus
bar arrangement

14.3 LAB BLOCK FLOOR AC PANEL NOS 3

i) 1 No.160A 4P MCCB complete with Over current & S/C


protection as incomer
ii) 6Nos. 63A TPN MCB as outgoing
iii) 3Nos. 32A TPN MCB as outgoing
iv) 3Nos. 20A DP MCB as outgoing
v) 96 mm² Voltmeter 0 - 600V with Voltmeter selector switch -
1 No
vI) 96 mm² Ampmeter 0-250A with Ampmeter selector switch -
1No
vii) 3 Nos. CT's 250/5A 10VA Class-I accuracy
viii) 3 Nos. indicating lamps (LED Type)
ix) TPN Aluminium busbar mounted on non-hygroscopic
insulator supports - 1x100x6 mm electrical grade bar for phase
1x80x6 mm electrical grade bar for neutral
x) Two Nos. 10 mm stud type earth terminals G.I. earth bus
bar arrangement
15.00 MV CABLE
Supply of heavy duty 1100V grade LT XLPE insulated
15.1 sheathed & armoured cables with aluminium / copper
conductors as specified and required.

15.1.1 4C X 10sq.mm. Al. Ar. XLPE Cable RM 762

15.1.2 4C X 16sq.mm. Al. Ar. XLPE Cable RM 1602

15.1.3 3.5C X 35sq.mm. Al. Ar. XLPE Cable RM 108

15.1.4 3.5C X 185sq.mm. Al. Ar. XLPE Cable RM 120

15.1.5 3.5C X 300sq.mm. Al. Ar. XLPE Cable RM 160

Supply, installation, testing & commissioning of modular type


16.0 240V, 50Hz, 25A stater with 20 A plug point including base EACH 137
plate and necessary connection in modular type MS box for
2TR, 1.5TR & 1TR split type AC machine.
1 VENTILATION
Supply, erection, testing & commissioning of long casing GSS
Vane Axial (motor should complete accomodated in side the
fan casing) Flow Exhaust Fans (Fire Rated)of capacity as
below with TEFC single speed motor to suit 250 deg C for 2
hours.Fan should be complete with back draft damper, outet
1.1 wire guard, fan support frame work in standard MS
construction with painting. Fan should be AMCA certified.
Sound pressure level of the fan should not exceed 73 dB(A) at
3 meter in room condition at given CFM.
In case of vane axial, vanes outside of fan casing is not
acceptable.

EXHAUST FAN:AXIAL FLOW FAN: 3100 CFM @ 35 mm wg


1.1.1 Nos 1
static pressure for Kitchen, (SISW belt driven fan)

FRESH AIR SUPPLY FAN:AXIAL FLOW FAN: 3100 CFM @


1.1.2 35 mm wg static pressure for Kitchen, (Vane Axial type direct Nos 1
driven fan)

Supply, erection, testing & commissioning of rectangular type


direct driven inline fan. Fan should be AMCA certified. Sound
2
pressure level of the fan should not exceed 55 dB(A) at 3
meter in room condition at given CFM.

2.1 750 CFM inline Fan for exhaust Nos 4

2.2 700 CFM inline Fan for exhaust Nos 4

3 DUCTING & ACCESSORIES


Supply and installation of sheet metal ducting complete with
GI threaded supports, vanes, splitters, gaskets for joints,
3.1 thermal isolation blocks, etc. as per specs. 120 GSM sheets
GI Sheet Metal Ducting (Rectangular) Factory Fabricated
(made on lock forming machine RTV sealed)

