Академический Документы
Профессиональный Документы
Культура Документы
1
shown in Figure 1. Example Of CT Saturation
S2
Io
S1
Iom in
Ir
Figure 1
The typical two slope differential
characteristic used provides a minimum Figure 2
pickup level defined as Iomin for It can be seen in Figure 2 the primary
conditions where bus loading is low, current sine waveform is distorted for
then a Ir area under slope S1 where several cycles . This error in secondary
typical bus loading occurs. This slope current can create an Io quantity for an
allows for some error from the CTs external fault and a false bus trip as a
during normal load conditions. Finally consequence.
the characteristic provides a S2 slope to Various techniques are used to detect CT
allow for CT errors during fault saturation to block the bus relay from
conditions near the bus. false tripping.
In summary, therefore, any factors that
may cause improper transformations of DC Current Offset
the primary bus currents can cause the Io
quantity to cross into the trip region It can be seen that in Figure 2 that DC
above the S1-S2 slope lines. offset can accommodate CT saturation .
This DC offset can occur on the CT
CT Saturation secondary even if saturation does not
If a CT is subjected to currents on the occur. Some bus protection relays use
primary side that cause the secondary software techniques to reduce or remove
currents to saturate, these secondary the DC offset by use of filtering.
currents will not be representative of the Introduction of a filter may however
primary currents and therefore could introduce current phase shifts and time
cause improper differential operation. delays in recreating the currents.
An example of CT saturation is shown in
Figure 2.
The Delta Phase Dot Product
Technique
2
currents, a decision can be made if a opposite. If a fault is internal to a
fault is external or internal to the protected zone, the current phasors will
protected bus zone. By comparing phase be approximately in phase.
currents in near real time, a comparison Comparing the phase angles of the
can be made between currents that are currents at every sample point of time
entering the bus and those currents that allows the slope characteristic algorithm
are leaving the bus. If little CT saturation to be supervised by the delta phase
occurs, for an internal bus fault phase function. This technique works because
angle currents will be nearly in phase current phasors that are heavily saturated
while for an external fault, one or more have DC offset or are otherwise distorted
phase angles of the currents will be near in magnitude will still retain their correct
180 degrees from the other currents. phase angle relationships. This
This is intuitively true as well since information can then be used to provide
Kirchoff’s law also applies to phase correct operation of the overall
angles as well as to current magnitudes. differential protection by supervising the
The phase angle comparison is used in slope characteristic. The phase angle
conjunction with a slope characteristic difference for discrimination of fault/no
The key challenge in the delta phase fault conditions is fixed at 90 degrees, so
technique is to rapidly measure phase if all current phasors are within less than
angle between all current phase angles. 90 degrees from each other, slope
In the technique utilized, the DOT tripping is allowed. If the measured
PRODUCT is calculated between input current phasors are within an angle
phase currents. If A and B are vectors, greater than 90 degrees, this is
the DOT product of A*B = AB Cos recognized as an external fault and
theta where A and B are scalars and tripping is blocked. If only one current
theta is the angle between the vectors. input is present, tripping will be
The DOT product of vectors A and B permitted if the slope characteristic
where A= a1 + j a2 operates. The delta phase logic is shown
in Figure 3 & 4 showing three inputs
And B= b1 + j b2 from elements connected to the
A * B = a1 b1 + a2 b2 ----Eq. 1 protected bus zone.
The calculation of the current phase
The calculation of A*B using Eq.1 has angles is done for every time that the
the advantage in that the Cosine function current vectors are measured. Relays
does not need to be used. typically sample waveforms from 32 to
Implementation of a trig function is a 96 samples per cycle and current vectors
laborious process when done by a for protection purposes are typically
microprocessor, whereas multiplication calculated every 2 ms or so.
and summation is easy to do with small
resource requirement.
The delta phase algorithm looks at the
phase angles of each of the similar phase
currents to determine their phase
relationships. If a fault is external to the
protected zone for instance, the phase
angles will be approximately equal and
3
Current Vectors For No Fault product is negative, the coincidence
In Protected Zone angle is greater than 90 degrees.
I1 It should be noted that if the
protected zone has only one source
Angle > 90 degrees connected to it, a phase comparison
cannot be made. At least two current
vectors are required to make a phase
I2 angle decision. If only one current
I3 vector is available, the phase angle
Phase angles between currents
control defaults to a trip condition. In
Greater than 90 degrees, delta those cases, the slope characteristic
Phase BLOCKS differential trip.
is the only logic that is used. Also, if
Figure 3 input currents are too low to be
measured accurately, these vector
Current Vectors For Fault In currents are not used. The
Protected Zone measurement of phase angle can
typically be done down to 0.05 A for
Angle < 90 degrees a 1 A nominal input relay, or .25 A
for a 5 A relay.
4
In applying any differential It can be seen from this example, that the
protection, it is important to phase angles of the three input A phase
determine that wiring connections currents are 180 degrees from each other
and connection settings are made with currents 2 and 3 in phase and these
correctly. This can be done during 180 degrees out of phase with current 1.
the commissioning by viewing the
metering screen on the relay Internal B Phase Fault
metering screens. If current
magnitude errors are present in the
initial installation, the slope Input 1
characteristic will operate and can B Phase
annunciate a high MISMATCH
indication to draw attention to the
fact that something is amiss. Input 2
Tripping will largely be prevented B Phase
even in this condition if no actual
fault on the protected zone is present.
Figure 6
A ph
Input 1 Figure 6 displays an internal B phase bus
fault . It can be seen that even though
Input 1 has a DC offset amount, the
phase angles of the input currents come
A ph close to coinciding.
Input 2
Application To Device 87N
5
can be used to measure the individual 4. Use of the Dot phase angle
phase currents. comparison can compliment the
slope characteristic in that it can
Observations Of The Use Of The Dot provide a zone checking function to
Product For Bus Protection prevent false relay trips that might
Enhancement otherwise take place because of
wiring or application errors.
The Dot product phase angle comparison
of current inputs for a bus has been
verified through hundreds of tests using
the RTDS simulator. In fact, the phase
angle comparator has shown to be
equally effective when used with
differential protection for other
applications such as transformer
protection as well.
The use of the phase angle comparison
along with the slope detection method in
combination has proven to be a very
stable combination especially for
external faults where severe input
current saturation or DC offsets can
occur.