Telecommunication Building

HVAC Load Analysis


for

Al-Cardinal Group
Sudan

Prepared By:

M. R. Berair Architects & Consulting


Khartoum

Sunday, November 21, 2010


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 2

General Project Data Input


General Project Information
Project file name: D:\Ongoing Projects\HAM
Electromechanical\Telecommunication
Building\Telecommunication Building.CHV
Project title: Telecommunication Building
Project address: B- Hal Matar
Project city, state, ZIP: Juba, Central Equatoria
Project date: Sunday, November 21, 2010
Weather reference city: Juba, EQUATORIA, SUDAN
Client name: Al-Cardinal Group
Client address: Sudan
Company name: M. R. Berair Architects & Consulting
Company address: Khartoum
Barometric pressure: 956.848 mbar
Altitude: 456.8952 meters
Latitude: 5 Degrees
Mean daily temperature range: 11.11111 Degrees
Starting & ending time for HVAC load calculations: 1am - 12am
Number of unique zones in this project: 12

Building Default Values


Calculations performed: Cooling loads only
Lighting requirements: 20.00 Watts per square meter
Equipment requirements: 10.00 Watts per square meter
People sensible load multiplier: 70 Watts per person
People latent load multiplier: 45 Watts per person
Zone sensible safety factor: 10 %
Zone latent safety factor: 10 %
Zone heating safety factor: 0 %
People diversity factor: 100 %
Lighting profile number: 1
Equipment profile number: 1
People profile number: 1
Building default ceiling height: 3.20 meters
Building default wall height: 3.20 meters

Internal Operating Load Profiles (C = 100)


hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 C C C C C C C C C C C C C C C C C C C C C C C C
2 C C C C C C C C C C C C C C C C C C C C C C C C
3 C C C C C C C C C C C C C C C C C C C C C C C C
4 C C C C C C C C C C C C C C C C C C C C C C C C
5 C C C C C C C C C C C C C C C C C C C C C C C C
6 C C C C C C C C C C C C C C C C C C C C C C C C
7 C C C C C C C C C C C C C C C C C C C C C C C C
8 C C C C C C C C C C C C C C C C C C C C C C C C
9 C C C C C C C C C C C C C C C C C C C C C C C C
10 C C C C C C C C C C C C C C C C C C C C C C C C
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 3

General Project Data Input (cont'd)


Building-Level Design Conditions
Design Outdoor Outdoor Indoor Indoor Grams In/Outdoor
Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
December 36 24 50% 24 4.59 2
January 37 24 50% 24 4.36 3
February 38 24 50% 24 3.89 4
March 37 24 50% 24 4.13 3
Winter -18 0

Master Roofs
Roof ASHRAE Roof Dark Susp.
No. Roof# U-Fac Color Ceil
1 8 1.200 No No

Master Walls
Wall ASHRAE Wall Wall
No. Group U-Fac Color
1 A 0.500 D

Master Glass
Glass Summer Winter Glass Interior Interior
No. U-Factor U-Factor Shd.Coef. Shading Shd.Coef
1 3.700 3.900 0.600 1 0.550
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 4

Building Summary Loads


Building peaks in February at 4pm.
Bldg Load Area Sen %Tot Lat Sen Net %Net
Descriptions Quan Loss Loss Gain Gain Gain Gain
Roof 1,859 0 0.00 0 36,530 36,530 11.44
Wall 1,400 0 0.00 0 10,410 10,410 3.26
Glass 538 0 0.00 0 100,504 100,504 31.47
Floor Slab 0 0 0.00 0 0 0 0.00
Skin Loads 0 0.00 0 147,444 147,444 46.16
Lighting 37,174 0 0.00 0 40,891 40,891 12.80
Equipment 18,587 0 0.00 0 20,446 20,446 6.40
People 262 0 0.00 12,989 20,205 33,194 10.39
Partition 0 0 0.00 0 0 0 0.00
Cool. Pret. 0 0 0.00 0 0 0 0.00
Heat. Pret. 0 0 0.00 0 0 0 0.00
Cool. Vent. 2,592 0 0.00 33,738 42,270 76,008 23.80
Heat. Vent. 0 0 0.00 0 0 0 0.00
Cool. Infil. 0 0 0.00 0 0 0 0.00
Heat. Infil. 0 0 0.00 0 0 0 0.00
Draw-Thru Fan 0 0 0.00 0 1,404 1,404 0.44
Blow-Thru Fan 0 0 0.00 0 0 0 0.00
Reserve Cap. 0 0 0.00 0 0 0 0.00
Reheat Cap. 0 0 0.00 0 0 0 0.00
Supply Duct 0 0 0.00 0 0 0 0.00
Return Duct 0 0 0.00 0 0 0 0.00
Misc. Supply 0 0 0.00 0 0 0 0.00
Misc. Return 0 0 0.00 0 0 0 0.00
Building Totals 0 0.00 46,727 272,659 319,386 100.00

Building Sen %Tot Lat Sen Net %Net


Summary Loss Loss Gain Gain Gain Gain
Ventilation 0 0.00 33,738 42,270 76,008 23.80
Infiltration 0 0.00 0 0 0 0.00
Pretreated Air 0 0.00 0 0 0 0.00
Zone Loads 0 0.00 12,989 228,986 241,975 75.76
Plenum Loads 0 0.00 0 0 0 0.00
Fan & Duct Loads 0 0.00 0 1,404 1,404 0.44
Building Totals 0 0.00 46,727 272,659 319,386 100.00

Check Figures
Total Building Supply Air (based on a 11° TD): 18,067 L/s
Total Building Vent. Air (14.35% of Supply): 2,592 L/s
Total Conditioned Air Space: 1,859 Sq.m
Supply Air Per Unit Area: 9.7203 L/s/Sq.m
Area Per Cooling Capacity: 5.8196 Sq.m/kW 20.5 Sq.m/Ton
Cooling Capacity Per Area: 0.1718 kW/Sq.m 0.0489 Tons/Sq.m
Heating Capacity Per Area: 0.00 Watts/Sq.m
Total Heating Required With Outside Air: 0.00 kW
Total Cooling With Outside Air: 319.39 kW 90.82 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 5

Air Handler #1 - Grounf Floor - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.L/s Clg.L/s S.Exh Req.L/s Req.L/s
Volume L/s/Sqm L/s/Sqm W.Exh Act.L/s Act.L/s
1 Ground Floor 429 0 54,212 2,970 None 10/P
4pm February 60 0 4,257 0 0 600
1,372 0.00 9.93 0 0 600
Zone Peak Totals: 429 0 54,212 2,970
Total Zones: 1 60 0 4,257 0 0 600
Unique Zones: 1 1,372 0.00 9.93 0 0 600
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 6

