Вы находитесь на странице: 1из 6

Reprinted from conference "Power System Protection and Automation", December 2010, New Delhi, India.

Secured Busbar Differential Protection Using A


Computationally Efficient Dot Product Technique
Krish Narendra, ERLPhase Power Technologies
Dave Fedirchuk, ERLPhase Power Technologies

the large primary currents into 1A or 5A


Abstract nominal values that can be handled by
protective relays.
The use of low impedance bus The traditional approach to measure
differential protection has increased over differential currents is to sum the vector
the recent years because of its versatility quantities. This sum is typically called
and cost effectiveness. an Operating current, Io. If this
Low impedance bus differential schemes measurement is done accurately, the Io
can take advantage of the use of current current vector summation should be
transformers that can also be used for zero. In practice, however, the primary
other protections. Use of low impedance currents measured by current
bus protection also has some issues that transformers can result in secondary
must be overcome such as current currents supplied to protective
transformer saturation and DC current differential protections that is affected
offsets that must be considered in the by factors such as:
differential calculations. This paper 1. CT errors during loading and
discusses one way that these nuisance during nearby faults.
error quantities can be controlled. Use of 2. CT errors due to CT saturation.
phase angle measurement between 3. CT errors due to DC offsets
current inputs of a bus protection scheme 4. CT ratio, setting and wiring
is presented here using an efficient Dot errors.
Product Technique. CT saturations or can be affected on
a steady state basis due to CT design
errors. The traditional way that
Introduction
differential relays were made to be
Low impedance bus differential
more secure, has been to sum the
protection takes advantage of Kirchoff’s
arithmetic sum of the input currents
law in that the sum of current flow into a
to provide a restraint quantity , often
zone of protection must balance. The
called an Ir quantity. In addition, the
balance needs to include current
Ir quantity is typically the arithmetic
magnitude as well as angle . The
current summation divided by two.
resultant vector additions must therefore
The resulting Io and Ir quantities are
sum to zero for a protection zone in
then arranged in a configuration as is
which no fault is present.
Currents flowing into and out from a
protection zone are measured using
current transformers that provide
electrical isolation and effectively reduce

1
shown in Figure 1. Example Of CT Saturation

TYPICAL TWO SLOPE CHARACTERISTIC

S2
Io
S1
Iom in

Ir

Figure 1
The typical two slope differential
characteristic used provides a minimum Figure 2
pickup level defined as Iomin for It can be seen in Figure 2 the primary
conditions where bus loading is low, current sine waveform is distorted for
then a Ir area under slope S1 where several cycles . This error in secondary
typical bus loading occurs. This slope current can create an Io quantity for an
allows for some error from the CTs external fault and a false bus trip as a
during normal load conditions. Finally consequence.
the characteristic provides a S2 slope to Various techniques are used to detect CT
allow for CT errors during fault saturation to block the bus relay from
conditions near the bus. false tripping.
In summary, therefore, any factors that
may cause improper transformations of DC Current Offset
the primary bus currents can cause the Io
quantity to cross into the trip region It can be seen that in Figure 2 that DC
above the S1-S2 slope lines. offset can accommodate CT saturation .
This DC offset can occur on the CT
CT Saturation secondary even if saturation does not
If a CT is subjected to currents on the occur. Some bus protection relays use
primary side that cause the secondary software techniques to reduce or remove
currents to saturate, these secondary the DC offset by use of filtering.
currents will not be representative of the Introduction of a filter may however
primary currents and therefore could introduce current phase shifts and time
cause improper differential operation. delays in recreating the currents.
An example of CT saturation is shown in
Figure 2.
The Delta Phase Dot Product
Technique

It was observed that, to a large degree,


preservation of current phase angle will
always take place even if CT saturation
or DC offset conditions occur. As a
result, if the phase angle of the current
waveforms is compared with phase
angles of each of the bus element

2
currents, a decision can be made if a opposite. If a fault is internal to a
fault is external or internal to the protected zone, the current phasors will
protected bus zone. By comparing phase be approximately in phase.
currents in near real time, a comparison Comparing the phase angles of the
can be made between currents that are currents at every sample point of time
entering the bus and those currents that allows the slope characteristic algorithm
are leaving the bus. If little CT saturation to be supervised by the delta phase
occurs, for an internal bus fault phase function. This technique works because
angle currents will be nearly in phase current phasors that are heavily saturated
while for an external fault, one or more have DC offset or are otherwise distorted
phase angles of the currents will be near in magnitude will still retain their correct
180 degrees from the other currents. phase angle relationships. This
This is intuitively true as well since information can then be used to provide
Kirchoff’s law also applies to phase correct operation of the overall
angles as well as to current magnitudes. differential protection by supervising the
The phase angle comparison is used in slope characteristic. The phase angle
conjunction with a slope characteristic difference for discrimination of fault/no
The key challenge in the delta phase fault conditions is fixed at 90 degrees, so
technique is to rapidly measure phase if all current phasors are within less than
angle between all current phase angles. 90 degrees from each other, slope
In the technique utilized, the DOT tripping is allowed. If the measured
PRODUCT is calculated between input current phasors are within an angle
phase currents. If A and B are vectors, greater than 90 degrees, this is
the DOT product of A*B = AB Cos recognized as an external fault and
theta where A and B are scalars and tripping is blocked. If only one current
theta is the angle between the vectors. input is present, tripping will be
The DOT product of vectors A and B permitted if the slope characteristic
where A= a1 + j a2 operates. The delta phase logic is shown
in Figure 3 & 4 showing three inputs
And B= b1 + j b2 from elements connected to the
A * B = a1 b1 + a2 b2 ----Eq. 1 protected bus zone.
The calculation of the current phase
The calculation of A*B using Eq.1 has angles is done for every time that the
the advantage in that the Cosine function current vectors are measured. Relays
does not need to be used. typically sample waveforms from 32 to
Implementation of a trig function is a 96 samples per cycle and current vectors
laborious process when done by a for protection purposes are typically
microprocessor, whereas multiplication calculated every 2 ms or so.
and summation is easy to do with small
resource requirement.
The delta phase algorithm looks at the
phase angles of each of the similar phase
currents to determine their phase
relationships. If a fault is external to the
protected zone for instance, the phase
angles will be approximately equal and