3.1.1 24 Gauge Sqm 310


3.1.2 22 gauge Sqm 80

4 EXHAUST AIR DIFFUSERS


Supply, installation ,testing and balancing of rectangular
square type air Grilles / Diffusers with volume control
dampers. Each diffuser shall be equipped with fixed air
4.1 distribution grid, removable core for proper balancing of air Sqm 20
distribution system Powder coated extruded aluminium
diffusers of approved colour suitable for installation in ceiling
with sizes.
5 SUPPLY AIR DIFFUSERS
Supply, installation ,testing and balancing of rectangular
square type air Grilles / Diffusers with volume control
dampers. Each diffuser shall be equipped with fixed air
5.1 distribution grid, removable core for proper balancing of air Sqm 10
distribution system Powder coated extruded aluminium
diffusers of approved colour suitable for installation in ceiling
with sizes.
6 GRAVITY LOUVER WITH BIRD SCREEN
Gravity louvershall be designed to maintained 3.0 mm over
pressure inside the room. Frame and louver (self acting type)
thickness shall be 1.25 mm & 0.63 mm respectively.
6.1 No. 8
Constructional feature of frame & louver shall G.I. & aluminum
respectively. Size : As per the dimension of discharge section
of fan
7 DUCT DAMPER
Duct damper shall be fabricated from G.I. sheet with MS
Frame. Frame & louver thickness shall be 1.6 mm & 1.0 mm
8 Sqm 10
respectively. Damper shall have suitable operating lever with
bush / bearing and low leakage.

9 Lifting and shifting charges Lot 1


10 Specialised structural works required for ventilation system Kg 100

Total of Sub Head-A

Sub Head-B
CHAPTER 7-MV CABLE LAYING
Laying and fixing of one number PVC insulated and PVC
1 sheathed / XLPE power cable of 1.1 kV grade of following size on
cable tray as required.

1.1 Upto 35 sq. mm (clamped with 1mm thick saddle) meter 2472

Above 95 sq. mm and upto 185 sq. mm (clamped with 25/


1.2 40x3mm MS flat clamp) meter 60

Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm
1.3 MS flat clamp) meter 280

CHAPTER 9-MV CABLE JOINTING & END TERMINATION


Supplying and making end termination with brass compression
gland and aluminium lugs for following size of PVC insulated and
2 PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as
required.

2.1 3½ X 35 sq. mm (32mm) each 12

2.2 3½ X 185 sq. mm (57mm) each 2

2.3 3½ X 300 sq. mm (70 mm) each 6


2.4 4 X 10 sq. mm (25 mm) each 26

2.5 4 X 16 sq. mm (28mm) each 44

CHAPTER-4-CABLE TRAYS

Supplying and installing following size of perforated Hot Dipped


Galvanised Iron cable tray (galvanisation thickness not less than 50
3 microns) with perforation not more than 17.5%, in convenient
sections, joined with connectors, suspended from the ceiling with
G.I. suspenders including G.I. bolts & nuts, etc. as required.

3.1 150 mm width X 50 mm depth X 1.6 mm thickness Each 210

3.2 300 mm width X 50 mm depth X 1.6 mm thickness Each 150

Supplying and installing following size of perforated Hot Dipped


Galvanised Iron cable tray “bends” (galvanisation not less than 50
4 microns) with perforation not more than 17.5%, in convenient
sections, joined with connectors, suspended from the ceiling with
G.I. suspenders including G.I. bolts & nuts, etc. as required.

4.1 150 mm width X 50 mm depth X 1.6 mm thickness Each 8

4.2 300 mm width X 50 mm depth X 1.6 mm thickness Each 8


Supplying and installing following size of perforated Hot Dipped
Galvanised Iron cable tray “Tee” (galvanisation not less than 50
5 microns) with perforation not more than 17.5%, in convenient
sections, joined with connectors, suspended from the ceiling with
G.I. suspenders including G.I. bolts & nuts, etc. as required.

5.1 150 mm width X 50 mm depth X 1.6 mm thickness Each 8

5.2 300 mm width X 50 mm depth X 1.6 mm thickness Each 8

CHAPTER-5-EARTHING
Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including
accessories, and providing masonry enclosure with cover plate
6.1 having locking arrangement and watering pipe etc. with Each 4
charcoal/coke and salt as required.

Supplying and laying 25 mm X 5 mm G.I strip at 0.50 meter


below ground as strip earth electrode, including
6.2 connection/terminating with G.I. nut, bolt, spring, washer etc. meter 40
as required.(Jointing shall be done by overlapping and with 2
sets of G.I. nut bolt & spring washer spaced at 50 mm)

Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess


6.3 for connections etc. as required. meter 20

Providing and fixing 6 SWG dia G.I. wire on surface or in recess for
6.4 loop earthing as required. meter 80

Total of Sub Head-B

Total of Part-F

Вам также может понравиться