Air Handler #1 - Grounf Floor - Total Load Summary


Air Handler Description: Grounf Floor Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.35 kW
Fan Input: 85% motor and fan efficiency with 0 kPa across the fan
Sensible Heat Ratio: 0.95 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 4pm in February.
Outdoor Conditions: 37° DB, 24° WB, 14.13 grams moisture per kg dry air
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Watts
Infiltration sensible loss: 0 Watts 0 L/s
Outside Air sensible loss: 0 Watts 0 L/s
Supply Duct sensible loss: 0 Watts
Return Duct sensible loss: 0 Watts
Return Plenum sensible loss: 0 Watts
Total System sensible loss: 0 Watts
Heating Supply Air: 0 / (.947 X 1.21 X 0) = 0 L/s
Winter Vent Outside Air (0.0% of supply) = 0 L/s
Zone space sensible gain: 54,212 Watts
Infiltration sensible gain: 0 Watts
Draw-thru fan sensible gain: 331 Watts
Supply duct sensible gain: 0 Watts
Reserve sensible gain: 0 Watts
Total sensible gain on supply side of coil: 54,543 Watts
Cooling Supply Air: 54,543 / (.947 X 1.23 X 11) = 4,257 L/s
Summer Vent Outside Air (14.1% of supply) = 600 L/s
Return duct sensible gain: 0 Watts
Return plenum sensible gain: 0 Watts
Outside air sensible gain: 9,785 Watts 600 L/s
Blow-thru fan sensible gain: 0 Watts
Total sensible gain on return side of coil: 9,785 Watts
Total sensible gain on air handling system: 64,327 Watts
Zone space latent gain: 2,970 Watts
Infiltration latent gain: 0 Watts
Outside air latent gain: 7,809 Watts
Total latent gain on air handling system: 10,779 Watts
Total system sensible and latent gain: 75,107 Watts

Check Figures
Total Air Handler Supply Air (based on a 11° TD): 4,257 L/s
Total Air Handler Vent. Air (14.10% of Supply): 600 L/s
Total Conditioned Air Space: 429 Sq.m
Supply Air Per Unit Area: 9.9283 L/s/Sq.m
Area Per Cooling Capacity: 5.7085 Sq.m/kW 20.1 Sq.m/Ton
Cooling Capacity Per Area: 0.1752 kW/Sq.m 0.0498 Tons/Sq.m
Heating Capacity Per Area: 0.00 Watts/Sq.m
Total Heating Required With Outside Air: 0.00 kW
Total Cooling With Outside Air: 75.11 kW 21.36 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 7

Air Handler #2 - Ground Floor Reception - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.L/s Clg.L/s S.Exh Req.L/s Req.L/s
Volume L/s/Sqm L/s/Sqm W.Exh Act.L/s Act.L/s
Ground Floor
38 0 3,369 347 None 8/P
2 Reception
7 0 265 0 0 56
8pm February
120 0.00 7.05 0 0 56

Zone Peak Totals: 38 0 3,369 347


Total Zones: 1 7 0 265 0 0 56
Unique Zones: 1 120 0.00 7.05 0 0 56
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 8

Air Handler #2 - Ground Floor Reception - Total Load Summary


Air Handler Description: Ground Floor Reception Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.02 kW
Fan Input: 85% motor and fan efficiency with 0 kPa across the fan
Sensible Heat Ratio: 0.91 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 5pm in February.
Outdoor Conditions: 37° DB, 24° WB, 14.45 grams moisture per kg dry air
Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in February at 8pm
is different from the total system peak time, hence the air system L/s was computed using a zone sensible load
of 3,369.
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Watts
Infiltration sensible loss: 0 Watts 0 L/s
Outside Air sensible loss: 0 Watts 0 L/s
Supply Duct sensible loss: 0 Watts
Return Duct sensible loss: 0 Watts
Return Plenum sensible loss: 0 Watts
Total System sensible loss: 0 Watts
Heating Supply Air: 0 / (.947 X 1.21 X 0) = 0 L/s
Winter Vent Outside Air (0.0% of supply) = 0 L/s
Zone space sensible gain: 3,188 Watts
Infiltration sensible gain: 0 Watts
Draw-thru fan sensible gain: 21 Watts
Supply duct sensible gain: 0 Watts
Reserve sensible gain: 0 Watts
Total sensible gain on supply side of coil: 3,208 Watts
Cooling Supply Air: 3,389 / (.947 X 1.23 X 11) = 265 L/s
Summer Vent Outside Air (21.2% of supply) = 56 L/s
Return duct sensible gain: 0 Watts
Return plenum sensible gain: 0 Watts
Outside air sensible gain: 848 Watts 56 L/s
Blow-thru fan sensible gain: 0 Watts
Total sensible gain on return side of coil: 848 Watts
Total sensible gain on air handling system: 4,056 Watts
Zone space latent gain: 347 Watts
Infiltration latent gain: 0 Watts
Outside air latent gain: 729 Watts
Total latent gain on air handling system: 1,075 Watts
Total system sensible and latent gain: 5,132 Watts

Check Figures
Total Air Handler Supply Air (based on a 11° TD): 265 L/s
Total Air Handler Vent. Air (21.17% of Supply): 56 L/s
Total Conditioned Air Space: 38 Sq.m
Supply Air Per Unit Area: 7.0537 L/s/Sq.m
Area Per Cooling Capacity: 7.3074 Sq.m/kW 25.7 Sq.m/Ton
Cooling Capacity Per Area: 0.1368 kW/Sq.m 0.0389 Tons/Sq.m
Heating Capacity Per Area: 0.00 Watts/Sq.m
Total Heating Required With Outside Air: 0.00 kW
Total Cooling With Outside Air: 5.13 kW 1.46 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 9

Air Handler #3 - G. Office - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.L/s Clg.L/s S.Exh Req.L/s Req.L/s
Volume L/s/Sqm L/s/Sqm W.Exh Act.L/s Act.L/s
3 G. Office 4 0 474 20 None 10/P
9pm February 0 0 37 0 0 4
13 0.00 9.19 0 0 4
Zone Peak Totals: 4 0 474 20
Total Zones: 1 0 0 37 0 0 4
Unique Zones: 1 13 0.00 9.19 0 0 4
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 10

Air Handler #3 - G. Office - Total Load Summary


Air Handler Description: G. Office Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.00 kW
Fan Input: 85% motor and fan efficiency with 0 kPa across the fan
Sensible Heat Ratio: 0.96 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 8pm in February.
Outdoor Conditions: 33° DB, 23° WB, 14.57 grams moisture per kg dry air
Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in February at 9pm
is different from the total system peak time, hence the air system L/s was computed using a zone sensible load
of 474.
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Watts
Infiltration sensible loss: 0 Watts 0 L/s
Outside Air sensible loss: 0 Watts 0 L/s
Supply Duct sensible loss: 0 Watts
Return Duct sensible loss: 0 Watts
Return Plenum sensible loss: 0 Watts
Total System sensible loss: 0 Watts
Heating Supply Air: 0 / (.947 X 1.21 X 0) = 0 L/s
Winter Vent Outside Air (0.0% of supply) = 0 L/s
Zone space sensible gain: 469 Watts
Infiltration sensible gain: 0 Watts
Draw-thru fan sensible gain: 3 Watts
Supply duct sensible gain: 0 Watts
Reserve sensible gain: 0 Watts
Total sensible gain on supply side of coil: 472 Watts
Cooling Supply Air: 477 / (.947 X 1.23 X 11) = 37 L/s
Summer Vent Outside Air (10.9% of supply) = 4 L/s
Return duct sensible gain: 0 Watts
Return plenum sensible gain: 0 Watts
Outside air sensible gain: 42 Watts 4 L/s
Blow-thru fan sensible gain: 0 Watts
Total sensible gain on return side of coil: 42 Watts
Total sensible gain on air handling system: 515 Watts
Zone space latent gain: 20 Watts
Infiltration latent gain: 0 Watts
Outside air latent gain: 53 Watts
Total latent gain on air handling system: 73 Watts
Total system sensible and latent gain: 588 Watts