3
Current Vectors For No Fault product is negative, the coincidence
In Protected Zone angle is greater than 90 degrees.
I1 It should be noted that if the
protected zone has only one source
Angle > 90 degrees connected to it, a phase comparison
cannot be made. At least two current
vectors are required to make a phase
I2 angle decision. If only one current
I3 vector is available, the phase angle
Phase angles between currents
control defaults to a trip condition. In
Greater than 90 degrees, delta those cases, the slope characteristic
Phase BLOCKS differential trip.
is the only logic that is used. Also, if
Figure 3 input currents are too low to be
measured accurately, these vector
Current Vectors For Fault In currents are not used. The
Protected Zone measurement of phase angle can
typically be done down to 0.05 A for
Angle < 90 degrees a 1 A nominal input relay, or .25 A
for a 5 A relay.

IHV Overall Transformer Differential


Performance
ITV I LV
Phase angles between currents
Less than 90 degrees, delta The phase comparison Dot product
Phase ALLOWS differential trip. function operates to supervise the
operation of the slope characteristic.
Figure 4 In many ways, the setting of the
slope characteristic function
It can be seen from Figures 3 & 4 becomes less critical because of delta
that the phase angles of the input phase supervision. The Iomin setting
currents of the elements connected to determines the amount of unbalance
the protected bus are either about or fault current that can be present in
180 degrees apart or approximately the transformer zone before the slope
in phase . In the Dot product characteristic tries to trip. The delta
technique, the current vectors are phase supervision will then allow or
measured to determine if vectors are block the trip based on current angle
within 90 degrees of each other . If measurement. Setting the slope
all input vectors are within 90 characteristic to avoid tripping for
degrees of each other, it is an current measurement errors can be a
indication of an internal fault. The timely and laborious task. This is
Dot product of two vectors is ZERO. because CT performance and
So in the calculation of phase angle application parameters need to be
the actual phase angle does not need known to provide these studies. With
to be measured. If the Dot product is phase supervision, phase angles are
greater than zero, angle coincidence largely preserved even if CT saturate
is less than 90 degrees. If the Dot or if DC offset quantities occur.

4
In applying any differential It can be seen from this example, that the
protection, it is important to phase angles of the three input A phase
determine that wiring connections currents are 180 degrees from each other
and connection settings are made with currents 2 and 3 in phase and these
correctly. This can be done during 180 degrees out of phase with current 1.
the commissioning by viewing the
metering screen on the relay Internal B Phase Fault
metering screens. If current
magnitude errors are present in the
initial installation, the slope Input 1
characteristic will operate and can B Phase
annunciate a high MISMATCH
indication to draw attention to the
fact that something is amiss. Input 2
Tripping will largely be prevented B Phase
even in this condition if no actual
fault on the protected zone is present.

Examples Of Protected Bus Zone Input 3


B Phase
Operations

For An External Fault

Figure 6
A ph
Input 1 Figure 6 displays an internal B phase bus
fault . It can be seen that even though
Input 1 has a DC offset amount, the
phase angles of the input currents come
A ph close to coinciding.
Input 2
Application To Device 87N

The previous Figures showed how phase


current phase angles can be compared to
A ph determine if faults are within a protected
Input 3 zone or whether they are external faults.
The same phase angle comparison can
be done on zero sequence currents as
well. For this case Kirchoff’s rule
equally applies to 3Io currents over a
protected zone. Current transformers can
Figure 5 ebe used to summate the phase currents
to generate 3Io , just as these same CTs

5
can be used to measure the individual 4. Use of the Dot phase angle
phase currents. comparison can compliment the
slope characteristic in that it can
Observations Of The Use Of The Dot provide a zone checking function to
Product For Bus Protection prevent false relay trips that might
Enhancement otherwise take place because of
wiring or application errors.
The Dot product phase angle comparison
of current inputs for a bus has been
verified through hundreds of tests using
the RTDS simulator. In fact, the phase
angle comparator has shown to be
equally effective when used with
differential protection for other
applications such as transformer
protection as well.
The use of the phase angle comparison
along with the slope detection method in
combination has proven to be a very
stable combination especially for
external faults where severe input
current saturation or DC offsets can
occur.

Benefits Of The Dot Product Phase


Angle Comparison

1. The addition of phase angle


comparison to a differential function
provides excellent security for all
external faults where current
quantities into the differential relay
could be corrupted due to DC
offsets, CT saturation or other CT
errors.
2. The addition of the Dot angle
comparison simplifies differential
relay application as the stability of
the CT phase angles makes possible
fault discrimination and lessens the
emphasis put on the slope
characteristic requirements.
3. Use of the rapid Dot product
computation allows for phase angle
measurement without time to
operate speed penalties.

Вам также может понравиться