Check Figures
Total Air Handler Supply Air (based on a 11° TD): 37 L/s
Total Air Handler Vent. Air (10.88% of Supply): 4 L/s
Total Conditioned Air Space: 4 Sq.m
Supply Air Per Unit Area: 9.1874 L/s/Sq.m
Area Per Cooling Capacity: 6.8879 Sq.m/kW 24.2 Sq.m/Ton
Cooling Capacity Per Area: 0.1452 kW/Sq.m 0.0413 Tons/Sq.m
Heating Capacity Per Area: 0.00 Watts/Sq.m
Total Heating Required With Outside Air: 0.00 kW
Total Cooling With Outside Air: 0.59 kW 0.17 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 11

Air Handler #4 - First Floor - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.L/s Clg.L/s S.Exh Req.L/s Req.L/s
Volume L/s/Sqm L/s/Sqm W.Exh Act.L/s Act.L/s
4 First Floor 429 0 54,212 2,970 None 10/P
4pm February 60 0 4,257 0 0 600
1,372 0.00 9.93 0 0 600
Zone Peak Totals: 429 0 54,212 2,970
Total Zones: 1 60 0 4,257 0 0 600
Unique Zones: 1 1,372 0.00 9.93 0 0 600
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 12

Air Handler #4 - First Floor - Total Load Summary


Air Handler Description: First Floor Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.35 kW
Fan Input: 85% motor and fan efficiency with 0 kPa across the fan
Sensible Heat Ratio: 0.95 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 4pm in February.
Outdoor Conditions: 37° DB, 24° WB, 14.13 grams moisture per kg dry air
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Watts
Infiltration sensible loss: 0 Watts 0 L/s
Outside Air sensible loss: 0 Watts 0 L/s
Supply Duct sensible loss: 0 Watts
Return Duct sensible loss: 0 Watts
Return Plenum sensible loss: 0 Watts
Total System sensible loss: 0 Watts
Heating Supply Air: 0 / (.947 X 1.21 X 0) = 0 L/s
Winter Vent Outside Air (0.0% of supply) = 0 L/s
Zone space sensible gain: 54,212 Watts
Infiltration sensible gain: 0 Watts
Draw-thru fan sensible gain: 331 Watts
Supply duct sensible gain: 0 Watts
Reserve sensible gain: 0 Watts
Total sensible gain on supply side of coil: 54,543 Watts
Cooling Supply Air: 54,543 / (.947 X 1.23 X 11) = 4,257 L/s
Summer Vent Outside Air (14.1% of supply) = 600 L/s
Return duct sensible gain: 0 Watts
Return plenum sensible gain: 0 Watts
Outside air sensible gain: 9,785 Watts 600 L/s
Blow-thru fan sensible gain: 0 Watts
Total sensible gain on return side of coil: 9,785 Watts
Total sensible gain on air handling system: 64,327 Watts
Zone space latent gain: 2,970 Watts
Infiltration latent gain: 0 Watts
Outside air latent gain: 7,809 Watts
Total latent gain on air handling system: 10,779 Watts
Total system sensible and latent gain: 75,107 Watts

Check Figures
Total Air Handler Supply Air (based on a 11° TD): 4,257 L/s
Total Air Handler Vent. Air (14.10% of Supply): 600 L/s
Total Conditioned Air Space: 429 Sq.m
Supply Air Per Unit Area: 9.9283 L/s/Sq.m
Area Per Cooling Capacity: 5.7085 Sq.m/kW 20.1 Sq.m/Ton
Cooling Capacity Per Area: 0.1752 kW/Sq.m 0.0498 Tons/Sq.m
Heating Capacity Per Area: 0.00 Watts/Sq.m
Total Heating Required With Outside Air: 0.00 kW
Total Cooling With Outside Air: 75.11 kW 21.36 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 13

Air Handler #5 - First Floor Reception - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.L/s Clg.L/s S.Exh Req.L/s Req.L/s
Volume L/s/Sqm L/s/Sqm W.Exh Act.L/s Act.L/s
5 First Floor Reception 30 0 2,537 149 None 8/P
8pm February 3 0 199 0 0 24
96 0.00 6.64 0 0 24
Zone Peak Totals: 30 0 2,537 149
Total Zones: 1 3 0 199 0 0 24
Unique Zones: 1 96 0.00 6.64 0 0 24
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 14

Air Handler #5 - First Floor Reception - Total Load Summary


Air Handler Description: First Floor Reception Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.02 kW
Fan Input: 85% motor and fan efficiency with 0 kPa across the fan
Sensible Heat Ratio: 0.94 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 8pm in February.
Outdoor Conditions: 33° DB, 23° WB, 14.57 grams moisture per kg dry air
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Watts
Infiltration sensible loss: 0 Watts 0 L/s
Outside Air sensible loss: 0 Watts 0 L/s
Supply Duct sensible loss: 0 Watts
Return Duct sensible loss: 0 Watts
Return Plenum sensible loss: 0 Watts
Total System sensible loss: 0 Watts
Heating Supply Air: 0 / (.947 X 1.21 X 0) = 0 L/s
Winter Vent Outside Air (0.0% of supply) = 0 L/s
Zone space sensible gain: 2,537 Watts
Infiltration sensible gain: 0 Watts
Draw-thru fan sensible gain: 15 Watts
Supply duct sensible gain: 0 Watts
Reserve sensible gain: 0 Watts
Total sensible gain on supply side of coil: 2,553 Watts
Cooling Supply Air: 2,553 / (.947 X 1.23 X 11) = 199 L/s
Summer Vent Outside Air (12.0% of supply) = 24 L/s
Return duct sensible gain: 0 Watts
Return plenum sensible gain: 0 Watts
Outside air sensible gain: 252 Watts 24 L/s
Blow-thru fan sensible gain: 0 Watts
Total sensible gain on return side of coil: 252 Watts
Total sensible gain on air handling system: 2,804 Watts
Zone space latent gain: 149 Watts
Infiltration latent gain: 0 Watts
Outside air latent gain: 317 Watts
Total latent gain on air handling system: 465 Watts
Total system sensible and latent gain: 3,269 Watts

Check Figures
Total Air Handler Supply Air (based on a 11° TD): 199 L/s
Total Air Handler Vent. Air (12.05% of Supply): 24 L/s
Total Conditioned Air Space: 30 Sq.m
Supply Air Per Unit Area: 6.6404 L/s/Sq.m
Area Per Cooling Capacity: 9.1762 Sq.m/kW 32.3 Sq.m/Ton
Cooling Capacity Per Area: 0.1090 kW/Sq.m 0.0310 Tons/Sq.m
Heating Capacity Per Area: 0.00 Watts/Sq.m
Total Heating Required With Outside Air: 0.00 kW
Total Cooling With Outside Air: 3.27 kW 0.93 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 15

Air Handler #6 - F. Office - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.L/s Clg.L/s S.Exh Req.L/s Req.L/s
Volume L/s/Sqm L/s/Sqm W.Exh Act.L/s Act.L/s
6 F. Office 4 0 597 99 None 10/P
9pm February 2 0 47 0 0 20
13 0.00 11.57 0 0 20
Zone Peak Totals: 4 0 597 99
Total Zones: 1 2 0 47 0 0 20
Unique Zones: 1 13 0.00 11.57 0 0 20
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 16

Air Handler #6 - F. Office - Total Load Summary


Air Handler Description: F. Office Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.00 kW
Fan Input: 85% motor and fan efficiency with 0 kPa across the fan
Sensible Heat Ratio: 0.86 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 4pm in February.
Outdoor Conditions: 37° DB, 24° WB, 14.13 grams moisture per kg dry air
Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in February at 9pm
is different from the total system peak time, hence the air system L/s was computed using a zone sensible load
of 597.
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Watts
Infiltration sensible loss: 0 Watts 0 L/s
Outside Air sensible loss: 0 Watts 0 L/s
Supply Duct sensible loss: 0 Watts
Return Duct sensible loss: 0 Watts
Return Plenum sensible loss: 0 Watts
Total System sensible loss: 0 Watts
Heating Supply Air: 0 / (.947 X 1.21 X 0) = 0 L/s
Winter Vent Outside Air (0.0% of supply) = 0 L/s
Zone space sensible gain: 548 Watts
Infiltration sensible gain: 0 Watts
Draw-thru fan sensible gain: 4 Watts
Supply duct sensible gain: 0 Watts
Reserve sensible gain: 0 Watts
Total sensible gain on supply side of coil: 552 Watts
Cooling Supply Air: 600 / (.947 X 1.23 X 11) = 47 L/s
Summer Vent Outside Air (42.7% of supply) = 20 L/s
Return duct sensible gain: 0 Watts
Return plenum sensible gain: 0 Watts
Outside air sensible gain: 326 Watts 20 L/s
Blow-thru fan sensible gain: 0 Watts
Total sensible gain on return side of coil: 326 Watts
Total sensible gain on air handling system: 878 Watts
Zone space latent gain: 99 Watts
Infiltration latent gain: 0 Watts
Outside air latent gain: 260 Watts
Total latent gain on air handling system: 359 Watts
Total system sensible and latent gain: 1,238 Watts

Check Figures
Total Air Handler Supply Air (based on a 11° TD): 47 L/s
Total Air Handler Vent. Air (42.69% of Supply): 20 L/s
Total Conditioned Air Space: 4 Sq.m
Supply Air Per Unit Area: 11.5685 L/s/Sq.m
Area Per Cooling Capacity: 3.2726 Sq.m/kW 11.5 Sq.m/Ton
Cooling Capacity Per Area: 0.3056 kW/Sq.m 0.0869 Tons/Sq.m
Heating Capacity Per Area: 0.00 Watts/Sq.m
Total Heating Required With Outside Air: 0.00 kW
Total Cooling With Outside Air: 1.24 kW 0.35 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 17

Air Handler #7 - Second Floor - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.L/s Clg.L/s S.Exh Req.L/s Req.L/s
Volume L/s/Sqm L/s/Sqm W.Exh Act.L/s Act.L/s
7 Second Floor 429 0 54,212 2,970 None 10/P
4pm February 60 0 4,257 0 0 600
1,372 0.00 9.93 0 0 600
Zone Peak Totals: 429 0 54,212 2,970
Total Zones: 1 60 0 4,257 0 0 600
Unique Zones: 1 1,372 0.00 9.93 0 0 600
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 18

Air Handler #7 - Second Floor - Total Load Summary


Air Handler Description: Second Floor Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.35 kW
Fan Input: 85% motor and fan efficiency with 0 kPa across the fan
Sensible Heat Ratio: 0.95 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 4pm in February.
Outdoor Conditions: 37° DB, 24° WB, 14.13 grams moisture per kg dry air
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Watts
Infiltration sensible loss: 0 Watts 0 L/s
Outside Air sensible loss: 0 Watts 0 L/s
Supply Duct sensible loss: 0 Watts
Return Duct sensible loss: 0 Watts
Return Plenum sensible loss: 0 Watts
Total System sensible loss: 0 Watts
Heating Supply Air: 0 / (.947 X 1.21 X 0) = 0 L/s
Winter Vent Outside Air (0.0% of supply) = 0 L/s
Zone space sensible gain: 54,212 Watts
Infiltration sensible gain: 0 Watts
Draw-thru fan sensible gain: 331 Watts
Supply duct sensible gain: 0 Watts
Reserve sensible gain: 0 Watts
Total sensible gain on supply side of coil: 54,543 Watts
Cooling Supply Air: 54,543 / (.947 X 1.23 X 11) = 4,257 L/s
Summer Vent Outside Air (14.1% of supply) = 600 L/s
Return duct sensible gain: 0 Watts
Return plenum sensible gain: 0 Watts
Outside air sensible gain: 9,785 Watts 600 L/s
Blow-thru fan sensible gain: 0 Watts
Total sensible gain on return side of coil: 9,785 Watts
Total sensible gain on air handling system: 64,327 Watts
Zone space latent gain: 2,970 Watts
Infiltration latent gain: 0 Watts
Outside air latent gain: 7,809 Watts
Total latent gain on air handling system: 10,779 Watts
Total system sensible and latent gain: 75,107 Watts

Check Figures
Total Air Handler Supply Air (based on a 11° TD): 4,257 L/s
Total Air Handler Vent. Air (14.10% of Supply): 600 L/s
Total Conditioned Air Space: 429 Sq.m
Supply Air Per Unit Area: 9.9283 L/s/Sq.m
Area Per Cooling Capacity: 5.7085 Sq.m/kW 20.1 Sq.m/Ton
Cooling Capacity Per Area: 0.1752 kW/Sq.m 0.0498 Tons/Sq.m
Heating Capacity Per Area: 0.00 Watts/Sq.m
Total Heating Required With Outside Air: 0.00 kW
Total Cooling With Outside Air: 75.11 kW 21.36 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 19

Air Handler #8 - Second Floor Reception - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.L/s Clg.L/s S.Exh Req.L/s Req.L/s
Volume L/s/Sqm L/s/Sqm W.Exh Act.L/s Act.L/s
Second Floor
30 0 2,537 149 None 8/P
8 Reception
3 0 199 0 0 24
8pm February
96 0.00 6.64 0 0 24

Zone Peak Totals: 30 0 2,537 149


Total Zones: 1 3 0 199 0 0 24
Unique Zones: 1 96 0.00 6.64 0 0 24
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 20

Air Handler #8 - Second Floor Reception - Total Load Summary


Air Handler Description: Second Floor Reception Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.02 kW
Fan Input: 85% motor and fan efficiency with 0 kPa across the fan
Sensible Heat Ratio: 0.94 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 8pm in February.
Outdoor Conditions: 33° DB, 23° WB, 14.57 grams moisture per kg dry air
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Watts
Infiltration sensible loss: 0 Watts 0 L/s
Outside Air sensible loss: 0 Watts 0 L/s
Supply Duct sensible loss: 0 Watts
Return Duct sensible loss: 0 Watts
Return Plenum sensible loss: 0 Watts
Total System sensible loss: 0 Watts
Heating Supply Air: 0 / (.947 X 1.21 X 0) = 0 L/s
Winter Vent Outside Air (0.0% of supply) = 0 L/s
Zone space sensible gain: 2,537 Watts
Infiltration sensible gain: 0 Watts
Draw-thru fan sensible gain: 15 Watts
Supply duct sensible gain: 0 Watts
Reserve sensible gain: 0 Watts
Total sensible gain on supply side of coil: 2,553 Watts
Cooling Supply Air: 2,553 / (.947 X 1.23 X 11) = 199 L/s
Summer Vent Outside Air (12.0% of supply) = 24 L/s
Return duct sensible gain: 0 Watts
Return plenum sensible gain: 0 Watts
Outside air sensible gain: 252 Watts 24 L/s
Blow-thru fan sensible gain: 0 Watts
Total sensible gain on return side of coil: 252 Watts
Total sensible gain on air handling system: 2,804 Watts
Zone space latent gain: 149 Watts
Infiltration latent gain: 0 Watts
Outside air latent gain: 317 Watts
Total latent gain on air handling system: 465 Watts
Total system sensible and latent gain: 3,269 Watts

Check Figures
Total Air Handler Supply Air (based on a 11° TD): 199 L/s
Total Air Handler Vent. Air (12.05% of Supply): 24 L/s
Total Conditioned Air Space: 30 Sq.m
Supply Air Per Unit Area: 6.6404 L/s/Sq.m
Area Per Cooling Capacity: 9.1762 Sq.m/kW 32.3 Sq.m/Ton
Cooling Capacity Per Area: 0.1090 kW/Sq.m 0.0310 Tons/Sq.m
Heating Capacity Per Area: 0.00 Watts/Sq.m
Total Heating Required With Outside Air: 0.00 kW
Total Cooling With Outside Air: 3.27 kW 0.93 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 21

Air Handler #9 - S. Office - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.L/s Clg.L/s S.Exh Req.L/s Req.L/s
Volume L/s/Sqm L/s/Sqm W.Exh Act.L/s Act.L/s
9 S. Office 4 0 597 99 None 10/P
9pm February 2 0 47 0 0 20
13 0.00 11.57 0 0 20
Zone Peak Totals: 4 0 597 99
Total Zones: 1 2 0 47 0 0 20
Unique Zones: 1 13 0.00 11.57 0 0 20
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 22

Air Handler #9 - S. Office - Total Load Summary


Air Handler Description: S. Office Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.00 kW
Fan Input: 85% motor and fan efficiency with 0 kPa across the fan
Sensible Heat Ratio: 0.86 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 4pm in February.
Outdoor Conditions: 37° DB, 24° WB, 14.13 grams moisture per kg dry air
Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in February at 9pm
is different from the total system peak time, hence the air system L/s was computed using a zone sensible load
of 597.
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Watts
Infiltration sensible loss: 0 Watts 0 L/s
Outside Air sensible loss: 0 Watts 0 L/s
Supply Duct sensible loss: 0 Watts
Return Duct sensible loss: 0 Watts
Return Plenum sensible loss: 0 Watts
Total System sensible loss: 0 Watts
Heating Supply Air: 0 / (.947 X 1.21 X 0) = 0 L/s
Winter Vent Outside Air (0.0% of supply) = 0 L/s
Zone space sensible gain: 548 Watts
Infiltration sensible gain: 0 Watts
Draw-thru fan sensible gain: 4 Watts
Supply duct sensible gain: 0 Watts
Reserve sensible gain: 0 Watts
Total sensible gain on supply side of coil: 552 Watts
Cooling Supply Air: 600 / (.947 X 1.23 X 11) = 47 L/s
Summer Vent Outside Air (42.7% of supply) = 20 L/s
Return duct sensible gain: 0 Watts
Return plenum sensible gain: 0 Watts
Outside air sensible gain: 326 Watts 20 L/s
Blow-thru fan sensible gain: 0 Watts
Total sensible gain on return side of coil: 326 Watts
Total sensible gain on air handling system: 878 Watts
Zone space latent gain: 99 Watts
Infiltration latent gain: 0 Watts
Outside air latent gain: 260 Watts
Total latent gain on air handling system: 359 Watts
Total system sensible and latent gain: 1,238 Watts

Check Figures
Total Air Handler Supply Air (based on a 11° TD): 47 L/s
Total Air Handler Vent. Air (42.69% of Supply): 20 L/s
Total Conditioned Air Space: 4 Sq.m
Supply Air Per Unit Area: 11.5685 L/s/Sq.m
Area Per Cooling Capacity: 3.2726 Sq.m/kW 11.5 Sq.m/Ton
Cooling Capacity Per Area: 0.3056 kW/Sq.m 0.0869 Tons/Sq.m
Heating Capacity Per Area: 0.00 Watts/Sq.m
Total Heating Required With Outside Air: 0.00 kW
Total Cooling With Outside Air: 1.24 kW 0.35 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 23

Air Handler #10 - Third Floor - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.L/s Clg.L/s S.Exh Req.L/s Req.L/s
Volume L/s/Sqm L/s/Sqm W.Exh Act.L/s Act.L/s
10 Third Floor 429 0 54,212 2,970 None 10/P
4pm February 60 0 4,257 0 0 600
1,372 0.00 9.93 0 0 600
Zone Peak Totals: 429 0 54,212 2,970
Total Zones: 1 60 0 4,257 0 0 600
Unique Zones: 1 1,372 0.00 9.93 0 0 600
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 24

Air Handler #10 - Third Floor - Total Load Summary


Air Handler Description: Third Floor Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.35 kW
Fan Input: 85% motor and fan efficiency with 0 kPa across the fan
Sensible Heat Ratio: 0.95 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 4pm in February.
Outdoor Conditions: 37° DB, 24° WB, 14.13 grams moisture per kg dry air
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Watts
Infiltration sensible loss: 0 Watts 0 L/s
Outside Air sensible loss: 0 Watts 0 L/s
Supply Duct sensible loss: 0 Watts
Return Duct sensible loss: 0 Watts
Return Plenum sensible loss: 0 Watts
Total System sensible loss: 0 Watts
Heating Supply Air: 0 / (.947 X 1.21 X 0) = 0 L/s
Winter Vent Outside Air (0.0% of supply) = 0 L/s
Zone space sensible gain: 54,212 Watts
Infiltration sensible gain: 0 Watts
Draw-thru fan sensible gain: 331 Watts
Supply duct sensible gain: 0 Watts
Reserve sensible gain: 0 Watts
Total sensible gain on supply side of coil: 54,543 Watts
Cooling Supply Air: 54,543 / (.947 X 1.23 X 11) = 4,257 L/s
Summer Vent Outside Air (14.1% of supply) = 600 L/s
Return duct sensible gain: 0 Watts
Return plenum sensible gain: 0 Watts
Outside air sensible gain: 9,785 Watts 600 L/s
Blow-thru fan sensible gain: 0 Watts
Total sensible gain on return side of coil: 9,785 Watts
Total sensible gain on air handling system: 64,327 Watts
Zone space latent gain: 2,970 Watts
Infiltration latent gain: 0 Watts
Outside air latent gain: 7,809 Watts
Total latent gain on air handling system: 10,779 Watts
Total system sensible and latent gain: 75,107 Watts

Check Figures
Total Air Handler Supply Air (based on a 11° TD): 4,257 L/s
Total Air Handler Vent. Air (14.10% of Supply): 600 L/s
Total Conditioned Air Space: 429 Sq.m
Supply Air Per Unit Area: 9.9283 L/s/Sq.m
Area Per Cooling Capacity: 5.7085 Sq.m/kW 20.1 Sq.m/Ton
Cooling Capacity Per Area: 0.1752 kW/Sq.m 0.0498 Tons/Sq.m
Heating Capacity Per Area: 0.00 Watts/Sq.m
Total Heating Required With Outside Air: 0.00 kW
Total Cooling With Outside Air: 75.11 kW 21.36 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 25

Air Handler #11 - Third Floor Reception - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.L/s Clg.L/s S.Exh Req.L/s Req.L/s
Volume L/s/Sqm L/s/Sqm W.Exh Act.L/s Act.L/s
11 Third Floor Reception 30 0 2,537 149 None 8/P
8pm February 3 0 199 0 0 24
96 0.00 6.64 0 0 24
Zone Peak Totals: 30 0 2,537 149
Total Zones: 1 3 0 199 0 0 24
Unique Zones: 1 96 0.00 6.64 0 0 24
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 26

Air Handler #11 - Third Floor Reception - Total Load Summary


Air Handler Description: Third Floor Reception Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.02 kW
Fan Input: 85% motor and fan efficiency with 0 kPa across the fan
Sensible Heat Ratio: 0.94 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 8pm in February.
Outdoor Conditions: 33° DB, 23° WB, 14.57 grams moisture per kg dry air
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Watts
Infiltration sensible loss: 0 Watts 0 L/s
Outside Air sensible loss: 0 Watts 0 L/s
Supply Duct sensible loss: 0 Watts
Return Duct sensible loss: 0 Watts
Return Plenum sensible loss: 0 Watts
Total System sensible loss: 0 Watts
Heating Supply Air: 0 / (.947 X 1.21 X 0) = 0 L/s
Winter Vent Outside Air (0.0% of supply) = 0 L/s
Zone space sensible gain: 2,537 Watts
Infiltration sensible gain: 0 Watts
Draw-thru fan sensible gain: 15 Watts
Supply duct sensible gain: 0 Watts
Reserve sensible gain: 0 Watts
Total sensible gain on supply side of coil: 2,553 Watts
Cooling Supply Air: 2,553 / (.947 X 1.23 X 11) = 199 L/s
Summer Vent Outside Air (12.0% of supply) = 24 L/s
Return duct sensible gain: 0 Watts
Return plenum sensible gain: 0 Watts
Outside air sensible gain: 252 Watts 24 L/s
Blow-thru fan sensible gain: 0 Watts
Total sensible gain on return side of coil: 252 Watts
Total sensible gain on air handling system: 2,804 Watts
Zone space latent gain: 149 Watts
Infiltration latent gain: 0 Watts
Outside air latent gain: 317 Watts
Total latent gain on air handling system: 465 Watts
Total system sensible and latent gain: 3,269 Watts

Check Figures
Total Air Handler Supply Air (based on a 11° TD): 199 L/s
Total Air Handler Vent. Air (12.05% of Supply): 24 L/s
Total Conditioned Air Space: 30 Sq.m
Supply Air Per Unit Area: 6.6404 L/s/Sq.m
Area Per Cooling Capacity: 9.1762 Sq.m/kW 32.3 Sq.m/Ton
Cooling Capacity Per Area: 0.1090 kW/Sq.m 0.0310 Tons/Sq.m
Heating Capacity Per Area: 0.00 Watts/Sq.m
Total Heating Required With Outside Air: 0.00 kW
Total Cooling With Outside Air: 3.27 kW 0.93 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 27

Air Handler #12 - T. Office - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.L/s Clg.L/s S.Exh Req.L/s Req.L/s
Volume L/s/Sqm L/s/Sqm W.Exh Act.L/s Act.L/s
12 T. Office 4 0 597 99 None 10/P
9pm February 2 0 47 0 0 20
13 0.00 11.57 0 0 20
Zone Peak Totals: 4 0 597 99
Total Zones: 1 2 0 47 0 0 20
Unique Zones: 1 13 0.00 11.57 0 0 20
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 28

Air Handler #12 - T. Office - Total Load Summary


Air Handler Description: T. Office Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.00 kW
Fan Input: 85% motor and fan efficiency with 0 kPa across the fan
Sensible Heat Ratio: 0.86 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 4pm in February.
Outdoor Conditions: 37° DB, 24° WB, 14.13 grams moisture per kg dry air
Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in February at 9pm
is different from the total system peak time, hence the air system L/s was computed using a zone sensible load
of 597.
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Watts
Infiltration sensible loss: 0 Watts 0 L/s
Outside Air sensible loss: 0 Watts 0 L/s
Supply Duct sensible loss: 0 Watts
Return Duct sensible loss: 0 Watts
Return Plenum sensible loss: 0 Watts
Total System sensible loss: 0 Watts
Heating Supply Air: 0 / (.947 X 1.21 X 0) = 0 L/s
Winter Vent Outside Air (0.0% of supply) = 0 L/s
Zone space sensible gain: 548 Watts
Infiltration sensible gain: 0 Watts
Draw-thru fan sensible gain: 4 Watts
Supply duct sensible gain: 0 Watts
Reserve sensible gain: 0 Watts
Total sensible gain on supply side of coil: 552 Watts
Cooling Supply Air: 600 / (.947 X 1.23 X 11) = 47 L/s
Summer Vent Outside Air (42.7% of supply) = 20 L/s
Return duct sensible gain: 0 Watts
Return plenum sensible gain: 0 Watts
Outside air sensible gain: 326 Watts 20 L/s
Blow-thru fan sensible gain: 0 Watts
Total sensible gain on return side of coil: 326 Watts
Total sensible gain on air handling system: 878 Watts
Zone space latent gain: 99 Watts
Infiltration latent gain: 0 Watts
Outside air latent gain: 260 Watts
Total latent gain on air handling system: 359 Watts
Total system sensible and latent gain: 1,238 Watts

Check Figures
Total Air Handler Supply Air (based on a 11° TD): 47 L/s
Total Air Handler Vent. Air (42.69% of Supply): 20 L/s
Total Conditioned Air Space: 4 Sq.m
Supply Air Per Unit Area: 11.5685 L/s/Sq.m
Area Per Cooling Capacity: 3.2726 Sq.m/kW 11.5 Sq.m/Ton
Cooling Capacity Per Area: 0.3056 kW/Sq.m 0.0869 Tons/Sq.m
Heating Capacity Per Area: 0.00 Watts/Sq.m
Total Heating Required With Outside Air: 0.00 kW
Total Cooling With Outside Air: 1.24 kW 0.35 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 29

Zone Detailed Loads (At Zone Peak Times)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 1-Ground Floor peaks (sensible) in February at 4pm, Air Handler 1 (Grounf Floor), Group
0, 24.5 x 17.5, Construction Type: 1 (Light)
Roof-1-8-No.Clg-L 429 0.50 14.9 1.200 7,660 21.333 9,147
Wall-1-N-A-D 27 1 7.9 0.500 107 8.889 242
Wall-2-E-A-D 28 1 16.9 0.500 235 8.889 247
Wall-3-E-A-D 34 1 16.9 0.500 284 8.889 299
Wall-4-S-A-D 78 1 13.1 0.500 515 8.889 697
Wall-5-W-A-D 45 1 13.9 0.500 311 8.889 398
Wall-6-W-A-D 38 1 13.9 0.500 267 8.889 341
Gls-E-1-90-Tran 51.2 1.000 12 3.700 2,252 69.333 3,550
0%S-0-WS-Solar 51.2 0.550 760 0.170 3,638
Gls-N-1-90-Tran 51.2 1.000 12 3.700 2,252 69.333 3,550
0%S-0-WS-Solar 51.2 0.550 110 0.750 2,323
Gls-W-1-90-Tran 32.0 1.000 12 3.700 1,408 69.333 2,219
0%S-0-WS-Solar 32.0 0.550 760 0.820 10,968
Lights-Prof=1 8,575 1.000 8,575
Equipment-Prof=1 4,288 1.000 4,288 0
People-Prof=1 60.0 1.000 4,200 2,700
Sub-total 49,284 2,700 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 54,212 2,970 0

Zone 2-Ground Floor Reception peaks (sensible) in February at 8pm, Air Handler 2 (Ground
Floor Reception), Group 0, 5.0 x 7.5, Construction Type: 1 (Light)
Roof-1-8-No.Clg-L 38 0.50 18.9 1.200 850 21.333 800
Wall-1-N-A-D 16 1 8.9 0.500 71 8.889 142
Wall-2-E-A-D 24 1 17.9 0.500 215 8.889 213
Wall-3-S-A-D 16 1 15.1 0.500 121 8.889 142
Wall-4-W-A-D 24 1 15.9 0.500 191 8.889 213
Lights-Prof=1 750 1.000 750
Equipment-Prof=1 375 1.000 375 0
People-Prof=1 7.0 1.000 490 315
Sub-total 3,063 315 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 3,369 347 0

Zone 3-G. Office peaks (sensible) in February at 9pm, Air Handler 3 (G. Office), Group 0, 2.7 x
1.5, Construction Type: 1 (Light)
Roof-1-8-No.Clg-L 4 0.50 18.4 1.200 89 21.333 86
Wall-1-N-A-D 9 1 8.9 0.500 38 8.889 77
Wall-2-E-A-D 5 1 17.9 0.500 43 8.889 43
Wall-3-S-A-D 9 1 16.1 0.500 70 8.889 77
Wall-4-W-A-D 5 1 16.9 0.500 41 8.889 43
Lights-Prof=1 81 1.000 81
Equipment-Prof=1 41 1.000 41 0
People-Prof=1 0.4 1.000 28 18
Sub-total 431 18 0
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 30

Zone Detailed Loads (At Zone Peak Times) (cont'd)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 474 20 0

Zone 4-First Floor peaks (sensible) in February at 4pm, Air Handler 4 (First Floor), Group 0,
24.5 x 17.5, Construction Type: 1 (Light)
Roof-1-8-No.Clg-L 429 0.50 14.9 1.200 7,660 21.333 9,147
Wall-1-N-A-D 27 1 7.9 0.500 107 8.889 242
Wall-2-E-A-D 28 1 16.9 0.500 235 8.889 247
Wall-3-E-A-D 34 1 16.9 0.500 284 8.889 299
Wall-4-S-A-D 78 1 13.1 0.500 515 8.889 697
Wall-5-W-A-D 45 1 13.9 0.500 311 8.889 398
Wall-6-W-A-D 38 1 13.9 0.500 267 8.889 341
Gls-E-1-90-Tran 51.2 1.000 12 3.700 2,252 69.333 3,550
0%S-0-WS-Solar 51.2 0.550 760 0.170 3,638
Gls-N-1-90-Tran 51.2 1.000 12 3.700 2,252 69.333 3,550
0%S-0-WS-Solar 51.2 0.550 110 0.750 2,323
Gls-W-1-90-Tran 32.0 1.000 12 3.700 1,408 69.333 2,219
0%S-0-WS-Solar 32.0 0.550 760 0.820 10,968
Lights-Prof=1 8,575 1.000 8,575
Equipment-Prof=1 4,288 1.000 4,288 0
People-Prof=1 60.0 1.000 4,200 2,700
Sub-total 49,284 2,700 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 54,212 2,970 0

Zone 5-First Floor Reception peaks (sensible) in February at 8pm, Air Handler 5 (First Floor
Reception), Group 0, 5.0 x 6.0, Construction Type: 1 (Light)
Roof-1-8-No.Clg-L 30 0.50 18.9 1.200 680 21.333 640
Wall-1-N-A-D 16 1 8.9 0.500 71 8.889 142
Wall-2-E-A-D 19 1 17.9 0.500 172 8.889 171
Wall-3-S-A-D 16 1 15.1 0.500 121 8.889 142
Wall-4-W-A-D 19 1 15.9 0.500 153 8.889 171
Lights-Prof=1 600 1.000 600
Equipment-Prof=1 300 1.000 300 0
People-Prof=1 3.0 1.000 210 135
Sub-total 2,306 135 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 2,537 149 0

Zone 6-F. Office peaks (sensible) in February at 9pm, Air Handler 6 (F. Office), Group 0, 2.7 x
1.5, Construction Type: 1 (Light)
Roof-1-8-No.Clg-L 4 0.50 18.4 1.200 89 21.333 86
Wall-1-N-A-D 9 1 8.9 0.500 38 8.889 77
Wall-2-E-A-D 5 1 17.9 0.500 43 8.889 43
Wall-3-S-A-D 9 1 16.1 0.500 70 8.889 77
Wall-4-W-A-D 5 1 16.9 0.500 41 8.889 43
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 31

Zone Detailed Loads (At Zone Peak Times) (cont'd)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Lights-Prof=1 81 1.000 81
Equipment-Prof=1 41 1.000 41 0
People-Prof=1 2.0 1.000 140 90
Sub-total 542 90 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 597 99 0

Zone 7-Second Floor peaks (sensible) in February at 4pm, Air Handler 7 (Second Floor), Group
0, 24.5 x 17.5, Construction Type: 1 (Light)
Roof-1-8-No.Clg-L 429 0.50 14.9 1.200 7,660 21.333 9,147
Wall-1-N-A-D 27 1 7.9 0.500 107 8.889 242
Wall-2-E-A-D 28 1 16.9 0.500 235 8.889 247
Wall-3-E-A-D 34 1 16.9 0.500 284 8.889 299
Wall-4-S-A-D 78 1 13.1 0.500 515 8.889 697
Wall-5-W-A-D 45 1 13.9 0.500 311 8.889 398
Wall-6-W-A-D 38 1 13.9 0.500 267 8.889 341
Gls-E-1-90-Tran 51.2 1.000 12 3.700 2,252 69.333 3,550
0%S-0-WS-Solar 51.2 0.550 760 0.170 3,638
Gls-N-1-90-Tran 51.2 1.000 12 3.700 2,252 69.333 3,550
0%S-0-WS-Solar 51.2 0.550 110 0.750 2,323
Gls-W-1-90-Tran 32.0 1.000 12 3.700 1,408 69.333 2,219
0%S-0-WS-Solar 32.0 0.550 760 0.820 10,968
Lights-Prof=1 8,575 1.000 8,575
Equipment-Prof=1 4,288 1.000 4,288 0
People-Prof=1 60.0 1.000 4,200 2,700
Sub-total 49,284 2,700 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 54,212 2,970 0

Zone 8-Second Floor Reception peaks (sensible) in February at 8pm, Air Handler 8 (Second
Floor Reception), Group 0, 5.0 x 6.0, Construction Type: 1 (Light)
Roof-1-8-No.Clg-L 30 0.50 18.9 1.200 680 21.333 640
Wall-1-N-A-D 16 1 8.9 0.500 71 8.889 142
Wall-2-E-A-D 19 1 17.9 0.500 172 8.889 171
Wall-3-S-A-D 16 1 15.1 0.500 121 8.889 142
Wall-4-W-A-D 19 1 15.9 0.500 153 8.889 171
Lights-Prof=1 600 1.000 600
Equipment-Prof=1 300 1.000 300 0
People-Prof=1 3.0 1.000 210 135
Sub-total 2,306 135 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 2,537 149 0

Zone 9-S. Office peaks (sensible) in February at 9pm, Air Handler 9 (S. Office), Group 0, 2.7 x
1.5, Construction Type: 1 (Light)
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 32

Zone Detailed Loads (At Zone Peak Times) (cont'd)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Roof-1-8-No.Clg-L 4 0.50 18.4 1.200 89 21.333 86
Wall-1-N-A-D 9 1 8.9 0.500 38 8.889 77
Wall-2-E-A-D 5 1 17.9 0.500 43 8.889 43
Wall-3-S-A-D 9 1 16.1 0.500 70 8.889 77
Wall-4-W-A-D 5 1 16.9 0.500 41 8.889 43
Lights-Prof=1 81 1.000 81
Equipment-Prof=1 41 1.000 41 0
People-Prof=1 2.0 1.000 140 90
Sub-total 542 90 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 597 99 0

Zone 10-Third Floor peaks (sensible) in February at 4pm, Air Handler 10 (Third Floor), Group 0,
24.5 x 17.5, Construction Type: 1 (Light)
Roof-1-8-No.Clg-L 429 0.50 14.9 1.200 7,660 21.333 9,147
Wall-1-N-A-D 27 1 7.9 0.500 107 8.889 242
Wall-2-E-A-D 28 1 16.9 0.500 235 8.889 247
Wall-3-E-A-D 34 1 16.9 0.500 284 8.889 299
Wall-4-S-A-D 78 1 13.1 0.500 515 8.889 697
Wall-5-W-A-D 45 1 13.9 0.500 311 8.889 398
Wall-6-W-A-D 38 1 13.9 0.500 267 8.889 341
Gls-E-1-90-Tran 51.2 1.000 12 3.700 2,252 69.333 3,550
0%S-0-WS-Solar 51.2 0.550 760 0.170 3,638
Gls-N-1-90-Tran 51.2 1.000 12 3.700 2,252 69.333 3,550
0%S-0-WS-Solar 51.2 0.550 110 0.750 2,323
Gls-W-1-90-Tran 32.0 1.000 12 3.700 1,408 69.333 2,219
0%S-0-WS-Solar 32.0 0.550 760 0.820 10,968
Lights-Prof=1 8,575 1.000 8,575
Equipment-Prof=1 4,288 1.000 4,288 0
People-Prof=1 60.0 1.000 4,200 2,700
Sub-total 49,284 2,700 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 54,212 2,970 0

Zone 11-Third Floor Reception peaks (sensible) in February at 8pm, Air Handler 11 (Third Floor
Reception), Group 0, 5.0 x 6.0, Construction Type: 1 (Light)
Roof-1-8-No.Clg-L 30 0.50 18.9 1.200 680 21.333 640
Wall-1-N-A-D 16 1 8.9 0.500 71 8.889 142
Wall-2-E-A-D 19 1 17.9 0.500 172 8.889 171
Wall-3-S-A-D 16 1 15.1 0.500 121 8.889 142
Wall-4-W-A-D 19 1 15.9 0.500 153 8.889 171
Lights-Prof=1 600 1.000 600
Equipment-Prof=1 300 1.000 300 0
People-Prof=1 3.0 1.000 210 135
Sub-total 2,306 135 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 2,537 149 0
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Eng. Yassir A. A. El.Bukhari Telecommunication Building
Page 33

Zone Detailed Loads (At Zone Peak Times) (cont'd)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss

Zone 12-T. Office peaks (sensible) in February at 9pm, Air Handler 12 (T. Office), Group 0, 2.7 x
1.5, Construction Type: 1 (Light)
Roof-1-8-No.Clg-L 4 0.50 18.4 1.200 89 21.333 86
Wall-1-N-A-D 9 1 8.9 0.500 38 8.889 77
Wall-2-E-A-D 5 1 17.9 0.500 43 8.889 43
Wall-3-S-A-D 9 1 16.1 0.500 70 8.889 77
Wall-4-W-A-D 5 1 16.9 0.500 41 8.889 43
Lights-Prof=1 81 1.000 81
Equipment-Prof=1 41 1.000 41 0
People-Prof=1 2.0 1.000 140 90
Sub-total 542 90 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 597 99 0